FIRE PROTECTION FACILITIES
FOR
PETROLEUM DEPOTS, TERMINALS, PIPELINE INSTALLATIONS
AND
LUBE OIL INSTALLATIONS
CONTENTS
SECTION
10
20
30
3 1
3.2
33
40
41
42
43
44
45
46
47
50
5 1
52
60
61
62
70
80
81
8.2
8.3
84
85
86
8.7
90
ANNEXURE
1
2.
3
4.
5
DESCRIPTION
Introduction
Scope
Definitions
Petroleum Depots, Terminals & a,l Installations
Classification of Petroleum Products
Flash POint
Fire Protection Facilities
GeneralConslderatlon
Design Criteria of Fire Protection System
Fire Water System
Foam System
Clean Agent Fire Protection System
First Aid Fire Fighting Equipment
Mobile Fire Fighting Equipment
Fire Alarm/Communication System
Communication System
Fire Alarm System
Fire Safety OrganlZatlonlTralning
Organization
Training
Fire Emergency Manual
Fire Protection System, Inspection & Testing
Fire Water Pumps
Fire Water Ring Main
Fire Water Spray System
Fixed/ Semi Fixed Foam System
Clean Agent Fire Pro:ectlon System
Hoses
Communication System
Reference
Sample Calculation of Fire Water Flow Rate for Storage Tanks
Sample Calculation of Fire Water Flow Rate for POL Tank Wagon
Loading Gantry
Brief Description of Fire Fighting Foams.
Typical Example for Calculation of Foam Compound ReqUIrement Large
Floating Roof Tank After Sinking of Roof.
TYPical System of Automatic Actuated Foam Flooding System for Rim
Seal of Larger Floatlr.g Roof Tanks.
FIRE PROTECTION FACILITIES
FOR
PETROLEUM DEPOTS, TERMINALS AND PIPELINE/LUBE OIL INSTALLATIONS
1.0 INTRODUCTION
The petroleum depots, terminals &
plpeline/lube 011 Installations are
generally located In the remote
areas and near railway sidings
However, the experience shows that
with the passage of time, these get
surrounded by resldential/lndustnal
installations The Inventory of
flammable materials stored therein
necessitates Inbullt fire protection
facilities
covered In 0ISD-STD-144, also-
STO-150 or 0ISO-STO-169 as the
case may be
illl Drilling rigs, Work over rigs and
Production Installations (GGSiOCS,
GCPIGCS, EPS, QPSIWHI etc)
which are covered In OISO-STD-
189
IV) Port all Terminals for which also-
$TO-156 shall be referred
v) Control Room Building & Electncal
Installations shall be prOVidedas per
0ISO-$TO-163 & 173 respectively,
It can be Impractical and
prohibitively costly to deSign fire
protection facilities to control
catastrophiC fires The usual
requirement of a good system IS to
prevent emergencies from
developing into major threat to the
oil Installation and surroundings
2.0 SCOPE
21 This standard tays down the
minimum requirement of fire
protection facilities at Petroleum
Depots, Terminals, Pipeline
Installations With or Without
Storages, Central Tank Farms
(CTF) Lube a,l Installations,
Grease Manufactunng & Filling
FaCllilies
2 2 ThiS standard does not cover the fire
protection faCilities for ,-
23
3.0
It IS not intended that the prOVISions
as speCified in this reVised standard
should be applied ngldly to eXisting
premises. However, these
proviSions shall be reviewed
considenng various hazards for
Implementalion where for a variety
of reasons, it may not be practicable
to comply with ThiS standard shall
be applicable in selective
Implementation of the
recommendations at such locations
for which a SUitable structured
approach should be adopted to carry
out the review at site consldenng
various hazards. However, the
additional reqUirements shall be
applicable to all new locations
conceived after publication of the
new edition.
DEFINITIONS
A portion of the property, where
combustible/flammable liqUids are
received by tanker, pipelines, tank
wagons, tank trucks and are stored
or blended in bulk for the purpose of
distribution by tankers, pipelines,
I) Depots, Terminals/lnstallalions In
Refineries and/or a,l/Gas
Processing Plants under the same
management and In ctose proximity
for which 0ISO-STO-116 shall be
referred
II) Instaltatlons handling liquefied
Petroleum Gas (LPG) Storage,
Handling and Bottling The same are
3.1 PETROLEUM
TERMINAS
DEPOTS &
likely to be refined, blended or
stored at above its flash pOint.
For classlflcation and e~tent of
hazardous area, refer 'The
Petroleum Rules - 2002".
tank wagons, tank trucks, portable
tanks or containers
3.1.1 PIPELINE INSTAllATIONS
Pipeline Installations are those
facilities on cross-country pipelines
which have pumping and/or delivery
station with or without storages
3,2 CLASSIFICATION
PETROLEUM PRODUCTS
OF
General Classification
Excluded Petroleum means
petroleum having a flash point
above 23'C and above.
Petroleum Class B means
petroleum having a flash pOint of
n'c and above but below 6S'('
Petroleum Class C means
petroleum having a flash point of
6S'C and above but below 93'(,
A means
flash point
Petroleum Class
petroleum having a
below 23'(,
Petroleum means any liqUid
hydrocarbon Or ml~ture of
hydrocarbons and any Inflammable
ml~ture (liquid, viscous or solid)
containing any liquid hydrocarbon.
Petroleum products other than LPG
which IS a separate category, are
classified according to their closed
cup Flash Poinl as follows
3.2.1
3.2.2
The facilities meant for receipt,
storage and blending of base oils &
additives Into finished Lube
products. It Includes lube-blending
plants, grease manufactUring plants
& small can filling plants
These are the facilities such as
Control Room Building, Sub-Slatlon,
Diesel Generator (with diesel
storage tank). & Administrative
Building, etc. provided in Petroleum
Depots, Terminals and Pipeline
Installations
The facilities where ATF is received
by tank wagons, tank trucks &
pipeline and stored In bulk for
dispatch of product by refuellers &
pipeline It include also storage of
Methanol/AVGAS & other addilives
in drums.
3.1.2 lUBE Oil INSTAllATIONS
3.1.3 AVIATION FUllEING STATIONS
3.1.4 INFRASTRUCTUREIOTHER
FACILITIES
Flash Point of any petroleum
means the lowest temperature at
which it Yields a vapor which will give
a momentary flash when Ignited
The locations where product is
handled by artificially heating it to
above it's flash pOint, Class C
product shall be considered as
3.1.5 HARZARDOUS AREA
An area will be deemed to be
hazardous where-
Petroleum haVing flash pOint below
65'C or any flammable gas or vapor
in a concentration capable of ignition
ISlikely to be present
Petroleum or any flammable liqUid
haVing flash point above 65'C IS
3.2.3 Classification for
Petroleum Products
Heated
4.1 GENERAL CONSIDERATIONS
4.1.1 layout
3.3
4.0
Class B product and Class B
product as Class A product
GENERAL TERMINOLOGY
Clean agent electrically non·
conductive, volatile or gaseous fire
extingulshants that does not leave a
reSidue upon evaporation and meets
the reqUirements given In the latest
NFPA 2001 on clean agent fire
extinguishing systems in line With
environmental consideration of
Kyoto Protocol
Shall Indicate that provIsion IS
mandatory
Should Indicate that provision IS
recommendatory as per good
engineering practices
May indicate that provision IS
optional
FIRE PROTECTION FACILITIES
The fire protection philosophy IS
based on loss prevention & control
It considers that a depot/terminal,
carries an Inherent potential hazard
due to flammable nature of
petroleum products stored therein. A
fire In one facility can endanger
other facility of the depot/terminal. If
not controlled/extinguished as
qUickly as possible to minimize the
loss of life & property and prevent
further spread of fire
The Size of product storage &
handling faCilities. their localion and
terrain determine the baSIC fire
protection reqUirements.
layout of a depot or terminal.
pipeline Installation. lube 011
Installation. grease manufacturing &
filling faCilities and handlingldisposal
system of blow down, drain from
eqUipment handling flammable
liqUids shall be done in accordance
With 0ISO·STO·118 & OISO·STD.
109 as applicable
SpeCial consideration should be
given In the plant layout & product
line layout for heated products lines
laid alongside the pipeline carrying
lighter petroleum products.
4.1.2 FIRE PROTECTION
Depending on the nature of risk.
follOWing fire protection facilities
shall be provided in the Installation
• Fire Water System.
• Foam System
• Clean Agent Protection System
• First Aid Fire Fighting
Equipment
• Mobile Fire Fighting Equipment.
• Fire Detection, Alarm &
Communication System.
4.2 DESIGN CRITERIA FOR FIRE
PROTECTION SYSTEM
4.2.1 Facilrlles shall be designed on the
baSISthat city fire water supply is not
available close to the Installation.
4.2.2 One Single largest risk shall be
considered for providing faCilities
4.2.3 The hazardous areas shall be
protected by a well laid combination
of hydrants & monitors. The
follOWing installations are exempted
from this provision'-
I) The Installation haVing aggregate
above ground storage capacity of
less than 1000 KL (ClassA+B+C)
other than AFS.
Ii) Pipeline installation having only
scrapper stations or sectlonallzlng
valve stations.
4,2,4 Tank Wagon (TW)lTank Truck (TT)
loading/unloading facilities, Manifold
area of product pump house &
Exchange pit shall be fully covered
with a well laid out combination of
hydrants and water-cum-foam
monitors.
4,2,5 The Installations storing Class A
petroleum In above ground tanks
shall have fixed water spray system
However, Installations above 1000
KL storage fulfilling the following
both conditions are exempted from
the provIsion of fixed water spray
system -
• Aggregate above ground
storage of Class A & 8
petroleum up to 5000 KL
• Floating roof tank storing Class
A petroleum haVing diameter up
to 9 rn
4,2,6 Class '8' above ground Petroleum
storage tanks of diameter larger
than 30 m shall be provided with
fixed water spray system
4,2,7 When Class A & B above ground
storage tanks are placed In a
common dyke, the fixed water
spray system shall be provided on
all tanks except for small terminals
as mentioned In 4.2.6
4,2,8 TW loading gantries shall be
provided with manually operated
fixed water spray system. In case
automatic fixed water spray system
IS provided, the gantry may be
divided Into sUitable number of
segments (each segment haVing
min. length of 15 m length & width of
12 m) and three segments operating
at a time shall be considered as
Single risk for calculating the water
reqUIrement.
Accordingly, a provision shall be
made to actuate the water spray
system from a safe approachable
central location i.e affected zone
and adjoining zones
4,2,9 The fixed water spray system shall
also be provided on all tanks
irrespective of diameter where Inter
distances between tanks In a dyke
and/or within dykes are not meeting
the reqUIrements of 0ISD-STO-118
4,2,10 Fixed foam system or Semi-fixed
foam system with foam trolley/s
shall be provided on tanks (floating
roof or fixed roof) exceeding 18 m
diameter storing Class A or Class 8
petroleum.
4-2,11 Portable foam and/or water-cum-
foam mOnitors shall be provided for
suppression of pool fire In tank farm
area
4,2,12 Automatic actuated rim seal fire
extinguishing system may be
provided based on foam or clean
agent flooding mechanism on
floating roof tanks having diameter
larger than 60 m
ThiS is in addition to the fixed water
spray system and Fixed foam
system or Semi-fixed foam system
on all floating roof tanks storing
Class A & 8 petroleum.
Foam Flooding System Selection
and deSign of foam based flooding
system should be as defined in
latest "Standard for Foam Systems -
NFPA-11A".
Clean Agent Flooding System
Selection and deSign of clean agent
based flooding system should be in
line with the "Standard on Clean
Agent Fire Extinguishing Systems -
NFPA 2001 (latest Edition).
The clean agent should also comply
with the reqUirements of "Ozone
Depletion Substances Regulation &
Control Rules - 2000, Ministry of
Forests,
4.2.13
EnVifonment &
Government of India
The listed clean agents like
Triflurolodide & F/uroketone can be
used as fire suppressant for floating
roof rim seal fire protection and In
control room/computer room/
pressunzed room fire protection
respectively
The clean agent based protection
system consists of an in-built fire
detection. control and actuation
mechanism If a rrm seal fire occurs.
its heat causes one or more spray
nozzles to open and the
extinguishing gas (clean agent) IS
applied on the surface of fire and
Simultaneous alarm ISalso sounded
Refer (Annexure-V) for a typical
system of automatic nm seal frre
protection uSing ctean agent
The follOWing additional
requirements shall be apphcable to
the installations located In lightening
prone areas & where inter distances
between tanks In a tank dyke andlor
Withintank dykes are not conforming
to the proVISionsof 0ISo-STo-118
• Double seal of appropnate
matenal for all sizes of floating
roof tanks storrng Class A
petroleum .
• Automatic actuated nm seal fire
protection system based on
foam or clean agent for tanks
haVing diameter more than 60 m
and storrng Class A petroleum.
4.2.16 Clean Agent (Halon substitute)
based flooding system may be
considered for control rooms.
computer rooms and pressurized
rooms In major locations having
automated pipeline receipt/dispatch
andlor TW/TT loading faCilities.
Selection of clean agent and design
of fire protection system for control
rooms, computer rooms and
pressunzed rooms should follow the
Standard on "Clean Agent
Extinguishing systems NFPA
Standard 2001 (Edition 2004)
Including its safety guidelines With
respect to "Hazards to Personnel".
electrrcal clearance and
envrronmental factors In hne With
enVifonmental conSiderations of
Kyoto Protocol Clean agent like
Inert gas, Fluroketone can be used
as fire suppressant In control rooms,
computer rooms and pressunzed
rooms
4.3 FIRE WATER SYSTEM
Water IS used for fire
extinguishments, fire control, coohng
of equipment exposure protection of
equipment and personnel from heat
radiation.
The fire water ring main shall be
provided all around perrmeter of the
installation With hydrants/monitors
spaced at Intervals not exceeding 30
m when measured aerially.
4.2,14 As an additional requirement,
fixed foam system or semi-fixed
foam system With foam trolleyls
shall also be prOVided on all tanks
irrespective of diameter where Inter
distances between tanks In a tank
dyke andlor Within tank dykes are
not meeting the requirements of
0ISo-STo-118.
4.2.15 Water spray system shall be
provided on TW loading gantry
4.3.1 Components of Fire Water
System
The main components of the system
are Fire Water Storage, Fire Water
Pumps and Distribution Piping
Network.
4.3.2 Basis
The frre water system In an
Installation shall be deSigned to
4.3.2.1 Design Flow Rate
meet the fire water flow reqUirement
to fight single largest nsk at a time.
I) Fire water flow rate for a tank farm
shall be aggregate of the follOWing
•
•
•
Water flow calculated for cooling a
tank on fife at a rate of 3 Ipm/m' of
tank shell area
Water flow calculated for exposure
protection for all other tanks failing
within a radius of (R +30)m from
centre of the tank on fife (R-Radlus
of tank on fife) and situated in the
same dyke at a rate of 3 Ipm/m' of
tank shell area
Water flow calculated for exposure
protection for all other tanks failing
outSide a radius of (R+30)m from
centre of the tank on fife and
situated In the same dyke at a rate
of 1 Ipm/m' of tank shell area
shall be at a rate of 10.2 Ipm/m' In
case the penpheral distance
between any two of the above
facilities ISless than 15 m, It shall be
conSidered as single nsk for the
calculation of fire water requirement
ill) Fife water flow rate for TW loadjng
gantry (Refer Annexure - II) and
product pump house in a depot or
terminal shall be calculated at a rate
of@ 102 Ipm/m2
However, If pump house of volatile
productls IS located under pipe rack
fife water flow rate shall be
calculated at a rate of 20.4 Ipm/m2
IV) Fife water flow rate for
supplementary streams shall be
based on using 4 Single hydrant
outlets and 1 monitor
simultaneously Capacity of each
hydrant outlet as 36 m3/hr and of
each monitor as 144 m3/hr
minimum may be conSidered at a
pressure of 7 kg/cm2g.
• For water flow calculations, all tanks
farms h~vlng class A or B petroleum
storage shall be conSidered
irrespective of diameter of tanks and
whether fixed water spray system is
provided or not
The deSign fife water rate shall be
the largest of [4321 (I)J, [4.3.2.1
(l1)J, [4.32.1 (IIi)], or [43.2.1 (Iv)].
(Refer Annexure-I)
4.3.3 Header Pressure
• Waler flow required for applYing
loam on a Single largest tank by way
of fixed foam system, where
provided, or by use of water/foam
momtors (Refer section 448 for
foam solution application rates)
Fife water system shall be designed
for a minimum reSIdual pressure of
7 kg/cm2(g) at hydraulically
remotest pOint In the installation
consldenng single largest nsk
scenario.
• Various combinations shall be
considered in Ihe tank larm lor
arnvlng at different fire water flow
rate and the largest rate to be
considered for deSign
II) Fife water flow rate for pump house
shed, scrapper area, metenng area,
flltenng area & manifold area at
CraSs country pipeline Installations
4.3.4 Storage
Water for the fire fighting shall be
stored in any eaSily accessible
surface or underground or above
ground tanks of steel, concrete or
masonry.
The effective capacity of the
reservolf/tank above the level of
suction pOint shall be minimUm 4
hours aggregate rated capacity of
pumps However. where reliable
make up water supply is 50% or
more of design flow rate. the storage
capacity may be reduced to 3 hours
aggregate rated capacity of pumps
Fresh water should be used for fire
fighting purposes. /n case sea water
or treated effluent water IS used for
fire fighting purposes. the material of
the pipe selected shall be sUitable
for the service
The installation shall have facilities
for receiving and diverting all the
water coming to the installation to
fife water storage tanks in case of
an emergency
Storage reservoir shall be In two
equal Interconnected compartments
to faCilitate cleaning and repairs. In
case of steel tanks there shall be
minimum two tanks each having 50
% of required capacity.
Large natural reservolfs haVing
water capacity exceeding 10 times
the aggregate water requirement of
fire pumps may be left unlined
4.3.5 Fire Water Pumps
(I) Fire water pumps haVing flooded
suction shall be installed to meet the
deSign fire water flow rate and head
/f fire water is stored in underground
tanks. an overhead water tank of
sufficient capacity shall be provided
for flooded suction and accounting
for leakages in the network. If any
(ii) The pumps shall be capable of
discharging 150% of its rated
discharge at a minimum of 65% of
the rated head. The Shut-off head
shall not exceed 120% of rated head
for hOrizontal centrifugal pumps and
140% for vertical turbine pump
(Iii) At/east one standby fire water pump
shall be provided up to 2 nos. of
main pumps. For main pumps 3 nos.
and above, minimum 2 nos. standby
pumps of the same type, capacity &
head as the main pumps shall be
provided.
(IV) The fire water pump(s) including the
standby pump(s) shall be of diesel
engine driven type Where electric
supply IS reliable 50% of the pumps
may be €Iectric driven. The diesel
engines shall be qUick starting type
with the help of push buttons located
on or near the pumps or located at a
remote location Each engine shall
have an Independent fuel tank
adequately Sized for 6 hours
continuous running of the pump
(vi Fife water pumps & storage shall
be located at 30 m (minimum)
away from equipment or where
hydrocarbons are handled or
stored
(Vi) Fire water pumps shall be
exclusively used for fire fighting
purpose only
(VII) Suction and discharge valves of fire
water pumps shall be kept full
open all the times.
(Viii) The fire water network shall be kept
pressurized by static water tank or
Jockey pump( s)
(ix) In case jockey pump is used for
pressurrzation. a standby jockey
pump of similar type. capacity &
head shall be prOVided
4.3.6 Fire Water Network
(i) Looping
The fire water network shall be laid
in closed loops as far as possible to
ensure multi-directional flow in the
system. Isolation valves shall be
provided in the network to enable
Isolation of any section of the
network without affecting the flow In
the rest. The Isolation valves shall
be located normally near the loop
Junctions. Additional valves shall be
provided In the segments where the
length of the segment exceeds 300
m.
(ii) Above I Underground Network
The fire water ring mains shall be
laid above ground at least at a
height of 300 mm above finished
ground level
• For rail crossIng. proVIsions
stipulated by Indian Railways shall
be compiled,
• The ufg ring main shall be
protected against SOilcorrosion by
suitable coalingfwrapPlng or
cathodiC protection wherever
cathodiC proteclion already exists
for protection of other pipelines
system
• Pipe supports under the pipe line
shall be SUitable for soli
conditions.
jii) Support & Protection of above
ground pipelines
However, the ring main may be laid
underground at the following places
If fire water ring mains are laid
underground, the following shall be
ensured -
• Road crossings
• Places where above ground piping
IS likely to cause obstruction to
operalion and vehicle movement
• Places where above ground piping
IS likely to get damaged
mechanically
• Where frost conditions warrant and
ambient temperature IS likely to fall
subzero, under ground piping shall
be laid at least 1 m below the
finished grade level to avoid freeZing
of water Alternatively, water
circulation may be carried out In the
above ground pipelines or any other
sUitable means.
ii) Protection
pipeline
of underground
The mains shall be supported at
regular Intervals not exceeding 6
en. For pipeline size less than 150
NB, support Interval shall not
exceed 3 m
The pipe support shall have only
pOintcontact.
The system for above ground
portion shall be analyzed for
fleXibility against thermal
expansion and necessary
expansion loops, guidesfcross
gUides and supports prOVided.
(iv) Sizing of pipeline
Fire water ring main shall be sized
for 120% of the design water flow
rate Design flow rates shall be
distributed at nodal pOints to give
the most realistiC way of water
reqUirements In an emergency It
may be necessary to assume
several combinations of flow
requirement for deSign of network
• The ring main shall have at least 1
m earth cushion in open ground, 15
m cushion under the road crossings
and in case of crane movement area
pipeline may be protected with
concretefsteel encasement as per
deSign requirement
In case of sea water service, the
fire water main pipes shall be
concrete mortar lined internally or
other SUitable coating matenal
shall be used
The stand post for hydrants and
monitors shall be Sized to meet
the respective deSign water flow
rates
Iv) General
Conneclions for fixed water monitors
on the network shall be provided
with independent Isolation valves
Fire water mains shall not pass
through bUildings or dyke areas
In case of underground mains the
isolation valves shall be located In
RCC/bnck masonry chamber of
sUitable size to facilitate operation
dunng emergency & maintenance
4.3.7 Hydrants & Monitors
I) Hydrants shall be located bearing In
mind the fire hazards at different
sections of the premises to be
prolected and to give most effective
service At least one hydrant post
shall be provided for every 30 m of
external wall measurement or
penmeter of battery limit In case of
high hazard areas For non-
hazardous area. they shall be
spaced al 45 m Intervals The
honzontal range & coverage of
hydrants with hose conneclions shall
not be considered beyond 45 m
II) Hydrants shall be located at a
minimum distance of 15 m from the
penphery of storage tank or
eqUipment under protection. In case
of buildings this dlslance shall not be
less than 2 m and not more than 15
m from the face of bUilding
ProvIsion of hydrants within the
building shall be provided In
accordance with J S . 3844
Ill) HydrantiMonltors shall be located
along road Side berms for easy
acceSSibility
IV) Double headed hydrants with two
separate landing valves or momtor
on SUitablysized stand post shall be
used. All hydrant outlets/monitor
Isolalion valves shall be situated at
workable height above ground or
hydrantlmomtor operating platform
level.
v) Monitors shall be located to direct
water on the object as well as to
provide water shield to firemen
approaching a fire.
The requirement of monitors shall
be established based on hazards
Involved and layout considerations.
Monitors shall not be Installed within
15 m of hazardous equipment
The location of the monitors shall
not exceed 45 m from the hazard to
be protected
High volume long range monitors.
shall be located more than 45 m
from the hazardous equipment &
their water header/s sized
accordingly to meet the rated water
flow rate of monitor as well as
deSign water flow reqUifement of
Single largest nsk scenano
vi) Hydrants and monitors shall not be
Installed InSide the dyke areas
However, as an additional
requirement, oscillating monitors
may be provided in inaccessible
area within dyke with isolalion valve
or ROV outside the tank farm.
vii) TWITT loading & unloading facilities
shall be provided with alternate
hydrant and water-cum-foam
monitors having multipurpose
combination nozzles for Jet spray &
fog arrangement and fire hydrants
located at a spacing of 30 m on both
Sides of the gantry The hydrants &
monitors shall be located at a
mln,mum distance of 15 m from the
hazard (eg TW & TT
loading/unloading facilities) to be
protected
VII') Hydrants/Monitors
preferably located
connection
shall
with
be
branch
VII Hose boxes, water monitors and
hydrant outlets shall be painted WIth
"LuminOUSYellow" paint as per IS5
4.3.8 Material Specifications
The matenals used In fire water
system shall be of approved type as
Indicated below
i) Pipes
Carbon Steel as per
tS3589/IS1239/IS 1978 or It'S
equivalent for fresh water service.
A sUitable proven matenal
conforming to design. heat radiation
& It's associated hazards. operation
& maintenance requirements shall
be used for saline/brackish waler
service
vii) Corrosion resistant paint shall be
used In corrosion prone areas
4.3.9 FIXED WATER SPRAY SYSTEM
i) Fixed water spray system is a fixed
pipe system connected to a reliable
source of water supply and
eqUipped With water spray nozzles
for speCific water discharge and
dlstributton over the surface of area
to be protected The piping system
,s connected to the hydrant system
water supply through an
automatically or manually actuated
valve which initiates the flow of
water
IV) Monitors
As per IS/Ul or EqUivalent
Standard
II) Isolation Valves
Gate or butterfly type isolatton valves
made of Cast Steel haVing
open/close Indication shall be used
Other matenals such as cupro-
nickel for saline/brackish waler may
be used
III) Hydrants
Stand post
Outlet valves
Carbon Steel
Gunmetal/
Alumlnum/
Stainless/
Steel/AI-Zn Alloy
In case the system IS manually
actuated, the Isolation valve shall be
located outSIde the dyke for easy of
access & operation
II) Spray nozzles shall be directed
radially to the tank at a distance not
exceeding 06 m from the tank
surface Only one type and size of
spray nozzle shall be used in a
particular facility
ill) While calculating the water rates for
spray applicalton for cases other
than tanks/vessels, the area should
be diVided Into suitable segments so
that maximum water requirement
can be opt,mlZed (Refer Annexure-
V for typical calculations)
v) Fire Hoses
Reinforced Rubber lined Hose as
per IS 636 (Type A)/Non-percolattng
SynthetiC Hose (Type B)/Ul or
Equivalent Standard
(VI) Fire water mainS, hydrant & monitor
sland posts, nsers of water spray
system shall be painted With "Fire
Red" paint as per of IS5
4.4 FOAM SYSTEMS
4.4.1 Types of Foam
Foams are claSSified by producing
action of generatton and expansion
Foam concentrate to be used shall
conform to IS4989 (part-III)
2006/Ul-162 or Equivalent
Standard. Refer (Annexure - III) for
bilef deScilptlon of foam
4.4.2 Types of Low Expansion Foam
For combating large hydrocarbon
fifes particularly In a contained area
tlke storage tank, foam has proved
useful for Its Inherent blanketing
ability, heat resistance and secuilty
against burn-back Aqueous FIlm
Forming Foam (AFFF) compound IS
technically supenor and compatible
wllh other fife f/ghttng agents
EffICient and effectIve foam delIvery
system IS a vital tool for ItS
usefulness In coniroiling the fife.
The process of adding or tnJecttng
the foam concentrate to water IS
called proportioning The mixture of
water and foam compound (foam
solution) IS then mixed wIth alf In a
foam maker for onward transmIsSion
to burntng surface
4.4.3 CONVEYING SYSTEMS
The system conSists of an adequate
water supply, supply of foam
concentrate, SUitable proportioning
equipment. a proper piping system,
foam makers and dIscharge deVices
deSigned to adequately distribute the
foam over the hazard.
ConventIonal systems are of the
open outlet type tn which foam
dIscharges from all outlets at the
same lIme, covenng the entlfe
hazard within the confines of the
system There are three types of
systems
i) Fixed
Ii) Semi-Fixed
ill) Mobile
(i) Fixed Foam System
Fixed foam conveying system
compnses of fixed piping for water
supply at adequate pressure, foam
concentrate tank, eductor, suitable
proportIoning equipment for draWing
foam concentrate and making foam
solutIon, fIxed piping system for
onward conveYing to foam makers
for making foam, vapor seal box and
foam pourer
(ii) Semi-Fixed Foam System
Semi-fixed foam system gets supply
of foam solution through the mobIle
foam tender. A fixed piping system
connected to foam makers cum
vapor seal box in case of cone roof
tanks and foam maker and foam
pourers In the case of floattng roof
tanks conveys foam to the surface
of tank.
(iii) Mobile System
Mobile system Includes foam
producing unit mounted on wheels
whIch may be self propelled or
towed by a vehicle These units
supply foam through momtors/foam
towers to the burning surface.
(Iv) Sub-surface foam injection
ThISsystem ISfor proteclton of fixed
roof ~torage tanks It compnses of
high back pressure foam generator
connected through product lines or
separate lines near the bottom of
the tank.
(v) Under the Seal Foam application
ThiS is a system for floattng roof tank
where the foam Iravels through a
flexible pIpe inSide the tank upto the
center of the tank roof and eXits at
the seal rim of the floating roof
precisely where the fire IS located
thus rapidly flooding the seal rim area
and qUickly extinguishing the fire
spaced at the periphery of the tank
and each discharge outlet shall be
sized to deliver foam at
approximately the same rate.
4.4.5 FIXED ROOF TANK PROTECTION
IV) A mlmmum of two foam pourers
shall be prOVided
I) System be deSigned to create foam
blanket on the burning surface In a
reasonably short period
Il) Foam shall be applied to the burning
hazard continuously at a rate high
enough to overcome the destructive
effects of radiant heat
Foam Pourer
(Mln Nos)
2
3
4
5
6
8
10
Tank diameter
(In M)
Above 18 & up to 20
Above 20 & up to 25
Above 25 & up to 30
Above 30 & up to 35
Above 35 & up to 40
Above 40 & up to 45
Above 45 & IJPto 50
The estimation of number of foam
discharge outlet IS based on pourer
capacity of 1000 Ipm at a pressure
of 7 kg/cm2
(g) upstream of eductor.
This can be suitably adjusted for
different pourer capacity in
accordance with section 4.44 (ill).
In case foam pourers are to be
provided on tanks haVing diameter
up to 18 m, min 2 nos foam
pourers shall be provided.
III) Tanks should be provided with foam
discharge outlets/pourers as
indicated below
TANK
For floating roof lank, foam shall be
poured at the foam dam to blanket
the roof seal Features of foam
system for floating roof tank
protection shall be as follows-
III) Foam makers/foam pourers shall be
located not more than 24 m apart
on the shell perimeter based on 600
mm foam dam height
4.4.4 FLOATING ROOF
PROTECTION
Foam conveYing system shall have
same features as of floating roof
tank excepting that a vapor seal
chamber IS reqUired before the foam
discharge outlet
4.4.6 FLOATING CUM FIXED ROOF
TANK PROTECTION
Protection facilities shall be prOVided
as reqUired for fixed roof tank.
Features of the foam system for
fixed roof protection shall be as
follows
4.4.7 PROTECTION FOR DYKE
AREA/SPILL FIRE
FOAM APPLICATION RATE
I) The vapor seal chamber shall be
prOVided wllh an effective and
durable seal. fragile under low
pressure, to prevent entrance of
vapour Into the foam conveying
piping system
4.4.8
Portable
streams
fighting
spills.
momtors/foam hose
shall be considered for
fires In' dyked area and
ii) Where two or more pourers are
reqUired these shall be equally
The minimum delivery rate for
primary protection based on the
assumption that all the foam
4.4.11 FOAM QUANTITY REQUIREMENT
reaches the area being protected
shall be as Indicated below
For cone roof tanks containing liquid
hydrocarbons, the foam solullon
delivery rate shall be at least 5
Ipmlm2 of liqUid surface area of the
tank to be protected
For floating roof tanks containing
liqUid hydrocarbons foam solution
delivery rate shall be at least 12
Ipm/m2 of seal area With foam dam
height of 600 mm of the tank to be
protected
In case of floating roof Sinking, the
rate conSidered should be 8 1
Ipm/m2 of liqUid surface areas
tn determining total solution flow
reqUirements, potenllal foam losses
from wind and other factors shall be
considered
I)
II)
The aggregate quantity of foam
solution should be calculated as
below
Foam solution application at the rate
of 5 Ipm/m2 for the liquid surface of
the single largest cone roof tank or
at the rate of 12 Ipm/m2 of seal area
of the single largest floating roof
tank whichever IShigher
However, a foam solullon
application rate of 81 Ipm/m2 of the
liqUid surface of the largest floating
roof tank for 65 minutes may be
conSidered for a roof Sinking case
For sample calculation, refer
(Annexure-IV)
Quantity of foam solullon requlfed
should be calculated based on the
following guidelines .-
Two hose streams of foam each
With a capadty of 1140 Ipm of foam
solution.
4.4.9 DURATION OF FOAM DISCHARGE
The equipment shall be capable of
prOViding pnmary protecllon at the
specified delivery rates for the
follOWing minimum duration
I) Tanks containing Class 'A' & 'B'
65 minutes
il) Where the system's pnmary
purpose is for spill fire protection
30 minutes
4.4.10 WATER FOR FOAM MAKING
Water quantity required for making
foam solullon depends on the
percent concentration of foam
compound Foams In normal use
have a 3% to 6% proporflonlng ratio
However, foam supplier data shall
be used for determining water
requiremenl
III)
Size of Terminal
(InKl)
For Installation having
aggregate capacity of
1000 KL
For Installation having
aggregate capacIty up
to 10,000 KL
For Installation having
aggregate capacity up
to 25,000 KL
For fnstarfation having
aggregate capacity
more than 25,000 KL
Water/Foam
Monitor (Nos.)
Nil.
1 No of
1600lpm
1 No. of
2400 Ipm
2 Nos of
2400 Ipm.
The aggregate quantity of foam
solutions should be largest of
4411(i), 44.11(11) and 4.4 11 (III)
as above for a minimum period of
65 minutes From this the quantity
of foam based on 3% or 6%
proportion should be calculated
However, for installation having
aggregate storage not more than
10,000 Kl, the foam concentrate
storage shall be based on 4.4 l(i)
only
In case of AViation Fuelling Stations
where aggregate product storage
capacity IS less than 1000 KL, foam
quantity for spill fire protection of 30
minutes shall be made
4.4.12 FOAM COMPOUND STORAGE
Foam compound should be stored
as explained In IS-49892006/Ul-
162
Type of foam compound used can
be protein or fluro-proteln or AFFF
Alcohol Resistant Foam shall be
used for handling methanol/ ethanol
or furfural fICes M,nimum 1 Kl of
Alcohol Resistant Foam compound
shall be maintained at the
installation to handle
methanol/ethanol or furfural fICe
Shelf life of foam compound shall be
taken from manufacturer's data
Foam compound shall be tested
periodically as per OEM gUidelines
to ensure its quality and the
deteriorated quantity replaced The
deteriorated foam compound can be
used for fire training purposes For
details of type of tests & their
periodicity, refer IS 4989 2006/UL-
162 or EqUivalent Standard
Quantity of foam compound equal to
100% of requirement as calculated
in 4 411 should be stored in the
Installation, NOI. 2 ThiS quantity may
be SUitably reduced if mutual aid for
foam supply ISavailable
4.5
4.5.1
4.5.2
4.5.3
For sample calculation, refer
(Annexure- IV)
CLEAN AGENT FIRE
PROTECTION SYSTEM
General
Clean agent fire extingUishing
system as per NFPA-2001 (latest
edllion) shall be conSidered for such
protection system
The Protection System broadly
consists of container, feed Imes, ring
mains/laterals, spray nozzles,
Signaling equipment and cables,
heat detection and activation
devices
The Protection System can detect,
control & extmgulsh the fICeand also
Simultaneously give audiO Visual
,ndicat,on on the control panel
Recommended Use
The system may be conSidered for
protection of floating roof tanks,
control rooms and computer rooms,
QUANTITY AND STORAGE
Each hazard area to be protected by
the protection system shall have an
Independent system
The lime needed to obtam the gas
for replacement to restore the
systems shall be considered as a
governmg factor In determlnmg the
reserve supply needed, 100%
standby containers shall be
conSidered for each protected
hazard
Storage contamers shall be tocated
as near as pOSSibleto hazard area
but shall not be exposed to fire,
Storage containers shall be carefully
located so that they are not
subjected to mechanical, chemical
or other damage.
All the components of the system
shall be capable of withstanding
heat of fire and severe weather
conditions
4.5.4 FLOATING ROOF
PROTECTION
TANK
Floaling roof tanks of 60 m and
above diameter may be conSidered
for proteclion by installing such
systems
4.5.5 CONTROL ROOM AND
COMPUTER ROOM PROTECTION
Control rOom and computer room
may be protected by Clean Agent
Fire Extinguishing System.
Floating roof tank may be protected
by clean agent or foam flooding
based fire extinguishing system for
Its In bUilt detection, control and
actuation mechanism If a rim seal
fife occurs, "Its heat causes one or
more spray nozzles to open and the
gas IS applied on the surface of fire
and alarm ISsounded
This IS In addition to the fixed water
spray system and Fixed foam
system or SemHlxed foam system
on all floating roof tanks stOring
Class A & B petroleum.
It ,s considered good practice to
avoid unnecessary exposure to
Clean Agent Fire Extinguishing
System In order to minimiZe the
exposure, persons should be
evacuated from the areas before the
system comes into operation.
4.6 FIRST AID FIRE FIGHTING EQUIPMENT
4.6.1 Portable Fire Extinguishers
i) All fire extinguishers shall conform to respective IS/UL or EqUivalent codes, VIZ 10 Kg
OCP Type (IS2171/Ul299), 45/6.8 Kg C02 Type (IS 2878/Ul 154) & 25/50/75 Kg OCP
Type (IS 10658/UL 299) and bear ISI/Ul mark. BIS/UL or Equivalent certificates of all
extJngUishers shall be maintained at the location
II) While selecting the Extinguisher, due consideration should be given to the factors like
flow rate, discharge lime and throw In line with IS2190 J UL711.
ill) The Dry Chemical Powder used In extJngUisher and carbon diOXide gas used as
expelling agent shall be as per relevant ISJUl or EqUivalent code
iv) While o;electlng the dry chemical powder, due conSideration should be given to the
typical properties VIZ Apparent DenSity (065 +/- 005), Fife Rating (144B), Thermal
Gravimetric AnalysIs (WithdecompOSitionat around 250°C) and foam compatibility
v) Siliconlsed Potassium bicarbonate OCP powder (IS 43082003) / Mono-ammonium
phosphate based OCP powder (IS 14609) can also be used for recharging OCP fife
extinguishers.
vi) Spare C02 cartridges and OCP refdls as required based on thelf shelf life should be
maintained However, minimum '0% of the total cllarge In the extinguishers should be
maintained at the 10catJon.
vII) Portable fire extinguIshers shall be located at convenient locations and are readily
accessible and clearly VISibleI at all times
VIII)The sand buckets shall have round bottom With bottom handle haVing 9 liter water
capaCity conforming to IS2546 The sand stored In bucket shall be fine and free from 011,
water or rubbish.
ix) Rain protection of sUitable design should be provided for all extingUishers & sand
buckets
x) The maximum running distance to locate an extrngUisher shall not exceed 15 m
xi) The extingUisher shall be Installed in such a way that ItStop surface IS not be more than
15m above the floor/ground level
xII) The no. of extinguishers at various locations shall be provided as under
Petroleum Depots, Terminals & Lube Oil Installations
Sr, No. Type of Area , Scale of Portable Fire Extinguishers
(I) lube Godown 1 No 10 Kg OCP extinguisher for every 200 m2 or
min 2 Nos In each Godown whichever IShigher.
(II)
I
Lube Filling Shed 1 No 10 Kg OCP extinguisher for 200 m2 Or mln
2 Nos In each Shed whichever IShigher
(III) Storage of (Class NB) 1 No 10 Kg OCP extinguisher for 100 m2 or mln
In packed containers and 2 Nos In each Storage Area whichever IShigher.
stored In open/closed area
(Iv) Pump House (Class NB) 1 No. 10 Kg OCP for 2 pumps.
Up to 50 HP 1 No 10 Kg OCP for each pump
Above 50-100 HP 2 Nos of 10 kg or 1 no. of 25 kg OCP for each
Beyond 100 HP pump
(v) Pump House (Class C)
Up to 50 HP 1 no. 1OKgOCPfor every 4 pumps up to 50 HP
Above 50 HP 2 nos 10 Kg OCP or 1x25 kg OCP for 4 pumps
(VI) Tank Truck loading & 1 No. 10 Kg OCP extingUisher for each bay plus 1
unloading gantry for No. 75 Kg OCP extinguisher for each gantry
POL/Special products
(VII) Tank Wagon loading 1 No. 10 Kg OCP extinguisher for every 30 m of
and unloading gantrylsldlng ISldlng plus 1 No 75 Kg OCP extinguisher for each
gantry/siding
(vIii) NG Tank Farm 2 Nos 10 Kg OCP extingUishers for each tank plus
4 Nos. 25 Kg OCP extingUishers for each Tank
Farm pOSitioned at four corners in case of
adjoining tank farms, the no. of
25 Kg extinguishers may be reduced by 2 nos. per
tank farm
(Ix) U/G Tank Farm 2 Nos 10 Kg OCP extingUisher for each Tank
Farm
(x) Other Pump Houses 1 No 10 Kg OCP extinguisher for every two
pumps or mln 2 Nos 10 Kg OCP extinguisher for
each Pump House whichever IS higher.
(XI) Admin Building/Store 1 No 10 Kg OCP extinguisher tor every 200 m2 or
House mln 2 Nos 10 Kg OCP extinguishers for each
floor of BUlldlnglStore whichever is higher
(xiI) OG Room 2 Nos e~ch 10 Kg OCP & 4.5 Kg CO2
extingUishers for each OG room.
(XIII) Main SWitch Room/Sub- 1 No. 45 Kg C02 extinguisher for every 25 m2
Station plus 1 No 9 Uter sand bucket per transformer bay.
(XIV) Computer Room/ Cabm 2 Nos of 2 Kg C02 or 2 Nos. of 2.5 Kg Clean
Agent extingUisher per Computer Room and 1 No.
2 Kg CO2 or 1 No. 10 Kg Clean Agent
extinguisher per cabin.
(xv) Secuflty Cabin 1 No 10 Kg OCP extinguisher per cabin.
(XVI) Canteen 1 No 10 Kg OCP extingUisher for 100 m2
(xvII) Workshop 1 No 10 Kg OCP extinguisher & 1 No 2 Kg CO2
extinguisher
(XVIII) Laboratory 1 NO.1 0 Kg OCP extinguisher & 1 NO.4 5 Kg CO2
extinguisher
(XIX) Oil Sample Storage Room 1 No. 10 Kg OCP extinguisher per 100 m2 or min.
1 no. 10 Kg extinguisher per room whichever is
higher.
(xx) Effluent Treatment'Plant 1 No 75 Kg. & 2 nos. 10 Kg OCP Extinguisher
(XXI) Transformer 1 No 10 Kg. OCP extingUisher
(XXii) UPS / Charger Room 1 No 2 Kg C02 extinguisher
NOTE ;- ALL FIRE EXTINGUISHERS SHALL BEAR ISI OR EQUIVALENT MARK
Pipeline Installations
For pipeline Installations, the portable extinguisher shall be provided as per the above list
(46 1) sUitably amended along with follOWing addillons-
Sr. No. Type of Area Scale of Portable Fire Extinguishers
(I) Main line pump shed 1 No 75 Kg DCP, 10 Kg DCP & 6.8 Kg CO2
(Engine/Motor Driven) extinguishers per two pumps up to a maximum of
4 nos
(II) Booster Pump 1 No 10 Kg DCP per two pumps up to a maximum
. of 3 nos and 1 No 6.8 Kg C02 extinguIsher
(III) , Sump Pump, 1 No 10 Kg DCP extinguisher
Transmix Pump & Oil
Water Separator Pump
(Iv) Scrapper Barrel 1 NO.1 0 Kg DCP extinguisher
(v) Control Room 2 Nos 2 5 Kg Clean Agent and 1 No 4.5 Kg CO2
extinguisher
(VI) UHF / RadiO Room 2 Nos 2 5 Kg Clean Agent and 1 No 45 Kg CO2
extinguisher
(vII) Meter Prover/Separator 1 No 10 Kg DCP extinguisher
Filter
(VIII) Repeater Station . 1 No 10 Kg OCP & 1 No 2 Kg C02 extinguisher.
(IX) Mainline Emergency 4 Nos. 10 Kg DCP & 2 Nos.
Equipment Centre 2 Kg C02 extinguishers
(x) Air Compressor 1 No 2 Kg C02 & 1 No 5 Kg DCP extingUisher
4.6.2 Wheeled Fire Fighting Equipment
For Installations having tanks of diameter large than 9 m follOWing fire fightlngequipments
shall be provlded-
Size of Terminal (In KL) Water/Foam Monitor (Nos.)
For installation having aggregate Nil
capacity of 1000 KL
For installation having aggregate 1 No of 1600 Ipm
capacity up to 10,000 KL
For InstallatIOn having aggregate 1 No. of 2400 Ipm
capacity up to 25,000 KL
For Installation having aggregate 2 Nos of 2400lpm
capacity more than 25,000 KL
Foam compound trolley 200/210 liters shall be prOVided as Under-
Tank diameter (In m) Water/Foam Monitor (Nos.)
UP to 24 m 1 No
24 m - 30 m 2 Nos
Above 30 m 3 Nos
4.6.3 HOSES, NOZZLES & ACCESSORIES
(i) Hoses
i) Reinforced rubber hned canvas or Non-
percolat'ng synthetic fire hoses
conforming to IS- 636/ UL 19 (Type A or
B) shall be provided
il) The length and diameter of the hoses
shall be 15 m and 63 mm respectively
fltled with Instantaneous type male &
female couplings of malenal as speCIfied
In IS 636/UL 19
III) The number of hoses stored In an oil
Installalion shall be 30% of the number
of hydrant outlets. The minimum No of
hoses stored. however. shall not be less
than 10
IV)The hoses shall be stored at convenient
and easily acceSSible location In the 011
,nstallation
(Iii Nozzles
In addition to the Jet nozzle provided In
each hose box, there shall be at least
two nozzles In each category VIZ. Jet
nozzle with branch pipe. Fog nozzle,
Universal nozzle. Foam branch pipe and
Water curtain nozzle as per relevant
IS/UL Codes maintained at the location.
(iii) Accessories
The following Personal Protective
Equipment, First Aid EqUipment &
Safety Instrument shall be prOVided as
indicated against each Item
Sand drum with scoop. 4 Nos
Safety helmet. 1 No. per person
Stretcher with blanket 2 Nos
First Aid box: 1 No
Rubber hand glove' 2 Pairs
Explosimeter . 1 No.
Fire proximity SUit 1 Suit
Resuscitator: 1 No
Electrical siren (3 Km range) 1 No
Hand operated siren One each at
Admn Bldg. Laboratory. Planning room,
Control room, T/L Loadlng/Unloading
Facility, TfW Loadlng/Unloading Facility,
Tank Farm, FW Pump House & Product
Pump House (s).
Water Jel blanket: 1 No.
Red & Green flag for fire drill. 2 Nos. in
each color
SCBA Set (30 minute capacity) 1 Set
Withspare cylinder.
PA System - 1 No
Hose box Between two hydrant points
Frre hose 2 Nos per hose box
Jet nozzle 1 No In each hose box
The above gUidelines are mimmum
reqUirement of each Item and can be
Increased depending on the scale of
operations/slze of installation or
requrrement of Local Statutory
Bodles/State Govt
A trolley containing Fire Proxlmily SUIt,B
A. Set. Water Jel Blanket, Resuscitator,
First A,d Box, Stretcher with blanket.
Spare fire hoses, SpeCial purpose
nozzles, Foam branch pipes,
Exploslmeter. P A System shall be
readily available at the location and
POSitioned to have easy access to It
dunng emergency situation
4.7 MOBILE FIRE FIGHTING EQUIPMENT
Mobile fire fighting equipment include
Foam trolleys, Portable water-cum-foam
montlors, etc. In view of comprehensive
Fixed and First Aid Fire proteclion
equipment recommended in the
Standard. provIsion of Mobile fire
fighting equipments in the installation is
not conSidered necessary. However, the
requirement of such equipment may be
reViewed keeping In mind the size,
nature and location of the Installation.
5.0
5.1
FIRE ALARM/COMMUNICATION
SYSTEM
FIRE ALARM SYSTEM
iii) Wherever possible hot line
connection between City Fire Brigade
& nearby Industnes shall be provided
for major installation on need baSIS
I) Hand operated sirens shall be
provided at strategic locations and
clearly marked in the Installation
II) Electnc fire siren shall be Installed at
sUitable location with operating SWitch
located near the risk area at a safe,
Identifiable and easily accessible
place
III) Electnc fire sICenshall be audible to
the farthest distance In the installation
and also In the surrounding area up
to 1 km from the penphery of the
Installalion
IV) Electnc fire sirens shall be connected
to feeder to ensure continuous power
supply dunng emergency shut down
v) The tone of fire siren shall be
different from shift siren
VI) The following fire siren codes should
be followed for different emergency
SituatIons
• FIRE' For fire Situation, the siren
shall be walling sound for 2
minutes
• DISASTER For disaster
situation. the siren shall be wailing
sound for 2 minutes repeated
thnce with a gap of 10 seconds
• ALL CLEAR For all clear
situation, the Siren shall be straight
run sound for 2 minutes
• TEST'SIREN For testing. the
siren shall be straight run sound
for 2 minutes
5.2 COMMUNICA nON SYSTEM
I) Communication system like
Telephone, Public Address System,
etc should be prOVided In non-
hazardous areas of the Instillation
H) In hazardous areas, flame-
proof/lntnnslcally safe Paging
Syslem. Walkie-talkie system or VHF
Set shall be prOVided
IV) Installation shall have a 'Mutual Aid'
arrangement With nearby Industnes to
pool in their resources during
emergency
6.0 FIRE SAFETY ORGANISATION/
TRAINING
6,1 ORGANISATION
A well defined comprehensive On-site
Emergency Plan as per OISO-GDN-
168 shall be drawn,
6,2 TRAINING
I) The fire fighling training shall be
compulsory for all officers, clencals,
operators. security, TfT drivers &
contract workmen who are likely to be
present In the Installation and record
maintained
II) Training on fire & safety aspects to all
concerned shall be Imparted as per
0150-5TO-154
ill) Every employee or authorized person
of contractor working in the
Installation shall be made familiarized
With fire siren codes and know the
location of fire siren operating SWitch
nearest to his place of work.
IV) Instruclions on the aclion to be taken
In the event fire should be pasted at
each sICen point and familiarity With
these instruclions ensured and
recorded.
v) Monthly fire drills shall be conducted
regularly With full Involvement of all
employees of the installation.
VI) Mock disaster dnlls shall be
conducted penodically as per local
statutory reqUirements
Vii) The post drill analysis should be
camed out & discussed emphasJzlng
areas of Improvements.
Viii) The record of such drills should be
maintained at the location
7.0 FIRE EMERGENCY MANUAL
I) Each Installation shall prepare a
comprehensive fire emergency
manual covenng all emergency
scenanos detailing the actions to be
taken In the event of fire emergency
for effective handilng
II) The key action pOints of this manual
shall be displayed at strategic
locations In the Installation for ready
reference
8.0 FIRE PROTECTION SYSTEM,
INSPECTION AND TESTING
I) The fICeprotection equipment shall be
kept In good working condition all the
time
II) The fire protection system shall be
penodically tested for proper
functioning and logged for record and
correctIve actions
III) Inspection & maintenance of fire
fighting equipment shall be done in
accordance with OISD-STD-142
IV) In addition to routine daily
checks/maintenance. the following
periodic Inspection/testing of fire
fighting eqUipment shall be ensured
v) One officer shall be designated and
made responsible for Inspectlo,,,
maintenance & testing of fICe
protection system
VI) The responSibilities of each officer
shall be clearly defined. explained and
communicated to all concerned In
writing for role clanty
8.1 FIRE WATER PUMPS
I) Every pump shall be test run for at
least half an hour or as per OEM
gUidelines. whichever IShigher twice a
week at the rated head & flow
Ii) Each pump shall be checked. tested
and its shut-off pressure observed
once In a month
IIi) Each pump shall be checked & tested
for its performance once In six month
by opening requICed nos of
hydrants/monitors depending on the
capacity of the pump to venfy that the
discharge pressure. flow & motor load
are In conformity WIth the deSign
parameters
IV) Each pump shall be test run
continuously for 4 hours at Its rated
head & flow uSing Circulation line of
fICe water storage tanks and
observations logged once a year.
v) The testing of standby Jockeypump. If
provided shall be checked weekly
Frequent starts & stops of the pump
indicates that there are water leaks In
the system which should be attended
to promptly
8.2 FIRE WATER RING MAINS
(i) The ring main shall be checked for
leaks once In a year by operatmg one
or more pumps & keeping the hydrant
points closed to get the maximum
pressure
(II) The nng maIns. hydrant. monitor &
water spray header valves shall be
visually Inspected for any missing
accessOries. defects. damage and
corrosion every month and records
maintained
(ill) All valves on the ring mains. hydrants.
monitors & water spray headers shall
be checked for leaks, smooth
operation and lubncated once In a
month
8.3 FIRE WATER SPRAY SYSTEM
I) Water spray system on storage tanks
shall be tested lor spray density. flow
rate & response time and venfled With
the performance test certificate
proVided by manufacturer once In six
months
II) Spray nozzles shall be inspected for
proper orientation, corrosion and
cleaned If necessary al least once a
year
iil) The strainers provided In the water
spray system shall be cleaned once In
a quarter and records maintained
8.4 FIXED/SEMI FIXED FOAM SYSTEM
Fixed/Semi fixed foam system on
storage tanks should be tested once in
six months. This shall Include the
testing of foam makerlchamber
9,0 REFERENCES
1) NFPA 11 - Standard on Low
Expansion Foam Systems.
2) NFPA 13 - Standard on
Installation of Spnnkler System.
on
Spray
Standard
of Water
3) NFPA 15 -
Installation
System.
The foam chamber should be
designed sUitably to facilitate of foam
discharge outside the cone roof tank
After testmg foam system, plpmg
should be flushed with water.
CLEAN AGENT SYSTEM
8,5
Clean agent fire extmgulshlng system
should be checked as under-
I) Agent quantity and pressure of
refillable containers shall be checked
once every six month.
It) The complete system should be
mspected for proper operation once
every year (Refer latest NFPA
2001(2004 Edition) for details of
mspectlon of vanous systems)
4) NFPA 20 Standard on
Installation 01 Centnfugal Fife
Pumps.
5) NFPA - 2001 (Edition 2004)
Standard on Ctean Agent Fife
ExtingUishing System
6) No 72-289 - French Regulation
for Hydrocarbon Depots
8,6 HOSES 10) The Petroleum Rules - 2002,
Fire hoses shall be hydraulically tested
once in six months to a water pressure
as specified In relevant
ISIUUEqulvalent codes
11) Model Code of Safe Practices
The Institute of Petroleum (U K.)
15) International Safe Practices of
Oil Industry
8,7 COMMUNICATION SYSTEM
Electnc and hand operated fire sirens
should be tested for their maximum
audible range once a week.
16) 15-3844 Code of Practice on
Installation of Internal Hydrants
In Multistory Building
0ISO-STO-142 Standard on
Inspection of Fire Fighting
EqUIpment & Systems
8,8 FIRE WATER TANK/RESERVOIR
i) Above ground fire water tanks should
be Inspected externally & Internally as
per OISD-STD-129.
il) The water of reservoir shall be
cleaned once In 6 months or as &
when required to keep It free from
foreign matenal, fungus & vegetation
8,9 FIRE EXTINGUISHERS
17)
18)
19)
0ISO-GON-115
Fife Fightmg
Appliances In
Industry
0ISO-STD-154
Safety Aspects
Tralnmg
GUIdelines on
EqUipment &
Petroleum
Standard on
in Functional
Inspection, testing frequency and
procedure should be in line With
OISD-STD-142
20) Ozone Depletion Substances
Regulation & Control Rules •
2000 Ministry of Environment &
Forests, Government of India
21) Kyoto Protocol
22) IS,15683,' Standard on Portable
Fife ExtingUishers
Performance & Construction
SpeCIficatIOns
23) IS,4308 Standard on Dry
Chemical Powder for Fighting 8
& C Class Fifes
SpeCIfications
24) IS, 14609 Standard on Dry
Chemical Powder for Fighting
A.8, C Class Fires
SpeCifications
25) IS,4989 Standard on Foam
Concentrate for Producing
Mechanical Foam for Fire
Fighting Flammable Liquid Fires
, Specifications,
ANNEXURE-I
SAMPLE CALCULATION OF FIRE WATER FLOW RATE FOR STORAGE TANKS
1. DESIGN BASIS
The fire water system in an installation shall be designed to meet the fire water now
reqUIrement of fighting single largest fire scenariO
2. FIRE WATER DEMAND FOR SINGLE LARGEST FIRE
Consider various areas under fire and calculate fire water demand for each area based
on design basIs
2.1 FIRE WATER FLOW RATE FOR FLOATING ROOF TANK PROTECTION
Data
Total storage capacJty In one dyke are" =
No. of tanks =
Capacity of each tank =
Diameter of each tank =
Height of each tank =
a) Cooling water flow rate
Cooling water required for tank on fire
Cooling water rate =
Cooling water reqUfred =
=
=
32,000 m
3
2
16,000 m
3
40 m
14.4 m
3 Ipm/m2
of tank area for tank on fire
3 142 x 40 m x 144 m x 3 Ipmlm'
5426 Ipm
5426 x 60 m'lhr = 326 m'/hr
1000
Assuming that second tank IS located within the tank dyke at a distance more than 30 m
from the tanks shell Therefore, m such case cOolmgreqUJred ISat the rate of 1 Ipmlm' of
tank shell area
Cooling water required for tank falling beyond (R+30) from centre of tank on fire
,
Cooling water rate = 1 Ipmlm of tank area
Cooling water reqUfred = 3 142 x 40 m x 14.4 m x 11pmlm'
= 18091pm
= 1809 x 60 m'lhr = 109 m'/hr.
1000
b} Foam water flow rate
Foam solution application rate
Foam solution required
Foam water required
=
=
=
=
12 Ipm/m' of rim seal area of tank
3.142 x 40 m x 0 8 m x 12 Ipm/m'
097x12121pm = 11761pm
1176 x 60 m'lhr = 71 m'lhr.
1000
ANNEXURE- J
SAMPLE CALCULATION OF FIRE WATER FLOW RATE FOR STORAGE TANKS
1. DESIGN BASIS
The fire water system in an installation shall be deSigned to meet the fire water fiow
requirement of fighting single largest fire scenario
2. FIRE WATER DEMAND FOR SINGLE LARGEST FIRE
Consider various areas under fire and calculate fire water demand for each area based
on design baSIS.
2.1 FIRE WATER FLOW RATE FOR FLOATING ROOF TANK PROTECTION
Data
Total storage capacity in one dyke ares =
No. of tanks =
Capacity of each tank =
Diameter of each tank =
Height of each tank =
a) Cooling water flow rate
Cooling water required for tank on fire
Cooling water rate =
Cooling water reqUired =
=
=
32,000 m'
2
16,000 m'
40m
144m
3 Ipmtm' of tank area for tank on fire
3.142 x 40 m x 14.4 m x 3 Ipm/m'
5426 Ipm
5426 x 60 m'/hr = 326 m'thr.
1000
Assuming that second tank IS located within the tank dyke at a distance more than 30 m
from the tanks shell. Therefore, In such case cooling reqUIred ISat the rate of 1 Ipm/m' of
tank shell area
Cooling water required for tank falling beyond (R+30) from centre of tank on fire
Cooling water rate = 1 Ipmtm' of tank area
Cooling water required = 3142 x 40 m x 144 m x 1lpm/m'.
= 18091pm
= 1809 x 60 m'/hr = 109 m'/hr.
1000
b) Foam water flow rate
Foam solution application rate
Foam solullon required
Foam water required
=
=
=
=
12 Ipm/m' of rim seal area of tank
3.142 x 40 m x 08 m x 12lpm/m'.
097 x 12121pm = 11761pm.
1176 x 60 m'thr = 71 m'/hr.
1000
c) Tolal waler flow rale
Tank cooling
Foam solution application
Total
Say
=
=
=
=
326 + 109 = 435m'/hr
71 m'/hr.
506 m'/hr
510 m'/hr.
2.2 FIRE WATER FLOW RATE FOR CONE ROOF TANK PROTECTION
Data
Total storage capacity in one dyke area =
No of tanks =
Capacity of each tank =
Diameter of each tank =
Height of each tank =
a) Cooling water flow rate
Cooling water required for tank on fire
Cooling water rate =
Cooling water required =
=
=
50.000 m'
4
12,500 m'.
375 m
12 m
3 Ipm/m' of tank area for tank on fire
3142 x 37.5 m x 12 m x 3/pm/m'
4242 Ipm.
4242 x 60 m'/hr = 255 m'/hr
1000
Cooling water required for tanks falling within (R+30) from centre of lank on fire
Cooling water rate = 3 Ipm/m' of tank area
Cooling water required = 3.142 x 375 m x 12 m x 3 Ipm/m' x 3
= 127261pm
= 12726 x 60 m'/hr = 764 m'/hr,
1000
Total cooling water required = 254 + 762 = 1019 m3/hr.
b) Foam water flow rate
Foam solution application rate
Foam solution reqUired
Foam water reqUired
c) Total waler flow rate
Tank cooling
Foam solution application
Total
=
=
=
=
=
=
=
=
5 Ipm/m' of liqUid surface area
3142 x (1875 m)' x 5Ipm/m'.
55231pm.
0.97 x 5523 Ipm = 5357 Ipm.
5357 x 60 m'/hr = 321 m'/hr.
1000
1019 m'/hr
321 m'/hr.
1340 m'/hr.
2.3 FIRE WATER FLOW RATE FOR COOLING POL TANK WAGON LOADING GANTRY
(Ref Annex - II) : Total water requirement = 918 m3/hr.
2.4 FIRE WATER FLOW RATE FOR SUPPLEMENTARY HOSE STREAMS
Water for 4 single hydrant streams
Water for 1 monitor stream
Total water reqUirement
=
=
=
4 x 36 = 144 m3/hr
144 m3/hr
288 m3 / hr.
3.0 TOTAL DESIGN FIRE WATER FLOW RATE
Total design fire water flow rate would be the largest of rlre water flow rates calculated as
per 21, 22, 2 3 and 2.4 above
Design fJre water rate = 1340 m3/hr.
_m_) 0 X 0 ( _m_
ANNEXURE-II
SAMPLE CALCULATION OF FIRE WATER FLOW RATE FOR POL TANK WAGON LOADING
GANTRY
a) Data
Total No. of loading points
'Conslder 20 loading pOints on each side
Length of Rail Gantry
Width of tank wagon gantry
Cooling two spur other distance
b) Cooling water flow rate
=
=
=
=
72 Conventional or
48 BTPN
700 m
12 m
D,v,de total area of gantry Into 24 segments, each segment admeasuring 292m X 12 m
and consider 3 segments operating at a time
Water rate requrred
Total water requrrement
(including hydrant/monitors)
=
=
=
=
_.u.) 0 x 0 (._.u
3 x 29 2 x 12 x 10
630 cum/hr
630 cum/hr + 288 cum
918 cum/hr
ANNEXURE-II'
BRIEF DESCRIPTION OF FIRE FIGHTING FOAM
1.0 FIRE FIGHTING FOAM
Fire flghling foam is a homogeneous mass of tiny air or gas filled bubble of low specific
gravity, which when applied In correct manner and In sufficient quanlity, forms a compact
fluid and stable blanket which IScapable of floating on the surface of flammable liquids
and preventmg atmospheric air from reachmg the liqUid
2.0 TYPES OF FOAM COMPOUND
Two Types of foams are used for fighting liquid fires
2.1 CHEMICAL FOAM
When two or more chemicals are added the foam generates due to chemical reaclion
The most common Ingredlerts used for chemical foam are sodium bicarbonate and
aluminum sulphate With slabllizer. The chemical foam IS generally used In Fire
extinguishers
2.2 MECHANICAL FOAM
It IS produced by mechanically miXing a gas or alf to a solution of foam compound
(concentrate) in water. Vanous types of foam concentrates are used for generating foam.
depending on the requlfement and sUitability E~ch concentrate has Its own advantage
and limitations. The bnef descnptlon of foam concentrates is given below
3.0 MECHANICAL FOAM COMPOUND
Mechanical foam compound may be classified In to 3 categories based on It'Sexpansion
ratIo
3.1 LOW EXPANSION FOAM
Foam expansion ratio may be upto 50 to 1, but usually between 5 1 to 151 as typically
produced by self aspirating foam branch pipes
The low expansion foam contains more water and has better resistant to fife It ISsUitable
for hydrocarbon liqUid fires and ISwidely used In 011 refinery, 011 platforms, petrochemical
and other chemicallndustnes
3.2 MEDIUM EXPANSION FOAM:
Foam expansion ratio vary from 51 1 to 500 1 as typically produced by self asplfaling
foam branch pipes With nets ThiS foam has limited use In controlling hydrocarbon liquid
fife because of it's limitations w r. t poor cooilng. poor resistant to hot surface/radiant
heat etc
3.4 HIGH EXPANSION FOAM
Foam expansion ratio vary from 5011 to 15001, usually between 7501 to 1000:1 as
typically produced by foam generators with air fans This foam has also very limited use In
controlling hydrocarbon liqUid fire because of its limitations W r. t poor cooling. poor
resistant to hot surface/radiant heat etc It IS used for protection of hydrocarbon gases
stored under cryogenic conditions and for warehouse protection
4.0 TYPES OF LOW EXPANSION FOAM
4.1 PROTEIN BASE FOAM
The foam concentrate IS prepared from hydrolyzed protein either from animals or
vegetable source The SUitable stabilizer and preservatives are also added
The concentrate forms a thick foam blanket and IS SUitable for hydrocarbon liquid fires,
but not on water miSCible liqUids The effectiveness of foam IS not very good on deep
pools or low flash pOint fuels which have had lengthy preburn time unless applied very
gently to the surface
The concentrate IS available for induction rate of 3 to 6%. The shelf life of concentrate is
2 years
4.2 FlUORO PROTEIN FOAM
This is similar to protein base foam With fluro-chemlcal which makes It more effective than
protein base foam.
The concentrate forms a thick foam blanket and IS SUitable for hydrocarbon liqUid fires.
but not on water miscible liqUids The foam IS very effective on deep pools of low Nash
point fuels which have had lengthy pre burn time.
The concentrate is available for induction rate of 3 to 6% and the shelf life ISSimilar to that
of protein base foam.
4.3 AQUEOUS FILM FORMING FOAM (AFFF)
The foam concentrate mainly consists of fluoro carbon surfactants, foaming agent and
stabilizer. ThiS can be used with fresh water as well as with sea water
It produces very fluid foam, which flows freely on liquid surface The aqueous film
produced suppresses the liquid vapour qUickly The foam has qUick fire knock down
property and is SUitable for liqUid hydrocarbon fifes As the foam has poor drainage rate,
the effectiveness is limited on deep pool flies of low flash pOint fuels which have lengthy
pre burn time
The concentrate is available for Induction rate of 3 to 6% and the shelf life ISmore than 10
years. This can also be used With non aspirating type nozzles.
4.4 MULTIPURPOSE AFFF
Multipurpose AFFF concentrate IS synthetic, foaming liquid designed specially for fire
protection of water soluble solvents and water Insoluble hydrocarbon liqUids. ThiS can be
used either with fresh water of sea water.
When applied It forms foam with a cohesive polymeric layer on liquid surface, which
suppresses the vapour and extingUishes the fire. The foam is also SUitable for deep pool
fires because of superior drainage rate and more resistive to hot fuels/radiant heat
The 3% induction rate IS SUitable for liqUid hydrocarbon fires and 5% for water miSCible
solvents. The shelf life of concentrate is not less than 10 years ThiS can also be used
with non aspirating type nozzles
4,5 FILM FORMING FLOURO PROTEIN (FFFP)
FFFP combines the rapid fire knock down quality of conventional film forming AFFF with
the high level of post fire securlly and burn back resistance of flouro proleln foam The
concentrate can either be used with fresh water or sea water
The foam ISsuitable for hydrocarbon liquid fires including deep pool fires of low flash point
fuels which have had lengthy pre burn time.
The concentrate ISavailable for Induction rate of 3 to 6% and the shelf life is not less than
5 years. This can also be used with non aspirating type nozzles
5,0 TYPES OF MEDIUM AND HIGH EXPANSION FOAM
SynthetiC foam concentrate IS used with SUitable devices to produce medium and high
expansion foams ThiS can be used on hydrocarbon fuels with low boiling pOint The.
foam IS very light In weight and gives poor cooling effect In comparison to low expansion
foams. The foam ISsusceptible 10 easy break down by hot fuel layers and radiant heat
The Induction rate In water may vary from 15 to 3% Many of the low expansion foam
concentrate can also be used With sl'ltable devices to produce medium / high expansion
foam.
m __ ) OxO( __m
ANNEXURE IV
TYPICAL EXAMPLE OF FIRE CASE IN A LARGE FLOATING ROOF TANK AFTER SINKING
OF FLOATING ROOF
Example for Calculation of Foam ReqUIrement for Floating Tank with Portable Monitors
DATA
Diameter of Tank
Type of Roof
Foam APplication Rate
Foam Solution ReqUlCement
=
=
=
40 m
Floatmg Roof
8 11pm (as per NEPA-11)
II x 40 x 40 x 8 114
= 1017361pm
= 6104 m'/hr
Say = 610 m' /hr.
This much quantities has to be thrown over to sunken roof area with the help of external long
range high volume monitors from the road side periphery of the tank farm The same may be
achieved by 2 nos, of 1000 gpm such monitors, In deSign rate calculation m Ann 1, sinking of
floating roof has not been considered, however, Installation may conSider sIzing the water
network around tank farms to take up such load sO than long range monitors can be fed from this
network by diverting other water available In installation to tank farms In such emergency"
Foam Compound Requirement
=
Say =
101736 x 3/100
305 2 Ipm
305 Ipm
Foam Compound ReqUirement for 65 minutes with 3% concentration
=
Say =
305 x 65
19825 L
20,000 L
•• If two major fife occurs In an Installation with roof sinking case as one of them
n_n) OxO(n __-

More Related Content

What's hot

Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Venu Kandi
 
Aicarr vicenza 2016 emerson
Aicarr vicenza 2016 emersonAicarr vicenza 2016 emerson
Aicarr vicenza 2016 emersonVenu Kandi
 
Belt heater-2009-catalog
Belt heater-2009-catalogBelt heater-2009-catalog
Belt heater-2009-catalogGeorge Hebb
 
Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Muhammed Fuad Al-Barznji
 
Changing Best Practices in Flue Gas Analysis
Changing Best Practices in Flue Gas AnalysisChanging Best Practices in Flue Gas Analysis
Changing Best Practices in Flue Gas AnalysisYokogawa1
 
Practicing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGAPracticing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGATRANSEQUIPOS S.A.
 
Carbon dioxide solutions
Carbon dioxide solutionsCarbon dioxide solutions
Carbon dioxide solutionsUNEP OzonAction
 
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
 Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi... Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...BREEZE Software
 
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...Centro Studi Galileo
 
Thermal pretreatment of biomass/torrefaction - Jaap Kiel
Thermal pretreatment of biomass/torrefaction - Jaap KielThermal pretreatment of biomass/torrefaction - Jaap Kiel
Thermal pretreatment of biomass/torrefaction - Jaap KielEBAconference
 
Milena Gasification - Bram van der Drift
Milena Gasification - Bram van der DriftMilena Gasification - Bram van der Drift
Milena Gasification - Bram van der DriftEBAconference
 
Process improvement
Process improvementProcess improvement
Process improvementLeeya Najwa
 
Final Year Thesis.PDF
Final Year Thesis.PDFFinal Year Thesis.PDF
Final Year Thesis.PDFOmer Farooqi
 
Alternative refrigerant
Alternative refrigerantAlternative refrigerant
Alternative refrigerantDARSHAN B S
 
Design and safety_handbook_3001.5
Design and safety_handbook_3001.5Design and safety_handbook_3001.5
Design and safety_handbook_3001.5CARLOS POZZUOLI
 
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016John Newquist
 

What's hot (20)

Scroll compressors for propane (R290)
Scroll compressors for propane (R290)Scroll compressors for propane (R290)
Scroll compressors for propane (R290)
 
Aicarr vicenza 2016 emerson
Aicarr vicenza 2016 emersonAicarr vicenza 2016 emerson
Aicarr vicenza 2016 emerson
 
Nitrogen purging
Nitrogen  purgingNitrogen  purging
Nitrogen purging
 
Novec 1230 fluid cust
Novec 1230 fluid custNovec 1230 fluid cust
Novec 1230 fluid cust
 
Belt heater-2009-catalog
Belt heater-2009-catalogBelt heater-2009-catalog
Belt heater-2009-catalog
 
Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology Important Conversion Factors in Petroleum Technology
Important Conversion Factors in Petroleum Technology
 
Changing Best Practices in Flue Gas Analysis
Changing Best Practices in Flue Gas AnalysisChanging Best Practices in Flue Gas Analysis
Changing Best Practices in Flue Gas Analysis
 
Practicing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGAPracticing DGA - Diagnóstico DGA
Practicing DGA - Diagnóstico DGA
 
Carbon dioxide solutions
Carbon dioxide solutionsCarbon dioxide solutions
Carbon dioxide solutions
 
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
 Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi... Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
 
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
Bachir Bella - Emerson Climate Technologies - REFRIGERANTI A BASSO GWP IN APP...
 
Thermal pretreatment of biomass/torrefaction - Jaap Kiel
Thermal pretreatment of biomass/torrefaction - Jaap KielThermal pretreatment of biomass/torrefaction - Jaap Kiel
Thermal pretreatment of biomass/torrefaction - Jaap Kiel
 
IDP project
IDP projectIDP project
IDP project
 
Milena Gasification - Bram van der Drift
Milena Gasification - Bram van der DriftMilena Gasification - Bram van der Drift
Milena Gasification - Bram van der Drift
 
Process improvement
Process improvementProcess improvement
Process improvement
 
Final Year Thesis.PDF
Final Year Thesis.PDFFinal Year Thesis.PDF
Final Year Thesis.PDF
 
Alternative refrigerant
Alternative refrigerantAlternative refrigerant
Alternative refrigerant
 
Design and safety_handbook_3001.5
Design and safety_handbook_3001.5Design and safety_handbook_3001.5
Design and safety_handbook_3001.5
 
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
Discussing osha 1910 106 nfpa 30 and recent fire incidents of 2015 2016
 
Mq2420912096
Mq2420912096Mq2420912096
Mq2420912096
 

Similar to Fire protection facilities for petroleum

IRJET- Safety in Petroleum Industry
IRJET- Safety in Petroleum IndustryIRJET- Safety in Petroleum Industry
IRJET- Safety in Petroleum IndustryIRJET Journal
 
Internal cleaning of fuel tanks
Internal cleaning of fuel tanksInternal cleaning of fuel tanks
Internal cleaning of fuel tanksMohamed Basyoni
 
2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Codeandrewwcwong
 
EMERGENCY ISOLATION OF CHEMICAL PLANTS
EMERGENCY ISOLATION OF CHEMICAL PLANTS EMERGENCY ISOLATION OF CHEMICAL PLANTS
EMERGENCY ISOLATION OF CHEMICAL PLANTS Gerard B. Hawkins
 
Planning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage TanksPlanning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage TanksOrlando Costa
 
Boiler operation technical information
Boiler operation   technical informationBoiler operation   technical information
Boiler operation technical informationstephen maloba
 
E uv usexplosiveareas
E uv usexplosiveareasE uv usexplosiveareas
E uv usexplosiveareasIntertek CE
 
FuelCellEurope RCS Workshop
FuelCellEurope RCS WorkshopFuelCellEurope RCS Workshop
FuelCellEurope RCS Workshopdivacreative
 
rosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdfrosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdfssuser3eddcd
 
POLTankFarmLayersProtection (1).pdf
POLTankFarmLayersProtection (1).pdfPOLTankFarmLayersProtection (1).pdf
POLTankFarmLayersProtection (1).pdfBHAVLEOMKARNAVNATAHR
 
Steam Boiler BG01 Compliance with Flomar
Steam Boiler BG01 Compliance with FlomarSteam Boiler BG01 Compliance with Flomar
Steam Boiler BG01 Compliance with FlomarLeigh Ridlington
 
Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016
Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016
Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016David Byrne
 
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...gurkanarifyalcinkaya
 
Thomas & Betts - Hazardous Area Electrical Equipment & Cable Accessories
Thomas & Betts - Hazardous Area Electrical Equipment & Cable AccessoriesThomas & Betts - Hazardous Area Electrical Equipment & Cable Accessories
Thomas & Betts - Hazardous Area Electrical Equipment & Cable AccessoriesThorne & Derrick International
 

Similar to Fire protection facilities for petroleum (20)

Fire fighting
Fire fightingFire fighting
Fire fighting
 
IRJET- Safety in Petroleum Industry
IRJET- Safety in Petroleum IndustryIRJET- Safety in Petroleum Industry
IRJET- Safety in Petroleum Industry
 
Internal cleaning of fuel tanks
Internal cleaning of fuel tanksInternal cleaning of fuel tanks
Internal cleaning of fuel tanks
 
Chap 43
Chap 43Chap 43
Chap 43
 
Area classification
Area classification Area classification
Area classification
 
2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code2009 Sfpe Technical Changes To The Part 4 Fire Code
2009 Sfpe Technical Changes To The Part 4 Fire Code
 
EMERGENCY ISOLATION OF CHEMICAL PLANTS
EMERGENCY ISOLATION OF CHEMICAL PLANTS EMERGENCY ISOLATION OF CHEMICAL PLANTS
EMERGENCY ISOLATION OF CHEMICAL PLANTS
 
OISD.ppt
OISD.pptOISD.ppt
OISD.ppt
 
Planning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage TanksPlanning to Avoid Failure Storage Tanks
Planning to Avoid Failure Storage Tanks
 
Boiler operation technical information
Boiler operation   technical informationBoiler operation   technical information
Boiler operation technical information
 
SPCC Training .pptx
SPCC Training                       .pptxSPCC Training                       .pptx
SPCC Training .pptx
 
E uv usexplosiveareas
E uv usexplosiveareasE uv usexplosiveareas
E uv usexplosiveareas
 
ACA-02
ACA-02ACA-02
ACA-02
 
FuelCellEurope RCS Workshop
FuelCellEurope RCS WorkshopFuelCellEurope RCS Workshop
FuelCellEurope RCS Workshop
 
rosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdfrosemount_level_user_guide_refining_ind.pdf
rosemount_level_user_guide_refining_ind.pdf
 
POLTankFarmLayersProtection (1).pdf
POLTankFarmLayersProtection (1).pdfPOLTankFarmLayersProtection (1).pdf
POLTankFarmLayersProtection (1).pdf
 
Steam Boiler BG01 Compliance with Flomar
Steam Boiler BG01 Compliance with FlomarSteam Boiler BG01 Compliance with Flomar
Steam Boiler BG01 Compliance with Flomar
 
Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016
Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016
Wellhead 6pp Brochure WEB VERSION_FINAL_Feb2016
 
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
 
Thomas & Betts - Hazardous Area Electrical Equipment & Cable Accessories
Thomas & Betts - Hazardous Area Electrical Equipment & Cable AccessoriesThomas & Betts - Hazardous Area Electrical Equipment & Cable Accessories
Thomas & Betts - Hazardous Area Electrical Equipment & Cable Accessories
 

Recently uploaded

(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 

Recently uploaded (20)

Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
★ CALL US 9953330565 ( HOT Young Call Girls In Badarpur delhi NCR
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 

Fire protection facilities for petroleum

  • 1. Report On Fire Protection Facilities For Petroleum Depots, Terminals, Pipeline Installations And Lube Oil Installations - By OISD (March 2007)
  • 2. FIRE PROTECTION FACILITIES FOR PETROLEUM DEPOTS, TERMINALS, PIPELINE INSTALLATIONS AND LUBE OIL INSTALLATIONS CONTENTS SECTION 10 20 30 3 1 3.2 33 40 41 42 43 44 45 46 47 50 5 1 52 60 61 62 70 80 81 8.2 8.3 84 85 86 8.7 90 ANNEXURE 1 2. 3 4. 5 DESCRIPTION Introduction Scope Definitions Petroleum Depots, Terminals & a,l Installations Classification of Petroleum Products Flash POint Fire Protection Facilities GeneralConslderatlon Design Criteria of Fire Protection System Fire Water System Foam System Clean Agent Fire Protection System First Aid Fire Fighting Equipment Mobile Fire Fighting Equipment Fire Alarm/Communication System Communication System Fire Alarm System Fire Safety OrganlZatlonlTralning Organization Training Fire Emergency Manual Fire Protection System, Inspection & Testing Fire Water Pumps Fire Water Ring Main Fire Water Spray System Fixed/ Semi Fixed Foam System Clean Agent Fire Pro:ectlon System Hoses Communication System Reference Sample Calculation of Fire Water Flow Rate for Storage Tanks Sample Calculation of Fire Water Flow Rate for POL Tank Wagon Loading Gantry Brief Description of Fire Fighting Foams. Typical Example for Calculation of Foam Compound ReqUIrement Large Floating Roof Tank After Sinking of Roof. TYPical System of Automatic Actuated Foam Flooding System for Rim Seal of Larger Floatlr.g Roof Tanks.
  • 3. FIRE PROTECTION FACILITIES FOR PETROLEUM DEPOTS, TERMINALS AND PIPELINE/LUBE OIL INSTALLATIONS 1.0 INTRODUCTION The petroleum depots, terminals & plpeline/lube 011 Installations are generally located In the remote areas and near railway sidings However, the experience shows that with the passage of time, these get surrounded by resldential/lndustnal installations The Inventory of flammable materials stored therein necessitates Inbullt fire protection facilities covered In 0ISD-STD-144, also- STO-150 or 0ISO-STO-169 as the case may be illl Drilling rigs, Work over rigs and Production Installations (GGSiOCS, GCPIGCS, EPS, QPSIWHI etc) which are covered In OISO-STD- 189 IV) Port all Terminals for which also- $TO-156 shall be referred v) Control Room Building & Electncal Installations shall be prOVidedas per 0ISO-$TO-163 & 173 respectively, It can be Impractical and prohibitively costly to deSign fire protection facilities to control catastrophiC fires The usual requirement of a good system IS to prevent emergencies from developing into major threat to the oil Installation and surroundings 2.0 SCOPE 21 This standard tays down the minimum requirement of fire protection facilities at Petroleum Depots, Terminals, Pipeline Installations With or Without Storages, Central Tank Farms (CTF) Lube a,l Installations, Grease Manufactunng & Filling FaCllilies 2 2 ThiS standard does not cover the fire protection faCilities for ,- 23 3.0 It IS not intended that the prOVISions as speCified in this reVised standard should be applied ngldly to eXisting premises. However, these proviSions shall be reviewed considenng various hazards for Implementalion where for a variety of reasons, it may not be practicable to comply with ThiS standard shall be applicable in selective Implementation of the recommendations at such locations for which a SUitable structured approach should be adopted to carry out the review at site consldenng various hazards. However, the additional reqUirements shall be applicable to all new locations conceived after publication of the new edition. DEFINITIONS A portion of the property, where combustible/flammable liqUids are received by tanker, pipelines, tank wagons, tank trucks and are stored or blended in bulk for the purpose of distribution by tankers, pipelines, I) Depots, Terminals/lnstallalions In Refineries and/or a,l/Gas Processing Plants under the same management and In ctose proximity for which 0ISO-STO-116 shall be referred II) Instaltatlons handling liquefied Petroleum Gas (LPG) Storage, Handling and Bottling The same are 3.1 PETROLEUM TERMINAS DEPOTS &
  • 4. likely to be refined, blended or stored at above its flash pOint. For classlflcation and e~tent of hazardous area, refer 'The Petroleum Rules - 2002". tank wagons, tank trucks, portable tanks or containers 3.1.1 PIPELINE INSTAllATIONS Pipeline Installations are those facilities on cross-country pipelines which have pumping and/or delivery station with or without storages 3,2 CLASSIFICATION PETROLEUM PRODUCTS OF General Classification Excluded Petroleum means petroleum having a flash point above 23'C and above. Petroleum Class B means petroleum having a flash pOint of n'c and above but below 6S'(' Petroleum Class C means petroleum having a flash point of 6S'C and above but below 93'(, A means flash point Petroleum Class petroleum having a below 23'(, Petroleum means any liqUid hydrocarbon Or ml~ture of hydrocarbons and any Inflammable ml~ture (liquid, viscous or solid) containing any liquid hydrocarbon. Petroleum products other than LPG which IS a separate category, are classified according to their closed cup Flash Poinl as follows 3.2.1 3.2.2 The facilities meant for receipt, storage and blending of base oils & additives Into finished Lube products. It Includes lube-blending plants, grease manufactUring plants & small can filling plants These are the facilities such as Control Room Building, Sub-Slatlon, Diesel Generator (with diesel storage tank). & Administrative Building, etc. provided in Petroleum Depots, Terminals and Pipeline Installations The facilities where ATF is received by tank wagons, tank trucks & pipeline and stored In bulk for dispatch of product by refuellers & pipeline It include also storage of Methanol/AVGAS & other addilives in drums. 3.1.2 lUBE Oil INSTAllATIONS 3.1.3 AVIATION FUllEING STATIONS 3.1.4 INFRASTRUCTUREIOTHER FACILITIES Flash Point of any petroleum means the lowest temperature at which it Yields a vapor which will give a momentary flash when Ignited The locations where product is handled by artificially heating it to above it's flash pOint, Class C product shall be considered as 3.1.5 HARZARDOUS AREA An area will be deemed to be hazardous where- Petroleum haVing flash pOint below 65'C or any flammable gas or vapor in a concentration capable of ignition ISlikely to be present Petroleum or any flammable liqUid haVing flash point above 65'C IS 3.2.3 Classification for Petroleum Products Heated
  • 5. 4.1 GENERAL CONSIDERATIONS 4.1.1 layout 3.3 4.0 Class B product and Class B product as Class A product GENERAL TERMINOLOGY Clean agent electrically non· conductive, volatile or gaseous fire extingulshants that does not leave a reSidue upon evaporation and meets the reqUirements given In the latest NFPA 2001 on clean agent fire extinguishing systems in line With environmental consideration of Kyoto Protocol Shall Indicate that provIsion IS mandatory Should Indicate that provision IS recommendatory as per good engineering practices May indicate that provision IS optional FIRE PROTECTION FACILITIES The fire protection philosophy IS based on loss prevention & control It considers that a depot/terminal, carries an Inherent potential hazard due to flammable nature of petroleum products stored therein. A fire In one facility can endanger other facility of the depot/terminal. If not controlled/extinguished as qUickly as possible to minimize the loss of life & property and prevent further spread of fire The Size of product storage & handling faCilities. their localion and terrain determine the baSIC fire protection reqUirements. layout of a depot or terminal. pipeline Installation. lube 011 Installation. grease manufacturing & filling faCilities and handlingldisposal system of blow down, drain from eqUipment handling flammable liqUids shall be done in accordance With 0ISO·STO·118 & OISO·STD. 109 as applicable SpeCial consideration should be given In the plant layout & product line layout for heated products lines laid alongside the pipeline carrying lighter petroleum products. 4.1.2 FIRE PROTECTION Depending on the nature of risk. follOWing fire protection facilities shall be provided in the Installation • Fire Water System. • Foam System • Clean Agent Protection System • First Aid Fire Fighting Equipment • Mobile Fire Fighting Equipment. • Fire Detection, Alarm & Communication System. 4.2 DESIGN CRITERIA FOR FIRE PROTECTION SYSTEM 4.2.1 Facilrlles shall be designed on the baSISthat city fire water supply is not available close to the Installation. 4.2.2 One Single largest risk shall be considered for providing faCilities 4.2.3 The hazardous areas shall be protected by a well laid combination of hydrants & monitors. The follOWing installations are exempted from this provision'- I) The Installation haVing aggregate above ground storage capacity of less than 1000 KL (ClassA+B+C) other than AFS. Ii) Pipeline installation having only scrapper stations or sectlonallzlng valve stations.
  • 6. 4,2,4 Tank Wagon (TW)lTank Truck (TT) loading/unloading facilities, Manifold area of product pump house & Exchange pit shall be fully covered with a well laid out combination of hydrants and water-cum-foam monitors. 4,2,5 The Installations storing Class A petroleum In above ground tanks shall have fixed water spray system However, Installations above 1000 KL storage fulfilling the following both conditions are exempted from the provIsion of fixed water spray system - • Aggregate above ground storage of Class A & 8 petroleum up to 5000 KL • Floating roof tank storing Class A petroleum haVing diameter up to 9 rn 4,2,6 Class '8' above ground Petroleum storage tanks of diameter larger than 30 m shall be provided with fixed water spray system 4,2,7 When Class A & B above ground storage tanks are placed In a common dyke, the fixed water spray system shall be provided on all tanks except for small terminals as mentioned In 4.2.6 4,2,8 TW loading gantries shall be provided with manually operated fixed water spray system. In case automatic fixed water spray system IS provided, the gantry may be divided Into sUitable number of segments (each segment haVing min. length of 15 m length & width of 12 m) and three segments operating at a time shall be considered as Single risk for calculating the water reqUIrement. Accordingly, a provision shall be made to actuate the water spray system from a safe approachable central location i.e affected zone and adjoining zones 4,2,9 The fixed water spray system shall also be provided on all tanks irrespective of diameter where Inter distances between tanks In a dyke and/or within dykes are not meeting the reqUIrements of 0ISD-STO-118 4,2,10 Fixed foam system or Semi-fixed foam system with foam trolley/s shall be provided on tanks (floating roof or fixed roof) exceeding 18 m diameter storing Class A or Class 8 petroleum. 4-2,11 Portable foam and/or water-cum- foam mOnitors shall be provided for suppression of pool fire In tank farm area 4,2,12 Automatic actuated rim seal fire extinguishing system may be provided based on foam or clean agent flooding mechanism on floating roof tanks having diameter larger than 60 m ThiS is in addition to the fixed water spray system and Fixed foam system or Semi-fixed foam system on all floating roof tanks storing Class A & 8 petroleum. Foam Flooding System Selection and deSign of foam based flooding system should be as defined in latest "Standard for Foam Systems - NFPA-11A". Clean Agent Flooding System Selection and deSign of clean agent based flooding system should be in line with the "Standard on Clean Agent Fire Extinguishing Systems - NFPA 2001 (latest Edition). The clean agent should also comply with the reqUirements of "Ozone Depletion Substances Regulation & Control Rules - 2000, Ministry of
  • 7. Forests, 4.2.13 EnVifonment & Government of India The listed clean agents like Triflurolodide & F/uroketone can be used as fire suppressant for floating roof rim seal fire protection and In control room/computer room/ pressunzed room fire protection respectively The clean agent based protection system consists of an in-built fire detection. control and actuation mechanism If a rrm seal fire occurs. its heat causes one or more spray nozzles to open and the extinguishing gas (clean agent) IS applied on the surface of fire and Simultaneous alarm ISalso sounded Refer (Annexure-V) for a typical system of automatic nm seal frre protection uSing ctean agent The follOWing additional requirements shall be apphcable to the installations located In lightening prone areas & where inter distances between tanks In a tank dyke andlor Withintank dykes are not conforming to the proVISionsof 0ISo-STo-118 • Double seal of appropnate matenal for all sizes of floating roof tanks storrng Class A petroleum . • Automatic actuated nm seal fire protection system based on foam or clean agent for tanks haVing diameter more than 60 m and storrng Class A petroleum. 4.2.16 Clean Agent (Halon substitute) based flooding system may be considered for control rooms. computer rooms and pressurized rooms In major locations having automated pipeline receipt/dispatch andlor TW/TT loading faCilities. Selection of clean agent and design of fire protection system for control rooms, computer rooms and pressunzed rooms should follow the Standard on "Clean Agent Extinguishing systems NFPA Standard 2001 (Edition 2004) Including its safety guidelines With respect to "Hazards to Personnel". electrrcal clearance and envrronmental factors In hne With enVifonmental conSiderations of Kyoto Protocol Clean agent like Inert gas, Fluroketone can be used as fire suppressant In control rooms, computer rooms and pressunzed rooms 4.3 FIRE WATER SYSTEM Water IS used for fire extinguishments, fire control, coohng of equipment exposure protection of equipment and personnel from heat radiation. The fire water ring main shall be provided all around perrmeter of the installation With hydrants/monitors spaced at Intervals not exceeding 30 m when measured aerially. 4.2,14 As an additional requirement, fixed foam system or semi-fixed foam system With foam trolleyls shall also be prOVided on all tanks irrespective of diameter where Inter distances between tanks In a tank dyke andlor Within tank dykes are not meeting the requirements of 0ISo-STo-118. 4.2.15 Water spray system shall be provided on TW loading gantry 4.3.1 Components of Fire Water System The main components of the system are Fire Water Storage, Fire Water Pumps and Distribution Piping Network. 4.3.2 Basis The frre water system In an Installation shall be deSigned to
  • 8. 4.3.2.1 Design Flow Rate meet the fire water flow reqUirement to fight single largest nsk at a time. I) Fire water flow rate for a tank farm shall be aggregate of the follOWing • • • Water flow calculated for cooling a tank on fife at a rate of 3 Ipm/m' of tank shell area Water flow calculated for exposure protection for all other tanks failing within a radius of (R +30)m from centre of the tank on fife (R-Radlus of tank on fife) and situated in the same dyke at a rate of 3 Ipm/m' of tank shell area Water flow calculated for exposure protection for all other tanks failing outSide a radius of (R+30)m from centre of the tank on fife and situated In the same dyke at a rate of 1 Ipm/m' of tank shell area shall be at a rate of 10.2 Ipm/m' In case the penpheral distance between any two of the above facilities ISless than 15 m, It shall be conSidered as single nsk for the calculation of fire water requirement ill) Fife water flow rate for TW loadjng gantry (Refer Annexure - II) and product pump house in a depot or terminal shall be calculated at a rate of@ 102 Ipm/m2 However, If pump house of volatile productls IS located under pipe rack fife water flow rate shall be calculated at a rate of 20.4 Ipm/m2 IV) Fife water flow rate for supplementary streams shall be based on using 4 Single hydrant outlets and 1 monitor simultaneously Capacity of each hydrant outlet as 36 m3/hr and of each monitor as 144 m3/hr minimum may be conSidered at a pressure of 7 kg/cm2g. • For water flow calculations, all tanks farms h~vlng class A or B petroleum storage shall be conSidered irrespective of diameter of tanks and whether fixed water spray system is provided or not The deSign fife water rate shall be the largest of [4321 (I)J, [4.3.2.1 (l1)J, [4.32.1 (IIi)], or [43.2.1 (Iv)]. (Refer Annexure-I) 4.3.3 Header Pressure • Waler flow required for applYing loam on a Single largest tank by way of fixed foam system, where provided, or by use of water/foam momtors (Refer section 448 for foam solution application rates) Fife water system shall be designed for a minimum reSIdual pressure of 7 kg/cm2(g) at hydraulically remotest pOint In the installation consldenng single largest nsk scenario. • Various combinations shall be considered in Ihe tank larm lor arnvlng at different fire water flow rate and the largest rate to be considered for deSign II) Fife water flow rate for pump house shed, scrapper area, metenng area, flltenng area & manifold area at CraSs country pipeline Installations 4.3.4 Storage Water for the fire fighting shall be stored in any eaSily accessible surface or underground or above ground tanks of steel, concrete or masonry. The effective capacity of the reservolf/tank above the level of
  • 9. suction pOint shall be minimUm 4 hours aggregate rated capacity of pumps However. where reliable make up water supply is 50% or more of design flow rate. the storage capacity may be reduced to 3 hours aggregate rated capacity of pumps Fresh water should be used for fire fighting purposes. /n case sea water or treated effluent water IS used for fire fighting purposes. the material of the pipe selected shall be sUitable for the service The installation shall have facilities for receiving and diverting all the water coming to the installation to fife water storage tanks in case of an emergency Storage reservoir shall be In two equal Interconnected compartments to faCilitate cleaning and repairs. In case of steel tanks there shall be minimum two tanks each having 50 % of required capacity. Large natural reservolfs haVing water capacity exceeding 10 times the aggregate water requirement of fire pumps may be left unlined 4.3.5 Fire Water Pumps (I) Fire water pumps haVing flooded suction shall be installed to meet the deSign fire water flow rate and head /f fire water is stored in underground tanks. an overhead water tank of sufficient capacity shall be provided for flooded suction and accounting for leakages in the network. If any (ii) The pumps shall be capable of discharging 150% of its rated discharge at a minimum of 65% of the rated head. The Shut-off head shall not exceed 120% of rated head for hOrizontal centrifugal pumps and 140% for vertical turbine pump (Iii) At/east one standby fire water pump shall be provided up to 2 nos. of main pumps. For main pumps 3 nos. and above, minimum 2 nos. standby pumps of the same type, capacity & head as the main pumps shall be provided. (IV) The fire water pump(s) including the standby pump(s) shall be of diesel engine driven type Where electric supply IS reliable 50% of the pumps may be €Iectric driven. The diesel engines shall be qUick starting type with the help of push buttons located on or near the pumps or located at a remote location Each engine shall have an Independent fuel tank adequately Sized for 6 hours continuous running of the pump (vi Fife water pumps & storage shall be located at 30 m (minimum) away from equipment or where hydrocarbons are handled or stored (Vi) Fire water pumps shall be exclusively used for fire fighting purpose only (VII) Suction and discharge valves of fire water pumps shall be kept full open all the times. (Viii) The fire water network shall be kept pressurized by static water tank or Jockey pump( s) (ix) In case jockey pump is used for pressurrzation. a standby jockey pump of similar type. capacity & head shall be prOVided 4.3.6 Fire Water Network (i) Looping The fire water network shall be laid in closed loops as far as possible to ensure multi-directional flow in the system. Isolation valves shall be
  • 10. provided in the network to enable Isolation of any section of the network without affecting the flow In the rest. The Isolation valves shall be located normally near the loop Junctions. Additional valves shall be provided In the segments where the length of the segment exceeds 300 m. (ii) Above I Underground Network The fire water ring mains shall be laid above ground at least at a height of 300 mm above finished ground level • For rail crossIng. proVIsions stipulated by Indian Railways shall be compiled, • The ufg ring main shall be protected against SOilcorrosion by suitable coalingfwrapPlng or cathodiC protection wherever cathodiC proteclion already exists for protection of other pipelines system • Pipe supports under the pipe line shall be SUitable for soli conditions. jii) Support & Protection of above ground pipelines However, the ring main may be laid underground at the following places If fire water ring mains are laid underground, the following shall be ensured - • Road crossings • Places where above ground piping IS likely to cause obstruction to operalion and vehicle movement • Places where above ground piping IS likely to get damaged mechanically • Where frost conditions warrant and ambient temperature IS likely to fall subzero, under ground piping shall be laid at least 1 m below the finished grade level to avoid freeZing of water Alternatively, water circulation may be carried out In the above ground pipelines or any other sUitable means. ii) Protection pipeline of underground The mains shall be supported at regular Intervals not exceeding 6 en. For pipeline size less than 150 NB, support Interval shall not exceed 3 m The pipe support shall have only pOintcontact. The system for above ground portion shall be analyzed for fleXibility against thermal expansion and necessary expansion loops, guidesfcross gUides and supports prOVided. (iv) Sizing of pipeline Fire water ring main shall be sized for 120% of the design water flow rate Design flow rates shall be distributed at nodal pOints to give the most realistiC way of water reqUirements In an emergency It may be necessary to assume several combinations of flow requirement for deSign of network • The ring main shall have at least 1 m earth cushion in open ground, 15 m cushion under the road crossings and in case of crane movement area pipeline may be protected with concretefsteel encasement as per deSign requirement In case of sea water service, the fire water main pipes shall be concrete mortar lined internally or other SUitable coating matenal shall be used The stand post for hydrants and monitors shall be Sized to meet the respective deSign water flow rates
  • 11. Iv) General Conneclions for fixed water monitors on the network shall be provided with independent Isolation valves Fire water mains shall not pass through bUildings or dyke areas In case of underground mains the isolation valves shall be located In RCC/bnck masonry chamber of sUitable size to facilitate operation dunng emergency & maintenance 4.3.7 Hydrants & Monitors I) Hydrants shall be located bearing In mind the fire hazards at different sections of the premises to be prolected and to give most effective service At least one hydrant post shall be provided for every 30 m of external wall measurement or penmeter of battery limit In case of high hazard areas For non- hazardous area. they shall be spaced al 45 m Intervals The honzontal range & coverage of hydrants with hose conneclions shall not be considered beyond 45 m II) Hydrants shall be located at a minimum distance of 15 m from the penphery of storage tank or eqUipment under protection. In case of buildings this dlslance shall not be less than 2 m and not more than 15 m from the face of bUilding ProvIsion of hydrants within the building shall be provided In accordance with J S . 3844 Ill) HydrantiMonltors shall be located along road Side berms for easy acceSSibility IV) Double headed hydrants with two separate landing valves or momtor on SUitablysized stand post shall be used. All hydrant outlets/monitor Isolalion valves shall be situated at workable height above ground or hydrantlmomtor operating platform level. v) Monitors shall be located to direct water on the object as well as to provide water shield to firemen approaching a fire. The requirement of monitors shall be established based on hazards Involved and layout considerations. Monitors shall not be Installed within 15 m of hazardous equipment The location of the monitors shall not exceed 45 m from the hazard to be protected High volume long range monitors. shall be located more than 45 m from the hazardous equipment & their water header/s sized accordingly to meet the rated water flow rate of monitor as well as deSign water flow reqUifement of Single largest nsk scenano vi) Hydrants and monitors shall not be Installed InSide the dyke areas However, as an additional requirement, oscillating monitors may be provided in inaccessible area within dyke with isolalion valve or ROV outside the tank farm. vii) TWITT loading & unloading facilities shall be provided with alternate hydrant and water-cum-foam monitors having multipurpose combination nozzles for Jet spray & fog arrangement and fire hydrants located at a spacing of 30 m on both Sides of the gantry The hydrants & monitors shall be located at a mln,mum distance of 15 m from the hazard (eg TW & TT loading/unloading facilities) to be protected
  • 12. VII') Hydrants/Monitors preferably located connection shall with be branch VII Hose boxes, water monitors and hydrant outlets shall be painted WIth "LuminOUSYellow" paint as per IS5 4.3.8 Material Specifications The matenals used In fire water system shall be of approved type as Indicated below i) Pipes Carbon Steel as per tS3589/IS1239/IS 1978 or It'S equivalent for fresh water service. A sUitable proven matenal conforming to design. heat radiation & It's associated hazards. operation & maintenance requirements shall be used for saline/brackish waler service vii) Corrosion resistant paint shall be used In corrosion prone areas 4.3.9 FIXED WATER SPRAY SYSTEM i) Fixed water spray system is a fixed pipe system connected to a reliable source of water supply and eqUipped With water spray nozzles for speCific water discharge and dlstributton over the surface of area to be protected The piping system ,s connected to the hydrant system water supply through an automatically or manually actuated valve which initiates the flow of water IV) Monitors As per IS/Ul or EqUivalent Standard II) Isolation Valves Gate or butterfly type isolatton valves made of Cast Steel haVing open/close Indication shall be used Other matenals such as cupro- nickel for saline/brackish waler may be used III) Hydrants Stand post Outlet valves Carbon Steel Gunmetal/ Alumlnum/ Stainless/ Steel/AI-Zn Alloy In case the system IS manually actuated, the Isolation valve shall be located outSIde the dyke for easy of access & operation II) Spray nozzles shall be directed radially to the tank at a distance not exceeding 06 m from the tank surface Only one type and size of spray nozzle shall be used in a particular facility ill) While calculating the water rates for spray applicalton for cases other than tanks/vessels, the area should be diVided Into suitable segments so that maximum water requirement can be opt,mlZed (Refer Annexure- V for typical calculations) v) Fire Hoses Reinforced Rubber lined Hose as per IS 636 (Type A)/Non-percolattng SynthetiC Hose (Type B)/Ul or Equivalent Standard (VI) Fire water mainS, hydrant & monitor sland posts, nsers of water spray system shall be painted With "Fire Red" paint as per of IS5 4.4 FOAM SYSTEMS 4.4.1 Types of Foam Foams are claSSified by producing action of generatton and expansion Foam concentrate to be used shall conform to IS4989 (part-III) 2006/Ul-162 or Equivalent
  • 13. Standard. Refer (Annexure - III) for bilef deScilptlon of foam 4.4.2 Types of Low Expansion Foam For combating large hydrocarbon fifes particularly In a contained area tlke storage tank, foam has proved useful for Its Inherent blanketing ability, heat resistance and secuilty against burn-back Aqueous FIlm Forming Foam (AFFF) compound IS technically supenor and compatible wllh other fife f/ghttng agents EffICient and effectIve foam delIvery system IS a vital tool for ItS usefulness In coniroiling the fife. The process of adding or tnJecttng the foam concentrate to water IS called proportioning The mixture of water and foam compound (foam solution) IS then mixed wIth alf In a foam maker for onward transmIsSion to burntng surface 4.4.3 CONVEYING SYSTEMS The system conSists of an adequate water supply, supply of foam concentrate, SUitable proportioning equipment. a proper piping system, foam makers and dIscharge deVices deSigned to adequately distribute the foam over the hazard. ConventIonal systems are of the open outlet type tn which foam dIscharges from all outlets at the same lIme, covenng the entlfe hazard within the confines of the system There are three types of systems i) Fixed Ii) Semi-Fixed ill) Mobile (i) Fixed Foam System Fixed foam conveying system compnses of fixed piping for water supply at adequate pressure, foam concentrate tank, eductor, suitable proportIoning equipment for draWing foam concentrate and making foam solutIon, fIxed piping system for onward conveYing to foam makers for making foam, vapor seal box and foam pourer (ii) Semi-Fixed Foam System Semi-fixed foam system gets supply of foam solution through the mobIle foam tender. A fixed piping system connected to foam makers cum vapor seal box in case of cone roof tanks and foam maker and foam pourers In the case of floattng roof tanks conveys foam to the surface of tank. (iii) Mobile System Mobile system Includes foam producing unit mounted on wheels whIch may be self propelled or towed by a vehicle These units supply foam through momtors/foam towers to the burning surface. (Iv) Sub-surface foam injection ThISsystem ISfor proteclton of fixed roof ~torage tanks It compnses of high back pressure foam generator connected through product lines or separate lines near the bottom of the tank. (v) Under the Seal Foam application ThiS is a system for floattng roof tank where the foam Iravels through a flexible pIpe inSide the tank upto the center of the tank roof and eXits at the seal rim of the floating roof
  • 14. precisely where the fire IS located thus rapidly flooding the seal rim area and qUickly extinguishing the fire spaced at the periphery of the tank and each discharge outlet shall be sized to deliver foam at approximately the same rate. 4.4.5 FIXED ROOF TANK PROTECTION IV) A mlmmum of two foam pourers shall be prOVided I) System be deSigned to create foam blanket on the burning surface In a reasonably short period Il) Foam shall be applied to the burning hazard continuously at a rate high enough to overcome the destructive effects of radiant heat Foam Pourer (Mln Nos) 2 3 4 5 6 8 10 Tank diameter (In M) Above 18 & up to 20 Above 20 & up to 25 Above 25 & up to 30 Above 30 & up to 35 Above 35 & up to 40 Above 40 & up to 45 Above 45 & IJPto 50 The estimation of number of foam discharge outlet IS based on pourer capacity of 1000 Ipm at a pressure of 7 kg/cm2 (g) upstream of eductor. This can be suitably adjusted for different pourer capacity in accordance with section 4.44 (ill). In case foam pourers are to be provided on tanks haVing diameter up to 18 m, min 2 nos foam pourers shall be provided. III) Tanks should be provided with foam discharge outlets/pourers as indicated below TANK For floating roof lank, foam shall be poured at the foam dam to blanket the roof seal Features of foam system for floating roof tank protection shall be as follows- III) Foam makers/foam pourers shall be located not more than 24 m apart on the shell perimeter based on 600 mm foam dam height 4.4.4 FLOATING ROOF PROTECTION Foam conveYing system shall have same features as of floating roof tank excepting that a vapor seal chamber IS reqUired before the foam discharge outlet 4.4.6 FLOATING CUM FIXED ROOF TANK PROTECTION Protection facilities shall be prOVided as reqUired for fixed roof tank. Features of the foam system for fixed roof protection shall be as follows 4.4.7 PROTECTION FOR DYKE AREA/SPILL FIRE FOAM APPLICATION RATE I) The vapor seal chamber shall be prOVided wllh an effective and durable seal. fragile under low pressure, to prevent entrance of vapour Into the foam conveying piping system 4.4.8 Portable streams fighting spills. momtors/foam hose shall be considered for fires In' dyked area and ii) Where two or more pourers are reqUired these shall be equally The minimum delivery rate for primary protection based on the assumption that all the foam
  • 15. 4.4.11 FOAM QUANTITY REQUIREMENT reaches the area being protected shall be as Indicated below For cone roof tanks containing liquid hydrocarbons, the foam solullon delivery rate shall be at least 5 Ipmlm2 of liqUid surface area of the tank to be protected For floating roof tanks containing liqUid hydrocarbons foam solution delivery rate shall be at least 12 Ipm/m2 of seal area With foam dam height of 600 mm of the tank to be protected In case of floating roof Sinking, the rate conSidered should be 8 1 Ipm/m2 of liqUid surface areas tn determining total solution flow reqUirements, potenllal foam losses from wind and other factors shall be considered I) II) The aggregate quantity of foam solution should be calculated as below Foam solution application at the rate of 5 Ipm/m2 for the liquid surface of the single largest cone roof tank or at the rate of 12 Ipm/m2 of seal area of the single largest floating roof tank whichever IShigher However, a foam solullon application rate of 81 Ipm/m2 of the liqUid surface of the largest floating roof tank for 65 minutes may be conSidered for a roof Sinking case For sample calculation, refer (Annexure-IV) Quantity of foam solullon requlfed should be calculated based on the following guidelines .- Two hose streams of foam each With a capadty of 1140 Ipm of foam solution. 4.4.9 DURATION OF FOAM DISCHARGE The equipment shall be capable of prOViding pnmary protecllon at the specified delivery rates for the follOWing minimum duration I) Tanks containing Class 'A' & 'B' 65 minutes il) Where the system's pnmary purpose is for spill fire protection 30 minutes 4.4.10 WATER FOR FOAM MAKING Water quantity required for making foam solullon depends on the percent concentration of foam compound Foams In normal use have a 3% to 6% proporflonlng ratio However, foam supplier data shall be used for determining water requiremenl III) Size of Terminal (InKl) For Installation having aggregate capacity of 1000 KL For Installation having aggregate capacIty up to 10,000 KL For Installation having aggregate capacity up to 25,000 KL For fnstarfation having aggregate capacity more than 25,000 KL Water/Foam Monitor (Nos.) Nil. 1 No of 1600lpm 1 No. of 2400 Ipm 2 Nos of 2400 Ipm. The aggregate quantity of foam solutions should be largest of 4411(i), 44.11(11) and 4.4 11 (III)
  • 16. as above for a minimum period of 65 minutes From this the quantity of foam based on 3% or 6% proportion should be calculated However, for installation having aggregate storage not more than 10,000 Kl, the foam concentrate storage shall be based on 4.4 l(i) only In case of AViation Fuelling Stations where aggregate product storage capacity IS less than 1000 KL, foam quantity for spill fire protection of 30 minutes shall be made 4.4.12 FOAM COMPOUND STORAGE Foam compound should be stored as explained In IS-49892006/Ul- 162 Type of foam compound used can be protein or fluro-proteln or AFFF Alcohol Resistant Foam shall be used for handling methanol/ ethanol or furfural fICes M,nimum 1 Kl of Alcohol Resistant Foam compound shall be maintained at the installation to handle methanol/ethanol or furfural fICe Shelf life of foam compound shall be taken from manufacturer's data Foam compound shall be tested periodically as per OEM gUidelines to ensure its quality and the deteriorated quantity replaced The deteriorated foam compound can be used for fire training purposes For details of type of tests & their periodicity, refer IS 4989 2006/UL- 162 or EqUivalent Standard Quantity of foam compound equal to 100% of requirement as calculated in 4 411 should be stored in the Installation, NOI. 2 ThiS quantity may be SUitably reduced if mutual aid for foam supply ISavailable 4.5 4.5.1 4.5.2 4.5.3 For sample calculation, refer (Annexure- IV) CLEAN AGENT FIRE PROTECTION SYSTEM General Clean agent fire extingUishing system as per NFPA-2001 (latest edllion) shall be conSidered for such protection system The Protection System broadly consists of container, feed Imes, ring mains/laterals, spray nozzles, Signaling equipment and cables, heat detection and activation devices The Protection System can detect, control & extmgulsh the fICeand also Simultaneously give audiO Visual ,ndicat,on on the control panel Recommended Use The system may be conSidered for protection of floating roof tanks, control rooms and computer rooms, QUANTITY AND STORAGE Each hazard area to be protected by the protection system shall have an Independent system The lime needed to obtam the gas for replacement to restore the systems shall be considered as a governmg factor In determlnmg the reserve supply needed, 100% standby containers shall be conSidered for each protected hazard Storage contamers shall be tocated as near as pOSSibleto hazard area but shall not be exposed to fire,
  • 17. Storage containers shall be carefully located so that they are not subjected to mechanical, chemical or other damage. All the components of the system shall be capable of withstanding heat of fire and severe weather conditions 4.5.4 FLOATING ROOF PROTECTION TANK Floaling roof tanks of 60 m and above diameter may be conSidered for proteclion by installing such systems 4.5.5 CONTROL ROOM AND COMPUTER ROOM PROTECTION Control rOom and computer room may be protected by Clean Agent Fire Extinguishing System. Floating roof tank may be protected by clean agent or foam flooding based fire extinguishing system for Its In bUilt detection, control and actuation mechanism If a rim seal fife occurs, "Its heat causes one or more spray nozzles to open and the gas IS applied on the surface of fire and alarm ISsounded This IS In addition to the fixed water spray system and Fixed foam system or SemHlxed foam system on all floating roof tanks stOring Class A & B petroleum. It ,s considered good practice to avoid unnecessary exposure to Clean Agent Fire Extinguishing System In order to minimiZe the exposure, persons should be evacuated from the areas before the system comes into operation.
  • 18. 4.6 FIRST AID FIRE FIGHTING EQUIPMENT 4.6.1 Portable Fire Extinguishers i) All fire extinguishers shall conform to respective IS/UL or EqUivalent codes, VIZ 10 Kg OCP Type (IS2171/Ul299), 45/6.8 Kg C02 Type (IS 2878/Ul 154) & 25/50/75 Kg OCP Type (IS 10658/UL 299) and bear ISI/Ul mark. BIS/UL or Equivalent certificates of all extJngUishers shall be maintained at the location II) While selecting the Extinguisher, due consideration should be given to the factors like flow rate, discharge lime and throw In line with IS2190 J UL711. ill) The Dry Chemical Powder used In extJngUisher and carbon diOXide gas used as expelling agent shall be as per relevant ISJUl or EqUivalent code iv) While o;electlng the dry chemical powder, due conSideration should be given to the typical properties VIZ Apparent DenSity (065 +/- 005), Fife Rating (144B), Thermal Gravimetric AnalysIs (WithdecompOSitionat around 250°C) and foam compatibility v) Siliconlsed Potassium bicarbonate OCP powder (IS 43082003) / Mono-ammonium phosphate based OCP powder (IS 14609) can also be used for recharging OCP fife extinguishers. vi) Spare C02 cartridges and OCP refdls as required based on thelf shelf life should be maintained However, minimum '0% of the total cllarge In the extinguishers should be maintained at the 10catJon. vII) Portable fire extinguIshers shall be located at convenient locations and are readily accessible and clearly VISibleI at all times VIII)The sand buckets shall have round bottom With bottom handle haVing 9 liter water capaCity conforming to IS2546 The sand stored In bucket shall be fine and free from 011, water or rubbish. ix) Rain protection of sUitable design should be provided for all extingUishers & sand buckets x) The maximum running distance to locate an extrngUisher shall not exceed 15 m xi) The extingUisher shall be Installed in such a way that ItStop surface IS not be more than 15m above the floor/ground level xII) The no. of extinguishers at various locations shall be provided as under Petroleum Depots, Terminals & Lube Oil Installations Sr, No. Type of Area , Scale of Portable Fire Extinguishers (I) lube Godown 1 No 10 Kg OCP extinguisher for every 200 m2 or min 2 Nos In each Godown whichever IShigher. (II) I Lube Filling Shed 1 No 10 Kg OCP extinguisher for 200 m2 Or mln 2 Nos In each Shed whichever IShigher (III) Storage of (Class NB) 1 No 10 Kg OCP extinguisher for 100 m2 or mln In packed containers and 2 Nos In each Storage Area whichever IShigher. stored In open/closed area (Iv) Pump House (Class NB) 1 No. 10 Kg OCP for 2 pumps. Up to 50 HP 1 No 10 Kg OCP for each pump Above 50-100 HP 2 Nos of 10 kg or 1 no. of 25 kg OCP for each Beyond 100 HP pump (v) Pump House (Class C) Up to 50 HP 1 no. 1OKgOCPfor every 4 pumps up to 50 HP Above 50 HP 2 nos 10 Kg OCP or 1x25 kg OCP for 4 pumps (VI) Tank Truck loading & 1 No. 10 Kg OCP extingUisher for each bay plus 1 unloading gantry for No. 75 Kg OCP extinguisher for each gantry POL/Special products
  • 19. (VII) Tank Wagon loading 1 No. 10 Kg OCP extinguisher for every 30 m of and unloading gantrylsldlng ISldlng plus 1 No 75 Kg OCP extinguisher for each gantry/siding (vIii) NG Tank Farm 2 Nos 10 Kg OCP extingUishers for each tank plus 4 Nos. 25 Kg OCP extingUishers for each Tank Farm pOSitioned at four corners in case of adjoining tank farms, the no. of 25 Kg extinguishers may be reduced by 2 nos. per tank farm (Ix) U/G Tank Farm 2 Nos 10 Kg OCP extingUisher for each Tank Farm (x) Other Pump Houses 1 No 10 Kg OCP extinguisher for every two pumps or mln 2 Nos 10 Kg OCP extinguisher for each Pump House whichever IS higher. (XI) Admin Building/Store 1 No 10 Kg OCP extinguisher tor every 200 m2 or House mln 2 Nos 10 Kg OCP extinguishers for each floor of BUlldlnglStore whichever is higher (xiI) OG Room 2 Nos e~ch 10 Kg OCP & 4.5 Kg CO2 extingUishers for each OG room. (XIII) Main SWitch Room/Sub- 1 No. 45 Kg C02 extinguisher for every 25 m2 Station plus 1 No 9 Uter sand bucket per transformer bay. (XIV) Computer Room/ Cabm 2 Nos of 2 Kg C02 or 2 Nos. of 2.5 Kg Clean Agent extingUisher per Computer Room and 1 No. 2 Kg CO2 or 1 No. 10 Kg Clean Agent extinguisher per cabin. (xv) Secuflty Cabin 1 No 10 Kg OCP extinguisher per cabin. (XVI) Canteen 1 No 10 Kg OCP extingUisher for 100 m2 (xvII) Workshop 1 No 10 Kg OCP extinguisher & 1 No 2 Kg CO2 extinguisher (XVIII) Laboratory 1 NO.1 0 Kg OCP extinguisher & 1 NO.4 5 Kg CO2 extinguisher (XIX) Oil Sample Storage Room 1 No. 10 Kg OCP extinguisher per 100 m2 or min. 1 no. 10 Kg extinguisher per room whichever is higher. (xx) Effluent Treatment'Plant 1 No 75 Kg. & 2 nos. 10 Kg OCP Extinguisher (XXI) Transformer 1 No 10 Kg. OCP extingUisher (XXii) UPS / Charger Room 1 No 2 Kg C02 extinguisher NOTE ;- ALL FIRE EXTINGUISHERS SHALL BEAR ISI OR EQUIVALENT MARK
  • 20. Pipeline Installations For pipeline Installations, the portable extinguisher shall be provided as per the above list (46 1) sUitably amended along with follOWing addillons- Sr. No. Type of Area Scale of Portable Fire Extinguishers (I) Main line pump shed 1 No 75 Kg DCP, 10 Kg DCP & 6.8 Kg CO2 (Engine/Motor Driven) extinguishers per two pumps up to a maximum of 4 nos (II) Booster Pump 1 No 10 Kg DCP per two pumps up to a maximum . of 3 nos and 1 No 6.8 Kg C02 extinguIsher (III) , Sump Pump, 1 No 10 Kg DCP extinguisher Transmix Pump & Oil Water Separator Pump (Iv) Scrapper Barrel 1 NO.1 0 Kg DCP extinguisher (v) Control Room 2 Nos 2 5 Kg Clean Agent and 1 No 4.5 Kg CO2 extinguisher (VI) UHF / RadiO Room 2 Nos 2 5 Kg Clean Agent and 1 No 45 Kg CO2 extinguisher (vII) Meter Prover/Separator 1 No 10 Kg DCP extinguisher Filter (VIII) Repeater Station . 1 No 10 Kg OCP & 1 No 2 Kg C02 extinguisher. (IX) Mainline Emergency 4 Nos. 10 Kg DCP & 2 Nos. Equipment Centre 2 Kg C02 extinguishers (x) Air Compressor 1 No 2 Kg C02 & 1 No 5 Kg DCP extingUisher 4.6.2 Wheeled Fire Fighting Equipment For Installations having tanks of diameter large than 9 m follOWing fire fightlngequipments shall be provlded- Size of Terminal (In KL) Water/Foam Monitor (Nos.) For installation having aggregate Nil capacity of 1000 KL For installation having aggregate 1 No of 1600 Ipm capacity up to 10,000 KL For InstallatIOn having aggregate 1 No. of 2400 Ipm capacity up to 25,000 KL For Installation having aggregate 2 Nos of 2400lpm capacity more than 25,000 KL Foam compound trolley 200/210 liters shall be prOVided as Under- Tank diameter (In m) Water/Foam Monitor (Nos.) UP to 24 m 1 No 24 m - 30 m 2 Nos Above 30 m 3 Nos
  • 21. 4.6.3 HOSES, NOZZLES & ACCESSORIES (i) Hoses i) Reinforced rubber hned canvas or Non- percolat'ng synthetic fire hoses conforming to IS- 636/ UL 19 (Type A or B) shall be provided il) The length and diameter of the hoses shall be 15 m and 63 mm respectively fltled with Instantaneous type male & female couplings of malenal as speCIfied In IS 636/UL 19 III) The number of hoses stored In an oil Installalion shall be 30% of the number of hydrant outlets. The minimum No of hoses stored. however. shall not be less than 10 IV)The hoses shall be stored at convenient and easily acceSSible location In the 011 ,nstallation (Iii Nozzles In addition to the Jet nozzle provided In each hose box, there shall be at least two nozzles In each category VIZ. Jet nozzle with branch pipe. Fog nozzle, Universal nozzle. Foam branch pipe and Water curtain nozzle as per relevant IS/UL Codes maintained at the location. (iii) Accessories The following Personal Protective Equipment, First Aid EqUipment & Safety Instrument shall be prOVided as indicated against each Item Sand drum with scoop. 4 Nos Safety helmet. 1 No. per person Stretcher with blanket 2 Nos First Aid box: 1 No Rubber hand glove' 2 Pairs Explosimeter . 1 No. Fire proximity SUit 1 Suit Resuscitator: 1 No Electrical siren (3 Km range) 1 No Hand operated siren One each at Admn Bldg. Laboratory. Planning room, Control room, T/L Loadlng/Unloading Facility, TfW Loadlng/Unloading Facility, Tank Farm, FW Pump House & Product Pump House (s). Water Jel blanket: 1 No. Red & Green flag for fire drill. 2 Nos. in each color SCBA Set (30 minute capacity) 1 Set Withspare cylinder. PA System - 1 No Hose box Between two hydrant points Frre hose 2 Nos per hose box Jet nozzle 1 No In each hose box The above gUidelines are mimmum reqUirement of each Item and can be Increased depending on the scale of operations/slze of installation or requrrement of Local Statutory Bodles/State Govt A trolley containing Fire Proxlmily SUIt,B A. Set. Water Jel Blanket, Resuscitator, First A,d Box, Stretcher with blanket. Spare fire hoses, SpeCial purpose nozzles, Foam branch pipes, Exploslmeter. P A System shall be readily available at the location and POSitioned to have easy access to It dunng emergency situation 4.7 MOBILE FIRE FIGHTING EQUIPMENT Mobile fire fighting equipment include Foam trolleys, Portable water-cum-foam montlors, etc. In view of comprehensive Fixed and First Aid Fire proteclion equipment recommended in the Standard. provIsion of Mobile fire fighting equipments in the installation is not conSidered necessary. However, the requirement of such equipment may be reViewed keeping In mind the size, nature and location of the Installation.
  • 22. 5.0 5.1 FIRE ALARM/COMMUNICATION SYSTEM FIRE ALARM SYSTEM iii) Wherever possible hot line connection between City Fire Brigade & nearby Industnes shall be provided for major installation on need baSIS I) Hand operated sirens shall be provided at strategic locations and clearly marked in the Installation II) Electnc fire siren shall be Installed at sUitable location with operating SWitch located near the risk area at a safe, Identifiable and easily accessible place III) Electnc fire sICenshall be audible to the farthest distance In the installation and also In the surrounding area up to 1 km from the penphery of the Installalion IV) Electnc fire sirens shall be connected to feeder to ensure continuous power supply dunng emergency shut down v) The tone of fire siren shall be different from shift siren VI) The following fire siren codes should be followed for different emergency SituatIons • FIRE' For fire Situation, the siren shall be walling sound for 2 minutes • DISASTER For disaster situation. the siren shall be wailing sound for 2 minutes repeated thnce with a gap of 10 seconds • ALL CLEAR For all clear situation, the Siren shall be straight run sound for 2 minutes • TEST'SIREN For testing. the siren shall be straight run sound for 2 minutes 5.2 COMMUNICA nON SYSTEM I) Communication system like Telephone, Public Address System, etc should be prOVided In non- hazardous areas of the Instillation H) In hazardous areas, flame- proof/lntnnslcally safe Paging Syslem. Walkie-talkie system or VHF Set shall be prOVided IV) Installation shall have a 'Mutual Aid' arrangement With nearby Industnes to pool in their resources during emergency 6.0 FIRE SAFETY ORGANISATION/ TRAINING 6,1 ORGANISATION A well defined comprehensive On-site Emergency Plan as per OISO-GDN- 168 shall be drawn, 6,2 TRAINING I) The fire fighling training shall be compulsory for all officers, clencals, operators. security, TfT drivers & contract workmen who are likely to be present In the Installation and record maintained II) Training on fire & safety aspects to all concerned shall be Imparted as per 0150-5TO-154 ill) Every employee or authorized person of contractor working in the Installation shall be made familiarized With fire siren codes and know the location of fire siren operating SWitch nearest to his place of work. IV) Instruclions on the aclion to be taken In the event fire should be pasted at each sICen point and familiarity With these instruclions ensured and recorded. v) Monthly fire drills shall be conducted regularly With full Involvement of all employees of the installation. VI) Mock disaster dnlls shall be conducted penodically as per local statutory reqUirements Vii) The post drill analysis should be camed out & discussed emphasJzlng areas of Improvements. Viii) The record of such drills should be maintained at the location
  • 23. 7.0 FIRE EMERGENCY MANUAL I) Each Installation shall prepare a comprehensive fire emergency manual covenng all emergency scenanos detailing the actions to be taken In the event of fire emergency for effective handilng II) The key action pOints of this manual shall be displayed at strategic locations In the Installation for ready reference 8.0 FIRE PROTECTION SYSTEM, INSPECTION AND TESTING I) The fICeprotection equipment shall be kept In good working condition all the time II) The fire protection system shall be penodically tested for proper functioning and logged for record and correctIve actions III) Inspection & maintenance of fire fighting equipment shall be done in accordance with OISD-STD-142 IV) In addition to routine daily checks/maintenance. the following periodic Inspection/testing of fire fighting eqUipment shall be ensured v) One officer shall be designated and made responsible for Inspectlo,,, maintenance & testing of fICe protection system VI) The responSibilities of each officer shall be clearly defined. explained and communicated to all concerned In writing for role clanty 8.1 FIRE WATER PUMPS I) Every pump shall be test run for at least half an hour or as per OEM gUidelines. whichever IShigher twice a week at the rated head & flow Ii) Each pump shall be checked. tested and its shut-off pressure observed once In a month IIi) Each pump shall be checked & tested for its performance once In six month by opening requICed nos of hydrants/monitors depending on the capacity of the pump to venfy that the discharge pressure. flow & motor load are In conformity WIth the deSign parameters IV) Each pump shall be test run continuously for 4 hours at Its rated head & flow uSing Circulation line of fICe water storage tanks and observations logged once a year. v) The testing of standby Jockeypump. If provided shall be checked weekly Frequent starts & stops of the pump indicates that there are water leaks In the system which should be attended to promptly 8.2 FIRE WATER RING MAINS (i) The ring main shall be checked for leaks once In a year by operatmg one or more pumps & keeping the hydrant points closed to get the maximum pressure (II) The nng maIns. hydrant. monitor & water spray header valves shall be visually Inspected for any missing accessOries. defects. damage and corrosion every month and records maintained (ill) All valves on the ring mains. hydrants. monitors & water spray headers shall be checked for leaks, smooth operation and lubncated once In a month 8.3 FIRE WATER SPRAY SYSTEM I) Water spray system on storage tanks shall be tested lor spray density. flow rate & response time and venfled With the performance test certificate proVided by manufacturer once In six months II) Spray nozzles shall be inspected for proper orientation, corrosion and cleaned If necessary al least once a year iil) The strainers provided In the water spray system shall be cleaned once In a quarter and records maintained 8.4 FIXED/SEMI FIXED FOAM SYSTEM Fixed/Semi fixed foam system on storage tanks should be tested once in
  • 24. six months. This shall Include the testing of foam makerlchamber 9,0 REFERENCES 1) NFPA 11 - Standard on Low Expansion Foam Systems. 2) NFPA 13 - Standard on Installation of Spnnkler System. on Spray Standard of Water 3) NFPA 15 - Installation System. The foam chamber should be designed sUitably to facilitate of foam discharge outside the cone roof tank After testmg foam system, plpmg should be flushed with water. CLEAN AGENT SYSTEM 8,5 Clean agent fire extmgulshlng system should be checked as under- I) Agent quantity and pressure of refillable containers shall be checked once every six month. It) The complete system should be mspected for proper operation once every year (Refer latest NFPA 2001(2004 Edition) for details of mspectlon of vanous systems) 4) NFPA 20 Standard on Installation 01 Centnfugal Fife Pumps. 5) NFPA - 2001 (Edition 2004) Standard on Ctean Agent Fife ExtingUishing System 6) No 72-289 - French Regulation for Hydrocarbon Depots 8,6 HOSES 10) The Petroleum Rules - 2002, Fire hoses shall be hydraulically tested once in six months to a water pressure as specified In relevant ISIUUEqulvalent codes 11) Model Code of Safe Practices The Institute of Petroleum (U K.) 15) International Safe Practices of Oil Industry 8,7 COMMUNICATION SYSTEM Electnc and hand operated fire sirens should be tested for their maximum audible range once a week. 16) 15-3844 Code of Practice on Installation of Internal Hydrants In Multistory Building 0ISO-STO-142 Standard on Inspection of Fire Fighting EqUIpment & Systems 8,8 FIRE WATER TANK/RESERVOIR i) Above ground fire water tanks should be Inspected externally & Internally as per OISD-STD-129. il) The water of reservoir shall be cleaned once In 6 months or as & when required to keep It free from foreign matenal, fungus & vegetation 8,9 FIRE EXTINGUISHERS 17) 18) 19) 0ISO-GON-115 Fife Fightmg Appliances In Industry 0ISO-STD-154 Safety Aspects Tralnmg GUIdelines on EqUipment & Petroleum Standard on in Functional Inspection, testing frequency and procedure should be in line With OISD-STD-142
  • 25. 20) Ozone Depletion Substances Regulation & Control Rules • 2000 Ministry of Environment & Forests, Government of India 21) Kyoto Protocol 22) IS,15683,' Standard on Portable Fife ExtingUishers Performance & Construction SpeCIficatIOns 23) IS,4308 Standard on Dry Chemical Powder for Fighting 8 & C Class Fifes SpeCIfications 24) IS, 14609 Standard on Dry Chemical Powder for Fighting A.8, C Class Fires SpeCifications 25) IS,4989 Standard on Foam Concentrate for Producing Mechanical Foam for Fire Fighting Flammable Liquid Fires , Specifications,
  • 26. ANNEXURE-I SAMPLE CALCULATION OF FIRE WATER FLOW RATE FOR STORAGE TANKS 1. DESIGN BASIS The fire water system in an installation shall be designed to meet the fire water now reqUIrement of fighting single largest fire scenariO 2. FIRE WATER DEMAND FOR SINGLE LARGEST FIRE Consider various areas under fire and calculate fire water demand for each area based on design basIs 2.1 FIRE WATER FLOW RATE FOR FLOATING ROOF TANK PROTECTION Data Total storage capacJty In one dyke are" = No. of tanks = Capacity of each tank = Diameter of each tank = Height of each tank = a) Cooling water flow rate Cooling water required for tank on fire Cooling water rate = Cooling water reqUfred = = = 32,000 m 3 2 16,000 m 3 40 m 14.4 m 3 Ipm/m2 of tank area for tank on fire 3 142 x 40 m x 144 m x 3 Ipmlm' 5426 Ipm 5426 x 60 m'lhr = 326 m'/hr 1000 Assuming that second tank IS located within the tank dyke at a distance more than 30 m from the tanks shell Therefore, m such case cOolmgreqUJred ISat the rate of 1 Ipmlm' of tank shell area Cooling water required for tank falling beyond (R+30) from centre of tank on fire , Cooling water rate = 1 Ipmlm of tank area Cooling water reqUfred = 3 142 x 40 m x 14.4 m x 11pmlm' = 18091pm = 1809 x 60 m'lhr = 109 m'/hr. 1000 b} Foam water flow rate Foam solution application rate Foam solution required Foam water required = = = = 12 Ipm/m' of rim seal area of tank 3.142 x 40 m x 0 8 m x 12 Ipm/m' 097x12121pm = 11761pm 1176 x 60 m'lhr = 71 m'lhr. 1000
  • 27. ANNEXURE- J SAMPLE CALCULATION OF FIRE WATER FLOW RATE FOR STORAGE TANKS 1. DESIGN BASIS The fire water system in an installation shall be deSigned to meet the fire water fiow requirement of fighting single largest fire scenario 2. FIRE WATER DEMAND FOR SINGLE LARGEST FIRE Consider various areas under fire and calculate fire water demand for each area based on design baSIS. 2.1 FIRE WATER FLOW RATE FOR FLOATING ROOF TANK PROTECTION Data Total storage capacity in one dyke ares = No. of tanks = Capacity of each tank = Diameter of each tank = Height of each tank = a) Cooling water flow rate Cooling water required for tank on fire Cooling water rate = Cooling water reqUired = = = 32,000 m' 2 16,000 m' 40m 144m 3 Ipmtm' of tank area for tank on fire 3.142 x 40 m x 14.4 m x 3 Ipm/m' 5426 Ipm 5426 x 60 m'/hr = 326 m'thr. 1000 Assuming that second tank IS located within the tank dyke at a distance more than 30 m from the tanks shell. Therefore, In such case cooling reqUIred ISat the rate of 1 Ipm/m' of tank shell area Cooling water required for tank falling beyond (R+30) from centre of tank on fire Cooling water rate = 1 Ipmtm' of tank area Cooling water required = 3142 x 40 m x 144 m x 1lpm/m'. = 18091pm = 1809 x 60 m'/hr = 109 m'/hr. 1000 b) Foam water flow rate Foam solution application rate Foam solullon required Foam water required = = = = 12 Ipm/m' of rim seal area of tank 3.142 x 40 m x 08 m x 12lpm/m'. 097 x 12121pm = 11761pm. 1176 x 60 m'thr = 71 m'/hr. 1000
  • 28. c) Tolal waler flow rale Tank cooling Foam solution application Total Say = = = = 326 + 109 = 435m'/hr 71 m'/hr. 506 m'/hr 510 m'/hr. 2.2 FIRE WATER FLOW RATE FOR CONE ROOF TANK PROTECTION Data Total storage capacity in one dyke area = No of tanks = Capacity of each tank = Diameter of each tank = Height of each tank = a) Cooling water flow rate Cooling water required for tank on fire Cooling water rate = Cooling water required = = = 50.000 m' 4 12,500 m'. 375 m 12 m 3 Ipm/m' of tank area for tank on fire 3142 x 37.5 m x 12 m x 3/pm/m' 4242 Ipm. 4242 x 60 m'/hr = 255 m'/hr 1000 Cooling water required for tanks falling within (R+30) from centre of lank on fire Cooling water rate = 3 Ipm/m' of tank area Cooling water required = 3.142 x 375 m x 12 m x 3 Ipm/m' x 3 = 127261pm = 12726 x 60 m'/hr = 764 m'/hr, 1000 Total cooling water required = 254 + 762 = 1019 m3/hr. b) Foam water flow rate Foam solution application rate Foam solution reqUired Foam water reqUired c) Total waler flow rate Tank cooling Foam solution application Total = = = = = = = = 5 Ipm/m' of liqUid surface area 3142 x (1875 m)' x 5Ipm/m'. 55231pm. 0.97 x 5523 Ipm = 5357 Ipm. 5357 x 60 m'/hr = 321 m'/hr. 1000 1019 m'/hr 321 m'/hr. 1340 m'/hr. 2.3 FIRE WATER FLOW RATE FOR COOLING POL TANK WAGON LOADING GANTRY (Ref Annex - II) : Total water requirement = 918 m3/hr.
  • 29. 2.4 FIRE WATER FLOW RATE FOR SUPPLEMENTARY HOSE STREAMS Water for 4 single hydrant streams Water for 1 monitor stream Total water reqUirement = = = 4 x 36 = 144 m3/hr 144 m3/hr 288 m3 / hr. 3.0 TOTAL DESIGN FIRE WATER FLOW RATE Total design fire water flow rate would be the largest of rlre water flow rates calculated as per 21, 22, 2 3 and 2.4 above Design fJre water rate = 1340 m3/hr. _m_) 0 X 0 ( _m_
  • 30. ANNEXURE-II SAMPLE CALCULATION OF FIRE WATER FLOW RATE FOR POL TANK WAGON LOADING GANTRY a) Data Total No. of loading points 'Conslder 20 loading pOints on each side Length of Rail Gantry Width of tank wagon gantry Cooling two spur other distance b) Cooling water flow rate = = = = 72 Conventional or 48 BTPN 700 m 12 m D,v,de total area of gantry Into 24 segments, each segment admeasuring 292m X 12 m and consider 3 segments operating at a time Water rate requrred Total water requrrement (including hydrant/monitors) = = = = _.u.) 0 x 0 (._.u 3 x 29 2 x 12 x 10 630 cum/hr 630 cum/hr + 288 cum 918 cum/hr
  • 31. ANNEXURE-II' BRIEF DESCRIPTION OF FIRE FIGHTING FOAM 1.0 FIRE FIGHTING FOAM Fire flghling foam is a homogeneous mass of tiny air or gas filled bubble of low specific gravity, which when applied In correct manner and In sufficient quanlity, forms a compact fluid and stable blanket which IScapable of floating on the surface of flammable liquids and preventmg atmospheric air from reachmg the liqUid 2.0 TYPES OF FOAM COMPOUND Two Types of foams are used for fighting liquid fires 2.1 CHEMICAL FOAM When two or more chemicals are added the foam generates due to chemical reaclion The most common Ingredlerts used for chemical foam are sodium bicarbonate and aluminum sulphate With slabllizer. The chemical foam IS generally used In Fire extinguishers 2.2 MECHANICAL FOAM It IS produced by mechanically miXing a gas or alf to a solution of foam compound (concentrate) in water. Vanous types of foam concentrates are used for generating foam. depending on the requlfement and sUitability E~ch concentrate has Its own advantage and limitations. The bnef descnptlon of foam concentrates is given below 3.0 MECHANICAL FOAM COMPOUND Mechanical foam compound may be classified In to 3 categories based on It'Sexpansion ratIo 3.1 LOW EXPANSION FOAM Foam expansion ratio may be upto 50 to 1, but usually between 5 1 to 151 as typically produced by self aspirating foam branch pipes The low expansion foam contains more water and has better resistant to fife It ISsUitable for hydrocarbon liqUid fires and ISwidely used In 011 refinery, 011 platforms, petrochemical and other chemicallndustnes 3.2 MEDIUM EXPANSION FOAM: Foam expansion ratio vary from 51 1 to 500 1 as typically produced by self asplfaling foam branch pipes With nets ThiS foam has limited use In controlling hydrocarbon liquid fife because of it's limitations w r. t poor cooilng. poor resistant to hot surface/radiant heat etc
  • 32. 3.4 HIGH EXPANSION FOAM Foam expansion ratio vary from 5011 to 15001, usually between 7501 to 1000:1 as typically produced by foam generators with air fans This foam has also very limited use In controlling hydrocarbon liqUid fire because of its limitations W r. t poor cooling. poor resistant to hot surface/radiant heat etc It IS used for protection of hydrocarbon gases stored under cryogenic conditions and for warehouse protection 4.0 TYPES OF LOW EXPANSION FOAM 4.1 PROTEIN BASE FOAM The foam concentrate IS prepared from hydrolyzed protein either from animals or vegetable source The SUitable stabilizer and preservatives are also added The concentrate forms a thick foam blanket and IS SUitable for hydrocarbon liquid fires, but not on water miSCible liqUids The effectiveness of foam IS not very good on deep pools or low flash pOint fuels which have had lengthy preburn time unless applied very gently to the surface The concentrate IS available for induction rate of 3 to 6%. The shelf life of concentrate is 2 years 4.2 FlUORO PROTEIN FOAM This is similar to protein base foam With fluro-chemlcal which makes It more effective than protein base foam. The concentrate forms a thick foam blanket and IS SUitable for hydrocarbon liqUid fires. but not on water miscible liqUids The foam IS very effective on deep pools of low Nash point fuels which have had lengthy pre burn time. The concentrate is available for induction rate of 3 to 6% and the shelf life ISSimilar to that of protein base foam. 4.3 AQUEOUS FILM FORMING FOAM (AFFF) The foam concentrate mainly consists of fluoro carbon surfactants, foaming agent and stabilizer. ThiS can be used with fresh water as well as with sea water It produces very fluid foam, which flows freely on liquid surface The aqueous film produced suppresses the liquid vapour qUickly The foam has qUick fire knock down property and is SUitable for liqUid hydrocarbon fifes As the foam has poor drainage rate, the effectiveness is limited on deep pool flies of low flash pOint fuels which have lengthy pre burn time The concentrate is available for Induction rate of 3 to 6% and the shelf life ISmore than 10 years. This can also be used With non aspirating type nozzles.
  • 33. 4.4 MULTIPURPOSE AFFF Multipurpose AFFF concentrate IS synthetic, foaming liquid designed specially for fire protection of water soluble solvents and water Insoluble hydrocarbon liqUids. ThiS can be used either with fresh water of sea water. When applied It forms foam with a cohesive polymeric layer on liquid surface, which suppresses the vapour and extingUishes the fire. The foam is also SUitable for deep pool fires because of superior drainage rate and more resistive to hot fuels/radiant heat The 3% induction rate IS SUitable for liqUid hydrocarbon fires and 5% for water miSCible solvents. The shelf life of concentrate is not less than 10 years ThiS can also be used with non aspirating type nozzles 4,5 FILM FORMING FLOURO PROTEIN (FFFP) FFFP combines the rapid fire knock down quality of conventional film forming AFFF with the high level of post fire securlly and burn back resistance of flouro proleln foam The concentrate can either be used with fresh water or sea water The foam ISsuitable for hydrocarbon liquid fires including deep pool fires of low flash point fuels which have had lengthy pre burn time. The concentrate ISavailable for Induction rate of 3 to 6% and the shelf life is not less than 5 years. This can also be used with non aspirating type nozzles 5,0 TYPES OF MEDIUM AND HIGH EXPANSION FOAM SynthetiC foam concentrate IS used with SUitable devices to produce medium and high expansion foams ThiS can be used on hydrocarbon fuels with low boiling pOint The. foam IS very light In weight and gives poor cooling effect In comparison to low expansion foams. The foam ISsusceptible 10 easy break down by hot fuel layers and radiant heat The Induction rate In water may vary from 15 to 3% Many of the low expansion foam concentrate can also be used With sl'ltable devices to produce medium / high expansion foam. m __ ) OxO( __m
  • 34. ANNEXURE IV TYPICAL EXAMPLE OF FIRE CASE IN A LARGE FLOATING ROOF TANK AFTER SINKING OF FLOATING ROOF Example for Calculation of Foam ReqUIrement for Floating Tank with Portable Monitors DATA Diameter of Tank Type of Roof Foam APplication Rate Foam Solution ReqUlCement = = = 40 m Floatmg Roof 8 11pm (as per NEPA-11) II x 40 x 40 x 8 114 = 1017361pm = 6104 m'/hr Say = 610 m' /hr. This much quantities has to be thrown over to sunken roof area with the help of external long range high volume monitors from the road side periphery of the tank farm The same may be achieved by 2 nos, of 1000 gpm such monitors, In deSign rate calculation m Ann 1, sinking of floating roof has not been considered, however, Installation may conSider sIzing the water network around tank farms to take up such load sO than long range monitors can be fed from this network by diverting other water available In installation to tank farms In such emergency" Foam Compound Requirement = Say = 101736 x 3/100 305 2 Ipm 305 Ipm Foam Compound ReqUirement for 65 minutes with 3% concentration = Say = 305 x 65 19825 L 20,000 L •• If two major fife occurs In an Installation with roof sinking case as one of them n_n) OxO(n __-