Galaxy VM
apc.com/products
From 160 kVA to 1000 kVA
Three-phase power protection
Highly efficient, easy-to-deploy, three-phase power protection that seamlessly
integrates into the electrical, physical, and monitoring environments of customers’
medium data centers, industrial, or facilities applications.
•	 Very high efficiency with multimode energy management including ECOnversionTM
technology even at very low load levels
•	 Robust mechanical design with fully isolated input/output cabinet
•	 Flexible battery solutions
•	 Seven-inch, color touch-screen display with a separate mimic diagram
Features and benefits
The GalaxyTM
VM is a key component of the fully integrated and comprehensive Schneider ElectricTM
energy
management solution for data centers and industrial applications. Deploying the latest in technology,
it lowers energy costs through high efficiency and an ECOnversion mode. State-of-the-art electrical
performance options, such as wide input voltage range, high overload and short-circuit capacities, and
integrated backfeed protection, allow the Galaxy VM to seamlessly integrate into your electrical network to
provide excellent power quality. Highly compact, the Galaxy VM also integrates well with facility monitoring
systems requirements, offering energy storage flexibility that tailors the solution to your specific needs. It
features top and bottom cable entry, full front service access, back-to-the-wall installation, and includes
start-up services, making the Galaxy VM one of the easiest UPS units in its class to deploy, install,
and maintain.
Galaxy VM — trusted partner
for your business continuity
apc.com/products2
Integration
•	 Schneider Electric StruxureWareTM
software applications and suites
•	 Electrical network earthing systems
•	 Facilities infrastructure
•	 Seismic certified
•	 Monitoring systems — BMS, modbus, etc.
Energy and cost savings
•	 ECOnversion mode
•	 High-efficiency double conversion mode
•	 ECO mode
Energy storage flexibility
•	 Traditional (VRLA) and modular battery offer
•	 Common battery available in standard
•	 Short and long backup times
•	 Selectable charging modes
Ease of installation
•	 System designed for ease of cabling
in confined installation spaces
•	 Single cabinet top and bottom cable entry
•	 Integrated casters for ease of mobility
on UPS and modular battery cabinets
IT integrates
to protect
your world.
IT increases
your energy storage
flexibility.
IT makes your
decisions easy.
IT lowers your
energy costs
through high
efficiency.
Galaxy VM 
Galaxy VM features
IT integrates to protect your world.
apc.com/products 3
AC bypass
Distributed parallel connection for increased power and redundancy
AC normal AC normal
Load
AC normal AC normal AC normal
IT integrates
to protect
your world.
IT increases
your energy storage
flexibility.
IT makes your
decisions easy.
IT lowers your
energy costs
through high
efficiency.
Integration into your facility infrastructure
•	 Compact footprint
•	 Back-to-the-wall installation
•	 Operates at 40 o
C continuously without de-rating
•	 Embedded seismic certified to OSHPD, IBC2012
and CBC2013 to Sds=2.02 g
•	 Low audible noise levels
•	 Replaceable dust filter for harsh environments
•	 Configurable input/output relays
•	 Top and bottom cable entry
•	 Parallel capability to increase multiple UPS
systems for capacity or redundancy
•	 Ability to add UPSs in a parallel configuration
without the need to transfer the load to bypass
•	 Cold start: capability to start the UPS on battery
without mains power present
•	 External synchronization capability
Integration into your electrical network
•	 Wide input voltage and frequency ranges
•	 Genset compliant with adaptive ramp-in
•	 Integrated parallel capability up to five UPS units
•	 Built-in integrated and tested backfeed protection
Full integration with Schneider Electric solutions
Fully integrates into the comprehensive Schneider
Electric energy management solution for data
centers and industrial applications
Smart power test
Ability to test the UPS at full load without the need
to rent a load bank and before bringing customers’
load online
Galaxy VM features
IT lowers your energy costs through high efficiency.
apc.com/products4
IT lowers your
energy costs
through high
efficiency.
IT integrates
to protect
your world.
IT increases
your energy storage
flexibility.
IT makes your
decisions easy.
At 100% load Alternate UPS Alternate UPS Alternate UPS
Efficiency 95% 94% 93%
Savings by using
Galaxy VM/year
(in ECOnversion mode)
€23,700 €29,625 €35,550
Ten-year savings
by using Galaxy VM
(in ECOnversion mode)
€237,000 €296,250 €355,500
High-efficiency operating modes
Considering a total UPS load of 720 kW (4 x 200 kVA running
at 100 percent load).
At the national average rate of €0.07/kWh, a 720 kW Galaxy VM
installation running in ECOnversion mode (99% efficiency) can
save €296,250 for 10 years compared to a 720 kW UPS with
94 percent efficiency.*
In the same scenario, a Galaxy VM operating in double
conversion mode ( 96.5% efficiency) has cost savings equal
to €130,350 over five years compared to a 720 kW UPS with
94 percent efficiency.
Cost savings by using Galaxy VM
Very high efficiency for small to medium data centers, buildings, and facilities
*Figures calculated using APCTM
by Schneider Electric UPS
efficiency comparison calculator are estimates. Individual savings
could vary.
+ +
=
=
=
=
~ ~AC in
Bypass Switch
Battery
Load
PFC Recfifier Inverter
DC/DC
1000.1 1 10
NominalValue(Voltage%)
100%
80%
60%
40%
20%
0%
-20%
-40%
-60%
-80%
-100%
1,000
Overvoltage transient limit
Undervoltage transient limit
+10%
-10%
Galaxy VM ECOnversion meets Class 1 of IEC 62040-3:
zero break transfer during power outage
ECOnversion
ECOnversion mode
Enables control of input current to almost
same quality as known from on-line UPS
Transient duration in milliseconds (ms)
•	 Compliant with IEC 62040-3 Class 1
output voltage of UPS standard
•	 Input power factor correction
and no harmonics
ECOnversion mode
•	 Ultrahigh efficiency up to 99%
•	 Keeps excellent load protection
•	 Continuously charged batteries
Double conversion mode
•	 Up to 96.5% efficiency in double
conversion online mode even
at low load levels
•	 Less energy losses = cost savings
•	 Less heat dissipation = lower cooling
needed, hence cost savings
ECO mode
•	 Up to 99.5% efficiency
•	 Compliant with IEC 62040-3 Class 3
output definition of UPS standard
apc.com/products 5
Galaxy VM features
IT increases your energy storage flexibility.
IT increases
your energy storage
flexibility.
IT integrates
to protect
your world.
IT makes your
decisions easy.
IT lowers your
energy costs
through high
efficiency.
•	 Traditional (VRLA) battery offer:
–– Choice of multiple runtime options
and battery cabinet configurations
–– Each cabinet has only one battery string
with its own DC breaker and slide-out
shelves that are designed for ease of use
•	 Modular battery offer:
–– Ease of scaling in smaller increments
provides customizable backup time
or redundancy
–– Advanced string monitoring of current
and voltage impedance allows for predictive
information of the batteries
–– Battery replacement without the need to go
to bypass keeps the load protected
•	 Matching wall-mounted battery breaker box
and battery breaker kits as well as empty battery
cabinets are available
•	 Parallel UPS configurations can be connected
to a common battery without the need for
a battery coupling cabinet, reducing footprint
and increasing cost savings
•	 Flywheel and lithium ion compatibility
Energy storage options
Modular battery cabinets
Advanced individual battery
string monitoring for both
current and voltage
Wall-mounted battery
breaker box
Classical battery cabinet: seismic IBC level 2 with battery
disconnect at string level
apc.com/products6
Galaxy VM features
IT makes your decisions easy.
IT makes your
decisions easy.
IT integrates
to protect
your world.
IT increases
your energy storage
flexibility.
IT lowers your
energy costs
through high
efficiency.
From ordering to installation, the
Galaxy VM makes your solution
choice easy.
Start-up
•	 5 x 8 start-up services are included,
allowing for full coverage of factory warranty
•	 Remote monitoring service included
for first year
Installation
•	 Casters allow UPS configurations to be moved
easily and installed up against the wall
•	 Separate I/O cabinet for input and output
cabling ensures quick, error-free, and
easy installation
•	 Top and bottom cable entry standard provides
great flexibility to the installer
Monitoring
•	 7-inch, color touch-screen display
•	 Integrated network management capability
for easy access to the network
•	 Integrated battery monitoring capability
included for modular battery offer
•	 Modbus (SCADA and ION-E) capability
•	 Customizable dry contacts and relays
LCD display
Power cabinet I/O cabinet
UPS
SKU/part number Description Protocol supported
Included with
Galaxy VM
•	1 plug: Ethernet SNMP
(similar to AP9630)
•	1 plug: RS485 modbus RTU
•	6 configurable dry contacts IN
•	10 configurable dry contacts OUT
•	2 free slots for optional
communication cards
•	HTTP, HTTPS, IPv4, IPv6, NTP,
SMTP, SNMP v1, SNMP v3, SSH
V1, SSH V2, SSL, TCP/IP, Telnet,
and modbus RTU
•	Optional com cards : AP9635CH,
AP9631, AP9630
AP9635CH
UPS network management card 2 w/
environmental monitoring up to 1 sensor,
out-of-band access, and modbus capabilities
HTTP, HTTPS, IPv4, IPv6, NTP,
SMTP, SNMP v1, SNMP v3, SSH
V1, SSH V2, SSL, TCP/IP, Telnet,
modbus RTU, modbus TCP/IP
AP9631
Remote monitoring and control of an individual
UPS by connecting it directly to the network —
card also has environmental monitoring for up
to 2 sensors
HTTP, HTTPS, IPv4, IPv6, NTP,
SMTP, SNMP v1, SNMP v2c,
SNMP v3, SSH V1, SSH V2, SSL,
TCP/IP, Telnet
AP9630
Remote monitoring and control of an
individual UPS by connecting it directly to
the network
HTTP, HTTPS, IPv4, IPv6, NTP,
SMTP, SNMP v1, SNMP v3, SSH V1,
SSH V2, SSL, TCP/IP, Telnet
Galaxy VM management card compatibility chart
apc.com/products 7
A comprehensive portfolio of services
Schneider Electric Critical Power  Cooling Services provides the expertise,
services, and support you need for your building, industry, power, or data
center infrastructure. Our world-class life cycle services offer a smart way
to install and maintain your critical applications, ensuring your systems
are always running at peak performance.
Assembly and start-up service by a certified Field Service Engineer (FSE)
allows full factory warranty coverage. A Schneider Electric-certified installation
makes certain your equipment is properly configured for optimal performance.
This service features a standard eight-hour, five-day response time, with
upgrades available for off-business hours.
On-site warranty extension service
In the case of a system event, an FSE will arrive by the next business day
(or faster with upgrades) to isolate, diagnose, and correct in as little time
as possible, minimizing downtime.
Advantage plans
Flexible service packages offer smooth system maintenance to improve
uptime at a predictable cost. The Advantage Plus, Prime, Ultra, and Max are
full-service packages that include technical support, preventive maintenance,
quick on-site response, and remote monitoring. Response time upgrades
are available.
Remote monitoring service (RMS)
RMS is an economical and easy-to-use Web-based service that lets you
quickly respond to environmental or system changes. Trained technicians
provide secure 24-hour monitoring of your physical infrastructure to diagnose
and resolve events before they become critical.
Preventive maintenance
Preventive maintenance on-site examinations keep your critical systems
running at maximum efficiency.
StruxureWare for Data Centers software suite
In the data center environment, Galaxy VM is fully managed through
StruxureWare for Data Centers software, an integrated suite of data center
infrastructure management applications. It enables businesses to prosper
by managing their data centers across multiple domains, providing actionable
intelligence for an ideal balance of high availability and peak efficiency
throughout the entire data center life cycle. StruxureWare software applications
and suites are key elements of Schneider Electric EcoStruxureTM
integrated
hardware and software system architecture — a system designed for intelligent
energy management.
Rated power ( kVA/kW ) 160/144 200/180 320/288 400/360 480/432 600/540 640/576 800/720 1000/900
Normal AC supply input
Input voltage (V) 250 – 600 V
Normal and bypass AC inputs Single input or dual input as standard
Frequency (Hz) 40 – 70 Hz
Input power factor 0.99
THDI  3% full load
Bypass AC input
Input voltage range 342 – 457 V
Frequency 50 Hz or 60 Hz
Output
Phase-to-phase output voltage (V) 380/400/415 V
Load power factor 0.9 (0.7 leading to 0.5 lagging without de-rating)
Output frequency 50/60 Hz +/- 0.1% (free-running)
Overload capacity utility operation at 40 °C 150% for 1 minute and 125% for 10 minutes
Output voltage regulation +/- 1%
Total harmonic distortion (THDU)  2% at 100% linear load;  3% at 100% nonlinear load
Output voltage tolerance Symmetric load (0 – 100%): +/- 1% static; asymmetric load: +/- 3% static
Overall efficiency
ECOnversion mode (meets EN62040-3 Class 1) Up to 99% (meets EN62040-3 Class 1)
Efficiency at full load (AC-AC) at 100% load Up to 96.5%
Standard ECO mode Up to 99%
Communication and management
Control panel
Multifunction 7 touch-screen color LCD display with built-in NMC,
modbus (SCADA and ION-E), two empty NMC card slots
Dimensions and weights
UPS (H x W x D) mm 1970 x 1052 x 854 1970 x 2104 x 854 1970 x 3156 x 854 1970 x 4208 x 854 1970 x 5260 x 854
Weight in kg. (UPS) (total -power cabinet plus I/O
cabinet)
699 724 1398 1448 2097 2172 2796 2896 3620
Regulatory
Safety IEC 62040-1
EMC/EMI/RFI IEC 62040-2
Markings CE,C-Tick
Performance IEC 62040-3, VFI -SS -111
Transportation ISTA 2B
Seismic zone IBC Level 2:2006
Environmental
Operating temperature 0 °C – 40 °C2
Storage temperature
-25 °C to 55 °C — without batteries
-15 °C to 40 °C — with batteries
Relative humidity 0% – 95% non-condensing
Operating elevation 1,000 m. at 100% load
Storage elevation 0 – 15,000 m
Max. audible noise at 1 m from unit 55 dB at 70% load, 65 dB at 100% load
Schneider Electric
132 Fairgrounds Road
West Kingston, RI 02892
USA
email: esupport@apc.com
www.schneider-electric.com
June 2016
©2016 Schneider Electric. All Rights Reserved. Schneider Electric | Life Is On, ECOnversion, Galaxy, StruxureWare,
APC, and EcoStruxure are trademarks and the property of Schneider Electric SE, its subsidiaries, and affiliated
companies. All other trademarks are the property of their respective owners. • 998-1203811_50hz_IEC_B

More Related Content

What's hot

Presentation gamatronic
Presentation gamatronicPresentation gamatronic
Presentation gamatronichoanv
 
Eaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_CEaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_CEhab Saleh
 
Power Adapter Design for 400 V DC Power Distribution in Electronic Systems
Power Adapter Design for 400 V DC Power Distribution in Electronic SystemsPower Adapter Design for 400 V DC Power Distribution in Electronic Systems
Power Adapter Design for 400 V DC Power Distribution in Electronic SystemsVicor Corporation
 
Uninterruptible power supply (ups)
Uninterruptible power supply (ups)Uninterruptible power supply (ups)
Uninterruptible power supply (ups)Corporate Services
 
Online UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter SupplierOnline UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter Suppliersuman bala
 
Uninterruptible Power Supply (UPS)
Uninterruptible Power Supply (UPS)Uninterruptible Power Supply (UPS)
Uninterruptible Power Supply (UPS)Panduit
 
Meeting DC-DC Power System Requirements in Defense Applications Webinar
Meeting DC-DC Power System Requirements in Defense Applications WebinarMeeting DC-DC Power System Requirements in Defense Applications Webinar
Meeting DC-DC Power System Requirements in Defense Applications WebinarVicor Corporation
 
Power components for battery applications webinar presentation
Power components for battery applications   webinar presentationPower components for battery applications   webinar presentation
Power components for battery applications webinar presentationVicor Corporation
 
Short-Circuit Current Ratings and AC Drives
Short-Circuit Current Ratings and AC DrivesShort-Circuit Current Ratings and AC Drives
Short-Circuit Current Ratings and AC DrivesSchneider Electric
 
Case Study - Reliance Industries_Mumbai - 20100329
Case Study - Reliance Industries_Mumbai - 20100329Case Study - Reliance Industries_Mumbai - 20100329
Case Study - Reliance Industries_Mumbai - 20100329Chris Dow
 
Servo Drive Solution for Yarn Winding Machine
Servo Drive Solution for Yarn Winding MachineServo Drive Solution for Yarn Winding Machine
Servo Drive Solution for Yarn Winding MachineElmo Motion Control
 
Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.
Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.
Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.Long Trump
 

What's hot (19)

Gamatronics Solutions for Data Centers
Gamatronics Solutions for Data CentersGamatronics Solutions for Data Centers
Gamatronics Solutions for Data Centers
 
Presentation gamatronic
Presentation gamatronicPresentation gamatronic
Presentation gamatronic
 
Eaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_CEaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_C
 
Corporate Profile of Silicon Technologies, Karachi, Pakistan 2017
Corporate Profile of Silicon Technologies, Karachi, Pakistan 2017Corporate Profile of Silicon Technologies, Karachi, Pakistan 2017
Corporate Profile of Silicon Technologies, Karachi, Pakistan 2017
 
Smart ups brochure
Smart ups brochureSmart ups brochure
Smart ups brochure
 
Delta ia pq-all_c_en_20160307
Delta ia pq-all_c_en_20160307Delta ia pq-all_c_en_20160307
Delta ia pq-all_c_en_20160307
 
All
AllAll
All
 
How to choose a ups
How to choose a upsHow to choose a ups
How to choose a ups
 
Power Adapter Design for 400 V DC Power Distribution in Electronic Systems
Power Adapter Design for 400 V DC Power Distribution in Electronic SystemsPower Adapter Design for 400 V DC Power Distribution in Electronic Systems
Power Adapter Design for 400 V DC Power Distribution in Electronic Systems
 
Uninterruptible power supply (ups)
Uninterruptible power supply (ups)Uninterruptible power supply (ups)
Uninterruptible power supply (ups)
 
Online UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter SupplierOnline UPS,Battery, Solar Inverter Supplier
Online UPS,Battery, Solar Inverter Supplier
 
XANT
XANTXANT
XANT
 
Uninterruptible Power Supply (UPS)
Uninterruptible Power Supply (UPS)Uninterruptible Power Supply (UPS)
Uninterruptible Power Supply (UPS)
 
Meeting DC-DC Power System Requirements in Defense Applications Webinar
Meeting DC-DC Power System Requirements in Defense Applications WebinarMeeting DC-DC Power System Requirements in Defense Applications Webinar
Meeting DC-DC Power System Requirements in Defense Applications Webinar
 
Power components for battery applications webinar presentation
Power components for battery applications   webinar presentationPower components for battery applications   webinar presentation
Power components for battery applications webinar presentation
 
Short-Circuit Current Ratings and AC Drives
Short-Circuit Current Ratings and AC DrivesShort-Circuit Current Ratings and AC Drives
Short-Circuit Current Ratings and AC Drives
 
Case Study - Reliance Industries_Mumbai - 20100329
Case Study - Reliance Industries_Mumbai - 20100329Case Study - Reliance Industries_Mumbai - 20100329
Case Study - Reliance Industries_Mumbai - 20100329
 
Servo Drive Solution for Yarn Winding Machine
Servo Drive Solution for Yarn Winding MachineServo Drive Solution for Yarn Winding Machine
Servo Drive Solution for Yarn Winding Machine
 
Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.
Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.
Biến tần yaskawa d1000 - Biến tần hiệu suất cao và tiết kiệm năng lượng.
 

Similar to Galaxy VM UPS Efficiency & Flexibility

998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdf
998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdf998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdf
998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdfJesusEnriqueAnaya1
 
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmElektrumlv
 
CP02IPTT01_C_[T&D_Presentation].pdf
CP02IPTT01_C_[T&D_Presentation].pdfCP02IPTT01_C_[T&D_Presentation].pdf
CP02IPTT01_C_[T&D_Presentation].pdfHUYNGUYN930004
 
schneider-electric-storage.pptx
schneider-electric-storage.pptxschneider-electric-storage.pptx
schneider-electric-storage.pptxPoooi2
 
Off grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solarOff grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solarelsolsolar
 
Efore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supply
Efore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supplyEfore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supply
Efore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supplyEFORE Group
 
16120788_PG_Energypack40ft_brochure.pdf
16120788_PG_Energypack40ft_brochure.pdf16120788_PG_Energypack40ft_brochure.pdf
16120788_PG_Energypack40ft_brochure.pdfMichaelSchreck11
 
Riello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheetRiello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheetRobin Koffler MBA CDCEP
 
AlphaESS company presentation
AlphaESS company presentationAlphaESS company presentation
AlphaESS company presentationAlphaESS
 
ComNet C1PS Data Sheet
ComNet C1PS Data SheetComNet C1PS Data Sheet
ComNet C1PS Data SheetJMAC Supply
 
ComNet C1PS Data Sheet
ComNet C1PS Data SheetComNet C1PS Data Sheet
ComNet C1PS Data SheetJMAC Supply
 
6dec2011 - Power Back-up_1
6dec2011 - Power Back-up_16dec2011 - Power Back-up_1
6dec2011 - Power Back-up_1Agora Group
 
RF Battery Solar PPT
RF Battery Solar PPTRF Battery Solar PPT
RF Battery Solar PPTGeof Moser
 

Similar to Galaxy VM UPS Efficiency & Flexibility (20)

998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdf
998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdf998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdf
998-21963451_GalaxyVS208-480V_GMA_brochure_final.pdf
 
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
 
CP02IPTT01_C_[T&D_Presentation].pdf
CP02IPTT01_C_[T&D_Presentation].pdfCP02IPTT01_C_[T&D_Presentation].pdf
CP02IPTT01_C_[T&D_Presentation].pdf
 
schneider-electric-storage.pptx
schneider-electric-storage.pptxschneider-electric-storage.pptx
schneider-electric-storage.pptx
 
Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
  Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK  Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
 
Off grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solarOff grid rooftop pv – elsol solar
Off grid rooftop pv – elsol solar
 
Efore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supply
Efore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supplyEfore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supply
Efore DC backup SYSTEM, Master Portfolio 2016, uninterruptible power supply
 
16120788_PG_Energypack40ft_brochure.pdf
16120788_PG_Energypack40ft_brochure.pdf16120788_PG_Energypack40ft_brochure.pdf
16120788_PG_Energypack40ft_brochure.pdf
 
NetSure-502-Brochure
NetSure-502-BrochureNetSure-502-Brochure
NetSure-502-Brochure
 
Riello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheetRiello multi-power-modular-ups-datasheet
Riello multi-power-modular-ups-datasheet
 
Ecopowersupplies: Riello-Multi-Sentry-UPS
Ecopowersupplies: Riello-Multi-Sentry-UPSEcopowersupplies: Riello-Multi-Sentry-UPS
Ecopowersupplies: Riello-Multi-Sentry-UPS
 
Ecopowersupplies: Riello Sentinel Dual High Power UPS
Ecopowersupplies: Riello Sentinel Dual High Power UPSEcopowersupplies: Riello Sentinel Dual High Power UPS
Ecopowersupplies: Riello Sentinel Dual High Power UPS
 
AlphaESS company presentation
AlphaESS company presentationAlphaESS company presentation
AlphaESS company presentation
 
ComNet C1PS Data Sheet
ComNet C1PS Data SheetComNet C1PS Data Sheet
ComNet C1PS Data Sheet
 
ComNet C1PS Data Sheet
ComNet C1PS Data SheetComNet C1PS Data Sheet
ComNet C1PS Data Sheet
 
Flyer 4 page
Flyer 4 pageFlyer 4 page
Flyer 4 page
 
Products & services (new)
Products & services (new)Products & services (new)
Products & services (new)
 
6dec2011 - Power Back-up_1
6dec2011 - Power Back-up_16dec2011 - Power Back-up_1
6dec2011 - Power Back-up_1
 
Busduct
BusductBusduct
Busduct
 
RF Battery Solar PPT
RF Battery Solar PPTRF Battery Solar PPT
RF Battery Solar PPT
 

Recently uploaded

Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsMark Billinghurst
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfSeasiaInfotech2
 
CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):comworks
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Mattias Andersson
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesZilliz
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Wonjun Hwang
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr BaganFwdays
 
Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Enterprise Knowledge
 
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationBeyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationSafe Software
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024Lorenzo Miniero
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenHervé Boutemy
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupFlorian Wilhelm
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Patryk Bandurski
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxhariprasad279825
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsSergiu Bodiu
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationRidwan Fadjar
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr LapshynFwdays
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024BookNet Canada
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLScyllaDB
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piececharlottematthew16
 

Recently uploaded (20)

Human Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR SystemsHuman Factors of XR: Using Human Factors to Design XR Systems
Human Factors of XR: Using Human Factors to Design XR Systems
 
The Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdfThe Future of Software Development - Devin AI Innovative Approach.pdf
The Future of Software Development - Devin AI Innovative Approach.pdf
 
CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):CloudStudio User manual (basic edition):
CloudStudio User manual (basic edition):
 
Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?Are Multi-Cloud and Serverless Good or Bad?
Are Multi-Cloud and Serverless Good or Bad?
 
Vector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector DatabasesVector Databases 101 - An introduction to the world of Vector Databases
Vector Databases 101 - An introduction to the world of Vector Databases
 
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
Bun (KitWorks Team Study 노별마루 발표 2024.4.22)
 
"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan"ML in Production",Oleksandr Bagan
"ML in Production",Oleksandr Bagan
 
Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024Designing IA for AI - Information Architecture Conference 2024
Designing IA for AI - Information Architecture Conference 2024
 
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry InnovationBeyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
Beyond Boundaries: Leveraging No-Code Solutions for Industry Innovation
 
SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024SIP trunking in Janus @ Kamailio World 2024
SIP trunking in Janus @ Kamailio World 2024
 
DevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache MavenDevoxxFR 2024 Reproducible Builds with Apache Maven
DevoxxFR 2024 Reproducible Builds with Apache Maven
 
Streamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project SetupStreamlining Python Development: A Guide to a Modern Project Setup
Streamlining Python Development: A Guide to a Modern Project Setup
 
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
Integration and Automation in Practice: CI/CD in Mule Integration and Automat...
 
Artificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptxArtificial intelligence in cctv survelliance.pptx
Artificial intelligence in cctv survelliance.pptx
 
DevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platformsDevEX - reference for building teams, processes, and platforms
DevEX - reference for building teams, processes, and platforms
 
My Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 PresentationMy Hashitalk Indonesia April 2024 Presentation
My Hashitalk Indonesia April 2024 Presentation
 
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
"Federated learning: out of reach no matter how close",Oleksandr Lapshyn
 
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
New from BookNet Canada for 2024: BNC CataList - Tech Forum 2024
 
Developer Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQLDeveloper Data Modeling Mistakes: From Postgres to NoSQL
Developer Data Modeling Mistakes: From Postgres to NoSQL
 
Story boards and shot lists for my a level piece
Story boards and shot lists for my a level pieceStory boards and shot lists for my a level piece
Story boards and shot lists for my a level piece
 

Galaxy VM UPS Efficiency & Flexibility

  • 1. Galaxy VM apc.com/products From 160 kVA to 1000 kVA Three-phase power protection
  • 2. Highly efficient, easy-to-deploy, three-phase power protection that seamlessly integrates into the electrical, physical, and monitoring environments of customers’ medium data centers, industrial, or facilities applications. • Very high efficiency with multimode energy management including ECOnversionTM technology even at very low load levels • Robust mechanical design with fully isolated input/output cabinet • Flexible battery solutions • Seven-inch, color touch-screen display with a separate mimic diagram Features and benefits The GalaxyTM VM is a key component of the fully integrated and comprehensive Schneider ElectricTM energy management solution for data centers and industrial applications. Deploying the latest in technology, it lowers energy costs through high efficiency and an ECOnversion mode. State-of-the-art electrical performance options, such as wide input voltage range, high overload and short-circuit capacities, and integrated backfeed protection, allow the Galaxy VM to seamlessly integrate into your electrical network to provide excellent power quality. Highly compact, the Galaxy VM also integrates well with facility monitoring systems requirements, offering energy storage flexibility that tailors the solution to your specific needs. It features top and bottom cable entry, full front service access, back-to-the-wall installation, and includes start-up services, making the Galaxy VM one of the easiest UPS units in its class to deploy, install, and maintain. Galaxy VM — trusted partner for your business continuity apc.com/products2 Integration • Schneider Electric StruxureWareTM software applications and suites • Electrical network earthing systems • Facilities infrastructure • Seismic certified • Monitoring systems — BMS, modbus, etc. Energy and cost savings • ECOnversion mode • High-efficiency double conversion mode • ECO mode Energy storage flexibility • Traditional (VRLA) and modular battery offer • Common battery available in standard • Short and long backup times • Selectable charging modes Ease of installation • System designed for ease of cabling in confined installation spaces • Single cabinet top and bottom cable entry • Integrated casters for ease of mobility on UPS and modular battery cabinets IT integrates to protect your world. IT increases your energy storage flexibility. IT makes your decisions easy. IT lowers your energy costs through high efficiency. Galaxy VM 
  • 3. Galaxy VM features IT integrates to protect your world. apc.com/products 3 AC bypass Distributed parallel connection for increased power and redundancy AC normal AC normal Load AC normal AC normal AC normal IT integrates to protect your world. IT increases your energy storage flexibility. IT makes your decisions easy. IT lowers your energy costs through high efficiency. Integration into your facility infrastructure • Compact footprint • Back-to-the-wall installation • Operates at 40 o C continuously without de-rating • Embedded seismic certified to OSHPD, IBC2012 and CBC2013 to Sds=2.02 g • Low audible noise levels • Replaceable dust filter for harsh environments • Configurable input/output relays • Top and bottom cable entry • Parallel capability to increase multiple UPS systems for capacity or redundancy • Ability to add UPSs in a parallel configuration without the need to transfer the load to bypass • Cold start: capability to start the UPS on battery without mains power present • External synchronization capability Integration into your electrical network • Wide input voltage and frequency ranges • Genset compliant with adaptive ramp-in • Integrated parallel capability up to five UPS units • Built-in integrated and tested backfeed protection Full integration with Schneider Electric solutions Fully integrates into the comprehensive Schneider Electric energy management solution for data centers and industrial applications Smart power test Ability to test the UPS at full load without the need to rent a load bank and before bringing customers’ load online
  • 4. Galaxy VM features IT lowers your energy costs through high efficiency. apc.com/products4 IT lowers your energy costs through high efficiency. IT integrates to protect your world. IT increases your energy storage flexibility. IT makes your decisions easy. At 100% load Alternate UPS Alternate UPS Alternate UPS Efficiency 95% 94% 93% Savings by using Galaxy VM/year (in ECOnversion mode) €23,700 €29,625 €35,550 Ten-year savings by using Galaxy VM (in ECOnversion mode) €237,000 €296,250 €355,500 High-efficiency operating modes Considering a total UPS load of 720 kW (4 x 200 kVA running at 100 percent load). At the national average rate of €0.07/kWh, a 720 kW Galaxy VM installation running in ECOnversion mode (99% efficiency) can save €296,250 for 10 years compared to a 720 kW UPS with 94 percent efficiency.* In the same scenario, a Galaxy VM operating in double conversion mode ( 96.5% efficiency) has cost savings equal to €130,350 over five years compared to a 720 kW UPS with 94 percent efficiency. Cost savings by using Galaxy VM Very high efficiency for small to medium data centers, buildings, and facilities *Figures calculated using APCTM by Schneider Electric UPS efficiency comparison calculator are estimates. Individual savings could vary. + + = = = = ~ ~AC in Bypass Switch Battery Load PFC Recfifier Inverter DC/DC 1000.1 1 10 NominalValue(Voltage%) 100% 80% 60% 40% 20% 0% -20% -40% -60% -80% -100% 1,000 Overvoltage transient limit Undervoltage transient limit +10% -10% Galaxy VM ECOnversion meets Class 1 of IEC 62040-3: zero break transfer during power outage ECOnversion ECOnversion mode Enables control of input current to almost same quality as known from on-line UPS Transient duration in milliseconds (ms) • Compliant with IEC 62040-3 Class 1 output voltage of UPS standard • Input power factor correction and no harmonics ECOnversion mode • Ultrahigh efficiency up to 99% • Keeps excellent load protection • Continuously charged batteries Double conversion mode • Up to 96.5% efficiency in double conversion online mode even at low load levels • Less energy losses = cost savings • Less heat dissipation = lower cooling needed, hence cost savings ECO mode • Up to 99.5% efficiency • Compliant with IEC 62040-3 Class 3 output definition of UPS standard
  • 5. apc.com/products 5 Galaxy VM features IT increases your energy storage flexibility. IT increases your energy storage flexibility. IT integrates to protect your world. IT makes your decisions easy. IT lowers your energy costs through high efficiency. • Traditional (VRLA) battery offer: –– Choice of multiple runtime options and battery cabinet configurations –– Each cabinet has only one battery string with its own DC breaker and slide-out shelves that are designed for ease of use • Modular battery offer: –– Ease of scaling in smaller increments provides customizable backup time or redundancy –– Advanced string monitoring of current and voltage impedance allows for predictive information of the batteries –– Battery replacement without the need to go to bypass keeps the load protected • Matching wall-mounted battery breaker box and battery breaker kits as well as empty battery cabinets are available • Parallel UPS configurations can be connected to a common battery without the need for a battery coupling cabinet, reducing footprint and increasing cost savings • Flywheel and lithium ion compatibility Energy storage options Modular battery cabinets Advanced individual battery string monitoring for both current and voltage Wall-mounted battery breaker box Classical battery cabinet: seismic IBC level 2 with battery disconnect at string level
  • 6. apc.com/products6 Galaxy VM features IT makes your decisions easy. IT makes your decisions easy. IT integrates to protect your world. IT increases your energy storage flexibility. IT lowers your energy costs through high efficiency. From ordering to installation, the Galaxy VM makes your solution choice easy. Start-up • 5 x 8 start-up services are included, allowing for full coverage of factory warranty • Remote monitoring service included for first year Installation • Casters allow UPS configurations to be moved easily and installed up against the wall • Separate I/O cabinet for input and output cabling ensures quick, error-free, and easy installation • Top and bottom cable entry standard provides great flexibility to the installer Monitoring • 7-inch, color touch-screen display • Integrated network management capability for easy access to the network • Integrated battery monitoring capability included for modular battery offer • Modbus (SCADA and ION-E) capability • Customizable dry contacts and relays LCD display Power cabinet I/O cabinet UPS SKU/part number Description Protocol supported Included with Galaxy VM • 1 plug: Ethernet SNMP (similar to AP9630) • 1 plug: RS485 modbus RTU • 6 configurable dry contacts IN • 10 configurable dry contacts OUT • 2 free slots for optional communication cards • HTTP, HTTPS, IPv4, IPv6, NTP, SMTP, SNMP v1, SNMP v3, SSH V1, SSH V2, SSL, TCP/IP, Telnet, and modbus RTU • Optional com cards : AP9635CH, AP9631, AP9630 AP9635CH UPS network management card 2 w/ environmental monitoring up to 1 sensor, out-of-band access, and modbus capabilities HTTP, HTTPS, IPv4, IPv6, NTP, SMTP, SNMP v1, SNMP v3, SSH V1, SSH V2, SSL, TCP/IP, Telnet, modbus RTU, modbus TCP/IP AP9631 Remote monitoring and control of an individual UPS by connecting it directly to the network — card also has environmental monitoring for up to 2 sensors HTTP, HTTPS, IPv4, IPv6, NTP, SMTP, SNMP v1, SNMP v2c, SNMP v3, SSH V1, SSH V2, SSL, TCP/IP, Telnet AP9630 Remote monitoring and control of an individual UPS by connecting it directly to the network HTTP, HTTPS, IPv4, IPv6, NTP, SMTP, SNMP v1, SNMP v3, SSH V1, SSH V2, SSL, TCP/IP, Telnet Galaxy VM management card compatibility chart
  • 7. apc.com/products 7 A comprehensive portfolio of services Schneider Electric Critical Power Cooling Services provides the expertise, services, and support you need for your building, industry, power, or data center infrastructure. Our world-class life cycle services offer a smart way to install and maintain your critical applications, ensuring your systems are always running at peak performance. Assembly and start-up service by a certified Field Service Engineer (FSE) allows full factory warranty coverage. A Schneider Electric-certified installation makes certain your equipment is properly configured for optimal performance. This service features a standard eight-hour, five-day response time, with upgrades available for off-business hours. On-site warranty extension service In the case of a system event, an FSE will arrive by the next business day (or faster with upgrades) to isolate, diagnose, and correct in as little time as possible, minimizing downtime. Advantage plans Flexible service packages offer smooth system maintenance to improve uptime at a predictable cost. The Advantage Plus, Prime, Ultra, and Max are full-service packages that include technical support, preventive maintenance, quick on-site response, and remote monitoring. Response time upgrades are available. Remote monitoring service (RMS) RMS is an economical and easy-to-use Web-based service that lets you quickly respond to environmental or system changes. Trained technicians provide secure 24-hour monitoring of your physical infrastructure to diagnose and resolve events before they become critical. Preventive maintenance Preventive maintenance on-site examinations keep your critical systems running at maximum efficiency. StruxureWare for Data Centers software suite In the data center environment, Galaxy VM is fully managed through StruxureWare for Data Centers software, an integrated suite of data center infrastructure management applications. It enables businesses to prosper by managing their data centers across multiple domains, providing actionable intelligence for an ideal balance of high availability and peak efficiency throughout the entire data center life cycle. StruxureWare software applications and suites are key elements of Schneider Electric EcoStruxureTM integrated hardware and software system architecture — a system designed for intelligent energy management.
  • 8. Rated power ( kVA/kW ) 160/144 200/180 320/288 400/360 480/432 600/540 640/576 800/720 1000/900 Normal AC supply input Input voltage (V) 250 – 600 V Normal and bypass AC inputs Single input or dual input as standard Frequency (Hz) 40 – 70 Hz Input power factor 0.99 THDI 3% full load Bypass AC input Input voltage range 342 – 457 V Frequency 50 Hz or 60 Hz Output Phase-to-phase output voltage (V) 380/400/415 V Load power factor 0.9 (0.7 leading to 0.5 lagging without de-rating) Output frequency 50/60 Hz +/- 0.1% (free-running) Overload capacity utility operation at 40 °C 150% for 1 minute and 125% for 10 minutes Output voltage regulation +/- 1% Total harmonic distortion (THDU) 2% at 100% linear load; 3% at 100% nonlinear load Output voltage tolerance Symmetric load (0 – 100%): +/- 1% static; asymmetric load: +/- 3% static Overall efficiency ECOnversion mode (meets EN62040-3 Class 1) Up to 99% (meets EN62040-3 Class 1) Efficiency at full load (AC-AC) at 100% load Up to 96.5% Standard ECO mode Up to 99% Communication and management Control panel Multifunction 7 touch-screen color LCD display with built-in NMC, modbus (SCADA and ION-E), two empty NMC card slots Dimensions and weights UPS (H x W x D) mm 1970 x 1052 x 854 1970 x 2104 x 854 1970 x 3156 x 854 1970 x 4208 x 854 1970 x 5260 x 854 Weight in kg. (UPS) (total -power cabinet plus I/O cabinet) 699 724 1398 1448 2097 2172 2796 2896 3620 Regulatory Safety IEC 62040-1 EMC/EMI/RFI IEC 62040-2 Markings CE,C-Tick Performance IEC 62040-3, VFI -SS -111 Transportation ISTA 2B Seismic zone IBC Level 2:2006 Environmental Operating temperature 0 °C – 40 °C2 Storage temperature -25 °C to 55 °C — without batteries -15 °C to 40 °C — with batteries Relative humidity 0% – 95% non-condensing Operating elevation 1,000 m. at 100% load Storage elevation 0 – 15,000 m Max. audible noise at 1 m from unit 55 dB at 70% load, 65 dB at 100% load Schneider Electric 132 Fairgrounds Road West Kingston, RI 02892 USA email: esupport@apc.com www.schneider-electric.com June 2016 ©2016 Schneider Electric. All Rights Reserved. Schneider Electric | Life Is On, ECOnversion, Galaxy, StruxureWare, APC, and EcoStruxure are trademarks and the property of Schneider Electric SE, its subsidiaries, and affiliated companies. All other trademarks are the property of their respective owners. • 998-1203811_50hz_IEC_B