IOSR Journal of Electronics and Communication Engineering (IOSR-JECE)
e-ISSN: 2278-2834,p- ISSN: 2278-8735.Volume 8, Issue 1 (Sep. - Oct. 2013), PP 01-06
www.iosrjournals.org
www.iosrjournals.org 1 | Page
An Overview of Compact Flourescent Lamp Retrofitting In
Nigeria: Case Study of Hostel Environment in University Of
Lagos
Igwilo.O.C.1*
, Abolarin.S.M.1
,Eguma.C.A.1
,Adegbenro.O.1
1
National Center for Energy Efficiency and Conservation(Energy Commission of Nigeria), Faculty of
Engineering, University of Lagos, Lagos, Nigeria
Abstract: This case study cuts across the evaluation of the performance of the use of compact tubes in the
University of Lagos hostel environment .Data were collected by means of questionnaires centralized basically
on three major areas; the level of awareness of the students with compact fluorescent tube,the current
Luminaire information data and finally,the beneficiary experiences and reactions to the retrofitting project of
compact fluorescent lamps which has already been executed prior to the review on the evaluation.The latter of
the three major areas of case study was solely based on perception of the students which could be affected by
psychological,health and environmental factors.A chart of the evaluation of twenty questions in the
questionnaire given to each student whose total population is over 500 in the environment of study was
demonstrated. Project test duration is two hundred and fifty days. Also, an energy/cost audit calculation were
carried out. We found out that about 3197kw-hr/ ₦41,145.39 can be saved by retrofitting the 36 watt
fluorescent tube with CFL and about 45,662kw-hr/ ₦587,669.90 for the 60 watt incandescent fluorescent tubes
to compact tubes per 120-rooms hostel at a unit cost of ₦12.87 per kw/hr. For effective application, we also
calculated house hold use.
Key words: Compact, CFL, Fluorescent, Lamp, Naira
I. Introduction
In recent times in some developing countries, some projects have been undertaken to phase out
incandescent lamps which were replaced with compact fluorescent tubes. As at 10th
of August 2010 for example
,India had already planned to replace 400 million incandescent bulbs with compact fluorescent tubes saving
6000MW annually(1,2)This indicates that developing countries are waking up to the fact that energy-saving
compact fluorescent lamp is very vital in energy management in a country. It should be noted that replacement
of incandescent tubes with compact fluorescent tubes in developing countries or economies will lead to
reduction in energy consumption annually. This development will in turn reduce the capital waste in budgeting
for more power projects that might not be needed or channeling the excess power that could be sold
internationally to generate more revenue for the Country. In places like Nigeria, the macroscopic level of
awareness (3,4) in the use of energy-efficient bulbs, is seriously very low, indicating that more work
disseminating information and creating awareness of compact fluorescent tubes have to be carried out more
frequently.
Due to the fact that cfls are initially more expensive considering the initial switch-over investment
(5),the government should put in more effort in funding initially energy-efficiency projects, considering the high
return on the investment at the long term. Firstly, the government should also involve stake holders in reducing
the prices of cfls (1).The government could come up with incentives and good marketing strategies that will
coax the populace to buy into this project. However, the masses have a part to play also, in improvising of
funds. The government duty here is to carry the implementation of the project and also help in subsidizing for
funds if possible or needed. We are still buttressing the need for the government’s approval and involvement
based on the fact that, if this retrofitting exercise is carried out by individual business enterprises relevant to
distribution of cfls for profit purposes, this might delay the significant impact being expected in the overall
populace (3). Hence Government should be the initial driver for such global projects. There should be tax
incentives for industries or institutions that invest in such energy saving projects.
The significant advantage of compact fluorescent tube cannot be over emphasized. This study gives a
breakdown structure of the analysis found from the evaluation and review of compact fluorescent cfl retrofitting
exercise in a school hostel after two hundred and fifty days. We will also indicate the amount of energy and the
cost that can be saved from the retrofitting exercise. The application of this study model to the entire Nigeria
environment will save Billions of Nigerian Naira energy equivalent.
An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel
www.iosrjournals.org 2 | Page
II. Objective
 To buttress the importance of energy saving initiative.
 To highlight the general performance of CFL over incandescent and fluorescent tubes.
 To create more awareness for the distribution,supply and implementation of CFL bulbs for house
hold,office and industrial use,as this would reduce the energy demands thus reducing cost of energy.
III. Methodology
First of all, a retrofitting exercise was undertaken in the hostel environment, which involved replacing
the previously conventionally used 36watt fluorescent tube with about 14 watt compact fluorescent tubes.
After two hundred and fifty days (250) usage of the new compact fluorescent tube, questionnaires were
distributed to capture the necessary data.
We made use of excel to gather all data from questionnaire. We created tables and designed charts that
will use the results obtained to give clear feedback evaluation picture of the impact of the CFL switch-over
project.
3.1 Assumptions
 It was assumed that each room was retrofitted with two CFL bulbs owing to the fact that most of the rooms
only had two fittings except the common room, the reading room and the shop outlets which had extra
fittings making it a total of three fittings for each of the rooms mentioned.
 It should also be assumed that one hundred and eleven student answered the questionnaire which was in
shortened number of the 120 rooms which were retrofitted.This indicates that a percentage error will be
calculated.
Questionnaires were distributed to capture the necessary data from 111 student occupants in this hostel of
study. It should be noted that about 120 rooms were covered in this hostel.
It should be noted that the questionnaires were answered according to perception of the student
representative. It should be noted that over 240 CFL bulbs were used in the retrofitting exercise to replace
the 36 watt fluorescent tubes in each room.
The questionnaire was comprised of compact fluorescent feedback form to access the performance,
durability and sustainability of the compact fluorescent tube to ascertain whether this new technology has
withstood the test of time or whether the quality control should be reviewed.
The questionnaire focused on three area (see attached the sample of the questionnaire)
 Understanding consumer knowledge and perception of energy efficiency/CFLS,
 the current luminaire information data and finally;
 The beneficiary experiences and reactions to the project.
3.2 Energy Audit Data Collection
To obtain the energy consumption data, we collected data from question 7 and 13 of the questionnaire,
which cover how long the student left the lamp on and the wattage of the lamp respectively. However, for
optimum data collection we picked the highest limit of hours spent leaving the lamp on each day, and from
investigation we noted that during that switch-over project 14watt bulbs were suppose to have been installed but
some had 11watt capacity label. We did take care of the effects of this anomaly by multiplying each cfl power
capacity by the total consumed hours each day using excel calculator programme to obtain the total watt
hours,we then divided by 1000 to get the kw/hr. We then multiplied by 2 to cover up for the two lamps per
room.We then multiplied for the total of the 250 days.
This was executed by the use of excel programming, which suited this purpose.
3.2.1 Comparison Data For Energy Audit Simulation for 36 Watt Fluorescent Tube
We simulated the energy data collection for the previously used 36 watt bulbs (6,7,8); we used data
collated to multiply the duration in which the lamp is left on by 36 watt fluorescent tube to know the amount
that was left on for 250 days.
3.2.2 Comparison Data for Energy Audit Simulation for 6O Watt Incandescent Bulb
We also simulated for the 60 watt incandescent bulb which is used in house hold compartments,we got
the total energy used by multiplying 60 watt by each of the time duration of the bulbs simulated to be left on if
also utilized in each room.We then calculated difference by subtracting the total energy utilized by the CFL
LAMP from the total energy utilized by the 60 watt incandescent lamp.
An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel
www.iosrjournals.org 3 | Page
3.2.3 Determination of the Percentage Error Encountered during the Retrofitting Process.
It should also be noted that over 120 rooms were retrofitted, but the questionnaire indicated just 111
rooms excluding the three bulbs for the common room and shop. Therefore, we calculated the percentage error
resulting from these differences to be ±7.4%.
IV. Results/Discussion
4.1 Energy Audit Result
We got the total energy utilized by the compact fluorescent tube(2 lamps per room) for two hundred
and fifty days .The energy utilized amounted to 14,038KW-Hr.We also simulated the result for the total energy
used for the 36 watt bulb. It amounted to 18135 KW-HR. We also simulated for house hold incandescent bulb
which amounted to 60,600KWHR.
The results generated from the project using the Excel Sheet application showed that 3197kw-hr and
45662kw-hr of power can be saved by retrofitting with 36watt and 60watt bulbs respectively with compact
fluorescent tube.
4.2 Cost Audit Result
The first and most important finding is the cost that could be saved by CFL retrofitting exercise.We
found out that about ₦41,145.39 can be saved by retrofitting the 36 watt fluorescent tube with CFL and about
₦587,669.90 for the 60 watt incandescent house hold simulation can be saved keeping unit cost at ₦12.87 per
kw-hr. It should also be noted that over 120 rooms were retrofitted, but the questionnaire indicated just 111
rooms excluding the three bulbs for the common room and shop. This exercise was executed for over 250 days.
We can deduce that the application of this cost audit as a result of the energy conserved by the retrofitting
exercise, will significantly save more cost and energy that could be utilized to support more businesses for
employment generation.
We found out that over 81% of the students were aware of energy efficiency and conservation. About
19% were not aware.It indicates the fact that more awareness needs to be created generally in order to inform
the populace of energy efficiency, but as we can see, only 19% of the students were novice.
From my investigation we noted that over 100% used 14 watts bulb.We also found out from that about
95% of the students are aware of switching off the lamps in the day and making use of natural day light.We
matched this result using a pie chart to indicate the percentage of each property of each feedback form.We got
the result that over 3% left their lights on from 1-5hrs, 9% left their lights on from 6-10hrs,28% left their lights
on from 11-15hrs, about 35% left their lights on from 16-20hrs and finally about 25% left their lights on from
21-24hrs.From the result it shows that just over 12% use natural light and save energy,and about over 55% of
the student to practice what they believe in.So emphasis needs to be placed on practicing what we preach as this
is reflected that over 95% believe in saving light energy during the day,but about over 55% don’t practice that.
Fig 1 pie chart indicates that over 55% do not utilize the natural light energy. This is very disappointing and will
not prolong the life span of the CFL lamp. Fig 2 indicates that 95% are aware of the daylight saving energy
initiative but do not practice it. We will also represent the percentage of the student that rated the brightness of
the CFL LAMP which is very important for readability. This is demonstrated in the pie- chart. We can see a
wide number precisely about 87% rated it as good. This indicates the general acceptance of CFL for readability
standards and this rating could be marked at 95%.
For heat emission we would give the result of the finding of the percentage of student who said YES
OR NO that CFL cause heat or not. Fig 4 indicates the general light output is relatively good (over 96 %). We
can see infer that CFL LAMPS hardly released heat. This means they have little heat emissions making it
conducive for people in tropical regions of the world. It should be noted in design of lighting technology that
readability should be put into consideration. From our survey we noted that 84% rated this CFL LAMPS as
having good readability standards, the rest of the 16% could have just been skeptical or it was probably due to
environmental and internal perception factors.
Fig 6 rates the life span of the CFL after duration of 250 days. It was noted that the overall rating was
96% very good life span. This is very encouraging. In design and marketing, we have to take in the remark of
the consumer or customer, because the customer is always right. We discovered that over 99% rated the
appearance or the physical design of the build as very good. This result indicates it has an excellent appearance.
An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel
www.iosrjournals.org 4 | Page
FIGURES & TABLES
fig 1: q7 duration of hours used by bulb
fig 2: q4 percentage aware of daylight energy saving
An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel
www.iosrjournals.org 5 | Page
fig 4: q18 rating for the light output
fig 5: q19 readability rating
fig 6: q20 life span rating
An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel
www.iosrjournals.org 6 | Page
fig 7: q21 design appearance rating
VI. Conclusion
6.1 Limitation and Future Studies
 The intermittent switching on and off of the CFLS could make it less sustainable. However, they are
supposed to last for 10 000 hours. They should be left on for a while without being turned on and off
frequently for optimum performance.
 Not all CFLS can be used with dimmers or regulators. A regular CFL if used with dimmer will burn off
quickly. One has to check package before use.
 CFL Lamps used outdoors must be protected from weather elements.
 They have high sensitivity to temperatures and can cause lower light levels. The lower the temperature, the
lower the light level. This indicates it is not readily suitable for high temperate or low temperature regions.
 CFLS are not suitable for towered or spot lights, or where narrowed beams of light are required. They are
only designed for ambient lighting.
 If a CFL is broken or burnt, the mercury is being released, and the presence of mercury makes it hazardous
to the environment. It should be noted that if not correctly disposed, it could intoxicate the environment,
because mercury is naturally a toxic metal in study of chemistry.
More work should be done to create designs for CFL that will be used in spot lights which will help the
entertainment industry and could also be used for auditorium or conference hall services.
From the result of the energy audit in comparison with the energy that would have been expended by a 36 watt
bulb and 60 watt incandescent bulb with the CFL bulbs based on simulation,it can be inferred that CFL could
save a significant amount of energy therefore reducing the initial cost.It can also drastically reduce the overall
cost spent on energy consumption.It could also be noted that the light output is relatively the same in
comparison with the 36 watt bulb and 60 watt in candescent bulb,which gives the same output for lesser amount
of energy and cost.It should be noted that the conventional 60 watt incandescent bulb should be phased out and
replaced by CFL as they have stood the test of time.More work should be done in increasing the awareness of
the energy efficiency initiative at a macroscopic level of the populace in Nigeria and globally considering the
economic impact of the current energy demand and limited supply.
References
[1]. The Bureau Energy Efficiency (BEE);Documentation of best practice.Lighting Energy Efficiency project under Bachat Lamp Y
ajonascheme; 2001;3-5
[2]. BolajiF.SuleKajogbola R AlaoHabeeb A AJIMOTOKAN Mohammed K Garba; Compact fluorescent lamps and electricity
consumption trend in residential buildings in Ilorin, Nigeria”,International Journal of Energy Sector Management;5(2);2011;162-
168
[3]. United Nations Development Programme. Promoting Energy Efficiency in Residential and Public Sector in Nigeria;
http://www.ng.undp.org/energy/EE-project-document.pdf.;2011;41-46
[4]. Lebot,B.;Energy Efficiency and Market Transformation:A short overview of Best Practices.A paper presented during the inception
Workshop of the UNDP-GEF Project to promote Energy Efficiency in Residential and public building in Nigeria;2008.
[5]. MridulChadha earth industry http://earthandindustry.com/2010/05/india-to-launch-worlds-largest-cdm-project-will-replace-400-
million-incandescent-lamps-with-cfls; 2010;1-2
[6]. Thumann A and Younger WJ.Handbook of Energy Audit.Published by the Fairmont Press,Inc.2008
[7]. http://www.energymanagertraining.com/CDM/cdm_main.htm
[8]. Furniture.about.com/od/accesoriesguide/0/cfladvant.htm by Ale Abbas

More Related Content

Similar to An Overview of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study of Hostel Environment in University Of Lagos

Ab0401 s04 team 4 e learning week assignment
Ab0401 s04 team 4 e learning week assignmentAb0401 s04 team 4 e learning week assignment
Ab0401 s04 team 4 e learning week assignmentjgoh009
 
AB0401 S04 team 4 E- learning week assignment
AB0401 S04 team 4 E- learning week assignmentAB0401 S04 team 4 E- learning week assignment
AB0401 S04 team 4 E- learning week assignmentNBS
 
Paper presentation
Paper presentationPaper presentation
Paper presentationSudeep Kc
 
Design a Highly Efficient Push-Pull converter for Photovoltaic Applications
Design a Highly Efficient Push-Pull converter for Photovoltaic ApplicationsDesign a Highly Efficient Push-Pull converter for Photovoltaic Applications
Design a Highly Efficient Push-Pull converter for Photovoltaic ApplicationsEklavya Sharma
 
Energia solar thermal energy storage systems
Energia solar   thermal energy storage systemsEnergia solar   thermal energy storage systems
Energia solar thermal energy storage systemsUsama Abudawud
 
A Low-cost Renewable Energy Solution for Improved Energy Access in Nigeria
A Low-cost Renewable Energy Solution for Improved Energy Access in NigeriaA Low-cost Renewable Energy Solution for Improved Energy Access in Nigeria
A Low-cost Renewable Energy Solution for Improved Energy Access in NigeriaIRJET Journal
 
IRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case StudyIRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case StudyIRJET Journal
 
Design and fabrication of solar conentrator ( content )
Design and fabrication of solar conentrator ( content )Design and fabrication of solar conentrator ( content )
Design and fabrication of solar conentrator ( content )Kavin Prasath KS
 
A Systematic Review of Renewable Energy Trend.pdf
A Systematic Review of Renewable Energy Trend.pdfA Systematic Review of Renewable Energy Trend.pdf
A Systematic Review of Renewable Energy Trend.pdfssuser793b4e
 
Energy audit, conservation and power factor
Energy audit, conservation and power factorEnergy audit, conservation and power factor
Energy audit, conservation and power factoreSAT Publishing House
 
ena_the_great_energy_quest_september_2015
ena_the_great_energy_quest_september_2015ena_the_great_energy_quest_september_2015
ena_the_great_energy_quest_september_2015Stuart Johnston
 
Techno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdf
Techno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdfTechno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdf
Techno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdfAarthi Venkatesh N
 
Environmentalreviewpaper57371357
Environmentalreviewpaper57371357Environmentalreviewpaper57371357
Environmentalreviewpaper57371357Aun Ahsan
 
Energy audit, conservation and power factor improvement for bmsit campus
Energy audit, conservation and power factor improvement for bmsit campusEnergy audit, conservation and power factor improvement for bmsit campus
Energy audit, conservation and power factor improvement for bmsit campuseSAT Journals
 
technical paper
technical papertechnical paper
technical paperJ K Shree
 

Similar to An Overview of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study of Hostel Environment in University Of Lagos (20)

Ab0401 s04 team 4 e learning week assignment
Ab0401 s04 team 4 e learning week assignmentAb0401 s04 team 4 e learning week assignment
Ab0401 s04 team 4 e learning week assignment
 
AB0401 S04 team 4 E- learning week assignment
AB0401 S04 team 4 E- learning week assignmentAB0401 S04 team 4 E- learning week assignment
AB0401 S04 team 4 E- learning week assignment
 
Paper presentation
Paper presentationPaper presentation
Paper presentation
 
Fritillaries5-1
Fritillaries5-1Fritillaries5-1
Fritillaries5-1
 
report 2
report 2report 2
report 2
 
Design a Highly Efficient Push-Pull converter for Photovoltaic Applications
Design a Highly Efficient Push-Pull converter for Photovoltaic ApplicationsDesign a Highly Efficient Push-Pull converter for Photovoltaic Applications
Design a Highly Efficient Push-Pull converter for Photovoltaic Applications
 
energyproject
energyprojectenergyproject
energyproject
 
Energia solar thermal energy storage systems
Energia solar   thermal energy storage systemsEnergia solar   thermal energy storage systems
Energia solar thermal energy storage systems
 
Final Draft
Final DraftFinal Draft
Final Draft
 
A Low-cost Renewable Energy Solution for Improved Energy Access in Nigeria
A Low-cost Renewable Energy Solution for Improved Energy Access in NigeriaA Low-cost Renewable Energy Solution for Improved Energy Access in Nigeria
A Low-cost Renewable Energy Solution for Improved Energy Access in Nigeria
 
IRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case StudyIRJET- Energy Saving in Governmental Educational Buildings: Case Study
IRJET- Energy Saving in Governmental Educational Buildings: Case Study
 
E031201028033
E031201028033E031201028033
E031201028033
 
Design and fabrication of solar conentrator ( content )
Design and fabrication of solar conentrator ( content )Design and fabrication of solar conentrator ( content )
Design and fabrication of solar conentrator ( content )
 
A Systematic Review of Renewable Energy Trend.pdf
A Systematic Review of Renewable Energy Trend.pdfA Systematic Review of Renewable Energy Trend.pdf
A Systematic Review of Renewable Energy Trend.pdf
 
Energy audit, conservation and power factor
Energy audit, conservation and power factorEnergy audit, conservation and power factor
Energy audit, conservation and power factor
 
ena_the_great_energy_quest_september_2015
ena_the_great_energy_quest_september_2015ena_the_great_energy_quest_september_2015
ena_the_great_energy_quest_september_2015
 
Techno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdf
Techno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdfTechno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdf
Techno_Economic_Analysis_of_Solar_Hybrid_System_for_Residential_Sector.pdf
 
Environmentalreviewpaper57371357
Environmentalreviewpaper57371357Environmentalreviewpaper57371357
Environmentalreviewpaper57371357
 
Energy audit, conservation and power factor improvement for bmsit campus
Energy audit, conservation and power factor improvement for bmsit campusEnergy audit, conservation and power factor improvement for bmsit campus
Energy audit, conservation and power factor improvement for bmsit campus
 
technical paper
technical papertechnical paper
technical paper
 

More from IOSR Journals (20)

A011140104
A011140104A011140104
A011140104
 
M0111397100
M0111397100M0111397100
M0111397100
 
L011138596
L011138596L011138596
L011138596
 
K011138084
K011138084K011138084
K011138084
 
J011137479
J011137479J011137479
J011137479
 
I011136673
I011136673I011136673
I011136673
 
G011134454
G011134454G011134454
G011134454
 
H011135565
H011135565H011135565
H011135565
 
F011134043
F011134043F011134043
F011134043
 
E011133639
E011133639E011133639
E011133639
 
D011132635
D011132635D011132635
D011132635
 
C011131925
C011131925C011131925
C011131925
 
B011130918
B011130918B011130918
B011130918
 
A011130108
A011130108A011130108
A011130108
 
I011125160
I011125160I011125160
I011125160
 
H011124050
H011124050H011124050
H011124050
 
G011123539
G011123539G011123539
G011123539
 
F011123134
F011123134F011123134
F011123134
 
E011122530
E011122530E011122530
E011122530
 
D011121524
D011121524D011121524
D011121524
 

Recently uploaded

result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college projectTonystark477637
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxupamatechverse
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Serviceranjana rawat
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).pptssuser5c9d4b1
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdfankushspencer015
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...ranjana rawat
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxupamatechverse
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINESIVASHANKAR N
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 

Recently uploaded (20)

result management system report for college project
result management system report for college projectresult management system report for college project
result management system report for college project
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Introduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptxIntroduction to Multiple Access Protocol.pptx
Introduction to Multiple Access Protocol.pptx
 
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
(RIA) Call Girls Bhosari ( 7001035870 ) HI-Fi Pune Escorts Service
 
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
247267395-1-Symmetric-and-distributed-shared-memory-architectures-ppt (1).ppt
 
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service NashikCall Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
Call Girls Service Nashik Vaishnavi 7001305949 Independent Escort Service Nashik
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Introduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptxIntroduction and different types of Ethernet.pptx
Introduction and different types of Ethernet.pptx
 
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINEMANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
MANUFACTURING PROCESS-II UNIT-2 LATHE MACHINE
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 

An Overview of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study of Hostel Environment in University Of Lagos

  • 1. IOSR Journal of Electronics and Communication Engineering (IOSR-JECE) e-ISSN: 2278-2834,p- ISSN: 2278-8735.Volume 8, Issue 1 (Sep. - Oct. 2013), PP 01-06 www.iosrjournals.org www.iosrjournals.org 1 | Page An Overview of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study of Hostel Environment in University Of Lagos Igwilo.O.C.1* , Abolarin.S.M.1 ,Eguma.C.A.1 ,Adegbenro.O.1 1 National Center for Energy Efficiency and Conservation(Energy Commission of Nigeria), Faculty of Engineering, University of Lagos, Lagos, Nigeria Abstract: This case study cuts across the evaluation of the performance of the use of compact tubes in the University of Lagos hostel environment .Data were collected by means of questionnaires centralized basically on three major areas; the level of awareness of the students with compact fluorescent tube,the current Luminaire information data and finally,the beneficiary experiences and reactions to the retrofitting project of compact fluorescent lamps which has already been executed prior to the review on the evaluation.The latter of the three major areas of case study was solely based on perception of the students which could be affected by psychological,health and environmental factors.A chart of the evaluation of twenty questions in the questionnaire given to each student whose total population is over 500 in the environment of study was demonstrated. Project test duration is two hundred and fifty days. Also, an energy/cost audit calculation were carried out. We found out that about 3197kw-hr/ ₦41,145.39 can be saved by retrofitting the 36 watt fluorescent tube with CFL and about 45,662kw-hr/ ₦587,669.90 for the 60 watt incandescent fluorescent tubes to compact tubes per 120-rooms hostel at a unit cost of ₦12.87 per kw/hr. For effective application, we also calculated house hold use. Key words: Compact, CFL, Fluorescent, Lamp, Naira I. Introduction In recent times in some developing countries, some projects have been undertaken to phase out incandescent lamps which were replaced with compact fluorescent tubes. As at 10th of August 2010 for example ,India had already planned to replace 400 million incandescent bulbs with compact fluorescent tubes saving 6000MW annually(1,2)This indicates that developing countries are waking up to the fact that energy-saving compact fluorescent lamp is very vital in energy management in a country. It should be noted that replacement of incandescent tubes with compact fluorescent tubes in developing countries or economies will lead to reduction in energy consumption annually. This development will in turn reduce the capital waste in budgeting for more power projects that might not be needed or channeling the excess power that could be sold internationally to generate more revenue for the Country. In places like Nigeria, the macroscopic level of awareness (3,4) in the use of energy-efficient bulbs, is seriously very low, indicating that more work disseminating information and creating awareness of compact fluorescent tubes have to be carried out more frequently. Due to the fact that cfls are initially more expensive considering the initial switch-over investment (5),the government should put in more effort in funding initially energy-efficiency projects, considering the high return on the investment at the long term. Firstly, the government should also involve stake holders in reducing the prices of cfls (1).The government could come up with incentives and good marketing strategies that will coax the populace to buy into this project. However, the masses have a part to play also, in improvising of funds. The government duty here is to carry the implementation of the project and also help in subsidizing for funds if possible or needed. We are still buttressing the need for the government’s approval and involvement based on the fact that, if this retrofitting exercise is carried out by individual business enterprises relevant to distribution of cfls for profit purposes, this might delay the significant impact being expected in the overall populace (3). Hence Government should be the initial driver for such global projects. There should be tax incentives for industries or institutions that invest in such energy saving projects. The significant advantage of compact fluorescent tube cannot be over emphasized. This study gives a breakdown structure of the analysis found from the evaluation and review of compact fluorescent cfl retrofitting exercise in a school hostel after two hundred and fifty days. We will also indicate the amount of energy and the cost that can be saved from the retrofitting exercise. The application of this study model to the entire Nigeria environment will save Billions of Nigerian Naira energy equivalent.
  • 2. An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel www.iosrjournals.org 2 | Page II. Objective  To buttress the importance of energy saving initiative.  To highlight the general performance of CFL over incandescent and fluorescent tubes.  To create more awareness for the distribution,supply and implementation of CFL bulbs for house hold,office and industrial use,as this would reduce the energy demands thus reducing cost of energy. III. Methodology First of all, a retrofitting exercise was undertaken in the hostel environment, which involved replacing the previously conventionally used 36watt fluorescent tube with about 14 watt compact fluorescent tubes. After two hundred and fifty days (250) usage of the new compact fluorescent tube, questionnaires were distributed to capture the necessary data. We made use of excel to gather all data from questionnaire. We created tables and designed charts that will use the results obtained to give clear feedback evaluation picture of the impact of the CFL switch-over project. 3.1 Assumptions  It was assumed that each room was retrofitted with two CFL bulbs owing to the fact that most of the rooms only had two fittings except the common room, the reading room and the shop outlets which had extra fittings making it a total of three fittings for each of the rooms mentioned.  It should also be assumed that one hundred and eleven student answered the questionnaire which was in shortened number of the 120 rooms which were retrofitted.This indicates that a percentage error will be calculated. Questionnaires were distributed to capture the necessary data from 111 student occupants in this hostel of study. It should be noted that about 120 rooms were covered in this hostel. It should be noted that the questionnaires were answered according to perception of the student representative. It should be noted that over 240 CFL bulbs were used in the retrofitting exercise to replace the 36 watt fluorescent tubes in each room. The questionnaire was comprised of compact fluorescent feedback form to access the performance, durability and sustainability of the compact fluorescent tube to ascertain whether this new technology has withstood the test of time or whether the quality control should be reviewed. The questionnaire focused on three area (see attached the sample of the questionnaire)  Understanding consumer knowledge and perception of energy efficiency/CFLS,  the current luminaire information data and finally;  The beneficiary experiences and reactions to the project. 3.2 Energy Audit Data Collection To obtain the energy consumption data, we collected data from question 7 and 13 of the questionnaire, which cover how long the student left the lamp on and the wattage of the lamp respectively. However, for optimum data collection we picked the highest limit of hours spent leaving the lamp on each day, and from investigation we noted that during that switch-over project 14watt bulbs were suppose to have been installed but some had 11watt capacity label. We did take care of the effects of this anomaly by multiplying each cfl power capacity by the total consumed hours each day using excel calculator programme to obtain the total watt hours,we then divided by 1000 to get the kw/hr. We then multiplied by 2 to cover up for the two lamps per room.We then multiplied for the total of the 250 days. This was executed by the use of excel programming, which suited this purpose. 3.2.1 Comparison Data For Energy Audit Simulation for 36 Watt Fluorescent Tube We simulated the energy data collection for the previously used 36 watt bulbs (6,7,8); we used data collated to multiply the duration in which the lamp is left on by 36 watt fluorescent tube to know the amount that was left on for 250 days. 3.2.2 Comparison Data for Energy Audit Simulation for 6O Watt Incandescent Bulb We also simulated for the 60 watt incandescent bulb which is used in house hold compartments,we got the total energy used by multiplying 60 watt by each of the time duration of the bulbs simulated to be left on if also utilized in each room.We then calculated difference by subtracting the total energy utilized by the CFL LAMP from the total energy utilized by the 60 watt incandescent lamp.
  • 3. An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel www.iosrjournals.org 3 | Page 3.2.3 Determination of the Percentage Error Encountered during the Retrofitting Process. It should also be noted that over 120 rooms were retrofitted, but the questionnaire indicated just 111 rooms excluding the three bulbs for the common room and shop. Therefore, we calculated the percentage error resulting from these differences to be ±7.4%. IV. Results/Discussion 4.1 Energy Audit Result We got the total energy utilized by the compact fluorescent tube(2 lamps per room) for two hundred and fifty days .The energy utilized amounted to 14,038KW-Hr.We also simulated the result for the total energy used for the 36 watt bulb. It amounted to 18135 KW-HR. We also simulated for house hold incandescent bulb which amounted to 60,600KWHR. The results generated from the project using the Excel Sheet application showed that 3197kw-hr and 45662kw-hr of power can be saved by retrofitting with 36watt and 60watt bulbs respectively with compact fluorescent tube. 4.2 Cost Audit Result The first and most important finding is the cost that could be saved by CFL retrofitting exercise.We found out that about ₦41,145.39 can be saved by retrofitting the 36 watt fluorescent tube with CFL and about ₦587,669.90 for the 60 watt incandescent house hold simulation can be saved keeping unit cost at ₦12.87 per kw-hr. It should also be noted that over 120 rooms were retrofitted, but the questionnaire indicated just 111 rooms excluding the three bulbs for the common room and shop. This exercise was executed for over 250 days. We can deduce that the application of this cost audit as a result of the energy conserved by the retrofitting exercise, will significantly save more cost and energy that could be utilized to support more businesses for employment generation. We found out that over 81% of the students were aware of energy efficiency and conservation. About 19% were not aware.It indicates the fact that more awareness needs to be created generally in order to inform the populace of energy efficiency, but as we can see, only 19% of the students were novice. From my investigation we noted that over 100% used 14 watts bulb.We also found out from that about 95% of the students are aware of switching off the lamps in the day and making use of natural day light.We matched this result using a pie chart to indicate the percentage of each property of each feedback form.We got the result that over 3% left their lights on from 1-5hrs, 9% left their lights on from 6-10hrs,28% left their lights on from 11-15hrs, about 35% left their lights on from 16-20hrs and finally about 25% left their lights on from 21-24hrs.From the result it shows that just over 12% use natural light and save energy,and about over 55% of the student to practice what they believe in.So emphasis needs to be placed on practicing what we preach as this is reflected that over 95% believe in saving light energy during the day,but about over 55% don’t practice that. Fig 1 pie chart indicates that over 55% do not utilize the natural light energy. This is very disappointing and will not prolong the life span of the CFL lamp. Fig 2 indicates that 95% are aware of the daylight saving energy initiative but do not practice it. We will also represent the percentage of the student that rated the brightness of the CFL LAMP which is very important for readability. This is demonstrated in the pie- chart. We can see a wide number precisely about 87% rated it as good. This indicates the general acceptance of CFL for readability standards and this rating could be marked at 95%. For heat emission we would give the result of the finding of the percentage of student who said YES OR NO that CFL cause heat or not. Fig 4 indicates the general light output is relatively good (over 96 %). We can see infer that CFL LAMPS hardly released heat. This means they have little heat emissions making it conducive for people in tropical regions of the world. It should be noted in design of lighting technology that readability should be put into consideration. From our survey we noted that 84% rated this CFL LAMPS as having good readability standards, the rest of the 16% could have just been skeptical or it was probably due to environmental and internal perception factors. Fig 6 rates the life span of the CFL after duration of 250 days. It was noted that the overall rating was 96% very good life span. This is very encouraging. In design and marketing, we have to take in the remark of the consumer or customer, because the customer is always right. We discovered that over 99% rated the appearance or the physical design of the build as very good. This result indicates it has an excellent appearance.
  • 4. An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel www.iosrjournals.org 4 | Page FIGURES & TABLES fig 1: q7 duration of hours used by bulb fig 2: q4 percentage aware of daylight energy saving
  • 5. An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel www.iosrjournals.org 5 | Page fig 4: q18 rating for the light output fig 5: q19 readability rating fig 6: q20 life span rating
  • 6. An Overview Of Compact Flourescent Lamp Retrofitting In Nigeria: Case Study Of Hostel www.iosrjournals.org 6 | Page fig 7: q21 design appearance rating VI. Conclusion 6.1 Limitation and Future Studies  The intermittent switching on and off of the CFLS could make it less sustainable. However, they are supposed to last for 10 000 hours. They should be left on for a while without being turned on and off frequently for optimum performance.  Not all CFLS can be used with dimmers or regulators. A regular CFL if used with dimmer will burn off quickly. One has to check package before use.  CFL Lamps used outdoors must be protected from weather elements.  They have high sensitivity to temperatures and can cause lower light levels. The lower the temperature, the lower the light level. This indicates it is not readily suitable for high temperate or low temperature regions.  CFLS are not suitable for towered or spot lights, or where narrowed beams of light are required. They are only designed for ambient lighting.  If a CFL is broken or burnt, the mercury is being released, and the presence of mercury makes it hazardous to the environment. It should be noted that if not correctly disposed, it could intoxicate the environment, because mercury is naturally a toxic metal in study of chemistry. More work should be done to create designs for CFL that will be used in spot lights which will help the entertainment industry and could also be used for auditorium or conference hall services. From the result of the energy audit in comparison with the energy that would have been expended by a 36 watt bulb and 60 watt incandescent bulb with the CFL bulbs based on simulation,it can be inferred that CFL could save a significant amount of energy therefore reducing the initial cost.It can also drastically reduce the overall cost spent on energy consumption.It could also be noted that the light output is relatively the same in comparison with the 36 watt bulb and 60 watt in candescent bulb,which gives the same output for lesser amount of energy and cost.It should be noted that the conventional 60 watt incandescent bulb should be phased out and replaced by CFL as they have stood the test of time.More work should be done in increasing the awareness of the energy efficiency initiative at a macroscopic level of the populace in Nigeria and globally considering the economic impact of the current energy demand and limited supply. References [1]. The Bureau Energy Efficiency (BEE);Documentation of best practice.Lighting Energy Efficiency project under Bachat Lamp Y ajonascheme; 2001;3-5 [2]. BolajiF.SuleKajogbola R AlaoHabeeb A AJIMOTOKAN Mohammed K Garba; Compact fluorescent lamps and electricity consumption trend in residential buildings in Ilorin, Nigeria”,International Journal of Energy Sector Management;5(2);2011;162- 168 [3]. United Nations Development Programme. Promoting Energy Efficiency in Residential and Public Sector in Nigeria; http://www.ng.undp.org/energy/EE-project-document.pdf.;2011;41-46 [4]. Lebot,B.;Energy Efficiency and Market Transformation:A short overview of Best Practices.A paper presented during the inception Workshop of the UNDP-GEF Project to promote Energy Efficiency in Residential and public building in Nigeria;2008. [5]. MridulChadha earth industry http://earthandindustry.com/2010/05/india-to-launch-worlds-largest-cdm-project-will-replace-400- million-incandescent-lamps-with-cfls; 2010;1-2 [6]. Thumann A and Younger WJ.Handbook of Energy Audit.Published by the Fairmont Press,Inc.2008 [7]. http://www.energymanagertraining.com/CDM/cdm_main.htm [8]. Furniture.about.com/od/accesoriesguide/0/cfladvant.htm by Ale Abbas