Functional Range
IWE - Earth Fault Relay
C&S Protection & Control Ltd.
2
3
Contents
Page No.
1 .1 .1 .1 .1 . ApplicationApplicationApplicationApplicationApplication 44444
2 .2 .2 .2 .2 . Operating PrincipleOperating PrincipleOperating PrincipleOperating PrincipleOperating Principle 44444
3 .3 .3 .3 .3 . Current TCurrent TCurrent TCurrent TCurrent Transformer Connectionsransformer Connectionsransformer Connectionsransformer Connectionsransformer Connections 55555
4 .4 .4 .4 .4 . Connections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting Adjustments 77777
5 .5 .5 .5 .5 . Functional CheckFunctional CheckFunctional CheckFunctional CheckFunctional Check 88888
6 .6 .6 .6 .6 . TTTTTechnical Dataechnical Dataechnical Dataechnical Dataechnical Data 99999
7 .7 .7 .7 .7 . Information Required with OrderInformation Required with OrderInformation Required with OrderInformation Required with OrderInformation Required with Order 1 11 11 11 11 1
4
1. Application
The IWEIWEIWEIWEIWE relay is a definite time relay suitable for earth
fault protection of generators, motors, transformers,
capacitor banks, shunt reactors and radial feeders in
distribution networks.
Examples of the application of non-directional earth
fault protection using the relay type IWE are shown
below.
Example 1: Generator Stator Earth Fault
Protection.
With the generator neutral point earthed as shown in
Fig.1, the earth fault relay type IWEIWEIWEIWEIWE responds only to
phase-earth faults between the generator and the
location of the current transformers supplying the relay.
Earth faults beyond the current transformer, i.e. on the
consumer or line side, will not be detected.
Fig. 1Fig. 1Fig. 1Fig. 1Fig. 1
Example 2 : System Earth Fault Protection.
With the generator neutral point earthed as shown in
Fig.2, the earth fault relay type IWEIWEIWEIWEIWE responds only to
earth faults in the power system connected to the
generator. It does not respond to earth faults on the
generator terminals or in the generator stator.
Fig. 2Fig. 2Fig. 2Fig. 2Fig. 2
Example 3 : Back-up Earth Fault Proteciton
With the earth fault relay type IWEIWEIWEIWEIWE connected as shown
in fig.3 it responds to any earth fault on the generator
(or transformer) or on the network. In order to
discriminate with other system earth fault protection
the relay type IWE must have a tripping delay time
which is longer than all other system earth fault
protection devices.
Fig. 3Fig. 3Fig. 3Fig. 3Fig. 3
2. Operating Principle
The earth fault relay type IWEIWEIWEIWEIWE is a definite time over
current relay with an additional low-pass filter.
Fig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristic
It comprises a current input circuit, an electronic
current measuring circuit and a time delay unit. It also
includes a low pass filter which blocks higher harmonic
currents such as third, fifth, seventh etc. Third and
triple harmonics (e.g. 9th, 27th etc.) are of particular
importance when applying earth fault protection since
these harmonics are additive and co-phasal in a three
phase system and thus appear in the system neutral or
in an earth fault relay as zero sequence (or earth fault)
current. Such a current would be detected by an earth
fault relay and may cause unwanted tripping. The relay
measuring system responds and initiates a timing
circuit, if the effective current exceeds the relay current
setting. If the earth fault current remains above the
IE
5
setting for the set time delay the output tripping contacts
operates.
The tripping time delay is independent of the current
level. When applied in a power system the relay time
delay must be selected so that it coordinates with other
earth fault relays.
Fig.5a and 5b illustrate the operating characteristic of
the relay. Consider a relay with a current setting IE
=1.5
A and a time delay setting tE
=0.8s:
Fig.5a:Fig.5a:Fig.5a:Fig.5a:Fig.5a:
At t=0.4s, the current exceeds the relay current setting
and initiates the time delay circuit. The indicating LED
“I” on the relay fascia is illuminated.
At t=1s the earth fault current drops below the current
setting. The LED “I” extinguishes and the time delay
circuit reset to zero. There is no trip output.
Fig. 5b:Fig. 5b:Fig. 5b:Fig. 5b:Fig. 5b:
At t=0.4s the current exceeds the relay current setting
and initiates the relay time delay circuit as in the
example described above and illustrated in fig.5a.
At t=1.2s, e.g. 0.8s, after the current exceeded the
relay setting the time delay has elapsed and the “TRIP”
LED is illuminated. The relay produces a trip output and
the relay current is interrupted.
Fig. 5a and 5bFig. 5a and 5bFig. 5a and 5bFig. 5a and 5bFig. 5a and 5b
3. Current Transformer Connections
Current transformer must be arranged so that the
relay type IWEIWEIWEIWEIWE measures zero sequences (or earth
fault) currents as indicated schematically in figs. 1 and
2.
This can be achieved by using several current
transformers connected suitable or by using a single
ring type current transformer.
Earth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several current
transformerstransformerstransformerstransformerstransformers
The arrangement shown in figs. 6 and 7 should be
used only where significant levels of earth fault current
are available (e.g. in solidly earthed or low impedance
earthed networks) since the errors associated with each
current transformer are additive and these are
recognized by the relay as zero sequence current.
Such an arrangement can therefore only be used
where the relay current setting is in excess of the sum
of the CT errors.
Guide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangement
as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7
CT’s must be matched and have the same current
ration, accuracy class, rated output, secondary
winding resistance and magnetising
characteristic.
The current ratio and primary current withstand
should be selected according to the maximum
rated current of the circuit.
The combination of rated output, overcurrent
factor and secondary winding resistance should
be chosen such that a CT does not saturate at the
maximum short circuit current. If this combination
is not correct the CT may saturate under external
phase fault conditions (i.e. for a 2 or 3 phase
fault which the relay should remains unoperated).
In this case the several line CT’s may saturate
unequally. Therefore the sum of the secondary
currents in no longer zero and the relay
maloperates.
Relay output contacts
operate. Circuit
breaker tripped.
I
/A
1
0
Dt = 0.2s
1 2
2
-1.6AIE
3
4
t
/s
Dt = <0.2s
t
/s20 1
1
2
3
4
I
/A
l
/A
l
/A
6
Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7
Relationship between CT actual overcurrent factor,
rated overcurrent factor rated output, connected
burden and secondary winding resistance.
If the burden connected to the secondary winding of a
current transformer does not match exactly the rated
burden, the actual overcurrent factor of the CT will no
longer be equal to the rated overcurrent factor.
For example, if the total connected burden is less than
the rated output of the CT, the actual overcurrent factor
will be greater than the rated overcurrent factor.
Conversely, if the total connected burden is greater
than the rated output the CT, the actual overcurrent
factor will be less than the rated overcurrent factor.
Actual overcurrent factors can be calculated as follows:
n’= n
where
n’ = actual overcurrent factor
n = rated overcurrent factor
PN
= Nominal rated output of CT (VA)
PE
= Burden of secondary winding resistance of CT
rated current
= IN
2
RCT
(VA)
PN
-PE
PB
-PE
PB
= Burden connected to CT secondary circuit (VA)
Earth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’s
The use of ring type current transformers for supplying
earth fault relays as shown in fig. 8 and 9 is preferred
wherever possible to the arrangement using separate
CT’s connected in parallel as indicated in figs. 6 and 7.
Such an arrangement is particularly recommended for
earth fault protection on high impedance earthed
systems where the level of earth fault current is low.
A ring type CT comprises a single magnetic core which
surrounds all conductors and therefore under normal
load conditions, or during two or three phase fault
conditions, the resultant magnetic flux is zero and the
CT produces no secondary current. Only in the
presence of zero sequence current is the resultant flux
not equal to zero and the CT produces a secondary
current. Therefore, unlike the arrangement which
summates, the secondary currents from several CT’s
under normal load and other non earth fault
conditions, and which is the therefore sensitive to
individual CT errors, a single ring type CT is not subject
to the same errors and a very high degree of sensivity
can be achieved.
Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9
76 1211
IWE
Fig. 9
Measurement of earth fault
current in a three phase,
four wire system using a
Ring type CT
Fig. 8
Measurement of earth fault
current in a three phase,
three wire system using a
Ring type CT
43ba
L3
L2
L1
N
76 1211
43ba
IWE
L3
L2
L1
E E
L1
L2
N
ba
IWE
Fig. 7
Three Phase, four
wire system
Fig. 6
Holmgreen connection,
three phase three wire
system
43
6 7 1211
L3
L1
L2
L3
IWE
43ba
6 7 1211
E E
7
Guide for Dimensioning of Ring Type CT’s
• The inside diameter of the CT must be large
enough to slide over the cable.
•
The primary rated current of the CT should match
the maximum earth fault current in the case of
high impedance earthed system.
•
The rated secondary current is generally 1A or
5A.
•
the case of a feeder comprising several cables in
parallel, a ring CT can be fitted to each cable.
The CT secondary windings should then be
connected in parallel and connected to a single
earth fault relay type IWE. CT’s should have
identical magnetising characteristic, ratio, rated
output, accuracy class etc.
4. Connections, Contact Arrangement
and Setting Adjustments
Fig.10 shows the main connections to the relay type
IWE. The auxiliary supply should be connected to
terminals “a” and “6” and should be a secure supply
with a variation of not greater than 10 per cent.
Fig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connections
If a ring type CT is used, it is important to ensure that
the cable and CT are installed precisely as shows in fig.
11 and cable gland must be insulated from the cable
terminating box, and the cable sheath and armour
must be earthed by taking the earth connection back
through the CT as shown. If the earth lead is not
connected as shown, the earth return current in the
cable sheath or armour sets up a magnetic flux which
cancels the flux produced by the earth current in the
cable, and therefore the relay would not operate
during an earth fault.
Fig. 11Fig. 11Fig. 11Fig. 11Fig. 11 Cable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangements
when using Ring type CTwhen using Ring type CTwhen using Ring type CTwhen using Ring type CTwhen using Ring type CT
Fig.12Fig.12Fig.12Fig.12Fig.12 shows the position of the relay contacts. Under
normal healthy conditions, or with no auxiliary voltage
supplied the contacts are as shown in position 1. With
the relay operated after the set time delay has elapsed,
the contacts are shown as in position 2.
76
auxiliary
supply voltage
CT
secondary
current
S (I)2
S1 (k)
1211
IWE
43ba
L1 L2 L3
cable gland to be
insulated from earth
cable
earth
connection
Ring type CT
E
8
Fig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positions
Fig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unit IWEIWEIWEIWEIWE
5. Functional Check
A simple functional check can be made with the aid of
a secondary injection test set and an ammeter as
follows:
Connect rated auxiliary supply voltage to terminal
“a” and “6”.
Connect the injection test set output current
terminals via an ammeter to the relay terminals
“7” and “b”.
Note that the injected current should be kept less
than the rated current of the relay i.e. less than
1A or 5A as appropriate.
Adjust the time delay setting potentiometer to
t=0s.
With the current setting potentiometer set to a
suitable value increase the current from the test
set until the relay LED “I” is illuminated. This
indicates that the relay has picked up. Since the
set time delay t=0s, the tripping LED “TRIP” will
be illuminated simultaneously. Check that the pick
up current is within 5 per cent of the current
setting on the relay. Switch off the test current.
Adjust the time delay setting potentiometer to the
required time delay.
Switch on the test set, increase the test current to
a value which is higher than the current setting.
The relay will only operate and produce a trip
output after the set time delay has elapsed.
Contact position 2Contact position 1
Protected system healthy
Relay non-operated
No auxiliary voltage
Relay operated
Tripping
1211
43
1211
43
DC/ACDC/ACDC/AC
EARTH FAULT CURRENT RELAY
current time
S
I> ba 3 4
12117
I
k
6
TRIP
IWE
A
9570
9
6. Technical Data
IWE-Earth Fault Current Relay
General Data
Design : electronic state definite time overcurrent relay with low-pass filter
Maintenance : none
Permissible operating time : continuous
Mounting position : independent
Auxiliary Supply Voltages
Supply Voltage : 24 V, 110 V d.c
Own consumption : 2.5 W
Permissible voltage variation : ± 10%
Measuring circuit
Rated current IN
: 1 A or 5 A
Rated frequency : 50 Hz or 60 Hz
Burden of current circuit : 0.5 VA at rated current
Short time current setting : 20.IN
for max. 1S
Current settings : 1 A relay: 0 - 100 mA/ 0-0.5 A
5A relay: 0 - 2A / 0 -4A
Time delay settings : 0.2-2s/0.5-4s
Reset radio : 99.5 %
Output Circuits
Contacts : 1 NC, 1 NO potential free
Breaking capacity : 1000 VA at 250 V AC 2 A at 24 V dc
Contact life : greater than 106
switching operations
Terminals : M4, wire termination max. conductor 2.5mm2
Ambient Conditions
Ambient temperature range:
•
for storage : -40 0
C up to +70 0
C
•
for operation within claimed
accuracy : -200
C up to +600
C
10
Accuracy
Effect of temperature : ± 1% of the setting over the range 00
C < V < 600
C
Case, Dimensions,
Weight and Installation
Case : CSPCCSPCCSPCCSPCCSPC standard case
Material : track resistant moulded base and transparent cover
Height *width*depth : 142 mm*105 mm * 90 mm
Weight : 0.4 kg (approx.)
Mounting : Flush mounting
Protection class case : IP20
terminals : IP00
Dimensions and
drill-holes
(dimensions in mm)
105
91
98.5
86
52.5
19
4.5
a
105
6
Freespace for bolts
6.5
4.5
Dm-3.8mm
Dm-4.2mm
15
26
111
126.5
136.5
141
34
b 1 2 3 4
6 7 8 10 11 12
a
11
7. Information required with order
When placing an order, please fill in the form on the
right.
Earth fault relay IWE
Rated Current 1A 11111
Rated Current 5A 55555
Current ranges 1A (0 - 0.1 A) 0.10.10.10.10.1
(0 - 0.5 A) 0.50.50.50.50.5
5A (0 - 2 A) 2.02.02.02.02.0
(0 - 4 A) 4.04.04.04.04.0
Time Ranges 0.2 - 2 sec. 22222
0.5 - 4 sec. 44444
Auxiliary Voltage 24 V DC 2424242424
110 V DC 110110110110110
12
FR/IWE/05.06.01/160405

More Related Content

What's hot

Power System Operation and Control
Power System Operation and ControlPower System Operation and Control
Power System Operation and Control
Biswajit Pratihari
 
Lab manual psd v sem experiment no 6
Lab manual psd v sem experiment no 6Lab manual psd v sem experiment no 6
Lab manual psd v sem experiment no 6
Sachin Airan
 
Automatic power factor correction unit
Automatic power factor correction unitAutomatic power factor correction unit
Automatic power factor correction unit
Biswajit Pratihari
 

What's hot (20)

Harmonics and mitigation techniques
Harmonics and mitigation techniquesHarmonics and mitigation techniques
Harmonics and mitigation techniques
 
Protection of alternator
Protection of alternatorProtection of alternator
Protection of alternator
 
Differential relay
Differential relayDifferential relay
Differential relay
 
Principles of Power Systems V.K Mehta Complete Book - Chapter 6
Principles of Power Systems V.K Mehta Complete Book - Chapter 6Principles of Power Systems V.K Mehta Complete Book - Chapter 6
Principles of Power Systems V.K Mehta Complete Book - Chapter 6
 
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]Electrical measurement &amp; measuring instruments [emmi  (nee-302) -unit-2]
Electrical measurement &amp; measuring instruments [emmi (nee-302) -unit-2]
 
PPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITYPPT ON POWER SYSTEM STABILITY
PPT ON POWER SYSTEM STABILITY
 
Power System Operation and Control
Power System Operation and ControlPower System Operation and Control
Power System Operation and Control
 
Chapter 2 breakdown in liquids
Chapter 2 breakdown in liquidsChapter 2 breakdown in liquids
Chapter 2 breakdown in liquids
 
Voltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTSVoltage source Converters as a building block of HVDC and FACTS
Voltage source Converters as a building block of HVDC and FACTS
 
distance relay
distance relaydistance relay
distance relay
 
Relay coordination
Relay coordinationRelay coordination
Relay coordination
 
Unsymmetrical fault in transmission line
Unsymmetrical fault in transmission lineUnsymmetrical fault in transmission line
Unsymmetrical fault in transmission line
 
Unit 1 Power System Stability
Unit 1 Power System Stability Unit 1 Power System Stability
Unit 1 Power System Stability
 
3_Overcurrent Protection.pdf
3_Overcurrent Protection.pdf3_Overcurrent Protection.pdf
3_Overcurrent Protection.pdf
 
statcom
statcomstatcom
statcom
 
Lab manual psd v sem experiment no 6
Lab manual psd v sem experiment no 6Lab manual psd v sem experiment no 6
Lab manual psd v sem experiment no 6
 
Relay & Protection
Relay  & ProtectionRelay  & Protection
Relay & Protection
 
Automatic power factor correction unit
Automatic power factor correction unitAutomatic power factor correction unit
Automatic power factor correction unit
 
Power angle curve calclation
Power angle curve calclationPower angle curve calclation
Power angle curve calclation
 
Transient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psatTransient stability analysis on a multi machine system in psat
Transient stability analysis on a multi machine system in psat
 

Viewers also liked

17th Edition Part 4 3
17th  Edition  Part 4 317th  Edition  Part 4 3
17th Edition Part 4 3
Paul Holden
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
Nageswar Rao
 

Viewers also liked (17)

Impedance Matching
Impedance MatchingImpedance Matching
Impedance Matching
 
Over-current-earth-fault-relay-MC-31
 Over-current-earth-fault-relay-MC-31 Over-current-earth-fault-relay-MC-31
Over-current-earth-fault-relay-MC-31
 
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
Dalroad Norslo - Electric Equipment - Contactor training level 1 - LS Industr...
 
EEP303: Ex 5
EEP303: Ex 5EEP303: Ex 5
EEP303: Ex 5
 
Ocr efr
Ocr efrOcr efr
Ocr efr
 
EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013EE6702 Protection and Switchgear notes R2013
EE6702 Protection and Switchgear notes R2013
 
17th Edition Part 4 3
17th  Edition  Part 4 317th  Edition  Part 4 3
17th Edition Part 4 3
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
Contactor Generalizations
Contactor GeneralizationsContactor Generalizations
Contactor Generalizations
 
Protection of alternator
Protection of alternator Protection of alternator
Protection of alternator
 
Vacuum circuit breaker
Vacuum circuit breakerVacuum circuit breaker
Vacuum circuit breaker
 
Er rahul sharma feeder protection
Er rahul sharma feeder protectionEr rahul sharma feeder protection
Er rahul sharma feeder protection
 
Busbar configuarations
Busbar configuarationsBusbar configuarations
Busbar configuarations
 
Ppt of current transformer
Ppt of current transformerPpt of current transformer
Ppt of current transformer
 
protection and relay scheme
protection and relay schemeprotection and relay scheme
protection and relay scheme
 
LinkedIn SlideShare: Knowledge, Well-Presented
LinkedIn SlideShare: Knowledge, Well-PresentedLinkedIn SlideShare: Knowledge, Well-Presented
LinkedIn SlideShare: Knowledge, Well-Presented
 
TEDx Manchester: AI & The Future of Work
TEDx Manchester: AI & The Future of WorkTEDx Manchester: AI & The Future of Work
TEDx Manchester: AI & The Future of Work
 

Similar to 1 7 earth fault relay

06 current -__voltage_transformers
06 current -__voltage_transformers06 current -__voltage_transformers
06 current -__voltage_transformers
Krishna Das
 
1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx
jackiewalcutt
 
Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...
IJERD Editor
 
Review of the DTC Controller and Estimation of Stator Resistance in IM Drives
Review of the DTC Controller and Estimation of Stator Resistance in IM DrivesReview of the DTC Controller and Estimation of Stator Resistance in IM Drives
Review of the DTC Controller and Estimation of Stator Resistance in IM Drives
IAES-IJPEDS
 

Similar to 1 7 earth fault relay (20)

C0212014018
C0212014018C0212014018
C0212014018
 
06 current -__voltage_transformers
06 current -__voltage_transformers06 current -__voltage_transformers
06 current -__voltage_transformers
 
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab ModelIRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
IRJET- Study Over Current Relay (MCGG53) Response using Matlab Model
 
Dynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changerDynamic Analysis and Testing of on-load tap changer
Dynamic Analysis and Testing of on-load tap changer
 
Reach and Operating Time Correction of Digital Distance Relay
Reach and Operating Time Correction of Digital Distance Relay Reach and Operating Time Correction of Digital Distance Relay
Reach and Operating Time Correction of Digital Distance Relay
 
Reach and Operating Time Correction of Digital Distance Relay
Reach and Operating Time Correction of Digital Distance Relay Reach and Operating Time Correction of Digital Distance Relay
Reach and Operating Time Correction of Digital Distance Relay
 
1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx1. Determine the voltage drop at the motor frame for an earth .docx
1. Determine the voltage drop at the motor frame for an earth .docx
 
Detection of Power Grid Synchronization Failure by Sensing Bad Voltage and Fr...
Detection of Power Grid Synchronization Failure by Sensing Bad Voltage and Fr...Detection of Power Grid Synchronization Failure by Sensing Bad Voltage and Fr...
Detection of Power Grid Synchronization Failure by Sensing Bad Voltage and Fr...
 
Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...
 
Get 8402
Get 8402Get 8402
Get 8402
 
Review of the DTC Controller and Estimation of Stator Resistance in IM Drives
Review of the DTC Controller and Estimation of Stator Resistance in IM DrivesReview of the DTC Controller and Estimation of Stator Resistance in IM Drives
Review of the DTC Controller and Estimation of Stator Resistance in IM Drives
 
Module 1_8 PSP.pptx
Module 1_8 PSP.pptxModule 1_8 PSP.pptx
Module 1_8 PSP.pptx
 
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
IRJET- Simulation of Energization and De-Energization of Capacitor Banks and ...
 
Out of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit BreakersOut of phase current switching in High Voltage Circuit Breakers
Out of phase current switching in High Voltage Circuit Breakers
 
Review of DC Offset Compensation Techniques for Grid Connected Inverters
Review of DC Offset Compensation Techniques for Grid Connected InvertersReview of DC Offset Compensation Techniques for Grid Connected Inverters
Review of DC Offset Compensation Techniques for Grid Connected Inverters
 
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
Auto Reset on Temporary Fault Otherwise Permanent Trip in Three Phase Transmi...
 
Capacitive voltage transformer (1)
Capacitive voltage transformer (1)Capacitive voltage transformer (1)
Capacitive voltage transformer (1)
 
Real time parameter estimation for power quality control and intelligent prot...
Real time parameter estimation for power quality control and intelligent prot...Real time parameter estimation for power quality control and intelligent prot...
Real time parameter estimation for power quality control and intelligent prot...
 
Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017Minor_project_b.tech_sem7_dec_2017
Minor_project_b.tech_sem7_dec_2017
 
Fuzzy Based Analysis of Inverter Fed Micro Grid in Islanding Operation-Experi...
Fuzzy Based Analysis of Inverter Fed Micro Grid in Islanding Operation-Experi...Fuzzy Based Analysis of Inverter Fed Micro Grid in Islanding Operation-Experi...
Fuzzy Based Analysis of Inverter Fed Micro Grid in Islanding Operation-Experi...
 

Recently uploaded

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 

Recently uploaded (20)

NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
The Most Attractive Pune Call Girls Budhwar Peth 8250192130 Will You Miss Thi...
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Wakad Call Me 7737669865 Budget Friendly No Advance Booking
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 

1 7 earth fault relay

  • 1. Functional Range IWE - Earth Fault Relay C&S Protection & Control Ltd.
  • 2. 2
  • 3. 3 Contents Page No. 1 .1 .1 .1 .1 . ApplicationApplicationApplicationApplicationApplication 44444 2 .2 .2 .2 .2 . Operating PrincipleOperating PrincipleOperating PrincipleOperating PrincipleOperating Principle 44444 3 .3 .3 .3 .3 . Current TCurrent TCurrent TCurrent TCurrent Transformer Connectionsransformer Connectionsransformer Connectionsransformer Connectionsransformer Connections 55555 4 .4 .4 .4 .4 . Connections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting AdjustmentsConnections, Contact Arrangement and Setting Adjustments 77777 5 .5 .5 .5 .5 . Functional CheckFunctional CheckFunctional CheckFunctional CheckFunctional Check 88888 6 .6 .6 .6 .6 . TTTTTechnical Dataechnical Dataechnical Dataechnical Dataechnical Data 99999 7 .7 .7 .7 .7 . Information Required with OrderInformation Required with OrderInformation Required with OrderInformation Required with OrderInformation Required with Order 1 11 11 11 11 1
  • 4. 4 1. Application The IWEIWEIWEIWEIWE relay is a definite time relay suitable for earth fault protection of generators, motors, transformers, capacitor banks, shunt reactors and radial feeders in distribution networks. Examples of the application of non-directional earth fault protection using the relay type IWE are shown below. Example 1: Generator Stator Earth Fault Protection. With the generator neutral point earthed as shown in Fig.1, the earth fault relay type IWEIWEIWEIWEIWE responds only to phase-earth faults between the generator and the location of the current transformers supplying the relay. Earth faults beyond the current transformer, i.e. on the consumer or line side, will not be detected. Fig. 1Fig. 1Fig. 1Fig. 1Fig. 1 Example 2 : System Earth Fault Protection. With the generator neutral point earthed as shown in Fig.2, the earth fault relay type IWEIWEIWEIWEIWE responds only to earth faults in the power system connected to the generator. It does not respond to earth faults on the generator terminals or in the generator stator. Fig. 2Fig. 2Fig. 2Fig. 2Fig. 2 Example 3 : Back-up Earth Fault Proteciton With the earth fault relay type IWEIWEIWEIWEIWE connected as shown in fig.3 it responds to any earth fault on the generator (or transformer) or on the network. In order to discriminate with other system earth fault protection the relay type IWE must have a tripping delay time which is longer than all other system earth fault protection devices. Fig. 3Fig. 3Fig. 3Fig. 3Fig. 3 2. Operating Principle The earth fault relay type IWEIWEIWEIWEIWE is a definite time over current relay with an additional low-pass filter. Fig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristicFig. 4 Relay characteristic It comprises a current input circuit, an electronic current measuring circuit and a time delay unit. It also includes a low pass filter which blocks higher harmonic currents such as third, fifth, seventh etc. Third and triple harmonics (e.g. 9th, 27th etc.) are of particular importance when applying earth fault protection since these harmonics are additive and co-phasal in a three phase system and thus appear in the system neutral or in an earth fault relay as zero sequence (or earth fault) current. Such a current would be detected by an earth fault relay and may cause unwanted tripping. The relay measuring system responds and initiates a timing circuit, if the effective current exceeds the relay current setting. If the earth fault current remains above the IE
  • 5. 5 setting for the set time delay the output tripping contacts operates. The tripping time delay is independent of the current level. When applied in a power system the relay time delay must be selected so that it coordinates with other earth fault relays. Fig.5a and 5b illustrate the operating characteristic of the relay. Consider a relay with a current setting IE =1.5 A and a time delay setting tE =0.8s: Fig.5a:Fig.5a:Fig.5a:Fig.5a:Fig.5a: At t=0.4s, the current exceeds the relay current setting and initiates the time delay circuit. The indicating LED “I” on the relay fascia is illuminated. At t=1s the earth fault current drops below the current setting. The LED “I” extinguishes and the time delay circuit reset to zero. There is no trip output. Fig. 5b:Fig. 5b:Fig. 5b:Fig. 5b:Fig. 5b: At t=0.4s the current exceeds the relay current setting and initiates the relay time delay circuit as in the example described above and illustrated in fig.5a. At t=1.2s, e.g. 0.8s, after the current exceeded the relay setting the time delay has elapsed and the “TRIP” LED is illuminated. The relay produces a trip output and the relay current is interrupted. Fig. 5a and 5bFig. 5a and 5bFig. 5a and 5bFig. 5a and 5bFig. 5a and 5b 3. Current Transformer Connections Current transformer must be arranged so that the relay type IWEIWEIWEIWEIWE measures zero sequences (or earth fault) currents as indicated schematically in figs. 1 and 2. This can be achieved by using several current transformers connected suitable or by using a single ring type current transformer. Earth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several currentEarth fault measurement using several current transformerstransformerstransformerstransformerstransformers The arrangement shown in figs. 6 and 7 should be used only where significant levels of earth fault current are available (e.g. in solidly earthed or low impedance earthed networks) since the errors associated with each current transformer are additive and these are recognized by the relay as zero sequence current. Such an arrangement can therefore only be used where the relay current setting is in excess of the sum of the CT errors. Guide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangementGuide for dimensioning of CT’s arrangement as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7as shown in figs. 6 and 7 CT’s must be matched and have the same current ration, accuracy class, rated output, secondary winding resistance and magnetising characteristic. The current ratio and primary current withstand should be selected according to the maximum rated current of the circuit. The combination of rated output, overcurrent factor and secondary winding resistance should be chosen such that a CT does not saturate at the maximum short circuit current. If this combination is not correct the CT may saturate under external phase fault conditions (i.e. for a 2 or 3 phase fault which the relay should remains unoperated). In this case the several line CT’s may saturate unequally. Therefore the sum of the secondary currents in no longer zero and the relay maloperates. Relay output contacts operate. Circuit breaker tripped. I /A 1 0 Dt = 0.2s 1 2 2 -1.6AIE 3 4 t /s Dt = <0.2s t /s20 1 1 2 3 4 I /A l /A l /A
  • 6. 6 Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7Fig. 6 and 7 Relationship between CT actual overcurrent factor, rated overcurrent factor rated output, connected burden and secondary winding resistance. If the burden connected to the secondary winding of a current transformer does not match exactly the rated burden, the actual overcurrent factor of the CT will no longer be equal to the rated overcurrent factor. For example, if the total connected burden is less than the rated output of the CT, the actual overcurrent factor will be greater than the rated overcurrent factor. Conversely, if the total connected burden is greater than the rated output the CT, the actual overcurrent factor will be less than the rated overcurrent factor. Actual overcurrent factors can be calculated as follows: n’= n where n’ = actual overcurrent factor n = rated overcurrent factor PN = Nominal rated output of CT (VA) PE = Burden of secondary winding resistance of CT rated current = IN 2 RCT (VA) PN -PE PB -PE PB = Burden connected to CT secondary circuit (VA) Earth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’sEarth fault current measuring using ring type CT’s The use of ring type current transformers for supplying earth fault relays as shown in fig. 8 and 9 is preferred wherever possible to the arrangement using separate CT’s connected in parallel as indicated in figs. 6 and 7. Such an arrangement is particularly recommended for earth fault protection on high impedance earthed systems where the level of earth fault current is low. A ring type CT comprises a single magnetic core which surrounds all conductors and therefore under normal load conditions, or during two or three phase fault conditions, the resultant magnetic flux is zero and the CT produces no secondary current. Only in the presence of zero sequence current is the resultant flux not equal to zero and the CT produces a secondary current. Therefore, unlike the arrangement which summates, the secondary currents from several CT’s under normal load and other non earth fault conditions, and which is the therefore sensitive to individual CT errors, a single ring type CT is not subject to the same errors and a very high degree of sensivity can be achieved. Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9Fig. 8 and 9 76 1211 IWE Fig. 9 Measurement of earth fault current in a three phase, four wire system using a Ring type CT Fig. 8 Measurement of earth fault current in a three phase, three wire system using a Ring type CT 43ba L3 L2 L1 N 76 1211 43ba IWE L3 L2 L1 E E L1 L2 N ba IWE Fig. 7 Three Phase, four wire system Fig. 6 Holmgreen connection, three phase three wire system 43 6 7 1211 L3 L1 L2 L3 IWE 43ba 6 7 1211 E E
  • 7. 7 Guide for Dimensioning of Ring Type CT’s • The inside diameter of the CT must be large enough to slide over the cable. • The primary rated current of the CT should match the maximum earth fault current in the case of high impedance earthed system. • The rated secondary current is generally 1A or 5A. • the case of a feeder comprising several cables in parallel, a ring CT can be fitted to each cable. The CT secondary windings should then be connected in parallel and connected to a single earth fault relay type IWE. CT’s should have identical magnetising characteristic, ratio, rated output, accuracy class etc. 4. Connections, Contact Arrangement and Setting Adjustments Fig.10 shows the main connections to the relay type IWE. The auxiliary supply should be connected to terminals “a” and “6” and should be a secure supply with a variation of not greater than 10 per cent. Fig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connectionsFig. 10 Relay connections If a ring type CT is used, it is important to ensure that the cable and CT are installed precisely as shows in fig. 11 and cable gland must be insulated from the cable terminating box, and the cable sheath and armour must be earthed by taking the earth connection back through the CT as shown. If the earth lead is not connected as shown, the earth return current in the cable sheath or armour sets up a magnetic flux which cancels the flux produced by the earth current in the cable, and therefore the relay would not operate during an earth fault. Fig. 11Fig. 11Fig. 11Fig. 11Fig. 11 Cable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangementsCable and earthing arrangements when using Ring type CTwhen using Ring type CTwhen using Ring type CTwhen using Ring type CTwhen using Ring type CT Fig.12Fig.12Fig.12Fig.12Fig.12 shows the position of the relay contacts. Under normal healthy conditions, or with no auxiliary voltage supplied the contacts are as shown in position 1. With the relay operated after the set time delay has elapsed, the contacts are shown as in position 2. 76 auxiliary supply voltage CT secondary current S (I)2 S1 (k) 1211 IWE 43ba L1 L2 L3 cable gland to be insulated from earth cable earth connection Ring type CT E
  • 8. 8 Fig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positionsFig. 12 Contact positions Fig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unitFig. 13 Front cover of unit IWEIWEIWEIWEIWE 5. Functional Check A simple functional check can be made with the aid of a secondary injection test set and an ammeter as follows: Connect rated auxiliary supply voltage to terminal “a” and “6”. Connect the injection test set output current terminals via an ammeter to the relay terminals “7” and “b”. Note that the injected current should be kept less than the rated current of the relay i.e. less than 1A or 5A as appropriate. Adjust the time delay setting potentiometer to t=0s. With the current setting potentiometer set to a suitable value increase the current from the test set until the relay LED “I” is illuminated. This indicates that the relay has picked up. Since the set time delay t=0s, the tripping LED “TRIP” will be illuminated simultaneously. Check that the pick up current is within 5 per cent of the current setting on the relay. Switch off the test current. Adjust the time delay setting potentiometer to the required time delay. Switch on the test set, increase the test current to a value which is higher than the current setting. The relay will only operate and produce a trip output after the set time delay has elapsed. Contact position 2Contact position 1 Protected system healthy Relay non-operated No auxiliary voltage Relay operated Tripping 1211 43 1211 43 DC/ACDC/ACDC/AC EARTH FAULT CURRENT RELAY current time S I> ba 3 4 12117 I k 6 TRIP IWE A 9570
  • 9. 9 6. Technical Data IWE-Earth Fault Current Relay General Data Design : electronic state definite time overcurrent relay with low-pass filter Maintenance : none Permissible operating time : continuous Mounting position : independent Auxiliary Supply Voltages Supply Voltage : 24 V, 110 V d.c Own consumption : 2.5 W Permissible voltage variation : ± 10% Measuring circuit Rated current IN : 1 A or 5 A Rated frequency : 50 Hz or 60 Hz Burden of current circuit : 0.5 VA at rated current Short time current setting : 20.IN for max. 1S Current settings : 1 A relay: 0 - 100 mA/ 0-0.5 A 5A relay: 0 - 2A / 0 -4A Time delay settings : 0.2-2s/0.5-4s Reset radio : 99.5 % Output Circuits Contacts : 1 NC, 1 NO potential free Breaking capacity : 1000 VA at 250 V AC 2 A at 24 V dc Contact life : greater than 106 switching operations Terminals : M4, wire termination max. conductor 2.5mm2 Ambient Conditions Ambient temperature range: • for storage : -40 0 C up to +70 0 C • for operation within claimed accuracy : -200 C up to +600 C
  • 10. 10 Accuracy Effect of temperature : ± 1% of the setting over the range 00 C < V < 600 C Case, Dimensions, Weight and Installation Case : CSPCCSPCCSPCCSPCCSPC standard case Material : track resistant moulded base and transparent cover Height *width*depth : 142 mm*105 mm * 90 mm Weight : 0.4 kg (approx.) Mounting : Flush mounting Protection class case : IP20 terminals : IP00 Dimensions and drill-holes (dimensions in mm) 105 91 98.5 86 52.5 19 4.5 a 105 6 Freespace for bolts 6.5 4.5 Dm-3.8mm Dm-4.2mm 15 26 111 126.5 136.5 141 34 b 1 2 3 4 6 7 8 10 11 12 a
  • 11. 11 7. Information required with order When placing an order, please fill in the form on the right. Earth fault relay IWE Rated Current 1A 11111 Rated Current 5A 55555 Current ranges 1A (0 - 0.1 A) 0.10.10.10.10.1 (0 - 0.5 A) 0.50.50.50.50.5 5A (0 - 2 A) 2.02.02.02.02.0 (0 - 4 A) 4.04.04.04.04.0 Time Ranges 0.2 - 2 sec. 22222 0.5 - 4 sec. 44444 Auxiliary Voltage 24 V DC 2424242424 110 V DC 110110110110110