Improving Reliability on Mixed Overhead
and Underground Distribution Feeders
M. MEISINGER, M. BISHOP, S. WILLIAMS
S&C Electric Company
USA
SUMMARY
Many utility companies are converting overhead (OH) main line feeder sections to underground
(UG) to improve reliability, system resiliency, or other local customer demands. A Hybrid
distribution feeder is one with a mixture of OH and UG main line sections. Conventional protection
philosophies for hybrid feeders normally result in lower overall feeder reliability. This paper will
examine an example feeder to demonstrate the impact of protection and isolation system
improvements on predicted reliability for Hybrid distribution feeders.
KEYWORDS
FLISR, SAIFI, SAIDI, MAIFI, Distribution Feeder Reliability Improvement
21, rue d’Artois, F-75008 PARIS CIGRE US National Committee
http : //www.cigre.org 2019 Grid of the Future Symposium
2
INTRODUCTION
Distribution system overcurrent devices have been applied by electric company distribution
engineers to detect and clear system faults to minimize the probability of damage to equipment
due to sustained faults. Inspection and maintenance of lines is performed to minimize the number
of faults that are experienced on the feeder. Despite these efforts, the exposure to weather, animals,
vegetation, vehicles and other hazards results in the expectation that some number of system faults
will still be experienced. To mitigate the extent of outages, equipment is placed on the feeder to
identify fault conditions and quickly isolate faulted sections of the distribution feeder.
In addition to recognizing and clearing overcurrent conditions caused by fault events, the same
equipment elements are used in an overall system that performs Fault Location, Isolation, and
Service Restoration (FLISR). These systems apply greater levels of system automation and
integration designed to reduce outage times for customers that are somewhat remote from the
actual faulted section of the feeder. The demand for these types of systems increases with customer
expectations for high reliability.
Many electric utilities focus reliability improvement initiatives around maintenance activities,
such as tree trimming, aimed at reducing the number of fault events. These activities should result
in a lower fault rate for the feeder section as measured by faults per mile per year. It can be shown
that investments in sectionalizing and automation systems, such as the design of overcurrent
protection systems to better sectionalize the system after a fault, also have major reliability
improvement potential for any given fault rate. If fault records indicate that many events were tree
related, then increased vegetation management expense may be justified. However, in many utility
situations where fault records exist, “unknown” may be the largest category of fault causes listed.
In areas where high fault rates have been experienced, or areas where customer demands for
various reasons warrant the investment, utilities are converting sections of the distribution feeder
from overhead (OH) to underground (UG) construction. The reduced exposure to weather,
animals, and other physical hazards normally results in a lower fault incidence rate for UG
construction. Since cost is higher for UG construction, the application along the feeder may only
be in limited areas, resulting in a mix of OH and UG main line feeder miles. This presents
challenges to conventional overcurrent protection philosophies that can result in lower overall
feeder reliability. This paper will examine the application using an example feeder and
demonstrate that new protection equipment technology can achieve the improvement needed to
capture the intended reliability improvement
FEEDER OVERCURRENT PROTECTION STRATEGIES
Distribution system overcurrent conditions are detected and interrupted when needed using a
variety of devices that include fuses, reclosing devices (single phase or three-phase), and circuit
breakers in substations. The devices are designed to operate in a coordinated fashion to isolate the
smallest part of the system possible for each fault event. Coordination studies are completed by
system protection engineers for specific feeders with knowledge of system short circuit currents
at points on the feeder. Protection philosophies are followed according to individual company
developed standards, but the overall final design includes engineering judgements on the part of
the distribution protection engineer. The application of the protection systems also impacts the
sectionalizing of the feeder that results in accumulated outage numbers used in calculating
reliability indices for the feeder and overall system.
Electric distribution companies utilize strategies to recover from the fault events experienced on
the distribution feeders, since faults may be transient or persistent. A transient fault is one where
fast interruption of the fault current prevents any damage to line conductors or equipment that
would require a repair crew and the circuit can be automatically reclosed after a few seconds to
3
restore service. A persistent fault cannot be re-energized without a service crew performing some
equipment or line repair or replacement. The mix of transient and persistent faults on the feeder
impacts the selection of overcurrent protection system philosophy regarding equipment interaction
as a system.
When applying interrupting devices that can be reclosed along the main line and fuses at lateral
connections to the main line, a choice is made between two overcurrent protection methodologies
called “fuse saving” and “fuse sacrifice”. Fuse saving utilizes a fast-trip-and-reclose scheme to
clear transient faults on the laterals before the fuse has operated. This causes a momentary outage
to all customers located downstream of the reclosing device but overall reduces sustained outages.
This scheme is often used in rural areas or when repair time is longer due to the time for crews to
get to the fuse location. A fuse sacrifice philosophy can reduce momentary outages by eliminating
fast tripping on relayed circuit breakers and downstream overcurrent devices. The elimination of
fuse saving may reduce momentary operations, but it increases the overall sustained outage
minutes, since transient faults on fused laterals result in a fuse operation and sustained outage. This
scheme is often used in urban areas where crews can quickly arrive to the scene and make repairs
and/or replace the fuse link. Intelligent fuse saving systems technologies can now be applied that
blend the best of both techniques to further enhance reliability. Intelligent fuse saving prevents a
fuse saving attempt when a fault interrupter’s fault clearing time for a measured fault current
cannot prevent fuse operation. This is in contrast to conventional fuse saving schemes that often
result in the fuse and the fault interrupter both operating.
Reliability rates can also be improved by employing automation to minimize outages resulting
from either transient or persistent faults. It can be shown that sectionalizing of a radial feeder has
an improvement limit and diminishing returns may not produce the desired reliability level from
sectionalizing alone. Once this point is reached further improvement can be realized by
sectionalizing to minimize the faulted portion of the system with feeder ties to alternate sources,
such as neighboring feeders.
The general approach used to design higher reliability distribution service on radial feeders
includes the following initiatives:
1. Use automatic reclosing to eliminate outages caused by transient faults on OH sections.
General industry practice avoids reclosing on UG systems since cable faults are normally
persistent. Therefore, hybrid main line distribution feeders present a protection challenge with
the mix of UG and OH construction. However, a low-energy fault testing fault interrupter can
be used to avoid reclosing into faults and further stress system components for all forms of
feeder construction.
2. Use automatic reclosing on lateral circuits to eliminate momentary operations of main line
devices for faults on the lateral circuits. UG and hybrid circuits essentially preclude the fuse
saving philosophy. The steps taken in this example feeder will show the benefits of re-
introducing reclosing and fuse-saving using a cutout-mounted recloser at the lateral level.
3. Sectionalize the system to limit the number of customers affected by a persistent fault and
reduce the time necessary to locate a fault. Smart switches can accomplish this, but fault
interrupting devices can further limit the affected area.
4. Build for improved reliability by including bridging points to alternate sources that are
managed by a distributed intelligence automation system that reconfigures the system
following an outage based on monitored system conditions.
5. Reduce device hazard rates. This can be driven by a root cause analysis to determine
maintenance levels required to drive feeder fault rate to target levels.
4
The subsequent sections examine a typical radial utility distribution feeder with the objective being
improvement of reliability indices through selection and application of appropriate fault
interrupting equipment. Calculations are performed for each equipment addition to demonstrate
the improvement that each step provides in the reliability indices.
EXAMPLE FEEDER EXAMINATION FOR RELIABILITY IMPROVEMENT
Figure 1 shows a simplified one-line diagram of a distribution feeder served by a substation bus
located at the left side of the figure. The main line is 5.9 miles in length and provides radial service
to customers that are served on laterals at the end of the feeder. There is a short section of main
line UG construction shown in red (270 feet). The remainder of the main line is OH. Total circuit
miles for all 3-phase, 2-phase, and 1-phase lines is 20.18 miles of OH and 1.81 miles of UG
construction.
The 12.47 kV feeder being analyzed is a
problem feeder that is primarily OH
construction with a customer count of
approximately 1300 and reliability that is
not near company targets. Outage data was
broken into a variety of categories with the
largest numbers due to lightning and
vegetation. The main line feeder is radial as
shown in Figure 1 with many laterals
connected to the main line. Total feeder
load is approximately 9 MVA.
The base case reliability calculations used fuse saving on the main line feeder recloser and three-
phase lateral recloser near the substation. Fuse saving was disabled on the substation circuit
breaker to help reduce momentary interruptions for all customers on the feeder. Most laterals are
fused at the connection to the main line and there are several long laterals that have additional
fuses placed downline in series. The following are the base case reliability indices for the feeder:
CIRCUIT CHANGES IMPLEMENTED TO IMPROVE RELIABILITY
Next, improvements to the feeder construction and the protection system design will be applied
and the resulting changes in the reliability indices calculated. The following sections summarize
the changes to the circuit.
Convert selected sections of the Main line from OH to UG and add selected lateral circuit devices
The existing sections of the main line are predominantly OH. There are many utility companies
that are converting sections of OH to UG, either to meet local demands for aesthetic improvements
or to improve the overall feeder reliability. In this feeder example three sections of the main line
have been converted to UG cable. They are shown in Figure 2 as sections shown in red. The end
of line UG section is 5500 ft, the midline UG section is 2600 ft. and the section near the substation
is 2200 ft. The underground part of the main line is 38% of the feeder.
A protection system upgrade to this feeder shown in Figure 2 includes the replacement of fuses at
5 feeder lateral locations using cutout-mounted reclosers (TS2). This type of device can sense
overcurrent conditions, trip and then reclose to clear transient faults. It can also be configured to
provide the fuse saving strategy for sections of the lateral that have fusing which further
sectionalizes the lateral for persistent faults. The five lateral locations selected were the longer
2500ft
ExistingRecloser O
Substation
End of Mainline
Figure 1. One-line diagram of example distribution
feeder used for analysis.
5
lateral circuits that would be expected to experience one or more faults per year.
The number of faults expected in the new UG sections of the main line is lower than for the OH
line sections. After the conversion of the OH to UG of 38% of the main feeder length the reliability
experienced by the customer population served by the feeder should improve. Applying a lower
fault rate to the new underground feeder sections results in the following expected reliability
indices:
As expected, all the reliability
indices have improved and this is a
direct result of the lower number of
fault events expected along the main line with 38% of it now UG.
However, with a significant part of the main line now UG construction, the use of standard
reclosing philosophies becomes questionable due to the higher probability that a fault might be in
the UG line sections. Faults in UG cable are a result of punctures of the solid insulation system in
the cable and removing the applied voltage does not result in the insulation system restoring to full
capability as would be the case with OH construction. Reclosing will result in a second (or third
or fourth) fault current event until the protection device locks out. This re-application of fault
current results in additional equipment stress. As a result of the UG main line conversion the
reclosing on the feeder overcurrent devices will need to be blocked, but the trade-off is that any
main line fault event becomes a single
operation to lockout of the main line recloser
or the substation circuit breaker.
Likewise, any faults on all fused laterals will
result in a sustained outage because a fuse
saving strategy requires reclosing to
implement. Therefore, transient faults
downline of all lateral reclosers are the only
faults that will be automatically cleared and
service restored.
A simulation of the feeder reliability with the reclosing at the substation breaker turned off on the
feeder results in the following reliability indices:
The change to the feeder construction and
the protection system has resulted in
dramatic changes to the reliability indices
for the feeder. Despite the reduction in the expected number of faults by converting 38% of the
feeder to UG, the overall sustained reliability has not improved when compared to the expected
performance of the original OH feeder design. The momentary events have been reduced by a
large amount since there is no longer any main line device reclosing. This is due to the fact that
any main line fault event, whether transient or persistent, results in a sustained outage since a
protection device opens and does not reclose. Any fused lateral fault also results in a sustained
outage, even for transient faults because fuse saving can no longer be practiced. The result is higher
sustained outage numbers, with SAIFI increasing by over 50% relative to the base case circuit
configuration. This is a direct result of the inability to use traditional reclosing on main line devices
without any ability to test the circuit for sustained faults in the UG line sections.
The continued industry innovation in distribution line protection equipment has resulted in the
development of low-energy fault-testing technology that can be effectively applied in situations
such as this example feeder. In circuits that have UG sections of the line, low-energy fault-testing
technology can identify if a fault on the circuit is persistent and prevent a reclosing operation when
Figure 2. One-line diagram with the addition of 5
cutout-mounted reclosers (TS2), sections changed to
underground construction and existing devices.
2500ft
Existing Recloser O
Substation
End of Mainline
Converted to Underground Sections
New TS2s
New TS2sExisting Recloser
6
there is a cable fault. If the fault is present in an overhead line section and is transient, this new
technology will determine that the fault has cleared after the circuit has been de-energized and the
circuit can be re-energized. The application of circuit protection devices with the low-energy fault-
testing feature allow the system to take advantage of the presence of transient faults on the OH
sections of the line and block reclosing for persistent faults in either the OH or UG sections of the
feeder.
Add main line fault interrupters with low-energy fault-testing capability and additional lateral
cutout-mounted reclosers
The circuit with the new UG main line sections can be sectionalized to provide improved reliability
for the customers connected to the feeder using three fault interrupter devices with low-energy
fault-testing technology. These devices would be placed upstream of each UG main line section
where the main line circuit is OH construction. Options exist for pad-mounted low-energy fault
testing fault interrupters if there is a desire to place these devices in the UG portion of the OH/UG
transition. The result is each section has a mix of UG and OH main line construction and the low-
energy fault-testing feature of the fault interrupter will be applied to allow reclosing after
successful interruption of transient faults in the OH line sections and prevent reclosing for
persistent faults in either the OH or UG feeder sections. The device locations are shown on the
one-line diagram in Figure 3.
This intelligent reclosing following a test of the circuit using low-energy fault-testing is applied to
regain the reliability improvement expected by converting OH main line sections to UG. A
simulation of the feeder reliability with the low-energy fault-testing technology applied on the
feeder results in the following reliability indices:
The use of low-energy fault-testing
technology results in a significant reduction
in the reliability indices for the feeder
compared to the original feeder design. The
sustained outage rate experienced by the
average customer on the feeder has been
reduced by approximately 40% (11.96 to
7.16). The momentary outage rate
experienced by the average customer on the
feeder has been reduced by approximately
81% (22.82 to 4.29). The dramatic reduction
in the momentary outage rate is because there
is a lower main line transient fault rate due to
the UG conversion plus the protection
system operating in a fuse sacrifice mode.
Add cutout-mounted reclosers in the heavy customer concentration at the far end of the feeder
Laterals connected to the feeder are predominantly OH construction that typically would have a
large number of transient fault events. The lateral exposure is approximately 70% of the total
feeder construction. The main line devices are not configured in a fuse saving protection mode, so
these transient faults result in a sustained outage for the lateral customers when the fuse operates.
This will add to the sustained outages experienced by customers connected to the feeder.
The design of the fault detection system for a distribution feeder requires that decisions must be
made that impact operations as well as overall outage rates. Cutout-mounted reclosers placed at
lateral connection points can help reduce the number of sustained outages by tripping and reclosing
when transient faults are experienced. In the case of a fuse operation a service crew would need to
Figure 3. One-line diagram with two additional low-
energy fault-testing fault interrupters (IR), 5 additional
cutout-mounted recloser (TS2) devices, underground
conversions and existing device locations shown.
2500ft
New IR Reclosers
Existing Recloser
Substation
End of Mainline
Converted to Underground Sections
New TS2s
Existing Recloser New TS2s New IR Reclosers
7
be dispatched to replace the fuse to restore service. Overhead laterals that have sufficient length to
experience frequent faults can quickly justify the cost of a cutout-mounted recloser. Payback is
typically achieved after a cutout-mounted recloser clears four transient outages, saving four field
visits by a line crew.
The following reliability improvement
strategy examined the impact of adding
five additional cutout-mounted recloser
locationss. Lateral locations near the end
of the feeder were selected for applications
of these devices. This results in the ten
longest laterals on the feeder being
equipped with cutout-mounted recloser
devices that only trip and reclose the
faulted lateral circuit. The five additional
(TS2) locations are shown in Figure 4.
The addition of the five cutout-mounted recloser locations on the longest laterals connected to the
circuit in the downline location and coordinated to work with the upstream low-energy fault-testing
fault interrupter is expected to further reduce the number of sustained outages. The following are
the resulting reliability improvement indices for the feeder:
Momentary interruptions have increased
slightly (≈8%) with the application of the
additional five cutout-mounted recloser
locationss. This occurs because any lateral reclosing device causes downline customers to
experience brief interruptions instead of sustained outages as transient faults are sensed and
cleared. However, the sustained outages experienced for the average customer served by the feeder
has decreased as a result of the clearing of these transient fault events.
Add a low-energy fault-testing fault interrupter tie point device located near the end of the feeder
using non-communicating or communication-based automation to restore service
Serving a distribution feeder in radial fashion results in limits to the resulting reliability
experienced by the average customer on the feeder. Sectionalizing the feeder into smaller segments
helps to drive down the outage frequency and outage time but customers at the end of the feeder
are still impacted by fault events between the substation and customer location. The ability to serve
the customers with an alternative source during an outage can further drive down the outage time
experienced. With a second source of supply at a strategic location on the feeder, smaller sections
can be isolated for persistent faults, while quickly restoring other customers on the feeder.
In this example a tie point is added near the end of the feeder with an alternate source that has
sufficient capacity to recover the unfaulted load when a fault occurs on the feeder. The restoration
process in this example can be accomplished
through a loop scheme type of application
that does not require communications
between devices or it can also be completed
using an automation system that uses the
feeder loading data prior to restoring service.
In either case the service can be restored in
times that are faster than the threshold for
sustained outage recording. The fault event
does result in a momentary outage to some
customers while the automatic fault
2500ft
New IR Reclosers
Existing Recloser
Substation
End of Mainline
Converted to Underground Sections
New TS2s
Figure 4. One-line diagram with 5 additional cutout-
mounted recloser (TS2) devices, previous improvements
and existing device locations shown.
Existing Recloser New TS2s New IR Reclosers
Figure 5. One-line diagram showing previous
improvements, the addition of a tie-point low-energy
fault-testing fault interrupter (IR) and existing device
locations.
Existing Recloser New TS2s New IR Reclosers
8
clearing, and restoration action is completed. Figure 5 shows the feeder with the devices added
and the location of the tie point to an alternative feeder that recovers unfaulted feeder load when
needed.
The addition of the feeder tie and capability to restore service to customer loads when a main line
persistent fault is experienced is expected to improve the sustained outage reliability numbers. For
example, a sustained fault in the mid-line UG section would normally result in a long outage for
customers connected to the end of the feeder. With the feeder tie, there is a brief outage to
customers as sectionalizing devices open on the main line to isolate the cable fault and the tie
device closes restoring service. This does result in a momentary outage to these customers, but the
sustained customer outage event (SAIFI) and the outage event time (SAIDI) are avoided. The
following are the resulting reliability indices for the feeder:
Momentary interruptions increase with the
application of the tie device and automatic
service restoration for main line persistent
faults. The sustained outages experienced for the average customer served by the feeder has
decreased as a result of the ability to quickly provide service from another source for these events.
PROTECTION SYSTEM COORDINATION STUDIES
The addition of the main line and lateral protection devices resulting in the higher reliability
experience for the average customer on the feeder require devices that can be coordinated to
function as an overall system. The philosophy examined earlier when calculating the performance
of the system assumed that the main line devices would not apply a fuse saving strategy but would
be configured to reclose following a low-energy test of the feeder sections prior to reclosing. Fuse
saving will be applied on the lateral interconnection point to the main line using cutout-mounted
recloser devices to prevent outages for temporary faults downstream of fuses on the laterals.
Settings applied consider the full load current expected at the protection device location as well as
the fault currents that are experienced by the device at the installation location and at the remote
end of the feeder where that device would be called upon to sense and clear any fault. A fault
analysis for the feeder was completed to obtain the fault currents described to compare against the
protective device curves. One will note that the fault currents increase with the feeder changes due
to the lower overall main line feeder impedance of the underground cable sections compared to
the equivalent length of overhead construction.
Main line low-energy fault-testing fault interrupter
time-current characteristic curves (TCCs) were selected
as an example to demonstrate the ability to coordinate
multiple devices along the feeder. The tighter
overcurrent protection response tolerances of the low-
energy fault-testing fault interrupters are desirable
when considering placement of multiple series devices
when all the tolerances of a device’s performance are
considered.[3] In this example, a fault that is
experienced at the more remote parts of the feeder on a single-phase lateral will result in fault
current flowing through as many as six overcurrent devices – the substation relayed circuit breaker,
three main line low-energy fault-testing fault interrupters (IR#1, IR#2 & IR#3), one cutout-
mounted recloser (TS2), and one 40 Amp fuse that is closest to the fault. Figure 6 shows a
simplified one-line diagram with the protection devices. Table 1 shows the details of the load
current and fault current at the location of each of the six devices.
Figure 6. One-line diagram with
coordinated series low-energy fault-testing
fault interrupters.
9
The operating current and tolerance-based TCC
curve [4] selected for achieving the desired
coordinated fault sectionalizing of each
example feeder device results in the curves
shown in Figure 7. As a general starting point,
the minimum operating current was selected
based on approximately 2.5 times the maximum
load current expected at each device location.
The maximum fault current at each device
location was also examined using the values
shown in Table 1. The final device is a 40-
ampere fuse that is down line of cutout-mounted
recloser on a lateral. The cutout-mounted
recloser fast (fuse saving) and delayed (fuse
sacrifice) curves selected are also shown. A
final consideration in a TCC selection and
setting might also include its minimum fault
sensing capability where a line to ground fault
is considered with an impedance. For this
example, a minimum fault current of 180
amperes for a single-line-to-ground fault on a
lateral was applied. This value is within the
operating range of the fuse and cutout-mounted
recloser devices placed on the feeder achieving
the minimum fault sensing requirement.
SUMMARY AND CONCLUSIONS
This paper has examined the impact of
converting a distribution feeder from entirely
OH design to a hybrid design that has multiple
sections of the main line converted to UG
construction. The initial change included the
OH to UG conversion and addition of lateral
cutout-mounted recloser devices at five
locations, but no change to the main line feeder
overcurrent protection devices. The application of UG feeder construction will normally result in
reclosing being undesirable using conventional protection equipment since faults in the UG
sections are typically persistent faults. The reliability is negatively impacted by eliminating
reclosing because a significant part of the feeder remains OH construction. Reclosing can be used
provided protection equipment unobtrusively tests the feeder for persistent faults using low energy
prior to a reclose attempt which the low-energy fault-testing fault interrupter provides. Applying
these devices upstream of the three cable sections in the example feeder allows a reclosing strategy
to be applied without risking reclosing on a faulted circuit.
Cutout-mounted reclosers were used to replace fuses at 10 lateral locations on the feeder to offset
the loss of fuse saving for transient faults on the lateral circuits – a fuse saving strategy was
abandoned because of UG feeder section additions. This equipment provides improvements to
overall feeder reliability as reflected in the summary of the predictive reliability analysis shown
in Table 2. In addition to the reliability benefits, the cutout-mounted recloser devices also offer
reduced O&M costs by eliminating the time required to replace fuses for transient fault events.
Device Name Load Current (Amps) Fault Current (Amps)
Feeder Breaker 450 6863
IR #3 450 6863
IR #2 320 3600
IR #1 200 2585
TS2 17 1165
40 Amp Fuse 9 1100
End of Line 0.45 1013
Table 1. Fault currents at low-energy fault-testing
fault interrupters (IR #s), cutout-mounted recloser
(TS2), 40A fuse and end-of -line locations.
Study: C:DGOOncor ReliabilityFA 2018Study1.tcc
PLOTTING VOLTAGE:
BY:
DATE:
NO:
12.47 kV
0.01
0.1
1
10
100
1000
1Minute
0.5 1 10 100 1000 10000
Current in Amperes: x 1 at 12.47 kV.
TimeinSeconds
Feeder Breaker
IR3
IR2
IR1
TS2 Fast Curve
TS2 Slow Curve
40 Amp Std Speed Fuse
Figure 7. TCC curves selected for example feeder
devices. Note: TCC curves are truncated at the
maximum available fault current for their respective
devices
10
Long laterals were selected to produce an estimated payback on this example feeder in less than
2-years due to the high fault rate.
The final radial feeder alternative (with no
normally open tie to an adjacent feeder)
examined the application of state-of-the-art
protective devices using low-energy fault-
testing technology along the main line and
cutout mounted reclosing devices at 10
selected lateral locations. This resulted in a
43% reduction in sustained outage indices
compared to the average customer experience
with the original OH circuit design. The
momentary outages experienced by the
average customer was reduced by
approximately 80%. Table 2 is a summary of
the reliability values for each alternative
discussed in this paper.
The addition of an automated normally open
tie device further improved the sustained
outage indices. This addition resulted in a 63%
reduction in sustained outage indices
compared to the average customer experience
with the original OH circuit design. The load
restoration of unfaulted feeder segments using
the automated normally open tie increases the
momentary outage index in order to drive down sustained outages and sustained outage times. But
the momentary outages experienced by the average customer is still reduced by approximately
69% compared to the original OH circuit.
BIBLIOGRAPHY
[1] Out of Sight, Out of Mind 2012 – An Updated Study on the Undergrounding of Overhead
Power Lines, Published by the Edison Electric Institute, 2012. Web site: www.eei.org
[2] A New Fuse-Saving Philosophy, McCarthy, C., O’Leary R., Staszesky D., Presented at
DistribuTECH 2008, January 22-24, 2008, Tampa, Florida.
[3] Improving Medium-Voltage Main-Feeder Reliability by Increasing Fault-Sectionalizing,
Meisinger, © 2017 S&C Electric Company, November 6, 2017, Paper No. 766-T112.
[4] Tolerance-Based Time-Current Coordination, Meisinger, © 2015 S&C Electric Company,
November 23, 2015, Paper No. 766-576.
Description SAIFI MAIFIe SAIDI
Base case - All OH Feeder 11.97 22.83 20.44
OH main line sections converted
to UG. Added Lateral Devices at 5
locations with reclosing enabled.
7.63 18.84 13.85
OH main line sections converted
to UG. Applied cutout-mounted
recloser devices on 5 selected
lateral locations. Main line device
reclosing disabled.
18.27 1.32 23.31
OH main line sections converted
to UG. Applied cutout-mounted
recloser devices on 5 selected
lateral locations. Main line device
reclosing enabled using 3 low-
energy fault-testing interrupters.
7.16 4.29 11.82
OH main line sections converted
to UG. Applied cutout-mounted
recloser devices on 10 selected
lateral locations. Main line device
reclosing enabled using 3 low-
energy fault-testing interrupters.
6.86 4.64 11.61
OH main line sections converted
to UG. Applied Cutout-mounted
recloser II devices on 10 selected
lateral locations. Main line device
reclosing enabled using 3 low-
energy fault-testing interrupters.
Added automated feeder tie
device to line end area.
4.45 7.05 3.00
Table 2. Reliability index comparison summary of example
feeder alternatives.

More Related Content

What's hot

2016 artigo wireless control
2016 artigo wireless control2016 artigo wireless control
2016 artigo wireless controlFabricio Schlag
 
Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.IRJET Journal
 
Real Time and Wireless Smart Faults Detection Device for Wind Turbines
Real Time and Wireless Smart Faults Detection Device for Wind TurbinesReal Time and Wireless Smart Faults Detection Device for Wind Turbines
Real Time and Wireless Smart Faults Detection Device for Wind Turbineschokrio
 
IRJET- Loss Reduction in Agricultural Feeders through HVDS Concept
IRJET- Loss Reduction in Agricultural Feeders through HVDS ConceptIRJET- Loss Reduction in Agricultural Feeders through HVDS Concept
IRJET- Loss Reduction in Agricultural Feeders through HVDS ConceptIRJET Journal
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET Journal
 
Seminar presentation
Seminar presentationSeminar presentation
Seminar presentationAfzal Tiwari
 
Wind Exchange 2015 Report
Wind Exchange 2015 ReportWind Exchange 2015 Report
Wind Exchange 2015 ReportJoshua Chokera
 
Factors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsFactors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsJim White
 
Protective relaying-philosphy-and-design-guidelines
Protective relaying-philosphy-and-design-guidelinesProtective relaying-philosphy-and-design-guidelines
Protective relaying-philosphy-and-design-guidelinesGanesan Nagarajan
 
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOMModeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOMijsrd.com
 
Introduction of switcg gear
Introduction of switcg gearIntroduction of switcg gear
Introduction of switcg gearjawaharramaya
 
Short-circuit fault diagnosis of the DC-Link capacitor and its impact on an ...
Short-circuit fault diagnosis of the DC-Link capacitor and  its impact on an ...Short-circuit fault diagnosis of the DC-Link capacitor and  its impact on an ...
Short-circuit fault diagnosis of the DC-Link capacitor and its impact on an ...IJECEIAES
 
Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Alexander Decker
 
11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...Alexander Decker
 
Why we need power-system protection? System Protection
Why we need power-system protection? System ProtectionWhy we need power-system protection? System Protection
Why we need power-system protection? System ProtectionSystem Protection
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)IJERD Editor
 
Power System Analysis | Power System Protection
Power System Analysis | Power System ProtectionPower System Analysis | Power System Protection
Power System Analysis | Power System ProtectionSystem Protection
 
Kada003 ac drives_diagnostics_report
Kada003 ac drives_diagnostics_reportKada003 ac drives_diagnostics_report
Kada003 ac drives_diagnostics_reportbrumaller
 

What's hot (20)

2016 artigo wireless control
2016 artigo wireless control2016 artigo wireless control
2016 artigo wireless control
 
Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.Review paper on Fault analysis and its Limiting Techniques.
Review paper on Fault analysis and its Limiting Techniques.
 
Real Time and Wireless Smart Faults Detection Device for Wind Turbines
Real Time and Wireless Smart Faults Detection Device for Wind TurbinesReal Time and Wireless Smart Faults Detection Device for Wind Turbines
Real Time and Wireless Smart Faults Detection Device for Wind Turbines
 
IRJET- Loss Reduction in Agricultural Feeders through HVDS Concept
IRJET- Loss Reduction in Agricultural Feeders through HVDS ConceptIRJET- Loss Reduction in Agricultural Feeders through HVDS Concept
IRJET- Loss Reduction in Agricultural Feeders through HVDS Concept
 
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
IRJET- Analysis of Load Frequency Control for a Distributed Grid System Invol...
 
IJET-V3I2P17
IJET-V3I2P17IJET-V3I2P17
IJET-V3I2P17
 
Seminar presentation
Seminar presentationSeminar presentation
Seminar presentation
 
Wind Exchange 2015 Report
Wind Exchange 2015 ReportWind Exchange 2015 Report
Wind Exchange 2015 Report
 
Factors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE TransactionsFactors to Consider When Perfroming Maint - IEEE Transactions
Factors to Consider When Perfroming Maint - IEEE Transactions
 
Protective relaying-philosphy-and-design-guidelines
Protective relaying-philosphy-and-design-guidelinesProtective relaying-philosphy-and-design-guidelines
Protective relaying-philosphy-and-design-guidelines
 
RAMS Tech Paper
RAMS Tech PaperRAMS Tech Paper
RAMS Tech Paper
 
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOMModeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
Modeling Analysis& Solution of Power Quality Problems Using DVR & DSTATCOM
 
Introduction of switcg gear
Introduction of switcg gearIntroduction of switcg gear
Introduction of switcg gear
 
Short-circuit fault diagnosis of the DC-Link capacitor and its impact on an ...
Short-circuit fault diagnosis of the DC-Link capacitor and  its impact on an ...Short-circuit fault diagnosis of the DC-Link capacitor and  its impact on an ...
Short-circuit fault diagnosis of the DC-Link capacitor and its impact on an ...
 
Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...Methods to determine the overall health and condition of large power transfor...
Methods to determine the overall health and condition of large power transfor...
 
11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...11.methods to determine the overall health and condition of large power trans...
11.methods to determine the overall health and condition of large power trans...
 
Why we need power-system protection? System Protection
Why we need power-system protection? System ProtectionWhy we need power-system protection? System Protection
Why we need power-system protection? System Protection
 
International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)International Journal of Engineering Research and Development (IJERD)
International Journal of Engineering Research and Development (IJERD)
 
Power System Analysis | Power System Protection
Power System Analysis | Power System ProtectionPower System Analysis | Power System Protection
Power System Analysis | Power System Protection
 
Kada003 ac drives_diagnostics_report
Kada003 ac drives_diagnostics_reportKada003 ac drives_diagnostics_report
Kada003 ac drives_diagnostics_report
 

Similar to Improving Reliability on Mixed Overhead and Underground Distribution Feeders

Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...Power System Operation
 
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...Power System Operation
 
A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...
A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...
A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...IRJET Journal
 
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINE
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINEFUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINE
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINEJournal For Research
 
IRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC AutomationIRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC AutomationIRJET Journal
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerIRJET Journal
 
Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...eSAT Publishing House
 
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...Power System Operation
 
IRJET- Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...
IRJET-  	  Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...IRJET-  	  Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...
IRJET- Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...IRJET Journal
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...iosrjce
 
Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...eSAT Publishing House
 
Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...eSAT Journals
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit iivenki249
 
IRJET- Experimental and Investigation of Automation Pipe Crack Detection ...
IRJET-  	  Experimental and Investigation of Automation Pipe Crack Detection ...IRJET-  	  Experimental and Investigation of Automation Pipe Crack Detection ...
IRJET- Experimental and Investigation of Automation Pipe Crack Detection ...IRJET Journal
 
Condition-based Maintenance with sensor arrays and telematics
Condition-based Maintenance with sensor arrays and telematicsCondition-based Maintenance with sensor arrays and telematics
Condition-based Maintenance with sensor arrays and telematicsGopalakrishna Palem
 
a26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptxa26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptxTesloachKongGilo
 
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...ELELIJ
 
Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...
Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...
Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...IJPEDS-IAES
 

Similar to Improving Reliability on Mixed Overhead and Underground Distribution Feeders (20)

Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
 
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
Energy Storage Systems as a Reliable Alternative to Diesel Generators for Cri...
 
ASHUTOSH BHATT DT19EEJ008 RPC JUNE22.ppt
ASHUTOSH BHATT DT19EEJ008 RPC JUNE22.pptASHUTOSH BHATT DT19EEJ008 RPC JUNE22.ppt
ASHUTOSH BHATT DT19EEJ008 RPC JUNE22.ppt
 
A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...
A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...
A Review on Selection of Proper Busbar Arrangement for Typical Substation (Bu...
 
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINE
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINEFUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINE
FUZZY LOGIC APPROACH FOR FAULT DIAGNOSIS OF THREE PHASE TRANSMISSION LINE
 
IRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC AutomationIRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
IRJET- Overhead Line Protection with Automatic Switch by using PLC Automation
 
Review on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power TransformerReview on Different Techniques for Differential Protection of Power Transformer
Review on Different Techniques for Differential Protection of Power Transformer
 
Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...Redundant power supply architecture for self healing substation using ultraca...
Redundant power supply architecture for self healing substation using ultraca...
 
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
A Novel Back Up Wide Area Protection Technique for Power Transmission Grids U...
 
IRJET- Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...
IRJET-  	  Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...IRJET-  	  Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...
IRJET- Analysis of Micro Inversion to Improve Fault Tolerance in High Spe...
 
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
An adaptive protection scheme to prevent recloser-fuse miscoordination in dis...
 
D010622334
D010622334D010622334
D010622334
 
Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...
 
Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...Study and comparison of various communication based protective relaying schem...
Study and comparison of various communication based protective relaying schem...
 
Pq unit ii
Pq unit iiPq unit ii
Pq unit ii
 
IRJET- Experimental and Investigation of Automation Pipe Crack Detection ...
IRJET-  	  Experimental and Investigation of Automation Pipe Crack Detection ...IRJET-  	  Experimental and Investigation of Automation Pipe Crack Detection ...
IRJET- Experimental and Investigation of Automation Pipe Crack Detection ...
 
Condition-based Maintenance with sensor arrays and telematics
Condition-based Maintenance with sensor arrays and telematicsCondition-based Maintenance with sensor arrays and telematics
Condition-based Maintenance with sensor arrays and telematics
 
a26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptxa26e8dedece825e530c50c1240886cf0.pptx
a26e8dedece825e530c50c1240886cf0.pptx
 
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...
PROTECTION COORDINATION OF DISTRIBUTION SYSTEMS EQUIPPED WITH DISTRIBUTED GEN...
 
Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...
Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...
Design and Simulation of Dynamic Voltage Restorer Based on Fuzzy Controller O...
 

More from Power System Operation

Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panelsPower System Operation
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsPower System Operation
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action SchemePower System Operation
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...Power System Operation
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePower System Operation
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)Power System Operation
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & PartsPower System Operation
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools Power System Operation
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy SystemPower System Operation
 

More from Power System Operation (20)

ENERGY TRANSITION OUTLOOK 2021
ENERGY TRANSITION OUTLOOK  2021ENERGY TRANSITION OUTLOOK  2021
ENERGY TRANSITION OUTLOOK 2021
 
Thermography test of electrical panels
Thermography test of electrical panelsThermography test of electrical panels
Thermography test of electrical panels
 
What does peak shaving mean
What does peak shaving meanWhat does peak shaving mean
What does peak shaving mean
 
What's short circuit level
What's short circuit levelWhat's short circuit level
What's short circuit level
 
Power System Restoration Guide
Power System Restoration Guide  Power System Restoration Guide
Power System Restoration Guide
 
Big Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid OperationsBig Data Analytics for Power Grid Operations
Big Data Analytics for Power Grid Operations
 
SPS to RAS Special Protection Scheme Remedial Action Scheme
SPS to RAS Special Protection Scheme  Remedial Action SchemeSPS to RAS Special Protection Scheme  Remedial Action Scheme
SPS to RAS Special Protection Scheme Remedial Action Scheme
 
Substation Neutral Earthing
Substation Neutral EarthingSubstation Neutral Earthing
Substation Neutral Earthing
 
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...SVC PLUS Frequency Stabilizer Frequency and voltage support for  dynamic grid...
SVC PLUS Frequency Stabilizer Frequency and voltage support for dynamic grid...
 
Principles & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground ResistancePrinciples & Testing Methods Of Earth Ground Resistance
Principles & Testing Methods Of Earth Ground Resistance
 
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)Gas Insulated Switchgear?  Gas-Insulated High-Voltage Switchgear (GIS)
Gas Insulated Switchgear? Gas-Insulated High-Voltage Switchgear (GIS)
 
Electrical Transmission Tower Types - Design & Parts
Electrical Transmission Tower  Types - Design & PartsElectrical Transmission Tower  Types - Design & Parts
Electrical Transmission Tower Types - Design & Parts
 
What is load management
What is load managementWhat is load management
What is load management
 
What does merit order mean
What does merit order meanWhat does merit order mean
What does merit order mean
 
What are Balancing Services ?
What are  Balancing Services ?What are  Balancing Services ?
What are Balancing Services ?
 
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools The Need for Enhanced  Power System  Modelling Techniques  &  Simulation Tools
The Need for Enhanced Power System Modelling Techniques & Simulation Tools
 
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
Power Quality  Trends in the Transition to  Carbon-Free Electrical Energy SystemPower Quality  Trends in the Transition to  Carbon-Free Electrical Energy System
Power Quality Trends in the Transition to Carbon-Free Electrical Energy System
 
Power Purchase Agreement PPA
Power Purchase Agreement PPA Power Purchase Agreement PPA
Power Purchase Agreement PPA
 
Harmonic study and analysis
Harmonic study and analysisHarmonic study and analysis
Harmonic study and analysis
 
What is leakage current testing
What is leakage current testingWhat is leakage current testing
What is leakage current testing
 

Recently uploaded

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 

Recently uploaded (20)

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 

Improving Reliability on Mixed Overhead and Underground Distribution Feeders

  • 1. Mike.Meisinger@sandc.com Improving Reliability on Mixed Overhead and Underground Distribution Feeders M. MEISINGER, M. BISHOP, S. WILLIAMS S&C Electric Company USA SUMMARY Many utility companies are converting overhead (OH) main line feeder sections to underground (UG) to improve reliability, system resiliency, or other local customer demands. A Hybrid distribution feeder is one with a mixture of OH and UG main line sections. Conventional protection philosophies for hybrid feeders normally result in lower overall feeder reliability. This paper will examine an example feeder to demonstrate the impact of protection and isolation system improvements on predicted reliability for Hybrid distribution feeders. KEYWORDS FLISR, SAIFI, SAIDI, MAIFI, Distribution Feeder Reliability Improvement 21, rue d’Artois, F-75008 PARIS CIGRE US National Committee http : //www.cigre.org 2019 Grid of the Future Symposium
  • 2. 2 INTRODUCTION Distribution system overcurrent devices have been applied by electric company distribution engineers to detect and clear system faults to minimize the probability of damage to equipment due to sustained faults. Inspection and maintenance of lines is performed to minimize the number of faults that are experienced on the feeder. Despite these efforts, the exposure to weather, animals, vegetation, vehicles and other hazards results in the expectation that some number of system faults will still be experienced. To mitigate the extent of outages, equipment is placed on the feeder to identify fault conditions and quickly isolate faulted sections of the distribution feeder. In addition to recognizing and clearing overcurrent conditions caused by fault events, the same equipment elements are used in an overall system that performs Fault Location, Isolation, and Service Restoration (FLISR). These systems apply greater levels of system automation and integration designed to reduce outage times for customers that are somewhat remote from the actual faulted section of the feeder. The demand for these types of systems increases with customer expectations for high reliability. Many electric utilities focus reliability improvement initiatives around maintenance activities, such as tree trimming, aimed at reducing the number of fault events. These activities should result in a lower fault rate for the feeder section as measured by faults per mile per year. It can be shown that investments in sectionalizing and automation systems, such as the design of overcurrent protection systems to better sectionalize the system after a fault, also have major reliability improvement potential for any given fault rate. If fault records indicate that many events were tree related, then increased vegetation management expense may be justified. However, in many utility situations where fault records exist, “unknown” may be the largest category of fault causes listed. In areas where high fault rates have been experienced, or areas where customer demands for various reasons warrant the investment, utilities are converting sections of the distribution feeder from overhead (OH) to underground (UG) construction. The reduced exposure to weather, animals, and other physical hazards normally results in a lower fault incidence rate for UG construction. Since cost is higher for UG construction, the application along the feeder may only be in limited areas, resulting in a mix of OH and UG main line feeder miles. This presents challenges to conventional overcurrent protection philosophies that can result in lower overall feeder reliability. This paper will examine the application using an example feeder and demonstrate that new protection equipment technology can achieve the improvement needed to capture the intended reliability improvement FEEDER OVERCURRENT PROTECTION STRATEGIES Distribution system overcurrent conditions are detected and interrupted when needed using a variety of devices that include fuses, reclosing devices (single phase or three-phase), and circuit breakers in substations. The devices are designed to operate in a coordinated fashion to isolate the smallest part of the system possible for each fault event. Coordination studies are completed by system protection engineers for specific feeders with knowledge of system short circuit currents at points on the feeder. Protection philosophies are followed according to individual company developed standards, but the overall final design includes engineering judgements on the part of the distribution protection engineer. The application of the protection systems also impacts the sectionalizing of the feeder that results in accumulated outage numbers used in calculating reliability indices for the feeder and overall system. Electric distribution companies utilize strategies to recover from the fault events experienced on the distribution feeders, since faults may be transient or persistent. A transient fault is one where fast interruption of the fault current prevents any damage to line conductors or equipment that would require a repair crew and the circuit can be automatically reclosed after a few seconds to
  • 3. 3 restore service. A persistent fault cannot be re-energized without a service crew performing some equipment or line repair or replacement. The mix of transient and persistent faults on the feeder impacts the selection of overcurrent protection system philosophy regarding equipment interaction as a system. When applying interrupting devices that can be reclosed along the main line and fuses at lateral connections to the main line, a choice is made between two overcurrent protection methodologies called “fuse saving” and “fuse sacrifice”. Fuse saving utilizes a fast-trip-and-reclose scheme to clear transient faults on the laterals before the fuse has operated. This causes a momentary outage to all customers located downstream of the reclosing device but overall reduces sustained outages. This scheme is often used in rural areas or when repair time is longer due to the time for crews to get to the fuse location. A fuse sacrifice philosophy can reduce momentary outages by eliminating fast tripping on relayed circuit breakers and downstream overcurrent devices. The elimination of fuse saving may reduce momentary operations, but it increases the overall sustained outage minutes, since transient faults on fused laterals result in a fuse operation and sustained outage. This scheme is often used in urban areas where crews can quickly arrive to the scene and make repairs and/or replace the fuse link. Intelligent fuse saving systems technologies can now be applied that blend the best of both techniques to further enhance reliability. Intelligent fuse saving prevents a fuse saving attempt when a fault interrupter’s fault clearing time for a measured fault current cannot prevent fuse operation. This is in contrast to conventional fuse saving schemes that often result in the fuse and the fault interrupter both operating. Reliability rates can also be improved by employing automation to minimize outages resulting from either transient or persistent faults. It can be shown that sectionalizing of a radial feeder has an improvement limit and diminishing returns may not produce the desired reliability level from sectionalizing alone. Once this point is reached further improvement can be realized by sectionalizing to minimize the faulted portion of the system with feeder ties to alternate sources, such as neighboring feeders. The general approach used to design higher reliability distribution service on radial feeders includes the following initiatives: 1. Use automatic reclosing to eliminate outages caused by transient faults on OH sections. General industry practice avoids reclosing on UG systems since cable faults are normally persistent. Therefore, hybrid main line distribution feeders present a protection challenge with the mix of UG and OH construction. However, a low-energy fault testing fault interrupter can be used to avoid reclosing into faults and further stress system components for all forms of feeder construction. 2. Use automatic reclosing on lateral circuits to eliminate momentary operations of main line devices for faults on the lateral circuits. UG and hybrid circuits essentially preclude the fuse saving philosophy. The steps taken in this example feeder will show the benefits of re- introducing reclosing and fuse-saving using a cutout-mounted recloser at the lateral level. 3. Sectionalize the system to limit the number of customers affected by a persistent fault and reduce the time necessary to locate a fault. Smart switches can accomplish this, but fault interrupting devices can further limit the affected area. 4. Build for improved reliability by including bridging points to alternate sources that are managed by a distributed intelligence automation system that reconfigures the system following an outage based on monitored system conditions. 5. Reduce device hazard rates. This can be driven by a root cause analysis to determine maintenance levels required to drive feeder fault rate to target levels.
  • 4. 4 The subsequent sections examine a typical radial utility distribution feeder with the objective being improvement of reliability indices through selection and application of appropriate fault interrupting equipment. Calculations are performed for each equipment addition to demonstrate the improvement that each step provides in the reliability indices. EXAMPLE FEEDER EXAMINATION FOR RELIABILITY IMPROVEMENT Figure 1 shows a simplified one-line diagram of a distribution feeder served by a substation bus located at the left side of the figure. The main line is 5.9 miles in length and provides radial service to customers that are served on laterals at the end of the feeder. There is a short section of main line UG construction shown in red (270 feet). The remainder of the main line is OH. Total circuit miles for all 3-phase, 2-phase, and 1-phase lines is 20.18 miles of OH and 1.81 miles of UG construction. The 12.47 kV feeder being analyzed is a problem feeder that is primarily OH construction with a customer count of approximately 1300 and reliability that is not near company targets. Outage data was broken into a variety of categories with the largest numbers due to lightning and vegetation. The main line feeder is radial as shown in Figure 1 with many laterals connected to the main line. Total feeder load is approximately 9 MVA. The base case reliability calculations used fuse saving on the main line feeder recloser and three- phase lateral recloser near the substation. Fuse saving was disabled on the substation circuit breaker to help reduce momentary interruptions for all customers on the feeder. Most laterals are fused at the connection to the main line and there are several long laterals that have additional fuses placed downline in series. The following are the base case reliability indices for the feeder: CIRCUIT CHANGES IMPLEMENTED TO IMPROVE RELIABILITY Next, improvements to the feeder construction and the protection system design will be applied and the resulting changes in the reliability indices calculated. The following sections summarize the changes to the circuit. Convert selected sections of the Main line from OH to UG and add selected lateral circuit devices The existing sections of the main line are predominantly OH. There are many utility companies that are converting sections of OH to UG, either to meet local demands for aesthetic improvements or to improve the overall feeder reliability. In this feeder example three sections of the main line have been converted to UG cable. They are shown in Figure 2 as sections shown in red. The end of line UG section is 5500 ft, the midline UG section is 2600 ft. and the section near the substation is 2200 ft. The underground part of the main line is 38% of the feeder. A protection system upgrade to this feeder shown in Figure 2 includes the replacement of fuses at 5 feeder lateral locations using cutout-mounted reclosers (TS2). This type of device can sense overcurrent conditions, trip and then reclose to clear transient faults. It can also be configured to provide the fuse saving strategy for sections of the lateral that have fusing which further sectionalizes the lateral for persistent faults. The five lateral locations selected were the longer 2500ft ExistingRecloser O Substation End of Mainline Figure 1. One-line diagram of example distribution feeder used for analysis.
  • 5. 5 lateral circuits that would be expected to experience one or more faults per year. The number of faults expected in the new UG sections of the main line is lower than for the OH line sections. After the conversion of the OH to UG of 38% of the main feeder length the reliability experienced by the customer population served by the feeder should improve. Applying a lower fault rate to the new underground feeder sections results in the following expected reliability indices: As expected, all the reliability indices have improved and this is a direct result of the lower number of fault events expected along the main line with 38% of it now UG. However, with a significant part of the main line now UG construction, the use of standard reclosing philosophies becomes questionable due to the higher probability that a fault might be in the UG line sections. Faults in UG cable are a result of punctures of the solid insulation system in the cable and removing the applied voltage does not result in the insulation system restoring to full capability as would be the case with OH construction. Reclosing will result in a second (or third or fourth) fault current event until the protection device locks out. This re-application of fault current results in additional equipment stress. As a result of the UG main line conversion the reclosing on the feeder overcurrent devices will need to be blocked, but the trade-off is that any main line fault event becomes a single operation to lockout of the main line recloser or the substation circuit breaker. Likewise, any faults on all fused laterals will result in a sustained outage because a fuse saving strategy requires reclosing to implement. Therefore, transient faults downline of all lateral reclosers are the only faults that will be automatically cleared and service restored. A simulation of the feeder reliability with the reclosing at the substation breaker turned off on the feeder results in the following reliability indices: The change to the feeder construction and the protection system has resulted in dramatic changes to the reliability indices for the feeder. Despite the reduction in the expected number of faults by converting 38% of the feeder to UG, the overall sustained reliability has not improved when compared to the expected performance of the original OH feeder design. The momentary events have been reduced by a large amount since there is no longer any main line device reclosing. This is due to the fact that any main line fault event, whether transient or persistent, results in a sustained outage since a protection device opens and does not reclose. Any fused lateral fault also results in a sustained outage, even for transient faults because fuse saving can no longer be practiced. The result is higher sustained outage numbers, with SAIFI increasing by over 50% relative to the base case circuit configuration. This is a direct result of the inability to use traditional reclosing on main line devices without any ability to test the circuit for sustained faults in the UG line sections. The continued industry innovation in distribution line protection equipment has resulted in the development of low-energy fault-testing technology that can be effectively applied in situations such as this example feeder. In circuits that have UG sections of the line, low-energy fault-testing technology can identify if a fault on the circuit is persistent and prevent a reclosing operation when Figure 2. One-line diagram with the addition of 5 cutout-mounted reclosers (TS2), sections changed to underground construction and existing devices. 2500ft Existing Recloser O Substation End of Mainline Converted to Underground Sections New TS2s New TS2sExisting Recloser
  • 6. 6 there is a cable fault. If the fault is present in an overhead line section and is transient, this new technology will determine that the fault has cleared after the circuit has been de-energized and the circuit can be re-energized. The application of circuit protection devices with the low-energy fault- testing feature allow the system to take advantage of the presence of transient faults on the OH sections of the line and block reclosing for persistent faults in either the OH or UG sections of the feeder. Add main line fault interrupters with low-energy fault-testing capability and additional lateral cutout-mounted reclosers The circuit with the new UG main line sections can be sectionalized to provide improved reliability for the customers connected to the feeder using three fault interrupter devices with low-energy fault-testing technology. These devices would be placed upstream of each UG main line section where the main line circuit is OH construction. Options exist for pad-mounted low-energy fault testing fault interrupters if there is a desire to place these devices in the UG portion of the OH/UG transition. The result is each section has a mix of UG and OH main line construction and the low- energy fault-testing feature of the fault interrupter will be applied to allow reclosing after successful interruption of transient faults in the OH line sections and prevent reclosing for persistent faults in either the OH or UG feeder sections. The device locations are shown on the one-line diagram in Figure 3. This intelligent reclosing following a test of the circuit using low-energy fault-testing is applied to regain the reliability improvement expected by converting OH main line sections to UG. A simulation of the feeder reliability with the low-energy fault-testing technology applied on the feeder results in the following reliability indices: The use of low-energy fault-testing technology results in a significant reduction in the reliability indices for the feeder compared to the original feeder design. The sustained outage rate experienced by the average customer on the feeder has been reduced by approximately 40% (11.96 to 7.16). The momentary outage rate experienced by the average customer on the feeder has been reduced by approximately 81% (22.82 to 4.29). The dramatic reduction in the momentary outage rate is because there is a lower main line transient fault rate due to the UG conversion plus the protection system operating in a fuse sacrifice mode. Add cutout-mounted reclosers in the heavy customer concentration at the far end of the feeder Laterals connected to the feeder are predominantly OH construction that typically would have a large number of transient fault events. The lateral exposure is approximately 70% of the total feeder construction. The main line devices are not configured in a fuse saving protection mode, so these transient faults result in a sustained outage for the lateral customers when the fuse operates. This will add to the sustained outages experienced by customers connected to the feeder. The design of the fault detection system for a distribution feeder requires that decisions must be made that impact operations as well as overall outage rates. Cutout-mounted reclosers placed at lateral connection points can help reduce the number of sustained outages by tripping and reclosing when transient faults are experienced. In the case of a fuse operation a service crew would need to Figure 3. One-line diagram with two additional low- energy fault-testing fault interrupters (IR), 5 additional cutout-mounted recloser (TS2) devices, underground conversions and existing device locations shown. 2500ft New IR Reclosers Existing Recloser Substation End of Mainline Converted to Underground Sections New TS2s Existing Recloser New TS2s New IR Reclosers
  • 7. 7 be dispatched to replace the fuse to restore service. Overhead laterals that have sufficient length to experience frequent faults can quickly justify the cost of a cutout-mounted recloser. Payback is typically achieved after a cutout-mounted recloser clears four transient outages, saving four field visits by a line crew. The following reliability improvement strategy examined the impact of adding five additional cutout-mounted recloser locationss. Lateral locations near the end of the feeder were selected for applications of these devices. This results in the ten longest laterals on the feeder being equipped with cutout-mounted recloser devices that only trip and reclose the faulted lateral circuit. The five additional (TS2) locations are shown in Figure 4. The addition of the five cutout-mounted recloser locations on the longest laterals connected to the circuit in the downline location and coordinated to work with the upstream low-energy fault-testing fault interrupter is expected to further reduce the number of sustained outages. The following are the resulting reliability improvement indices for the feeder: Momentary interruptions have increased slightly (≈8%) with the application of the additional five cutout-mounted recloser locationss. This occurs because any lateral reclosing device causes downline customers to experience brief interruptions instead of sustained outages as transient faults are sensed and cleared. However, the sustained outages experienced for the average customer served by the feeder has decreased as a result of the clearing of these transient fault events. Add a low-energy fault-testing fault interrupter tie point device located near the end of the feeder using non-communicating or communication-based automation to restore service Serving a distribution feeder in radial fashion results in limits to the resulting reliability experienced by the average customer on the feeder. Sectionalizing the feeder into smaller segments helps to drive down the outage frequency and outage time but customers at the end of the feeder are still impacted by fault events between the substation and customer location. The ability to serve the customers with an alternative source during an outage can further drive down the outage time experienced. With a second source of supply at a strategic location on the feeder, smaller sections can be isolated for persistent faults, while quickly restoring other customers on the feeder. In this example a tie point is added near the end of the feeder with an alternate source that has sufficient capacity to recover the unfaulted load when a fault occurs on the feeder. The restoration process in this example can be accomplished through a loop scheme type of application that does not require communications between devices or it can also be completed using an automation system that uses the feeder loading data prior to restoring service. In either case the service can be restored in times that are faster than the threshold for sustained outage recording. The fault event does result in a momentary outage to some customers while the automatic fault 2500ft New IR Reclosers Existing Recloser Substation End of Mainline Converted to Underground Sections New TS2s Figure 4. One-line diagram with 5 additional cutout- mounted recloser (TS2) devices, previous improvements and existing device locations shown. Existing Recloser New TS2s New IR Reclosers Figure 5. One-line diagram showing previous improvements, the addition of a tie-point low-energy fault-testing fault interrupter (IR) and existing device locations. Existing Recloser New TS2s New IR Reclosers
  • 8. 8 clearing, and restoration action is completed. Figure 5 shows the feeder with the devices added and the location of the tie point to an alternative feeder that recovers unfaulted feeder load when needed. The addition of the feeder tie and capability to restore service to customer loads when a main line persistent fault is experienced is expected to improve the sustained outage reliability numbers. For example, a sustained fault in the mid-line UG section would normally result in a long outage for customers connected to the end of the feeder. With the feeder tie, there is a brief outage to customers as sectionalizing devices open on the main line to isolate the cable fault and the tie device closes restoring service. This does result in a momentary outage to these customers, but the sustained customer outage event (SAIFI) and the outage event time (SAIDI) are avoided. The following are the resulting reliability indices for the feeder: Momentary interruptions increase with the application of the tie device and automatic service restoration for main line persistent faults. The sustained outages experienced for the average customer served by the feeder has decreased as a result of the ability to quickly provide service from another source for these events. PROTECTION SYSTEM COORDINATION STUDIES The addition of the main line and lateral protection devices resulting in the higher reliability experience for the average customer on the feeder require devices that can be coordinated to function as an overall system. The philosophy examined earlier when calculating the performance of the system assumed that the main line devices would not apply a fuse saving strategy but would be configured to reclose following a low-energy test of the feeder sections prior to reclosing. Fuse saving will be applied on the lateral interconnection point to the main line using cutout-mounted recloser devices to prevent outages for temporary faults downstream of fuses on the laterals. Settings applied consider the full load current expected at the protection device location as well as the fault currents that are experienced by the device at the installation location and at the remote end of the feeder where that device would be called upon to sense and clear any fault. A fault analysis for the feeder was completed to obtain the fault currents described to compare against the protective device curves. One will note that the fault currents increase with the feeder changes due to the lower overall main line feeder impedance of the underground cable sections compared to the equivalent length of overhead construction. Main line low-energy fault-testing fault interrupter time-current characteristic curves (TCCs) were selected as an example to demonstrate the ability to coordinate multiple devices along the feeder. The tighter overcurrent protection response tolerances of the low- energy fault-testing fault interrupters are desirable when considering placement of multiple series devices when all the tolerances of a device’s performance are considered.[3] In this example, a fault that is experienced at the more remote parts of the feeder on a single-phase lateral will result in fault current flowing through as many as six overcurrent devices – the substation relayed circuit breaker, three main line low-energy fault-testing fault interrupters (IR#1, IR#2 & IR#3), one cutout- mounted recloser (TS2), and one 40 Amp fuse that is closest to the fault. Figure 6 shows a simplified one-line diagram with the protection devices. Table 1 shows the details of the load current and fault current at the location of each of the six devices. Figure 6. One-line diagram with coordinated series low-energy fault-testing fault interrupters.
  • 9. 9 The operating current and tolerance-based TCC curve [4] selected for achieving the desired coordinated fault sectionalizing of each example feeder device results in the curves shown in Figure 7. As a general starting point, the minimum operating current was selected based on approximately 2.5 times the maximum load current expected at each device location. The maximum fault current at each device location was also examined using the values shown in Table 1. The final device is a 40- ampere fuse that is down line of cutout-mounted recloser on a lateral. The cutout-mounted recloser fast (fuse saving) and delayed (fuse sacrifice) curves selected are also shown. A final consideration in a TCC selection and setting might also include its minimum fault sensing capability where a line to ground fault is considered with an impedance. For this example, a minimum fault current of 180 amperes for a single-line-to-ground fault on a lateral was applied. This value is within the operating range of the fuse and cutout-mounted recloser devices placed on the feeder achieving the minimum fault sensing requirement. SUMMARY AND CONCLUSIONS This paper has examined the impact of converting a distribution feeder from entirely OH design to a hybrid design that has multiple sections of the main line converted to UG construction. The initial change included the OH to UG conversion and addition of lateral cutout-mounted recloser devices at five locations, but no change to the main line feeder overcurrent protection devices. The application of UG feeder construction will normally result in reclosing being undesirable using conventional protection equipment since faults in the UG sections are typically persistent faults. The reliability is negatively impacted by eliminating reclosing because a significant part of the feeder remains OH construction. Reclosing can be used provided protection equipment unobtrusively tests the feeder for persistent faults using low energy prior to a reclose attempt which the low-energy fault-testing fault interrupter provides. Applying these devices upstream of the three cable sections in the example feeder allows a reclosing strategy to be applied without risking reclosing on a faulted circuit. Cutout-mounted reclosers were used to replace fuses at 10 lateral locations on the feeder to offset the loss of fuse saving for transient faults on the lateral circuits – a fuse saving strategy was abandoned because of UG feeder section additions. This equipment provides improvements to overall feeder reliability as reflected in the summary of the predictive reliability analysis shown in Table 2. In addition to the reliability benefits, the cutout-mounted recloser devices also offer reduced O&M costs by eliminating the time required to replace fuses for transient fault events. Device Name Load Current (Amps) Fault Current (Amps) Feeder Breaker 450 6863 IR #3 450 6863 IR #2 320 3600 IR #1 200 2585 TS2 17 1165 40 Amp Fuse 9 1100 End of Line 0.45 1013 Table 1. Fault currents at low-energy fault-testing fault interrupters (IR #s), cutout-mounted recloser (TS2), 40A fuse and end-of -line locations. Study: C:DGOOncor ReliabilityFA 2018Study1.tcc PLOTTING VOLTAGE: BY: DATE: NO: 12.47 kV 0.01 0.1 1 10 100 1000 1Minute 0.5 1 10 100 1000 10000 Current in Amperes: x 1 at 12.47 kV. TimeinSeconds Feeder Breaker IR3 IR2 IR1 TS2 Fast Curve TS2 Slow Curve 40 Amp Std Speed Fuse Figure 7. TCC curves selected for example feeder devices. Note: TCC curves are truncated at the maximum available fault current for their respective devices
  • 10. 10 Long laterals were selected to produce an estimated payback on this example feeder in less than 2-years due to the high fault rate. The final radial feeder alternative (with no normally open tie to an adjacent feeder) examined the application of state-of-the-art protective devices using low-energy fault- testing technology along the main line and cutout mounted reclosing devices at 10 selected lateral locations. This resulted in a 43% reduction in sustained outage indices compared to the average customer experience with the original OH circuit design. The momentary outages experienced by the average customer was reduced by approximately 80%. Table 2 is a summary of the reliability values for each alternative discussed in this paper. The addition of an automated normally open tie device further improved the sustained outage indices. This addition resulted in a 63% reduction in sustained outage indices compared to the average customer experience with the original OH circuit design. The load restoration of unfaulted feeder segments using the automated normally open tie increases the momentary outage index in order to drive down sustained outages and sustained outage times. But the momentary outages experienced by the average customer is still reduced by approximately 69% compared to the original OH circuit. BIBLIOGRAPHY [1] Out of Sight, Out of Mind 2012 – An Updated Study on the Undergrounding of Overhead Power Lines, Published by the Edison Electric Institute, 2012. Web site: www.eei.org [2] A New Fuse-Saving Philosophy, McCarthy, C., O’Leary R., Staszesky D., Presented at DistribuTECH 2008, January 22-24, 2008, Tampa, Florida. [3] Improving Medium-Voltage Main-Feeder Reliability by Increasing Fault-Sectionalizing, Meisinger, © 2017 S&C Electric Company, November 6, 2017, Paper No. 766-T112. [4] Tolerance-Based Time-Current Coordination, Meisinger, © 2015 S&C Electric Company, November 23, 2015, Paper No. 766-576. Description SAIFI MAIFIe SAIDI Base case - All OH Feeder 11.97 22.83 20.44 OH main line sections converted to UG. Added Lateral Devices at 5 locations with reclosing enabled. 7.63 18.84 13.85 OH main line sections converted to UG. Applied cutout-mounted recloser devices on 5 selected lateral locations. Main line device reclosing disabled. 18.27 1.32 23.31 OH main line sections converted to UG. Applied cutout-mounted recloser devices on 5 selected lateral locations. Main line device reclosing enabled using 3 low- energy fault-testing interrupters. 7.16 4.29 11.82 OH main line sections converted to UG. Applied cutout-mounted recloser devices on 10 selected lateral locations. Main line device reclosing enabled using 3 low- energy fault-testing interrupters. 6.86 4.64 11.61 OH main line sections converted to UG. Applied Cutout-mounted recloser II devices on 10 selected lateral locations. Main line device reclosing enabled using 3 low- energy fault-testing interrupters. Added automated feeder tie device to line end area. 4.45 7.05 3.00 Table 2. Reliability index comparison summary of example feeder alternatives.