Q&A from Dr John H Klote’s webinar – Design Fires 3 June 2014
1. What is an axisymmetric plume?
John: As the name implies, an axisymmetric plume is an idealized plume that is symmetric about
the axis of the rising plume. It is shaped something like a cone with a round cross-section, and
ideally it has a round fire. The plumes from many other fire shapes behave like an axisymmetric
plume at some distance above the fire. These plumes have been the subject of much research,
and several empirical equations have been developed for axisymmetric plumes.
2. How accurate do you believe the equations are in NFPA 92 for axisymmetric &
balcony smoke plume calculations? Would they be valid for very tall atria, say
greater than 10 storeys?
John: I am using the term “atrium” for this webinar in a generic way to mean any large volume
space such as a multi-story shopping mall, sports arena or airplane hangar. The mass flow
equation for axisymmetric plumes used in NFPA 92 is based on research by Gunnar Heskestad at
Factory Mutual in the US. Another empirical equation was developed by McCaffrey at the National
Institute of Standards and Technology in the U.S. However, much of McCaffrey’s experimental
work was done as a guest worker at BRE in a facility in Cardington, Bedfordshire, that had been
an airship hangar. Because the former airship hangar had a very high ceiling, it may be possible
that McCaffrey’s equation is better for tall spaces than that of Heskestad. However, the difference
between these equations may be academic. As a plume rises, it pulls in air from the surroundings
causing the mass flow of the plume to increase with height and the plume temperature to
decrease with height. All the plume equations are for strongly buoyant plumes. NFPA 92 indicates
that the plume equations are not to be used when the temperature rise of the plume above
ambient is less than 4°F (2.2 °C). Provided that this plume temperature condition is met, the mass
flow equation in NFPA 92 yields appropriate results for smoke control design regardless of atrium
height.
3. When would you say that CFD analysis necessary and zone models/smoke plume
correlations may not be valid?
John: Both the zone fire model approach and the algebraic equation approach can be used for
atrium smoke control analysis, provided the conditions of these approaches are appropriate for the
application. It should be noted that both approaches have assumptions that tend to yield
conservative designs. The conditions fall into two categories of geometry and empirical equations.
The geometry conditions of both approaches are (1) that the atrium ceiling is nearly flat and (2) the
cross-sectional area of the atrium is nearly constant with height. Because different empirical
equations can be used for these approaches, it requires knowledge of the specific empirical
equation to determine if the conditions are appropriate for a particular application.
Either CFD modelling or scale modelling should be used when the conditions of the zone fire
model approach, or the algebraic equation approach, are not appropriate for the application. While
scale modelling is not used much for design analysis, designers should remember that it has the
advantage of being able to model real smoke flow from a real fire in a scaled down version of the
actual atrium.
CFD modelling is capable of more realistic simulations than those of the zone fire model approach
or the algebraic equation approach provided the CFD simulations are properly done. I started
using CFD models over twenty years ago, and I have used the FDS model for atrium smoke
© 2013 Colt International Licensing Ltd.
control analysis extensively. If properly used, CFD modelling often can result in atrium smoke
control systems that are less expensive than those analysed with an approach based on the
conservative assumptions mentioned above.
4. In practice 1m/s is hard to achieve for makeup air. In the UK the limit normally used
is 5m/s and in Australia 2.5m/s. What's the reason for the 1m/s limit in the US?
I was of the impression that the 1m/s requirement is near the fire area. I am having
trouble when I am sizing louvers as make-up air because the selections typically
range from 3m/s to 5m/s.
What is the maximum inlet velocity for make-up air (in louvers for example)
recommended for smoke control applications?
John: The 1 m/s limitation is for the air velocity at all possible fire locations in the atrium. NFPA 92
has a maximum makeup air velocity of about 1 m/s (in NFPA 92 it is stated as 200 fpm or 1.02
m/s) based on concern about disrupting the plume resulting in system failure. This maximum
makeup air velocity has been verified by research at the National Research Council of Canada
that was funded by ASHRAE. There is also a concern about increased fire spread due to airflow.
Airflow causes the flame to bend resulting in increased fire spread and fires possibly larger than
the design fire. ASHRAE is funding another research project at the University of Maryland on
airflow velocity in the region of the flame, and this project is addressing fire spread to some extent.
In fully sprinklered buildings, air velocity is not a concern in one story spaces that open to the
atrium, and these spaces open to the atrium are called communicating spaces. For a makeup air
inlet in a communicating space, the velocity can exceed 1 m/s provided that when the air reached
possible fire locations in the atrium space it decreased to 1 m/s or less.
Paul: 3 very similar questions here I’ll answer together. I can’t comment on the Australian velocity
as I don’t know its basis. The limit in the UK is for the velocity through escape routes. It’s set to
ensure that the incoming air velocity does not exceed 5m/s so that it doesn’t impede escape (even
in a worst case condition when the doors provide the majority of the inlet air and are partially
blocked by people this means the inlet velocity should not exceed 10m/s). It’s generally taken as
the design limit for any inlet ventilators. The limit in the US is for the velocity at the plume. It’s set
to limit the influence of the air flow on the plume as excess velocity could cause the plume to lean
and could cause excess air entrainment. In fact a similar recommendation is included in the British
Standard, BS 7346-4, as well, relating to air flow under the smoke layer.
5. Is there a way to calculate/derive design fire sizes equivalent to each sprinkler
hazard classification e.g. Ordinary Hazard, Extra Hazard, etc?
John: This is an interesting idea that could simplify design fires analysis. For example consider an
ordinary hazard space. A design fire for such a space could be based on a severe successfully
sprinklered fire that could happen in an ordinary hazard space. Such a severe design fire may not
be the absolute worst of all possible fires, but it should be a fire that would only be exceeded in
very unusual circumstances. Possibly the severe design fire would be a shielded fire. Determining
such a fire with confidence might require research. Currently in the US, the design fires are based
on the anticipated fuel (normal and transient) in the space which is determined by an engineering
analysis. The design fire from the anticipated fuel could be less than that based on sprinkler
hazard classification, but this would result in a conservative smoke control design. Of course
design fires based on sprinkler hazard classification would need an exception for atrium (or atrium
like) spaces where the benefit of sprinklers should not be taken into account.
© 2013 Colt International Licensing Ltd.
6. Hello, Thank you for the presentation, my question is do we have like standard of a
typical / common building?
John: There is no standard of a typical or common building. Architects tend to design buildings
that are unique and anything but common. When doing computer studies involving smoke flow, I
have tried to select buildings that have some common characteristics with other buildings. More
than once I have cautioned engineers to be very careful when trying to generalize the results of
such studies because of the wide variety of buildings that exist.
7. Unsprinklered 11m high theatre with transient fuel on stage? As the transient fuel
may be set up differently during each performance, how would you recommend
calculating a design fire?
John: I have done an analysis of design fire on the stage of a theatre, but this analysis should be
much like the design fire analysis for many other spaces. The objects that can burn often are
moved around by the occupants, and there can be a wide range of transient fuels. Typically the
likely fuels are evaluated to determine a severe design fire.
8. How do you determine the HRR for an unsprinklered warehouse?
John: I have not done an analysis of the design fire for an unsprinklered warehouse. If the design
fire is not prescribed in the code, I would start by asking what other engineers have done.
9. How can we calculate unsprinklered steady fires? If they are twice like sprinklered,
then are they 9x9 or 3x3x2?
Paul: In the Smoke Ventilation Association guidance it is the area that is doubled. If a sprinklered
fire is assessed at 3m x 3m, i.e. 9m2
, the unsprinklered design fire would be 18m2
or 4.25m x
4.25m. The HRR per unit area is unchanged so the total HRR also doubles.
10. There is change in the smoke movement when there are sprinklers working (the
smoke cools down and there is drag) that is not taken into account with changing
the HRR. How can it be taken into account?
John: In fire experiments in one story spaces, the sprinkler spray can push some of the smoke
down to the floor. In videos of such fire tests, this can even look like the smoke layer drops to the
floor. In the US, it is considered much better to supress the fire with some smoke near the floor
than not to suppress the fire. When sprinklers activate in an atrium, such smoke mixing may not
happen. Full-scale fire tests with sprinklers conducted at the BHP Laboratory in Australia by
Bennetts in 1997 showed that sprinklered fires in a space open to an atrium can produce buoyant
smoke that flows out of the space and upward to the ceiling of the atrium.
Paul: In the UK this is treated as a local effect and ignored.
11. Is water mist outside of this presentation?
John: Yes.
12. I understand Colt in the UK performs CFD for corridor smoke ventilation...is there a
range of typical published design fires used in this CFD analysis?
Paul: For residential buildings there is a free design guide from the Smoke Control Association
which provides some guidance. The BRE reports on the development of their natural shaft
systems also provide useful design conditions.
© 2013 Colt International Licensing Ltd.
13. In car HRR curves that come from research you often see a long incubation period
before the fire starts growing rapidly. For CFD application of such curve, would you
skip this period of slow burning, as it largely depends on random factors or would
you include it in your CFD calculation? This is a big issue as it will largely influence
Available Safe Evacuation Time calculation.
John: Because nothing relevant to smoke control performance is happening during the slow
burning incubation period, I would not include it in the CFD simulations for smoke control analysis.
However, I would note that this was done in the report of this analysis. If I was calculating the
available safe time for evacuation, I would use a zone fire model like CFAST to calculate sprinkler
activation time. The design fire for the CFAST simulations would include incubation period.
Paul: Personally I’d skip this incubation period in the CFD analysis as it will increase the
calculation time for no great benefit, but I’d include it in any ASET/RSET analysis.
14. Is 6MW recommended for car park car fire?
Paul: In the UK, BS 7346-7 sets recommended steady state car fires. We use a single car 4MW
fire for sprinklered car parks and a two car 8MW fire for unsprinklered car parks. For steady state
design we are ignoring the peak output as this is a very short term transient load for a car.
15. I would like to thank you for this presentation. Furthermore, would you give a
presentation (sometime in the near future) on this same subject, related to smoke
control in car parks?
John: The most recent research involving fires in car parks (called parking garages in the US) that
I am aware of was done at the British Research Establishment (BRE) in the UK by Shipp et al.
published in 2006 and 2010, and there has been much earlier work on this subject. While I could
give a presentation about car parks, I suspect the there are people in the UK who might be more
appropriate.
© 2013 Colt International Licensing Ltd.

More Related Content

Viewers also liked

Piping handbook
Piping handbookPiping handbook
Piping handbookpdmsguy
 
SEWAGE TREATMENT PLANT,LUCKNOW
SEWAGE TREATMENT PLANT,LUCKNOWSEWAGE TREATMENT PLANT,LUCKNOW
SEWAGE TREATMENT PLANT,LUCKNOWGLA University
 
Physical Unit Operations (screens )
Physical Unit Operations (screens )Physical Unit Operations (screens )
Physical Unit Operations (screens )GAURAV. H .TANDON
 
Design criteria for waste water treatment
Design criteria for waste water treatmentDesign criteria for waste water treatment
Design criteria for waste water treatmentBibhabasu Mohanty
 
Sewage treatment plant design calculation
Sewage treatment plant design calculationSewage treatment plant design calculation
Sewage treatment plant design calculationSharifah Ain
 

Viewers also liked (8)

Chapter 12
Chapter 12Chapter 12
Chapter 12
 
Piping handbook
Piping handbookPiping handbook
Piping handbook
 
SEWAGE TREATMENT PLANT,LUCKNOW
SEWAGE TREATMENT PLANT,LUCKNOWSEWAGE TREATMENT PLANT,LUCKNOW
SEWAGE TREATMENT PLANT,LUCKNOW
 
Physical Unit Operations
Physical Unit OperationsPhysical Unit Operations
Physical Unit Operations
 
Physical Unit Operations (screens )
Physical Unit Operations (screens )Physical Unit Operations (screens )
Physical Unit Operations (screens )
 
Design criteria for waste water treatment
Design criteria for waste water treatmentDesign criteria for waste water treatment
Design criteria for waste water treatment
 
Waste Water Treatment
Waste Water TreatmentWaste Water Treatment
Waste Water Treatment
 
Sewage treatment plant design calculation
Sewage treatment plant design calculationSewage treatment plant design calculation
Sewage treatment plant design calculation
 

Similar to Q&A from Dr John H Klotes webinar on design fires for smoke control

model calcul jet fan Flakt Woods.pdf
model calcul jet fan Flakt Woods.pdfmodel calcul jet fan Flakt Woods.pdf
model calcul jet fan Flakt Woods.pdfIonutCatalin8
 
Smoke evacuation in industrial building
Smoke evacuation in industrial buildingSmoke evacuation in industrial building
Smoke evacuation in industrial buildingZuhal Şimşek
 
Fire modeling performance based technical approach
Fire modeling performance based technical approachFire modeling performance based technical approach
Fire modeling performance based technical approachThapa Prakash (TA-1)
 
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...Fire Equipment Manufacturers' Association
 
Understanding Industrial Flame Arrestors
Understanding Industrial Flame ArrestorsUnderstanding Industrial Flame Arrestors
Understanding Industrial Flame ArrestorsArjay Automation
 
Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...
Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...
Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...Sergio A. Guerra
 
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
 Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi... Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...BREEZE Software
 
Smoke and environmental ventilation of multi-storey buildings using shafts we...
Smoke and environmental ventilation of multi-storey buildings using shafts we...Smoke and environmental ventilation of multi-storey buildings using shafts we...
Smoke and environmental ventilation of multi-storey buildings using shafts we...Colt UK
 
Combustible dust
Combustible dust Combustible dust
Combustible dust anfelogo03
 
Optimization of Fire Suppression using Fire Dynamics Simulator
Optimization of Fire Suppression using Fire Dynamics SimulatorOptimization of Fire Suppression using Fire Dynamics Simulator
Optimization of Fire Suppression using Fire Dynamics SimulatorIRJET Journal
 
These allumage ifpen_en
These allumage ifpen_enThese allumage ifpen_en
These allumage ifpen_enCdricMehl
 
2016 T Fire Catalog
2016 T Fire Catalog2016 T Fire Catalog
2016 T Fire CatalogColin Hough
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfMarcGajudo
 
Performance evaluation of lean premixed prevapourised combustion chamber
Performance evaluation of lean premixed prevapourised combustion chamberPerformance evaluation of lean premixed prevapourised combustion chamber
Performance evaluation of lean premixed prevapourised combustion chamberIAEME Publication
 
Leadpresentation98
Leadpresentation98Leadpresentation98
Leadpresentation98DanaDickson
 
Supersonic Mixed-Compression Intake - Paper Ready
Supersonic Mixed-Compression Intake - Paper ReadySupersonic Mixed-Compression Intake - Paper Ready
Supersonic Mixed-Compression Intake - Paper ReadyMuhammad Adnan Hutomo
 

Similar to Q&A from Dr John H Klotes webinar on design fires for smoke control (20)

model calcul jet fan Flakt Woods.pdf
model calcul jet fan Flakt Woods.pdfmodel calcul jet fan Flakt Woods.pdf
model calcul jet fan Flakt Woods.pdf
 
Smoke evacuation in industrial building
Smoke evacuation in industrial buildingSmoke evacuation in industrial building
Smoke evacuation in industrial building
 
Fire modeling performance based technical approach
Fire modeling performance based technical approachFire modeling performance based technical approach
Fire modeling performance based technical approach
 
Garazi
GaraziGarazi
Garazi
 
Flame arrestor
Flame arrestorFlame arrestor
Flame arrestor
 
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed P...
 
Full dissertation
Full dissertationFull dissertation
Full dissertation
 
Understanding Industrial Flame Arrestors
Understanding Industrial Flame ArrestorsUnderstanding Industrial Flame Arrestors
Understanding Industrial Flame Arrestors
 
Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...
Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...
Advanced Modeling Techniques for Permit Modeling - Turning challenges into o...
 
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
 Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi... Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
Performing Safety Modeling Analysis To Comply With LNG Facility Siting Requi...
 
Smoke and environmental ventilation of multi-storey buildings using shafts we...
Smoke and environmental ventilation of multi-storey buildings using shafts we...Smoke and environmental ventilation of multi-storey buildings using shafts we...
Smoke and environmental ventilation of multi-storey buildings using shafts we...
 
Combustible dust
Combustible dust Combustible dust
Combustible dust
 
Optimization of Fire Suppression using Fire Dynamics Simulator
Optimization of Fire Suppression using Fire Dynamics SimulatorOptimization of Fire Suppression using Fire Dynamics Simulator
Optimization of Fire Suppression using Fire Dynamics Simulator
 
These allumage ifpen_en
These allumage ifpen_enThese allumage ifpen_en
These allumage ifpen_en
 
2016 T Fire Catalog
2016 T Fire Catalog2016 T Fire Catalog
2016 T Fire Catalog
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
 
DPCFinalReport
DPCFinalReportDPCFinalReport
DPCFinalReport
 
Performance evaluation of lean premixed prevapourised combustion chamber
Performance evaluation of lean premixed prevapourised combustion chamberPerformance evaluation of lean premixed prevapourised combustion chamber
Performance evaluation of lean premixed prevapourised combustion chamber
 
Leadpresentation98
Leadpresentation98Leadpresentation98
Leadpresentation98
 
Supersonic Mixed-Compression Intake - Paper Ready
Supersonic Mixed-Compression Intake - Paper ReadySupersonic Mixed-Compression Intake - Paper Ready
Supersonic Mixed-Compression Intake - Paper Ready
 

More from Colt UK

Seven good practices for pressurisation systems
Seven good practices for pressurisation systemsSeven good practices for pressurisation systems
Seven good practices for pressurisation systemsColt UK
 
Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Colt UK
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centresColt UK
 
The top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilatorsThe top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilatorsColt UK
 
CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...Colt UK
 
CPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtainsCPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtainsColt UK
 
CPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvresCPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvresColt UK
 
People feel better in colt conditions
People feel better in colt conditions People feel better in colt conditions
People feel better in colt conditions Colt UK
 
CPD Presentation: Pressurisation
CPD Presentation: PressurisationCPD Presentation: Pressurisation
CPD Presentation: PressurisationColt UK
 
CPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsCPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsColt UK
 
CPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationColt UK
 
CPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlCPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlColt UK
 
You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?Colt UK
 
Can your factory be more productive?
Can your factory be more productive?Can your factory be more productive?
Can your factory be more productive?Colt UK
 
Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?Colt UK
 
When is a U value real?
When is a U value real?When is a U value real?
When is a U value real?Colt UK
 
Questions and answers from Paul Compton's pressurisation webinar
Questions and answers from Paul Compton's pressurisation webinar Questions and answers from Paul Compton's pressurisation webinar
Questions and answers from Paul Compton's pressurisation webinar Colt UK
 
The Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocksThe Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocksColt UK
 
Not all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equalNot all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equalColt UK
 
Green micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in HamburgGreen micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in HamburgColt UK
 

More from Colt UK (20)

Seven good practices for pressurisation systems
Seven good practices for pressurisation systemsSeven good practices for pressurisation systems
Seven good practices for pressurisation systems
 
Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centres
 
The top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilatorsThe top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilators
 
CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...
 
CPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtainsCPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtains
 
CPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvresCPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvres
 
People feel better in colt conditions
People feel better in colt conditions People feel better in colt conditions
People feel better in colt conditions
 
CPD Presentation: Pressurisation
CPD Presentation: PressurisationCPD Presentation: Pressurisation
CPD Presentation: Pressurisation
 
CPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsCPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using Shafts
 
CPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park Ventilation
 
CPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlCPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke Control
 
You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?
 
Can your factory be more productive?
Can your factory be more productive?Can your factory be more productive?
Can your factory be more productive?
 
Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?
 
When is a U value real?
When is a U value real?When is a U value real?
When is a U value real?
 
Questions and answers from Paul Compton's pressurisation webinar
Questions and answers from Paul Compton's pressurisation webinar Questions and answers from Paul Compton's pressurisation webinar
Questions and answers from Paul Compton's pressurisation webinar
 
The Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocksThe Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocks
 
Not all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equalNot all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equal
 
Green micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in HamburgGreen micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in Hamburg
 

Recently uploaded

Essential UI/UX Design Principles: A Comprehensive Guide
Essential UI/UX Design Principles: A Comprehensive GuideEssential UI/UX Design Principles: A Comprehensive Guide
Essential UI/UX Design Principles: A Comprehensive GuideDesign Studio UI UX
 
The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024Ilham Brata
 
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...HyderabadDolls
 
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证eeanqy
 
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...nirzagarg
 
Simple Conference Style Presentation by Slidesgo.pptx
Simple Conference Style Presentation by Slidesgo.pptxSimple Conference Style Presentation by Slidesgo.pptx
Simple Conference Style Presentation by Slidesgo.pptxbalqisyamutia
 
一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证
一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证
一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证eqaqen
 
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEKLANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEKMarekMitek1
 
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789CristineGraceAcuyan
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Websitemark11275
 
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime PondicherryPondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherrymeghakumariji156
 
一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样
一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样
一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样awasv46j
 
Furniture & Joinery Details_Designs.pptx
Furniture & Joinery Details_Designs.pptxFurniture & Joinery Details_Designs.pptx
Furniture & Joinery Details_Designs.pptxNikhil Raut
 
How to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdfHow to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdfOffice Furniture Plus - Irving
 
Gamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad IbrahimGamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad Ibrahimamgadibrahim92
 
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service AvailableCall Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service AvailableNitya salvi
 
Minimalist Orange Portfolio by Slidesgo.pptx
Minimalist Orange Portfolio by Slidesgo.pptxMinimalist Orange Portfolio by Slidesgo.pptx
Minimalist Orange Portfolio by Slidesgo.pptxbalqisyamutia
 
Independent Escorts Goregaon WhatsApp +91-9930687706, Best Service
Independent Escorts Goregaon WhatsApp +91-9930687706, Best ServiceIndependent Escorts Goregaon WhatsApp +91-9930687706, Best Service
Independent Escorts Goregaon WhatsApp +91-9930687706, Best Servicemeghakumariji156
 
Q4-W4-SCIENCE-5 power point presentation
Q4-W4-SCIENCE-5 power point presentationQ4-W4-SCIENCE-5 power point presentation
Q4-W4-SCIENCE-5 power point presentationZenSeloveres
 

Recently uploaded (20)

Essential UI/UX Design Principles: A Comprehensive Guide
Essential UI/UX Design Principles: A Comprehensive GuideEssential UI/UX Design Principles: A Comprehensive Guide
Essential UI/UX Design Principles: A Comprehensive Guide
 
The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024The hottest UI and UX Design Trends 2024
The hottest UI and UX Design Trends 2024
 
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
Madhyamgram \ (Genuine) Escort Service Kolkata | Service-oriented sexy call g...
 
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
怎样办理伦敦国王学院毕业证(KCL毕业证书)成绩单留信认证
 
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
Top profile Call Girls In Mau [ 7014168258 ] Call Me For Genuine Models We ar...
 
Simple Conference Style Presentation by Slidesgo.pptx
Simple Conference Style Presentation by Slidesgo.pptxSimple Conference Style Presentation by Slidesgo.pptx
Simple Conference Style Presentation by Slidesgo.pptx
 
一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证
一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证
一比一定(购)西悉尼大学毕业证(WSU毕业证)成绩单学位证
 
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEKLANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
LANDSCAPE ARCHITECTURE PORTFOLIO - MAREK MITACEK
 
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
Q4-Trends-Networks-Module-3.pdfqquater days sheets123456789
 
How to Build a Simple Shopify Website
How to Build a Simple Shopify WebsiteHow to Build a Simple Shopify Website
How to Build a Simple Shopify Website
 
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime PondicherryPondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
Pondicherry Escorts Service Girl ^ 9332606886, WhatsApp Anytime Pondicherry
 
一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样
一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样
一比一原版(WLU毕业证)罗瑞尔大学毕业证成绩单留信学历认证原版一模一样
 
Furniture & Joinery Details_Designs.pptx
Furniture & Joinery Details_Designs.pptxFurniture & Joinery Details_Designs.pptx
Furniture & Joinery Details_Designs.pptx
 
How to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdfHow to Create a Productive Workspace Trends and Tips.pdf
How to Create a Productive Workspace Trends and Tips.pdf
 
Gamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad IbrahimGamestore case study UI UX by Amgad Ibrahim
Gamestore case study UI UX by Amgad Ibrahim
 
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service AvailableCall Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
Call Girls Jalaun Just Call 8617370543 Top Class Call Girl Service Available
 
Minimalist Orange Portfolio by Slidesgo.pptx
Minimalist Orange Portfolio by Slidesgo.pptxMinimalist Orange Portfolio by Slidesgo.pptx
Minimalist Orange Portfolio by Slidesgo.pptx
 
Independent Escorts Goregaon WhatsApp +91-9930687706, Best Service
Independent Escorts Goregaon WhatsApp +91-9930687706, Best ServiceIndependent Escorts Goregaon WhatsApp +91-9930687706, Best Service
Independent Escorts Goregaon WhatsApp +91-9930687706, Best Service
 
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman MuscatAbortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
Abortion Pills in Oman (+918133066128) Cytotec clinic buy Oman Muscat
 
Q4-W4-SCIENCE-5 power point presentation
Q4-W4-SCIENCE-5 power point presentationQ4-W4-SCIENCE-5 power point presentation
Q4-W4-SCIENCE-5 power point presentation
 

Q&A from Dr John H Klotes webinar on design fires for smoke control

  • 1. Q&A from Dr John H Klote’s webinar – Design Fires 3 June 2014 1. What is an axisymmetric plume? John: As the name implies, an axisymmetric plume is an idealized plume that is symmetric about the axis of the rising plume. It is shaped something like a cone with a round cross-section, and ideally it has a round fire. The plumes from many other fire shapes behave like an axisymmetric plume at some distance above the fire. These plumes have been the subject of much research, and several empirical equations have been developed for axisymmetric plumes. 2. How accurate do you believe the equations are in NFPA 92 for axisymmetric & balcony smoke plume calculations? Would they be valid for very tall atria, say greater than 10 storeys? John: I am using the term “atrium” for this webinar in a generic way to mean any large volume space such as a multi-story shopping mall, sports arena or airplane hangar. The mass flow equation for axisymmetric plumes used in NFPA 92 is based on research by Gunnar Heskestad at Factory Mutual in the US. Another empirical equation was developed by McCaffrey at the National Institute of Standards and Technology in the U.S. However, much of McCaffrey’s experimental work was done as a guest worker at BRE in a facility in Cardington, Bedfordshire, that had been an airship hangar. Because the former airship hangar had a very high ceiling, it may be possible that McCaffrey’s equation is better for tall spaces than that of Heskestad. However, the difference between these equations may be academic. As a plume rises, it pulls in air from the surroundings causing the mass flow of the plume to increase with height and the plume temperature to decrease with height. All the plume equations are for strongly buoyant plumes. NFPA 92 indicates that the plume equations are not to be used when the temperature rise of the plume above ambient is less than 4°F (2.2 °C). Provided that this plume temperature condition is met, the mass flow equation in NFPA 92 yields appropriate results for smoke control design regardless of atrium height. 3. When would you say that CFD analysis necessary and zone models/smoke plume correlations may not be valid? John: Both the zone fire model approach and the algebraic equation approach can be used for atrium smoke control analysis, provided the conditions of these approaches are appropriate for the application. It should be noted that both approaches have assumptions that tend to yield conservative designs. The conditions fall into two categories of geometry and empirical equations. The geometry conditions of both approaches are (1) that the atrium ceiling is nearly flat and (2) the cross-sectional area of the atrium is nearly constant with height. Because different empirical equations can be used for these approaches, it requires knowledge of the specific empirical equation to determine if the conditions are appropriate for a particular application. Either CFD modelling or scale modelling should be used when the conditions of the zone fire model approach, or the algebraic equation approach, are not appropriate for the application. While scale modelling is not used much for design analysis, designers should remember that it has the advantage of being able to model real smoke flow from a real fire in a scaled down version of the actual atrium. CFD modelling is capable of more realistic simulations than those of the zone fire model approach or the algebraic equation approach provided the CFD simulations are properly done. I started using CFD models over twenty years ago, and I have used the FDS model for atrium smoke © 2013 Colt International Licensing Ltd.
  • 2. control analysis extensively. If properly used, CFD modelling often can result in atrium smoke control systems that are less expensive than those analysed with an approach based on the conservative assumptions mentioned above. 4. In practice 1m/s is hard to achieve for makeup air. In the UK the limit normally used is 5m/s and in Australia 2.5m/s. What's the reason for the 1m/s limit in the US? I was of the impression that the 1m/s requirement is near the fire area. I am having trouble when I am sizing louvers as make-up air because the selections typically range from 3m/s to 5m/s. What is the maximum inlet velocity for make-up air (in louvers for example) recommended for smoke control applications? John: The 1 m/s limitation is for the air velocity at all possible fire locations in the atrium. NFPA 92 has a maximum makeup air velocity of about 1 m/s (in NFPA 92 it is stated as 200 fpm or 1.02 m/s) based on concern about disrupting the plume resulting in system failure. This maximum makeup air velocity has been verified by research at the National Research Council of Canada that was funded by ASHRAE. There is also a concern about increased fire spread due to airflow. Airflow causes the flame to bend resulting in increased fire spread and fires possibly larger than the design fire. ASHRAE is funding another research project at the University of Maryland on airflow velocity in the region of the flame, and this project is addressing fire spread to some extent. In fully sprinklered buildings, air velocity is not a concern in one story spaces that open to the atrium, and these spaces open to the atrium are called communicating spaces. For a makeup air inlet in a communicating space, the velocity can exceed 1 m/s provided that when the air reached possible fire locations in the atrium space it decreased to 1 m/s or less. Paul: 3 very similar questions here I’ll answer together. I can’t comment on the Australian velocity as I don’t know its basis. The limit in the UK is for the velocity through escape routes. It’s set to ensure that the incoming air velocity does not exceed 5m/s so that it doesn’t impede escape (even in a worst case condition when the doors provide the majority of the inlet air and are partially blocked by people this means the inlet velocity should not exceed 10m/s). It’s generally taken as the design limit for any inlet ventilators. The limit in the US is for the velocity at the plume. It’s set to limit the influence of the air flow on the plume as excess velocity could cause the plume to lean and could cause excess air entrainment. In fact a similar recommendation is included in the British Standard, BS 7346-4, as well, relating to air flow under the smoke layer. 5. Is there a way to calculate/derive design fire sizes equivalent to each sprinkler hazard classification e.g. Ordinary Hazard, Extra Hazard, etc? John: This is an interesting idea that could simplify design fires analysis. For example consider an ordinary hazard space. A design fire for such a space could be based on a severe successfully sprinklered fire that could happen in an ordinary hazard space. Such a severe design fire may not be the absolute worst of all possible fires, but it should be a fire that would only be exceeded in very unusual circumstances. Possibly the severe design fire would be a shielded fire. Determining such a fire with confidence might require research. Currently in the US, the design fires are based on the anticipated fuel (normal and transient) in the space which is determined by an engineering analysis. The design fire from the anticipated fuel could be less than that based on sprinkler hazard classification, but this would result in a conservative smoke control design. Of course design fires based on sprinkler hazard classification would need an exception for atrium (or atrium like) spaces where the benefit of sprinklers should not be taken into account. © 2013 Colt International Licensing Ltd.
  • 3. 6. Hello, Thank you for the presentation, my question is do we have like standard of a typical / common building? John: There is no standard of a typical or common building. Architects tend to design buildings that are unique and anything but common. When doing computer studies involving smoke flow, I have tried to select buildings that have some common characteristics with other buildings. More than once I have cautioned engineers to be very careful when trying to generalize the results of such studies because of the wide variety of buildings that exist. 7. Unsprinklered 11m high theatre with transient fuel on stage? As the transient fuel may be set up differently during each performance, how would you recommend calculating a design fire? John: I have done an analysis of design fire on the stage of a theatre, but this analysis should be much like the design fire analysis for many other spaces. The objects that can burn often are moved around by the occupants, and there can be a wide range of transient fuels. Typically the likely fuels are evaluated to determine a severe design fire. 8. How do you determine the HRR for an unsprinklered warehouse? John: I have not done an analysis of the design fire for an unsprinklered warehouse. If the design fire is not prescribed in the code, I would start by asking what other engineers have done. 9. How can we calculate unsprinklered steady fires? If they are twice like sprinklered, then are they 9x9 or 3x3x2? Paul: In the Smoke Ventilation Association guidance it is the area that is doubled. If a sprinklered fire is assessed at 3m x 3m, i.e. 9m2 , the unsprinklered design fire would be 18m2 or 4.25m x 4.25m. The HRR per unit area is unchanged so the total HRR also doubles. 10. There is change in the smoke movement when there are sprinklers working (the smoke cools down and there is drag) that is not taken into account with changing the HRR. How can it be taken into account? John: In fire experiments in one story spaces, the sprinkler spray can push some of the smoke down to the floor. In videos of such fire tests, this can even look like the smoke layer drops to the floor. In the US, it is considered much better to supress the fire with some smoke near the floor than not to suppress the fire. When sprinklers activate in an atrium, such smoke mixing may not happen. Full-scale fire tests with sprinklers conducted at the BHP Laboratory in Australia by Bennetts in 1997 showed that sprinklered fires in a space open to an atrium can produce buoyant smoke that flows out of the space and upward to the ceiling of the atrium. Paul: In the UK this is treated as a local effect and ignored. 11. Is water mist outside of this presentation? John: Yes. 12. I understand Colt in the UK performs CFD for corridor smoke ventilation...is there a range of typical published design fires used in this CFD analysis? Paul: For residential buildings there is a free design guide from the Smoke Control Association which provides some guidance. The BRE reports on the development of their natural shaft systems also provide useful design conditions. © 2013 Colt International Licensing Ltd.
  • 4. 13. In car HRR curves that come from research you often see a long incubation period before the fire starts growing rapidly. For CFD application of such curve, would you skip this period of slow burning, as it largely depends on random factors or would you include it in your CFD calculation? This is a big issue as it will largely influence Available Safe Evacuation Time calculation. John: Because nothing relevant to smoke control performance is happening during the slow burning incubation period, I would not include it in the CFD simulations for smoke control analysis. However, I would note that this was done in the report of this analysis. If I was calculating the available safe time for evacuation, I would use a zone fire model like CFAST to calculate sprinkler activation time. The design fire for the CFAST simulations would include incubation period. Paul: Personally I’d skip this incubation period in the CFD analysis as it will increase the calculation time for no great benefit, but I’d include it in any ASET/RSET analysis. 14. Is 6MW recommended for car park car fire? Paul: In the UK, BS 7346-7 sets recommended steady state car fires. We use a single car 4MW fire for sprinklered car parks and a two car 8MW fire for unsprinklered car parks. For steady state design we are ignoring the peak output as this is a very short term transient load for a car. 15. I would like to thank you for this presentation. Furthermore, would you give a presentation (sometime in the near future) on this same subject, related to smoke control in car parks? John: The most recent research involving fires in car parks (called parking garages in the US) that I am aware of was done at the British Research Establishment (BRE) in the UK by Shipp et al. published in 2006 and 2010, and there has been much earlier work on this subject. While I could give a presentation about car parks, I suspect the there are people in the UK who might be more appropriate. © 2013 Colt International Licensing Ltd.