1. 7 ͭ ͪ FLOOR PLAN
(LEVEL3 RES.)
27810
8 ͭ ͪ FLOOR PLAN
(LEVEL4 RES.)
31410
C
B.O.SLAB3300
B.O.BEAM3100
B.O.CHW2709
B.O.FAD2669
B.O.CEILING2550
B.O.FP3137
B.O.FCU2778
B.O.FP2566
B.O.FP2562
B.O.RACK2600
B.O.FP3054
B.O.SAD2810
B.O.EAD3050
B.O.FP2902
B.O.CHW2899
B.O.SAD3010
B.O.CEILING2400
Ø100 FP
Ø25 FP
Ø65 FP
500x250 FAD
Ø65 FP
FCU
Ø25 FP Ø40 FP 200x150 FAD
Ø32 CHWR
Ø32 CHWS
350x200 EAD
RACK
7 ͭ ͪ FLOOR PLAN
(LEVEL3 RES.)
27810
8 ͭ ͪ FLOOR PLAN
(LEVEL4 RES.)
31410
B.O.SLAB3300
B.O.CEILING2600
B.O.SAD2810
B.O.FP3067
B.O.WP3176
B.O.DCW3079
B.O.FP3067
Ø20 DCW
Ø15 DHW
Ø25 FP
150x750 SA600x200 SAØ20 DCW
Ø15 DHW
Ø25 FP
150x200 SA
SLSD2-1mx25mm 65 L/s
RLSD2-1mx25mm65 L/s
7 ͭ ͪ FLOOR PLAN
(LEVEL3 RES.)
27810
8 ͭ ͪ FLOOR PLAN
(LEVEL4 RES.)
31410
A B.O.SAD2836
B.O.FP2783
B.O.FP2783
B.O.DHW2789
B.O.FCU2787
B.O.WP3085
B.O.DCW3249
B.O.CEILING2700
B.O.CEILING2600
B.O.SLAB3300
FCU
Ø110 WP Ø20 DCWØ25 FP
Ø15 DHW
200x850 SA
Ø25 FP
FVS-1000WD-1833x580x282
CHW-0.23 L/s, SA-453 L/s
AC-T301-LIV
B1(40X90)
B1(40X90)
S .S .L
30. 725
B(30X40)
B(30X40)
S B 4( 50 X7 0)
SB4( 50X70)
SB6(50X140)SB6(50X140)SB6(50X140)
SB6(50X140)
SB6(50X140)SB6(50X140)
S B 5( 60 X9 5)
S B 3( 40 X1 30 ) S B 3( 40 X1 30 )
S .S .L
30. 725
S .S .L
30. 725
S .S .L
30. 725
S .S .L
30. 725
S .S .L
30. 725
B2(40X50)
B2(40X50)
B2(40X50)
B2(40X50)
S B 5A (5 0 X1 05 )
SB9(50X50)
SB9(50X50)
PLBG SHAFT
PLBG SHAFT
M ECH SHAFT
PLBG SHAFT
M ECH SHAFT
PLBG SHAFTM EC H SHA FT
WATERMETER
MECHSHAFT
M ECH SHAFT
PRESSURIZATIONSHAFT
PLBG SHAFT
PLBG SHAFT
FHC
FHC
FI REM EN ELEVATO R
PRESSURIZATIONSHAFT
8400 8400 8400 8400 8400
94008000
A B C D E
F
5
4
3
UP
DN UP
MECCA
TRUENORTH
PROJECTNORTH
P.O. BOX 24689, DUBAI, U.A.E.
TEL. 04 5014800, FAX 04 3306430
www.plafondme.com
architects, designers & planners
TEL +971 4 332 2113+971 4 332 4455 FAX
po box 73033 dubai web site www.naga.ae
___
TEL +971 4 351 8873+971 4 351 8871 FAX
po box 120780 dubai web site www.kele.ae
MEP Contractor :
REFERENCE DWG. NO.:
DRAWING NO. DRAWING TITLEDATE
GENERAL NOTE:
REV
5. DISCREPANCY IN DIMENSIONS/GRAPHICS IN THIS DWG.
MUST BE CLARIFIED PRIOR TO FABRICATION,
EXECUTION AND INSTALLATION ON SITE, IF ANY.
4. ALL DIMENSIONS ARE IN MILLIMETERS OTHERWISE STATED.
1. THIS DRAWING IS THE PROPERTY OF PLAFOND - DUBAI. IT IS
FORBIDDEN TO PRODUCE ITS CONTENTS IN ANY
FORM, EXCEPT FOR THE INTENDED PURPOSE.
2. COPYRIGHT OF DESIGN SHOWN HEREON IS
RETAINED BY THIS OFFICE, AUTHORITY IS
REQUIRED FOR REPRODUCTION.
3. DO NOT SCALE FROM THE DRAWINGS.
Owner :
Rev. DESCRIPTION Date
Reviewed By Consultant
A APPROVED
B APPROVED WITH COMMENT
C REVISE & RESUBMIT
D REJECTED
Signature: Date:
Drawn
Principal Consultant :
1408
Drawing No. : Rev.
Drawing Title :
A0
SizeScale:Checked:Drawn:Job No.
Date: Date: Sheet no:
ANWA Real Estate Development
LLC
Consultant :
Project :
(G+ 4P +44), ON PLOT No: 3212014 (DMC-08b)
DUBAI MARITIME CITY
ANWA BY OMNIYAT
Main Contractor :
6. ALL MEP SERVICES INVERT LEVEL FROM S.S.L
KEY PLAN
MA
24.10.2016 24.10.2016
1 : 25
PLF-1408-AT-SD-CO-011
MS
7th to 9th & 12th to 15th
FLOOR PLAN - MEP H/L
SERVICES COORDINATION
LAYOUT ( 02 OF 02 )
00
00 ISSUED FOR APPROVAL 25.12.2016 MS
00PLF-1408-AT-SD-FP-008 21-04-2016 7th to 9th & 12th to 15th FLOOR FIRE FIGHTING
01PLF-1408-AT-SD-VE-009 21-02-2015
7th to 9th & 12th to 15th AC LAYOUT(LVL 1 RES.)02PLF-1408-AT-SD-AC-010 03-01-2016
01 23-03-2016 7th to 9th & 12th to 15th LIGHTING LAYOUT
7th to 9th & 12th to 15th FAVE LAYOUT(LEVEL 3 RES.)PLF-1408-AT-SD-FAVE-006 02 14-09-2016
A-123 N 21-03-2016 7TH FLOOR PLAN (LEVEL-3 RES.)
S-128 G 21-03-2016 7TH FLOOR PLAN (LEVEL-3 RES.)
VENTILATION 5TH FLOOR PLAN-LVL 01 RES.
LEVEL 7 REFLECTED CEILING PLAN21-03-2016HI-152 A
PLF-1408-AT-SD-EL-008
00 23-03-2016 7th to 9th & 12th to 15th CB LAYOUT(LEVEL 3 RES.)PLF-1408-AT-SD-CB-008
SECTION - 'C' (SCALE 1:25)
CO-ORDINATED CORRIDOR (Axonometric)
CO-ORDINATED CORRIDOR (3D VIEW) 2 BEDROOM LIVING & DINING AREA (3D VIEW)
2 BEDROOM LIVING & DINING AREA (Axonometric)
SECTION - 'D' (SCALE 1:25)
1 BEDROOM LIVING & DINING AREA (Axonometric)
SECTION - 'E' (SCALE 1:25)
1 BEDROOM LIVING & DINING AREA (3D VIEW)