Module I
Over Current Protection :
Current Time characteristics, TSM,PSM.
17EE72 Power System
Protection
Important Terms
 (i) Pick-up current. It is the minimum
current in the relay coil at which the
relay starts to operate.
 So long as the current in the relay is less
than the pick-up value, the relay does not
operate and the breaker controlled by it
remains in the closed position.
 However, when the relay coil current is
equal to or greater than the pickup value,
the relay operates to energise the trip coil
which opens the circuit breaker.
(ii) Current setting.
 It is often desirable to adjustthe pick-up current to
any required value. This is known as current setting
and is usually achieved by the use of tappings on
the relay operating coil.
 The taps are brought out to a plug bridge as shown
in Fig.
 The plug bridge permits to alter the number of turns
on the relay coil.
 This changes the torque on the disc and hence the
time of operation of the relay.
 The values assigned to each tap are expressed in
terms of percentage full-load rating of C.T. with
which the relay is associated and represents the
value above which the disc commences to rotate
∴ Pick-up current = Rated secondary current of C.T. ×
Current setting
For example, suppose that an over-current relay having
current setting of 125% is connected to a supply circuit
through a current transformer of 400/5.
The rated secondary current of C.T. is 5 amperes.
Therefore, the pick-up value will be 25% more than 5 A
i.e. 5 × 1·25 = 6·25 A.
It means that with above current setting, the relay will actually
operate for a relay coil current equal to or greater than 6·25
A.
The current plug settings usually
range from 50% to 200% in steps of
25% for over current relays
and 10% to 70% in steps of 10% for
earth leakage relays. The desired
current setting is obtained by
inserting a plug between the jaws
of a bridge type socket at the tap
value required.
(iii) Plug-setting multiplier (P.S.M.). It is the ratio of
fault current in relay coil to the pick-up current i.e.
For example, suppose that a relay is connected to a 400/5
current transformer and set at 150%.
With a primary fault current of 2400 A, the plug-setting
multiplier can be calculated as under :
Pick-up value = Rated secondary current of CT × Current
setting
= 5 × 1·5 = 7·5 A
(iv) Time-setting multiplier.
 A relay is generally provided with control to adjust
the time of operation. This adjustment is known as
time-setting multiplier.
 The time-setting dial is calibrated from 0 to 1 in steps of
0.05 sec (see Fig.).
 These figures are multipliers to be used to convert the
time derived from time/P.S.M. curve into the actual
operating time.
 Thus if the time setting is 0·1 and the time obtained
from the time/P.S.M. curve is 3 seconds, then actual
relay operating time = 3 × 0·1 = 0·3 second.
 For instance, in an induction relay, the time of
operation is controlled by adjusting the amount of travel
of the disc from its reset position to its pickup position.
 This is achieved by the adjustment of the position of a
movable backstop which controls the travel of the disc
and thereby varies the time in which the relay will close
its contacts for given values of fault current.
 A so-called “time dial” with an evenly divided scale
provides this adjustment.
 The acutal time of operation is calculated by multiplying
the time setting multiplier with the time obtained from
time/P.S.M. curve of the relay.
Time/P.S.M. Curve
 Fig. shows the curve between time of
operation and plug setting multiplier of a
typical relay.
 The horizontal scale is marked in terms of
plug-setting multiplier and represents the
number of times the relay current is in
excess of the current setting.
 The vertical scale is marked in terms of the
time required for relay operation. If the
P.S.M. is 10, then the time of operation (from
the curve) is 3 seconds.
 The actual time of operation is obtained by
Calculation of Relay Operating Time
In order to calculate the actual relay operating time, the
following things must be known :
(a) Time/P.S.M. curve
(b) Current setting
(c) Time setting
(d) Fault current
(e) Current transformer ratio
The procedure for calculating the actual relay operating time is
as follows :
(i) Convert the fault current into the relay coil current by
using the current transformer ratio.
(ii) Express the relay current as a multiple of current
setting i.e. calculate the P.S.M.
(iii) From the Time/P.S.M. curve of the relay, read off the
time of operation for the calculated P.S.M.
(iv) Determine the actual time of operation by multiplying
the above time of the relay by time setting
multiplier(TSM) in use.
Problem1
Determine the time of operation of a 5-ampere, 3-second over current relay
having a current setting of 125% and a time setting multiplier of 0.6 connected
to supply circuit through a 400/5 current transformer when the circuit carries a
fault current of 4000 A. Use the curve shown in Fig.
End Session

More Related Content

Similar to Module 1_8 PSP.pptx

Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...
IJERD Editor
 
Iaetsd load frequency control for a distributed grid
Iaetsd load frequency control for a distributed gridIaetsd load frequency control for a distributed grid
Iaetsd load frequency control for a distributed grid
Iaetsd Iaetsd
 
Final Project Paper
Final Project PaperFinal Project Paper
Final Project Paper
Ahmed Hashem
 

Similar to Module 1_8 PSP.pptx (20)

Artigo sea
Artigo seaArtigo sea
Artigo sea
 
Chapter_9_Instrument.pdf
Chapter_9_Instrument.pdfChapter_9_Instrument.pdf
Chapter_9_Instrument.pdf
 
Fuzzy-PI Torque and Flux Controllers for DTC with Multilevel Inverter of Indu...
Fuzzy-PI Torque and Flux Controllers for DTC with Multilevel Inverter of Indu...Fuzzy-PI Torque and Flux Controllers for DTC with Multilevel Inverter of Indu...
Fuzzy-PI Torque and Flux Controllers for DTC with Multilevel Inverter of Indu...
 
A Review to AC Modeling and Transfer Function of DCDC Converters
A Review to AC Modeling and Transfer Function of DCDC ConvertersA Review to AC Modeling and Transfer Function of DCDC Converters
A Review to AC Modeling and Transfer Function of DCDC Converters
 
H010245763
H010245763H010245763
H010245763
 
Chapter_9.ppt
Chapter_9.pptChapter_9.ppt
Chapter_9.ppt
 
Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...Knee-Point Voltage Determination for Current Transformer Functional Identific...
Knee-Point Voltage Determination for Current Transformer Functional Identific...
 
3_Overcurrent Protection.pdf
3_Overcurrent Protection.pdf3_Overcurrent Protection.pdf
3_Overcurrent Protection.pdf
 
Design Of Sub Synchronous Damping Controller (SSDC) For TCSC To Improve Power...
Design Of Sub Synchronous Damping Controller (SSDC) For TCSC To Improve Power...Design Of Sub Synchronous Damping Controller (SSDC) For TCSC To Improve Power...
Design Of Sub Synchronous Damping Controller (SSDC) For TCSC To Improve Power...
 
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
Design of Three-Phase Three-Switch Buck-Type Rectifier for Pre-Charging Appli...
 
Vaila ruthvik ece_510_project
Vaila ruthvik ece_510_projectVaila ruthvik ece_510_project
Vaila ruthvik ece_510_project
 
Design and Implementation of an Interface Circuit for DC Motor Speed Control ...
Design and Implementation of an Interface Circuit for DC Motor Speed Control ...Design and Implementation of an Interface Circuit for DC Motor Speed Control ...
Design and Implementation of an Interface Circuit for DC Motor Speed Control ...
 
Iaetsd load frequency control for a distributed grid
Iaetsd load frequency control for a distributed gridIaetsd load frequency control for a distributed grid
Iaetsd load frequency control for a distributed grid
 
Final Project Paper
Final Project PaperFinal Project Paper
Final Project Paper
 
FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION FEEDER AND BUS BAR PROTECTION
FEEDER AND BUS BAR PROTECTION
 
DC DC Converter.pptx
DC DC Converter.pptxDC DC Converter.pptx
DC DC Converter.pptx
 
Simulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulationSimulation of 3-phase matrix converter using space vector modulation
Simulation of 3-phase matrix converter using space vector modulation
 
Automatic generation control&voltage control(module 5:ktu syllabus)
Automatic generation control&voltage control(module 5:ktu syllabus)Automatic generation control&voltage control(module 5:ktu syllabus)
Automatic generation control&voltage control(module 5:ktu syllabus)
 
chapter13.pdf
chapter13.pdfchapter13.pdf
chapter13.pdf
 
Unit-2..pdf
Unit-2..pdfUnit-2..pdf
Unit-2..pdf
 

More from msmsn2k2 (7)

Module 5 FUSES.pptx
Module 5 FUSES.pptxModule 5 FUSES.pptx
Module 5 FUSES.pptx
 
Module 3 Generator Protection (1).pptx
Module 3 Generator Protection (1).pptxModule 3 Generator Protection (1).pptx
Module 3 Generator Protection (1).pptx
 
module 1 HVE_Gases.pptx
module 1 HVE_Gases.pptxmodule 1 HVE_Gases.pptx
module 1 HVE_Gases.pptx
 
module 1 HVE_Gases.pptx
module 1 HVE_Gases.pptxmodule 1 HVE_Gases.pptx
module 1 HVE_Gases.pptx
 
Ug cables
Ug cablesUg cables
Ug cables
 
Insulator problems
Insulator problemsInsulator problems
Insulator problems
 
Section 16461 dry type transformers
Section 16461   dry type transformersSection 16461   dry type transformers
Section 16461 dry type transformers
 

Recently uploaded

FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
rknatarajan
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 

Recently uploaded (20)

UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
(INDIRA) Call Girl Aurangabad Call Now 8617697112 Aurangabad Escorts 24x7
 
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
(INDIRA) Call Girl Meerut Call Now 8617697112 Meerut Escorts 24x7
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICSUNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
UNIT-IFLUID PROPERTIES & FLOW CHARACTERISTICS
 
Thermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.pptThermal Engineering -unit - III & IV.ppt
Thermal Engineering -unit - III & IV.ppt
 

Module 1_8 PSP.pptx

  • 1. Module I Over Current Protection : Current Time characteristics, TSM,PSM. 17EE72 Power System Protection
  • 2. Important Terms  (i) Pick-up current. It is the minimum current in the relay coil at which the relay starts to operate.  So long as the current in the relay is less than the pick-up value, the relay does not operate and the breaker controlled by it remains in the closed position.  However, when the relay coil current is equal to or greater than the pickup value, the relay operates to energise the trip coil which opens the circuit breaker.
  • 3. (ii) Current setting.  It is often desirable to adjustthe pick-up current to any required value. This is known as current setting and is usually achieved by the use of tappings on the relay operating coil.  The taps are brought out to a plug bridge as shown in Fig.  The plug bridge permits to alter the number of turns on the relay coil.  This changes the torque on the disc and hence the time of operation of the relay.  The values assigned to each tap are expressed in terms of percentage full-load rating of C.T. with which the relay is associated and represents the value above which the disc commences to rotate
  • 4. ∴ Pick-up current = Rated secondary current of C.T. × Current setting For example, suppose that an over-current relay having current setting of 125% is connected to a supply circuit through a current transformer of 400/5. The rated secondary current of C.T. is 5 amperes. Therefore, the pick-up value will be 25% more than 5 A i.e. 5 × 1·25 = 6·25 A. It means that with above current setting, the relay will actually operate for a relay coil current equal to or greater than 6·25 A. The current plug settings usually range from 50% to 200% in steps of 25% for over current relays and 10% to 70% in steps of 10% for earth leakage relays. The desired current setting is obtained by inserting a plug between the jaws of a bridge type socket at the tap value required.
  • 5. (iii) Plug-setting multiplier (P.S.M.). It is the ratio of fault current in relay coil to the pick-up current i.e. For example, suppose that a relay is connected to a 400/5 current transformer and set at 150%. With a primary fault current of 2400 A, the plug-setting multiplier can be calculated as under : Pick-up value = Rated secondary current of CT × Current setting = 5 × 1·5 = 7·5 A
  • 6. (iv) Time-setting multiplier.  A relay is generally provided with control to adjust the time of operation. This adjustment is known as time-setting multiplier.  The time-setting dial is calibrated from 0 to 1 in steps of 0.05 sec (see Fig.).  These figures are multipliers to be used to convert the time derived from time/P.S.M. curve into the actual operating time.  Thus if the time setting is 0·1 and the time obtained from the time/P.S.M. curve is 3 seconds, then actual relay operating time = 3 × 0·1 = 0·3 second.  For instance, in an induction relay, the time of operation is controlled by adjusting the amount of travel of the disc from its reset position to its pickup position.
  • 7.  This is achieved by the adjustment of the position of a movable backstop which controls the travel of the disc and thereby varies the time in which the relay will close its contacts for given values of fault current.  A so-called “time dial” with an evenly divided scale provides this adjustment.  The acutal time of operation is calculated by multiplying the time setting multiplier with the time obtained from time/P.S.M. curve of the relay.
  • 8. Time/P.S.M. Curve  Fig. shows the curve between time of operation and plug setting multiplier of a typical relay.  The horizontal scale is marked in terms of plug-setting multiplier and represents the number of times the relay current is in excess of the current setting.  The vertical scale is marked in terms of the time required for relay operation. If the P.S.M. is 10, then the time of operation (from the curve) is 3 seconds.  The actual time of operation is obtained by
  • 9.
  • 10. Calculation of Relay Operating Time In order to calculate the actual relay operating time, the following things must be known : (a) Time/P.S.M. curve (b) Current setting (c) Time setting (d) Fault current (e) Current transformer ratio The procedure for calculating the actual relay operating time is as follows : (i) Convert the fault current into the relay coil current by using the current transformer ratio. (ii) Express the relay current as a multiple of current setting i.e. calculate the P.S.M. (iii) From the Time/P.S.M. curve of the relay, read off the time of operation for the calculated P.S.M. (iv) Determine the actual time of operation by multiplying the above time of the relay by time setting multiplier(TSM) in use.
  • 11. Problem1 Determine the time of operation of a 5-ampere, 3-second over current relay having a current setting of 125% and a time setting multiplier of 0.6 connected to supply circuit through a 400/5 current transformer when the circuit carries a fault current of 4000 A. Use the curve shown in Fig.
  • 12.
  • 13.
  • 14.
  • 15.
  • 16.
  • 17.
  • 18.
  • 19.