Study of the thermal behaviour of a reused rural
building.
Ignacio Cañas1
, Silvia Martin1
and Jose Maria Fuentes1
1
Departamento de Construccion y Vias Rurales.
Escuela Técnica Superior de Ingenieros Agrónomos.
Avda Complutense s/n. 28040 Madrid
ABSTRACT: In this article the thermal behaviour of a reused rural building is analyzed. Spanish rural
areas are suffering the problem of depopulation with the loss of lot of traditional buildings.
The reuse of these buildings is a system for saving the loss of rural heritage that is causing the loss
of regional identities. The particular case studied here is an old building for sheep accommodation,
this type of building was common in the interior areas of Spain due to the agrarian way of life. The
owners bought the building some years ago with the aim of constructing a rural hotel. For the
construction of the new building they followed some criterions based on the bioclimatic design. The
study carried out tries to examine the thermal behaviour of this building by means of registering the
temperature and relative humidity in some points inside it. The results show that instead of the harsh
climatic conditions happening outside, the interior temperature is inside the comfort limits. This study
shows that the reuse of rural buildings, in addition of the economic and social advantages, is a
system of reducing energy consumption in the life cycle of the building.
Conference Topic: 6, Recycled architecture (re-use, upgrading and rehabilitation of buildings)
Keywords: reuse, thermal behaviour
1. INTRODUCTION. 2. BUILDING CHARACTERISTICS.
In Spain there is a great amount of rural buildings
( rural houses, stables, agricultural machinery stores,
dovecotes, …) abandoned from the fifties due to the
rural exodus.
The studied building is placed in a small town called
Covachuelas in the province of Segovia (Castilla y
Leon). The town was uninhabited in the fifties. The
altitude is 1005 m above sea level, and it is 120 km
far away from Madrid (see figure 1).
The reuse of old buildings provide an environmental
advantage because of the reduction in energy use
and building materials compared to a new
construction. The life cycle of reusing an old building
has less steps than constructing a new one. In
addition, the reuse of old buildings has social and
cultural advantages, as maintenance of regional
texture, scale and history, and the preservation of
local identity of traditional architecture.
One of the problems about the reuse of rural buildings
is their remoteness to large population centres and
the poor quality of infrastructure in rural areas. New
leisure alternatives offer the possibility of using again
this type of buildings. Give a new use to abandoned
rural buildings involves the presence of new people
and activities in rural areas, therefore the economy
could be improved.
In this paper the results from the monitoring of a
reused rural building during summer are shown.
The building was an abandoned sheep house that
was turned into a rural hotel. The rehabilitation of the
building was made following bioclimatic criterions.
The aim of this paper is to study the hygro-thermal
conditions inside this building.
Figure 1: Map of location.
Plea2004 - The 21
th
Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22
September 2004 Page 2 of 6
The area is characterized by a continental climate
with great temperature oscillations. The absolute
maximum temperature in the hottest month is 39º C,
and the absolute minimum temperature in the coldest
month is –15º C. The mean annual precipitation is
470 mm (see figure 2).
Climate in Covachuelas
0
5
10
15
20
25
30
35
January
February
March
April
May
June
July
August
September
October
November
December
T
(ºC)
0
10
20
30
40
50
60
70
P
(mm)
TM
Tm
P
Figure 4: The building after the rehabilitation.
2.1. Rehabilitation characteristics:
- All building materials used in the rehabilitation
works have low environmental impact.
Figure 2: Summary of climatic conditions in
Covachuelas. TM: monthly average of daily maximum
temperature; Tm: monthly average of daily minimum
temperature; P: monthly precipitation. Source:
National Institute of Meteorology. Weather station in
Segovia (1971 – 2000)
- Compressed earth blocks were made from local
soils. The use of this building material has two
advantages: the same colour as that found in
traditional architecture, and good thermal behaviour.
- The insulation was made of natural materials (pure
wool).
- A glazed surface was constructed in a part of the
roof oriented to South with the aim of making better
use of solar radiation in winter (greenhouse effect).
Finally, the glazed surface on the roof was larger
than that calculated in the rehabilitation project due to
several problems with the subvention for the solar
panels.
In the studied area there is plentiful use of earth as a
building material in popular architecture. This material
is very typical of some Spanish regions where the
lack of another building materials joined to the good
quality of their soils make it a suitable material as well
as ecologic.
The old sheep house was a large building constructed
of stone masonry and sun-dried bricks. When the
current owners bought the building, it was almost in
ruins. They wanted to build a rural accommodation.
The rehabilitation process aimed at keeping the
typology of regional traditional architecture as well as
incorporate some building elements from bioclimatic
design.
- The drop of the terrain was used for burying in part
the north façade, so it is less exposed to the
environment and has high thermal inertia like
underground constructions.
- The building uses renewable energy: wind power,
thermal and electric solar energy.
- The plumbing system allows to separate sewage
from washes and also to collect rainwater in a small
pond.
Figure 3: The building before the rehabilitation.
Figure 5: Elevation of the building, showing the
glazed surface on the roof oriented to South.
Plea2004 - The 21
th
Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22
September 2004 Page 3 of 6
3. ENERGY SAVING ON BUILDING
MATERIALS.
As indicated previously, the building materials used in
the rehabilitation works were selected following
environmental criterions. The embodied energy of the
selected materials is low, so the impact derived from
the construction phase is reduced (table 1).
Table 1: Embodied energy in various building
materials. Source: Sinha, 1997.
Material Embodied energy (MJ/kg)
Earth 0,1
Natural cement 3,8
Plaster 3,1
Aluminium 97,2
Local wood 0,72
Foreign wood 5,04
Glass 28,15
Plastic 162
In addition, the reuse of the building by itself involves
a reduction of the environmental impact due to the
elimination of some phases of the construction cycle.
In the studied case, demolition works were not
required and neither land preparation jobs previous to
the construction were done. Therefore, the energy
needed to reuse the abandoned building is less than
that needed in constructing a new building
completely.
The compressed earth block technique has the next
advantages:
- The compressed earth blocks can be made in the
same place where the building will be constructed, by
using local and plentiful material (soil), so the
transport and extraction costs are almost zero.
- The thermal behaviour of compressed earth
blocks is better than other building materials, so they
produce energy saving on insulation as well as indoor
comfort conditions (this subject is analyzed in the rest
of this paper, showing the results from the monitoring)
(table 2).
Table 2: Physical properties of adobe. Source:
Domínguez, 1998.
Property Value
Density 1200 – 1700 kg/m3
Ice resistance Low
Exposure to elements Low
Specific heat 0.85 kJ/kg
Thermal conductivity 0.46 – 0.81 W/mK
Thermal wave dampening
coefficient
(40 cm)
5 – 10 %
Daily gap (Outdoor – indoor
thermal wave)
10 – 12 h
Fire resistance Good
- The elaboration process does not need the use
of heavy machinery or working place, so the energetic
cost is also very low (table 3).
- The economic saving is helped by the low cost of
the soil/earth extracted from the local area.
- This construction system is low technological. It
does not require specialized workers, so it is suitable
for self-construction, therefore it can be another way
of economic saving. In addition, it can solve the
problem of rural depopulation because it can provide
job to rural people.
Table 3: Energy added during the manufacture
process of compressed earth blocks. Source:
Barbeta, 2000.
Concept Quantity Energy Energy/block Energy/kg
Earth 4,2 kg 0,1
MJ/kg
0,42 MJ 0,07
Natural
cement
0,65 kg 3,8
MJ/kg
2,47 MJ 0,42
Plaster 0,35 kg 3,1
MJ/kg
1,08 MJ 0,18
Water 0,87 kg 0 0 0
Energy cost
in
manufacture
0 0 0 0
TOTAL 3,97 MJ/block 0,67 MJ/kg
4. MEASUREMENT SCHEME.
In order to analyze the hygro-thermal behaviour of
this building, the monitoring of indoor and outdoor
conditions was carried out.
The measurement instruments used are:
- Data logger called Hobo H8 HR/Temp (H08-003-
02) for the measuring of temperature and relative
humidity inside the building. Its resolution is 0.4º C for
temperature and its accuracy for relative humidity is
5%.
- Data logger called Hobo Pro HR/Temp (H08-032-
08) for the measuring of the external conditions. Its
resolution is 0.02º C for temperature and its accuracy
for relative humidity is 3%.
- Data logger connected to a pyranometer for the
measuring of the global solar radiation. Its accuracy is
2%.
Inside the building the temperature was recorded in 7
points:
(i) inside the storeroom, which is placed on the
north part of the ground floor
(ii) in the kitchen, placed also in the north part on the
ground floor
(iii) in the hall on the ground floor (*)
(iv) under the glazed surface, on the ground floor
(v) inside a bedroom placed in the north part on the
first floor
(vi) in the corridor on the first floor (*)
(vii) in the south part on the first floor (*)
In the three points marked with asteriks, the relative
humidity was also recorded.
5. RESULTS.
The results from the monitoring carried out from 11 to
27 August, 2003, are showed below. Unfortunately
there have been failures in some instruments and the
Plea2004 - The 21
th
Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22
September 2004 Page 4 of 6
conditions in the north part on the ground floor was
not measured. Temperature comparison
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
08/18/03 08/19/03 08/20/03 08/21/03
ºC
Corridor in first floor North zone in first floor
South zone ground floor Outside
South zone in first floor
Figure 6: Comparison between indoor and outdoor
temperature (18
th
– 21
st
of August, 2003).
5.1. Outside conditions:
The maximum temperature recorded was 38.7º C at
15:00 on August , the 13th
, the minimum was 9.3º C at
7:00 on August, the 27
th
. The mean temperature was
22.9º C with an oscillation of 29.4º C.
The maximum relative humidity registered was 97%,
the minimum was 8% and the average was 48%.
The maximum value of global solar radiation recorded
was 1078 W/m2.
5.2. Indoor conditions:
- Ground floor:
On the ground floor the only recorded data are those
from the south part. This zone are affected by the
large glazed surface on the roof, whose purpose is to
be used as a solar collector during winter time when
the temperature is extremely cold.
The maximum temperature recorded was 28.7º C at
14:00 on August, the 14
th
, the minimum temperature
was 21.2º C at 8:00 on August, the 27th
. The average
temperature was 25.1º C with an oscillation of 7.5º C.
Relative humidity comparison
0.00
20.00
40.00
60.00
80.00
100.00
08/18/03 08/19/03 08/20/03 08/21/03
(%)
First Floor Ground floor Outside
Figure 7: Comparison between indoor and outdoor
relative humidity (18
th
– 21
st
of August, 2003).
The maximum relative humidity was 60%, the
minimum was 21% and the average was 39%.
- First Floor:
On the first floor there are three monitored points: the
corridor, the south zone and the bedroom oriented to
North.
In the corridor the maximum temperature registered
was 30.7º C from 18:30 to 19:30 on 13
th
of August.
The minimum temperature was 19º C at 7:30 on 27th
of August. The average temperature was 25.9º C with
an oscillation of 11.7º C. On the other hand, the
maximum relative humidity was 55%, the minimum
was 24% and the average was 35%.
In the south zone the maximum temperature
registered was 34.9º C at 15:00 on 13
th
of August.
The minimum temperature was 21.7º C. The average
temperature was 26.8º C with an oscillation of 13.2º
C.
In figures 8, 9, 10 and 11the level of cooling / heating
registered (indoor temperature – outdoor
temperature) against outdoor temperature is showed.
As it can be seen in the figures, there is a clear
overheating effect in the corridor and in the south
zone on the first floor. The poor level of natural
cooling is not able to move the points inside the
comfort band (which is around 24º C ±2º C). In the
the corridor most of points showing discomfort due to
overheating are placed between 27ºC and 30ºC. In
the south area there are some cases (10% of
measurements) near 35ºC. In the north zone the
points showing overheating are below 30º C, and
most of them are between 26ºC and 28ºC. In the
ground floor all measurements are below 29ºC, most
of them are between 26ºC and 27ºC (when the
outdoor temperature registered is in 20% of
measurements higher than 30ºC). From this analysis
we assert that the thermal behaviour of the building
can be improved. The indoor conditions registered
are much less extreme than that registered outside,
however in the corridor and the south zone on the first
floor there is an overheating effect.
In the bedroom oriented to North the maximum
temperature registered was 29.9º C from 19:30 to
00:30 on 13
th
of August. The minimum temperature
was 21.7º C at 5:30 on 21
st
of August. The average
temperature was 26.2º C with an oscillation of 8.2º C.
Figures 6 and 7 show the temperature and relative
humidity measurements during 4 days of monitoring
(18
th
– 21
st
of August, 2003).
The places where the maximum temperature is higher
are the corridor and the south area on the first floor, in
addition these two points show the higher
temperature oscillations. The North orientation and
the ground floor have the ability to control the
temperature in lower levels and more constant than
other parts of the building.
Plea2004 - The 21
th
Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22
September 2004 Page 5 of 6
In figure 12 the variation of indoor temperature with
regard to outdoor temperature is studied. The aim of
this analysis is to determine the influence of outdoor
conditions on the indoor ones.
Figure 8: Natural cooling/heating in the corridor on
the first floor.
From the figure the tendency lines where calculated,
where x is the outdoor temperature and y is the
indoor temperature for each point:
- in the south area on the first floor the tendency line
and the corresponding error factor are:
y= 0.3379x + 19.01 R2= 0.7408
- in the bedroom oriented to North on the first floor:
y= 0.0734x + 24.539 R2= 0.0721
The previous ecuations show that the temperature
recorded in the south area on the first floor are more
dependent on the outside temperature than that
measured in the bedroom oriented to North (first
floor). The results proves the effect of orientation as
shock absorber. In our latitudes it is better the north
orientation to achieve comfort conditions in summer.
Figure 9: Natural cooling/heating in the south zone
on the first floor.
Variation of inside temperatures according to
outside temperatures
18.00
20.00
22.00
24.00
26.00
28.00
30.00
32.00
34.00
36.00
0.00 10.00 20.00 30.00 40.00 50.00
T outside (ºC)
T
inside
(ºC) T corridor in first floor
T south area in first floor
T north area in first floor
T ground floor
Figure 12: Variation of inside temperatures according
to outside ones.
Figure 10: Natural cooling/heating in the north zone
on the first floor.
6. CONCLUSIONS.
From the data analysis and despite the lack of
measurements in most zones of ground floor, the next
conclusions were obtained:
- In this reused rural building the conservation of the
existing stone masonry walls joined to the excavation
in the north part of the ground floor below the ground
level, make the hygro-thermal conditions in this floor
comfortable. The measurements in this floor were
taken under the glazed surface. In spite of the
overheating suffered in summer due to the
greenhouse effect, the measurements recorded are
higher than the upper comfort limit only a few time.
- In spite of the existence of a small pond for the
collection of rainwater, whose main function is the
control of the relative humidity, the measurements are
in most cases below the lower relative humidity limit.
- The orientation is an important design element when
constructing a bioclimatic building, the differences
registered in zones with different orientations in the
same floor prove that conclusion.
Figure 11: Natural cooling/heating in the ground floor.
Plea2004 - The 21
th
Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22
September 2004 Page 6 of 6
Therefore, it is possible to dampen the external
thermal wave by means of a good orientation and
high thermal inertia envelope.
The hygro-thermal conditions on first floor could be
improved by keeping the openings on the roof opened
during the night, and by installing shading systems
during the day.
ACKNOWLEDGEMENT
The authors wish to thank the Ministry of Science and
Technology of Spain for funding the Investigation
Project PB8-0720 “Aproximación a una metodología
de reutilización de constructions rurales”.
The plans of the building were made by the architect
Gabi Barbeta, who directed the rehabilitation project.
REFERENCES
[1] G. Barbeta. Mejora de la tierra estabilizada en el
desarrollo de una arquitectura sostenible hacia el
siglo XXI. 2000. Tesis doctoral. Universidad
Politécnica de Catalunya.
[2] S. Sinha. Down to earth buildings. 1997.
Architectural Design, vol 67, pp 91 – 93.
[3] R. Ooka. Field study on sustainable indoor climate
design of a Japanese traditional folk house in cold
climate area. 2002. Building and Environmet, vol 37,
pp 319 – 329.
[4] F. Youcef Ettoumi. Temperature variations in a
housing of the semi-arid region of Djelfa (Algeria).
2003. Building and Environment, vol 38, pp 511 –
519.
[5] L. Borong et al. Study on the thermal performance
of the Chinese tradicional vernacular dwelling in
Summer. 2004. Energy and Buildings, vol 36, pp 73 –
79.
[6] Y. Hamada et al. Field performance of a Japanese
low energy home relying on renewable energy. 2001.
Energy and Buildings, vol 33, pp 805 – 814.
[7] M. Domínguez. Propiedades térmicas de los
adobes. 1998. Arquitectura de Tierra, Encuentros
Internacionales Centro de Investigación Navapalos.
Ministerio de Fomento.
[8] www.inm.es (Oficial Web of National Institute of
Meteorology).

More Related Content

Similar to 04cB3 study PLEA2004.pdf

Buildings: a huge potential for energy savings in France
Buildings: a huge potential for energy savings in France Buildings: a huge potential for energy savings in France
Buildings: a huge potential for energy savings in France Stéfan Le Dû
 
strategies for improving energy efficiency of housing
strategies for improving energy efficiency of housingstrategies for improving energy efficiency of housing
strategies for improving energy efficiency of housinglokeshsingh33957
 
La presentazione del Prof. Aste del Politecnico di Milano
La presentazione del Prof. Aste del Politecnico di MilanoLa presentazione del Prof. Aste del Politecnico di Milano
La presentazione del Prof. Aste del Politecnico di MilanoMilano4YOU
 
04cB6 study PLEA2005.doc
04cB6 study PLEA2005.doc04cB6 study PLEA2005.doc
04cB6 study PLEA2005.docwebtierra
 
Smictom in fougères region-en
Smictom in fougères region-enSmictom in fougères region-en
Smictom in fougères region-enlibnam
 
IAED 342-Research Presentation
IAED 342-Research PresentationIAED 342-Research Presentation
IAED 342-Research PresentationSerra's Art Studio
 
[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group A
[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group A[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group A
[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group AGBC Finland
 
Enviroment and sustainablity of buildings
Enviroment and sustainablity of buildingsEnviroment and sustainablity of buildings
Enviroment and sustainablity of buildingstahia130136
 
Continental Climatic Zone
Continental Climatic ZoneContinental Climatic Zone
Continental Climatic ZoneDhir Dhwaj
 
Experiences in Barcelona: Energy-efficient refurbishment in residential build...
Experiences in Barcelona: Energy-efficient refurbishment in residential build...Experiences in Barcelona: Energy-efficient refurbishment in residential build...
Experiences in Barcelona: Energy-efficient refurbishment in residential build...GrowSmarter
 
MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...
MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...
MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...RINNO
 
Design solutions for reducing the energy needs
Design solutions for reducing the energy needsDesign solutions for reducing the energy needs
Design solutions for reducing the energy needsProf.Ing.Francesco Nocera
 
The development of sustainable housing concepts in Denmark
The development of sustainable housing concepts in DenmarkThe development of sustainable housing concepts in Denmark
The development of sustainable housing concepts in DenmarkMichael Søgaard Jørgensen
 
Retrofitting of Academic Building by Energy Efficient Techniques
Retrofitting of Academic Building by Energy Efficient TechniquesRetrofitting of Academic Building by Energy Efficient Techniques
Retrofitting of Academic Building by Energy Efficient TechniquesIRJET Journal
 
PROMOTING GREEN BUILDINGS THROUGH BAMBOOS
PROMOTING GREEN BUILDINGS THROUGH BAMBOOSPROMOTING GREEN BUILDINGS THROUGH BAMBOOS
PROMOTING GREEN BUILDINGS THROUGH BAMBOOSJIT KUMAR GUPTA
 
Building Science 1: Project 1 G- Tower
Building Science 1: Project 1 G- TowerBuilding Science 1: Project 1 G- Tower
Building Science 1: Project 1 G- Towerhiewyennee
 
Energy system for buildings. It has how to build buildings efficiently by sav...
Energy system for buildings. It has how to build buildings efficiently by sav...Energy system for buildings. It has how to build buildings efficiently by sav...
Energy system for buildings. It has how to build buildings efficiently by sav...krishna4644
 
VERDI - OpenSource 11kWh/m2 Modular envelope NeZeR
VERDI - OpenSource 11kWh/m2 Modular envelope NeZeRVERDI - OpenSource 11kWh/m2 Modular envelope NeZeR
VERDI - OpenSource 11kWh/m2 Modular envelope NeZeRAndrei Toma
 
Deep Retrofit: Adding value to deep retrofit
Deep Retrofit: Adding value to deep retrofit Deep Retrofit: Adding value to deep retrofit
Deep Retrofit: Adding value to deep retrofit SustainableEnergyAut
 

Similar to 04cB3 study PLEA2004.pdf (20)

Buildings: a huge potential for energy savings in France
Buildings: a huge potential for energy savings in France Buildings: a huge potential for energy savings in France
Buildings: a huge potential for energy savings in France
 
strategies for improving energy efficiency of housing
strategies for improving energy efficiency of housingstrategies for improving energy efficiency of housing
strategies for improving energy efficiency of housing
 
La presentazione del Prof. Aste del Politecnico di Milano
La presentazione del Prof. Aste del Politecnico di MilanoLa presentazione del Prof. Aste del Politecnico di Milano
La presentazione del Prof. Aste del Politecnico di Milano
 
04cB6 study PLEA2005.doc
04cB6 study PLEA2005.doc04cB6 study PLEA2005.doc
04cB6 study PLEA2005.doc
 
Smictom in fougères region-en
Smictom in fougères region-enSmictom in fougères region-en
Smictom in fougères region-en
 
IAED 342-Research Presentation
IAED 342-Research PresentationIAED 342-Research Presentation
IAED 342-Research Presentation
 
[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group A
[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group A[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group A
[Metropolia Student Project Seminar 24.5.] Zero Energy Buildings, Group A
 
Enviroment and sustainablity of buildings
Enviroment and sustainablity of buildingsEnviroment and sustainablity of buildings
Enviroment and sustainablity of buildings
 
Continental Climatic Zone
Continental Climatic ZoneContinental Climatic Zone
Continental Climatic Zone
 
Experiences in Barcelona: Energy-efficient refurbishment in residential build...
Experiences in Barcelona: Energy-efficient refurbishment in residential build...Experiences in Barcelona: Energy-efficient refurbishment in residential build...
Experiences in Barcelona: Energy-efficient refurbishment in residential build...
 
MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...
MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...
MicroVent: Energy-Efficient, Façade-Integrated Ventilation Systems with Heat ...
 
Design solutions for reducing the energy needs
Design solutions for reducing the energy needsDesign solutions for reducing the energy needs
Design solutions for reducing the energy needs
 
The development of sustainable housing concepts in Denmark
The development of sustainable housing concepts in DenmarkThe development of sustainable housing concepts in Denmark
The development of sustainable housing concepts in Denmark
 
Retrofitting of Academic Building by Energy Efficient Techniques
Retrofitting of Academic Building by Energy Efficient TechniquesRetrofitting of Academic Building by Energy Efficient Techniques
Retrofitting of Academic Building by Energy Efficient Techniques
 
PROMOTING GREEN BUILDINGS THROUGH BAMBOOS
PROMOTING GREEN BUILDINGS THROUGH BAMBOOSPROMOTING GREEN BUILDINGS THROUGH BAMBOOS
PROMOTING GREEN BUILDINGS THROUGH BAMBOOS
 
Building Science 1: Project 1 G- Tower
Building Science 1: Project 1 G- TowerBuilding Science 1: Project 1 G- Tower
Building Science 1: Project 1 G- Tower
 
Gtower report
Gtower reportGtower report
Gtower report
 
Energy system for buildings. It has how to build buildings efficiently by sav...
Energy system for buildings. It has how to build buildings efficiently by sav...Energy system for buildings. It has how to build buildings efficiently by sav...
Energy system for buildings. It has how to build buildings efficiently by sav...
 
VERDI - OpenSource 11kWh/m2 Modular envelope NeZeR
VERDI - OpenSource 11kWh/m2 Modular envelope NeZeRVERDI - OpenSource 11kWh/m2 Modular envelope NeZeR
VERDI - OpenSource 11kWh/m2 Modular envelope NeZeR
 
Deep Retrofit: Adding value to deep retrofit
Deep Retrofit: Adding value to deep retrofit Deep Retrofit: Adding value to deep retrofit
Deep Retrofit: Adding value to deep retrofit
 

More from webtierra

06cB7 Las segundas residencias.doc
06cB7 Las segundas residencias.doc06cB7 Las segundas residencias.doc
06cB7 Las segundas residencias.docwebtierra
 
01cI8 inven2001Murcia.ppt
01cI8 inven2001Murcia.ppt01cI8 inven2001Murcia.ppt
01cI8 inven2001Murcia.pptwebtierra
 
INVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdf
INVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdfINVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdf
INVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdfwebtierra
 
01cI9 las construValencia2001.ppt
01cI9 las construValencia2001.ppt01cI9 las construValencia2001.ppt
01cI9 las construValencia2001.pptwebtierra
 
LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...
LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...
LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...webtierra
 
03c b1b caractercordoba2003
03c b1b caractercordoba200303c b1b caractercordoba2003
03c b1b caractercordoba2003webtierra
 
Impacto visual
Impacto visualImpacto visual
Impacto visualwebtierra
 
04c b6 study plea2005
04c b6 study plea200504c b6 study plea2005
04c b6 study plea2005webtierra
 

More from webtierra (9)

06cB7 Las segundas residencias.doc
06cB7 Las segundas residencias.doc06cB7 Las segundas residencias.doc
06cB7 Las segundas residencias.doc
 
01cI8 inven2001Murcia.ppt
01cI8 inven2001Murcia.ppt01cI8 inven2001Murcia.ppt
01cI8 inven2001Murcia.ppt
 
INVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdf
INVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdfINVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdf
INVENTARIO Y ESTUDIO DE CONSTRUCCIONES Tierras Sorianas del Cid.pdf
 
01cI9 las construValencia2001.ppt
01cI9 las construValencia2001.ppt01cI9 las construValencia2001.ppt
01cI9 las construValencia2001.ppt
 
LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...
LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...
LITTLE BRIDGES OF THE TRADITIONAL RURAL ROADS OF “TERRA CHA” (LUGO, SPAIN) TY...
 
03c b1b caractercordoba2003
03c b1b caractercordoba200303c b1b caractercordoba2003
03c b1b caractercordoba2003
 
Madera
MaderaMadera
Madera
 
Impacto visual
Impacto visualImpacto visual
Impacto visual
 
04c b6 study plea2005
04c b6 study plea200504c b6 study plea2005
04c b6 study plea2005
 

Recently uploaded

Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations120cr0395
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxAsutosh Ranjan
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)Suman Mia
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVRajaP95
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 

Recently uploaded (20)

Extrusion Processes and Their Limitations
Extrusion Processes and Their LimitationsExtrusion Processes and Their Limitations
Extrusion Processes and Their Limitations
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
Coefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptxCoefficient of Thermal Expansion and their Importance.pptx
Coefficient of Thermal Expansion and their Importance.pptx
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)Software Development Life Cycle By  Team Orange (Dept. of Pharmacy)
Software Development Life Cycle By Team Orange (Dept. of Pharmacy)
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(PRIYA) Rajgurunagar Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IVHARMONY IN THE NATURE AND EXISTENCE - Unit-IV
HARMONY IN THE NATURE AND EXISTENCE - Unit-IV
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 

04cB3 study PLEA2004.pdf

  • 1. Plea2004 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22 September 2004 Page 1 of 6 Study of the thermal behaviour of a reused rural building. Ignacio Cañas1 , Silvia Martin1 and Jose Maria Fuentes1 1 Departamento de Construccion y Vias Rurales. Escuela Técnica Superior de Ingenieros Agrónomos. Avda Complutense s/n. 28040 Madrid ABSTRACT: In this article the thermal behaviour of a reused rural building is analyzed. Spanish rural areas are suffering the problem of depopulation with the loss of lot of traditional buildings. The reuse of these buildings is a system for saving the loss of rural heritage that is causing the loss of regional identities. The particular case studied here is an old building for sheep accommodation, this type of building was common in the interior areas of Spain due to the agrarian way of life. The owners bought the building some years ago with the aim of constructing a rural hotel. For the construction of the new building they followed some criterions based on the bioclimatic design. The study carried out tries to examine the thermal behaviour of this building by means of registering the temperature and relative humidity in some points inside it. The results show that instead of the harsh climatic conditions happening outside, the interior temperature is inside the comfort limits. This study shows that the reuse of rural buildings, in addition of the economic and social advantages, is a system of reducing energy consumption in the life cycle of the building. Conference Topic: 6, Recycled architecture (re-use, upgrading and rehabilitation of buildings) Keywords: reuse, thermal behaviour 1. INTRODUCTION. 2. BUILDING CHARACTERISTICS. In Spain there is a great amount of rural buildings ( rural houses, stables, agricultural machinery stores, dovecotes, …) abandoned from the fifties due to the rural exodus. The studied building is placed in a small town called Covachuelas in the province of Segovia (Castilla y Leon). The town was uninhabited in the fifties. The altitude is 1005 m above sea level, and it is 120 km far away from Madrid (see figure 1). The reuse of old buildings provide an environmental advantage because of the reduction in energy use and building materials compared to a new construction. The life cycle of reusing an old building has less steps than constructing a new one. In addition, the reuse of old buildings has social and cultural advantages, as maintenance of regional texture, scale and history, and the preservation of local identity of traditional architecture. One of the problems about the reuse of rural buildings is their remoteness to large population centres and the poor quality of infrastructure in rural areas. New leisure alternatives offer the possibility of using again this type of buildings. Give a new use to abandoned rural buildings involves the presence of new people and activities in rural areas, therefore the economy could be improved. In this paper the results from the monitoring of a reused rural building during summer are shown. The building was an abandoned sheep house that was turned into a rural hotel. The rehabilitation of the building was made following bioclimatic criterions. The aim of this paper is to study the hygro-thermal conditions inside this building. Figure 1: Map of location.
  • 2. Plea2004 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22 September 2004 Page 2 of 6 The area is characterized by a continental climate with great temperature oscillations. The absolute maximum temperature in the hottest month is 39º C, and the absolute minimum temperature in the coldest month is –15º C. The mean annual precipitation is 470 mm (see figure 2). Climate in Covachuelas 0 5 10 15 20 25 30 35 January February March April May June July August September October November December T (ºC) 0 10 20 30 40 50 60 70 P (mm) TM Tm P Figure 4: The building after the rehabilitation. 2.1. Rehabilitation characteristics: - All building materials used in the rehabilitation works have low environmental impact. Figure 2: Summary of climatic conditions in Covachuelas. TM: monthly average of daily maximum temperature; Tm: monthly average of daily minimum temperature; P: monthly precipitation. Source: National Institute of Meteorology. Weather station in Segovia (1971 – 2000) - Compressed earth blocks were made from local soils. The use of this building material has two advantages: the same colour as that found in traditional architecture, and good thermal behaviour. - The insulation was made of natural materials (pure wool). - A glazed surface was constructed in a part of the roof oriented to South with the aim of making better use of solar radiation in winter (greenhouse effect). Finally, the glazed surface on the roof was larger than that calculated in the rehabilitation project due to several problems with the subvention for the solar panels. In the studied area there is plentiful use of earth as a building material in popular architecture. This material is very typical of some Spanish regions where the lack of another building materials joined to the good quality of their soils make it a suitable material as well as ecologic. The old sheep house was a large building constructed of stone masonry and sun-dried bricks. When the current owners bought the building, it was almost in ruins. They wanted to build a rural accommodation. The rehabilitation process aimed at keeping the typology of regional traditional architecture as well as incorporate some building elements from bioclimatic design. - The drop of the terrain was used for burying in part the north façade, so it is less exposed to the environment and has high thermal inertia like underground constructions. - The building uses renewable energy: wind power, thermal and electric solar energy. - The plumbing system allows to separate sewage from washes and also to collect rainwater in a small pond. Figure 3: The building before the rehabilitation. Figure 5: Elevation of the building, showing the glazed surface on the roof oriented to South.
  • 3. Plea2004 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22 September 2004 Page 3 of 6 3. ENERGY SAVING ON BUILDING MATERIALS. As indicated previously, the building materials used in the rehabilitation works were selected following environmental criterions. The embodied energy of the selected materials is low, so the impact derived from the construction phase is reduced (table 1). Table 1: Embodied energy in various building materials. Source: Sinha, 1997. Material Embodied energy (MJ/kg) Earth 0,1 Natural cement 3,8 Plaster 3,1 Aluminium 97,2 Local wood 0,72 Foreign wood 5,04 Glass 28,15 Plastic 162 In addition, the reuse of the building by itself involves a reduction of the environmental impact due to the elimination of some phases of the construction cycle. In the studied case, demolition works were not required and neither land preparation jobs previous to the construction were done. Therefore, the energy needed to reuse the abandoned building is less than that needed in constructing a new building completely. The compressed earth block technique has the next advantages: - The compressed earth blocks can be made in the same place where the building will be constructed, by using local and plentiful material (soil), so the transport and extraction costs are almost zero. - The thermal behaviour of compressed earth blocks is better than other building materials, so they produce energy saving on insulation as well as indoor comfort conditions (this subject is analyzed in the rest of this paper, showing the results from the monitoring) (table 2). Table 2: Physical properties of adobe. Source: Domínguez, 1998. Property Value Density 1200 – 1700 kg/m3 Ice resistance Low Exposure to elements Low Specific heat 0.85 kJ/kg Thermal conductivity 0.46 – 0.81 W/mK Thermal wave dampening coefficient (40 cm) 5 – 10 % Daily gap (Outdoor – indoor thermal wave) 10 – 12 h Fire resistance Good - The elaboration process does not need the use of heavy machinery or working place, so the energetic cost is also very low (table 3). - The economic saving is helped by the low cost of the soil/earth extracted from the local area. - This construction system is low technological. It does not require specialized workers, so it is suitable for self-construction, therefore it can be another way of economic saving. In addition, it can solve the problem of rural depopulation because it can provide job to rural people. Table 3: Energy added during the manufacture process of compressed earth blocks. Source: Barbeta, 2000. Concept Quantity Energy Energy/block Energy/kg Earth 4,2 kg 0,1 MJ/kg 0,42 MJ 0,07 Natural cement 0,65 kg 3,8 MJ/kg 2,47 MJ 0,42 Plaster 0,35 kg 3,1 MJ/kg 1,08 MJ 0,18 Water 0,87 kg 0 0 0 Energy cost in manufacture 0 0 0 0 TOTAL 3,97 MJ/block 0,67 MJ/kg 4. MEASUREMENT SCHEME. In order to analyze the hygro-thermal behaviour of this building, the monitoring of indoor and outdoor conditions was carried out. The measurement instruments used are: - Data logger called Hobo H8 HR/Temp (H08-003- 02) for the measuring of temperature and relative humidity inside the building. Its resolution is 0.4º C for temperature and its accuracy for relative humidity is 5%. - Data logger called Hobo Pro HR/Temp (H08-032- 08) for the measuring of the external conditions. Its resolution is 0.02º C for temperature and its accuracy for relative humidity is 3%. - Data logger connected to a pyranometer for the measuring of the global solar radiation. Its accuracy is 2%. Inside the building the temperature was recorded in 7 points: (i) inside the storeroom, which is placed on the north part of the ground floor (ii) in the kitchen, placed also in the north part on the ground floor (iii) in the hall on the ground floor (*) (iv) under the glazed surface, on the ground floor (v) inside a bedroom placed in the north part on the first floor (vi) in the corridor on the first floor (*) (vii) in the south part on the first floor (*) In the three points marked with asteriks, the relative humidity was also recorded. 5. RESULTS. The results from the monitoring carried out from 11 to 27 August, 2003, are showed below. Unfortunately there have been failures in some instruments and the
  • 4. Plea2004 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22 September 2004 Page 4 of 6 conditions in the north part on the ground floor was not measured. Temperature comparison 0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00 08/18/03 08/19/03 08/20/03 08/21/03 ºC Corridor in first floor North zone in first floor South zone ground floor Outside South zone in first floor Figure 6: Comparison between indoor and outdoor temperature (18 th – 21 st of August, 2003). 5.1. Outside conditions: The maximum temperature recorded was 38.7º C at 15:00 on August , the 13th , the minimum was 9.3º C at 7:00 on August, the 27 th . The mean temperature was 22.9º C with an oscillation of 29.4º C. The maximum relative humidity registered was 97%, the minimum was 8% and the average was 48%. The maximum value of global solar radiation recorded was 1078 W/m2. 5.2. Indoor conditions: - Ground floor: On the ground floor the only recorded data are those from the south part. This zone are affected by the large glazed surface on the roof, whose purpose is to be used as a solar collector during winter time when the temperature is extremely cold. The maximum temperature recorded was 28.7º C at 14:00 on August, the 14 th , the minimum temperature was 21.2º C at 8:00 on August, the 27th . The average temperature was 25.1º C with an oscillation of 7.5º C. Relative humidity comparison 0.00 20.00 40.00 60.00 80.00 100.00 08/18/03 08/19/03 08/20/03 08/21/03 (%) First Floor Ground floor Outside Figure 7: Comparison between indoor and outdoor relative humidity (18 th – 21 st of August, 2003). The maximum relative humidity was 60%, the minimum was 21% and the average was 39%. - First Floor: On the first floor there are three monitored points: the corridor, the south zone and the bedroom oriented to North. In the corridor the maximum temperature registered was 30.7º C from 18:30 to 19:30 on 13 th of August. The minimum temperature was 19º C at 7:30 on 27th of August. The average temperature was 25.9º C with an oscillation of 11.7º C. On the other hand, the maximum relative humidity was 55%, the minimum was 24% and the average was 35%. In the south zone the maximum temperature registered was 34.9º C at 15:00 on 13 th of August. The minimum temperature was 21.7º C. The average temperature was 26.8º C with an oscillation of 13.2º C. In figures 8, 9, 10 and 11the level of cooling / heating registered (indoor temperature – outdoor temperature) against outdoor temperature is showed. As it can be seen in the figures, there is a clear overheating effect in the corridor and in the south zone on the first floor. The poor level of natural cooling is not able to move the points inside the comfort band (which is around 24º C ±2º C). In the the corridor most of points showing discomfort due to overheating are placed between 27ºC and 30ºC. In the south area there are some cases (10% of measurements) near 35ºC. In the north zone the points showing overheating are below 30º C, and most of them are between 26ºC and 28ºC. In the ground floor all measurements are below 29ºC, most of them are between 26ºC and 27ºC (when the outdoor temperature registered is in 20% of measurements higher than 30ºC). From this analysis we assert that the thermal behaviour of the building can be improved. The indoor conditions registered are much less extreme than that registered outside, however in the corridor and the south zone on the first floor there is an overheating effect. In the bedroom oriented to North the maximum temperature registered was 29.9º C from 19:30 to 00:30 on 13 th of August. The minimum temperature was 21.7º C at 5:30 on 21 st of August. The average temperature was 26.2º C with an oscillation of 8.2º C. Figures 6 and 7 show the temperature and relative humidity measurements during 4 days of monitoring (18 th – 21 st of August, 2003). The places where the maximum temperature is higher are the corridor and the south area on the first floor, in addition these two points show the higher temperature oscillations. The North orientation and the ground floor have the ability to control the temperature in lower levels and more constant than other parts of the building.
  • 5. Plea2004 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22 September 2004 Page 5 of 6 In figure 12 the variation of indoor temperature with regard to outdoor temperature is studied. The aim of this analysis is to determine the influence of outdoor conditions on the indoor ones. Figure 8: Natural cooling/heating in the corridor on the first floor. From the figure the tendency lines where calculated, where x is the outdoor temperature and y is the indoor temperature for each point: - in the south area on the first floor the tendency line and the corresponding error factor are: y= 0.3379x + 19.01 R2= 0.7408 - in the bedroom oriented to North on the first floor: y= 0.0734x + 24.539 R2= 0.0721 The previous ecuations show that the temperature recorded in the south area on the first floor are more dependent on the outside temperature than that measured in the bedroom oriented to North (first floor). The results proves the effect of orientation as shock absorber. In our latitudes it is better the north orientation to achieve comfort conditions in summer. Figure 9: Natural cooling/heating in the south zone on the first floor. Variation of inside temperatures according to outside temperatures 18.00 20.00 22.00 24.00 26.00 28.00 30.00 32.00 34.00 36.00 0.00 10.00 20.00 30.00 40.00 50.00 T outside (ºC) T inside (ºC) T corridor in first floor T south area in first floor T north area in first floor T ground floor Figure 12: Variation of inside temperatures according to outside ones. Figure 10: Natural cooling/heating in the north zone on the first floor. 6. CONCLUSIONS. From the data analysis and despite the lack of measurements in most zones of ground floor, the next conclusions were obtained: - In this reused rural building the conservation of the existing stone masonry walls joined to the excavation in the north part of the ground floor below the ground level, make the hygro-thermal conditions in this floor comfortable. The measurements in this floor were taken under the glazed surface. In spite of the overheating suffered in summer due to the greenhouse effect, the measurements recorded are higher than the upper comfort limit only a few time. - In spite of the existence of a small pond for the collection of rainwater, whose main function is the control of the relative humidity, the measurements are in most cases below the lower relative humidity limit. - The orientation is an important design element when constructing a bioclimatic building, the differences registered in zones with different orientations in the same floor prove that conclusion. Figure 11: Natural cooling/heating in the ground floor.
  • 6. Plea2004 - The 21 th Conference on Passive and Low Energy Architecture. Eindhoven, The Netherlands, 19 - 22 September 2004 Page 6 of 6 Therefore, it is possible to dampen the external thermal wave by means of a good orientation and high thermal inertia envelope. The hygro-thermal conditions on first floor could be improved by keeping the openings on the roof opened during the night, and by installing shading systems during the day. ACKNOWLEDGEMENT The authors wish to thank the Ministry of Science and Technology of Spain for funding the Investigation Project PB8-0720 “Aproximación a una metodología de reutilización de constructions rurales”. The plans of the building were made by the architect Gabi Barbeta, who directed the rehabilitation project. REFERENCES [1] G. Barbeta. Mejora de la tierra estabilizada en el desarrollo de una arquitectura sostenible hacia el siglo XXI. 2000. Tesis doctoral. Universidad Politécnica de Catalunya. [2] S. Sinha. Down to earth buildings. 1997. Architectural Design, vol 67, pp 91 – 93. [3] R. Ooka. Field study on sustainable indoor climate design of a Japanese traditional folk house in cold climate area. 2002. Building and Environmet, vol 37, pp 319 – 329. [4] F. Youcef Ettoumi. Temperature variations in a housing of the semi-arid region of Djelfa (Algeria). 2003. Building and Environment, vol 38, pp 511 – 519. [5] L. Borong et al. Study on the thermal performance of the Chinese tradicional vernacular dwelling in Summer. 2004. Energy and Buildings, vol 36, pp 73 – 79. [6] Y. Hamada et al. Field performance of a Japanese low energy home relying on renewable energy. 2001. Energy and Buildings, vol 33, pp 805 – 814. [7] M. Domínguez. Propiedades térmicas de los adobes. 1998. Arquitectura de Tierra, Encuentros Internacionales Centro de Investigación Navapalos. Ministerio de Fomento. [8] www.inm.es (Oficial Web of National Institute of Meteorology).