Simple Vapor-
Absorption
Refrigeration System
Simple Vapor Absorption Refrigeration System
@Point 1
-low temperature and low pressure refrigerant
vapour from evaporator at state 1 enters the
absorber and is absorbed by solution weak in
refrigerant (state 8) .
The heat of absorption (Qa
) is rejected to an external
heat sink at Tāˆž
.
Simple Vapor Absorption Refrigeration System
@Point 2
-The solution, rich in refrigerant is pumped to the
generator pressure (Pg
) by the solution pump (state 3).
The pressurized solution gets heated up sensibly as it
flows through the solution heat exchanger by extracting
heat from hot solution coming from generator (state 4).
@Point 5
-Heat is supplied to this solution from an external heat
source in the generator (Qg
at Tg
), as a result refrigerant
vapour is generated (absorbent may also boil to give off
vapour in case of ammonia-water systems) at state 5.
This high-pressure refrigerant vapour condenses in the
condenser by rejecting heat of condensation to the external
heat sink (Qc
at Tāˆž
) and leaves the condenser as a high
pressure liquid (state 9).
Simple Vapor Absorption Refrigeration System
@Point 10
- the high pressure refrigerant liquid is throttled in the
expansion device to evaporator pressure Pe
from where it
enters the evaporator, extracts heat from low temperature
heat source (Qe
at Te
) and leaves the evaporator as vapour at
state 1, completing a cycle.
Simple Vapor Absorption Refrigeration System
@Point 6
- The hot solution that is weak in refrigerant (state 6)
leaves the generator at high temperature and is cooled
sensibly by rejecting heat to the solution going to the
generator in the solution heat exchanger (state 7).
Then it is throttled to the evaporator pressure in the throttle
valve (state 8), from where it enters the absorber to complete
the cycle.
Simple Vapor Absorption Refrigeration System
COP for Ideal Vapor Absorption Refrigeration
System
ā€¢ Absorption system requires a relatively large amount of low-
grade thermal energy at generator temperature to generate
refrigerant vapour from the solution in generator. Thus while
the energy input is in the form of mechanical energy in vapour
compression refrigeration systems, it is mainly in the form of
thermal energy in case of absorption systems.
COP for Ideal Vapor Absorption Refrigeration
System
ā€¢ The solution pump work is often negligible compared to the
generator heat input. Thus the COPs for compression and
absorption systems are given by:
COP for Ideal Vapor Absorption Refrigeration
System
ā€¢ Thus absorption systems are advantageous where a large
quantity of low-grade thermal energy is available freely at
required temperature. However, it will be seen that for the
refrigeration and heat rejection temperatures, the COP of
vapour compression refrigeration system will be much higher
than the COP of an absorption system as a high grade
mechanical energy is used in the former, while a low-grade
thermal energy is used in the latter.
COP for Ideal Vapor Absorption Refrigeration
System
ā€¢ However, comparing these systems based on COPs is not fully
justified, as mechanical energy is more expensive than
thermal energy. Hence, sometimes the second law (or
exergetic) efficiency is used to compare different refrigeration
systems. It is seen that the second law (or exergetic) efficiency
of absorption system is of the same order as that of a
compression system.
COP for Ideal Vapor Absorption Refrigeration
System
Maximum COP for Ideal Vapor Absorption Refrigeration
System
From first law of thermodynamics,
Where
Qe
is the heat transferred to the absorption system at
evaporator temperature Te
,
Qg
is the heat transferred to the generator of the absorption
system at temperature Tg
,
Qa+c
is the heat transferred from the absorber and condenser of
the absorption system at temperature To
and
Wp
is the work input to the solution pump.
Maximum COP for Ideal Vapor Absorption Refrigeration
System
ā€¢ If we assume that heat rejection at the absorber and
condenser takes place at same external heat sink temperature
To
, then a vapour absorption refrigeration system operates
between three temperature levels, Tg
, To
and Te
.
Maximum COP for Ideal Vapor Absorption Refrigeration
System
The maximum possible COP of an ideal VARS system is given by:
Maximum COP for Ideal Vapor Absorption Refrigeration
System
Thus the ideal COP is only a function of operating temperatures
similar to Carnot system. It can be seen from the above
expression that the ideal COP of VARS system is equal to the
product of efficiency of a Carnot heat engine operating between
Tg
and To
and COP of a Carnot refrigeration system operating
between To
and Te
,
Maximum COP for Ideal Vapor Absorption Refrigeration
System
Thus an ideal vapour absorption refrigeration system can be
considered to be a combined system consisting of a Carnot heat
engine and a Carnot refrigerator as shown in Fig.14.4. Thus the
COP of an ideal VARS increases as generator temperature (Tg
)
and evaporator temperature (Te
) increase and heat rejection
temperature (To
) decreases. However, the COP of actual VARS
will be much less than that of an ideal VARS due to various
internal and external irreversibilities present in actual systems.
Maximum COP for Ideal Vapor Absorption Refrigeration
System
Example of VARS
ā€¢ 1. Hydrogen enters the
pipe with liquid
ammonia (or lithium
bromide solution)
2. Ammonia and
hydrogen enter the
inner compartment of
the refrigerator. An
increase in volume
causes a decrease in
the partial pressure of
the liquid ammonia.
The ammonia
evaporates, requiring
energy to overcome
the Ī”HVap. The required
energy is drawn from
the interior of the
refrigerator, thus
cooling it.
Example of VARS
ā€¢ 3. Ammonia and
hydrogen return from
the inner
compartment,
ammonia returns to
absorber and dissolves
in water. Hydrogen is
free to rise upwards.
4. Ammonia gas
condensation (passive
cooling).
5. Hot ammonia (gas).
6. Heat insulation and
distillation of ammonia
gas from water.
7. Heat source
(electric).
8. Absorber vessel
(water and ammonia
solution).
ā€¢ 1. Hydrogen enters the pipe with liquid ammonia (or
lithium bromide solution)
2. Ammonia and hydrogen enter the inner compartment
of the refrigerator. An increase in volume causes a
decrease in the partial pressure of the liquid ammonia.
The ammonia evaporates, requiring energy to overcome
the Ī”HVap. The required energy is drawn from the interior
of the refrigerator, thus cooling it.
3. Ammonia and hydrogen return from the inner
compartment, ammonia returns to absorber and dissolves
in water. Hydrogen is free to rise upwards.
4. Ammonia gas condensation (passive cooling).
5. Hot ammonia (gas).
6. Heat insulation and distillation of ammonia gas from
water.
7. Heat source (electric).
8. Absorber vessel (water and ammonia solution).
Practical Vapor Absorption Refrigeration System
ā€¢ A practical VARS has 3 additional parts :
ā€¢ ANALYSER
ā€¢ RECTIFIER
ā€¢ HEAT EXCHANGER
Practical Vapor ā€“ Absorption Refrigeration System
ā€¢ Analyser
-When ammonia is vaporized in the generator some water
is also vaporized ,and flow into the condenser along with
ammonia.
Thus the ammonia refrigerant leaving the generator
carries appreciable amount of water vapor. If this water
vapor is allowed to be carried to the evaporator, the
capacity of the refrigeration system would reduce. The
water vapor from ammonia refrigerant is removed by
analyzer and the rectifier.
Practical Vapor ā€“ Absorption Refrigeration System
ā€¢ The analyzer is a sort of distillation column that is
located at the top of the generator. The analyzer consists
of number of plates positioned horizontally. When the
ammonia refrigerant along with the water vapor
particles enters the analyzer, the solution is cooled. Since
water has higher saturation temperature, water vapor
gets condensed into the water particles that drip down
into the generator. The ammonia refrigerant in the
gaseous state continues to rise up and it moves to the
rectifier.
Practical Vapor ā€“ Absorption Refrigeration System
ā€¢ Rectifier - In case the water vapour are not completely
removed in the analyser, a closed type of vapour cooler called
rectifier is also known as dehydrator is used, it may be of
water cooled.
ā€¢ The rectifier is a sort of the heat exchanger cooled by the
water, which is also used for cooling the condenser. Due to
cooling the remaining water vapor mixed with the ammonia
refrigerant also gets condensed along with some particles of
ammonia. This weak solution of water and ammonia drains
down to the analyzer and then to the generator
Practical Vapor ā€“ Absorption Refrigeration System
ā€¢ Heat Exchanger -The heat exchanger provided between
the pump and the generator which is used to cool the
weak hot solution returning from the generator to
absorber.
Practical Vapor ā€“ Absorption Refrigeration System
Practical vapor ā€“ absorption refrigeration system
Generator: The strong solution
of ammonia refrigerant and
water absorbent are heated by
the external source of heat
such as steam or hot water. It
can also be heated by other
sources like natural gas, electric
heater, waste exhaust heat etc.
Practical vapor absorption refrigeration system
Generator - Due to heating the
refrigerant ammonia gets
vaporized and it leaves the
generator. However, since
water has strong affinity for
ammonia and its vaporization
point is quite low some water
particles also get carried away
with ammonia refrigerant, so it
is important to pass this
refrigerant through analyzer.
Vapour Absorption
Refrigeration Systems
Based On Water-Lithium Bromide
Pair
VARS based on H2O ā€“ LiBr Pair
ā€¢ Vapour absorption refrigeration systems using water-lithium
bromide pair are extensively used in large capacity air
conditioning systems.
ā€¢ In these systems water is used as refrigerant and a solution of
lithium bromide in water is used as absorbent.
ā€¢ Since water is used as refrigerant, using these systems it is not
possible to provide refrigeration at sub-zero temperatures.
Hence it is used only in applications requiring refrigeration at
temperatures above 0o
C.
ā€¢ Hence these systems are used for air conditioning
applications. The analysis of this system is relatively easy as
the vapour generated in the generator is almost pure
refrigerant (water), unlike ammonia-water systems where
both ammonia and water vapour are generated in the
generator.
VARS based on H2O ā€“ LiBr Pair
Steady flow analysis of Water-Lithium Bromide
Systems
A steady flow analysis of the system is carried out with the
following assumptions:
i. Steady state and steady flow
ii. Changes in potential and kinetic energies across each
component are negligible
iii. No pressure drops due to friction
iv. Only pure refrigerant boils in the generator.
The nomenclature followed is:
m= mass flow rate of refrigerant, kg/s
mss= mass flow rate of strong solution (rich in LiBr), kg/s
mws= mass flow rate of weak solution (weak in LiBr), kg/s
Circulation ratio (Ī»)
-defined as the ratio of
strong solution
flow rate to
refrigerant
flow rate.
It is given by:
Ī» = mss/m
@Condenser
m1 = m2 = m3
Qc = m(h1 ā€“ h2)
Pc = Psat (TC)
where TC is the
condenser
temperature
@Expansion valve (refrigerant):
m2 = m3= m
h2 = h3
@Evaporator:
m3 = m4 = m
QE = m(h4 ā€“ h3)
PE = PSAT(TE)
where TEis the
evaporator
temperature
@Absorber
From total mass balance:
m + mss = mws
but mss = Ī»m,
mws = (1+Ī»)m
QA=mh4+ Ī»mh10
- (1+Ī»)mh5
@Solution pump
m5 = m6 = mws
Wp = mws(h6-h5)
=(1+Ī»)m(h6-h5)
Even though
the solution pump
work is small it is
still required in the
selection of
suitable pump.
@Generator
m7 = m8 +m1
Heat input to the
generator is given by:
QG=mh1+Ī»mh8
-(1+Ī»)mh7
@Solution heat exchanger
m6 = m7 = mws
m8 = m9 = mss
heat transfer
rate in the solution
heat exchanger, Q
is given by:
QHX = (1+Ī»)m(h7-h6)
=Ī»m(h8-h9)
@Solution expansion valve
m9 = m10 = mws
h9 = h10
The COP of the
system is given by:
Sample Problem in Simple VARS
9. The operating temperatures of a single stage vapour
absorption refrigeration system are: generator: 90o
C; condenser
and absorber: 40o
C; evaporator: 0o
C. The system has a
refrigeration capacity of 100 kW and the heat input to the
system is 160 kW. The solution pump work is negligible.
ā€¢a) Find the COP of the system and the total heat rejection rate
from the system.
ā€¢b) An inventor claims that by improving the design of all the
components of the system he could reduce the heat input to the
system to 80 kW while keeping the refrigeration capacity and
operating temperatures same as before. Examine the validity of
the claim.
ā€¢ Solution:
Sample Problem in Simple VARS

More Related Content

What's hot

Air refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tubeAir refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tube
aparnamalyala
Ā 
Chapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdfChapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdf
AnupKashyap10
Ā 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)
shone john
Ā 

What's hot (20)

Vapor Compression Refrigeration System
Vapor Compression Refrigeration System Vapor Compression Refrigeration System
Vapor Compression Refrigeration System
Ā 
Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)Aircraft refrigeration system (air cooling system)
Aircraft refrigeration system (air cooling system)
Ā 
Vapor compression refrigeration cycle
Vapor compression refrigeration cycleVapor compression refrigeration cycle
Vapor compression refrigeration cycle
Ā 
Aircraft refrigeration system
Aircraft refrigeration systemAircraft refrigeration system
Aircraft refrigeration system
Ā 
Air refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tubeAir refrigeration system by Bell Coleman cycle and Vortex tube
Air refrigeration system by Bell Coleman cycle and Vortex tube
Ā 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
Ā 
Heat transfer from extended surfaces (or fins)
Heat transfer from extended surfaces (or fins)Heat transfer from extended surfaces (or fins)
Heat transfer from extended surfaces (or fins)
Ā 
Vapour absorption refrigeration systems
Vapour absorption refrigeration systemsVapour absorption refrigeration systems
Vapour absorption refrigeration systems
Ā 
Air refrigerationsystem
Air refrigerationsystemAir refrigerationsystem
Air refrigerationsystem
Ā 
Brayton cycle
Brayton cycleBrayton cycle
Brayton cycle
Ā 
Vapour power cycle a
Vapour power cycle aVapour power cycle a
Vapour power cycle a
Ā 
Air refrigeration systems
Air refrigeration systemsAir refrigeration systems
Air refrigeration systems
Ā 
Chapter 6 Psychrometry & Air-Conditioning
Chapter 6  Psychrometry & Air-ConditioningChapter 6  Psychrometry & Air-Conditioning
Chapter 6 Psychrometry & Air-Conditioning
Ā 
Chapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdfChapter 3 Vapour Compression Refrigeration Systems.pdf
Chapter 3 Vapour Compression Refrigeration Systems.pdf
Ā 
STEAM JET COOLING SYSTEM
STEAM JET COOLING SYSTEMSTEAM JET COOLING SYSTEM
STEAM JET COOLING SYSTEM
Ā 
Vapour compression refrigeration system
Vapour compression refrigeration systemVapour compression refrigeration system
Vapour compression refrigeration system
Ā 
Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)Refrigeration and air conditioning (full note)
Refrigeration and air conditioning (full note)
Ā 
Boot strap air cooling system
Boot strap air cooling systemBoot strap air cooling system
Boot strap air cooling system
Ā 
vapour compression cycle
vapour compression cyclevapour compression cycle
vapour compression cycle
Ā 
Evaporators
EvaporatorsEvaporators
Evaporators
Ā 

Similar to Simple Vapor Absorption Refrigeration System

15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v
Mahendiran Subramaniyan
Ā 
fdocuments.in_134167289-solar-refrigeration-ppt.ppt
fdocuments.in_134167289-solar-refrigeration-ppt.pptfdocuments.in_134167289-solar-refrigeration-ppt.ppt
fdocuments.in_134167289-solar-refrigeration-ppt.ppt
MunishSmw
Ā 

Similar to Simple Vapor Absorption Refrigeration System (20)

REFRIGERATION SYSTEM
REFRIGERATION SYSTEMREFRIGERATION SYSTEM
REFRIGERATION SYSTEM
Ā 
lec 5 Vapour Absorption Refregiration Cycle.ppt
lec 5 Vapour Absorption Refregiration Cycle.pptlec 5 Vapour Absorption Refregiration Cycle.ppt
lec 5 Vapour Absorption Refregiration Cycle.ppt
Ā 
15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v15679104 basic-civil-and-mechanical-engineering-unit-v
15679104 basic-civil-and-mechanical-engineering-unit-v
Ā 
EME Refrigeration ppt.pptx
EME Refrigeration ppt.pptxEME Refrigeration ppt.pptx
EME Refrigeration ppt.pptx
Ā 
Vapour absorption refrigerator
Vapour absorption refrigeratorVapour absorption refrigerator
Vapour absorption refrigerator
Ā 
refrigeration and air conditioning
refrigeration and air conditioningrefrigeration and air conditioning
refrigeration and air conditioning
Ā 
MTT 04102 L2.pptx
MTT 04102  L2.pptxMTT 04102  L2.pptx
MTT 04102 L2.pptx
Ā 
Rwfrigeration working principle
Rwfrigeration working principleRwfrigeration working principle
Rwfrigeration working principle
Ā 
Liquefaction
LiquefactionLiquefaction
Liquefaction
Ā 
PERFORMANCE ANALYSIS OF VAPOR COMPRESSION REFRIGERATION SYSTEM USING DIFFEREN...
PERFORMANCE ANALYSIS OF VAPOR COMPRESSION REFRIGERATION SYSTEM USING DIFFEREN...PERFORMANCE ANALYSIS OF VAPOR COMPRESSION REFRIGERATION SYSTEM USING DIFFEREN...
PERFORMANCE ANALYSIS OF VAPOR COMPRESSION REFRIGERATION SYSTEM USING DIFFEREN...
Ā 
Heat pumps
Heat pumpsHeat pumps
Heat pumps
Ā 
fdocuments.in_134167289-solar-refrigeration-ppt.ppt
fdocuments.in_134167289-solar-refrigeration-ppt.pptfdocuments.in_134167289-solar-refrigeration-ppt.ppt
fdocuments.in_134167289-solar-refrigeration-ppt.ppt
Ā 
Refrigeration & Air Conditioning Notes
Refrigeration & Air Conditioning NotesRefrigeration & Air Conditioning Notes
Refrigeration & Air Conditioning Notes
Ā 
WORKING OF HEAT PUMPS WITH (CO2) REFRIGERANT
WORKING OF HEAT PUMPS WITH (CO2) REFRIGERANT WORKING OF HEAT PUMPS WITH (CO2) REFRIGERANT
WORKING OF HEAT PUMPS WITH (CO2) REFRIGERANT
Ā 
Panipat thermal power station training ppt
Panipat thermal power station training pptPanipat thermal power station training ppt
Panipat thermal power station training ppt
Ā 
Seminar
SeminarSeminar
Seminar
Ā 
K-10714 ABHISHEK(TQM )
K-10714 ABHISHEK(TQM )K-10714 ABHISHEK(TQM )
K-10714 ABHISHEK(TQM )
Ā 
Rac 2 ppt
Rac 2 pptRac 2 ppt
Rac 2 ppt
Ā 
Refrigeration Senator Libya
Refrigeration  Senator LibyaRefrigeration  Senator Libya
Refrigeration Senator Libya
Ā 
L356367
L356367L356367
L356367
Ā 

Recently uploaded

Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7
Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7
Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
Ā 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
Ā 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
Ā 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
Health
Ā 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
MayuraD1
Ā 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
Ā 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
jaanualu31
Ā 

Recently uploaded (20)

BhubaneswaršŸŒ¹Call Girls Bhubaneswar ā¤Komal 9777949614 šŸ’Ÿ Full Trusted CALL GIRL...
BhubaneswaršŸŒ¹Call Girls Bhubaneswar ā¤Komal 9777949614 šŸ’Ÿ Full Trusted CALL GIRL...BhubaneswaršŸŒ¹Call Girls Bhubaneswar ā¤Komal 9777949614 šŸ’Ÿ Full Trusted CALL GIRL...
BhubaneswaršŸŒ¹Call Girls Bhubaneswar ā¤Komal 9777949614 šŸ’Ÿ Full Trusted CALL GIRL...
Ā 
Design For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the startDesign For Accessibility: Getting it right from the start
Design For Accessibility: Getting it right from the start
Ā 
Computer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to ComputersComputer Lecture 01.pptxIntroduction to Computers
Computer Lecture 01.pptxIntroduction to Computers
Ā 
Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7
Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7
Call Girls in South Ex (delhi) call me [šŸ”9953056974šŸ”] escort service 24X7
Ā 
School management system project Report.pdf
School management system project Report.pdfSchool management system project Report.pdf
School management system project Report.pdf
Ā 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Ā 
2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects2016EF22_0 solar project report rooftop projects
2016EF22_0 solar project report rooftop projects
Ā 
Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
Ā 
Rums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdfRums floating Omkareshwar FSPV IM_16112021.pdf
Rums floating Omkareshwar FSPV IM_16112021.pdf
Ā 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
Ā 
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Ā 
data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
Ā 
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
+97470301568>> buy weed in qatar,buy thc oil qatar,buy weed and vape oil in d...
Ā 
DeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakesDeepFakes presentation : brief idea of DeepFakes
DeepFakes presentation : brief idea of DeepFakes
Ā 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
Ā 
Air Compressor reciprocating single stage
Air Compressor reciprocating single stageAir Compressor reciprocating single stage
Air Compressor reciprocating single stage
Ā 
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills KuwaitKuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Kuwait City MTP kit ((+919101817206)) Buy Abortion Pills Kuwait
Ā 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
Ā 
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
COST-EFFETIVE  and Energy Efficient BUILDINGS ptxCOST-EFFETIVE  and Energy Efficient BUILDINGS ptx
COST-EFFETIVE and Energy Efficient BUILDINGS ptx
Ā 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
Ā 

Simple Vapor Absorption Refrigeration System

  • 2.
  • 3.
  • 4.
  • 5. Simple Vapor Absorption Refrigeration System @Point 1 -low temperature and low pressure refrigerant vapour from evaporator at state 1 enters the absorber and is absorbed by solution weak in refrigerant (state 8) . The heat of absorption (Qa ) is rejected to an external heat sink at Tāˆž .
  • 6. Simple Vapor Absorption Refrigeration System @Point 2 -The solution, rich in refrigerant is pumped to the generator pressure (Pg ) by the solution pump (state 3). The pressurized solution gets heated up sensibly as it flows through the solution heat exchanger by extracting heat from hot solution coming from generator (state 4).
  • 7. @Point 5 -Heat is supplied to this solution from an external heat source in the generator (Qg at Tg ), as a result refrigerant vapour is generated (absorbent may also boil to give off vapour in case of ammonia-water systems) at state 5. This high-pressure refrigerant vapour condenses in the condenser by rejecting heat of condensation to the external heat sink (Qc at Tāˆž ) and leaves the condenser as a high pressure liquid (state 9). Simple Vapor Absorption Refrigeration System
  • 8. @Point 10 - the high pressure refrigerant liquid is throttled in the expansion device to evaporator pressure Pe from where it enters the evaporator, extracts heat from low temperature heat source (Qe at Te ) and leaves the evaporator as vapour at state 1, completing a cycle. Simple Vapor Absorption Refrigeration System
  • 9. @Point 6 - The hot solution that is weak in refrigerant (state 6) leaves the generator at high temperature and is cooled sensibly by rejecting heat to the solution going to the generator in the solution heat exchanger (state 7). Then it is throttled to the evaporator pressure in the throttle valve (state 8), from where it enters the absorber to complete the cycle. Simple Vapor Absorption Refrigeration System
  • 10.
  • 11. COP for Ideal Vapor Absorption Refrigeration System
  • 12. ā€¢ Absorption system requires a relatively large amount of low- grade thermal energy at generator temperature to generate refrigerant vapour from the solution in generator. Thus while the energy input is in the form of mechanical energy in vapour compression refrigeration systems, it is mainly in the form of thermal energy in case of absorption systems. COP for Ideal Vapor Absorption Refrigeration System
  • 13. ā€¢ The solution pump work is often negligible compared to the generator heat input. Thus the COPs for compression and absorption systems are given by: COP for Ideal Vapor Absorption Refrigeration System
  • 14. ā€¢ Thus absorption systems are advantageous where a large quantity of low-grade thermal energy is available freely at required temperature. However, it will be seen that for the refrigeration and heat rejection temperatures, the COP of vapour compression refrigeration system will be much higher than the COP of an absorption system as a high grade mechanical energy is used in the former, while a low-grade thermal energy is used in the latter. COP for Ideal Vapor Absorption Refrigeration System
  • 15. ā€¢ However, comparing these systems based on COPs is not fully justified, as mechanical energy is more expensive than thermal energy. Hence, sometimes the second law (or exergetic) efficiency is used to compare different refrigeration systems. It is seen that the second law (or exergetic) efficiency of absorption system is of the same order as that of a compression system. COP for Ideal Vapor Absorption Refrigeration System
  • 16. Maximum COP for Ideal Vapor Absorption Refrigeration System
  • 17. From first law of thermodynamics, Where Qe is the heat transferred to the absorption system at evaporator temperature Te , Qg is the heat transferred to the generator of the absorption system at temperature Tg , Qa+c is the heat transferred from the absorber and condenser of the absorption system at temperature To and Wp is the work input to the solution pump. Maximum COP for Ideal Vapor Absorption Refrigeration System
  • 18. ā€¢ If we assume that heat rejection at the absorber and condenser takes place at same external heat sink temperature To , then a vapour absorption refrigeration system operates between three temperature levels, Tg , To and Te . Maximum COP for Ideal Vapor Absorption Refrigeration System
  • 19. The maximum possible COP of an ideal VARS system is given by: Maximum COP for Ideal Vapor Absorption Refrigeration System
  • 20. Thus the ideal COP is only a function of operating temperatures similar to Carnot system. It can be seen from the above expression that the ideal COP of VARS system is equal to the product of efficiency of a Carnot heat engine operating between Tg and To and COP of a Carnot refrigeration system operating between To and Te , Maximum COP for Ideal Vapor Absorption Refrigeration System
  • 21. Thus an ideal vapour absorption refrigeration system can be considered to be a combined system consisting of a Carnot heat engine and a Carnot refrigerator as shown in Fig.14.4. Thus the COP of an ideal VARS increases as generator temperature (Tg ) and evaporator temperature (Te ) increase and heat rejection temperature (To ) decreases. However, the COP of actual VARS will be much less than that of an ideal VARS due to various internal and external irreversibilities present in actual systems. Maximum COP for Ideal Vapor Absorption Refrigeration System
  • 22. Example of VARS ā€¢ 1. Hydrogen enters the pipe with liquid ammonia (or lithium bromide solution) 2. Ammonia and hydrogen enter the inner compartment of the refrigerator. An increase in volume causes a decrease in the partial pressure of the liquid ammonia. The ammonia evaporates, requiring energy to overcome the Ī”HVap. The required energy is drawn from the interior of the refrigerator, thus cooling it.
  • 23. Example of VARS ā€¢ 3. Ammonia and hydrogen return from the inner compartment, ammonia returns to absorber and dissolves in water. Hydrogen is free to rise upwards. 4. Ammonia gas condensation (passive cooling). 5. Hot ammonia (gas). 6. Heat insulation and distillation of ammonia gas from water. 7. Heat source (electric). 8. Absorber vessel (water and ammonia solution).
  • 24. ā€¢ 1. Hydrogen enters the pipe with liquid ammonia (or lithium bromide solution) 2. Ammonia and hydrogen enter the inner compartment of the refrigerator. An increase in volume causes a decrease in the partial pressure of the liquid ammonia. The ammonia evaporates, requiring energy to overcome the Ī”HVap. The required energy is drawn from the interior of the refrigerator, thus cooling it. 3. Ammonia and hydrogen return from the inner compartment, ammonia returns to absorber and dissolves in water. Hydrogen is free to rise upwards. 4. Ammonia gas condensation (passive cooling). 5. Hot ammonia (gas). 6. Heat insulation and distillation of ammonia gas from water. 7. Heat source (electric). 8. Absorber vessel (water and ammonia solution).
  • 25. Practical Vapor Absorption Refrigeration System ā€¢ A practical VARS has 3 additional parts : ā€¢ ANALYSER ā€¢ RECTIFIER ā€¢ HEAT EXCHANGER
  • 26. Practical Vapor ā€“ Absorption Refrigeration System ā€¢ Analyser -When ammonia is vaporized in the generator some water is also vaporized ,and flow into the condenser along with ammonia. Thus the ammonia refrigerant leaving the generator carries appreciable amount of water vapor. If this water vapor is allowed to be carried to the evaporator, the capacity of the refrigeration system would reduce. The water vapor from ammonia refrigerant is removed by analyzer and the rectifier.
  • 27. Practical Vapor ā€“ Absorption Refrigeration System ā€¢ The analyzer is a sort of distillation column that is located at the top of the generator. The analyzer consists of number of plates positioned horizontally. When the ammonia refrigerant along with the water vapor particles enters the analyzer, the solution is cooled. Since water has higher saturation temperature, water vapor gets condensed into the water particles that drip down into the generator. The ammonia refrigerant in the gaseous state continues to rise up and it moves to the rectifier.
  • 28. Practical Vapor ā€“ Absorption Refrigeration System ā€¢ Rectifier - In case the water vapour are not completely removed in the analyser, a closed type of vapour cooler called rectifier is also known as dehydrator is used, it may be of water cooled. ā€¢ The rectifier is a sort of the heat exchanger cooled by the water, which is also used for cooling the condenser. Due to cooling the remaining water vapor mixed with the ammonia refrigerant also gets condensed along with some particles of ammonia. This weak solution of water and ammonia drains down to the analyzer and then to the generator
  • 29. Practical Vapor ā€“ Absorption Refrigeration System ā€¢ Heat Exchanger -The heat exchanger provided between the pump and the generator which is used to cool the weak hot solution returning from the generator to absorber.
  • 30. Practical Vapor ā€“ Absorption Refrigeration System
  • 31. Practical vapor ā€“ absorption refrigeration system Generator: The strong solution of ammonia refrigerant and water absorbent are heated by the external source of heat such as steam or hot water. It can also be heated by other sources like natural gas, electric heater, waste exhaust heat etc.
  • 32. Practical vapor absorption refrigeration system Generator - Due to heating the refrigerant ammonia gets vaporized and it leaves the generator. However, since water has strong affinity for ammonia and its vaporization point is quite low some water particles also get carried away with ammonia refrigerant, so it is important to pass this refrigerant through analyzer.
  • 33. Vapour Absorption Refrigeration Systems Based On Water-Lithium Bromide Pair
  • 34. VARS based on H2O ā€“ LiBr Pair ā€¢ Vapour absorption refrigeration systems using water-lithium bromide pair are extensively used in large capacity air conditioning systems. ā€¢ In these systems water is used as refrigerant and a solution of lithium bromide in water is used as absorbent. ā€¢ Since water is used as refrigerant, using these systems it is not possible to provide refrigeration at sub-zero temperatures. Hence it is used only in applications requiring refrigeration at temperatures above 0o C.
  • 35. ā€¢ Hence these systems are used for air conditioning applications. The analysis of this system is relatively easy as the vapour generated in the generator is almost pure refrigerant (water), unlike ammonia-water systems where both ammonia and water vapour are generated in the generator. VARS based on H2O ā€“ LiBr Pair
  • 36.
  • 37.
  • 38.
  • 39. Steady flow analysis of Water-Lithium Bromide Systems A steady flow analysis of the system is carried out with the following assumptions: i. Steady state and steady flow ii. Changes in potential and kinetic energies across each component are negligible iii. No pressure drops due to friction iv. Only pure refrigerant boils in the generator. The nomenclature followed is: m= mass flow rate of refrigerant, kg/s mss= mass flow rate of strong solution (rich in LiBr), kg/s mws= mass flow rate of weak solution (weak in LiBr), kg/s
  • 40. Circulation ratio (Ī») -defined as the ratio of strong solution flow rate to refrigerant flow rate. It is given by: Ī» = mss/m
  • 41. @Condenser m1 = m2 = m3 Qc = m(h1 ā€“ h2) Pc = Psat (TC) where TC is the condenser temperature
  • 42. @Expansion valve (refrigerant): m2 = m3= m h2 = h3 @Evaporator: m3 = m4 = m QE = m(h4 ā€“ h3) PE = PSAT(TE) where TEis the evaporator temperature
  • 43. @Absorber From total mass balance: m + mss = mws but mss = Ī»m, mws = (1+Ī»)m QA=mh4+ Ī»mh10 - (1+Ī»)mh5
  • 44. @Solution pump m5 = m6 = mws Wp = mws(h6-h5) =(1+Ī»)m(h6-h5) Even though the solution pump work is small it is still required in the selection of suitable pump.
  • 45. @Generator m7 = m8 +m1 Heat input to the generator is given by: QG=mh1+Ī»mh8 -(1+Ī»)mh7
  • 46. @Solution heat exchanger m6 = m7 = mws m8 = m9 = mss heat transfer rate in the solution heat exchanger, Q is given by: QHX = (1+Ī»)m(h7-h6) =Ī»m(h8-h9)
  • 47. @Solution expansion valve m9 = m10 = mws h9 = h10 The COP of the system is given by:
  • 48. Sample Problem in Simple VARS 9. The operating temperatures of a single stage vapour absorption refrigeration system are: generator: 90o C; condenser and absorber: 40o C; evaporator: 0o C. The system has a refrigeration capacity of 100 kW and the heat input to the system is 160 kW. The solution pump work is negligible. ā€¢a) Find the COP of the system and the total heat rejection rate from the system. ā€¢b) An inventor claims that by improving the design of all the components of the system he could reduce the heat input to the system to 80 kW while keeping the refrigeration capacity and operating temperatures same as before. Examine the validity of the claim.