LS medium voltage vacuum contactors
LS medium voltage vacuum contactors using LS vacuum interrupters manufactured
with worldclass technology are type tested in LS PT & T that is accredited high power
test lab by worldclass KOLAS.
www.dienhathe.xyz
www.dienhathe.vn
Contents
Features 4
Technical data 10
Ordering information 12
External view 14
Safety components 15
Internal structure 16
Vacuum interrupters 17
Accessories 18
Drawing operations 19
Electrical circuit diagram 20
Internal connection diagrams 22
External dimensions 24
Selection tables 28
Power fuse 30
Power fuse selection guides 31
Coordination graph 32
Operation curves 34
www.dienhathe.xyz
www.dienhathe.vn
General description
We have the major technology that others can not catch up.
LS vacuum contactors provide high withstand-current strength and
switching capacity as well as versatile auxiliary functions.
Fixed type Drawout type (Standard type)
LS Tri-MEC vacuum contactors are mainly used for the switching of motors,
transformers, capacitors in AC power lines. They can be installed in multi-stack
cubicles.
A vacuum contactor comprises several assemblies such as switching mechanism
including vacuum interrupters, magnetic actuator, high strength molded front
cover and auxiliary devices. Stable and high operating cycle is executed by the
vacuum interrupters made of high alumina ceramic tube which makes it possible
to degas in a high temperature with excellent mechanical strength.
Actuating is available either at instantaneous or continuous excitation. Functions for
safety in connecting and disconnecting are also provided.
LS Vacuum Contactors
4
We have the major technology that others can not catch up.
LS vacuum contactors provide high withstand-current strength and
switching capacity as well as versatile auxiliary functions.
www.dienhathe.xyz
www.dienhathe.vn
Direct-drawout type - for MCSG Fuse connectable type (Standard type)
E-Class Cradle F2-Class Cradle G-Class Cradle
Fuse connectable type (Direct-drawout type)
Operation conditions
Ambient temperature : -5 to 40℃
Maximum temperature of 24-hour mean : 35 ℃
Altitude : 1000m
Humidity : 24-hour measured average - max. 95% RH
1 month measured average - max. 90% RH
Applied standards
IEC Pub. 60470, IEC 60282-1, JEM 1167, KEMC 1126
5
www.dienhathe.xyz
www.dienhathe.vn
[ 40kA ]
Power fused type vacuum contactors, in-house tested according to IEC 60282-1,
can provide short-circuit protection up to 40kA.
Short-circuit protection
High performance, high reliability
and long service life
LS vacuum interrupters that comply with
IEC, ANSI and NEMA standards are
manufactured by the process of brazing
and degasing together in a high
vacuum furnace to assure high reliability.
Superior mechanical strength and
degasing
Providing long service life and suited for
frequently operating purpose due to
using high alumina ceramic tube and
degasing in a high temperature.
High speed interruption and short
arcing time
It has fast recovering characteristic of
vacuum insulation. When opening it
breaks the current at the first current-zero
point to minimize the wearing of
contacts.
Reliable interruption of fault current
LS current limiting power fuse can protect
the devices and systems from fault current
by interrupting within half cycle.
High current such as short-circuit current
cause a fuse blown out due to the
reaction on the material inside of a fuse
within such a short time.
Applied standards
IEC 282-1, DIN 43625, BS 2692, KSC 4612
6
Up-graded performance
[ 6.3kA ]
Performance is up-graded to rated short-time current 6.3kA/1sec.
and switching capacity 4kA according to IEC60470.
Rated short-time current 6.3kA
[ 6.3kA ]
Performance is up-graded to rated short-time current 6.3kA/1sec.
and switching capacity 4kA according to IEC60470.
Rated short-time current 6.3kA
[ 40kA ]
Power fused type vacuum contactors, in-house tested according to IEC 60282-1,
can provide short-circuit protection up to 40kA.
Short-circuit protection
www.dienhathe.xyz
www.dienhathe.vn
7
Suitable for Metal Clad
Switchgear
The structure of G type cradle unification
bushings and single-molded fuse-holder
barrier enables vacuum contactors to
build Metal Clad Switchgears.
Directly withdrawable equipment
This enables the withdrawing of a
vacuum contactor from a panel without
opening a door to prevent any possibility
of electric shock.
Interlock
For the safety of a operator interlock is
equipped as standard.
Auxiliary contacts
Available up to 5NO+5NC.
Contactor over contactor arrangement
[ Safety ]
LS Tri-MEC vacuum contactors provide several auxiliary functions
for safe and comfortable use.
[ Safety ]
LS Tri-MEC vacuum contactors provide several auxiliary functions
for safe and comfortable use.
Personnel safety
■■Interlock button
■■Drawout cradle for MCSG
■■One-molded fuse holder
■■Fuse checher and micro switch
■■Unification bushing
■■Mechanical interlock type
■■Interlock button
■■Drawout cradle for MCSG
■■One-molded fuse holder
■■Fuse checher and micro switch
■■Unification bushing
■■Mechanical interlock type
Additional
equipment
www.dienhathe.xyz
www.dienhathe.vn
Technical data
8
Power fuse
Power fuses can be installed into combination(G, GB) type contactors
for the protection of equipments and systems from short-circuit.
Fuse ratings are selected properly after system analysis and some
accessories such as fuse link clips should be selected by the fuse rating.
Fixed (Z) type Drawout (D) type Direct-drawout (DB) type - for MCSG
Type LVC-3Z LVC-6Z LVC-3Z LVC-6Z LVC-3D LVC-6D LVC-3D LVC-6D LVC-3DB LVC-6DB LVC-3DB LVC-6DB
-42��D -42��D -44��D -44��D -42��D -42��D -44��D -44��D -42��D -42��D -44��D -44��D
Rated operation voltage [kV] 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6
Rated voltage Ur[kV] 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2
Rated operational current le[A] 200 400 200 400 200 400
Rated frequency fr[Hz] 50/60
Rated breaking current (kA, O-3min-CO-2min-CO) 4
Rated short-time current (kA-sec) 2.4kA-30s, 4kA-10s, 6kA-2s, 6.3kA-1s, 8kA-0.5s, 10kA-0.1s
Rated short-time peak current (kApeak- 0.5Cycle) 60
Switching frequency(AC3) [op./hr] E : Continuous 1200, L : Instantaneous 300
Lifetime Mechanical [××10,000operations] E : Continuous 300, L : Instantaneous 50
Electrical [××10,000operations] 30
Impulse withstand Up[kVp] 60
Dielectric strength Ud[kV/1min] 20
Excitation method E : Continuous, L : Instantaneous
Control voltage [V] AC 110V, AC 220V, DC 110V
Auxiliary contact Arrangement Continuous 3a3b, Instantaneous 2a2b 2a2b 2a2b
Current [A] 10 (AC)
Voltage [V] 600max ~ 48min
Max. Applicable Motors [kW] 750 1,500 1,500 3,000 750 1,500 1,500 3,000 750 1,500 1,500 3,000
Transformers [kVA] 1,000 2,000 2,000 4,000 1,000 2,000 2,000 4,000 1,000 2,000 2,000 4,000
Capacitors [kVA] 750 1,500 1,200 2,000 750 1,500 1,200 2,000 750 1,500 1,200 2,000
Weight [kg] 24 41 56
Note) 6a6b is available for Fixed/Ordinary operating type
www.dienhathe.xyz
www.dienhathe.vn
9
Standard Type
Rated
Rated current(A)
Diameter Length
voltage(kV) (mm) (mm)
LFL-3/6G-��B 3.6/7.2 5,10,20,30,40,50,63,75,100 192
DIN type
LFL-3/6G-��B 3.6/7.2 125Note1)
45
292
LFL-3G-��B 3.6 160, 200 292
LFL-6G-��B 7.2 160, 200 292
LFL-3/6G-�� 3.6/7.2
5(T1.5), 10(T3), 20(T7.5), 30(T15), 40(T20), 50(T30), 60(T30) 50 261
75(T50), 100(T75) 60 311
General
LFL-3G-�� 3.6
150(T100), 200(T150) 60 311
use
300(T250), 400(T300) 77 311
LFL-6G-�� 7.2 150(T100), 200(T150) 77 311
KS type M20, M50, M100 60 200
LFL-3M-�� 3.6 M150, M200 77 200
For M300(M400)Note2) 87 250
motors M20, M50 60 311
LFL-6M-�� 7.2 M100, M150 ,M200 77 350
M300(M400)Note2) 87 450
Note1) VC linkage is prohibited by using fuse checker when the fuse rated current is over 100A.
Note2) It have to be discussed with manufacturer when you applied M440.
� LFL-6G-300, 400 is not possible to combine with VC
Note) Load capacity is different from ratings of Power Fuse
Power fuse ratings combination type
Combination drawout (G) type Combination direct-drawout (GB) type - for MCSG
Type LVC-3G LVC-6G LVC-3G LVC-6G LVC-3GB LVC-6GB LVC-3GB LVC-6GB
-42��D -42��D -44��D -44��D -42��D -42��D -44��D -44��D
Rated operation voltage [kV] 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6
Rated voltage Ur[kV] 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2
Rated operational current le[A] 200 400 200 400
Rated frequency fr[Hz] 50/60
Rated breaking current (kA, O-3min-CO-2min-CO) 4 kA (40kA with fuse)
PF Combination Making 40kA
Rated breaking Breaking 40kA
current
take over(O-3min-O-3min-O) 4kA
Rated short-time current (kA-sec) 2.4kA-30s, 4kA-10s, 6kA-2s, 6.3kA-1s, 8kA-0.5s, 10kA-0.1s
Rated short-time peak current (kApeak- 0.5Cycle) 60
Switching frequency(AC3) [op./hr] E : Continuous 1200, L : Instantaneous 300
Lifetime Mechanical [××10,000operations] E : Continuous 300, L : Instantaneous 50
Electrical [××10,000operations] 30
Impulse withstand Up[kVp] 60
Dielectric strength Ud[kV/1min] 20
Excitation method E : Continuous, L : Instantaneous
Control voltage [V] AC 110V, AC 220V, DC 110V
Auxiliary contact Arrangement 2a2b
Current [A] 10 (AC)
Voltage [V] 600max ~ 48min
Weight [kg] 46 62
www.dienhathe.xyz
www.dienhathe.vn
Ordering information
10
Installation
Z Fixed type
D Drawout type
G Combination drawout type
(Fuse connectable)
DB Direct-drawout type
(For MCSG)
Combination direct-
GB drawout type
(Fuse connectable
and for MCSG)
Contactor
LS Vacuum
Contactor
Ratedvoltage(kV)
3 3.6
6 7.2
Ratedcurrent(A)
2 200
4 400
Breakingcurrent(kA)
4 4
ModificationNo.
D Tri-MEC
Controlmethod
E
Continuous
excitation
L
Instantaneous
excitation
Fusechecker
0 Without
1 With
PT
0 Without PT
1 1EA of 100Var
2 2EA of 100Var
3 1EA of 200Var
4 2EA of 200Var
Control voltage(V)
D1 DC 110
A1 AC 110
A2 AC 220
FUSE type
01 LFL-3/6G-5~60 L261-∅50
02 LFL-3M-20~100 L200-∅60
LFL-3/6G-75~100 L311-∅60
03 LFL-3G-150~200
LFL-6M-20~50
04 LFL-3M-150~200 L200-∅77
05
LFL-3G-300~400 L311-∅77
LFL-6G-150~200
06 LFL-6M-100~200 L350-∅77
07 LFL-3M-300 L250-∅87
08 LFL-6M-300 L450-∅87
09 LFL-3/6G-5B~100B L258-∅45
10 LFL-3/6G-125B~200B L358-∅45
Contactor type
Position Switch
0 Without
1 With
www.dienhathe.xyz
www.dienhathe.vn
11
Cradle
LS Vacuum
Contactor
Mechanical
Interlock
Vacuum Contactor
(VC1)
Position Switch
PS1 1a1b
PS2 2a2b
Cradle Type
E E class
F F2 class (with shutter only)
G G class (with shutter and bushings)
B For MCSG
RatingsLS Cradle
Breaking current
4kA
Rated current
200/400A common
Ratedvoltage(kV)
3/6
3.6/ 7.2kV
common 42
/
44
Mechanical interlock type
32E LVC-3Z-42ED
34E LVC-3Z-44ED
62E LVC-6Z-42ED
64E LVC-6Z-44ED
32L LVC-3Z-42LD
34L LVC-3Z-44LD
62L LVC-6Z-42LD
64L LVC-6Z-44LD
Control voltage(V)
D1 DC 110V
A1 AC 110V
A2 AC 220V
Control voltage(V)
D1 DC 110V
A1 AC 110V
A2 AC 220V
Vacuum Contactor
(VC2)
32E LVC-3Z-42ED
34E LVC-3Z-44ED
62E LVC-6Z-42ED
64E LVC-6Z-44ED
32L LVC-3Z-42LD
34L LVC-3Z-44LD
62L LVC-6Z-42LD
64L LVC-6Z-44LD
www.dienhathe.xyz
www.dienhathe.vn
External view
12
�
�
�
�
�
�
�
�
�
�
�
�
�
� � �
�
�
�
�
�
�
�
�
�
�Front cover
�Fuse checking window
�Connector
�Unlock button(Interlock lever)
�Handle(Draw-in and Drawout)
�ON/OFF indicator
�Operation counter
�Manual trip button
�Drawout carrier
�Direct drawout carrier
�Interlock lever
�Interlock button
�Hole for Interlock lever insertion
� Test/Run indicator
� Cradle
� CTD(Condensor trip device)
� Fuse case
www.dienhathe.xyz
www.dienhathe.vn
13
Safety components
CTD is built as standard in the contactor
with AC control of instantaneous
excitation so that the contactor can be
tripped within 30 seconds in the event of
an electricity failure. The automatic trip
circuit in the event of an electricity failure
is to be built by a customer.
Rating Description
Type CTD-100 CTD-200
Ratedinputvoltage(V) AC 100/110 AC 200/220
Frequency(Hz) 50/60 50/60
Ratedimpulsevoltage(V) 140/155 280/310
Chargingtime Within5sec. Within5sec.
Tripcommand
Max.30sec. Max.30sec.
possibletime
Inputvoltagerange 85%~110% 85%~110%
Capacitorrating(μμF) 400 160
Dimensions
AC input DC output
(For discharge)
Control circuit diagram Terminal
Handle
It is a bent-lever to actuate a direct-
drawout carrier by inserting and turning
in DB and GB type contactors
Fuse checking window
Enables the visible check of a fuse like its
outside status and temperature-rise in a
fuse combination type contactor.
ON/OFF indicator
To visiblly check whether power is
supplied or not
Counter
This is a ON/OFF operation counter by
using 5 digit.
CTD(Condensor Trip Device)
Test/Run position indicator
This enables checking contactor
positions visibly when connecting or
disconnecting a contactor.
Note) Applied direct drawout type only.
Fuse case
Made of high strength BMC resin to offer
superior insulation and safety.
Note) Applied fuse combination type.
Bushing
It is mono-block bushing to be used in
the cradles of G-type drawout
contactors. It provides high insulation
level, so recommended to use in
contactors for MCSG.
Note) Applied G-Class Cradle.
Direct-drawout carrier
It is a screw-sliding type drawout
equipment to draw-in and draw-out a
contactor directly out of a panel for
personal safety. It is built in DB and GB
type contactors.
1 2 3 4 5 6
7 8 9 10 11 12
www.dienhathe.xyz
www.dienhathe.vn
Internal structure
14
Main contact part
Consists of vacuum interrupters, main terminals and moving shunts that are supported
by a one-moulded frame that maintains insulation between phases. Vacuum
interrupters are operated by means of the actuating mechanism that is connected to
movable parts of a vacuum interrupter with a insulation rod.
Actuating mechanism
Designed simply without any linkage to be suited for frequent-operation and long
service life. The actuating lever connected to a moving core of a actuating magnet
that carrys out the function of a actuating shaft moves up and down to control the
contact pressure for stable operations.
Control method
Continuous excitation - During a contactor is closed the control coil is required to be
excited continuously to pull the moving core magnetically. In
case of discontinuing the control power the moving core is to
be returned by a spring because of the disappearance of
magnetic force, which causes the opening of a contactor.
Instantaneous excitation - In this method the continuous exciting of a control coil to
maintain the closing of a contactor is not required as the
latch built in it holds the mechanism. In case of manual
tripping, a contactor will be tripped by releasing the latch
when turn on the manual trip button.
Protection cover
Line terminal
Insulation
mold frame
Load terminal
Shunt
Control coil
Return spring
Spring guide Spring spacer
Vacuum
interrupter
Insulation rod
Contact spring
Actuating lever
Fixed core
Moving core
Latch mechanism
Main contact part
Instantaneous excitationContinuous excitation
Type Controlmethod
Control voltage Closingcurrent(A)/ Tripcurrent(A)/ Holdingcurrent(A)/ Pick-up Drop-out Tripping
(V) time(ms) time(ms) time(ms) voltage voltage voltage
DC 110 3/100 - 0.6/40
AC 110 3/100 - 0.6/40 85% 75% -
AC 220 2/100 - 0.3/40
DC 110 4.5/145 3/35 -
AC 110 4.5(6)/145 3(4)/35 - 85% 75% 10%~75%
AC 220 3(4)/145 10(14)/35 -
Note) The values in ( ) are maximum allowable currents in case of using CTD. (voltage increment considered)
LVC-3/6��-
42/44ED
Continuous
excitation(E)
Instantaneous excitation(L)
Instantaneous excitation(L)
(With CTD)
LVC-3/6��-
42/44LD
www.dienhathe.xyz
www.dienhathe.vn
15
Vacuum interrupters
Features
Vacuum interrupters
In the closed position, normal current flows
through the interrupter. When a fault occur
and interruption is required, the contacts are
quickly separated. The are which is oriented
between surfaces of contact shall diffuse at
the contact structure of flat shape. It prevents
local heating and damage. The arc burns in
an ionized metal vapor, which condenses on
the surrounding metal shield.
The arc is extinguished and vapor production
is ceased at current zero. The metal vapor
plasma is very rapidly dispersed, cooled,
recombined, and deionized, and the metal
vapor products are quickly condensed so that
the contacts withstand the transient recovery
voltage.
LS vacuum interrupters consists of spiral contact,
the material of which is CuCr to provide a long service life and
high withstand voltage characteristic.
Ratings
Voltage phenomena
(i) Arc re-ignition
(ii)Restrikes
(iii) B.I.L
(iv) A.C.voltage withstand
(i) Weld
(ii) Bridge explosion
(i) Contact jets
(ii) Shield involvement
(i) Arc instability
(ii) Interruption
Current zeroArc initiation High current arc mode
Time (ms) Time (㎲)
Fault
current
Recovery voltage
Moving electrode
Moving electrode terminal
Bellows
Bellows shield
Ceramic
Arc shield
Contact
Fixed electrode terminal
Fixed electrode
Internal structureExternal view
Fixed electrode
Dimensions
AC arcing and interruption phenomena in vacuum
Ratedvoltage 7.2
Ratedcurrent 400
Ratedinterruptingcurrent 4.5
Contactstroke 4.75
Openingspeedaverage 0.6
Closingspeedaverage 0.3
Contactforce 7Min
Movingsideweight 0.23
Interrupterweight 0.52
Max.contacterosion 1
(kV)
(A)
(kA)
(mm)
(m/s)
(m/s)
(kg)
(kg)
(kg)
(mm)
www.dienhathe.xyz
www.dienhathe.vn
Accessories
16
3300/6600 110/220 1 100/200 50/60
Ratedvoltage(V) Secondaryvoltage(V) Class Burden(Var) Frequency(Hz)
Fuse checker / Micro switch
PT(Potential transformer)
Fuse clip
Auxiliary switch
Fuse checker / Micro switch
Fuse checker is operated in case of fuse blowing and output
mechanical signal at same time. A micro switch is a part of
fuse checker. The mechanical input signal is changed to
electrical out signal by micro switch.
Note) 19-20 : NO contact, 19-21 : NC contact
PT(Potential transformer)
2 each of PTs can be mounted on drawout type contactors and fuse
combination type.
These are 100VA and 200VA PTs rated 3.6/7.2kV.
Fuse clip
It is used to install or uninstall a fuse link to the holder.
Its dimensions depend on ratings.
Note) Refer to fuse selection table on page 11.
Auxiliary switch
Auxiliary switches are 2NO+2NC as standard and additional 3NO+3NC can
be added on request.
Position switch
This enables checking contactor positions when draw-in and draw-out.
Remote checking is also possible through signaling via micro switches in each
position.
(Com)
(NO) (NC)
www.dienhathe.xyz
www.dienhathe.vn
17
Drawing operations
Unlock
button
Interlock
plate
Unlock pin
Unlock
button
Unlock
plate
Cradle
Cradle
108mm(Stroke)
Interlock
lever
Interlock
button
A hole for a
drawout lever
Cradle
Interlock
lever
Interlock
button
A hole for a
drawout lever
Cradle
Unlock
Unlock
Unlock pin
Details of TEST/RUN Position
<TEST Position>
<RUN Position>
<TEST Position>
<RUN Position>
For standard draw-out types (D, G)
■■ When draw-in a contactor into a cradle.
1. Check that the contactor is in the state of open (TEST Position).
2. While pushing the unlock push button, insert the contactor about 50mm into the
cradle.
3. Release the unlock push button and push the contactor into the cradle by the
RUN position.
■■ When draw-out a contactor from a cradle.
1. Check that the contactor is in the state of open (RUN Position).
2. While pushing the unlock push button, draw the contactor about 50mm out of
the cradle.
3. Release the unlock push button and pull the contactor from the cradle by the
TEST position.
For direct draw-out types (DB, GB)
■■ When draw-in a contactor into a cradle.
1. Check that the contactor is in the state of open (TEST Position).
2. While pushing the both sides of Interlock handle to the direction of the arrows,
insert the contactor about 50mm into the cradle.
3. Insert the drawout lever into a hole as shown in the fig. While pushing the
Interlock push button, swing the lever clockwise two times and release the
Interlock push button.
4. Turning the lever clockwise until the contactor reaches in the RUN position.
■■ When draw-out a contactor from a cradle.
1. Check that the contactor is in the state of open (RUN Position).
2. Insert the drawout lever into a hole as shown in the fig. While pushing the
Interlock push button, swing the lever counterclockwise two times and release
the Interlock push button.
4. Turning the lever counterclockwise until the contactor reaches in the TEST
position.
5. In case of separating the contactor from the cradle pull the contactor while
pushing the both sides of Interlock handle to the direction of the arrows as
shown in the fig.
Note) Check the power before connecting or disconnecting.
www.dienhathe.xyz
www.dienhathe.vn
Electrical circuit diagram
18
Continuous excitation
DC control
Fixed type (Continuous excitation)
AC control
�R : Holding resistance
�CC: Input Coil
�VZb: Assistance Switch b contact (time-delayed type)
Note1) 1,2 terminal is for power supply
Note2) 3,4 point is for Open/Close of contact point
Note3) Point line(---) is user wiring
�R: Holding resistance
�CC: Input Coil
�VZb: Assistance Switch b contact (time-delayed type)
Note1) 1,2 terminal is for power supply
Note2) 3,4 point is for Open/Close of contact point
Note3) Point line(---) is user wiring
www.dienhathe.xyz
www.dienhathe.vn
19
Fixed type (Instantaneous excitation)
Instantaneous excitation
DC control
AC control(CTD equipped)
�CC: Input coil
�TC: Trip Coil
�VZb: Assistance switch b contact
�VZa: Assistance switch a contact
Note1) Close the CB by using 4(+), 2(-) terminal
Note2) Trip by using 5(+), 2(-) terminal
Note3) Contactor is not working when the reverse contact.
Note4) Point line(---) is user wiring
�CC: Input coil
�TC: Trip Coil
�VZb: Assistance switch b contact
�VZa: Assistance switch a contact
�CTD: Condenser Trip unit
Note1) 1~2 terminal is for power supply
Note2) Close the CB by using 3~4 terminal
Note3) Trip by using 5~15 terminal.
Note4) Point line(---) is user wiring
www.dienhathe.xyz
www.dienhathe.vn
Internal connection diagrams
20
Continuous excitation
DC control
(Com)
(NO) (NC)
(Com)
(NO) (NC)
Drawout type (Continuous excitation)
AC control
�R: Holding resistance
�CC: Input Coil
�VZb: Assistance Switch b contact (time-delayed type)
�M: Microswitch for interlock
Note1) 1,2 terminal is for power supply
Note2) 3,4 point is for Open/Close of contact point
Note3) Point line(---) is user wiring
�R: Holding resistance
�CC: Input Coil
�VZb: Assistance Switch b contact (time-delayed type)
�M: Microswitch for interlock
Note1) 1,2 terminal is for power supply
Note2) 3,4 point is for Open/Close of contact point
Note3) Point line(---) is user wiring
www.dienhathe.xyz
www.dienhathe.vn
21
Drawout type (Instantaneous excitation)
Instantaneous excitation
DC control
(Com)
(NO) (NC)
(Com)
(NO) (NC)
AC control(CTD equipped)
�CC: Input Coil
�TC: Trip Coil
�VZb: Assistance switch b contact
�VZa: Assistance switch a contact
�M: Microswitch for interlock
Note1) Close the CB by using 4(+), 2(-) terminal
Note2) Trip by using 5(+), 2(-) terminal
Note3) Point line(---) is user wiring
Note4) Contactor is not working when the reverse contact.
�CC: Input Coil
�TC: Trip Coil
�VZb: Assistance switch b contact
�VZa: Assistance switch a contact
�CTD: Condenser Trip unit
�M: Microswitch for interlock
Note1) 1~2 terminal is for power supply
Note2) Close the CB by using 3~4 terminal
Note3) Trip by using 5~15 terminal.
Note4) Point line(---) is user wiring
www.dienhathe.xyz
www.dienhathe.vn
22
Connection diagrams
Instantaneous excitation
DC
CC TC
CC TC
12
13
14
4
5
2
1
10
9
8
7
12
13
14
4
5
1
2
10
9
8
7
11
11
AUX S/W 1
AUX S/W 2
17
13
A
B
A
B
A
A2
14
43
44
11
7
11
15
14
9
13
27
x Relay
x
13
A A2
14
43
44
x Relay
x
12
5
8
24
10
14
4
26
25
24
23
22
21
16
15
14
13
12
11
17
11
7
11
15
14
9
13
27
12
5
8
24
10
14
4
26
25
24
23
22
21
16
15
14
13
12
11
VC2
VC1
<2a2b>
<2a2b>
AC
AC
AC
AC
<2a2b>
<2a2b>
CC
CC TC
TC
CTD
C6C5C3C1
12
13
14
154
5
7
1
2
3
5
1
2
3
8
9
7
9
10987 1211
1 2 3 4 5 6
10987 1211
1 2 3 4 5 6
CTD
C6C5C3C1
10
11
12
13
14
154
8
10
11
AUX S/W 1
AUX S/W 2
B
B
A
A
13
A A2
14
43
44
x Relay
x
13
A A2
14
43
44
x Relay
x
17
16
15
14
13
12
11
11
7
11
15
14
9
13
12
5
8
27
26
25
24
23
22
21
24
10
14
4
17
16
15
14
13
12
11
11
7
11
15
14
9
13
12
5
827
26
25
24
23
22
21
24
10
14
4
+
~
~
-
+
~
~
Z
Z
-
VC2
VC1
Mechanical interlock type (Instantaneous excitation)
AC (With CTD)
www.dienhathe.xyz
www.dienhathe.vn
23
4
4
CCCC
10
9
12
11
6
5
2
(-)
Vzb1
R
DC
(+)
31
Vzb2
1614
1513
Vzb1
Vzb2
1513
14 1612
119
106
1 3
(+)
DC
(-)
2
5
R
CCCC
13
12
2
3
1
11
10
9
4
5
6
14
15
16
13
12
2
3
1
11
10
9
4
5
6
14
15
16
<3a2b>
<3a2b>
ON
OFF
ON
OFF
R
AC
Vzb1
CC CC
1
AC
Vzb2
3 4
ON
OFF
106 12 14
Vzb2
R
Vzb1
OFF
ON
CCCC
5 119 13
1
2
2
43
16
15
5
6
9 11
1210
13
14
15
16
13
12
2
3
1
11
10
9
4
5
6
14
15
16
13
12
2
3
1
11
10
9
4
5
6
14
15
16
<3a2b>
<3a2b>
CC
CC CC
CC CC
CC
CC CC
12
13
14
154
5
6
1
2
3
10
9
5
6
1
2
3
9
11
16
12
13
14
154
10
11
16
AUX S/W 1
AUX S/W 2
B
A
B
A
B
A
B
A
B
A
B
A
B
A
B
A
17
R11 R21
R22R R2R12
R11 R21
R22R R2R12
16
15
14
13
12
11
11
5
11
15
14
9
13
12
6
16
24
14
10
27
26
25
24
23
22
21
17
16
15
14
13
12
11
11
11
15
14
9
13
12
5 6
16
24
14
10
27
26
25
24
23
22
21
VC2
VC1
CC CC
CC CC
12
13
14
154
1
2
3
5
6
10
9
1
2
3
5
6
9
11
16
12
13
14
154
10
11
16
AUX S/W
AUX S/W
B
A
B
A
B
A
B
A
CC CC
CC CC
B
A
B
A
B
A
B
A
R2
R22R12
R1
R R
R2
R22R12
R1
R R
17
16
15
14
13
12
11
11
15
14
9
13
11
12
5 6
16
24
10
14
27
26
25
24
23
22
21
17
16
15
14
13
12
11
11
15
14
9
13
11
12
5 6
16
24
10
14
27
26
25
24
23
22
21
+
~
~
Z -
+
~
~
Z -
VC2
VC1
Mechanical interlock type (Continuous excitation)
Continuous excitation
DC
AC
www.dienhathe.xyz
www.dienhathe.vn
External dimensions
24
〔〔Unit : mm〕〕
Mounting hole
(Terminal hole)
Mounting hole
(Terminal hole)
Drawout type w/o a cradle
LVC-3/6D-42/44E(L)D
Combination drawout type
w/o a cradle (Fused combination)
LVC-3/6G-42/44E(L)D
Fixed type
LVC-3/6Z-42/44E(L)D
www.dienhathe.xyz
www.dienhathe.vn
25
Mounting hole
(Terminal hole)
(Terminal hole)
Mounting hole
(Terminal hole)
(Terminal hole)
Mounting hole
(Terminal hole)
(Terminal hole)
F2-Class Cradle
G-Class Cradle
〔〔Unit : mm〕〕Drawout type
E-Class Cradle
www.dienhathe.xyz
www.dienhathe.vn
External dimensions
26
Combination drawout type
(Fused combination)
F2-Class Cradle
G-Class Cradle
4-∅14
670(Terminal hole)
617.4
340(Terminal hole)
439
105
76.7
95
503.6
820
319.3
90
RUN(672)
165
160
6
20
RUN(742):6M-300 Fuse
TEST(108)
TEST(108)E-Class Cradle
4-∅14 670(Terminal hole)
617.4
439
340(Terminal hole)
105
95
76.7
559
821.6
319.3
90RUN(672)
188
20
6
160
TEST(108)
TEST(108) RUN(742):6M-300 Fuse
〔〔Unit : mm〕〕
4-∅14 670(Terminal hole)
617.4
105
439
340(Terminal hole)
95
76.7
559
821.6
319.3
90
188
160
6
20
RUN(672)TEST(108)
TEST(108) RUN(742):6M-300 Fuse
www.dienhathe.xyz
www.dienhathe.vn
27
G-Class Cradle
Direct-drawout type
(For MCSG)
Mechanical Interlock type
RUN(672)TEST(108)
TEST(108) RUN(742):6M-300 Fuse
188
4- 14
90
559
617.4
340(Terminal hole)
439
76.7
95 670(Terminal hole)
821.6
299.3200
20
6
∅
ON
〔〔Unit : mm〕〕
www.dienhathe.xyz
www.dienhathe.vn
Selection tables
28
Rated
voltage
(kV)
Fuselink
Rated
current
(A)
Rated
interrupting
current
(kA)
Lowest
interrupting
current
(A)
Transformerload(kVA)
Singlephase Threephase
Fuseselectionbyload
Capacitiveload(kVA)
Threephase
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3/6G -
LFL - 3G -
LFL - 3G -
LFL - 6G -
LFL - 6G -
5B
10B
20B
30B
40B
50B
60B
75B
100B
125B
160B
200B
160B
200B
3.6
(7.2)
3.6
7.2
40 4In
5
10
20
30
40
50
63
75
100
125
160
200
160
200
( 8 ~ 16 )
( 13 ~ 25 )
( 30 ~ 62 )
( 40 ~ 84 )
( 80 ~ 165)
( 98 ~ 204)
(132 ~ 275)
(134 ~ 330)
(256 ~ 440)
(302 ~ 550)
( - )
( - )
(425 ~ 704)
(437 ~ 880)
※4 ~ 8
6 ~ 13
15 ~ 31
21 ~ 42
40 ~ 82
49 ~102
66 ~137
68 ~165
128 ~220
151 ~275
211 ~352
265 ~440
-
-
( 13 ~ 28 )
( 21 ~ 44 )
( 51 ~ 107)
( 70 ~ 145)
(137 ~ 286)
(170 ~ 354)
(229 ~ 476)
(233 ~ 571)
(443 ~ 762)
(522 ~ 952)
( - )
( - )
(735~1,220 )
(755~1,520 )
※
※
6.7 ~ 14
11 ~ 22
25 ~ 53
35 ~ 73
69 ~143
85 ~117
114 ~238
117 ~285
222 ~381
261 ~476
365 ~610
495 ~762
-
-
( 9.8up to )
( 19 ~ 24 )
( 24 ~ 61 )
( 61 ~ 92 )
( 92 ~ 128)
(128 ~ 163)
(163 ~ 210)
(210 ~ 300)
(300 ~ 445)
(445 ~ 550)
( - )
( - )
(550~742 )
(742~1,000 )
※9.8up to
9.8 ~ 12
12 ~ 31
31 ~ 46
46 ~ 64
64 ~ 81
181 ~105
105 ~150
150 ~222
222 ~275
275 ~370
370 ~550
-
-
Rated
voltage
(kV)
Fuselink
Rated
current
(A)
Rated
interrupting
current
(kA)
Lowest
interrupting
current
(A)
Transformerload(kVA)
Singlephase Threephase
Fuseselectionbyload
Capacitiveload(kVA)
Threephase
5
10
20
30
40
50
63
75
100
150
200
300
400
150
200
300
400
20
50
100
150
200
300
400
20
50
100
150
200
300
400
-
-
-
-
-
-
-
-
-
-
-
-
-
-
- ( 5upto )
10upto ( 15upto )
20upto ( 50upto )
30upto ( 75upto )
50upto ( 100upto )
75upto ( 150upto )
- ( - )
150upto ( 200upto )
200upto ( 400upto )
300upto ( - )
400upto ( - )
625upto ( - )
750upto ( - )
- ( 500upto )
- ( 750upto )
- (1,250upto)
- ( - )
※ 5upto ( 15upto )
15upto ( 30upto )
30upto ( 75upto )
75upto ( 150upto )
100upto ( 200upto )
150upto ( 300upto )
- ( - )
200upto ( 400upto )
375upto ( 750upto )
500upto ( - )
750upto ( - )
1,000upto ( - )
1,500upto ( - )
- (1,000upto)
- (1,500upto)
- (2,000upto)
- (2,500upto)
※ - ( - )
10upto ( 25upto )
30upto ( 50upto )
50upto ( 100upto )
75upto ( 150upto )
100upto ( 200upto )
- ( - )
200upto ( 400upto )
300upto ( 600upto )
400upto ( - )
600upto ( - )
1,000upto ( - )
- ( - )
- ( 800upto )
- (1,200upto)
- ( - )
- ( - )
※
50upto ( - )
150upto ( - )
300upto ( - )
400upto ( - )
800upto ( - )
1,000upto ( - )
- ( - )
- ( 100upto )
- ( 300upto )
- ( 600upto )
- ( 800upto )
- ( - )
- ( - )
- ( - )
※
40 5In
3.6
(7.2)
3.6
7.2
G(General use)
type
M(Motorprotection)type
3.6
7.2
40 7In
Application
Model
Application
Model
DIN type
KS type
LFL -3/6G - 5
LFL - 3/6G - 10
LFL - 3/6G - 20
LFL - 3/6G - 30
LFL - 3/6G - 40
LFL - 3/6G - 50
LFL -3/6G - 60
LFL - 3/6G - 75
LFL -3/6G -100
LFL - 3G -150
LFL - 3G -200
LFL - 3G -300
LFL - 3G -400
LFL - 6G -150
LFL - 6G -200
LFL - 6G -300
LFL - 6G -400
LFL - 3M - 20
LFL - 3M - 50
LFL - 3M -100
LFL - 3M -150
LFL - 3M -200
LFL - 3M -300
LFL - 3M -400
LFL - 6M - 20
LFL - 6M - 50
LFL - 6M -100
LFL - 6M -150
LFL - 6M -200
LFL - 6M -300
LFL - 6M -400
www.dienhathe.xyz
www.dienhathe.vn
29
Selecting conditions and warning
1. ※ The values in ( ) apply to the loads of 7.2kV.
2. It is assumed that the inrush current of a transformer is
10 times of the full load current of a motor for 0.1
second.
- The rated current of a fuse is selected to carry
continuously the current of 1.5 times of rated current
of a transformer.(1.3 times in the case of ※)
- In the transformer load table it is assumed that the
interruption will be made at 25 times of rated current
within 2 seconds.
3. It is assumed that the inrush current of a motor is 5
times of full load current for 10 seconds.
4. In the case of using the M(motor protection) type
fuses for the purpose of the short-circuit protection of
a motor or a starter select the proper rating in
addition refer to the characteristic curves on the
catalog to make the device protected from
overload by a circuit breaker or a contactor.
5. It is assumed that the inrush current of a capacitor is
71 times of its rated current for 0.002 second.
- The rated current of a fuse is selected to carry
continuously the current of 1.43 times of rated
current of a capacitor.
- In case service life of more than 1000 operations is
required select in the M( motor protection) type fuse
table.
6. The above mentioned comments are according to
KS(Korean Industrial Standard) and subject to the real
situation.
Motorload(kVA)
Threephase
Dimensions(mm)
Applicableholder
A B C D
195 55 - -
LFH-6G-D1HB
192 77 - -
292 77 - - LFH-6G-D2HB
Fuseselectionbyload
( 13 ~ 22 )
( 22 ~ 36 )
( 36 ~ 86 )
( 86 ~ 117)
(117 ~ 230)
(230 ~ 284)
(276 ~ 382)
(362 ~ 503)
(469 ~ 739)
(556 ~ 870)
( - )
( - )
(751~1,223 )
(1,154~1,760 )
※6.5 ~10.7
10.7~ 28
28 ~ 57
50 ~ 85
85 ~115
115 ~142
138 ~191
181 ~252
253 ~369
293 ~435
343 ~572
375 ~630
-
-
Motorload(kW)
Threephase
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Fuseselectionbyload
DIN-Type fuse
Dimensions(mm)
Applicableholder
A B C D
261 50 47 25 LFH-6G-D60
311 60 57 30 LFH-6G-D1H
311 77 73 43 LFH-6G-D2H
350 110 108 55 LFH-6G-D4H
200 60 58 30 LFH-3M-100
200 77 73 43 LFH-3M-200
250 87 84 50 LFH-3M-400
311 60 58 30 LFH-6M-50
350 77 73 43 LFH-6M-200
450 87 84 50 LFH-6M-400
( - )
( - )
( - )
( - )
( - )
( - )
( - )
( 75 ~ 160)
(185 ~ 400)
(450 ~ 800)
(900 ~ 1,250)
( 1,500 )
( 2,500 )
( 3,000 )
※37 ~ 75
90 ~ 200
220 ~ 400
450 ~ 630
710 ~ 800
900 ~1250
1,500
-
-
-
-
-
-
-
www.dienhathe.xyz
www.dienhathe.vn
Power fuse
30
Power fuse
LS Prime-MEC power fuses are designed to protect equipments from fault current such as
short-circuit, and generally used for the protection the circuits of transformers, capacitors
and motors they protect.
For further safety and reliability the elements inside of fuses are made of silver, and high
quality quartzs and and ceramic are used for magnetic rods and tubes, respectively.
LS medium voltage vacuum contactors using LS vacuum interrupters manufactured with
worldclass technology are type tested in LS PT & T that is accredited high power test lab by
worldclass KOLAS. To ensure the performance they, installed in a vacuum contactor, are
tested according to IEC 60282-1 in LS PT & T that is accredited high power test lab by
worldclass KOLAS.
Considerations in application
�Power fuses are suitable for the protection from a short-circuit, Overload current will not
protected.
�Reset or re-use after blowing is not possible. Fuse reset or re-use is not possible after fused
are blown out.
�When the fuses are selected, the inrush currents arising from the starting transformers,
motors, capacitors should be considered.
�When the fuses are selected, their usage and circuit requirements should be considered.
�For the purpose of protection from the fault current below the lowest interrupting current
of the fuse it is desirable to replace it with a fuse having lower interrupting rate or add
other overcurrent relay in series
�Withstand voltage of the circuit should be higher than that of a fuse that protects it.
�If possible, select the fuse whose rated current is much higher than the load current. The
rated current not sufficiently exceeding the normal current of the load may cause
reduction in the service life.
�Replace all three fuses in case of blowing in a fuse.
Determination of the rated current
The rated current of the fuse must be selected properly after examination of the
current/time characteristics of fuses, equipments and the related circuit conditions.
General considerations
�When the fuses are selected the sufficient rated current should be considered to avoid
the deterioration of the fuse element due to sustained load current in the long term.
�The fuse rated current should be higher than the sum of all load currents.
�The estimated overload current should be within the fuse's time/current characteristics.The
estimated overload current should not exceed the allowable overload withstand currents
of the equipment and the number of its events should not exceed 100 times.
�The characteristic curve of a fuse must lie to the right of those of other equipments to be
protected.
�The withstand strength such as permissible let-through current, I²t of the equipments to be
protected must be higher than that of a fuse.
�Coordination of permissible time limit
Protection equipments in the line side < Fuses < Protection equipments in the load side
�Coordination when fuses are used as back-up protection
Permissible let-through current of a fuse < That of a protection equipment
�Use the same rating for all three phases even the differential current between phases
exists.
KERI(24kV)
www.dienhathe.xyz
www.dienhathe.vn
31
Power fuse selection guides
Considerations by the type of load
1. Power fuses for transformer loads
�The fuse with sufficient rated current must be selected to avoid the deterioration of the
fuse element due to permissible overload in the long term.
�The fuse's current/time characteristic should cover the inrush current/time of the
transformer.
�In case of power transformers the symmetrical inrush current must be within 10 times of the
fuse rating and the fuse should withstand at least 0.1second under the condition.
�Fuse rated current ≥ Transformer rated current
�The lowest interrupting current of the fuse < Short circuit current in the primary of the fuse
�In case of protection of two or more transformers
- Fuse rating should be selected on the basis of the phase condition where maximum
current flows.
- In the event of short-circuit in the secondary of the transformer
The lowest interrupting current of the fuse < Short circuit current in the primary of the
transformer
�In case of potential transformers
- When the fuses are selected do not consider the short-circuit happening in the
secondary of the PT, but protecting PT itself and the circuit against the fault in the primary
side.
- Select the fuse with higher rated current than the load current so as not to be damaged
by overcurrent.
- The characteristic curve of a fuse must lie to the right of those of other equipments to be
protected.
- The withstand strength such as permissible let-through current, I²t of the equipments to
be protected must be higher than that of a fuse.
Note) Refer to the general considerations other than the above mentioned.
2. Power fuses for motor loads
�The fuse with sufficient rated current must be selected to avoid the deterioration of the
- fuse element due to permissible overload in the long term.
�The fuse's current/time characteristic should cover the inrush current/time of the motor.
- The inrush current of the motor must be within 5 times of the fuse rating and the fuse
should withstand at least 10 seconds under the condition.
Fuse rated current ≥ Motor full load current
Note) Refer to the general considerations other than the above mentioned.
3. Power fuses for combination with vacuum contactors
�The current at the intersection between a fuse characteristic curve and a contactor
operation curve should greater than the lowest interrupting current of a fuse.
�And the current at the cross point between a fuse curve and a contactor minimum
dropout curve should not greater than the rated interrupting current of a contactor.
Note) Refer to the general considerations other than the above mentioned.
4. Power fuses for capacitor loads
�The fuse with sufficient rated current must be selected to avoid the deterioration of the
fuse element due to permissible overload in the long term.
�The fuse's current/time characteristic should cover the inrush current/time of the
capacitor.
�The size of inrush current depends on whether or not the serial reactors and parallel
capacitors exist.
�The inrush current of the capacitor must be within 70 times of the fuse rating and the fuse
should withstand at least 0.002 second under the condition.
Fuse rated current ≥ Capacitor rated current
�In the case of serial reactor(6%) connected the inrush current must be within 5 times of the
fuse rating and the fuse should withstand at least 0.1 second under the condition
Note) Refer to the general considerations other than the above mentioned.
Power fuses for transformer loads
Power fuses for motor loads
Note) Above picture shows korean
standard type, If you want to order
DIN type fuse, please contact LS
Industrial Systems before you
order it.
www.dienhathe.xyz
www.dienhathe.vn
Coordination graph
32
A.Permissible overload current/time of a transformer
B.Permissible overload characteristic of a transformer, Operation characteristic curve of a Fuse
C.inrush current and time at no load of a transformer
Characteristic curve of a secondary
circuit breaker or low voltage fuse
(Converted into the primary values)
Time
Permissible overload
characteristic curve of a transformer
Time/Current characteristic curve of a Fuse
Blow-out characteristic curve of a Fuse
Operation characteristic curve of a Fuse
[1]
[2]
[3]
[4]
[5]
[6]
Current
Coordination between fuse and transformer circuit
When any protection device is not installed in the secondary
of a transformer
�Permissible overload current of a transformer (point ③)) must lie to the left of the
curve ⓒ(time/current characteristic curve of a Fuse)
Full load current of a transformer ① ≤ Rated current of a fuse ④
�Point C(inrush current and time at no load of a transformer) must lie to the left of
the point ⓒ(time/current characteristic curve of a Fuse)
�Secondary short-circuit current⑧ > Lowest interrupting current of a fuse ⑥
Point B must lie to the left of the secondary short-circuit current⑧.
�Primary short-circuit current⑩ < Rated interrupting current of a fuse⑪
When a circuit breaker or fuse is installed in the secondary of
a transformer
�Must meet the requirements above mentioned in ①
�The characteristic curve of a secondary circuit breaker or low voltage fuse ⓐ
must lie to the left of permissible overload characteristic curve of a transformer ⓑ
and under the point B
�The characteristic curve of a secondary circuit breaker or low voltage fuse ⓐ
must lie to the Time/Current characteristic curve of a Fuse and under the
Secondary short-circuit current ⑧.
�Secondary short-circuit current⑧ < Characteristic curve of a secondary circuit
breaker or low voltage fuse ⓐ
�The secondary circuit breaker or low voltage fuse should meet the above
mentioned requirements to each branch circuit.
�Another medium voltage protection device is required for the ensured protection
against the fault happening between the secondary protection devices and the
internal short-circuit of a transformer in the zone of [3]+[4]+[5].
※※ Coordination in the graph
��Zone of [1] : Protection of primary side from short-
circuit by a fuse
��Zone of [2] : Protection of a transformer
��Zone of [3] : Out of the scope of fuse operation
��Zone of [4] : Interruption is not ensured even
though the fuse blows.
��Zone of [5] : Protection of a transformer is not
ensured even though the fuse
interrupts the circuit.
��Zone of [3]+[4]+[5] : No protection zone of a
transformer Circuit breaker or
low voltage fuse required for
the transformer protection
Fuse
Transformer
Circuit breaker
or low voltage fuse
Full load current of a transformer
The lowest interrupting current of the secondary circuit breaker
Permissible overload current of a transformer
Rated current of a fuse
Lowest blow-out current of a fuse
Lowest interrupting current of a fuse
Inrush current at no load of a transformer
Secondary short-circuit current
Rated interrupting current of a secondary circuit breaker
Primary short-circuit current
Rated interrupting current of a fuse
www.dienhathe.xyz
www.dienhathe.vn
33
Coordination between fuse and motor circuit
The lowest operation characteristic of
a vacuum contactor
(opening characteristic)
Operation characteristic of
a vacuum contactor
Overload characterictic of a motor
Time/Current characteristic curve of a Fuse
Blow-out characteristic curve of a Fuse
Operation characteristic curve of a Fuse
A : (Operation characteristic of a vacuum contactor, Time/Current characteristic curve of a Fuse)
B : (The lowest operation characteristic of a vacuum contactor, Operation characteristic curve of a Fuse )
C : ( Inrush current of a motor, Inrush time of a motor )
Inrush
time of
a motor
Time
Current
�Full load current of a motor① ≤ Rated current of a fuse②
�Short-circuit current⑥ < Rated interrupting current of a fuse⑦
�Inrush current of a motor (Locked rotor current)③ < Rated interrupting current of
a vacuum contactor⑤
�Point C must lie to the left of ⓐ(The lowest operation characteristic of a vacuum
contactor)and ⓓ(Time/Current characteristic curve of a Fuse)
�Operation characteristic of a vacuum contactorⓑ must lie to the left of
ⓒ( Overload characteristic of a motor )
�Point A must lie to the right of ④ Lowest interrupting current of a fuse.
�Point B must lie to the left of ⑤ Rated interrupting current of a vacuum contactor.
Note) The current less than point A can be protected by a vacuum contactor, and the current greater than point B is to
be protected by a fuse.
Fuse
Vacuum
contactor
Motor
Full load current of a motor
Rated current of a fuse
Inrush current of a motor (Locked rotor current)
Lowest interrupting current of a fuse
Rated interrupting current of a vacuum contactor
Short-circuit current
Rated interrupting current of a fuse
www.dienhathe.xyz
www.dienhathe.vn
Operation curves
34
DIN Type
3.6/7.2kV blowing characteristic 3.6/7.2kV current limiting characteristic
3.6kV blowing characteristic 3.6kV current limiting characteristic
7.2kV blowing characteristic 7.2kV current limiting characteristic
Current ( sym, A )
Operationtime(sec)
Current ( sym, A )
Operationtime(sec)
Current ( sym, A )
Operationtime(sec)
Interrupting current ( sym, kA )
Interrupting current ( sym, kA )
Currentlimited(peak,kA)Currentlimited(peak,kA)
Interrupting current ( sym, kA )
Currentlimited(peak,kA)
www.dienhathe.xyz
www.dienhathe.vn
35
KS Type
G(General use) type fuse
M(Motor protection) type fuse
3.6/7.2kV blowing characteristic 3.6/7.2kV current limiting characteristic
3.6kV blowing characteristic 7.2kV blowing characteristic
3.6kV, 7.2kV current limiting characteristic
Current ( sym, A )
Operationtime(sec)
Current ( sym, A )
Operationtime(sec)
Interrupting current ( sym, kA )
Interrupting current ( sym, kA )
Currentlimited(peak,kA)
Currentlimited(peak,kA)
Current ( sym, A )
Operationtime(sec)
www.dienhathe.xyz
www.dienhathe.vn
��For your safety, please read user's manual thoroughly before operating.
��Contact the nearest authorized service facility for examination, repair, or adjustment.
��Please contact qualified service technician when you need maintenance.
Do not disassemble or repair by yourself!
��Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions
��LS Industrial Systems (Middle East) FZE ����Dubai, U.A.E.
Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E.
Tel: 971-4-332-8289 Fax: 971-4-332-9444 e-mail: hwyim@lsis.biz
��Dalian LS Industrial Systems Co., Ltd. ����Dalian, China
Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China
Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn
��LS Industrial Systems (Wuxi) Co., Ltd. ����Wuxi, china
Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.China
Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn
��LS-VINA Industrial Systems Co., Ltd. ����Hanoi, Vietnam
Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam
Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com
��LS Industrial Systems Tokyo Office ����Tokyo, Japan
Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan
Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz
��LS Industrial Systems Shanghai Office ����Shanghai, China
Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China
Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn
��LS Industrial Systems Beijing Office ����Beijing, China
Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District,
Beijing 100013, P.R. China
Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn
��LS Industrial Systems Guangzhou Office ����Guangzhou, China
Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China
Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.com.cn
��LS Industrial Systems Chengdu Office ����Chengdu, China
Address: 12Floor, Guodong Buiding, No52 Jindun Road Chengdu, 610041, P.R. China
Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn
��LS Industrial Systems Qingdao Office ����Qingdao, China
Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China
Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn
�� HEAD OFFICE
Yonsei Jaedan Severance Bldg., 84-11, Namdaemunno 5ga,
Jung-gu, Seoul, 100-753, Korea
Tel. (82-2)2034-4870
Fax. (82-2)2034-4713
�� CHEONG-JU PLANT
Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku,
Cheong Ju, 361-720, Korea
Leader in Electrics & Automation
�� Global Network
www.lsis.biz
Specifications in this catalog are subject to change without notice due to
continuous product development and improvement.
2008. 01 LS Medium Voltage Vacuum Contactors(E) 2003. 04/(12) 2008. 01 Printed in Korea STAFF
ⓒ 2003.4 LS Industrial Systems Co.,Ltd. All rights reserved.
www.dienhathe.xyz
www.dienhathe.vn

More Related Content

What's hot

ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...Thorne & Derrick International
 
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...Thorne & Derrick International
 
Ns125 catalog - schneider-dienhathe.vn
Ns125   catalog - schneider-dienhathe.vnNs125   catalog - schneider-dienhathe.vn
Ns125 catalog - schneider-dienhathe.vnDien Ha The
 
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...Thorne & Derrick International
 
Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)
Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV) Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)
Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV) Thorne & Derrick International
 
Low voltage circuit breakers & contactors general leaflet ls
Low voltage circuit breakers & contactors general leaflet   lsLow voltage circuit breakers & contactors general leaflet   ls
Low voltage circuit breakers & contactors general leaflet lsmaianhbao_6519
 
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersThorne & Derrick International
 
Tecnical aplicacion1 abb
Tecnical aplicacion1 abbTecnical aplicacion1 abb
Tecnical aplicacion1 abbisaac diaz said
 
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03Thorne & Derrick International
 
Electronic timer | Electronic Timer Switch-GIC India
 Electronic timer | Electronic Timer Switch-GIC India Electronic timer | Electronic Timer Switch-GIC India
Electronic timer | Electronic Timer Switch-GIC IndiaPrasadPurohit1988
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learnedmichaeljmack
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersThorne & Derrick International
 

What's hot (16)

ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
ABB POLIM-C..LB Medium Voltage Surge Arresters AC up to 5kV - AC Surge Arrest...
 
Pfisterer KP-Test 5 Voltage Detectors
Pfisterer KP-Test 5 Voltage DetectorsPfisterer KP-Test 5 Voltage Detectors
Pfisterer KP-Test 5 Voltage Detectors
 
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
Pfisterer Continuous Voltage Indicators for Encapsulated Systems - Pfisterer ...
 
Ns125 catalog - schneider-dienhathe.vn
Ns125   catalog - schneider-dienhathe.vnNs125   catalog - schneider-dienhathe.vn
Ns125 catalog - schneider-dienhathe.vn
 
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
ABB POLIM-C..N High Voltage Surge Arresters AC up to 7.5 kV - AC Surge Arrest...
 
Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)
Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV) Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)
Pfiserer HV Connex Surge Arresters - Sizes 4 (72.5kV) & 5-S (145 kV)
 
Low voltage circuit breakers & contactors general leaflet ls
Low voltage circuit breakers & contactors general leaflet   lsLow voltage circuit breakers & contactors general leaflet   ls
Low voltage circuit breakers & contactors general leaflet ls
 
Mv design guide
Mv design guideMv design guide
Mv design guide
 
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
 
Tecnical aplicacion1 abb
Tecnical aplicacion1 abbTecnical aplicacion1 abb
Tecnical aplicacion1 abb
 
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
ABB CLMD Low Voltage Capacitors - ABB LV Capacitors CLMD03
 
Electronic timer | Electronic Timer Switch-GIC India
 Electronic timer | Electronic Timer Switch-GIC India Electronic timer | Electronic Timer Switch-GIC India
Electronic timer | Electronic Timer Switch-GIC India
 
Thông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LSThông số kĩ thuật MCCB LS
Thông số kĩ thuật MCCB LS
 
Thông số bộ đổi nguồn Mean Well, Catalogue Bộ đổi nguồn Mean Well, Meanwell
Thông số bộ đổi nguồn Mean Well, Catalogue Bộ đổi nguồn Mean Well, MeanwellThông số bộ đổi nguồn Mean Well, Catalogue Bộ đổi nguồn Mean Well, Meanwell
Thông số bộ đổi nguồn Mean Well, Catalogue Bộ đổi nguồn Mean Well, Meanwell
 
Electrical Lessons learned
Electrical Lessons learnedElectrical Lessons learned
Electrical Lessons learned
 
Schneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment DesignersSchneider Technical Guide - Medium Voltage Equipment Designers
Schneider Technical Guide - Medium Voltage Equipment Designers
 

Similar to Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn

Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnDien Ha The
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abbDien Ha The
 
Kyn28 metal clad switchgear
Kyn28 metal clad switchgearKyn28 metal clad switchgear
Kyn28 metal clad switchgearJoeChueng
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor correctorJoeChueng
 
Fvc4 vacuum contactor
Fvc4 vacuum contactorFvc4 vacuum contactor
Fvc4 vacuum contactorJoeChueng
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueThorne & Derrick International
 
Fvc8 vacuum contactor
Fvc8 vacuum contactorFvc8 vacuum contactor
Fvc8 vacuum contactorJoeChueng
 
Ls catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vnLs catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vnDien Ha The
 
Ls catalog thiet bi dien electric products e 1104
Ls catalog thiet bi dien electric products e 1104Ls catalog thiet bi dien electric products e 1104
Ls catalog thiet bi dien electric products e 1104Dien Ha The
 
Vb4 s lateral vacuum circuit breaker
Vb4 s lateral vacuum circuit breakerVb4 s lateral vacuum circuit breaker
Vb4 s lateral vacuum circuit breakerJoeChueng
 
Catalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vnCatalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vnDien Ha The
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear StandardsBryan Johnson
 
Cataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guardCataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guardDien Ha The
 
Cataloge ge 2.industrial components_dienhathe.com-2_entelli_guard
Cataloge ge 2.industrial components_dienhathe.com-2_entelli_guardCataloge ge 2.industrial components_dienhathe.com-2_entelli_guard
Cataloge ge 2.industrial components_dienhathe.com-2_entelli_guardDien Ha The
 
Cataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guardCataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guardThuan Kieu
 

Similar to Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn (20)

Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vnCatalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
Catalogue thiet bi dien abb rccb rcbo abb-dienhathe.vn
 
Catalog rccb va rcbo abb
Catalog rccb va rcbo abbCatalog rccb va rcbo abb
Catalog rccb va rcbo abb
 
Kyn28 metal clad switchgear
Kyn28 metal clad switchgearKyn28 metal clad switchgear
Kyn28 metal clad switchgear
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
 
Fvc4 vacuum contactor
Fvc4 vacuum contactorFvc4 vacuum contactor
Fvc4 vacuum contactor
 
36kV high voltage drawout VCB type switchgear
36kV high voltage drawout VCB type switchgear36kV high voltage drawout VCB type switchgear
36kV high voltage drawout VCB type switchgear
 
Epcos 5
Epcos 5Epcos 5
Epcos 5
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices Catalogue
 
Introduction to mv switchgear
Introduction to mv switchgearIntroduction to mv switchgear
Introduction to mv switchgear
 
Fvc8 vacuum contactor
Fvc8 vacuum contactorFvc8 vacuum contactor
Fvc8 vacuum contactor
 
KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
Ls catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vnLs catalog thiet bi dien electric products e 1104_dienhathe.vn
Ls catalog thiet bi dien electric products e 1104_dienhathe.vn
 
Ls catalog thiet bi dien electric products e 1104
Ls catalog thiet bi dien electric products e 1104Ls catalog thiet bi dien electric products e 1104
Ls catalog thiet bi dien electric products e 1104
 
Vb4 s lateral vacuum circuit breaker
Vb4 s lateral vacuum circuit breakerVb4 s lateral vacuum circuit breaker
Vb4 s lateral vacuum circuit breaker
 
Catalog ls lvcb
Catalog ls lvcbCatalog ls lvcb
Catalog ls lvcb
 
Catalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vnCatalog ls lvcb dienhathe.vn
Catalog ls lvcb dienhathe.vn
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards
 
Cataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guardCataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guard
 
Cataloge ge 2.industrial components_dienhathe.com-2_entelli_guard
Cataloge ge 2.industrial components_dienhathe.com-2_entelli_guardCataloge ge 2.industrial components_dienhathe.com-2_entelli_guard
Cataloge ge 2.industrial components_dienhathe.com-2_entelli_guard
 
Cataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guardCataloge ge 2.industrial components-2_entelli_guard
Cataloge ge 2.industrial components-2_entelli_guard
 

More from Dien Ha The

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Dien Ha The
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comDien Ha The
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comDien Ha The
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookDien Ha The
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseDien Ha The
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Dien Ha The
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Dien Ha The
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalogDien Ha The
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbDien Ha The
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Dien Ha The
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsDien Ha The
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter familyDien Ha The
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesDien Ha The
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesDien Ha The
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuDien Ha The
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesDien Ha The
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Dien Ha The
 

More from Dien Ha The (20)

Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)Vnd feb 2020 price list schneider (1)
Vnd feb 2020 price list schneider (1)
 
Resize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.comResize bientanfuji-dienhathe.com
Resize bientanfuji-dienhathe.com
 
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.comFed e-quick-start-up-guide-bientanfuji-dienhathe.com
Fed e-quick-start-up-guide-bientanfuji-dienhathe.com
 
Fed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.comFed e-quick-start-manual-bientanfuji-dienhathe.com
Fed e-quick-start-manual-bientanfuji-dienhathe.com
 
Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019Ls bang gia ls ap dung 20 04-2019
Ls bang gia ls ap dung 20 04-2019
 
Mitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library bookMitsubishi graphic operation terminal got2000 series parts library book
Mitsubishi graphic operation terminal got2000 series parts library book
 
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
Mitsubishi inverter fr-a700-instruction-manualbasic-160425031653
 
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product releaseMitsubishi graphic operation terminal got2000 series gt2103 new product release
Mitsubishi graphic operation terminal got2000 series gt2103 new product release
 
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...Mitsubishi graphic operation terminal got2000 series got mobile function quic...
Mitsubishi graphic operation terminal got2000 series got mobile function quic...
 
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...Mitsubishi graphic operation terminal got2000 series drive control interactiv...
Mitsubishi graphic operation terminal got2000 series drive control interactiv...
 
Mitsubishi inverter option catalog
Mitsubishi inverter option catalogMitsubishi inverter option catalog
Mitsubishi inverter option catalog
 
Mitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcbMitsubishi low voltage ws-v series mccb and elcb
Mitsubishi low voltage ws-v series mccb and elcb
 
Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)Mitsubishi graphic operation terminal got2000 series (concise)
Mitsubishi graphic operation terminal got2000 series (concise)
 
Mitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new modelsMitsubishi low voltage ws-v series comparison of previous and new models
Mitsubishi low voltage ws-v series comparison of previous and new models
 
Mitsubishi inverter inverter family
Mitsubishi inverter inverter familyMitsubishi inverter inverter family
Mitsubishi inverter inverter family
 
Mitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din seriesMitsubishi low voltage miniature circuit breakers din series
Mitsubishi low voltage miniature circuit breakers din series
 
Mitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 seriesMitsubishi inverter freqrol-hc2 series
Mitsubishi inverter freqrol-hc2 series
 
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsuMitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
Mitsubishi low voltage mccb and elcb(ws-v series) y0720-version 1-mitsu
 
Mitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj seriesMitsubishi inverter freqrol-f700 pj series
Mitsubishi inverter freqrol-f700 pj series
 
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
Mitsubishi inverter catalog-mitsubishi-inverter-option-160426021125
 

Recently uploaded

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Christo Ananth
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 

Recently uploaded (20)

Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANJALI) Dange Chowk Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 

Ls catalog thiet bi dien vcs ls medium voltage-vacuum contactor_dienhathe.vn

  • 1. Leader in Electrics & Automation Electric Equipment Tri-MEC LS Medium Voltage Vacuum Contactorswww.dienhathe.xyz www.dienhathe.vn
  • 2. Customer satisfaction through quality and service- LS medium voltage vacuum contactors LS medium voltage vacuum contactors using LS vacuum interrupters manufactured with worldclass technology are type tested in LS PT & T that is accredited high power test lab by worldclass KOLAS. www.dienhathe.xyz www.dienhathe.vn
  • 3. Contents Features 4 Technical data 10 Ordering information 12 External view 14 Safety components 15 Internal structure 16 Vacuum interrupters 17 Accessories 18 Drawing operations 19 Electrical circuit diagram 20 Internal connection diagrams 22 External dimensions 24 Selection tables 28 Power fuse 30 Power fuse selection guides 31 Coordination graph 32 Operation curves 34 www.dienhathe.xyz www.dienhathe.vn
  • 4. General description We have the major technology that others can not catch up. LS vacuum contactors provide high withstand-current strength and switching capacity as well as versatile auxiliary functions. Fixed type Drawout type (Standard type) LS Tri-MEC vacuum contactors are mainly used for the switching of motors, transformers, capacitors in AC power lines. They can be installed in multi-stack cubicles. A vacuum contactor comprises several assemblies such as switching mechanism including vacuum interrupters, magnetic actuator, high strength molded front cover and auxiliary devices. Stable and high operating cycle is executed by the vacuum interrupters made of high alumina ceramic tube which makes it possible to degas in a high temperature with excellent mechanical strength. Actuating is available either at instantaneous or continuous excitation. Functions for safety in connecting and disconnecting are also provided. LS Vacuum Contactors 4 We have the major technology that others can not catch up. LS vacuum contactors provide high withstand-current strength and switching capacity as well as versatile auxiliary functions. www.dienhathe.xyz www.dienhathe.vn
  • 5. Direct-drawout type - for MCSG Fuse connectable type (Standard type) E-Class Cradle F2-Class Cradle G-Class Cradle Fuse connectable type (Direct-drawout type) Operation conditions Ambient temperature : -5 to 40℃ Maximum temperature of 24-hour mean : 35 ℃ Altitude : 1000m Humidity : 24-hour measured average - max. 95% RH 1 month measured average - max. 90% RH Applied standards IEC Pub. 60470, IEC 60282-1, JEM 1167, KEMC 1126 5 www.dienhathe.xyz www.dienhathe.vn
  • 6. [ 40kA ] Power fused type vacuum contactors, in-house tested according to IEC 60282-1, can provide short-circuit protection up to 40kA. Short-circuit protection High performance, high reliability and long service life LS vacuum interrupters that comply with IEC, ANSI and NEMA standards are manufactured by the process of brazing and degasing together in a high vacuum furnace to assure high reliability. Superior mechanical strength and degasing Providing long service life and suited for frequently operating purpose due to using high alumina ceramic tube and degasing in a high temperature. High speed interruption and short arcing time It has fast recovering characteristic of vacuum insulation. When opening it breaks the current at the first current-zero point to minimize the wearing of contacts. Reliable interruption of fault current LS current limiting power fuse can protect the devices and systems from fault current by interrupting within half cycle. High current such as short-circuit current cause a fuse blown out due to the reaction on the material inside of a fuse within such a short time. Applied standards IEC 282-1, DIN 43625, BS 2692, KSC 4612 6 Up-graded performance [ 6.3kA ] Performance is up-graded to rated short-time current 6.3kA/1sec. and switching capacity 4kA according to IEC60470. Rated short-time current 6.3kA [ 6.3kA ] Performance is up-graded to rated short-time current 6.3kA/1sec. and switching capacity 4kA according to IEC60470. Rated short-time current 6.3kA [ 40kA ] Power fused type vacuum contactors, in-house tested according to IEC 60282-1, can provide short-circuit protection up to 40kA. Short-circuit protection www.dienhathe.xyz www.dienhathe.vn
  • 7. 7 Suitable for Metal Clad Switchgear The structure of G type cradle unification bushings and single-molded fuse-holder barrier enables vacuum contactors to build Metal Clad Switchgears. Directly withdrawable equipment This enables the withdrawing of a vacuum contactor from a panel without opening a door to prevent any possibility of electric shock. Interlock For the safety of a operator interlock is equipped as standard. Auxiliary contacts Available up to 5NO+5NC. Contactor over contactor arrangement [ Safety ] LS Tri-MEC vacuum contactors provide several auxiliary functions for safe and comfortable use. [ Safety ] LS Tri-MEC vacuum contactors provide several auxiliary functions for safe and comfortable use. Personnel safety ■■Interlock button ■■Drawout cradle for MCSG ■■One-molded fuse holder ■■Fuse checher and micro switch ■■Unification bushing ■■Mechanical interlock type ■■Interlock button ■■Drawout cradle for MCSG ■■One-molded fuse holder ■■Fuse checher and micro switch ■■Unification bushing ■■Mechanical interlock type Additional equipment www.dienhathe.xyz www.dienhathe.vn
  • 8. Technical data 8 Power fuse Power fuses can be installed into combination(G, GB) type contactors for the protection of equipments and systems from short-circuit. Fuse ratings are selected properly after system analysis and some accessories such as fuse link clips should be selected by the fuse rating. Fixed (Z) type Drawout (D) type Direct-drawout (DB) type - for MCSG Type LVC-3Z LVC-6Z LVC-3Z LVC-6Z LVC-3D LVC-6D LVC-3D LVC-6D LVC-3DB LVC-6DB LVC-3DB LVC-6DB -42��D -42��D -44��D -44��D -42��D -42��D -44��D -44��D -42��D -42��D -44��D -44��D Rated operation voltage [kV] 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6 Rated voltage Ur[kV] 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2 Rated operational current le[A] 200 400 200 400 200 400 Rated frequency fr[Hz] 50/60 Rated breaking current (kA, O-3min-CO-2min-CO) 4 Rated short-time current (kA-sec) 2.4kA-30s, 4kA-10s, 6kA-2s, 6.3kA-1s, 8kA-0.5s, 10kA-0.1s Rated short-time peak current (kApeak- 0.5Cycle) 60 Switching frequency(AC3) [op./hr] E : Continuous 1200, L : Instantaneous 300 Lifetime Mechanical [××10,000operations] E : Continuous 300, L : Instantaneous 50 Electrical [××10,000operations] 30 Impulse withstand Up[kVp] 60 Dielectric strength Ud[kV/1min] 20 Excitation method E : Continuous, L : Instantaneous Control voltage [V] AC 110V, AC 220V, DC 110V Auxiliary contact Arrangement Continuous 3a3b, Instantaneous 2a2b 2a2b 2a2b Current [A] 10 (AC) Voltage [V] 600max ~ 48min Max. Applicable Motors [kW] 750 1,500 1,500 3,000 750 1,500 1,500 3,000 750 1,500 1,500 3,000 Transformers [kVA] 1,000 2,000 2,000 4,000 1,000 2,000 2,000 4,000 1,000 2,000 2,000 4,000 Capacitors [kVA] 750 1,500 1,200 2,000 750 1,500 1,200 2,000 750 1,500 1,200 2,000 Weight [kg] 24 41 56 Note) 6a6b is available for Fixed/Ordinary operating type www.dienhathe.xyz www.dienhathe.vn
  • 9. 9 Standard Type Rated Rated current(A) Diameter Length voltage(kV) (mm) (mm) LFL-3/6G-��B 3.6/7.2 5,10,20,30,40,50,63,75,100 192 DIN type LFL-3/6G-��B 3.6/7.2 125Note1) 45 292 LFL-3G-��B 3.6 160, 200 292 LFL-6G-��B 7.2 160, 200 292 LFL-3/6G-�� 3.6/7.2 5(T1.5), 10(T3), 20(T7.5), 30(T15), 40(T20), 50(T30), 60(T30) 50 261 75(T50), 100(T75) 60 311 General LFL-3G-�� 3.6 150(T100), 200(T150) 60 311 use 300(T250), 400(T300) 77 311 LFL-6G-�� 7.2 150(T100), 200(T150) 77 311 KS type M20, M50, M100 60 200 LFL-3M-�� 3.6 M150, M200 77 200 For M300(M400)Note2) 87 250 motors M20, M50 60 311 LFL-6M-�� 7.2 M100, M150 ,M200 77 350 M300(M400)Note2) 87 450 Note1) VC linkage is prohibited by using fuse checker when the fuse rated current is over 100A. Note2) It have to be discussed with manufacturer when you applied M440. � LFL-6G-300, 400 is not possible to combine with VC Note) Load capacity is different from ratings of Power Fuse Power fuse ratings combination type Combination drawout (G) type Combination direct-drawout (GB) type - for MCSG Type LVC-3G LVC-6G LVC-3G LVC-6G LVC-3GB LVC-6GB LVC-3GB LVC-6GB -42��D -42��D -44��D -44��D -42��D -42��D -44��D -44��D Rated operation voltage [kV] 3.3 6.6 3.3 6.6 3.3 6.6 3.3 6.6 Rated voltage Ur[kV] 3.6 7.2 3.6 7.2 3.6 7.2 3.6 7.2 Rated operational current le[A] 200 400 200 400 Rated frequency fr[Hz] 50/60 Rated breaking current (kA, O-3min-CO-2min-CO) 4 kA (40kA with fuse) PF Combination Making 40kA Rated breaking Breaking 40kA current take over(O-3min-O-3min-O) 4kA Rated short-time current (kA-sec) 2.4kA-30s, 4kA-10s, 6kA-2s, 6.3kA-1s, 8kA-0.5s, 10kA-0.1s Rated short-time peak current (kApeak- 0.5Cycle) 60 Switching frequency(AC3) [op./hr] E : Continuous 1200, L : Instantaneous 300 Lifetime Mechanical [××10,000operations] E : Continuous 300, L : Instantaneous 50 Electrical [××10,000operations] 30 Impulse withstand Up[kVp] 60 Dielectric strength Ud[kV/1min] 20 Excitation method E : Continuous, L : Instantaneous Control voltage [V] AC 110V, AC 220V, DC 110V Auxiliary contact Arrangement 2a2b Current [A] 10 (AC) Voltage [V] 600max ~ 48min Weight [kg] 46 62 www.dienhathe.xyz www.dienhathe.vn
  • 10. Ordering information 10 Installation Z Fixed type D Drawout type G Combination drawout type (Fuse connectable) DB Direct-drawout type (For MCSG) Combination direct- GB drawout type (Fuse connectable and for MCSG) Contactor LS Vacuum Contactor Ratedvoltage(kV) 3 3.6 6 7.2 Ratedcurrent(A) 2 200 4 400 Breakingcurrent(kA) 4 4 ModificationNo. D Tri-MEC Controlmethod E Continuous excitation L Instantaneous excitation Fusechecker 0 Without 1 With PT 0 Without PT 1 1EA of 100Var 2 2EA of 100Var 3 1EA of 200Var 4 2EA of 200Var Control voltage(V) D1 DC 110 A1 AC 110 A2 AC 220 FUSE type 01 LFL-3/6G-5~60 L261-∅50 02 LFL-3M-20~100 L200-∅60 LFL-3/6G-75~100 L311-∅60 03 LFL-3G-150~200 LFL-6M-20~50 04 LFL-3M-150~200 L200-∅77 05 LFL-3G-300~400 L311-∅77 LFL-6G-150~200 06 LFL-6M-100~200 L350-∅77 07 LFL-3M-300 L250-∅87 08 LFL-6M-300 L450-∅87 09 LFL-3/6G-5B~100B L258-∅45 10 LFL-3/6G-125B~200B L358-∅45 Contactor type Position Switch 0 Without 1 With www.dienhathe.xyz www.dienhathe.vn
  • 11. 11 Cradle LS Vacuum Contactor Mechanical Interlock Vacuum Contactor (VC1) Position Switch PS1 1a1b PS2 2a2b Cradle Type E E class F F2 class (with shutter only) G G class (with shutter and bushings) B For MCSG RatingsLS Cradle Breaking current 4kA Rated current 200/400A common Ratedvoltage(kV) 3/6 3.6/ 7.2kV common 42 / 44 Mechanical interlock type 32E LVC-3Z-42ED 34E LVC-3Z-44ED 62E LVC-6Z-42ED 64E LVC-6Z-44ED 32L LVC-3Z-42LD 34L LVC-3Z-44LD 62L LVC-6Z-42LD 64L LVC-6Z-44LD Control voltage(V) D1 DC 110V A1 AC 110V A2 AC 220V Control voltage(V) D1 DC 110V A1 AC 110V A2 AC 220V Vacuum Contactor (VC2) 32E LVC-3Z-42ED 34E LVC-3Z-44ED 62E LVC-6Z-42ED 64E LVC-6Z-44ED 32L LVC-3Z-42LD 34L LVC-3Z-44LD 62L LVC-6Z-42LD 64L LVC-6Z-44LD www.dienhathe.xyz www.dienhathe.vn
  • 12. External view 12 � � � � � � � � � � � � � � � � � � � � � � � � � �Front cover �Fuse checking window �Connector �Unlock button(Interlock lever) �Handle(Draw-in and Drawout) �ON/OFF indicator �Operation counter �Manual trip button �Drawout carrier �Direct drawout carrier �Interlock lever �Interlock button �Hole for Interlock lever insertion � Test/Run indicator � Cradle � CTD(Condensor trip device) � Fuse case www.dienhathe.xyz www.dienhathe.vn
  • 13. 13 Safety components CTD is built as standard in the contactor with AC control of instantaneous excitation so that the contactor can be tripped within 30 seconds in the event of an electricity failure. The automatic trip circuit in the event of an electricity failure is to be built by a customer. Rating Description Type CTD-100 CTD-200 Ratedinputvoltage(V) AC 100/110 AC 200/220 Frequency(Hz) 50/60 50/60 Ratedimpulsevoltage(V) 140/155 280/310 Chargingtime Within5sec. Within5sec. Tripcommand Max.30sec. Max.30sec. possibletime Inputvoltagerange 85%~110% 85%~110% Capacitorrating(μμF) 400 160 Dimensions AC input DC output (For discharge) Control circuit diagram Terminal Handle It is a bent-lever to actuate a direct- drawout carrier by inserting and turning in DB and GB type contactors Fuse checking window Enables the visible check of a fuse like its outside status and temperature-rise in a fuse combination type contactor. ON/OFF indicator To visiblly check whether power is supplied or not Counter This is a ON/OFF operation counter by using 5 digit. CTD(Condensor Trip Device) Test/Run position indicator This enables checking contactor positions visibly when connecting or disconnecting a contactor. Note) Applied direct drawout type only. Fuse case Made of high strength BMC resin to offer superior insulation and safety. Note) Applied fuse combination type. Bushing It is mono-block bushing to be used in the cradles of G-type drawout contactors. It provides high insulation level, so recommended to use in contactors for MCSG. Note) Applied G-Class Cradle. Direct-drawout carrier It is a screw-sliding type drawout equipment to draw-in and draw-out a contactor directly out of a panel for personal safety. It is built in DB and GB type contactors. 1 2 3 4 5 6 7 8 9 10 11 12 www.dienhathe.xyz www.dienhathe.vn
  • 14. Internal structure 14 Main contact part Consists of vacuum interrupters, main terminals and moving shunts that are supported by a one-moulded frame that maintains insulation between phases. Vacuum interrupters are operated by means of the actuating mechanism that is connected to movable parts of a vacuum interrupter with a insulation rod. Actuating mechanism Designed simply without any linkage to be suited for frequent-operation and long service life. The actuating lever connected to a moving core of a actuating magnet that carrys out the function of a actuating shaft moves up and down to control the contact pressure for stable operations. Control method Continuous excitation - During a contactor is closed the control coil is required to be excited continuously to pull the moving core magnetically. In case of discontinuing the control power the moving core is to be returned by a spring because of the disappearance of magnetic force, which causes the opening of a contactor. Instantaneous excitation - In this method the continuous exciting of a control coil to maintain the closing of a contactor is not required as the latch built in it holds the mechanism. In case of manual tripping, a contactor will be tripped by releasing the latch when turn on the manual trip button. Protection cover Line terminal Insulation mold frame Load terminal Shunt Control coil Return spring Spring guide Spring spacer Vacuum interrupter Insulation rod Contact spring Actuating lever Fixed core Moving core Latch mechanism Main contact part Instantaneous excitationContinuous excitation Type Controlmethod Control voltage Closingcurrent(A)/ Tripcurrent(A)/ Holdingcurrent(A)/ Pick-up Drop-out Tripping (V) time(ms) time(ms) time(ms) voltage voltage voltage DC 110 3/100 - 0.6/40 AC 110 3/100 - 0.6/40 85% 75% - AC 220 2/100 - 0.3/40 DC 110 4.5/145 3/35 - AC 110 4.5(6)/145 3(4)/35 - 85% 75% 10%~75% AC 220 3(4)/145 10(14)/35 - Note) The values in ( ) are maximum allowable currents in case of using CTD. (voltage increment considered) LVC-3/6��- 42/44ED Continuous excitation(E) Instantaneous excitation(L) Instantaneous excitation(L) (With CTD) LVC-3/6��- 42/44LD www.dienhathe.xyz www.dienhathe.vn
  • 15. 15 Vacuum interrupters Features Vacuum interrupters In the closed position, normal current flows through the interrupter. When a fault occur and interruption is required, the contacts are quickly separated. The are which is oriented between surfaces of contact shall diffuse at the contact structure of flat shape. It prevents local heating and damage. The arc burns in an ionized metal vapor, which condenses on the surrounding metal shield. The arc is extinguished and vapor production is ceased at current zero. The metal vapor plasma is very rapidly dispersed, cooled, recombined, and deionized, and the metal vapor products are quickly condensed so that the contacts withstand the transient recovery voltage. LS vacuum interrupters consists of spiral contact, the material of which is CuCr to provide a long service life and high withstand voltage characteristic. Ratings Voltage phenomena (i) Arc re-ignition (ii)Restrikes (iii) B.I.L (iv) A.C.voltage withstand (i) Weld (ii) Bridge explosion (i) Contact jets (ii) Shield involvement (i) Arc instability (ii) Interruption Current zeroArc initiation High current arc mode Time (ms) Time (㎲) Fault current Recovery voltage Moving electrode Moving electrode terminal Bellows Bellows shield Ceramic Arc shield Contact Fixed electrode terminal Fixed electrode Internal structureExternal view Fixed electrode Dimensions AC arcing and interruption phenomena in vacuum Ratedvoltage 7.2 Ratedcurrent 400 Ratedinterruptingcurrent 4.5 Contactstroke 4.75 Openingspeedaverage 0.6 Closingspeedaverage 0.3 Contactforce 7Min Movingsideweight 0.23 Interrupterweight 0.52 Max.contacterosion 1 (kV) (A) (kA) (mm) (m/s) (m/s) (kg) (kg) (kg) (mm) www.dienhathe.xyz www.dienhathe.vn
  • 16. Accessories 16 3300/6600 110/220 1 100/200 50/60 Ratedvoltage(V) Secondaryvoltage(V) Class Burden(Var) Frequency(Hz) Fuse checker / Micro switch PT(Potential transformer) Fuse clip Auxiliary switch Fuse checker / Micro switch Fuse checker is operated in case of fuse blowing and output mechanical signal at same time. A micro switch is a part of fuse checker. The mechanical input signal is changed to electrical out signal by micro switch. Note) 19-20 : NO contact, 19-21 : NC contact PT(Potential transformer) 2 each of PTs can be mounted on drawout type contactors and fuse combination type. These are 100VA and 200VA PTs rated 3.6/7.2kV. Fuse clip It is used to install or uninstall a fuse link to the holder. Its dimensions depend on ratings. Note) Refer to fuse selection table on page 11. Auxiliary switch Auxiliary switches are 2NO+2NC as standard and additional 3NO+3NC can be added on request. Position switch This enables checking contactor positions when draw-in and draw-out. Remote checking is also possible through signaling via micro switches in each position. (Com) (NO) (NC) www.dienhathe.xyz www.dienhathe.vn
  • 17. 17 Drawing operations Unlock button Interlock plate Unlock pin Unlock button Unlock plate Cradle Cradle 108mm(Stroke) Interlock lever Interlock button A hole for a drawout lever Cradle Interlock lever Interlock button A hole for a drawout lever Cradle Unlock Unlock Unlock pin Details of TEST/RUN Position <TEST Position> <RUN Position> <TEST Position> <RUN Position> For standard draw-out types (D, G) ■■ When draw-in a contactor into a cradle. 1. Check that the contactor is in the state of open (TEST Position). 2. While pushing the unlock push button, insert the contactor about 50mm into the cradle. 3. Release the unlock push button and push the contactor into the cradle by the RUN position. ■■ When draw-out a contactor from a cradle. 1. Check that the contactor is in the state of open (RUN Position). 2. While pushing the unlock push button, draw the contactor about 50mm out of the cradle. 3. Release the unlock push button and pull the contactor from the cradle by the TEST position. For direct draw-out types (DB, GB) ■■ When draw-in a contactor into a cradle. 1. Check that the contactor is in the state of open (TEST Position). 2. While pushing the both sides of Interlock handle to the direction of the arrows, insert the contactor about 50mm into the cradle. 3. Insert the drawout lever into a hole as shown in the fig. While pushing the Interlock push button, swing the lever clockwise two times and release the Interlock push button. 4. Turning the lever clockwise until the contactor reaches in the RUN position. ■■ When draw-out a contactor from a cradle. 1. Check that the contactor is in the state of open (RUN Position). 2. Insert the drawout lever into a hole as shown in the fig. While pushing the Interlock push button, swing the lever counterclockwise two times and release the Interlock push button. 4. Turning the lever counterclockwise until the contactor reaches in the TEST position. 5. In case of separating the contactor from the cradle pull the contactor while pushing the both sides of Interlock handle to the direction of the arrows as shown in the fig. Note) Check the power before connecting or disconnecting. www.dienhathe.xyz www.dienhathe.vn
  • 18. Electrical circuit diagram 18 Continuous excitation DC control Fixed type (Continuous excitation) AC control �R : Holding resistance �CC: Input Coil �VZb: Assistance Switch b contact (time-delayed type) Note1) 1,2 terminal is for power supply Note2) 3,4 point is for Open/Close of contact point Note3) Point line(---) is user wiring �R: Holding resistance �CC: Input Coil �VZb: Assistance Switch b contact (time-delayed type) Note1) 1,2 terminal is for power supply Note2) 3,4 point is for Open/Close of contact point Note3) Point line(---) is user wiring www.dienhathe.xyz www.dienhathe.vn
  • 19. 19 Fixed type (Instantaneous excitation) Instantaneous excitation DC control AC control(CTD equipped) �CC: Input coil �TC: Trip Coil �VZb: Assistance switch b contact �VZa: Assistance switch a contact Note1) Close the CB by using 4(+), 2(-) terminal Note2) Trip by using 5(+), 2(-) terminal Note3) Contactor is not working when the reverse contact. Note4) Point line(---) is user wiring �CC: Input coil �TC: Trip Coil �VZb: Assistance switch b contact �VZa: Assistance switch a contact �CTD: Condenser Trip unit Note1) 1~2 terminal is for power supply Note2) Close the CB by using 3~4 terminal Note3) Trip by using 5~15 terminal. Note4) Point line(---) is user wiring www.dienhathe.xyz www.dienhathe.vn
  • 20. Internal connection diagrams 20 Continuous excitation DC control (Com) (NO) (NC) (Com) (NO) (NC) Drawout type (Continuous excitation) AC control �R: Holding resistance �CC: Input Coil �VZb: Assistance Switch b contact (time-delayed type) �M: Microswitch for interlock Note1) 1,2 terminal is for power supply Note2) 3,4 point is for Open/Close of contact point Note3) Point line(---) is user wiring �R: Holding resistance �CC: Input Coil �VZb: Assistance Switch b contact (time-delayed type) �M: Microswitch for interlock Note1) 1,2 terminal is for power supply Note2) 3,4 point is for Open/Close of contact point Note3) Point line(---) is user wiring www.dienhathe.xyz www.dienhathe.vn
  • 21. 21 Drawout type (Instantaneous excitation) Instantaneous excitation DC control (Com) (NO) (NC) (Com) (NO) (NC) AC control(CTD equipped) �CC: Input Coil �TC: Trip Coil �VZb: Assistance switch b contact �VZa: Assistance switch a contact �M: Microswitch for interlock Note1) Close the CB by using 4(+), 2(-) terminal Note2) Trip by using 5(+), 2(-) terminal Note3) Point line(---) is user wiring Note4) Contactor is not working when the reverse contact. �CC: Input Coil �TC: Trip Coil �VZb: Assistance switch b contact �VZa: Assistance switch a contact �CTD: Condenser Trip unit �M: Microswitch for interlock Note1) 1~2 terminal is for power supply Note2) Close the CB by using 3~4 terminal Note3) Trip by using 5~15 terminal. Note4) Point line(---) is user wiring www.dienhathe.xyz www.dienhathe.vn
  • 22. 22 Connection diagrams Instantaneous excitation DC CC TC CC TC 12 13 14 4 5 2 1 10 9 8 7 12 13 14 4 5 1 2 10 9 8 7 11 11 AUX S/W 1 AUX S/W 2 17 13 A B A B A A2 14 43 44 11 7 11 15 14 9 13 27 x Relay x 13 A A2 14 43 44 x Relay x 12 5 8 24 10 14 4 26 25 24 23 22 21 16 15 14 13 12 11 17 11 7 11 15 14 9 13 27 12 5 8 24 10 14 4 26 25 24 23 22 21 16 15 14 13 12 11 VC2 VC1 <2a2b> <2a2b> AC AC AC AC <2a2b> <2a2b> CC CC TC TC CTD C6C5C3C1 12 13 14 154 5 7 1 2 3 5 1 2 3 8 9 7 9 10987 1211 1 2 3 4 5 6 10987 1211 1 2 3 4 5 6 CTD C6C5C3C1 10 11 12 13 14 154 8 10 11 AUX S/W 1 AUX S/W 2 B B A A 13 A A2 14 43 44 x Relay x 13 A A2 14 43 44 x Relay x 17 16 15 14 13 12 11 11 7 11 15 14 9 13 12 5 8 27 26 25 24 23 22 21 24 10 14 4 17 16 15 14 13 12 11 11 7 11 15 14 9 13 12 5 827 26 25 24 23 22 21 24 10 14 4 + ~ ~ - + ~ ~ Z Z - VC2 VC1 Mechanical interlock type (Instantaneous excitation) AC (With CTD) www.dienhathe.xyz www.dienhathe.vn
  • 23. 23 4 4 CCCC 10 9 12 11 6 5 2 (-) Vzb1 R DC (+) 31 Vzb2 1614 1513 Vzb1 Vzb2 1513 14 1612 119 106 1 3 (+) DC (-) 2 5 R CCCC 13 12 2 3 1 11 10 9 4 5 6 14 15 16 13 12 2 3 1 11 10 9 4 5 6 14 15 16 <3a2b> <3a2b> ON OFF ON OFF R AC Vzb1 CC CC 1 AC Vzb2 3 4 ON OFF 106 12 14 Vzb2 R Vzb1 OFF ON CCCC 5 119 13 1 2 2 43 16 15 5 6 9 11 1210 13 14 15 16 13 12 2 3 1 11 10 9 4 5 6 14 15 16 13 12 2 3 1 11 10 9 4 5 6 14 15 16 <3a2b> <3a2b> CC CC CC CC CC CC CC CC 12 13 14 154 5 6 1 2 3 10 9 5 6 1 2 3 9 11 16 12 13 14 154 10 11 16 AUX S/W 1 AUX S/W 2 B A B A B A B A B A B A B A B A 17 R11 R21 R22R R2R12 R11 R21 R22R R2R12 16 15 14 13 12 11 11 5 11 15 14 9 13 12 6 16 24 14 10 27 26 25 24 23 22 21 17 16 15 14 13 12 11 11 11 15 14 9 13 12 5 6 16 24 14 10 27 26 25 24 23 22 21 VC2 VC1 CC CC CC CC 12 13 14 154 1 2 3 5 6 10 9 1 2 3 5 6 9 11 16 12 13 14 154 10 11 16 AUX S/W AUX S/W B A B A B A B A CC CC CC CC B A B A B A B A R2 R22R12 R1 R R R2 R22R12 R1 R R 17 16 15 14 13 12 11 11 15 14 9 13 11 12 5 6 16 24 10 14 27 26 25 24 23 22 21 17 16 15 14 13 12 11 11 15 14 9 13 11 12 5 6 16 24 10 14 27 26 25 24 23 22 21 + ~ ~ Z - + ~ ~ Z - VC2 VC1 Mechanical interlock type (Continuous excitation) Continuous excitation DC AC www.dienhathe.xyz www.dienhathe.vn
  • 24. External dimensions 24 〔〔Unit : mm〕〕 Mounting hole (Terminal hole) Mounting hole (Terminal hole) Drawout type w/o a cradle LVC-3/6D-42/44E(L)D Combination drawout type w/o a cradle (Fused combination) LVC-3/6G-42/44E(L)D Fixed type LVC-3/6Z-42/44E(L)D www.dienhathe.xyz www.dienhathe.vn
  • 25. 25 Mounting hole (Terminal hole) (Terminal hole) Mounting hole (Terminal hole) (Terminal hole) Mounting hole (Terminal hole) (Terminal hole) F2-Class Cradle G-Class Cradle 〔〔Unit : mm〕〕Drawout type E-Class Cradle www.dienhathe.xyz www.dienhathe.vn
  • 26. External dimensions 26 Combination drawout type (Fused combination) F2-Class Cradle G-Class Cradle 4-∅14 670(Terminal hole) 617.4 340(Terminal hole) 439 105 76.7 95 503.6 820 319.3 90 RUN(672) 165 160 6 20 RUN(742):6M-300 Fuse TEST(108) TEST(108)E-Class Cradle 4-∅14 670(Terminal hole) 617.4 439 340(Terminal hole) 105 95 76.7 559 821.6 319.3 90RUN(672) 188 20 6 160 TEST(108) TEST(108) RUN(742):6M-300 Fuse 〔〔Unit : mm〕〕 4-∅14 670(Terminal hole) 617.4 105 439 340(Terminal hole) 95 76.7 559 821.6 319.3 90 188 160 6 20 RUN(672)TEST(108) TEST(108) RUN(742):6M-300 Fuse www.dienhathe.xyz www.dienhathe.vn
  • 27. 27 G-Class Cradle Direct-drawout type (For MCSG) Mechanical Interlock type RUN(672)TEST(108) TEST(108) RUN(742):6M-300 Fuse 188 4- 14 90 559 617.4 340(Terminal hole) 439 76.7 95 670(Terminal hole) 821.6 299.3200 20 6 ∅ ON 〔〔Unit : mm〕〕 www.dienhathe.xyz www.dienhathe.vn
  • 28. Selection tables 28 Rated voltage (kV) Fuselink Rated current (A) Rated interrupting current (kA) Lowest interrupting current (A) Transformerload(kVA) Singlephase Threephase Fuseselectionbyload Capacitiveload(kVA) Threephase LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3/6G - LFL - 3G - LFL - 3G - LFL - 6G - LFL - 6G - 5B 10B 20B 30B 40B 50B 60B 75B 100B 125B 160B 200B 160B 200B 3.6 (7.2) 3.6 7.2 40 4In 5 10 20 30 40 50 63 75 100 125 160 200 160 200 ( 8 ~ 16 ) ( 13 ~ 25 ) ( 30 ~ 62 ) ( 40 ~ 84 ) ( 80 ~ 165) ( 98 ~ 204) (132 ~ 275) (134 ~ 330) (256 ~ 440) (302 ~ 550) ( - ) ( - ) (425 ~ 704) (437 ~ 880) ※4 ~ 8 6 ~ 13 15 ~ 31 21 ~ 42 40 ~ 82 49 ~102 66 ~137 68 ~165 128 ~220 151 ~275 211 ~352 265 ~440 - - ( 13 ~ 28 ) ( 21 ~ 44 ) ( 51 ~ 107) ( 70 ~ 145) (137 ~ 286) (170 ~ 354) (229 ~ 476) (233 ~ 571) (443 ~ 762) (522 ~ 952) ( - ) ( - ) (735~1,220 ) (755~1,520 ) ※ ※ 6.7 ~ 14 11 ~ 22 25 ~ 53 35 ~ 73 69 ~143 85 ~117 114 ~238 117 ~285 222 ~381 261 ~476 365 ~610 495 ~762 - - ( 9.8up to ) ( 19 ~ 24 ) ( 24 ~ 61 ) ( 61 ~ 92 ) ( 92 ~ 128) (128 ~ 163) (163 ~ 210) (210 ~ 300) (300 ~ 445) (445 ~ 550) ( - ) ( - ) (550~742 ) (742~1,000 ) ※9.8up to 9.8 ~ 12 12 ~ 31 31 ~ 46 46 ~ 64 64 ~ 81 181 ~105 105 ~150 150 ~222 222 ~275 275 ~370 370 ~550 - - Rated voltage (kV) Fuselink Rated current (A) Rated interrupting current (kA) Lowest interrupting current (A) Transformerload(kVA) Singlephase Threephase Fuseselectionbyload Capacitiveload(kVA) Threephase 5 10 20 30 40 50 63 75 100 150 200 300 400 150 200 300 400 20 50 100 150 200 300 400 20 50 100 150 200 300 400 - - - - - - - - - - - - - - - ( 5upto ) 10upto ( 15upto ) 20upto ( 50upto ) 30upto ( 75upto ) 50upto ( 100upto ) 75upto ( 150upto ) - ( - ) 150upto ( 200upto ) 200upto ( 400upto ) 300upto ( - ) 400upto ( - ) 625upto ( - ) 750upto ( - ) - ( 500upto ) - ( 750upto ) - (1,250upto) - ( - ) ※ 5upto ( 15upto ) 15upto ( 30upto ) 30upto ( 75upto ) 75upto ( 150upto ) 100upto ( 200upto ) 150upto ( 300upto ) - ( - ) 200upto ( 400upto ) 375upto ( 750upto ) 500upto ( - ) 750upto ( - ) 1,000upto ( - ) 1,500upto ( - ) - (1,000upto) - (1,500upto) - (2,000upto) - (2,500upto) ※ - ( - ) 10upto ( 25upto ) 30upto ( 50upto ) 50upto ( 100upto ) 75upto ( 150upto ) 100upto ( 200upto ) - ( - ) 200upto ( 400upto ) 300upto ( 600upto ) 400upto ( - ) 600upto ( - ) 1,000upto ( - ) - ( - ) - ( 800upto ) - (1,200upto) - ( - ) - ( - ) ※ 50upto ( - ) 150upto ( - ) 300upto ( - ) 400upto ( - ) 800upto ( - ) 1,000upto ( - ) - ( - ) - ( 100upto ) - ( 300upto ) - ( 600upto ) - ( 800upto ) - ( - ) - ( - ) - ( - ) ※ 40 5In 3.6 (7.2) 3.6 7.2 G(General use) type M(Motorprotection)type 3.6 7.2 40 7In Application Model Application Model DIN type KS type LFL -3/6G - 5 LFL - 3/6G - 10 LFL - 3/6G - 20 LFL - 3/6G - 30 LFL - 3/6G - 40 LFL - 3/6G - 50 LFL -3/6G - 60 LFL - 3/6G - 75 LFL -3/6G -100 LFL - 3G -150 LFL - 3G -200 LFL - 3G -300 LFL - 3G -400 LFL - 6G -150 LFL - 6G -200 LFL - 6G -300 LFL - 6G -400 LFL - 3M - 20 LFL - 3M - 50 LFL - 3M -100 LFL - 3M -150 LFL - 3M -200 LFL - 3M -300 LFL - 3M -400 LFL - 6M - 20 LFL - 6M - 50 LFL - 6M -100 LFL - 6M -150 LFL - 6M -200 LFL - 6M -300 LFL - 6M -400 www.dienhathe.xyz www.dienhathe.vn
  • 29. 29 Selecting conditions and warning 1. ※ The values in ( ) apply to the loads of 7.2kV. 2. It is assumed that the inrush current of a transformer is 10 times of the full load current of a motor for 0.1 second. - The rated current of a fuse is selected to carry continuously the current of 1.5 times of rated current of a transformer.(1.3 times in the case of ※) - In the transformer load table it is assumed that the interruption will be made at 25 times of rated current within 2 seconds. 3. It is assumed that the inrush current of a motor is 5 times of full load current for 10 seconds. 4. In the case of using the M(motor protection) type fuses for the purpose of the short-circuit protection of a motor or a starter select the proper rating in addition refer to the characteristic curves on the catalog to make the device protected from overload by a circuit breaker or a contactor. 5. It is assumed that the inrush current of a capacitor is 71 times of its rated current for 0.002 second. - The rated current of a fuse is selected to carry continuously the current of 1.43 times of rated current of a capacitor. - In case service life of more than 1000 operations is required select in the M( motor protection) type fuse table. 6. The above mentioned comments are according to KS(Korean Industrial Standard) and subject to the real situation. Motorload(kVA) Threephase Dimensions(mm) Applicableholder A B C D 195 55 - - LFH-6G-D1HB 192 77 - - 292 77 - - LFH-6G-D2HB Fuseselectionbyload ( 13 ~ 22 ) ( 22 ~ 36 ) ( 36 ~ 86 ) ( 86 ~ 117) (117 ~ 230) (230 ~ 284) (276 ~ 382) (362 ~ 503) (469 ~ 739) (556 ~ 870) ( - ) ( - ) (751~1,223 ) (1,154~1,760 ) ※6.5 ~10.7 10.7~ 28 28 ~ 57 50 ~ 85 85 ~115 115 ~142 138 ~191 181 ~252 253 ~369 293 ~435 343 ~572 375 ~630 - - Motorload(kW) Threephase - - - - - - - - - - - - - - - - - Fuseselectionbyload DIN-Type fuse Dimensions(mm) Applicableholder A B C D 261 50 47 25 LFH-6G-D60 311 60 57 30 LFH-6G-D1H 311 77 73 43 LFH-6G-D2H 350 110 108 55 LFH-6G-D4H 200 60 58 30 LFH-3M-100 200 77 73 43 LFH-3M-200 250 87 84 50 LFH-3M-400 311 60 58 30 LFH-6M-50 350 77 73 43 LFH-6M-200 450 87 84 50 LFH-6M-400 ( - ) ( - ) ( - ) ( - ) ( - ) ( - ) ( - ) ( 75 ~ 160) (185 ~ 400) (450 ~ 800) (900 ~ 1,250) ( 1,500 ) ( 2,500 ) ( 3,000 ) ※37 ~ 75 90 ~ 200 220 ~ 400 450 ~ 630 710 ~ 800 900 ~1250 1,500 - - - - - - - www.dienhathe.xyz www.dienhathe.vn
  • 30. Power fuse 30 Power fuse LS Prime-MEC power fuses are designed to protect equipments from fault current such as short-circuit, and generally used for the protection the circuits of transformers, capacitors and motors they protect. For further safety and reliability the elements inside of fuses are made of silver, and high quality quartzs and and ceramic are used for magnetic rods and tubes, respectively. LS medium voltage vacuum contactors using LS vacuum interrupters manufactured with worldclass technology are type tested in LS PT & T that is accredited high power test lab by worldclass KOLAS. To ensure the performance they, installed in a vacuum contactor, are tested according to IEC 60282-1 in LS PT & T that is accredited high power test lab by worldclass KOLAS. Considerations in application �Power fuses are suitable for the protection from a short-circuit, Overload current will not protected. �Reset or re-use after blowing is not possible. Fuse reset or re-use is not possible after fused are blown out. �When the fuses are selected, the inrush currents arising from the starting transformers, motors, capacitors should be considered. �When the fuses are selected, their usage and circuit requirements should be considered. �For the purpose of protection from the fault current below the lowest interrupting current of the fuse it is desirable to replace it with a fuse having lower interrupting rate or add other overcurrent relay in series �Withstand voltage of the circuit should be higher than that of a fuse that protects it. �If possible, select the fuse whose rated current is much higher than the load current. The rated current not sufficiently exceeding the normal current of the load may cause reduction in the service life. �Replace all three fuses in case of blowing in a fuse. Determination of the rated current The rated current of the fuse must be selected properly after examination of the current/time characteristics of fuses, equipments and the related circuit conditions. General considerations �When the fuses are selected the sufficient rated current should be considered to avoid the deterioration of the fuse element due to sustained load current in the long term. �The fuse rated current should be higher than the sum of all load currents. �The estimated overload current should be within the fuse's time/current characteristics.The estimated overload current should not exceed the allowable overload withstand currents of the equipment and the number of its events should not exceed 100 times. �The characteristic curve of a fuse must lie to the right of those of other equipments to be protected. �The withstand strength such as permissible let-through current, I²t of the equipments to be protected must be higher than that of a fuse. �Coordination of permissible time limit Protection equipments in the line side < Fuses < Protection equipments in the load side �Coordination when fuses are used as back-up protection Permissible let-through current of a fuse < That of a protection equipment �Use the same rating for all three phases even the differential current between phases exists. KERI(24kV) www.dienhathe.xyz www.dienhathe.vn
  • 31. 31 Power fuse selection guides Considerations by the type of load 1. Power fuses for transformer loads �The fuse with sufficient rated current must be selected to avoid the deterioration of the fuse element due to permissible overload in the long term. �The fuse's current/time characteristic should cover the inrush current/time of the transformer. �In case of power transformers the symmetrical inrush current must be within 10 times of the fuse rating and the fuse should withstand at least 0.1second under the condition. �Fuse rated current ≥ Transformer rated current �The lowest interrupting current of the fuse < Short circuit current in the primary of the fuse �In case of protection of two or more transformers - Fuse rating should be selected on the basis of the phase condition where maximum current flows. - In the event of short-circuit in the secondary of the transformer The lowest interrupting current of the fuse < Short circuit current in the primary of the transformer �In case of potential transformers - When the fuses are selected do not consider the short-circuit happening in the secondary of the PT, but protecting PT itself and the circuit against the fault in the primary side. - Select the fuse with higher rated current than the load current so as not to be damaged by overcurrent. - The characteristic curve of a fuse must lie to the right of those of other equipments to be protected. - The withstand strength such as permissible let-through current, I²t of the equipments to be protected must be higher than that of a fuse. Note) Refer to the general considerations other than the above mentioned. 2. Power fuses for motor loads �The fuse with sufficient rated current must be selected to avoid the deterioration of the - fuse element due to permissible overload in the long term. �The fuse's current/time characteristic should cover the inrush current/time of the motor. - The inrush current of the motor must be within 5 times of the fuse rating and the fuse should withstand at least 10 seconds under the condition. Fuse rated current ≥ Motor full load current Note) Refer to the general considerations other than the above mentioned. 3. Power fuses for combination with vacuum contactors �The current at the intersection between a fuse characteristic curve and a contactor operation curve should greater than the lowest interrupting current of a fuse. �And the current at the cross point between a fuse curve and a contactor minimum dropout curve should not greater than the rated interrupting current of a contactor. Note) Refer to the general considerations other than the above mentioned. 4. Power fuses for capacitor loads �The fuse with sufficient rated current must be selected to avoid the deterioration of the fuse element due to permissible overload in the long term. �The fuse's current/time characteristic should cover the inrush current/time of the capacitor. �The size of inrush current depends on whether or not the serial reactors and parallel capacitors exist. �The inrush current of the capacitor must be within 70 times of the fuse rating and the fuse should withstand at least 0.002 second under the condition. Fuse rated current ≥ Capacitor rated current �In the case of serial reactor(6%) connected the inrush current must be within 5 times of the fuse rating and the fuse should withstand at least 0.1 second under the condition Note) Refer to the general considerations other than the above mentioned. Power fuses for transformer loads Power fuses for motor loads Note) Above picture shows korean standard type, If you want to order DIN type fuse, please contact LS Industrial Systems before you order it. www.dienhathe.xyz www.dienhathe.vn
  • 32. Coordination graph 32 A.Permissible overload current/time of a transformer B.Permissible overload characteristic of a transformer, Operation characteristic curve of a Fuse C.inrush current and time at no load of a transformer Characteristic curve of a secondary circuit breaker or low voltage fuse (Converted into the primary values) Time Permissible overload characteristic curve of a transformer Time/Current characteristic curve of a Fuse Blow-out characteristic curve of a Fuse Operation characteristic curve of a Fuse [1] [2] [3] [4] [5] [6] Current Coordination between fuse and transformer circuit When any protection device is not installed in the secondary of a transformer �Permissible overload current of a transformer (point ③)) must lie to the left of the curve ⓒ(time/current characteristic curve of a Fuse) Full load current of a transformer ① ≤ Rated current of a fuse ④ �Point C(inrush current and time at no load of a transformer) must lie to the left of the point ⓒ(time/current characteristic curve of a Fuse) �Secondary short-circuit current⑧ > Lowest interrupting current of a fuse ⑥ Point B must lie to the left of the secondary short-circuit current⑧. �Primary short-circuit current⑩ < Rated interrupting current of a fuse⑪ When a circuit breaker or fuse is installed in the secondary of a transformer �Must meet the requirements above mentioned in ① �The characteristic curve of a secondary circuit breaker or low voltage fuse ⓐ must lie to the left of permissible overload characteristic curve of a transformer ⓑ and under the point B �The characteristic curve of a secondary circuit breaker or low voltage fuse ⓐ must lie to the Time/Current characteristic curve of a Fuse and under the Secondary short-circuit current ⑧. �Secondary short-circuit current⑧ < Characteristic curve of a secondary circuit breaker or low voltage fuse ⓐ �The secondary circuit breaker or low voltage fuse should meet the above mentioned requirements to each branch circuit. �Another medium voltage protection device is required for the ensured protection against the fault happening between the secondary protection devices and the internal short-circuit of a transformer in the zone of [3]+[4]+[5]. ※※ Coordination in the graph ��Zone of [1] : Protection of primary side from short- circuit by a fuse ��Zone of [2] : Protection of a transformer ��Zone of [3] : Out of the scope of fuse operation ��Zone of [4] : Interruption is not ensured even though the fuse blows. ��Zone of [5] : Protection of a transformer is not ensured even though the fuse interrupts the circuit. ��Zone of [3]+[4]+[5] : No protection zone of a transformer Circuit breaker or low voltage fuse required for the transformer protection Fuse Transformer Circuit breaker or low voltage fuse Full load current of a transformer The lowest interrupting current of the secondary circuit breaker Permissible overload current of a transformer Rated current of a fuse Lowest blow-out current of a fuse Lowest interrupting current of a fuse Inrush current at no load of a transformer Secondary short-circuit current Rated interrupting current of a secondary circuit breaker Primary short-circuit current Rated interrupting current of a fuse www.dienhathe.xyz www.dienhathe.vn
  • 33. 33 Coordination between fuse and motor circuit The lowest operation characteristic of a vacuum contactor (opening characteristic) Operation characteristic of a vacuum contactor Overload characterictic of a motor Time/Current characteristic curve of a Fuse Blow-out characteristic curve of a Fuse Operation characteristic curve of a Fuse A : (Operation characteristic of a vacuum contactor, Time/Current characteristic curve of a Fuse) B : (The lowest operation characteristic of a vacuum contactor, Operation characteristic curve of a Fuse ) C : ( Inrush current of a motor, Inrush time of a motor ) Inrush time of a motor Time Current �Full load current of a motor① ≤ Rated current of a fuse② �Short-circuit current⑥ < Rated interrupting current of a fuse⑦ �Inrush current of a motor (Locked rotor current)③ < Rated interrupting current of a vacuum contactor⑤ �Point C must lie to the left of ⓐ(The lowest operation characteristic of a vacuum contactor)and ⓓ(Time/Current characteristic curve of a Fuse) �Operation characteristic of a vacuum contactorⓑ must lie to the left of ⓒ( Overload characteristic of a motor ) �Point A must lie to the right of ④ Lowest interrupting current of a fuse. �Point B must lie to the left of ⑤ Rated interrupting current of a vacuum contactor. Note) The current less than point A can be protected by a vacuum contactor, and the current greater than point B is to be protected by a fuse. Fuse Vacuum contactor Motor Full load current of a motor Rated current of a fuse Inrush current of a motor (Locked rotor current) Lowest interrupting current of a fuse Rated interrupting current of a vacuum contactor Short-circuit current Rated interrupting current of a fuse www.dienhathe.xyz www.dienhathe.vn
  • 34. Operation curves 34 DIN Type 3.6/7.2kV blowing characteristic 3.6/7.2kV current limiting characteristic 3.6kV blowing characteristic 3.6kV current limiting characteristic 7.2kV blowing characteristic 7.2kV current limiting characteristic Current ( sym, A ) Operationtime(sec) Current ( sym, A ) Operationtime(sec) Current ( sym, A ) Operationtime(sec) Interrupting current ( sym, kA ) Interrupting current ( sym, kA ) Currentlimited(peak,kA)Currentlimited(peak,kA) Interrupting current ( sym, kA ) Currentlimited(peak,kA) www.dienhathe.xyz www.dienhathe.vn
  • 35. 35 KS Type G(General use) type fuse M(Motor protection) type fuse 3.6/7.2kV blowing characteristic 3.6/7.2kV current limiting characteristic 3.6kV blowing characteristic 7.2kV blowing characteristic 3.6kV, 7.2kV current limiting characteristic Current ( sym, A ) Operationtime(sec) Current ( sym, A ) Operationtime(sec) Interrupting current ( sym, kA ) Interrupting current ( sym, kA ) Currentlimited(peak,kA) Currentlimited(peak,kA) Current ( sym, A ) Operationtime(sec) www.dienhathe.xyz www.dienhathe.vn
  • 36. ��For your safety, please read user's manual thoroughly before operating. ��Contact the nearest authorized service facility for examination, repair, or adjustment. ��Please contact qualified service technician when you need maintenance. Do not disassemble or repair by yourself! ��Any maintenance and inspection shall be performed by the personnel having expertise concerned.Safety Instructions ��LS Industrial Systems (Middle East) FZE ����Dubai, U.A.E. Address: P.O.Box-114216, API World Tower, 303B, Sheikhe Zayed Road, Dubai, U.A.E. Tel: 971-4-332-8289 Fax: 971-4-332-9444 e-mail: hwyim@lsis.biz ��Dalian LS Industrial Systems Co., Ltd. ����Dalian, China Address: No.15, Liaohexi 3-Road, Economic and Technical Development zone, Dalian 116600, China Tel: 86-411-8273-7777 Fax: 86-411-8730-7560 e-mail: lixk@lsis.com.cn ��LS Industrial Systems (Wuxi) Co., Ltd. ����Wuxi, china Address: 102-A , National High & New Tech Industrial Development Area, Wuxi, Jiangsu,214028, P.R.China Tel: 86-510-8534-6666 Fax: 86-510-522-4078 e-mail: xuhg@lsis.com.cn ��LS-VINA Industrial Systems Co., Ltd. ����Hanoi, Vietnam Address: Nguyen Khe - Dong Anh - Ha Noi - Viet Nam Tel: 84-4-882-0222 Fax: 84-4-882-0220 e-mail: srjo@lsisvina.com ��LS Industrial Systems Tokyo Office ����Tokyo, Japan Address: 16FL, Higashi-Kan, Akasaka Twin Tower 17-22, 2-chome, Akasaka, Minato-ku Tokyo 107-8470, Japan Tel: 81-3-3582-9128 Fax: 81-3-3582-2667 e-mail: jschuna@lsis.biz ��LS Industrial Systems Shanghai Office ����Shanghai, China Address: Room E-G, 12th Floor Huamin Empire Plaza, No.726, West Yan'an Road Shanghai 200050, P.R. China Tel: 86-21-5237-9977 (609) Fax: 89-21-5237-7191 e-mail: jinhk@lsis.com.cn ��LS Industrial Systems Beijing Office ����Beijing, China Address: B-Tower 17FL.Beijing Global Trade Center B/D. No.36, BeiSanHuanDong-Lu, DongCheng-District, Beijing 100013, P.R. China Tel: 86-10-5825-6025,7 Fax: 86-10-5825-6026 e-mail: cuixiaorong@lsis.com.cn ��LS Industrial Systems Guangzhou Office ����Guangzhou, China Address: Room 1403,14F,New Poly Tower,2 Zhongshan Liu Road,Guangzhou, P.R. China Tel: 86-20-8326-6764 Fax: 86-20-8326-6287 e-mail: linsz@lsis.com.cn ��LS Industrial Systems Chengdu Office ����Chengdu, China Address: 12Floor, Guodong Buiding, No52 Jindun Road Chengdu, 610041, P.R. China Tel: 86-28-8612-9151 Fax: 86-28-8612-9236 e-mail: yangcf@lsis.com.cn ��LS Industrial Systems Qingdao Office ����Qingdao, China Address: 7B40,Haixin Guangchang Shenye Building B, No.9, Shandong Road Qingdao 26600, P.R. China Tel: 86-532-8501-6568 Fax: 86-532-583-3793 e-mail: lirj@lsis.com.cn �� HEAD OFFICE Yonsei Jaedan Severance Bldg., 84-11, Namdaemunno 5ga, Jung-gu, Seoul, 100-753, Korea Tel. (82-2)2034-4870 Fax. (82-2)2034-4713 �� CHEONG-JU PLANT Cheong-Ju Plant #1, Song Jung Dong, Hung Duk Ku, Cheong Ju, 361-720, Korea Leader in Electrics & Automation �� Global Network www.lsis.biz Specifications in this catalog are subject to change without notice due to continuous product development and improvement. 2008. 01 LS Medium Voltage Vacuum Contactors(E) 2003. 04/(12) 2008. 01 Printed in Korea STAFF ⓒ 2003.4 LS Industrial Systems Co.,Ltd. All rights reserved. www.dienhathe.xyz www.dienhathe.vn