APPENDIX R

                                       STRAW-BALE STRUCTURES

                      SECTION AR101                                   ilar plants, shall be acceptable if they meet the minimum re-
                          PURPOSE                                     quirements for density, shape, moisture content and ties.
AR101.1 Minimum standards. The purpose of this appendix               AR104.2 Shape. Bales shall be rectangular in shape.
chapter is to establish minimum prescriptive standards of                AR104.2.1 Dimensions. Bales used within a continuous
safety for the construction of structures that use baled straw as a      wall shall be of consistent height and width to ensure even
load-bearing or nonload-bearing material.                                distribution of loads within wall systems.
                                                                         AR104.2.2 Wall thickness. Nominal minimum bale wall
                                                                         thickness shall be 14 inches (356 mm).
                      SECTION AR102
                            SCOPE                                        AR104.2.3 Custom size bales. Where custom made partial
AR102.1 Applicability. The provisions of this chapter shall              bales are used, they shall be of the same density, same string
apply to single family detached structures and relate accessory          or wire tension, and where possible, use the same number of
structures as defined in Section R101.9, utilizing straw bales in        ties as the standard size bales.
the construction of wall systems.                                     AR104.3 Ties. Bales shall be bound with ties of either poly-
                                                                      propylene string or baling wire. Bales with broken or loose ties
                                                                      shall not be used unless the broken or loose ties are replaced
                     SECTION AR103                                    with ties which restore the original degree of compaction of the
                       DEFINITIONS                                    bale.
AR103.1 General. For the purpose of this chapter, certain             AR104.4 Moisture content. Moisture content of bales, at time
terms are defined as follows:                                         of installation and just prior to applying exterior weather pro-
BALES. Rectangular compressed blocks of straw, bound by               tection such as stucco, shall not exceed 20 percent of the total
strings or wire.                                                      weight of the bale. Bales that become wet or exceed 20-percent
                                                                      moisture content shall be replaced with dry bales or allowed to
FLAKES. Slabs of straw removed from an untied bale. Flakes            dry and be retested. Bales that exceed 20-percent moisture con-
are used to fill small gaps between the ends of stacked bales.        tent shall be replaced. Special inspection of the moisture con-
LAID FLAT. Refers to stacking bales so that the sides with the        tent of bales shall be performed using one of he following
largest cross-sectional area are horizontal and the longest di-       methods:
mension of this area is parallel with the wall plane.                    AR104.4.1 Field method. A suitable moisture meter, de-
LAID ON EDGE. Refers to stacking bales so that the sides                 signed for use with baled straw or hay, and equipped with a
with the largest cross-sectional area are vertical and the longest       probe of sufficient length to reach the center of the bale,
dimension of this area is horizontal and parallel with the wall          shall be used to determine the average moisture content of
plane.                                                                   five bales randomly selected from the bales to be used.
STRAW. The dry stems of cereal grains left after the seed                AR104.4.2 Laboratory method. A total of five samples,
heads have been removed.                                                 taken from the center of each of five bales randomly se-
                                                                         lected from the bales to be used, shall be tested for moisture
LOAD BEARING. The use of straw bale walls as structural                  content by a recognized testing lab.
load-bearing walls supporting the roof and resisting lateral
loads.                                                                AR104.5 Density. Bales in load-bearing structures shall have a
                                                                      minimum calculated dry density of 7.0 pounds per cubic foot
NONLOAD BEARING. A structure where straw bales are                    (112 kg/m3). The calculated dry density shall be determined af-
used to in-fill between the supporting structural members. The        ter reducing the actual bale weight by the weight of the mois-
exterior straw bale in-fill wall sections collect lateral loads re-   ture content, as determined in Section AR104.4. The
sulting from wind or seismic activity and transfer these loads to     calculated dry density shall be determined by dividing the cal-
the primary structure for resistance.                                 culated dry weight of the bale by the volume of the bale.
IN-FILL WALL. The nonbearing section between vertical
supports.
                                                                                           SECTION AR105
                                                                                  FOUNDATION REQUIREMENTS
                      SECTION AR104                                   AR105.1 Foundations. Foundations shall comply with Chap-
              MATERIAL SPECIFICATIONS                                 ter 4. Foundations shall be sized to accommodate the thickness
AR104.1 Type of straw. Bales of various types of straw, in-           of the bale wall and support the imposed live and dead loads
cluding, but not limited to wheat, rice, rye, barley, oats and sim-   from walls and roofs. The minimum width of the footing shall

2008 OREGON RESIDENTIAL SPECIALTY CODE                                                                                             R-1
APPENDIX R




be the width of the bale it supports, except that the bales may          1. Wooden dowels at least 5/8 inch (16 mm) in diameter, of
overhang the exterior edge of the foundation by not more than 3             sufficient length to provide 12 inches (305 mm) of pene-
inches (76 mm) to accommodate rigid perimeter insulation.                   tration into the bale, driven through holes bored in the
                                                                            abutting wall stud, and spaced to provide one dowel con-
AR105.2 Wall reinforcement embedded in foundation. Ver-
                                                                            nection per bale.
tical reinforcing bars with a minimum diameter of 1/2 inch (12.7
mm), shall be embedded in the foundation a minimum depth of              2. Pointed wooden stakes, at least 12 inches (305 mm) in
6 inches (153 mm), and shall extend above the foundation a                  length and 11/2 inch by 31/2 (38.1 mm by 88.9 mm) at the
minimum of 12 inches (304.8 mm). These vertical bars shall be               exposed end, fully driven into each course of bales, as an-
located along the centerline of the bale wall, spaced not more              chorage points.
than 2 feet (610 mm) apart. A vertical bar shall also be located         3. Bolted or threaded rod connection of the abutting wall,
within 1 foot (305 mm) of any opening or corner, except at lo-              through the bale wall, to a steel nut and steel or plywood
cations occupied by anchor bolts.                                           plate washer, a minimum of 6 inches (153 mm) square
                                                                            and a minimum thickness of 3/16 inch (4.8 mm) for steel
AR105.3 Moisture barrier. A moisture barrier shall be used
                                                                            and 1/2 inch (12.7 mm) for plywood, in at least three loca-
between the top of the foundation and the bottom of the bale
                                                                            tions.
wall to prevent moisture from migrating through the founda-
tion into the bottom course of bales. This barrier shall consist of
one of the following.
                                                                                           SECTION AR107
   1.   Cementious waterproof coating;                                                  LOAD-BEARING WALLS
   2.   Type 30 asphalt felt over an asphalt emulsion;
                                                                      AR107.1 Anchor bolts. In addition to vertical reinforcement
   3.   Sheet metal flashing, sealed at joints; or                    bars required in Section M105.2, load-bearing bale walls shall
   4.   Other approved building moisture barrier.                     be anchored to the foundation by 1/2-inch (12.7 mm) diameter
                                                                      steel anchor bolts embedded at least 7 inches (178 mm) in the
   All penetrations through the moisture barrier, as well as all
                                                                      foundation at intervals of 6 feet (1829 mm) or less. A minimum
joints in the barrier, must be sealed with asphalt, caulking or an
                                                                      of two anchor bolts per wall shall be provided with one bolt lo-
approved sealant.
                                                                      cated within 36 inches (914 mm) of each end of each wall. Sec-
                                                                      tions of 1/2-inch (12.7 mm) diameter threaded rod shall be
                                                                      connected to the anchor bolts, and to each other, by means of
                    SECTION AR106                                     threaded coupling nuts and shall extend through the roof-bear-
                  WALL CONSTRUCTION                                   ing assembly and be fastened with a steel washer and nut. Bale
AR106.1 General (fire resistance). Bale walls, when covered           walls and roof-bearing assemblies may be anchored to the
with plaster or stucco shall be deemed to be fire resistive.          foundation by means of other methods, which are adequate to
                                                                      resist uplift forces resulting from the design wind load. There
  A straw bale covered with plaster or stucco having a mini-          shall be a minimum of two points of anchorage per wall, spaced
mum thickness of 7/8 inch (22.4 mm) on both sides maybe used          not more than 6 feet (1829 mm) apart, with one located within
between a dwelling and attached garage as required in Section         36 inches (914 mm) of each end of each wall.
R309.2.
                                                                         The dead load of the roof and ceiling systems will produce
AR106.2 Allowable Loads. The allowable vertical load (live            vertical compression of the bales. Regardless of the anchoring
and dead load) on the top of load-bearing bale walls shall not        system used to attach the roof bearing assembly to the founda-
exceed 360 pounds per square foot (psf) (17.2 kPa) [23 inches         tion, prior to installation of wall finish materials, bolts, straps or
(84.2 mm) divided by 12 inches (304.8 mm) by 360 pounds               cables shall be retightened to compensate for this compression
(17.2 kPa) = 690 pounds per linear foot (plf) (10.1 N/mm] and         after the actual dead load of the roof framing and roofing have
the resultant load shall act at the center of the wall. Bale struc-   been applied.
tures shall be designed to withstand all vertical and horizontal
loads as specified in Chapter 3 and the Structural Code, Chap-        AR107.2 Load-bearing wall height. Load-bearing straw bale
ter 16. Increases in stress and reductions of live loads specified    walls shall not exceed one story in height and the bale portion
in Structural Code Chapter 16 may be applied.                         shall not exceed a height to width ratio of 5.6:1 [for example,
                                                                      the maximum height for the bale portion of a 23-inch-thick
AR106.3 Insulation. Exterior walls using straw bales shall be         (584 mm) wall would be 10 feet, 8 inches (3251 mm)].
considered to meet the wall insulation requirements of Path 1
                                                                      AR107.3 Unsupported wall length. The ratio of unsupported
as described in Section N1104. All other exterior wall compo-
                                                                      wall length to thickness, for load-bearing bale walls, shall not
nents shall comply with Section N1104. For the purpose of cal-
                                                                      exceed 13:1 [for a 23-inch (584 mm) thick wall, the maximum
culating thermal performance using Table N1104.1.2, the
                                                                      unsupported length allowed is 25 feet (7620 mm)].
insulation of straw bale walls can assume to be R-2.1 per inch
[a 23-inch (584 mm) bale would be R-48 or U-0.021].                   AR107.4 Openings and lintels. All openings in load-bearing
                                                                      bale walls shall be a minimum of one full bale length from any
AR106.4 Intersecting walls. Walls of other materials inter-
                                                                      outside corner.
secting bale walls shall be attached to the bale wall by means of
one or more of the following methods or an acceptable equiva-            AR107.4.1 Openings. Openings in exterior bale walls shall
lent:                                                                    not exceed 50 percent of the total wall area, based on interior

R-2                                                                                    2008 OREGON RESIDENTIAL SPECIALTY CODE
APPENDIX R




   dimensions, where the wall is providing resistance to lateral      tion AR110.1 shall be provided that continues through the
   loads.                                                             gable end walls.
      Door and window frames (rough bucks) shall be stabi-
   lized with 1/2-inch (12.7 mm) diameter hardwood dowels
   extending 12 inches (305 mm) into every adjacent bale or by                             SECTION AR108
   means of a continuous metal lath applied to both the interior                    NONLOAD-BEARING WALLS
   and exterior, extending a minimum of 12 inches (305 mm)            AR108.1 General. A nonload-bearing wall is part of a struc-
   onto adjacent bales, installed prior to the application of plas-   tural system where the primary frame is an approved system
   ter or stucco.                                                     complying with this code or Structural Code Chapter 16. The
                                                                      straw bales are used as in-fill between structural members or
   AR107.4.2 Lintels. Wall and/or roof load present above any         framing.
   opening shall be carried, or transferred to the bales below by
   one of the following:                                              AR108.2 Primary frame. The primary frame (such as post
                                                                      and beam or pole building) shall comply with this code or
       1. A structural frame,                                         Structural Code Chapter 16. Structural calculations showing
       2. A lintel (such as an angle-iron cradle, wooden beam,        compliance shall be submitted with plans and application for
          wooden box beam). Lintels shall be at least twice as        building permits.
          long as the opening is wide and extend at least 24
                                                                         AR108.2.1 Anchorage to foundation. The primary frame
          inches (610 mm) beyond either side of the opening.
                                                                         shall be anchored to the foundation in accordance with
          Lintels shall be centered over openings, and shall not
                                                                         Chapters 4 and 6 of this code or Structural Code Chapter 16.
          exceed the load limitations of Section AR106.2 by
          more than 25 percent.                                       AR108.3 Wall anchorage to foundation. Vertical reinforcing
       3. A roof-bearing assembly designed to act as a rigid          bars with a minimum diameter of 1/2 inch (12.7 mm) shall be
          beam over the opening.                                      embedded in the foundation a minimum depth of 6 inches (153
                                                                      mm), and shall extend above the foundation a minimum of
AR107.5 Stacking. Bales in load-bearing walls shall be laid           one-and-one-half bales.
flat and stacked in running bond where possible, with each bale
overlapping the two bales beneath it. Bales in nonload-bearing           AR108.3.1 Location. The vertical bars shall be located
walls may be laid either flat or on-edge and stacked in running          along the centerline of the bale wall, spaced not more than 2
bond where possible. Overlaps shall be a minimum of 12                   feet (610 mm) apart and a minimum of two per bale.
inches (305 mm). Gaps between the ends of bales which are                AR108.3.2 Corners and openings. A vertical bar shall be
less than 6 inches (153 mm) in width may be filled by an untied          located within 1 foot (305 mm) of any opening or corner, ex-
flake inserted snugly into the gap. Only full-length bales shall         cept at locations occupied by anchor bolts.
be used at corners of load-bearing walls.                             AR108.4 Wall connections to primary frame. The straw bale
   AR107.5.1 Pinning. The first course of bales shall be laid         in-fill walls shall be securely anchored to all adjacent structural
   by impaling the bales on the vertical bars or threaded rods, if    members to sufficiently resist lateral displacement of the straw
   any, extending from the foundation. When the fourth course         bale in-fill walls.
   has been laid, No. 4 rebar pins, or an acceptable equivalent,         AR108.4.1 Anchors. Anchors shall be placed at every hori-
   long enough to extend through all four courses, shall be              zontal joint or one per bale along the vertical member and a
   driven down through the bales, two in each bale, located so           maximum of 24 inches (610 mm) on the center along hori-
   that they do not pass within 6 inches (153 mm) of, or                 zontal members at the top of the straw bale wall beginning
   through the space between the ends of any two bales. The              not more than 12 inches (305 mm) from each end of the
   layout of these pins shall approximate the layout of the verti-       in-fill.
   cal rebars extending from the foundation. As each subse-
   quent course is laid, two such pins, long enough to extend            AR108.4.2 Metal lath. At all points where the straw bales
   through the course being laid and the three courses immedi-           are butted against a different material (wood, concrete,
   ately below it, shall be driven down through each bale. This          steel, etc.), metal lath shall be used to cover the junction. Ex-
   pinning method shall be continued to the top of the wall. In          panded metal lath shall extend a minimum of 6 inches (153
   walls seven or eight courses high, pinning at the fifth course        mm) over the edge of the straw bales and shall be securely
   may be eliminated.                                                    fastened to the straw bales.
      AR107.5.1.1 Corners and openings. Vertical No. 4                AR108.5 Stacking and pinning. Nonbearing straw bale walls
      rebar pins, or an acceptable alternative, shall be located      shall be stacked and pinned as described in Section AR107.5
      within 1 foot (305 mm) of all corners or door openings.         AR108.6 Openings and lintels. The limitations of the open-
      AR107.5.1.2 Staples at corners. Staples made of No. 3           ings relative to wall area is controlled by the design of the pri-
      or larger rebar formed into a “U” shape, at least 18 inches     mary frame.
      (457 mm) long with two 6-inch (153 mm) legs, shall be           AR108.7 Wall Height. Nonload-bearing walls shall not ex-
      used at all corners of every course, driven with one leg        ceed 12 feet (3658 mm) in height.
      into the top of each abutting corner bale.                         AR108.7.1 Gable end walls. In the nonload-bearing exte-
AR107.6 Gable end walls. In load bearing exterior walls with             rior wall with gable or shed roofs, a continuous assembly as
gable or shed roofs, a continuous assembly as described in Sec-          described in Section AR110.1 shall be provided that contin-

2008 OREGON RESIDENTIAL SPECIALTY CODE                                                                                                R-3
APPENDIX R




   ues through the gable end wall or shall meet the require-         structure to the foundation. The roof-bearing assembly shall be
   ments of Section R601.2.                                          continuous along the tops of load bearing bale walls.
                                                                        AR110.1.1 Assembly option. An acceptable roof-bearing
                                                                        assembly option consists of two double 2 × 6, or larger, hori-
                        SECTION AR109                                   zontal top plates, one located at the inner edge of the wall
                        WALL FINISHES                                   and the other at the outer edge. Connecting the two doubled
AR109.1 Moisture protection. All weather-exposed bale                   top plates and located horizontally and perpendicular to the
walls shall be protected from water damage. An approved                 length of the wall shall be 2 × 6 cross members spaced no
building moisture barrier shall be used to protect at least the         more than 72 inches (1829 mm) center to center, and as re-
bottom course of bales, but not more than the lower one-third           quired to align with the threaded rods extending from the an-
of the vertical exterior wall surface, in order to allow natural        chor bolts in the foundation. The double 2 × 6 top plates
transpiration of moisture from the bales. The moisture barrier          shall be face nailed with 16d nails staggered at 16 inches
shall have its upper edge inserted at least 6 inches (153 mm)           (406 mm) on center, with laps and intersections face nailed
into the horizontal joint between two courses of bales, and shall       with four 16d nails. The cross members shall be face nailed
extend at least 3 inches (76 mm) below the top of the founda-           to the top plates with four 16d nails at each end. Corner con-
tion. Bale walls shall have special moisture protection provided        nections shall include overlaps nailed as above or an accept-
at all window sills. Unless protected by a roof, the tops of walls      able equivalent such as plywood gussets or metal plates.
shall also be protected. This moisture protection shall consist         Alternatives to this roof-bearing assembly option shall pro-
of a waterproof membrane, such as asphalt-impregnated felt              vide equal or greater vertical rigidity and provide horizontal
paper, polyethylene sheeting, or other acceptable moisture bar-         rigidity equivalent to a continuous double 2 × 4 top plate.
rier, installed in such manner as to prevent water from entering           The connection of roof framing members to the roof bear-
the wall system at window sills or at the tops of walls.                ing assembly shall comply with the appropriate sections of
   A vapor barrier paint having a 1-perm dry cup rating or less         this code.
shall be applied to the interior wall finish of straw bale walls
which separate heated and nonheated spaces and exterior walls
for compliance with Section N1104.9.1.                                                     SECTION AR111
                                                                          ELECTRICAL, PLUMBING AND MECHANICAL
AR109.2 Protection. Interior and exterior surfaces of bale
                                                                     AR111.1 Electrical. All wiring within or on bale walls shall
walls shall be protected from mechanical damage, flames, ani-
                                                                     meet the electrical provisions in this code. Type NM or UF4 ca-
mals, and prolonged exposure to water or snow. Bale walls ad-
                                                                     ble may be used, or wiring may be run in metallic or nonmetal-
jacent to bath and shower enclosures shall be protected by a
                                                                     lic conduit systems.
moisture barrier.
                                                                        Electrical boxes shall be securely attached to wooden stakes
   AR109.2.1 Stucco. Cement stucco shall be reinforced with          driven a minimum of 12 inches (305 mm) into the bales, or an
   galvanized woven wire, stucco netting or an acceptable            acceptable equivalent.
   equivalent. Such reinforcement shall be secured by attach-
   ment through the wall at a maximum spacing of 24 inches           AR111.2 Plumbing. Water or DWV pipes within bale walls
   (610 mm) horizontally and 16 inches (406 mm) vertically,          shall be encased in a continuous pipe sleeve to prevent leakage
   using a method approved by the building official.                 within the wall. Where pipes are mounted on bale walls, they
                                                                     shall be isolated from the bales by a moisture barrier.
     Where bales abut other materials the plaster/stucco shall
   be reinforced with galvanized expanded metal lath, or an ac-      AR111.3 Mechanical. Gas pipes within bale walls shall be en-
   ceptable equivalent, extending a minimum of 6 inches (153         cased in a continuous pipe sleeve to prevent leakage within the
   mm) onto the bales.                                               wall. Where pipes are mounted on bale walls, they shall be iso-
                                                                     lated from the bales by a moisture barrier.
   AR109.2.2 Plasters. Earthen and lime-based plasters may
   be applied directly onto the exterior and interior surface of
   bale walls without reinforcement, except where applied
   over materials other than straw. Weather-exposed earthen
   plasters shall be Portland cement stabilized using methods
   of application approved by the building official.
      Lime based plasters may be applied directly onto the ex-
   terior surface of bale walls without reinforcement, except
   where applied over materials other than straw.


                      SECTION AR110
              ROOF-TO-WALL CONNECTION
AR110.1 Roof-bearing assembly. Load-bearing bale walls
shall have a roof-bearing assembly at the top of the wall to bear
the roof load and to provide a means of connecting the roof

R-4                                                                                  2008 OREGON RESIDENTIAL SPECIALTY CODE

More Related Content

What's hot

Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Mike Coughlin
 
The tensile-strength
The tensile-strengthThe tensile-strength
The tensile-strengthLusitania hsr
 
EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER
 EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER  EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER
EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER SufiyanAhmedJeddy
 
Intake and Pipes joining
Intake and Pipes joiningIntake and Pipes joining
Intake and Pipes joiningLobsang Jampa
 
BIMETALLIC STRIPPER&PRE-CONC.
BIMETALLIC STRIPPER&PRE-CONC.BIMETALLIC STRIPPER&PRE-CONC.
BIMETALLIC STRIPPER&PRE-CONC.vipul srivastava
 
Neogard Product Presentation N6
Neogard Product Presentation   N6Neogard Product Presentation   N6
Neogard Product Presentation N6harleyguy
 
Bnp 65 pressure_blast_cabinet
Bnp 65 pressure_blast_cabinetBnp 65 pressure_blast_cabinet
Bnp 65 pressure_blast_cabinetJane Smith
 
BISOL Solar Company: PV Mounting Systems 2011
BISOL Solar Company: PV Mounting Systems 2011BISOL Solar Company: PV Mounting Systems 2011
BISOL Solar Company: PV Mounting Systems 2011BISOL Solar Company
 
WPM 002 Australian version
WPM 002 Australian versionWPM 002 Australian version
WPM 002 Australian versionnandu_raga
 
CP Material & Their Specific Uses - Charlie Poore - 2.5.2020
CP Material & Their Specific Uses - Charlie Poore - 2.5.2020CP Material & Their Specific Uses - Charlie Poore - 2.5.2020
CP Material & Their Specific Uses - Charlie Poore - 2.5.2020nacetwincities
 
Fero Strata product brochure 2013_friction_bolts
Fero Strata product brochure 2013_friction_boltsFero Strata product brochure 2013_friction_bolts
Fero Strata product brochure 2013_friction_boltsBrian Patience
 
Fero Strata product brochure 2013_strata-support-plates
Fero Strata product brochure 2013_strata-support-platesFero Strata product brochure 2013_strata-support-plates
Fero Strata product brochure 2013_strata-support-platesBrian Patience
 
Installation, testing and jointing of lt and ht power cables up to 33 kv
Installation, testing and jointing of lt and ht power cables up to 33 kvInstallation, testing and jointing of lt and ht power cables up to 33 kv
Installation, testing and jointing of lt and ht power cables up to 33 kvAlexander Decker
 
Bnp 55 suction_blast_cabinet
Bnp 55 suction_blast_cabinetBnp 55 suction_blast_cabinet
Bnp 55 suction_blast_cabinetJane Smith
 

What's hot (20)

Taming pipes
Taming pipesTaming pipes
Taming pipes
 
Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005Vent-Top X 1 and X 2 2005
Vent-Top X 1 and X 2 2005
 
The tensile-strength
The tensile-strengthThe tensile-strength
The tensile-strength
 
Bio engineering tips
Bio engineering tipsBio engineering tips
Bio engineering tips
 
EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER
 EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER  EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER
EXPERIMENTAL INVESTIGATION ON BEHAVIOR OF BAMBOO REINFORCED CONCRETE MEMBER
 
Intake and Pipes joining
Intake and Pipes joiningIntake and Pipes joining
Intake and Pipes joining
 
BIMETALLIC STRIPPER&PRE-CONC.
BIMETALLIC STRIPPER&PRE-CONC.BIMETALLIC STRIPPER&PRE-CONC.
BIMETALLIC STRIPPER&PRE-CONC.
 
Neogard Product Presentation N6
Neogard Product Presentation   N6Neogard Product Presentation   N6
Neogard Product Presentation N6
 
Bnp 65 pressure_blast_cabinet
Bnp 65 pressure_blast_cabinetBnp 65 pressure_blast_cabinet
Bnp 65 pressure_blast_cabinet
 
BISOL Solar Company: PV Mounting Systems 2011
BISOL Solar Company: PV Mounting Systems 2011BISOL Solar Company: PV Mounting Systems 2011
BISOL Solar Company: PV Mounting Systems 2011
 
WPM 002 Australian version
WPM 002 Australian versionWPM 002 Australian version
WPM 002 Australian version
 
CP Material & Their Specific Uses - Charlie Poore - 2.5.2020
CP Material & Their Specific Uses - Charlie Poore - 2.5.2020CP Material & Their Specific Uses - Charlie Poore - 2.5.2020
CP Material & Their Specific Uses - Charlie Poore - 2.5.2020
 
Fero Strata product brochure 2013_friction_bolts
Fero Strata product brochure 2013_friction_boltsFero Strata product brochure 2013_friction_bolts
Fero Strata product brochure 2013_friction_bolts
 
Fero Strata product brochure 2013_strata-support-plates
Fero Strata product brochure 2013_strata-support-platesFero Strata product brochure 2013_strata-support-plates
Fero Strata product brochure 2013_strata-support-plates
 
Gypsum Board
Gypsum BoardGypsum Board
Gypsum Board
 
Installation, testing and jointing of lt and ht power cables up to 33 kv
Installation, testing and jointing of lt and ht power cables up to 33 kvInstallation, testing and jointing of lt and ht power cables up to 33 kv
Installation, testing and jointing of lt and ht power cables up to 33 kv
 
Bamboo
BambooBamboo
Bamboo
 
Bnp 55 suction_blast_cabinet
Bnp 55 suction_blast_cabinetBnp 55 suction_blast_cabinet
Bnp 55 suction_blast_cabinet
 
Tron flex
Tron  flexTron  flex
Tron flex
 
Gypsum
GypsumGypsum
Gypsum
 

Viewers also liked

Here are the top 19 animals that kill the most humans
Here are the top 19 animals that kill the most humansHere are the top 19 animals that kill the most humans
Here are the top 19 animals that kill the most humansAlexandria University, Egypt
 
Resource ordering and mgmt presentation
Resource ordering and mgmt presentationResource ordering and mgmt presentation
Resource ordering and mgmt presentationBrandon Williams
 
Prirucnik tehnologijezaodrzivisvijet4web
Prirucnik tehnologijezaodrzivisvijet4webPrirucnik tehnologijezaodrzivisvijet4web
Prirucnik tehnologijezaodrzivisvijet4webMatija Kojitijevrag
 
Presentation2
Presentation2Presentation2
Presentation2rnck
 
Crossing Office Applications
Crossing Office ApplicationsCrossing Office Applications
Crossing Office Applicationsimacat .
 

Viewers also liked (20)

Here are the top 19 animals that kill the most humans
Here are the top 19 animals that kill the most humansHere are the top 19 animals that kill the most humans
Here are the top 19 animals that kill the most humans
 
15 charlotte bh_andersen_hillerslev i thy
15 charlotte bh_andersen_hillerslev i thy15 charlotte bh_andersen_hillerslev i thy
15 charlotte bh_andersen_hillerslev i thy
 
Theis Jensen - the use of 3 d photogrammetry for on-site recording
Theis Jensen - the use of 3 d photogrammetry for on-site recordingTheis Jensen - the use of 3 d photogrammetry for on-site recording
Theis Jensen - the use of 3 d photogrammetry for on-site recording
 
Louise Lund Johansen - om tørvegrave i nordsjælland
Louise Lund Johansen  - om tørvegrave i nordsjællandLouise Lund Johansen  - om tørvegrave i nordsjælland
Louise Lund Johansen - om tørvegrave i nordsjælland
 
Astrid Skou og Jannie Holm - spor efter udvinding og forarbejdning af jern
Astrid Skou og Jannie Holm -  spor efter udvinding og forarbejdning af jernAstrid Skou og Jannie Holm -  spor efter udvinding og forarbejdning af jern
Astrid Skou og Jannie Holm - spor efter udvinding og forarbejdning af jern
 
Jens Aagaard - Thomas b triges gade
Jens Aagaard -  Thomas b triges gadeJens Aagaard -  Thomas b triges gade
Jens Aagaard - Thomas b triges gade
 
Janet marstine - Museum ethics and museum change
Janet marstine  - Museum ethics and museum changeJanet marstine  - Museum ethics and museum change
Janet marstine - Museum ethics and museum change
 
Resource ordering and mgmt presentation
Resource ordering and mgmt presentationResource ordering and mgmt presentation
Resource ordering and mgmt presentation
 
Prirucnik tehnologijezaodrzivisvijet4web
Prirucnik tehnologijezaodrzivisvijet4webPrirucnik tehnologijezaodrzivisvijet4web
Prirucnik tehnologijezaodrzivisvijet4web
 
23 ditte skovjensen_k+ªrg+ñrd ôçô en maglemoselokalitet i midtjylland
23 ditte skovjensen_k+ªrg+ñrd ôçô en maglemoselokalitet i midtjylland23 ditte skovjensen_k+ªrg+ñrd ôçô en maglemoselokalitet i midtjylland
23 ditte skovjensen_k+ªrg+ñrd ôçô en maglemoselokalitet i midtjylland
 
Jørgen Westphal - bevaring af birkebark i jættestuen maglehøj
Jørgen Westphal  - bevaring af birkebark i jættestuen maglehøjJørgen Westphal  - bevaring af birkebark i jættestuen maglehøj
Jørgen Westphal - bevaring af birkebark i jættestuen maglehøj
 
107 anne bjerrekj+ªr_f+ªngselsmuseet i horsens
107 anne bjerrekj+ªr_f+ªngselsmuseet i horsens107 anne bjerrekj+ªr_f+ªngselsmuseet i horsens
107 anne bjerrekj+ªr_f+ªngselsmuseet i horsens
 
96 jannie amsgaardebsen_tips & tricks
96 jannie amsgaardebsen_tips & tricks96 jannie amsgaardebsen_tips & tricks
96 jannie amsgaardebsen_tips & tricks
 
Merete Sanderhoff og Jacob Wang: Passion for tilgængelig kulturarv. ODM Inter...
Merete Sanderhoff og Jacob Wang: Passion for tilgængelig kulturarv. ODM Inter...Merete Sanderhoff og Jacob Wang: Passion for tilgængelig kulturarv. ODM Inter...
Merete Sanderhoff og Jacob Wang: Passion for tilgængelig kulturarv. ODM Inter...
 
Presentation2
Presentation2Presentation2
Presentation2
 
28 kirsten christensen_bronzealderguld i boeslunde
28 kirsten christensen_bronzealderguld i boeslunde28 kirsten christensen_bronzealderguld i boeslunde
28 kirsten christensen_bronzealderguld i boeslunde
 
Vvoj2014
Vvoj2014Vvoj2014
Vvoj2014
 
Crossing Office Applications
Crossing Office ApplicationsCrossing Office Applications
Crossing Office Applications
 
Hans Mikkelsen - fjelstrup kirke
Hans Mikkelsen - fjelstrup kirkeHans Mikkelsen - fjelstrup kirke
Hans Mikkelsen - fjelstrup kirke
 
Karin Poulsen - håndværkerbebyggelse
Karin Poulsen -  håndværkerbebyggelseKarin Poulsen -  håndværkerbebyggelse
Karin Poulsen - håndværkerbebyggelse
 

Similar to Appendix r straw bale structures

Similar to Appendix r straw bale structures (20)

IS 13827
IS 13827IS 13827
IS 13827
 
Bamboo reinforced concrete
Bamboo reinforced concreteBamboo reinforced concrete
Bamboo reinforced concrete
 
Bamboo Reinforced Concrete
Bamboo Reinforced ConcreteBamboo Reinforced Concrete
Bamboo Reinforced Concrete
 
Bamboo a sustainable construction
Bamboo a sustainable constructionBamboo a sustainable construction
Bamboo a sustainable construction
 
Hdpe installation practice
Hdpe installation practiceHdpe installation practice
Hdpe installation practice
 
Hdpe installation practice
Hdpe installation practiceHdpe installation practice
Hdpe installation practice
 
Guidelines for construction of masonry with siporex
Guidelines for construction of masonry with siporexGuidelines for construction of masonry with siporex
Guidelines for construction of masonry with siporex
 
Replacement of Steel by Bamboo Reinforcement
Replacement of Steel by Bamboo ReinforcementReplacement of Steel by Bamboo Reinforcement
Replacement of Steel by Bamboo Reinforcement
 
3873
38733873
3873
 
Air seasoning
Air seasoningAir seasoning
Air seasoning
 
Bamboo construction, Ferrocement, Wattle & Daub technique
Bamboo construction, Ferrocement, Wattle & Daub techniqueBamboo construction, Ferrocement, Wattle & Daub technique
Bamboo construction, Ferrocement, Wattle & Daub technique
 
Cost effective roofs
Cost effective roofsCost effective roofs
Cost effective roofs
 
Auxiliary ventilation
Auxiliary ventilationAuxiliary ventilation
Auxiliary ventilation
 
IS 13828
IS 13828IS 13828
IS 13828
 
Designing with Tile
Designing with TileDesigning with Tile
Designing with Tile
 
Bamboo-as-Construction-Material.pptx
Bamboo-as-Construction-Material.pptxBamboo-as-Construction-Material.pptx
Bamboo-as-Construction-Material.pptx
 
Fabric as a building material
Fabric as a building materialFabric as a building material
Fabric as a building material
 
Cps wall vent9351l
Cps wall vent9351lCps wall vent9351l
Cps wall vent9351l
 
Termite Treatment
Termite TreatmentTermite Treatment
Termite Treatment
 
Laminar box
Laminar boxLaminar box
Laminar box
 

More from Matija Kojitijevrag

More from Matija Kojitijevrag (8)

Presentacio forn-solar-cob-en
Presentacio forn-solar-cob-enPresentacio forn-solar-cob-en
Presentacio forn-solar-cob-en
 
Solar%20cooker%20 jse
Solar%20cooker%20 jseSolar%20cooker%20 jse
Solar%20cooker%20 jse
 
Odrziva20gradnja
Odrziva20gradnjaOdrziva20gradnja
Odrziva20gradnja
 
Cooker book_ sun tracking
Cooker book_ sun trackingCooker book_ sun tracking
Cooker book_ sun tracking
 
Biodinamika
BiodinamikaBiodinamika
Biodinamika
 
Sa dobroshura
Sa dobroshuraSa dobroshura
Sa dobroshura
 
Straw bale home basics
Straw bale home basicsStraw bale home basics
Straw bale home basics
 
Narby, jeremy kozmicka zmija (dnk i podrijetlo znanja)
Narby, jeremy   kozmicka zmija (dnk i podrijetlo znanja)Narby, jeremy   kozmicka zmija (dnk i podrijetlo znanja)
Narby, jeremy kozmicka zmija (dnk i podrijetlo znanja)
 

Recently uploaded

8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCRashishs7044
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCRashishs7044
 
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptxContemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptxMarkAnthonyAurellano
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdfKhaled Al Awadi
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfpollardmorgan
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Servicecallgirls2057
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessSeta Wicaksana
 
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,noida100girls
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Kirill Klimov
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?Olivia Kresic
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckHajeJanKamps
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607dollysharma2066
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation SlidesKeppelCorporation
 
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadIslamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadAyesha Khan
 
Future Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionFuture Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionMintel Group
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfrichard876048
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesKeppelCorporation
 

Recently uploaded (20)

8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
8447779800, Low rate Call girls in New Ashok Nagar Delhi NCR
 
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
8447779800, Low rate Call girls in Uttam Nagar Delhi NCR
 
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptxContemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
Contemporary Economic Issues Facing the Filipino Entrepreneur (1).pptx
 
Corporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information TechnologyCorporate Profile 47Billion Information Technology
Corporate Profile 47Billion Information Technology
 
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdfNewBase  19 April  2024  Energy News issue - 1717 by Khaled Al Awadi.pdf
NewBase 19 April 2024 Energy News issue - 1717 by Khaled Al Awadi.pdf
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
 
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort ServiceCall US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
Call US-88OO1O2216 Call Girls In Mahipalpur Female Escort Service
 
Organizational Structure Running A Successful Business
Organizational Structure Running A Successful BusinessOrganizational Structure Running A Successful Business
Organizational Structure Running A Successful Business
 
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Old Faridabad ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
 
Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024Flow Your Strategy at Flight Levels Day 2024
Flow Your Strategy at Flight Levels Day 2024
 
MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?MAHA Global and IPR: Do Actions Speak Louder Than Words?
MAHA Global and IPR: Do Actions Speak Louder Than Words?
 
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deckPitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
Pitch Deck Teardown: Geodesic.Life's $500k Pre-seed deck
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
(Best) ENJOY Call Girls in Faridabad Ex | 8377087607
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
 
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in IslamabadIslamabad Escorts | Call 03070433345 | Escort Service in Islamabad
Islamabad Escorts | Call 03070433345 | Escort Service in Islamabad
 
Future Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted VersionFuture Of Sample Report 2024 | Redacted Version
Future Of Sample Report 2024 | Redacted Version
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
Innovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdfInnovation Conference 5th March 2024.pdf
Innovation Conference 5th March 2024.pdf
 
Annual General Meeting Presentation Slides
Annual General Meeting Presentation SlidesAnnual General Meeting Presentation Slides
Annual General Meeting Presentation Slides
 

Appendix r straw bale structures

  • 1. APPENDIX R STRAW-BALE STRUCTURES SECTION AR101 ilar plants, shall be acceptable if they meet the minimum re- PURPOSE quirements for density, shape, moisture content and ties. AR101.1 Minimum standards. The purpose of this appendix AR104.2 Shape. Bales shall be rectangular in shape. chapter is to establish minimum prescriptive standards of AR104.2.1 Dimensions. Bales used within a continuous safety for the construction of structures that use baled straw as a wall shall be of consistent height and width to ensure even load-bearing or nonload-bearing material. distribution of loads within wall systems. AR104.2.2 Wall thickness. Nominal minimum bale wall thickness shall be 14 inches (356 mm). SECTION AR102 SCOPE AR104.2.3 Custom size bales. Where custom made partial AR102.1 Applicability. The provisions of this chapter shall bales are used, they shall be of the same density, same string apply to single family detached structures and relate accessory or wire tension, and where possible, use the same number of structures as defined in Section R101.9, utilizing straw bales in ties as the standard size bales. the construction of wall systems. AR104.3 Ties. Bales shall be bound with ties of either poly- propylene string or baling wire. Bales with broken or loose ties shall not be used unless the broken or loose ties are replaced SECTION AR103 with ties which restore the original degree of compaction of the DEFINITIONS bale. AR103.1 General. For the purpose of this chapter, certain AR104.4 Moisture content. Moisture content of bales, at time terms are defined as follows: of installation and just prior to applying exterior weather pro- BALES. Rectangular compressed blocks of straw, bound by tection such as stucco, shall not exceed 20 percent of the total strings or wire. weight of the bale. Bales that become wet or exceed 20-percent moisture content shall be replaced with dry bales or allowed to FLAKES. Slabs of straw removed from an untied bale. Flakes dry and be retested. Bales that exceed 20-percent moisture con- are used to fill small gaps between the ends of stacked bales. tent shall be replaced. Special inspection of the moisture con- LAID FLAT. Refers to stacking bales so that the sides with the tent of bales shall be performed using one of he following largest cross-sectional area are horizontal and the longest di- methods: mension of this area is parallel with the wall plane. AR104.4.1 Field method. A suitable moisture meter, de- LAID ON EDGE. Refers to stacking bales so that the sides signed for use with baled straw or hay, and equipped with a with the largest cross-sectional area are vertical and the longest probe of sufficient length to reach the center of the bale, dimension of this area is horizontal and parallel with the wall shall be used to determine the average moisture content of plane. five bales randomly selected from the bales to be used. STRAW. The dry stems of cereal grains left after the seed AR104.4.2 Laboratory method. A total of five samples, heads have been removed. taken from the center of each of five bales randomly se- lected from the bales to be used, shall be tested for moisture LOAD BEARING. The use of straw bale walls as structural content by a recognized testing lab. load-bearing walls supporting the roof and resisting lateral loads. AR104.5 Density. Bales in load-bearing structures shall have a minimum calculated dry density of 7.0 pounds per cubic foot NONLOAD BEARING. A structure where straw bales are (112 kg/m3). The calculated dry density shall be determined af- used to in-fill between the supporting structural members. The ter reducing the actual bale weight by the weight of the mois- exterior straw bale in-fill wall sections collect lateral loads re- ture content, as determined in Section AR104.4. The sulting from wind or seismic activity and transfer these loads to calculated dry density shall be determined by dividing the cal- the primary structure for resistance. culated dry weight of the bale by the volume of the bale. IN-FILL WALL. The nonbearing section between vertical supports. SECTION AR105 FOUNDATION REQUIREMENTS SECTION AR104 AR105.1 Foundations. Foundations shall comply with Chap- MATERIAL SPECIFICATIONS ter 4. Foundations shall be sized to accommodate the thickness AR104.1 Type of straw. Bales of various types of straw, in- of the bale wall and support the imposed live and dead loads cluding, but not limited to wheat, rice, rye, barley, oats and sim- from walls and roofs. The minimum width of the footing shall 2008 OREGON RESIDENTIAL SPECIALTY CODE R-1
  • 2. APPENDIX R be the width of the bale it supports, except that the bales may 1. Wooden dowels at least 5/8 inch (16 mm) in diameter, of overhang the exterior edge of the foundation by not more than 3 sufficient length to provide 12 inches (305 mm) of pene- inches (76 mm) to accommodate rigid perimeter insulation. tration into the bale, driven through holes bored in the abutting wall stud, and spaced to provide one dowel con- AR105.2 Wall reinforcement embedded in foundation. Ver- nection per bale. tical reinforcing bars with a minimum diameter of 1/2 inch (12.7 mm), shall be embedded in the foundation a minimum depth of 2. Pointed wooden stakes, at least 12 inches (305 mm) in 6 inches (153 mm), and shall extend above the foundation a length and 11/2 inch by 31/2 (38.1 mm by 88.9 mm) at the minimum of 12 inches (304.8 mm). These vertical bars shall be exposed end, fully driven into each course of bales, as an- located along the centerline of the bale wall, spaced not more chorage points. than 2 feet (610 mm) apart. A vertical bar shall also be located 3. Bolted or threaded rod connection of the abutting wall, within 1 foot (305 mm) of any opening or corner, except at lo- through the bale wall, to a steel nut and steel or plywood cations occupied by anchor bolts. plate washer, a minimum of 6 inches (153 mm) square and a minimum thickness of 3/16 inch (4.8 mm) for steel AR105.3 Moisture barrier. A moisture barrier shall be used and 1/2 inch (12.7 mm) for plywood, in at least three loca- between the top of the foundation and the bottom of the bale tions. wall to prevent moisture from migrating through the founda- tion into the bottom course of bales. This barrier shall consist of one of the following. SECTION AR107 1. Cementious waterproof coating; LOAD-BEARING WALLS 2. Type 30 asphalt felt over an asphalt emulsion; AR107.1 Anchor bolts. In addition to vertical reinforcement 3. Sheet metal flashing, sealed at joints; or bars required in Section M105.2, load-bearing bale walls shall 4. Other approved building moisture barrier. be anchored to the foundation by 1/2-inch (12.7 mm) diameter steel anchor bolts embedded at least 7 inches (178 mm) in the All penetrations through the moisture barrier, as well as all foundation at intervals of 6 feet (1829 mm) or less. A minimum joints in the barrier, must be sealed with asphalt, caulking or an of two anchor bolts per wall shall be provided with one bolt lo- approved sealant. cated within 36 inches (914 mm) of each end of each wall. Sec- tions of 1/2-inch (12.7 mm) diameter threaded rod shall be connected to the anchor bolts, and to each other, by means of SECTION AR106 threaded coupling nuts and shall extend through the roof-bear- WALL CONSTRUCTION ing assembly and be fastened with a steel washer and nut. Bale AR106.1 General (fire resistance). Bale walls, when covered walls and roof-bearing assemblies may be anchored to the with plaster or stucco shall be deemed to be fire resistive. foundation by means of other methods, which are adequate to resist uplift forces resulting from the design wind load. There A straw bale covered with plaster or stucco having a mini- shall be a minimum of two points of anchorage per wall, spaced mum thickness of 7/8 inch (22.4 mm) on both sides maybe used not more than 6 feet (1829 mm) apart, with one located within between a dwelling and attached garage as required in Section 36 inches (914 mm) of each end of each wall. R309.2. The dead load of the roof and ceiling systems will produce AR106.2 Allowable Loads. The allowable vertical load (live vertical compression of the bales. Regardless of the anchoring and dead load) on the top of load-bearing bale walls shall not system used to attach the roof bearing assembly to the founda- exceed 360 pounds per square foot (psf) (17.2 kPa) [23 inches tion, prior to installation of wall finish materials, bolts, straps or (84.2 mm) divided by 12 inches (304.8 mm) by 360 pounds cables shall be retightened to compensate for this compression (17.2 kPa) = 690 pounds per linear foot (plf) (10.1 N/mm] and after the actual dead load of the roof framing and roofing have the resultant load shall act at the center of the wall. Bale struc- been applied. tures shall be designed to withstand all vertical and horizontal loads as specified in Chapter 3 and the Structural Code, Chap- AR107.2 Load-bearing wall height. Load-bearing straw bale ter 16. Increases in stress and reductions of live loads specified walls shall not exceed one story in height and the bale portion in Structural Code Chapter 16 may be applied. shall not exceed a height to width ratio of 5.6:1 [for example, the maximum height for the bale portion of a 23-inch-thick AR106.3 Insulation. Exterior walls using straw bales shall be (584 mm) wall would be 10 feet, 8 inches (3251 mm)]. considered to meet the wall insulation requirements of Path 1 AR107.3 Unsupported wall length. The ratio of unsupported as described in Section N1104. All other exterior wall compo- wall length to thickness, for load-bearing bale walls, shall not nents shall comply with Section N1104. For the purpose of cal- exceed 13:1 [for a 23-inch (584 mm) thick wall, the maximum culating thermal performance using Table N1104.1.2, the unsupported length allowed is 25 feet (7620 mm)]. insulation of straw bale walls can assume to be R-2.1 per inch [a 23-inch (584 mm) bale would be R-48 or U-0.021]. AR107.4 Openings and lintels. All openings in load-bearing bale walls shall be a minimum of one full bale length from any AR106.4 Intersecting walls. Walls of other materials inter- outside corner. secting bale walls shall be attached to the bale wall by means of one or more of the following methods or an acceptable equiva- AR107.4.1 Openings. Openings in exterior bale walls shall lent: not exceed 50 percent of the total wall area, based on interior R-2 2008 OREGON RESIDENTIAL SPECIALTY CODE
  • 3. APPENDIX R dimensions, where the wall is providing resistance to lateral tion AR110.1 shall be provided that continues through the loads. gable end walls. Door and window frames (rough bucks) shall be stabi- lized with 1/2-inch (12.7 mm) diameter hardwood dowels extending 12 inches (305 mm) into every adjacent bale or by SECTION AR108 means of a continuous metal lath applied to both the interior NONLOAD-BEARING WALLS and exterior, extending a minimum of 12 inches (305 mm) AR108.1 General. A nonload-bearing wall is part of a struc- onto adjacent bales, installed prior to the application of plas- tural system where the primary frame is an approved system ter or stucco. complying with this code or Structural Code Chapter 16. The straw bales are used as in-fill between structural members or AR107.4.2 Lintels. Wall and/or roof load present above any framing. opening shall be carried, or transferred to the bales below by one of the following: AR108.2 Primary frame. The primary frame (such as post and beam or pole building) shall comply with this code or 1. A structural frame, Structural Code Chapter 16. Structural calculations showing 2. A lintel (such as an angle-iron cradle, wooden beam, compliance shall be submitted with plans and application for wooden box beam). Lintels shall be at least twice as building permits. long as the opening is wide and extend at least 24 AR108.2.1 Anchorage to foundation. The primary frame inches (610 mm) beyond either side of the opening. shall be anchored to the foundation in accordance with Lintels shall be centered over openings, and shall not Chapters 4 and 6 of this code or Structural Code Chapter 16. exceed the load limitations of Section AR106.2 by more than 25 percent. AR108.3 Wall anchorage to foundation. Vertical reinforcing 3. A roof-bearing assembly designed to act as a rigid bars with a minimum diameter of 1/2 inch (12.7 mm) shall be beam over the opening. embedded in the foundation a minimum depth of 6 inches (153 mm), and shall extend above the foundation a minimum of AR107.5 Stacking. Bales in load-bearing walls shall be laid one-and-one-half bales. flat and stacked in running bond where possible, with each bale overlapping the two bales beneath it. Bales in nonload-bearing AR108.3.1 Location. The vertical bars shall be located walls may be laid either flat or on-edge and stacked in running along the centerline of the bale wall, spaced not more than 2 bond where possible. Overlaps shall be a minimum of 12 feet (610 mm) apart and a minimum of two per bale. inches (305 mm). Gaps between the ends of bales which are AR108.3.2 Corners and openings. A vertical bar shall be less than 6 inches (153 mm) in width may be filled by an untied located within 1 foot (305 mm) of any opening or corner, ex- flake inserted snugly into the gap. Only full-length bales shall cept at locations occupied by anchor bolts. be used at corners of load-bearing walls. AR108.4 Wall connections to primary frame. The straw bale AR107.5.1 Pinning. The first course of bales shall be laid in-fill walls shall be securely anchored to all adjacent structural by impaling the bales on the vertical bars or threaded rods, if members to sufficiently resist lateral displacement of the straw any, extending from the foundation. When the fourth course bale in-fill walls. has been laid, No. 4 rebar pins, or an acceptable equivalent, AR108.4.1 Anchors. Anchors shall be placed at every hori- long enough to extend through all four courses, shall be zontal joint or one per bale along the vertical member and a driven down through the bales, two in each bale, located so maximum of 24 inches (610 mm) on the center along hori- that they do not pass within 6 inches (153 mm) of, or zontal members at the top of the straw bale wall beginning through the space between the ends of any two bales. The not more than 12 inches (305 mm) from each end of the layout of these pins shall approximate the layout of the verti- in-fill. cal rebars extending from the foundation. As each subse- quent course is laid, two such pins, long enough to extend AR108.4.2 Metal lath. At all points where the straw bales through the course being laid and the three courses immedi- are butted against a different material (wood, concrete, ately below it, shall be driven down through each bale. This steel, etc.), metal lath shall be used to cover the junction. Ex- pinning method shall be continued to the top of the wall. In panded metal lath shall extend a minimum of 6 inches (153 walls seven or eight courses high, pinning at the fifth course mm) over the edge of the straw bales and shall be securely may be eliminated. fastened to the straw bales. AR107.5.1.1 Corners and openings. Vertical No. 4 AR108.5 Stacking and pinning. Nonbearing straw bale walls rebar pins, or an acceptable alternative, shall be located shall be stacked and pinned as described in Section AR107.5 within 1 foot (305 mm) of all corners or door openings. AR108.6 Openings and lintels. The limitations of the open- AR107.5.1.2 Staples at corners. Staples made of No. 3 ings relative to wall area is controlled by the design of the pri- or larger rebar formed into a “U” shape, at least 18 inches mary frame. (457 mm) long with two 6-inch (153 mm) legs, shall be AR108.7 Wall Height. Nonload-bearing walls shall not ex- used at all corners of every course, driven with one leg ceed 12 feet (3658 mm) in height. into the top of each abutting corner bale. AR108.7.1 Gable end walls. In the nonload-bearing exte- AR107.6 Gable end walls. In load bearing exterior walls with rior wall with gable or shed roofs, a continuous assembly as gable or shed roofs, a continuous assembly as described in Sec- described in Section AR110.1 shall be provided that contin- 2008 OREGON RESIDENTIAL SPECIALTY CODE R-3
  • 4. APPENDIX R ues through the gable end wall or shall meet the require- structure to the foundation. The roof-bearing assembly shall be ments of Section R601.2. continuous along the tops of load bearing bale walls. AR110.1.1 Assembly option. An acceptable roof-bearing assembly option consists of two double 2 × 6, or larger, hori- SECTION AR109 zontal top plates, one located at the inner edge of the wall WALL FINISHES and the other at the outer edge. Connecting the two doubled AR109.1 Moisture protection. All weather-exposed bale top plates and located horizontally and perpendicular to the walls shall be protected from water damage. An approved length of the wall shall be 2 × 6 cross members spaced no building moisture barrier shall be used to protect at least the more than 72 inches (1829 mm) center to center, and as re- bottom course of bales, but not more than the lower one-third quired to align with the threaded rods extending from the an- of the vertical exterior wall surface, in order to allow natural chor bolts in the foundation. The double 2 × 6 top plates transpiration of moisture from the bales. The moisture barrier shall be face nailed with 16d nails staggered at 16 inches shall have its upper edge inserted at least 6 inches (153 mm) (406 mm) on center, with laps and intersections face nailed into the horizontal joint between two courses of bales, and shall with four 16d nails. The cross members shall be face nailed extend at least 3 inches (76 mm) below the top of the founda- to the top plates with four 16d nails at each end. Corner con- tion. Bale walls shall have special moisture protection provided nections shall include overlaps nailed as above or an accept- at all window sills. Unless protected by a roof, the tops of walls able equivalent such as plywood gussets or metal plates. shall also be protected. This moisture protection shall consist Alternatives to this roof-bearing assembly option shall pro- of a waterproof membrane, such as asphalt-impregnated felt vide equal or greater vertical rigidity and provide horizontal paper, polyethylene sheeting, or other acceptable moisture bar- rigidity equivalent to a continuous double 2 × 4 top plate. rier, installed in such manner as to prevent water from entering The connection of roof framing members to the roof bear- the wall system at window sills or at the tops of walls. ing assembly shall comply with the appropriate sections of A vapor barrier paint having a 1-perm dry cup rating or less this code. shall be applied to the interior wall finish of straw bale walls which separate heated and nonheated spaces and exterior walls for compliance with Section N1104.9.1. SECTION AR111 ELECTRICAL, PLUMBING AND MECHANICAL AR109.2 Protection. Interior and exterior surfaces of bale AR111.1 Electrical. All wiring within or on bale walls shall walls shall be protected from mechanical damage, flames, ani- meet the electrical provisions in this code. Type NM or UF4 ca- mals, and prolonged exposure to water or snow. Bale walls ad- ble may be used, or wiring may be run in metallic or nonmetal- jacent to bath and shower enclosures shall be protected by a lic conduit systems. moisture barrier. Electrical boxes shall be securely attached to wooden stakes AR109.2.1 Stucco. Cement stucco shall be reinforced with driven a minimum of 12 inches (305 mm) into the bales, or an galvanized woven wire, stucco netting or an acceptable acceptable equivalent. equivalent. Such reinforcement shall be secured by attach- ment through the wall at a maximum spacing of 24 inches AR111.2 Plumbing. Water or DWV pipes within bale walls (610 mm) horizontally and 16 inches (406 mm) vertically, shall be encased in a continuous pipe sleeve to prevent leakage using a method approved by the building official. within the wall. Where pipes are mounted on bale walls, they shall be isolated from the bales by a moisture barrier. Where bales abut other materials the plaster/stucco shall be reinforced with galvanized expanded metal lath, or an ac- AR111.3 Mechanical. Gas pipes within bale walls shall be en- ceptable equivalent, extending a minimum of 6 inches (153 cased in a continuous pipe sleeve to prevent leakage within the mm) onto the bales. wall. Where pipes are mounted on bale walls, they shall be iso- lated from the bales by a moisture barrier. AR109.2.2 Plasters. Earthen and lime-based plasters may be applied directly onto the exterior and interior surface of bale walls without reinforcement, except where applied over materials other than straw. Weather-exposed earthen plasters shall be Portland cement stabilized using methods of application approved by the building official. Lime based plasters may be applied directly onto the ex- terior surface of bale walls without reinforcement, except where applied over materials other than straw. SECTION AR110 ROOF-TO-WALL CONNECTION AR110.1 Roof-bearing assembly. Load-bearing bale walls shall have a roof-bearing assembly at the top of the wall to bear the roof load and to provide a means of connecting the roof R-4 2008 OREGON RESIDENTIAL SPECIALTY CODE