SlideShare a Scribd company logo
1 of 8
Download to read offline
Siemens AG
Power Transmission and Distribution
Medium Voltage Division
Mozartstr. 31c
91052 Erlangen
Germany
www.siemens.com/energy
For questions on power transmission and
distribution, please contact our Customer
Support Center, 24 hours a day.
Tel.: +49 180 / 524 70 00
Fax: +49 180 / 524 24 71
(Subject to charge: e.g. 12 ct/min)
E-mail: support.energy@siemens.com
www.siemens.com/energy-support
Subject to change without prior notice
Order no. E50001-U229-A282-X-7600
Printed in Germany
Dispo 30403
GB 06612 101976 08064.
The information in this document contains general descriptions of the technical features, which may not always be available.
An obligation to provide the respective performance feature shall exist only if expressly agreed in the terms of contract.
Power Transmission and Distribution
We are ready: IEC 62271-200
The new switchgear standard
Standards for all
Switchgear are important nodal points
in modern power distribution. Corre-
spondingly important is their reliable
functioning, a clearly defined switch-
ing behavior according to specified
parameters as well as the protection of
personnel and protection against oper-
ational interruptions when an overload
occurs.
The International Electrotechnical
Commission (IEC) has taken up the
task of developing the required speci-
fications, their worldwide standard-
ization and further development. The
same applies to IEC 62271-200 – the
new standard for medium-voltage
switchgear.
As one of the first manufacturers,
Siemens has implemented these
requirements and already offers the
complete product range of air-insu­
lated and gas-insulated switchgear
today, type-tested according to
IEC 62271-200.
2
IEC 62271-200
IEC 62271-200
IEC 60298 – for four decades this abbre-
viation was the decisive factor for the type
testing of metal-enclosed switchgear. In
the meantime there are tens of thousands
of switchgear panels of the primary and
secondary distribution level based on this
standard in use – certified according to
the mandatory part of the standard and,
if required, according to optional tests.
The passing of the following tests was
obligatory in order to identify switchgear as
type-tested:
Dielectric test to verify the insulation
level of the switchgear (tests with rated
lightning impulse withstand voltage and
rated short-duration power frequency
withstand voltage with the specified
values depending on the respective rated
voltage).
Temperature rise tests to verify the
current carrying capacity with rated normal
currents.
Peak and short-time withstand current
tests to verify the dynamic and thermal
current carrying capacity of the main and
earth circuits; the tests are performed with
rated peak short-circuit current or rated
short-circuit making current or rated short-
time current or rated short-circuit breaking
current.
Switching capacity test to verify the
making/breaking capacity of the installed
switchgear.
Mechanical function test to verify the
mechanical functions and interlocks.
Degree of protection tests to verify the
protection against electric shock and foreign
objects.
Pressure and strength tests to verify
the gas tightness and pressure resistance for
gas-filled switchgear.
There is also the possibility of voluntarily
certifying switchgear for resistance to inter-
nal arc faults and for personal protection.
Manufacturers and operators can select the
criteria which are relevant to them from the
following six criteria and have them tested.
Criterion 1:
Doors and covers must not open.
Criterion 2:
Parts of the switchgear must not fly off.
Criterion 3:
Holes must not develop in the external parts
of the enclosure.
Criterion 4:
Vertical indicators must not ignite.
Criterion 5:
Horizontal indicators must not ignite.
Criterion 6:
Earth connections must remain effective.
In order to guarantee safe access to the
individual switchgear components, e.g.the
incoming cable, without isolating the busbar,
the IEC 60298 standard differentiates bet­
ween three types of compartmentalization
that serve exclusively as protection against
electric shock.
Metal-clad switchgear: Division of the
switchgear panel into four compartments
(busbar compartment, switching-device
compartment, connection compartment
and low-voltage compartment); partitions
between the compartments made of sheet
steel, front plate made of sheet steel or
insulating material.
Compartmented switchgear: Division of
the switchgear panel same as for metal-clad
switchgear, but with the partitions between
the individual compartments made of insu-
lating material.
Cubicle-type switchgear: All other types
of construction that do not meet the above
features of the metal-clad or compartmented
designs.
In this context, access to the then common
minimum-oil-content circuit-breakers for
maintenance work without longer opera-
tional interruptions was of prime importance
because of the limited number of operating
cycles. Therefore, with switchgear in metal-
clad or compartmented design, the busbar in
the busbar compartment and the incom-
ing cable in the connection compartment
could remain in operation. With a cubicle-
type design, the incoming cable had to be
isolated, but the busbar itself could remain in
operation.
Retrospective
3
Although the old IEC 60298 standard
was very helpful, in time it was super-
seded by the technological progress.
Above all, the appearance of mainte-
nance-free vacuum circuit-breakers,
with operating cycles far exceeding
the normal number, made frequent
access to this circuit-breaker no longer
of prime importance.
The vacuum arc-quenching principle
is technologically so superior to other
arc-quenching principles that the
circuit-breaker can be fixed-mounted
again. This resulted in the first-time
use of gas insulation with the impor-
tant features of climatic independence,
compactness and maintenance-free de-
sign. However, both technologies – the
vacuum arc-quenching principle and
gas insulation – were not adequately
taken into account in the existing
standard.
Therefore, at the end of the nine-
ties, the responsible IEC committees
decided on the reformulation of the
switchgear standard, which finally
came into effect as IEC 62271-200 in
November 2003. At the same time the
old IEC 60298 standard was withdrawn
without any transition period.
Four key features are of special note with
the new IEC 62271-200 standard:
1. Changed dielectric requirements
According to IEC 60298, two disruptive
discharges were permitted in a series of
15 voltage impulses for the test with rated
lightning impulse withstand voltage. Ac-
cording to the new standard, the series
must be extended by another five voltage
impulses if a disruptive discharge has oc-
curred during the first 15 impulses. This can
lead to a maximum of 25 voltage impulses,
whereas the maximum number of permis-
sible disruptive discharges is still two.
2. Increased demands on the circuit-
breaker and earthing switch
In contrast to the previous standard, the
switching capacity test of both switching
devices is no longer carried out as a pure
device test. Instead, it is now mandatory
to carry out the test in the corresponding
switchgear panel. The switching capacity
may get a negative influence from the
different arrangement of the switchgear
with contact arms, moving contacts,
conductor bars, etc.
For this reason, the test duties T100s and
T100a from the IEC 62271-100 standard
are stipulated for the test of the circuit-
breaker inside the switchgear panel.
3. New partition classification
The new partition classes PM (partitions
metallic = partitions and shutters made
of metal) or PI (partitions nonmetallic =
partitions and shutters made of insulat-
ing material) now apply with respect to
the protection against electric shock dur-
ing access to the individual components.
The assignment is no longer according
to the constructional description (metal-
clad, compartmented or cubicle-type
design), but according to operator-related
criteria (Tables 1 and 2).
4. Stricter internal arc classification
Significantly stricter changes have also
been implemented here. The energy flow
direction of the arc supply, the maximum
number of permissible panels with the
test in the end panel and the dependency
of the ceiling height on the respective
panel height have been redefined. In
addition, the five following new criteria
must always be completely fulfilled (no
exceptions are permitted):
1) Covers and doors remain closed.
Limited deformations are accepted.
2) No fragmentation of the enclosure,
no projection of small parts above
60 g weight.
3) No holes in the accessible sides up
to a height of 2 meters.
4) Horizontal and vertical indicators do not
ignite due to the effect of hot gases.
5) The enclosure remains connected to
its earthing parts.
For the internal arc classification of
substations with and without control
aisle, the testing of the substation with
installed switchgear is mandatory in the
new IEC 62271-202 standard. The clas-
sification of the substation is only valid
in combination with the switchgear used
for the test. The classification cannot be
transferred to a combination with an-
other switchgear type as each switchgear
behaves differently in the case of an in-
ternal arc (pressure relief equipment with
different cross-sections and pickup pres-
sures, different arcing conditions because
of different conductor geometries).
New specifications –
new challenges
Overview of IEC 62271-200
4
Loss of service
continuity category	
When an accessible compartment of
the switchgear is opened: …	
Constructional design
LSC 1 … then the busbar and therefore
the complete switchgear must be
isolated.
No partitions within the panel, no
panel partition walls to adjacent
panels.
LSC 2 LSC 2A … then the incoming cable must be
isolated. The busbar and the adjacent
switchgear panels can remain in
operation.
Panel partition walls and isolating
distance with compartmentaliza-
tion to the busbar.
LSC 2B … then the incoming cable, the
busbar and the adjacent switchgear
panels can remain in operation.
Panel partition walls and isolating
distance with compartmentaliza-
tion to the busbar and to the cable.
The notation IAC A FLR, I and t contains the abbreviations for the following values:
IAC Internal Arc Classification
A
Distance between the indicators 300 mm, i.e. installation in rooms with access for
authorized personnel, closed electrical service location
FLR Access from the front (F), from the sides (L = lateral) and from the rear (R)
I Test current = rated short-circuit breaking current (in kA)
t Internal arc duration (in seconds)
Type of accessibility
to a compartment
Access features
Interlock-based Opening for normal operation and
maintenance, e.g. fuse replacement.
Access is controlled by the
construction of the switchgear,
i.e. integrated interlocks prevent
impermissible opening.
Procedure-based Opening for normal operation and
maintenance, e.g. fuse replacement.
Access control via a suitable pro-
cedure (work instruction of the
operator) combined with a locking
device (lock).
Tool-based Opening not for normal operation or
maintenance, e.g. cable testing.
Access only with tool for opening,
special access procedure
(instruction of the operator).
Nonaccessible Opening not possible / not intended for operator,
opening can destroy the compartment.
This applies generally to the gas-filled compartments of gas-insulated
switchgear. As the switchgear is maintenance-free and climate-indepen-
dent, access is neither required nor possible.
Table 2
Overview of the characteristic values
The IAC classification describes a success-
ful test. It results from the definition of
the degree of accessibility, the possibili-
ties of arrangement inside a room, as
well as the test current and test time
(Table 3).
Medium-voltage switchgear in the pri-
mary and secondary distribution level is
generally classified with degree of acces-
sibility A. This means they are intended
for use in rooms that are only accessible
to authorized personnel (closed electrical
service locations).
Switchgear that is accessible by general
public has the degree of accessibility B
(distance of indicators = 100 mm) and
polemounted switchgear has the degree
of accessibility C (indicators below a
tower in an area of 3 x 3 m).
Consequences for operators
With the new IEC 62271-200 standard,
the following conditions must be satisfied
by the switchgear operators:
Already existing switchgear can still be
operated in accordance with IEC 60298.
However, new switchgear must fulfill the
IEC 62271-200 standard in order to avoid
any resulting legal disadvantages. A situ-
ation which has a number of advantages.
For example, the comparison and evalu-
ation of switchgear features is now more
transparent. But also from an economic
point of view, they are an investment in
the future.
Table 1
Table 3
5
6
With intensive development work and
comprehensive tests, Siemens has al-
ready implemented the performance
features requested by IEC 62271-200 at
an early stage. As one of the first man-
ufacturers, we offer the entire product
range of air- and gas-insulated switch-
gear for medium-voltage applications
in primary and secondary distribution
systems today – type-tested according
to the new IEC 62271-200 standard.
A greater margin for your safety
Not only that: the more stringent require-
ments of the dielectric type tests have
been implemented without exception.
All switching capacity tests for the various
circuit-breakers and earthing switches
were performed in installed condition,
i.e. inside the switchgear panel with the
associated arrangement of the conducting
path, contacts, etc. This means for you as
the operator: One hundred percent cer-
tainty that this combination of switchgear
and switchgear panel functions reliably.
All switchgear series were also tested for
the internal arc classification in accordance
with the new standard. The maximum
permissible number of test objects (gener-
ally two or three panels) as well as the
changed direction of energy flow of the arc
supply significantly increased the demands
on the switchgear panels. All switchgear
certified in accordance with IEC 62271-
200 satisfies all five criteria required for
the internal arc test without exception.
Siemens medium-voltage switchgear
therefore corresponds to the IAC A FLR
classification for short-circuit currents up
to 50 kA (depending on the system type)
and short-circuit times up to one second.
Ready for the future – with Siemens
With the fulfillment of the new IEC 62271-
200 standard, all our switchgear types
represent the latest state of development
in technology, safety and reliability.
Without exception, Siemens switchgear
fulfills the internal arc classification as vital
proof of the personal safety. Our switch-
gear therefore also meets the require-
ments of CAPIEL – the European associa-
tion of national switchgear manufacturer
associations: “This is now a type test and
not anymore subject of agreement be-
tween manufacturer and user.”
An investment in the switchgear technol-
ogy made by Siemens is a profitable invest-
ment in the future.
With the successfully verified internal arc
classification, IAC A FLR up to 50 kA and
one second arc duration, our switchgear
offers maximum possible personal protec-
tion. Our type-tested series also entirely
fulfill the specifications of IEC 62271-200
in all aspects. In addition, they guarantee
the highest possible degree of operational
reliability and therefore an extremely low
failure rate.
Air- and gas-insulated switchgear
from Siemens in accordance with
IEC 62271-200
We are ready – to make you ready as well
OverviewofSiemensswitchgear
*MaximumpossibleIACclassification
Distribution
level
Insula-
tion
DesignLossofservicecon-
tinuity
Partition
class
Internalarcclassifi-
cation*
Switchgear
type
BusbarsystemVoltage
(kV)
Short-circuit
current(kA)
1s3s
Ratedcurrent,
busbar(A)
Ratedcurrent,
feeder(A)
PrimaryGas-
insulated
ExtendableLSC2B(panels
withoutHVHRCfuses)
LSC2A(panelswith
HVHRCfuses)
PMIACAFLR31,5kA,1sNXPLUSCSingle15
24
31,5
25
31,5
25
2500
2500
2500
2000
LSC2B(panels
withoutHVHRCfuses)
LSC2A(panelswith
HVHRCfuses)
PMIACAFLR25kA,1sNXPLUSCDouble24252525001250
LSC2BPMIACAFLR31,5kA,1sNXPLUSSingle40,531,531,525002500
LSC2BPMIACAFLR31,5kA,1sNXPLUSDouble3631,531,525002500
LSC2BPMIACAFL40kA,1s8DA10Single40,5404040002500
LSC2BPMIACAFL40kA,1s8DB10Double40,5404040002500
Air-
insulated
ExtendableLSC2BPMIACAFLR40kA,1sNXAIRSingle12404031503150
LSC2BPMIACAFLR40kA,1sNXAIRDouble12404031503150
LSC2BPMIACAFLR25kA,1sNXAIRMSingle24252525002500
LSC2BPMIACAFLR25kA,1sNXAIRMDouble24252525002500
LSC2BPMIACAFLR50kA,1sNXAIRPSingle15505040004000
LSC2BPMIACAFLR50kA,1sNXAIRPDouble15505040004000
LSC2BPMIACAFLR31,5kA,1sSIMOPRIMESingle17,531,531,531503150
LSC2APMIACAFLR25kA,1s8BT1Single24252520002000
LSC2BPMIACAFL31,5kA,1s8BT2Single3631,531,525002500
LSC1PMIACAFL16kA,1s8BT3Single36161612501250
SecondaryGas-
insulated
Non-
extendable
LSC2B(panels
withoutHVHRCfuses)
LSC2A(panelswith
HVHRCfuses)
PMIACAFL21kA,1s8DJ10Single17,5
24
25
20
20
20
630
630
630
630
LSC2B(panels
withoutHVHRCfuses)
LSC2A(panelswith
HVHRCfuses)
PMIACAFL21kA,1s8DJ20Single17,5
24
25
20
20
20
630
630
630
630
ExtendableLSC2B(panels
withoutHVHRCfuses)
LSC2A(panelswith
HVHRCfuses)
PMIACAFLR21kA,1s8DH10Single17,5
24
25
20
20
20
1250
1250
630
630
Air-
insulated
ExtendableLSC2B(panels
withoutHVHRCfuses)
LSC2A(panelswith
HVHRCfuses)
PMIACAFLR20kA,1sSIMOSECSingle17,5
24
25
20
11,5
20
1250
1250
1250
1250

More Related Content

What's hot

ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
Thorne & Derrick International
 
ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...
ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...
ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...
Thorne & Derrick International
 

What's hot (20)

New VD4-Rockwill
New VD4-RockwillNew VD4-Rockwill
New VD4-Rockwill
 
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum ContactorsABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
ABB IEC Indoor Vacuum Contactors VSC - Medium Voltage Vacuum Contactors
 
07 - ELCB - Fuji Electric
07 - ELCB - Fuji Electric07 - ELCB - Fuji Electric
07 - ELCB - Fuji Electric
 
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge ArrestersABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
ABB Low Voltage LV Surge Arresters - ABB LOVOS 5 and LOVOS 10 Surge Arresters
 
Mv design guide
Mv design guideMv design guide
Mv design guide
 
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...ABB Medium Voltage MV Surge Arresters -  AC & DC Surge Arresters & Protection...
ABB Medium Voltage MV Surge Arresters - AC & DC Surge Arresters & Protection...
 
RLW type pole mounted vacuum load break switch
RLW type pole mounted vacuum load break switchRLW type pole mounted vacuum load break switch
RLW type pole mounted vacuum load break switch
 
ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...
ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...
ABB LOVOS Low Voltage Surge Arresters Presentation - Surge Arresters, Plugs &...
 
Air insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kvAir insulated sf6 ring main unit 36kv
Air insulated sf6 ring main unit 36kv
 
Training Adobe
Training AdobeTraining Adobe
Training Adobe
 
ROCKWELL Transformers
ROCKWELL TransformersROCKWELL Transformers
ROCKWELL Transformers
 
Catalogue ELCB Fuji - Earth Leakage Circuit Breaker Fuji - Beeteco.com
 Catalogue ELCB Fuji - Earth Leakage Circuit Breaker  Fuji - Beeteco.com Catalogue ELCB Fuji - Earth Leakage Circuit Breaker  Fuji - Beeteco.com
Catalogue ELCB Fuji - Earth Leakage Circuit Breaker Fuji - Beeteco.com
 
M type Pole mounted Vacuum type Auto recloser catalog
M type Pole mounted Vacuum type Auto recloser catalogM type Pole mounted Vacuum type Auto recloser catalog
M type Pole mounted Vacuum type Auto recloser catalog
 
01 - Contactor - Fuji Electric
 01 - Contactor - Fuji Electric 01 - Contactor - Fuji Electric
01 - Contactor - Fuji Electric
 
RPS-SF6LBS-PKE
RPS-SF6LBS-PKERPS-SF6LBS-PKE
RPS-SF6LBS-PKE
 
Abb low voltage lv capacitors, abb clmd
Abb low voltage lv capacitors, abb clmd  Abb low voltage lv capacitors, abb clmd
Abb low voltage lv capacitors, abb clmd
 
Technological centre
Technological centreTechnological centre
Technological centre
 
RBM Type Outdoor metering unit catalog
RBM Type Outdoor metering unit catalogRBM Type Outdoor metering unit catalog
RBM Type Outdoor metering unit catalog
 
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo PhươngCatalog contactor fuji-electric Mới Nhất - Hạo Phương
Catalog contactor fuji-electric Mới Nhất - Hạo Phương
 
RLS type indoor SF6 load break switch(Disconnector)
RLS type indoor SF6 load break switch(Disconnector)RLS type indoor SF6 load break switch(Disconnector)
RLS type indoor SF6 load break switch(Disconnector)
 

Similar to 06612 iec zerti_rz11_e

Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
JoeChueng
 
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Emeka Ojeah
 

Similar to 06612 iec zerti_rz11_e (20)

High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
High Voltage Gas Insulated Substation (GIS) Routine Tests According to IEEE C...
 
Power factor corrector
Power factor correctorPower factor corrector
Power factor corrector
 
Kyn28 metal clad switchgear
Kyn28 metal clad switchgearKyn28 metal clad switchgear
Kyn28 metal clad switchgear
 
2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards2015 Arc Flash Conference MV Switchgear Standards
2015 Arc Flash Conference MV Switchgear Standards
 
KYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgearKYN28 12kV Medium voltage metal clad switchgear
KYN28 12kV Medium voltage metal clad switchgear
 
Air insulated sf6 ring main unit
Air insulated sf6 ring main unitAir insulated sf6 ring main unit
Air insulated sf6 ring main unit
 
Air insulated sf6 ring main unit
Air insulated sf6 ring main unitAir insulated sf6 ring main unit
Air insulated sf6 ring main unit
 
Standing type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unitStanding type outdoor full sf6 gas insualted ring main unit
Standing type outdoor full sf6 gas insualted ring main unit
 
Standing type GIS RMU
Standing type GIS RMUStanding type GIS RMU
Standing type GIS RMU
 
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKERDIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
DIGITAL TESTING OF HIGH VOLTAGE CIRCUIT BREAKER
 
A study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendmentsA study on IEC 60947- 2 amendments
A study on IEC 60947- 2 amendments
 
3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf3D_Distribution transformer_Specification.pdf
3D_Distribution transformer_Specification.pdf
 
Gis4
Gis4Gis4
Gis4
 
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
AC High voltage Air Break Disconnector Switch Routine Test According to IEC 6...
 
Ac Test Transformer
Ac Test TransformerAc Test Transformer
Ac Test Transformer
 
Isolator and bushing
Isolator and bushingIsolator and bushing
Isolator and bushing
 
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
Gabriel Ojeah - HV CONFERENCE PAPER- PERTH 2015
 
5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd5 is 1554_2_pvc cables hd
5 is 1554_2_pvc cables hd
 
Switchgear presentation
Switchgear presentationSwitchgear presentation
Switchgear presentation
 
SEMA 2016 - Introduction to Transformer Rated Metering
SEMA 2016 -  Introduction to Transformer Rated MeteringSEMA 2016 -  Introduction to Transformer Rated Metering
SEMA 2016 - Introduction to Transformer Rated Metering
 

More from Cesar Chilet (6)

Apuntes_Malla_de_tierra_2011.pdf
Apuntes_Malla_de_tierra_2011.pdfApuntes_Malla_de_tierra_2011.pdf
Apuntes_Malla_de_tierra_2011.pdf
 
ieee-generator-protection-tutorial-presentation.pdf
ieee-generator-protection-tutorial-presentation.pdfieee-generator-protection-tutorial-presentation.pdf
ieee-generator-protection-tutorial-presentation.pdf
 
costo de energia
costo de energiacosto de energia
costo de energia
 
calidad de energia
calidad de energiacalidad de energia
calidad de energia
 
Trafo seco
Trafo secoTrafo seco
Trafo seco
 
Presentacion iec-62271-200
Presentacion iec-62271-200Presentacion iec-62271-200
Presentacion iec-62271-200
 

Recently uploaded

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Kandungan 087776558899
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
dharasingh5698
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak HamilCara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
Cara Menggugurkan Sperma Yang Masuk Rahim Biyar Tidak Hamil
 
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
Navigating Complexity: The Role of Trusted Partners and VIAS3D in Dassault Sy...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar  ≼🔝 Delhi door step de...
Call Now ≽ 9953056974 ≼🔝 Call Girls In New Ashok Nagar ≼🔝 Delhi door step de...
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
NFPA 5000 2024 standard .
NFPA 5000 2024 standard                                  .NFPA 5000 2024 standard                                  .
NFPA 5000 2024 standard .
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
(INDIRA) Call Girl Bhosari Call Now 8617697112 Bhosari Escorts 24x7
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoorTop Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
Top Rated Call Girls In chittoor 📱 {7001035870} VIP Escorts chittoor
 
KubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghlyKubeKraft presentation @CloudNativeHooghly
KubeKraft presentation @CloudNativeHooghly
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Intro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdfIntro To Electric Vehicles PDF Notes.pdf
Intro To Electric Vehicles PDF Notes.pdf
 
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort ServiceCall Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
Call Girls in Netaji Nagar, Delhi 💯 Call Us 🔝9953056974 🔝 Escort Service
 

06612 iec zerti_rz11_e

  • 1. Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact our Customer Support Center, 24 hours a day. Tel.: +49 180 / 524 70 00 Fax: +49 180 / 524 24 71 (Subject to charge: e.g. 12 ct/min) E-mail: support.energy@siemens.com www.siemens.com/energy-support Subject to change without prior notice Order no. E50001-U229-A282-X-7600 Printed in Germany Dispo 30403 GB 06612 101976 08064. The information in this document contains general descriptions of the technical features, which may not always be available. An obligation to provide the respective performance feature shall exist only if expressly agreed in the terms of contract.
  • 2. Power Transmission and Distribution We are ready: IEC 62271-200 The new switchgear standard
  • 3. Standards for all Switchgear are important nodal points in modern power distribution. Corre- spondingly important is their reliable functioning, a clearly defined switch- ing behavior according to specified parameters as well as the protection of personnel and protection against oper- ational interruptions when an overload occurs. The International Electrotechnical Commission (IEC) has taken up the task of developing the required speci- fications, their worldwide standard- ization and further development. The same applies to IEC 62271-200 – the new standard for medium-voltage switchgear. As one of the first manufacturers, Siemens has implemented these requirements and already offers the complete product range of air-insu­ lated and gas-insulated switchgear today, type-tested according to IEC 62271-200. 2 IEC 62271-200 IEC 62271-200
  • 4. IEC 60298 – for four decades this abbre- viation was the decisive factor for the type testing of metal-enclosed switchgear. In the meantime there are tens of thousands of switchgear panels of the primary and secondary distribution level based on this standard in use – certified according to the mandatory part of the standard and, if required, according to optional tests. The passing of the following tests was obligatory in order to identify switchgear as type-tested: Dielectric test to verify the insulation level of the switchgear (tests with rated lightning impulse withstand voltage and rated short-duration power frequency withstand voltage with the specified values depending on the respective rated voltage). Temperature rise tests to verify the current carrying capacity with rated normal currents. Peak and short-time withstand current tests to verify the dynamic and thermal current carrying capacity of the main and earth circuits; the tests are performed with rated peak short-circuit current or rated short-circuit making current or rated short- time current or rated short-circuit breaking current. Switching capacity test to verify the making/breaking capacity of the installed switchgear. Mechanical function test to verify the mechanical functions and interlocks. Degree of protection tests to verify the protection against electric shock and foreign objects. Pressure and strength tests to verify the gas tightness and pressure resistance for gas-filled switchgear. There is also the possibility of voluntarily certifying switchgear for resistance to inter- nal arc faults and for personal protection. Manufacturers and operators can select the criteria which are relevant to them from the following six criteria and have them tested. Criterion 1: Doors and covers must not open. Criterion 2: Parts of the switchgear must not fly off. Criterion 3: Holes must not develop in the external parts of the enclosure. Criterion 4: Vertical indicators must not ignite. Criterion 5: Horizontal indicators must not ignite. Criterion 6: Earth connections must remain effective. In order to guarantee safe access to the individual switchgear components, e.g.the incoming cable, without isolating the busbar, the IEC 60298 standard differentiates bet­ ween three types of compartmentalization that serve exclusively as protection against electric shock. Metal-clad switchgear: Division of the switchgear panel into four compartments (busbar compartment, switching-device compartment, connection compartment and low-voltage compartment); partitions between the compartments made of sheet steel, front plate made of sheet steel or insulating material. Compartmented switchgear: Division of the switchgear panel same as for metal-clad switchgear, but with the partitions between the individual compartments made of insu- lating material. Cubicle-type switchgear: All other types of construction that do not meet the above features of the metal-clad or compartmented designs. In this context, access to the then common minimum-oil-content circuit-breakers for maintenance work without longer opera- tional interruptions was of prime importance because of the limited number of operating cycles. Therefore, with switchgear in metal- clad or compartmented design, the busbar in the busbar compartment and the incom- ing cable in the connection compartment could remain in operation. With a cubicle- type design, the incoming cable had to be isolated, but the busbar itself could remain in operation. Retrospective 3
  • 5. Although the old IEC 60298 standard was very helpful, in time it was super- seded by the technological progress. Above all, the appearance of mainte- nance-free vacuum circuit-breakers, with operating cycles far exceeding the normal number, made frequent access to this circuit-breaker no longer of prime importance. The vacuum arc-quenching principle is technologically so superior to other arc-quenching principles that the circuit-breaker can be fixed-mounted again. This resulted in the first-time use of gas insulation with the impor- tant features of climatic independence, compactness and maintenance-free de- sign. However, both technologies – the vacuum arc-quenching principle and gas insulation – were not adequately taken into account in the existing standard. Therefore, at the end of the nine- ties, the responsible IEC committees decided on the reformulation of the switchgear standard, which finally came into effect as IEC 62271-200 in November 2003. At the same time the old IEC 60298 standard was withdrawn without any transition period. Four key features are of special note with the new IEC 62271-200 standard: 1. Changed dielectric requirements According to IEC 60298, two disruptive discharges were permitted in a series of 15 voltage impulses for the test with rated lightning impulse withstand voltage. Ac- cording to the new standard, the series must be extended by another five voltage impulses if a disruptive discharge has oc- curred during the first 15 impulses. This can lead to a maximum of 25 voltage impulses, whereas the maximum number of permis- sible disruptive discharges is still two. 2. Increased demands on the circuit- breaker and earthing switch In contrast to the previous standard, the switching capacity test of both switching devices is no longer carried out as a pure device test. Instead, it is now mandatory to carry out the test in the corresponding switchgear panel. The switching capacity may get a negative influence from the different arrangement of the switchgear with contact arms, moving contacts, conductor bars, etc. For this reason, the test duties T100s and T100a from the IEC 62271-100 standard are stipulated for the test of the circuit- breaker inside the switchgear panel. 3. New partition classification The new partition classes PM (partitions metallic = partitions and shutters made of metal) or PI (partitions nonmetallic = partitions and shutters made of insulat- ing material) now apply with respect to the protection against electric shock dur- ing access to the individual components. The assignment is no longer according to the constructional description (metal- clad, compartmented or cubicle-type design), but according to operator-related criteria (Tables 1 and 2). 4. Stricter internal arc classification Significantly stricter changes have also been implemented here. The energy flow direction of the arc supply, the maximum number of permissible panels with the test in the end panel and the dependency of the ceiling height on the respective panel height have been redefined. In addition, the five following new criteria must always be completely fulfilled (no exceptions are permitted): 1) Covers and doors remain closed. Limited deformations are accepted. 2) No fragmentation of the enclosure, no projection of small parts above 60 g weight. 3) No holes in the accessible sides up to a height of 2 meters. 4) Horizontal and vertical indicators do not ignite due to the effect of hot gases. 5) The enclosure remains connected to its earthing parts. For the internal arc classification of substations with and without control aisle, the testing of the substation with installed switchgear is mandatory in the new IEC 62271-202 standard. The clas- sification of the substation is only valid in combination with the switchgear used for the test. The classification cannot be transferred to a combination with an- other switchgear type as each switchgear behaves differently in the case of an in- ternal arc (pressure relief equipment with different cross-sections and pickup pres- sures, different arcing conditions because of different conductor geometries). New specifications – new challenges Overview of IEC 62271-200 4
  • 6. Loss of service continuity category When an accessible compartment of the switchgear is opened: … Constructional design LSC 1 … then the busbar and therefore the complete switchgear must be isolated. No partitions within the panel, no panel partition walls to adjacent panels. LSC 2 LSC 2A … then the incoming cable must be isolated. The busbar and the adjacent switchgear panels can remain in operation. Panel partition walls and isolating distance with compartmentaliza- tion to the busbar. LSC 2B … then the incoming cable, the busbar and the adjacent switchgear panels can remain in operation. Panel partition walls and isolating distance with compartmentaliza- tion to the busbar and to the cable. The notation IAC A FLR, I and t contains the abbreviations for the following values: IAC Internal Arc Classification A Distance between the indicators 300 mm, i.e. installation in rooms with access for authorized personnel, closed electrical service location FLR Access from the front (F), from the sides (L = lateral) and from the rear (R) I Test current = rated short-circuit breaking current (in kA) t Internal arc duration (in seconds) Type of accessibility to a compartment Access features Interlock-based Opening for normal operation and maintenance, e.g. fuse replacement. Access is controlled by the construction of the switchgear, i.e. integrated interlocks prevent impermissible opening. Procedure-based Opening for normal operation and maintenance, e.g. fuse replacement. Access control via a suitable pro- cedure (work instruction of the operator) combined with a locking device (lock). Tool-based Opening not for normal operation or maintenance, e.g. cable testing. Access only with tool for opening, special access procedure (instruction of the operator). Nonaccessible Opening not possible / not intended for operator, opening can destroy the compartment. This applies generally to the gas-filled compartments of gas-insulated switchgear. As the switchgear is maintenance-free and climate-indepen- dent, access is neither required nor possible. Table 2 Overview of the characteristic values The IAC classification describes a success- ful test. It results from the definition of the degree of accessibility, the possibili- ties of arrangement inside a room, as well as the test current and test time (Table 3). Medium-voltage switchgear in the pri- mary and secondary distribution level is generally classified with degree of acces- sibility A. This means they are intended for use in rooms that are only accessible to authorized personnel (closed electrical service locations). Switchgear that is accessible by general public has the degree of accessibility B (distance of indicators = 100 mm) and polemounted switchgear has the degree of accessibility C (indicators below a tower in an area of 3 x 3 m). Consequences for operators With the new IEC 62271-200 standard, the following conditions must be satisfied by the switchgear operators: Already existing switchgear can still be operated in accordance with IEC 60298. However, new switchgear must fulfill the IEC 62271-200 standard in order to avoid any resulting legal disadvantages. A situ- ation which has a number of advantages. For example, the comparison and evalu- ation of switchgear features is now more transparent. But also from an economic point of view, they are an investment in the future. Table 1 Table 3 5
  • 7. 6 With intensive development work and comprehensive tests, Siemens has al- ready implemented the performance features requested by IEC 62271-200 at an early stage. As one of the first man- ufacturers, we offer the entire product range of air- and gas-insulated switch- gear for medium-voltage applications in primary and secondary distribution systems today – type-tested according to the new IEC 62271-200 standard. A greater margin for your safety Not only that: the more stringent require- ments of the dielectric type tests have been implemented without exception. All switching capacity tests for the various circuit-breakers and earthing switches were performed in installed condition, i.e. inside the switchgear panel with the associated arrangement of the conducting path, contacts, etc. This means for you as the operator: One hundred percent cer- tainty that this combination of switchgear and switchgear panel functions reliably. All switchgear series were also tested for the internal arc classification in accordance with the new standard. The maximum permissible number of test objects (gener- ally two or three panels) as well as the changed direction of energy flow of the arc supply significantly increased the demands on the switchgear panels. All switchgear certified in accordance with IEC 62271- 200 satisfies all five criteria required for the internal arc test without exception. Siemens medium-voltage switchgear therefore corresponds to the IAC A FLR classification for short-circuit currents up to 50 kA (depending on the system type) and short-circuit times up to one second. Ready for the future – with Siemens With the fulfillment of the new IEC 62271- 200 standard, all our switchgear types represent the latest state of development in technology, safety and reliability. Without exception, Siemens switchgear fulfills the internal arc classification as vital proof of the personal safety. Our switch- gear therefore also meets the require- ments of CAPIEL – the European associa- tion of national switchgear manufacturer associations: “This is now a type test and not anymore subject of agreement be- tween manufacturer and user.” An investment in the switchgear technol- ogy made by Siemens is a profitable invest- ment in the future. With the successfully verified internal arc classification, IAC A FLR up to 50 kA and one second arc duration, our switchgear offers maximum possible personal protec- tion. Our type-tested series also entirely fulfill the specifications of IEC 62271-200 in all aspects. In addition, they guarantee the highest possible degree of operational reliability and therefore an extremely low failure rate. Air- and gas-insulated switchgear from Siemens in accordance with IEC 62271-200 We are ready – to make you ready as well
  • 8. OverviewofSiemensswitchgear *MaximumpossibleIACclassification Distribution level Insula- tion DesignLossofservicecon- tinuity Partition class Internalarcclassifi- cation* Switchgear type BusbarsystemVoltage (kV) Short-circuit current(kA) 1s3s Ratedcurrent, busbar(A) Ratedcurrent, feeder(A) PrimaryGas- insulated ExtendableLSC2B(panels withoutHVHRCfuses) LSC2A(panelswith HVHRCfuses) PMIACAFLR31,5kA,1sNXPLUSCSingle15 24 31,5 25 31,5 25 2500 2500 2500 2000 LSC2B(panels withoutHVHRCfuses) LSC2A(panelswith HVHRCfuses) PMIACAFLR25kA,1sNXPLUSCDouble24252525001250 LSC2BPMIACAFLR31,5kA,1sNXPLUSSingle40,531,531,525002500 LSC2BPMIACAFLR31,5kA,1sNXPLUSDouble3631,531,525002500 LSC2BPMIACAFL40kA,1s8DA10Single40,5404040002500 LSC2BPMIACAFL40kA,1s8DB10Double40,5404040002500 Air- insulated ExtendableLSC2BPMIACAFLR40kA,1sNXAIRSingle12404031503150 LSC2BPMIACAFLR40kA,1sNXAIRDouble12404031503150 LSC2BPMIACAFLR25kA,1sNXAIRMSingle24252525002500 LSC2BPMIACAFLR25kA,1sNXAIRMDouble24252525002500 LSC2BPMIACAFLR50kA,1sNXAIRPSingle15505040004000 LSC2BPMIACAFLR50kA,1sNXAIRPDouble15505040004000 LSC2BPMIACAFLR31,5kA,1sSIMOPRIMESingle17,531,531,531503150 LSC2APMIACAFLR25kA,1s8BT1Single24252520002000 LSC2BPMIACAFL31,5kA,1s8BT2Single3631,531,525002500 LSC1PMIACAFL16kA,1s8BT3Single36161612501250 SecondaryGas- insulated Non- extendable LSC2B(panels withoutHVHRCfuses) LSC2A(panelswith HVHRCfuses) PMIACAFL21kA,1s8DJ10Single17,5 24 25 20 20 20 630 630 630 630 LSC2B(panels withoutHVHRCfuses) LSC2A(panelswith HVHRCfuses) PMIACAFL21kA,1s8DJ20Single17,5 24 25 20 20 20 630 630 630 630 ExtendableLSC2B(panels withoutHVHRCfuses) LSC2A(panelswith HVHRCfuses) PMIACAFLR21kA,1s8DH10Single17,5 24 25 20 20 20 1250 1250 630 630 Air- insulated ExtendableLSC2B(panels withoutHVHRCfuses) LSC2A(panelswith HVHRCfuses) PMIACAFLR20kA,1sSIMOSECSingle17,5 24 25 20 11,5 20 1250 1250 1250 1250