Questions and answers from Paul Compton's pressurisation
webinar
First of all a big thank you to those who attended my webinar last Friday on 'Pressurisation Systems in
residential and commercial buildings'. If you missed it or would like to watch it again a recorded
version is available here. Many questions were asked after the presentation and I decided to post the
most interesting ones up here for everybody’s benefit.
Could a "pressure relief damper" or "air release" be fitted to an external window/fixed pane of
glass at the end of a corridor?
The pressure relief damper, if we are talking about pressure relief in a pressurised space, is normally
fitted in the stair, not the corridor, because the stair is where we are wanting to relieve pressure. When
we talk about the accommodation air release, then if the corridor is not pressurised, then yes, the air
release can replace an external window. Obviously it needs to be fully automatically opening, so it
would need to be a window with a motorised actuator, or it would need to be a specific ventilator, but
yes this can be done.
We’ve come across projects without ductwork with the air going straight into the stair - any
issues there?
In a small building that is fine. If you have only got a building which is 11m or less, then one inlet to the
stair (so effectively no ductwork) is perfectly permissible. If you’ve got a building which is taller than
that, then it comes down to whether you can make it work and achieve pressure differences between
the maximum and the minimum, i.e. between 55 and 45 Pa, between the top and at the bottom of the
stair. If you can achieve that, then this would normally be acceptable.
Obviously the requirement to have a grille every three storeys as set out in the standard is intended to
be conservative and safe. So, if you choose to put all the air in at the top, then that will normally be
accepted if you can achieve the pressures that you need to.
Is there a minimum amount of sample rooms need pressure testing, or do all rooms require
testing?
Normally if we have a very tall building that has a lot of similar storeys, then we wouldn’t necessarily
test every one of them. We would normally agree with client/building control, whoever is interested,
that we would do an initial test on a proportion of those rooms, perhaps four or five of them, on four or
five levels, and if the results on those are all satisfactory, then we would assume that the others are
probably ok as well. If those results aren’t satisfactory, then we would have to go through and test
every storey.
What is the process for deciding if we need a pressurisation system in the first place?
© 2013 Colt International Licensing Ltd.
There is a requirement in the Building Regulations that you need ventilation to residential escape
stairs and to commercial building fire fighting stairs. Whether you need pressurisation is basically
entirely up to you unless there is a very specific requirement for pressurisation in BS9999 or BS5588
Part 5, and that generally is for tall buildings for deep basements or for if you are putting a system in,
in order to avoid discounting the stairs.
If you do not have one of those conditions, then it is your choice whether you use pressurisation, or a
shaft system or an AOV system, and generally if there is no pressing requirement for you to use
pressurisation, then I tend to suggest that you use one of the other approaches if you can, simply
because they are cheaper. The other reason that you may need to use pressurisation is that it may be
a requirement from Building Control or the Fire Service where the building itself is not Building
Regulations compliant and therefore Building Control have asked for a pressurisation system as a
compensating factor.
Can you now tell us about the doors that are kept open when you are doing the testing?
Where you are doing a stairwell pressurisation system to Class A, B, C, D or E then you have to keep
the doors open in accordance with the standard, so if you know the class then the standard will tell you
which doors have to be open for that particular system. If you are doing pressurisation or de-
pressurisation of other spaces then the standard doesn’t very specifically tell you which doors need to
be open, that’s a design decision. But, for Class A to Class E systems, you simply follow the standard
to decide which doors are going to be open.
How are EN requirements different than NFPA/IBC requirements?
Here we are talking about the difference between the European standards and the American NFPA
standards. Basically there are an awful lot of detailed differences but the main difference is that under
the American NFPA standard, there is no velocity requirement in a door open condition. Instead the
standard requires you to maintain the pressure, even with doors open. So it requires the designer to
make a decision as to how many doors are going to be open, and then ensure that they can maintain
the pressure within the stair, even with all of those doors open. That tends to require a higher airflow
rate particularly if you have decided you are going to have a lot of doors open.
The other difference is that in the EN standard we have a fixed pressure requirement of 50 pascals; in
the NFPA standard the pressure differential required varies depending upon the height of the rooms
and is generally a little bit lower that the EN. So if you are designing to NFPA you will have a very
different system to if you design to the European standard.
We regularly design buildings with mechanical ventilation but use depressurisation as
opposed to positive pressurisation. Are there many instances where you would see a benefit of
using positive pressurisation over depressurisation?
So I presume there we are talking about mechanical shaft systems which, although they are not
generally classed as depressurisation systems to EN12101, do have the effect of depressurising the
corridor. Those systems generally are used because they are less complex and less expensive than a
pressurisation system.
The pressurisation system will generally give slightly better conditions within a building than a
mechanical shaft depressurisation type system, so yes there is a benefit but of course, under the
regulations, unless you have these particular times when pressurisation is absolutely required, nobody
really wants to pay for the additional benefit of a pressurisation system. So people would tend to use
these mechanical shaft systems simply because they are cheaper and because they meet the
regulations.
© 2013 Colt International Licensing Ltd.
Can one fit a pressure relief damper on a window in a stair?
The pressure relief damper can replace a window, certainly. If you look at a pressure relief damper it’s
a louvred damper assembly, its not normally weather proof on its own, so if you are going to replace a
window with it, normally you would have the damper and then you would put some kind of weather
proofing ventilator behind it, but certainly you can replace a window although you wouldn’t actually use
the window.
What effect would the fitting of smoke seals have on doors in the lobby/corridor?
Generally when we have a pressurisation system we wouldn’t fit smoke seals to the doors between
the various pressurised spaces or between the pressurised space and the accommodation. The
reason for that is basically that a bit of leakage there is generally beneficial in that it limits or minimises
the size of the pressure relief damper that we need or the variation that we are going to need on an
inverter system. So no we wouldn’t normally fit smoke seals on any of the doors within the pressurised
spaces.
Is the noise of a system a problem in relation to a voice comms system say from a disabled
persons refuge?
The answer to that is, yes it can be. If you have that sort of situation, then normally there will be a
noise spec or a volume spec for the voice comms system, and from that you will be able to set a
maximum noise level within the stair. Once you have that maximum noise level required within the
stair then its quite possible to calculate the noise level from the fan system and fit an attenuator if
required. On smaller systems it’s not normally a problem, but as the systems get bigger and noisier
then yes it can be a problem, particularly on the upper storeys close to the fan system.
.
© 2013 Colt International Licensing Ltd.

More Related Content

Similar to Questions and answers from Paul Compton's pressurisation webinar

S3 Supply Air Duct System Assignment
S3 Supply Air Duct System AssignmentS3 Supply Air Duct System Assignment
S3 Supply Air Duct System Assignmentno suhaila
 
Sizing vent n exhaust fans
Sizing vent n exhaust fansSizing vent n exhaust fans
Sizing vent n exhaust fansKim Pham
 
Energy efficientventilationsystembs
Energy efficientventilationsystembsEnergy efficientventilationsystembs
Energy efficientventilationsystembslohwenjun
 
LECTURE 6 ZONING IN HVAC.ppt
LECTURE  6 ZONING IN HVAC.pptLECTURE  6 ZONING IN HVAC.ppt
LECTURE 6 ZONING IN HVAC.pptBhaskarBhatia2
 
Introduction to Distillation Troubleshooting
Introduction to Distillation TroubleshootingIntroduction to Distillation Troubleshooting
Introduction to Distillation TroubleshootingKarl Kolmetz
 
Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...
Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...
Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...Gold Coast Air-Care Group
 
Working with vacuum piping
Working with vacuum pipingWorking with vacuum piping
Working with vacuum pipingiammikebrown6
 
CPD Presentation: Pressurisation
CPD Presentation: PressurisationCPD Presentation: Pressurisation
CPD Presentation: PressurisationColt UK
 
Propylene C3 Splitter Tower Efficiency
Propylene C3 Splitter Tower EfficiencyPropylene C3 Splitter Tower Efficiency
Propylene C3 Splitter Tower EfficiencyKarl Kolmetz
 
Whitepaper Home defects that impact energy bills
Whitepaper Home defects that impact energy billsWhitepaper Home defects that impact energy bills
Whitepaper Home defects that impact energy billsedreeve
 
Guidelines for controlling pressurazation nov. 2005
Guidelines for controlling pressurazation   nov. 2005Guidelines for controlling pressurazation   nov. 2005
Guidelines for controlling pressurazation nov. 2005Watashi Wa Arshavin
 
Syntec Company Profile
Syntec Company ProfileSyntec Company Profile
Syntec Company ProfileAJAY MANGLA
 
Ultimate operator safety with pressure decay testing
Ultimate operator safety with pressure decay testingUltimate operator safety with pressure decay testing
Ultimate operator safety with pressure decay testingSolo Containment
 
Kiddie smoke detector 0916 manual
Kiddie smoke detector 0916 manualKiddie smoke detector 0916 manual
Kiddie smoke detector 0916 manualToy Hut
 
Kidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 b
Kidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 bKidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 b
Kidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 bToy Hut
 
A facilities managers guide to achieving adaptive thermal comfort for occupants
A facilities managers guide to achieving adaptive thermal comfort for occupantsA facilities managers guide to achieving adaptive thermal comfort for occupants
A facilities managers guide to achieving adaptive thermal comfort for occupants21 Handshake
 

Similar to Questions and answers from Paul Compton's pressurisation webinar (20)

S3 Supply Air Duct System Assignment
S3 Supply Air Duct System AssignmentS3 Supply Air Duct System Assignment
S3 Supply Air Duct System Assignment
 
Sizing vent n exhaust fans
Sizing vent n exhaust fansSizing vent n exhaust fans
Sizing vent n exhaust fans
 
Energy efficientventilationsystembs
Energy efficientventilationsystembsEnergy efficientventilationsystembs
Energy efficientventilationsystembs
 
LECTURE 6 ZONING IN HVAC.ppt
LECTURE  6 ZONING IN HVAC.pptLECTURE  6 ZONING IN HVAC.ppt
LECTURE 6 ZONING IN HVAC.ppt
 
Introduction to Distillation Troubleshooting
Introduction to Distillation TroubleshootingIntroduction to Distillation Troubleshooting
Introduction to Distillation Troubleshooting
 
Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...
Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...
Advantages & Disadvantages of Ducted and Split System Air Conditioners - Air ...
 
Air Duct Leakage
Air Duct LeakageAir Duct Leakage
Air Duct Leakage
 
Working with vacuum piping
Working with vacuum pipingWorking with vacuum piping
Working with vacuum piping
 
CPD Presentation: Pressurisation
CPD Presentation: PressurisationCPD Presentation: Pressurisation
CPD Presentation: Pressurisation
 
Propylene C3 Splitter Tower Efficiency
Propylene C3 Splitter Tower EfficiencyPropylene C3 Splitter Tower Efficiency
Propylene C3 Splitter Tower Efficiency
 
Whitepaper Home defects that impact energy bills
Whitepaper Home defects that impact energy billsWhitepaper Home defects that impact energy bills
Whitepaper Home defects that impact energy bills
 
Guidelines for controlling pressurazation nov. 2005
Guidelines for controlling pressurazation   nov. 2005Guidelines for controlling pressurazation   nov. 2005
Guidelines for controlling pressurazation nov. 2005
 
Cleanrooms 101
Cleanrooms 101Cleanrooms 101
Cleanrooms 101
 
Syntec Company Profile
Syntec Company ProfileSyntec Company Profile
Syntec Company Profile
 
Ultimate operator safety with pressure decay testing
Ultimate operator safety with pressure decay testingUltimate operator safety with pressure decay testing
Ultimate operator safety with pressure decay testing
 
Kiddie smoke detector 0916 manual
Kiddie smoke detector 0916 manualKiddie smoke detector 0916 manual
Kiddie smoke detector 0916 manual
 
Kidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 b
Kidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 bKidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 b
Kidde smoke alarm 0916,44037502,21006655 english,spanish 8200898 b
 
A facilities managers guide to achieving adaptive thermal comfort for occupants
A facilities managers guide to achieving adaptive thermal comfort for occupantsA facilities managers guide to achieving adaptive thermal comfort for occupants
A facilities managers guide to achieving adaptive thermal comfort for occupants
 
3071irr.pdf
3071irr.pdf3071irr.pdf
3071irr.pdf
 
urr.pdf
urr.pdfurr.pdf
urr.pdf
 

More from Colt UK

Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Colt UK
 
Q&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke controlQ&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke controlColt UK
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centresColt UK
 
The top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilatorsThe top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilatorsColt UK
 
CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...Colt UK
 
CPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtainsCPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtainsColt UK
 
CPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvresCPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvresColt UK
 
People feel better in colt conditions
People feel better in colt conditions People feel better in colt conditions
People feel better in colt conditions Colt UK
 
CPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsCPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsColt UK
 
CPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationColt UK
 
CPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlCPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlColt UK
 
You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?Colt UK
 
Can your factory be more productive?
Can your factory be more productive?Can your factory be more productive?
Can your factory be more productive?Colt UK
 
Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?Colt UK
 
When is a U value real?
When is a U value real?When is a U value real?
When is a U value real?Colt UK
 
The Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocksThe Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocksColt UK
 
Not all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equalNot all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equalColt UK
 
Green micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in HamburgGreen micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in HamburgColt UK
 
The CPR and mandatory CE marking: what is changing and what will it mean for you
The CPR and mandatory CE marking: what is changing and what will it mean for youThe CPR and mandatory CE marking: what is changing and what will it mean for you
The CPR and mandatory CE marking: what is changing and what will it mean for youColt UK
 
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilationColt UK
 

More from Colt UK (20)

Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...
 
Q&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke controlQ&A from Dr John H Klotes webinar on design fires for smoke control
Q&A from Dr John H Klotes webinar on design fires for smoke control
 
CPD Presentation Evaporative cooling in data centres
CPD Presentation   Evaporative cooling in data centresCPD Presentation   Evaporative cooling in data centres
CPD Presentation Evaporative cooling in data centres
 
The top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilatorsThe top three considerations when specifying glass louvred ventilators
The top three considerations when specifying glass louvred ventilators
 
CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...CPD Presentation - Smoke control and environmental ventilation in residential...
CPD Presentation - Smoke control and environmental ventilation in residential...
 
CPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtainsCPD Presentation: Smoke curtains and fire curtains
CPD Presentation: Smoke curtains and fire curtains
 
CPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvresCPD Presentation: Key considerations when specifying weather louvres
CPD Presentation: Key considerations when specifying weather louvres
 
People feel better in colt conditions
People feel better in colt conditions People feel better in colt conditions
People feel better in colt conditions
 
CPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using ShaftsCPD Presentation: Smoke Ventilation using Shafts
CPD Presentation: Smoke Ventilation using Shafts
 
CPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park Ventilation
 
CPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke ControlCPD Presentation: General Principles of Smoke Control
CPD Presentation: General Principles of Smoke Control
 
You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?You want to improve your factory’s productivity: what’s next?
You want to improve your factory’s productivity: what’s next?
 
Can your factory be more productive?
Can your factory be more productive?Can your factory be more productive?
Can your factory be more productive?
 
Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?Are you sure your natural ventilation system is really energy efficient?
Are you sure your natural ventilation system is really energy efficient?
 
When is a U value real?
When is a U value real?When is a U value real?
When is a U value real?
 
The Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocksThe Lakanal House inquest and Local Authority tower blocks
The Lakanal House inquest and Local Authority tower blocks
 
Not all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equalNot all “Class A” weather louvres are equal
Not all “Class A” weather louvres are equal
 
Green micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in HamburgGreen micro-algae façade becomes reality in Hamburg
Green micro-algae façade becomes reality in Hamburg
 
The CPR and mandatory CE marking: what is changing and what will it mean for you
The CPR and mandatory CE marking: what is changing and what will it mean for youThe CPR and mandatory CE marking: what is changing and what will it mean for you
The CPR and mandatory CE marking: what is changing and what will it mean for you
 
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
5 reasons why it’s wrong to use HVAC control systems for smoke ventilation
 

Recently uploaded

Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝soniya singh
 
shot list for my tv series two steps back
shot list for my tv series two steps backshot list for my tv series two steps back
shot list for my tv series two steps back17lcow074
 
Architecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdfArchitecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdfSumit Lathwal
 
ARt app | UX Case Study
ARt app | UX Case StudyARt app | UX Case Study
ARt app | UX Case StudySophia Viganò
 
Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025Rndexperts
 
Call Girls Meghani Nagar 7397865700 Independent Call Girls
Call Girls Meghani Nagar 7397865700  Independent Call GirlsCall Girls Meghani Nagar 7397865700  Independent Call Girls
Call Girls Meghani Nagar 7397865700 Independent Call Girlsssuser7cb4ff
 
Revit Understanding Reference Planes and Reference lines in Revit for Family ...
Revit Understanding Reference Planes and Reference lines in Revit for Family ...Revit Understanding Reference Planes and Reference lines in Revit for Family ...
Revit Understanding Reference Planes and Reference lines in Revit for Family ...Narsimha murthy
 
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)jennyeacort
 
定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一
定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一
定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一lvtagr7
 
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一A SSS
 
Introduction-to-Canva-and-Graphic-Design-Basics.pptx
Introduction-to-Canva-and-Graphic-Design-Basics.pptxIntroduction-to-Canva-and-Graphic-Design-Basics.pptx
Introduction-to-Canva-and-Graphic-Design-Basics.pptxnewslab143
 
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts ServiceCall Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Servicejennyeacort
 
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一diploma 1
 
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一F dds
 
How to Be Famous in your Field just visit our Site
How to Be Famous in your Field just visit our SiteHow to Be Famous in your Field just visit our Site
How to Be Famous in your Field just visit our Sitegalleryaagency
 
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024CristobalHeraud
 
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`dajasot375
 
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCRCall In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCRdollysharma2066
 

Recently uploaded (20)

Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝
Call Girls in Okhla Delhi 💯Call Us 🔝8264348440🔝
 
shot list for my tv series two steps back
shot list for my tv series two steps backshot list for my tv series two steps back
shot list for my tv series two steps back
 
Architecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdfArchitecture case study India Habitat Centre, Delhi.pdf
Architecture case study India Habitat Centre, Delhi.pdf
 
ARt app | UX Case Study
ARt app | UX Case StudyARt app | UX Case Study
ARt app | UX Case Study
 
Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025Top 10 Modern Web Design Trends for 2025
Top 10 Modern Web Design Trends for 2025
 
Call Girls Meghani Nagar 7397865700 Independent Call Girls
Call Girls Meghani Nagar 7397865700  Independent Call GirlsCall Girls Meghani Nagar 7397865700  Independent Call Girls
Call Girls Meghani Nagar 7397865700 Independent Call Girls
 
Revit Understanding Reference Planes and Reference lines in Revit for Family ...
Revit Understanding Reference Planes and Reference lines in Revit for Family ...Revit Understanding Reference Planes and Reference lines in Revit for Family ...
Revit Understanding Reference Planes and Reference lines in Revit for Family ...
 
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
call girls in Harsh Vihar (DELHI) 🔝 >༒9953330565🔝 genuine Escort Service 🔝✔️✔️
 
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
Call Us ✡️97111⇛47426⇛Call In girls Vasant Vihar༒(Delhi)
 
定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一
定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一
定制(RMIT毕业证书)澳洲墨尔本皇家理工大学毕业证成绩单原版一比一
 
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
办理学位证(NTU证书)新加坡南洋理工大学毕业证成绩单原版一比一
 
Introduction-to-Canva-and-Graphic-Design-Basics.pptx
Introduction-to-Canva-and-Graphic-Design-Basics.pptxIntroduction-to-Canva-and-Graphic-Design-Basics.pptx
Introduction-to-Canva-and-Graphic-Design-Basics.pptx
 
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts ServiceCall Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
Call Girls In Safdarjung Enclave 24/7✡️9711147426✡️ Escorts Service
 
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
办理(USYD毕业证书)澳洲悉尼大学毕业证成绩单原版一比一
 
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
办理学位证(SFU证书)西蒙菲莎大学毕业证成绩单原版一比一
 
How to Be Famous in your Field just visit our Site
How to Be Famous in your Field just visit our SiteHow to Be Famous in your Field just visit our Site
How to Be Famous in your Field just visit our Site
 
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
PORTFOLIO DE ARQUITECTURA CRISTOBAL HERAUD 2024
 
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 night
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 nightCheap Rate Call girls Kalkaji 9205541914 shot 1500 night
Cheap Rate Call girls Kalkaji 9205541914 shot 1500 night
 
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
Abu Dhabi Call Girls O58993O4O2 Call Girls in Abu Dhabi`
 
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCRCall In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
Call In girls Bhikaji Cama Place 🔝 ⇛8377877756 FULL Enjoy Delhi NCR
 

Questions and answers from Paul Compton's pressurisation webinar

  • 1. Questions and answers from Paul Compton's pressurisation webinar First of all a big thank you to those who attended my webinar last Friday on 'Pressurisation Systems in residential and commercial buildings'. If you missed it or would like to watch it again a recorded version is available here. Many questions were asked after the presentation and I decided to post the most interesting ones up here for everybody’s benefit. Could a "pressure relief damper" or "air release" be fitted to an external window/fixed pane of glass at the end of a corridor? The pressure relief damper, if we are talking about pressure relief in a pressurised space, is normally fitted in the stair, not the corridor, because the stair is where we are wanting to relieve pressure. When we talk about the accommodation air release, then if the corridor is not pressurised, then yes, the air release can replace an external window. Obviously it needs to be fully automatically opening, so it would need to be a window with a motorised actuator, or it would need to be a specific ventilator, but yes this can be done. We’ve come across projects without ductwork with the air going straight into the stair - any issues there? In a small building that is fine. If you have only got a building which is 11m or less, then one inlet to the stair (so effectively no ductwork) is perfectly permissible. If you’ve got a building which is taller than that, then it comes down to whether you can make it work and achieve pressure differences between the maximum and the minimum, i.e. between 55 and 45 Pa, between the top and at the bottom of the stair. If you can achieve that, then this would normally be acceptable. Obviously the requirement to have a grille every three storeys as set out in the standard is intended to be conservative and safe. So, if you choose to put all the air in at the top, then that will normally be accepted if you can achieve the pressures that you need to. Is there a minimum amount of sample rooms need pressure testing, or do all rooms require testing? Normally if we have a very tall building that has a lot of similar storeys, then we wouldn’t necessarily test every one of them. We would normally agree with client/building control, whoever is interested, that we would do an initial test on a proportion of those rooms, perhaps four or five of them, on four or five levels, and if the results on those are all satisfactory, then we would assume that the others are probably ok as well. If those results aren’t satisfactory, then we would have to go through and test every storey. What is the process for deciding if we need a pressurisation system in the first place? © 2013 Colt International Licensing Ltd.
  • 2. There is a requirement in the Building Regulations that you need ventilation to residential escape stairs and to commercial building fire fighting stairs. Whether you need pressurisation is basically entirely up to you unless there is a very specific requirement for pressurisation in BS9999 or BS5588 Part 5, and that generally is for tall buildings for deep basements or for if you are putting a system in, in order to avoid discounting the stairs. If you do not have one of those conditions, then it is your choice whether you use pressurisation, or a shaft system or an AOV system, and generally if there is no pressing requirement for you to use pressurisation, then I tend to suggest that you use one of the other approaches if you can, simply because they are cheaper. The other reason that you may need to use pressurisation is that it may be a requirement from Building Control or the Fire Service where the building itself is not Building Regulations compliant and therefore Building Control have asked for a pressurisation system as a compensating factor. Can you now tell us about the doors that are kept open when you are doing the testing? Where you are doing a stairwell pressurisation system to Class A, B, C, D or E then you have to keep the doors open in accordance with the standard, so if you know the class then the standard will tell you which doors have to be open for that particular system. If you are doing pressurisation or de- pressurisation of other spaces then the standard doesn’t very specifically tell you which doors need to be open, that’s a design decision. But, for Class A to Class E systems, you simply follow the standard to decide which doors are going to be open. How are EN requirements different than NFPA/IBC requirements? Here we are talking about the difference between the European standards and the American NFPA standards. Basically there are an awful lot of detailed differences but the main difference is that under the American NFPA standard, there is no velocity requirement in a door open condition. Instead the standard requires you to maintain the pressure, even with doors open. So it requires the designer to make a decision as to how many doors are going to be open, and then ensure that they can maintain the pressure within the stair, even with all of those doors open. That tends to require a higher airflow rate particularly if you have decided you are going to have a lot of doors open. The other difference is that in the EN standard we have a fixed pressure requirement of 50 pascals; in the NFPA standard the pressure differential required varies depending upon the height of the rooms and is generally a little bit lower that the EN. So if you are designing to NFPA you will have a very different system to if you design to the European standard. We regularly design buildings with mechanical ventilation but use depressurisation as opposed to positive pressurisation. Are there many instances where you would see a benefit of using positive pressurisation over depressurisation? So I presume there we are talking about mechanical shaft systems which, although they are not generally classed as depressurisation systems to EN12101, do have the effect of depressurising the corridor. Those systems generally are used because they are less complex and less expensive than a pressurisation system. The pressurisation system will generally give slightly better conditions within a building than a mechanical shaft depressurisation type system, so yes there is a benefit but of course, under the regulations, unless you have these particular times when pressurisation is absolutely required, nobody really wants to pay for the additional benefit of a pressurisation system. So people would tend to use these mechanical shaft systems simply because they are cheaper and because they meet the regulations. © 2013 Colt International Licensing Ltd.
  • 3. Can one fit a pressure relief damper on a window in a stair? The pressure relief damper can replace a window, certainly. If you look at a pressure relief damper it’s a louvred damper assembly, its not normally weather proof on its own, so if you are going to replace a window with it, normally you would have the damper and then you would put some kind of weather proofing ventilator behind it, but certainly you can replace a window although you wouldn’t actually use the window. What effect would the fitting of smoke seals have on doors in the lobby/corridor? Generally when we have a pressurisation system we wouldn’t fit smoke seals to the doors between the various pressurised spaces or between the pressurised space and the accommodation. The reason for that is basically that a bit of leakage there is generally beneficial in that it limits or minimises the size of the pressure relief damper that we need or the variation that we are going to need on an inverter system. So no we wouldn’t normally fit smoke seals on any of the doors within the pressurised spaces. Is the noise of a system a problem in relation to a voice comms system say from a disabled persons refuge? The answer to that is, yes it can be. If you have that sort of situation, then normally there will be a noise spec or a volume spec for the voice comms system, and from that you will be able to set a maximum noise level within the stair. Once you have that maximum noise level required within the stair then its quite possible to calculate the noise level from the fan system and fit an attenuator if required. On smaller systems it’s not normally a problem, but as the systems get bigger and noisier then yes it can be a problem, particularly on the upper storeys close to the fan system. . © 2013 Colt International Licensing Ltd.