Abstract — The primary objective of a conventional
lightning protection system is to maximize the electric field
above the structure on which it is installed when it is subject to
the electrostatic meteorological environment of a
thunderstorm. This results in the promotion of successful
streamer to leader propagation which ultimately improves the
likelihood of the controlled earth termination of a cloud to
ground (CG) lightning strike. A conventional lightning
protection system is designed to prevent damage to a building
by providing a number of preferential strike receptors (air
terminals) with low impedance paths to conduct the lightning
discharge safely to ground. In this study, via the utilization of
Finite Element Analysis (FEA) software and solid modelling
Computer Aided Design software, several air terminal
topologies comprising conventional and non-conventional
geometrical surface characteristics were modelled in detail and
then subject to an electrostatic simulation environment
(thunderstorm replica) for analysis of their respective electric
field distributions. Results indicate discrepancies of up to
100KV in electric field distribution between that of the
conventional and non-conventional air terminal topologies.
This suggests that significant research opportunities lie within
optimizing the geometrical design of a conventional air
terminal with respect to its corona emission capabilities and
could ultimately lead to a review of LPS protocols embodied in
many national and international Lightning Protection
Standards.
Keywords – Lightning, Lightning Protection System, LPS, Air
Terminal Design, Surface Characteristics, Electric Field
Distribution, finite element modelling.
I. INTRODUCTION
HAT happens on the earth’s surface during a
thunderstorm is extremely relative to what is
happening in the clouds above. The negative charge in a
thundercloud induces a positive charge on the earth’s surface
beneath it. The natural space charge produced by pointed
corona emitting objects such as trees, power lines, antennas
buildings and the like, limits the electric field at ground level
to typically around 10kV/m [3]. In the presence of a
thunderstorm, and on closer approach of the negatively
charged descending stepped leader, the fields at the sharp
conducting points of exposed objects are intensified to such
Manuscript received October 14, 2015; Revised October 14, 2015. Paper
no. RMIT-3332395-2015.
James T. Fenwick is an undergraduate student with the school of
Electrical and Computer Engineering, Royal Melbourne Institute of
Technology, Melbourne, Victoria, Australia; (e-mail:
s3332395@student.rmit.edu.au)
an extent that they can reach the voltage breakdown level of
air. [3][6][7][8] When this happens, the pointed object emit
corona current which induces a positive spacial charge
above it that is strong enough to produce a positive electrical
discharge (streamer) that propagates towards the descending
leader. If the leader is close enough to ground such that the
electric field between them is strong enough to sustain a
positive streamer, successful streamer to leader propagation
occurs and the provision of a successful lightning discharge
path is established. [2]
The purpose in which a conventional lightning protection
system is intended to operate, is via the meticulous
positioning of lightning strike receptors (air terminals) with
low impedance paths (down conductors) to conduct the
lightning discharge safely to ground (earth termination
network). Preliminary insight into the relation of lightning to
grounded objects was first explored by Benjamin Franklin in
the 18th
century. Franklin later went on to conceptualize the
architecture of what is now considered to be a conventional
lightning protection system by identifying three key
elements; metallic rods (Air Terminals), horizontal roof
conductor networks, and vertical down conductors
connected to earth termination networks. The first ever air
terminals used by Franklin were thin, sharp tipped needles
mounted on to the top of iron rods, since then various
geometrical topologies have been investigated in an effort to
improve their lightning interception capabilities.[11]
Generally speaking, air terminals are considered to offer a
zone of protection to a structure relative to their electric field
distribution capabilities and other risk factors according to
many national and international lightning protection
standards. The basic principles of LPS design have been
embodied in such standards as the Australian and New
Zealand Lightning Protection Standard. This standard, like
many others, does not endorse or imply the endorsement of
non-conventional LPSs that claim enhanced performance. [1]
Irrespective of limitations imposed by such standards, a vast
array of literature exists investigating the claimed enhanced
performance of non-conventional LPSs but on a consistent
basis there is an absence of relevant conclusive results and
this suggests that they do not function as they claim.[2][3][4][5]
In this study, several air terminals comprising
conventional and non-conventional surface characteristics
are modelled in detail using Solid Works Computer Aided
Optimization of Conventional Air Terminal Design for Lightning
Protection Systems with Respect to Geometrical Surface
Characteristics
James T. Fenwick, Student, RMIT
W
Design (CAD) software. To allow for electrostatic analysis
of these designs, a 3-dimensional electrostatic simulation
model, replicating the meteorological conditions of a
thunderstorm, was built using ANSYS Maxwell Finite
Element Analysis (FEA) software. Each air terminal
topology was subject to the same simulation conditions for
comparative analysis of their respective electric field
distribution. Results outline the impact that geometry has on
an air terminal’s electrostatic performance capabilities and
provides preliminary insight into the optimization of
conventional air terminal design.
II. ELECTROSTATIC ENVIRONMENTAL PROPERTIES OF A
THUNDERSTORM
The cloud most commonly associated with a thunderstorm
is called the cumulonimbus cloud. This cloud structure is
typically characterized by a towering and dense, vertical
cloud in which strong rising air currents called updrafts are
present. The presence of these updrafts are believed to
instigate charge distribution within the cloud, smaller
particles rise to the top of the cloud via the updrafts and
acquire a positive charge whereas the larger particles
accumulate at the bottom of the cloud acquiring a negative
charge. The concentration of positive charges in the top of
the cloud and that of the negative charges in the bottom of
the cloud creates a significantly large potential difference
not only between different regions of the cloud, but also
between the bottom of the cloud and the earth. When this
potential difference becomes significant enough, the
phenomenon more formally known as lightning takes place
and bridges the two regions of charge via an ionized channel
that works to neutralize the intervening field.
A common method used to model the charge distribution
of a cumulonimbus cloud is the Simpson Cumulonimbus
Model. [10] In this model cumulonimbus cloud is broken into
three spheres of uniform distributing charges. The cloud
model below consists of three point charges suspended in air
at different heights from the ground. In the simulation, the
ground has been modelled with a boundary condition of odd
symmetry (Flux Normal) where E is normal to the boundary;
its normal components are 0. The surrounding walls of the
simulation region have been assigned a balloon boundary
condition, where the charge at the"infinity" balances the
charge in the drawing region. The net charge is 0. The three
charges of 3C, -40C and +40C are placed at heights of 2, 7
and 12km from ground level respectively. The charges are
modelled as spheres of radii 900m for the positive and
negative 40C charges, and radii 150m for the 3C charge. The
size of the spheres is picked in such a way that when the
meshing process takes place, the electric fields in the area of
interest within the model are accurate. The initial mesh
settings for this simulation are 1 meter. [9] On closer
inspection of the electrostatic simulation depicted in Fig. 1
we can see that the ground electric field rapidly runs to 0 as
the radius increases laterally from the vertical centreline. [10]
Fig. 1. Electrostatic simulation of Simpson Cumulonimbus Model [10]
III. LPS AIR TERMINAL MODELLING
Three air terminals were modelled in Solid Works CAD.
Each air terminal was designed at a height of 1 meter, a
radius of 9.5mm and assigned aluminum (Grade 1050)
material properties (as specified by [1]) with a bulk
conductivity of 38 Mega Siemens/m and a relative
permittivity of 1. One conventional air terminal was
modelled as the reference air terminal and is depicted in the
far left of Fig 2. This model featured conventional smooth
surface characteristics and ultimately generated the reference
data used to analyze its non-conventional counterparts. Two
non-conventional air terminals were modelled, both
comprising surface characteristic alterations. The air
terminal comprising surface characteristic #1 depicted in the
middle of Fig. 2 demonstrated a “knurled” rough surface in
which diamond like cut-outs and extrusions texturized the
terminal from top to bottom. The air terminal comprising
surface characteristic #2 depicted at the far right of Fig. 2
demonstrated a “pyramid swept” surface in which pyramid
like cut-outs and extrusions texturized the terminal from top
to bottom with a “zig-zag” like shape.
Fig. 2. Air Terminal Solid Works Models, (LEFT) Conventional
Reference Air Terminal, (MIDDLE) Non-Conventional Air Terminal
Surface Characteristic #1, (RIGHT) Non-Conventional Air Terminal
Surface Characteristic #2
IV. 3 DIMENSIONAL AIR TERMINAL ELECTROSTATIC
SIMULATION MODEL
The 3 dimensional electrostatic simulation model used for
the analysis of each air terminal topology consisted of a
2000mm x 2000mm x 200mm rectangular prism suspended
directly above the air terminal at a height of 2000mm,
therefore allowing a gap of 1000mm between the tip of the
air terminal and the under croft of the rectangular prism.
In order to mimic the excitation values of a thunderstorm
and its associated charge distribution, the rectangular prism
was assigned an excitation value of -10MV to emulate the
potential difference associated with the tip of the negative
downward leader and ground as stated in [10]. The air
terminals were then assigned an excitation value of +10KV
which is believed to be the electric field potential at ground
level under the presence of a thundercloud. Once all
excitations had successfully been assigned, a virtual force
was assigned to the rectangular prism and a region was
created in which the simulations would populate with
results. The floor of the region was assigned a boundary
condition of odd symmetry (normal flux). Finally a polyline
was drawn on the simulation as a non-model object. The
poly line was drawn horizontally 500mm directly above the
tip of the air terminal spanning 1.5 meters each way, this line
was ultimately used as a reference for the rectangular plots
that were utilized in the analysis of each air terminal’s
electric field distribution. Initial mesh settings for each
simulation were set at 0.001mm so to allow for recognition
of surface characteristic alterations.
V. PRELIMINARY INDIVIDUAL SIMULATION RESULTS
The following simulations depicted in Figures 3, 4, and 5
embody the preliminary stages of the electrostatic analysis
performed on each respective air terminal topology.
Fig. 3. 3 Dimensional Conventional Air Terminal Electrostatic Simulation
Figure 3 depicts the electric field distribution of a
conventional air terminal when a field overlay displaying
electric field magnitude is applied. From these results, a
rectangular plot was generated based on the values generated
at each point along the polyline, and the data was exported
and tabulated in excel.
Fig. 4. 3 Dimensional Non-Conventional Air Terminal (Surface
Characteristic #1) Electrostatic Simulation
Figure 4 depicts the electric field distribution of the non-
conventional air terminal comprising surface characteristics
#1 when a field overlay displaying electric field magnitude
is applied. From these results, a rectangular plot was
generated based on the values generated at each point along
the polyline, and the data was exported and tabulated in
excel.
Fig. 5. 3 Dimensional Non-Conventional Air Terminal (Surface
Characteristic #2) Electrostatic Simulation
Figure 5 depicts the electric field distribution of the non-
conventional air terminal comprising surface characteristics
#2 when a field overlay displaying electric field magnitude
is applied. From these results, a rectangular plot was
generated based on the values generated at each point along
the polyline, and the data was exported and tabulated in
excel.
Upon finer inspection of the preliminary non-conventional
simulations, it can be seen that the Electric Field at the
lateral most parts of the Poly Line reference line is of a
higher magnitude than that of the conventional. When
tabulated (Table 1), this discrepancy is quantified and it can
be seen that although electric fields are of a higher
magnitudes at the most lateral parts of the distribution,
magnitudes are significantly smaller directly above the non-
conventional air terminals when compared with that of the
conventional.
Table 1. Poly Line Electric Field Data Extracted From Preliminary
Electrostatic Simulations
VI. SECONDARY SIMULATION RESULTS
To further explore the preliminary electrostatic simulation
results of Part V., a secondary set of simulations were run to
analyze whether or not the conventional and non-
conventional air terminals would complement each other if
laid out in an array like manor. For this simulation, each air
terminal topology was laid out in the same configuration and
put under the same analysis for electric field distribution
capabilities. A simulation was also run utilizing both air
terminal topologies and results were analyzed.
The layout of air terminals for this configuration consisted
of a star like formation utilizing a total of five air terminals.
The electrostatic simulation environment they were subject
to was equivalent to that of Part V. Air terminals were offset
600mm in +x, -x, +z, and –z directions from the reference
air terminal located at 0,0,0,0 (+x, -x, +z, -z) at ground level.
Each air terminal was assigned a positive voltage of 10KV
similar to that of the preliminary simulation environment
and all results were exported to a single rectangular plot
which is analyzed in Part VII. of this report. For these
simulations the non-conventional air terminal model
comprising surface characteristics #1 was omitted from
simulations due to meshing problems.
Fig. 6. 3 Dimensional Conventional Air Terminal Electrostatic
Simulation (Secondary Array)
Figure 6 depicts the electric field distribution of the
conventional air terminal laid out in an array like manor
when a field overlay displaying electric field magnitude is
applied. From these results, a rectangular plot was generated
based on the values generated at each point along the
polyline, the data was exported and tabulated in excel.
Fig. 7. 3 Dimensional Non-Conventional (Surface Characteristics #2)
Air Terminal Electrostatic Simulation (Secondary Array)
Figure 7 depicts the electric field distribution of the
conventional air terminal laid out in an array like manor
when a field overlay displaying electric field magnitude is
applied. From these results, a rectangular plot was generated
based on the values generated at each point along the
polyline, the data was exported and tabulated in excel.
In addition to the simulations conducted in Figures 6 and
7, a third simulation was run that utilized both conventional
and non-conventional (Surface Characteristic #2) air
terminal topologies. To achieve the best possible layout for
this simulation, the conventional air terminal was used as the
reference air terminal located at 0,0,0,0 (+x, -x, +z, -z), the
non-conventional air terminals were offset in the same
fashion as the previous simulations and the results were also
included in the rectangular field plot in Part VII. for
analysis.
0.00 0.50 1.00 1.50 2.00 2.50 3.00
Distance [meter]
4.00E+006
4.50E+006
5.00E+006
5.50E+006
6.00E+006
6.50E+006
7.00E+006
Y1[V_per_meter]
Maxwell3DDesign1
Electric Field Distribution Plot ANSOFT
Curve Info
Mixed
Imported
Conventional
Setup1 : LastAdaptive
Non-Conventional SC2
Imported
Fig. 8. 3 Dimensional Non-Conventional & Conventional(Surface
Characteristics #2) Air Terminal Electrostatic Simulation (Secondary
Array)
Figure 8 depicts the electric field distribution of the mixed
conventional/non-conventional air terminal layout when a
field overlay displaying electric field magnitude is applied.
From these results, a rectangular plot was generated based
on the values generated at each point along the polyline, the
data was exported and tabulated in excel.
VII. ANALYSIS OF RESULTS
Upon the successful completion of all secondary
simulations the electric field distribution data for each layout
was plotted on one rectangular plot and is depicted below in
Graph. 1.
Graph 1. Electric Field Distribution Rectangular Plot
When analyzing discrepancies between electric field
distributions it is evident when looking at the plot that the
conventional system is still the most effective system for
overhead electric field maximization. The air terminals
comprising surface characteristic alterations have little
beneficial effect on electric field distribution other than
producing higher electric field magnitude at the most lateral
parts of the field distribution, this includes when they are
laid in conjunction with conventional air terminals. These
results have remained consistent throughout both
preliminary and secondary simulations. For a more
quantifiable analysis of the secondary simulations, data was
exported from the distribution plot and tabulated in excel
where discrepancies between electric field magnitude were
noted. This data can be seen below in Table. 2.
Table 2. Poly Line Electric Field Data Extracted From Secondary
Electrostatic Simulations
It can be deduced from Table 2 that utilizing the non-
conventional air terminals increases the electric field
magnitude at the most lateral parts of the electric field
distribution. This was expected as these results were
consistent in preliminary simulations. When utilizing both;
conventional and non-conventional systems in the same
array, whilst discrepancies between the electric field
associated with a fully conventional system are minimized;
there is no significant advantage of arranging a system in
this way in the context of this simulation environment.
To fully utilize the advantages of lateral electric field
maximization provided by non-conventional air terminals
comprising geometrical surface characteristics we must
compensate for the deficiency in overhead electric field
magnitudes when compared with fully conventional systems.
VIII. CONCLUSIONS
Determining the electric field distribution capabilities of
air terminals utilized in lightning protection systems is
critical in identifying the zone of protection in which the
system provides a structure against the damaging effects of
lightning. In this paper, via the utilization of SolidWorks
CAD software and ANSYS Maxwell FEA software, several
conventional and non-conventional air terminals were
modelled and subject to an electrostatic simulation
environment for analysis of their electric field distribution
capabilities when in the presence of a thunderstorm.
It can be deduced from both preliminary and secondary
results, that when altering the geometrical surface
characteristics of grounded structures in a thunderstorm
environment, their electric field distribution capabilities
change considerably. In the context of this analysis, although
electric field magnitudes were maximized at the most lateral
parts of electric field distribution for air terminals
comprising geometrical surface characteristic alterations,
this comes at a somewhat proportional depreciation in
overhead electric field intensity. Ultimately, to gain full
advantage of lateral electric field maximization provided by
such non-conventional air terminals we must compensate for
the co-ordinate reduction in overhead electric field intensity.
This paper has analyzed the affects that minor alterations
made to a conventional air terminal’s geometry can have on
its respective electric field distribution capabilities. Both
industry standard conventional, and non-conventional air
terminals have been analyzed, and the effects of air terminal
surface geometry have been identified as worthy of
consideration when designing a lightning protection system.
REFERENCES
[1] EL-024 Technical Committee, Protection Against Lightning, Council
of Standards Australia, Council of Standards New Zealand.
“Australian/New Zealand Standard, Lighting Protection”, AS/NZS
1768:2007, pp. 11 - 133 (2007)
[2] Van Brunt, R.J.; Nelson, T.L.; Stricklett, K.L. “Early streamer
emission lightning protection systems: An overview”, Electrical
Insulation Magazine, IEEE, Volume:16, Issue: 1, pp. 5-24 (2000)
[3] Rison, W. “Experimental validation of conventional and
nonconventional lightning protection systems”, Power Engineering
Society General Meeting, IEEE, Volume: 4. (2003)
[4] Tobias, J.M., “The Basis of Conventional Lightning Protection
Systems”, IEEE Transactions on Industry Applications, Volume: 40,
No. 4, July/August (2004)
[5] Zipse, D.W., “Lightning Protection Systems: Advantages and
Disadvantages”, in Proceedings of the IEEE Petroleum and Chemical
Industry Technical Conference (St Louis, MO USA), p. 343, IEEE,
(1993)
[6] Alconchel, O. and Thirion, B., “Study of a type of early streamer
emission lightning conductor”, in Workshop on Physics of Lightning
(Chamonix, France), (1993)
[7] Lee, J.B., Myung, S.H., Cho, Y.G., Chang, S.H., Kim, J.S., and Kil,
G.S., “Experimental Study on Lightning Protection Performance of
Air Terminals”, International Conference on Power System
Technology, 2002. Proceedings. PowerCon 2002, Volume: 4, (2002)
[8] Becerra, M., Cooray, V., and Roman, F., “Lightning Striking Distance
of Complex Structures”, Generation, Transmission & Distribution,
IET, Volume: 2, Issue: 1, (2008)
[9] Peesapati, V. ; Cotton, I., “Lightning protection of wind turbines — A
comparison of real lightning strike data and finite element lightning
attachment analysis”, International Conference on Sustainable Power
Generation and Supply, 2009. SUPERGEN '09., (2009)
[10] Xiangyu Liu ; Jiaqing Chen ; Yingqiang Wang ; Jun Liu ; Zaihui
Wang, “Finite-difference analysis of the atmosphere electric field
distribution around a thunderstorm monomer”, 2012 6th Asia-Pacific
Conference on Environmental Electromagnetics (CEEM), (2012)
[11] Cooray, Vernon, “Lightning Protection”, Power and Energy Series 58,
IET, (2009)

More Related Content

What's hot

Effect of HVTL Phase Transposition on Pipelines Induced Voltage
Effect of HVTL Phase Transposition on Pipelines Induced VoltageEffect of HVTL Phase Transposition on Pipelines Induced Voltage
Effect of HVTL Phase Transposition on Pipelines Induced Voltageijeei-iaes
 
Great pyramid giza alternative energy pg circular times
Great pyramid giza  alternative energy pg circular timesGreat pyramid giza  alternative energy pg circular times
Great pyramid giza alternative energy pg circular timestavennerpride
 
Numerical studies of the radiation patterns of resistively loaded dipoles
Numerical studies of the radiation patterns of resistively loaded dipolesNumerical studies of the radiation patterns of resistively loaded dipoles
Numerical studies of the radiation patterns of resistively loaded dipolesLeonid Krinitsky
 
A study of transient characteristics of an actual wind turbine grounding syst...
A study of transient characteristics of an actual wind turbine grounding syst...A study of transient characteristics of an actual wind turbine grounding syst...
A study of transient characteristics of an actual wind turbine grounding syst...duncans50
 
Ijmer 46051622
Ijmer 46051622Ijmer 46051622
Ijmer 46051622IJMER
 
Kelvin probe microscop
Kelvin probe microscopKelvin probe microscop
Kelvin probe microscopAhmed Elsayes
 
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  AntennaAnalysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP AntennaIJMER
 
Reduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution SystemsReduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution SystemsIJAPEJOURNAL
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD Editor
 
Mechanical stresses in transmission lines by a.guell 1912
Mechanical stresses in transmission lines by a.guell 1912Mechanical stresses in transmission lines by a.guell 1912
Mechanical stresses in transmission lines by a.guell 1912ARSAC CONTRATISTAS GENERALES
 
Substation lightning protection and earthing standard(august 2019)
Substation lightning protection and earthing standard(august 2019)Substation lightning protection and earthing standard(august 2019)
Substation lightning protection and earthing standard(august 2019)Mahesh Chandra Manav
 

What's hot (16)

Effect of HVTL Phase Transposition on Pipelines Induced Voltage
Effect of HVTL Phase Transposition on Pipelines Induced VoltageEffect of HVTL Phase Transposition on Pipelines Induced Voltage
Effect of HVTL Phase Transposition on Pipelines Induced Voltage
 
Ph3426792682
Ph3426792682Ph3426792682
Ph3426792682
 
Great pyramid giza alternative energy pg circular times
Great pyramid giza  alternative energy pg circular timesGreat pyramid giza  alternative energy pg circular times
Great pyramid giza alternative energy pg circular times
 
Electrostatic as a source of power in an aircraft
Electrostatic as a source of power in an aircraftElectrostatic as a source of power in an aircraft
Electrostatic as a source of power in an aircraft
 
Numerical studies of the radiation patterns of resistively loaded dipoles
Numerical studies of the radiation patterns of resistively loaded dipolesNumerical studies of the radiation patterns of resistively loaded dipoles
Numerical studies of the radiation patterns of resistively loaded dipoles
 
A study of transient characteristics of an actual wind turbine grounding syst...
A study of transient characteristics of an actual wind turbine grounding syst...A study of transient characteristics of an actual wind turbine grounding syst...
A study of transient characteristics of an actual wind turbine grounding syst...
 
Ijmer 46051622
Ijmer 46051622Ijmer 46051622
Ijmer 46051622
 
wireless power transfer
wireless power transferwireless power transfer
wireless power transfer
 
Ht2514031407
Ht2514031407Ht2514031407
Ht2514031407
 
Kelvin probe microscop
Kelvin probe microscopKelvin probe microscop
Kelvin probe microscop
 
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  AntennaAnalysis of MOS Capacitor Loaded Annular Ring MICROSTRIP  Antenna
Analysis of MOS Capacitor Loaded Annular Ring MICROSTRIP Antenna
 
Reduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution SystemsReduced Dielectric Losses for Underground Cable Distribution Systems
Reduced Dielectric Losses for Underground Cable Distribution Systems
 
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
IJERD (www.ijerd.com) International Journal of Engineering Research and Devel...
 
Earthing
EarthingEarthing
Earthing
 
Mechanical stresses in transmission lines by a.guell 1912
Mechanical stresses in transmission lines by a.guell 1912Mechanical stresses in transmission lines by a.guell 1912
Mechanical stresses in transmission lines by a.guell 1912
 
Substation lightning protection and earthing standard(august 2019)
Substation lightning protection and earthing standard(august 2019)Substation lightning protection and earthing standard(august 2019)
Substation lightning protection and earthing standard(august 2019)
 

Viewers also liked

Systems Insight - Industrial Release Placement Program Performance Report
Systems Insight - Industrial Release Placement Program Performance ReportSystems Insight - Industrial Release Placement Program Performance Report
Systems Insight - Industrial Release Placement Program Performance ReportJames Fenwick
 
Raining Thunder
Raining ThunderRaining Thunder
Raining ThunderEric Bolin
 
A FEW HINTS ON BETTER COLLABORATION
A FEW HINTS ON BETTER COLLABORATION A FEW HINTS ON BETTER COLLABORATION
A FEW HINTS ON BETTER COLLABORATION Rocklin
 
Taking Control of Your Life by Planning
Taking Control of Your Life by PlanningTaking Control of Your Life by Planning
Taking Control of Your Life by PlanningSuper Affiliate System
 

Viewers also liked (11)

Systems Insight - Industrial Release Placement Program Performance Report
Systems Insight - Industrial Release Placement Program Performance ReportSystems Insight - Industrial Release Placement Program Performance Report
Systems Insight - Industrial Release Placement Program Performance Report
 
Presentation1
Presentation1Presentation1
Presentation1
 
Ceska_zbroj_05
Ceska_zbroj_05Ceska_zbroj_05
Ceska_zbroj_05
 
Fresher Resume pvr1
Fresher Resume pvr1Fresher Resume pvr1
Fresher Resume pvr1
 
Raining Thunder
Raining ThunderRaining Thunder
Raining Thunder
 
Tarsitano_ARTV2121Syllabus
Tarsitano_ARTV2121SyllabusTarsitano_ARTV2121Syllabus
Tarsitano_ARTV2121Syllabus
 
A FEW HINTS ON BETTER COLLABORATION
A FEW HINTS ON BETTER COLLABORATION A FEW HINTS ON BETTER COLLABORATION
A FEW HINTS ON BETTER COLLABORATION
 
Lasten ja perheiden hyvinvointi tulevaisuudessa
Lasten ja perheiden hyvinvointi tulevaisuudessaLasten ja perheiden hyvinvointi tulevaisuudessa
Lasten ja perheiden hyvinvointi tulevaisuudessa
 
Taking Control of Your Life by Planning
Taking Control of Your Life by PlanningTaking Control of Your Life by Planning
Taking Control of Your Life by Planning
 
Gebeurtenis
GebeurtenisGebeurtenis
Gebeurtenis
 
Presentation
PresentationPresentation
Presentation
 

Similar to James Fenwick - Engineering Design 4 IEEE Paper (RMIT)

Measurment of ionizing radiation by dr. pushpendra
Measurment of ionizing radiation by dr. pushpendraMeasurment of ionizing radiation by dr. pushpendra
Measurment of ionizing radiation by dr. pushpendraDrPushpendraPatel
 
AME441AL_Final_Report
AME441AL_Final_ReportAME441AL_Final_Report
AME441AL_Final_ReportMatt Tonokawa
 
The Performance of a Cylindrical Microstrip Printed Antenna for TM10 Mode as...
The Performance of a Cylindrical Microstrip Printed Antenna for TM10  Mode as...The Performance of a Cylindrical Microstrip Printed Antenna for TM10  Mode as...
The Performance of a Cylindrical Microstrip Printed Antenna for TM10 Mode as...ijngnjournal
 
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...ISAR Publications
 
Chapter 8 overvoltage phenomenon and insulation coordination.ppt
Chapter 8 overvoltage phenomenon and insulation coordination.pptChapter 8 overvoltage phenomenon and insulation coordination.ppt
Chapter 8 overvoltage phenomenon and insulation coordination.pptborapring
 
Electromagnetic Modeling
Electromagnetic ModelingElectromagnetic Modeling
Electromagnetic ModelingJustin McKennon
 
45 investigation paper id 0008 edit septian
45 investigation paper id 0008 edit septian45 investigation paper id 0008 edit septian
45 investigation paper id 0008 edit septianIAESIJEECS
 
Effect of Dew and Raindrops on Electric Field around EHV Transmission Lines
Effect of Dew and Raindrops on Electric Field around EHV Transmission LinesEffect of Dew and Raindrops on Electric Field around EHV Transmission Lines
Effect of Dew and Raindrops on Electric Field around EHV Transmission LinesTELKOMNIKA JOURNAL
 
Co3210061014
Co3210061014Co3210061014
Co3210061014IJMER
 
Power loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission LinesPower loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission LinesIOSR Journals
 
Wireless power transmission ppt
Wireless power transmission pptWireless power transmission ppt
Wireless power transmission pptAishwary Verma
 
Transient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentTransient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentHimmelstern
 
1. Pertemuan Pendahuluan.pptx
1. Pertemuan Pendahuluan.pptx1. Pertemuan Pendahuluan.pptx
1. Pertemuan Pendahuluan.pptxJonah141
 
E233137
E233137E233137
E233137irjes
 
International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)irjes
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsBruno De Wachter
 

Similar to James Fenwick - Engineering Design 4 IEEE Paper (RMIT) (20)

LAB File
LAB FileLAB File
LAB File
 
Measurment of ionizing radiation by dr. pushpendra
Measurment of ionizing radiation by dr. pushpendraMeasurment of ionizing radiation by dr. pushpendra
Measurment of ionizing radiation by dr. pushpendra
 
AME441AL_Final_Report
AME441AL_Final_ReportAME441AL_Final_Report
AME441AL_Final_Report
 
The Performance of a Cylindrical Microstrip Printed Antenna for TM10 Mode as...
The Performance of a Cylindrical Microstrip Printed Antenna for TM10  Mode as...The Performance of a Cylindrical Microstrip Printed Antenna for TM10  Mode as...
The Performance of a Cylindrical Microstrip Printed Antenna for TM10 Mode as...
 
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
IJRET-V1I2P1 -Measurement and FEMM Modelling of Experimentally Generated Stro...
 
D1103042431
D1103042431D1103042431
D1103042431
 
Chapter 8 overvoltage phenomenon and insulation coordination.ppt
Chapter 8 overvoltage phenomenon and insulation coordination.pptChapter 8 overvoltage phenomenon and insulation coordination.ppt
Chapter 8 overvoltage phenomenon and insulation coordination.ppt
 
Insulation Coordination
Insulation CoordinationInsulation Coordination
Insulation Coordination
 
Electromagnetic Modeling
Electromagnetic ModelingElectromagnetic Modeling
Electromagnetic Modeling
 
45 investigation paper id 0008 edit septian
45 investigation paper id 0008 edit septian45 investigation paper id 0008 edit septian
45 investigation paper id 0008 edit septian
 
Effect of Dew and Raindrops on Electric Field around EHV Transmission Lines
Effect of Dew and Raindrops on Electric Field around EHV Transmission LinesEffect of Dew and Raindrops on Electric Field around EHV Transmission Lines
Effect of Dew and Raindrops on Electric Field around EHV Transmission Lines
 
Aq36257262
Aq36257262Aq36257262
Aq36257262
 
Co3210061014
Co3210061014Co3210061014
Co3210061014
 
Power loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission LinesPower loss due to Corona on High Voltage Transmission Lines
Power loss due to Corona on High Voltage Transmission Lines
 
Wireless power transmission ppt
Wireless power transmission pptWireless power transmission ppt
Wireless power transmission ppt
 
Transient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning currentTransient response of grounding systems under impulse lightning current
Transient response of grounding systems under impulse lightning current
 
1. Pertemuan Pendahuluan.pptx
1. Pertemuan Pendahuluan.pptx1. Pertemuan Pendahuluan.pptx
1. Pertemuan Pendahuluan.pptx
 
E233137
E233137E233137
E233137
 
International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)International Refereed Journal of Engineering and Science (IRJES)
International Refereed Journal of Engineering and Science (IRJES)
 
Earthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspectsEarthing systems - Basic constructional aspects
Earthing systems - Basic constructional aspects
 

James Fenwick - Engineering Design 4 IEEE Paper (RMIT)

  • 1. Abstract — The primary objective of a conventional lightning protection system is to maximize the electric field above the structure on which it is installed when it is subject to the electrostatic meteorological environment of a thunderstorm. This results in the promotion of successful streamer to leader propagation which ultimately improves the likelihood of the controlled earth termination of a cloud to ground (CG) lightning strike. A conventional lightning protection system is designed to prevent damage to a building by providing a number of preferential strike receptors (air terminals) with low impedance paths to conduct the lightning discharge safely to ground. In this study, via the utilization of Finite Element Analysis (FEA) software and solid modelling Computer Aided Design software, several air terminal topologies comprising conventional and non-conventional geometrical surface characteristics were modelled in detail and then subject to an electrostatic simulation environment (thunderstorm replica) for analysis of their respective electric field distributions. Results indicate discrepancies of up to 100KV in electric field distribution between that of the conventional and non-conventional air terminal topologies. This suggests that significant research opportunities lie within optimizing the geometrical design of a conventional air terminal with respect to its corona emission capabilities and could ultimately lead to a review of LPS protocols embodied in many national and international Lightning Protection Standards. Keywords – Lightning, Lightning Protection System, LPS, Air Terminal Design, Surface Characteristics, Electric Field Distribution, finite element modelling. I. INTRODUCTION HAT happens on the earth’s surface during a thunderstorm is extremely relative to what is happening in the clouds above. The negative charge in a thundercloud induces a positive charge on the earth’s surface beneath it. The natural space charge produced by pointed corona emitting objects such as trees, power lines, antennas buildings and the like, limits the electric field at ground level to typically around 10kV/m [3]. In the presence of a thunderstorm, and on closer approach of the negatively charged descending stepped leader, the fields at the sharp conducting points of exposed objects are intensified to such Manuscript received October 14, 2015; Revised October 14, 2015. Paper no. RMIT-3332395-2015. James T. Fenwick is an undergraduate student with the school of Electrical and Computer Engineering, Royal Melbourne Institute of Technology, Melbourne, Victoria, Australia; (e-mail: s3332395@student.rmit.edu.au) an extent that they can reach the voltage breakdown level of air. [3][6][7][8] When this happens, the pointed object emit corona current which induces a positive spacial charge above it that is strong enough to produce a positive electrical discharge (streamer) that propagates towards the descending leader. If the leader is close enough to ground such that the electric field between them is strong enough to sustain a positive streamer, successful streamer to leader propagation occurs and the provision of a successful lightning discharge path is established. [2] The purpose in which a conventional lightning protection system is intended to operate, is via the meticulous positioning of lightning strike receptors (air terminals) with low impedance paths (down conductors) to conduct the lightning discharge safely to ground (earth termination network). Preliminary insight into the relation of lightning to grounded objects was first explored by Benjamin Franklin in the 18th century. Franklin later went on to conceptualize the architecture of what is now considered to be a conventional lightning protection system by identifying three key elements; metallic rods (Air Terminals), horizontal roof conductor networks, and vertical down conductors connected to earth termination networks. The first ever air terminals used by Franklin were thin, sharp tipped needles mounted on to the top of iron rods, since then various geometrical topologies have been investigated in an effort to improve their lightning interception capabilities.[11] Generally speaking, air terminals are considered to offer a zone of protection to a structure relative to their electric field distribution capabilities and other risk factors according to many national and international lightning protection standards. The basic principles of LPS design have been embodied in such standards as the Australian and New Zealand Lightning Protection Standard. This standard, like many others, does not endorse or imply the endorsement of non-conventional LPSs that claim enhanced performance. [1] Irrespective of limitations imposed by such standards, a vast array of literature exists investigating the claimed enhanced performance of non-conventional LPSs but on a consistent basis there is an absence of relevant conclusive results and this suggests that they do not function as they claim.[2][3][4][5] In this study, several air terminals comprising conventional and non-conventional surface characteristics are modelled in detail using Solid Works Computer Aided Optimization of Conventional Air Terminal Design for Lightning Protection Systems with Respect to Geometrical Surface Characteristics James T. Fenwick, Student, RMIT W
  • 2. Design (CAD) software. To allow for electrostatic analysis of these designs, a 3-dimensional electrostatic simulation model, replicating the meteorological conditions of a thunderstorm, was built using ANSYS Maxwell Finite Element Analysis (FEA) software. Each air terminal topology was subject to the same simulation conditions for comparative analysis of their respective electric field distribution. Results outline the impact that geometry has on an air terminal’s electrostatic performance capabilities and provides preliminary insight into the optimization of conventional air terminal design. II. ELECTROSTATIC ENVIRONMENTAL PROPERTIES OF A THUNDERSTORM The cloud most commonly associated with a thunderstorm is called the cumulonimbus cloud. This cloud structure is typically characterized by a towering and dense, vertical cloud in which strong rising air currents called updrafts are present. The presence of these updrafts are believed to instigate charge distribution within the cloud, smaller particles rise to the top of the cloud via the updrafts and acquire a positive charge whereas the larger particles accumulate at the bottom of the cloud acquiring a negative charge. The concentration of positive charges in the top of the cloud and that of the negative charges in the bottom of the cloud creates a significantly large potential difference not only between different regions of the cloud, but also between the bottom of the cloud and the earth. When this potential difference becomes significant enough, the phenomenon more formally known as lightning takes place and bridges the two regions of charge via an ionized channel that works to neutralize the intervening field. A common method used to model the charge distribution of a cumulonimbus cloud is the Simpson Cumulonimbus Model. [10] In this model cumulonimbus cloud is broken into three spheres of uniform distributing charges. The cloud model below consists of three point charges suspended in air at different heights from the ground. In the simulation, the ground has been modelled with a boundary condition of odd symmetry (Flux Normal) where E is normal to the boundary; its normal components are 0. The surrounding walls of the simulation region have been assigned a balloon boundary condition, where the charge at the"infinity" balances the charge in the drawing region. The net charge is 0. The three charges of 3C, -40C and +40C are placed at heights of 2, 7 and 12km from ground level respectively. The charges are modelled as spheres of radii 900m for the positive and negative 40C charges, and radii 150m for the 3C charge. The size of the spheres is picked in such a way that when the meshing process takes place, the electric fields in the area of interest within the model are accurate. The initial mesh settings for this simulation are 1 meter. [9] On closer inspection of the electrostatic simulation depicted in Fig. 1 we can see that the ground electric field rapidly runs to 0 as the radius increases laterally from the vertical centreline. [10] Fig. 1. Electrostatic simulation of Simpson Cumulonimbus Model [10] III. LPS AIR TERMINAL MODELLING Three air terminals were modelled in Solid Works CAD. Each air terminal was designed at a height of 1 meter, a radius of 9.5mm and assigned aluminum (Grade 1050) material properties (as specified by [1]) with a bulk conductivity of 38 Mega Siemens/m and a relative permittivity of 1. One conventional air terminal was modelled as the reference air terminal and is depicted in the far left of Fig 2. This model featured conventional smooth surface characteristics and ultimately generated the reference data used to analyze its non-conventional counterparts. Two non-conventional air terminals were modelled, both comprising surface characteristic alterations. The air terminal comprising surface characteristic #1 depicted in the middle of Fig. 2 demonstrated a “knurled” rough surface in which diamond like cut-outs and extrusions texturized the terminal from top to bottom. The air terminal comprising surface characteristic #2 depicted at the far right of Fig. 2 demonstrated a “pyramid swept” surface in which pyramid like cut-outs and extrusions texturized the terminal from top to bottom with a “zig-zag” like shape. Fig. 2. Air Terminal Solid Works Models, (LEFT) Conventional Reference Air Terminal, (MIDDLE) Non-Conventional Air Terminal Surface Characteristic #1, (RIGHT) Non-Conventional Air Terminal Surface Characteristic #2
  • 3. IV. 3 DIMENSIONAL AIR TERMINAL ELECTROSTATIC SIMULATION MODEL The 3 dimensional electrostatic simulation model used for the analysis of each air terminal topology consisted of a 2000mm x 2000mm x 200mm rectangular prism suspended directly above the air terminal at a height of 2000mm, therefore allowing a gap of 1000mm between the tip of the air terminal and the under croft of the rectangular prism. In order to mimic the excitation values of a thunderstorm and its associated charge distribution, the rectangular prism was assigned an excitation value of -10MV to emulate the potential difference associated with the tip of the negative downward leader and ground as stated in [10]. The air terminals were then assigned an excitation value of +10KV which is believed to be the electric field potential at ground level under the presence of a thundercloud. Once all excitations had successfully been assigned, a virtual force was assigned to the rectangular prism and a region was created in which the simulations would populate with results. The floor of the region was assigned a boundary condition of odd symmetry (normal flux). Finally a polyline was drawn on the simulation as a non-model object. The poly line was drawn horizontally 500mm directly above the tip of the air terminal spanning 1.5 meters each way, this line was ultimately used as a reference for the rectangular plots that were utilized in the analysis of each air terminal’s electric field distribution. Initial mesh settings for each simulation were set at 0.001mm so to allow for recognition of surface characteristic alterations. V. PRELIMINARY INDIVIDUAL SIMULATION RESULTS The following simulations depicted in Figures 3, 4, and 5 embody the preliminary stages of the electrostatic analysis performed on each respective air terminal topology. Fig. 3. 3 Dimensional Conventional Air Terminal Electrostatic Simulation Figure 3 depicts the electric field distribution of a conventional air terminal when a field overlay displaying electric field magnitude is applied. From these results, a rectangular plot was generated based on the values generated at each point along the polyline, and the data was exported and tabulated in excel. Fig. 4. 3 Dimensional Non-Conventional Air Terminal (Surface Characteristic #1) Electrostatic Simulation Figure 4 depicts the electric field distribution of the non- conventional air terminal comprising surface characteristics #1 when a field overlay displaying electric field magnitude is applied. From these results, a rectangular plot was generated based on the values generated at each point along the polyline, and the data was exported and tabulated in excel. Fig. 5. 3 Dimensional Non-Conventional Air Terminal (Surface Characteristic #2) Electrostatic Simulation Figure 5 depicts the electric field distribution of the non- conventional air terminal comprising surface characteristics #2 when a field overlay displaying electric field magnitude is applied. From these results, a rectangular plot was generated based on the values generated at each point along the polyline, and the data was exported and tabulated in excel. Upon finer inspection of the preliminary non-conventional simulations, it can be seen that the Electric Field at the lateral most parts of the Poly Line reference line is of a higher magnitude than that of the conventional. When tabulated (Table 1), this discrepancy is quantified and it can
  • 4. be seen that although electric fields are of a higher magnitudes at the most lateral parts of the distribution, magnitudes are significantly smaller directly above the non- conventional air terminals when compared with that of the conventional. Table 1. Poly Line Electric Field Data Extracted From Preliminary Electrostatic Simulations VI. SECONDARY SIMULATION RESULTS To further explore the preliminary electrostatic simulation results of Part V., a secondary set of simulations were run to analyze whether or not the conventional and non- conventional air terminals would complement each other if laid out in an array like manor. For this simulation, each air terminal topology was laid out in the same configuration and put under the same analysis for electric field distribution capabilities. A simulation was also run utilizing both air terminal topologies and results were analyzed. The layout of air terminals for this configuration consisted of a star like formation utilizing a total of five air terminals. The electrostatic simulation environment they were subject to was equivalent to that of Part V. Air terminals were offset 600mm in +x, -x, +z, and –z directions from the reference air terminal located at 0,0,0,0 (+x, -x, +z, -z) at ground level. Each air terminal was assigned a positive voltage of 10KV similar to that of the preliminary simulation environment and all results were exported to a single rectangular plot which is analyzed in Part VII. of this report. For these simulations the non-conventional air terminal model comprising surface characteristics #1 was omitted from simulations due to meshing problems. Fig. 6. 3 Dimensional Conventional Air Terminal Electrostatic Simulation (Secondary Array) Figure 6 depicts the electric field distribution of the conventional air terminal laid out in an array like manor when a field overlay displaying electric field magnitude is applied. From these results, a rectangular plot was generated based on the values generated at each point along the polyline, the data was exported and tabulated in excel. Fig. 7. 3 Dimensional Non-Conventional (Surface Characteristics #2) Air Terminal Electrostatic Simulation (Secondary Array) Figure 7 depicts the electric field distribution of the conventional air terminal laid out in an array like manor when a field overlay displaying electric field magnitude is applied. From these results, a rectangular plot was generated based on the values generated at each point along the polyline, the data was exported and tabulated in excel. In addition to the simulations conducted in Figures 6 and 7, a third simulation was run that utilized both conventional and non-conventional (Surface Characteristic #2) air terminal topologies. To achieve the best possible layout for this simulation, the conventional air terminal was used as the reference air terminal located at 0,0,0,0 (+x, -x, +z, -z), the non-conventional air terminals were offset in the same fashion as the previous simulations and the results were also included in the rectangular field plot in Part VII. for analysis.
  • 5. 0.00 0.50 1.00 1.50 2.00 2.50 3.00 Distance [meter] 4.00E+006 4.50E+006 5.00E+006 5.50E+006 6.00E+006 6.50E+006 7.00E+006 Y1[V_per_meter] Maxwell3DDesign1 Electric Field Distribution Plot ANSOFT Curve Info Mixed Imported Conventional Setup1 : LastAdaptive Non-Conventional SC2 Imported Fig. 8. 3 Dimensional Non-Conventional & Conventional(Surface Characteristics #2) Air Terminal Electrostatic Simulation (Secondary Array) Figure 8 depicts the electric field distribution of the mixed conventional/non-conventional air terminal layout when a field overlay displaying electric field magnitude is applied. From these results, a rectangular plot was generated based on the values generated at each point along the polyline, the data was exported and tabulated in excel. VII. ANALYSIS OF RESULTS Upon the successful completion of all secondary simulations the electric field distribution data for each layout was plotted on one rectangular plot and is depicted below in Graph. 1. Graph 1. Electric Field Distribution Rectangular Plot When analyzing discrepancies between electric field distributions it is evident when looking at the plot that the conventional system is still the most effective system for overhead electric field maximization. The air terminals comprising surface characteristic alterations have little beneficial effect on electric field distribution other than producing higher electric field magnitude at the most lateral parts of the field distribution, this includes when they are laid in conjunction with conventional air terminals. These results have remained consistent throughout both preliminary and secondary simulations. For a more quantifiable analysis of the secondary simulations, data was exported from the distribution plot and tabulated in excel where discrepancies between electric field magnitude were noted. This data can be seen below in Table. 2. Table 2. Poly Line Electric Field Data Extracted From Secondary Electrostatic Simulations It can be deduced from Table 2 that utilizing the non- conventional air terminals increases the electric field magnitude at the most lateral parts of the electric field distribution. This was expected as these results were consistent in preliminary simulations. When utilizing both; conventional and non-conventional systems in the same array, whilst discrepancies between the electric field associated with a fully conventional system are minimized; there is no significant advantage of arranging a system in this way in the context of this simulation environment. To fully utilize the advantages of lateral electric field maximization provided by non-conventional air terminals comprising geometrical surface characteristics we must compensate for the deficiency in overhead electric field magnitudes when compared with fully conventional systems. VIII. CONCLUSIONS Determining the electric field distribution capabilities of air terminals utilized in lightning protection systems is critical in identifying the zone of protection in which the system provides a structure against the damaging effects of lightning. In this paper, via the utilization of SolidWorks CAD software and ANSYS Maxwell FEA software, several conventional and non-conventional air terminals were modelled and subject to an electrostatic simulation environment for analysis of their electric field distribution capabilities when in the presence of a thunderstorm. It can be deduced from both preliminary and secondary results, that when altering the geometrical surface
  • 6. characteristics of grounded structures in a thunderstorm environment, their electric field distribution capabilities change considerably. In the context of this analysis, although electric field magnitudes were maximized at the most lateral parts of electric field distribution for air terminals comprising geometrical surface characteristic alterations, this comes at a somewhat proportional depreciation in overhead electric field intensity. Ultimately, to gain full advantage of lateral electric field maximization provided by such non-conventional air terminals we must compensate for the co-ordinate reduction in overhead electric field intensity. This paper has analyzed the affects that minor alterations made to a conventional air terminal’s geometry can have on its respective electric field distribution capabilities. Both industry standard conventional, and non-conventional air terminals have been analyzed, and the effects of air terminal surface geometry have been identified as worthy of consideration when designing a lightning protection system. REFERENCES [1] EL-024 Technical Committee, Protection Against Lightning, Council of Standards Australia, Council of Standards New Zealand. “Australian/New Zealand Standard, Lighting Protection”, AS/NZS 1768:2007, pp. 11 - 133 (2007) [2] Van Brunt, R.J.; Nelson, T.L.; Stricklett, K.L. “Early streamer emission lightning protection systems: An overview”, Electrical Insulation Magazine, IEEE, Volume:16, Issue: 1, pp. 5-24 (2000) [3] Rison, W. “Experimental validation of conventional and nonconventional lightning protection systems”, Power Engineering Society General Meeting, IEEE, Volume: 4. (2003) [4] Tobias, J.M., “The Basis of Conventional Lightning Protection Systems”, IEEE Transactions on Industry Applications, Volume: 40, No. 4, July/August (2004) [5] Zipse, D.W., “Lightning Protection Systems: Advantages and Disadvantages”, in Proceedings of the IEEE Petroleum and Chemical Industry Technical Conference (St Louis, MO USA), p. 343, IEEE, (1993) [6] Alconchel, O. and Thirion, B., “Study of a type of early streamer emission lightning conductor”, in Workshop on Physics of Lightning (Chamonix, France), (1993) [7] Lee, J.B., Myung, S.H., Cho, Y.G., Chang, S.H., Kim, J.S., and Kil, G.S., “Experimental Study on Lightning Protection Performance of Air Terminals”, International Conference on Power System Technology, 2002. Proceedings. PowerCon 2002, Volume: 4, (2002) [8] Becerra, M., Cooray, V., and Roman, F., “Lightning Striking Distance of Complex Structures”, Generation, Transmission & Distribution, IET, Volume: 2, Issue: 1, (2008) [9] Peesapati, V. ; Cotton, I., “Lightning protection of wind turbines — A comparison of real lightning strike data and finite element lightning attachment analysis”, International Conference on Sustainable Power Generation and Supply, 2009. SUPERGEN '09., (2009) [10] Xiangyu Liu ; Jiaqing Chen ; Yingqiang Wang ; Jun Liu ; Zaihui Wang, “Finite-difference analysis of the atmosphere electric field distribution around a thunderstorm monomer”, 2012 6th Asia-Pacific Conference on Environmental Electromagnetics (CEEM), (2012) [11] Cooray, Vernon, “Lightning Protection”, Power and Energy Series 58, IET, (2009)