SlideShare a Scribd company logo
1 of 56
POET CONSULTANTS PVT. LTD.
TRAINING
ON
POET CONSULTANTS PVT. LTD.
TRAINING COURSE
ON
MOTORS
POET CONSULTANTS PVT. LTD.
MOTORS
• GENERAL
• BASIC TECHNICAL REQUIREMENTS
• SAFETY ASPECTS
• APPROVED MAKES
• LV MOTORS
• HV MOTORS
• SELECTION CRITERION
POET CONSULTANTS PVT. LTD.
MOTORS
• BRIEF SPECIFICATIONS
• PROTECTION & CONTROL REQUIREMENTS
• ENERGY EFFICIENT MOTORS & EVALUATION
CRITERION
• MAINTENANCE SCHEDULE
• APPLICABLE STANDARDS
• APPENDIX – 1
• APPENDIX - 2
POET CONSULTANTS PVT. LTD.
GENERAL:
UNDER THIS HEADING, APPLICABLE STANDARDS AND
APPLICATION OF MOTORS ARE COVERED
APPLICABLE STANDARDS:
• USER COMPANY SAFETY STANDARDS
• IE ACTS AND RULES
• IS/ BS/ IEC/ IEEE STANDARDS
APPLICATION:
• TYPE OF INSTALLATION - INDOOR/ OUTDOOR
• AREA OF USAGE - FACTORY, WAREHOUSE,
OFFICE, OFF-SHORE, HAZARDOUS, etc.,
• TYPE OF MOTOR - GENERAL PURPOSE OR
SPECIAL PURPOSE
MOTORS
POET CONSULTANTS PVT. LTD.
SAFETY ASPECTS:
DUE CONSIDERATION FOR THE SAFETY OF
PERSONNEL AND THE INSTALLATION IS
IMPORTANT. MAIN CATEGORIES ADDRESSED
UNDER SAFETY ASPECT ARE:
 RATINGS
 ENCLOSURE
 TERMINATION ARRANGEMENTS
 SAFETY ACCESSORIES
MOTORS
POET CONSULTANTS PVT. LTD.
RATING ASPECT:
WHILE SELECTING THE RATINGS FOR ANY APPLICATION/
VERIFICATION OF RATING FOR ALREADY EXISTING
INSTALLATION THE FOLLOWING KEY CRITERION HAVE TO
BE LOOKED INTO:
 10% MARGIN OVER DRIVEN EQUIPMENT
 VOLTAGE AND FREQUENCY VARIATION SHALL BE +/-
10% AND +/-5% RESPECTIVELY WITH A COMBINED
VARIATION OF +/-10%
 DESIGN AMBIENT TEMP. SHALL BE PROPERLY
SPECIFIED. TEMP. RISE ABOVE DESIGN AMBIENT TO BE
AS PER PERMISSIBLE FINAL TEMP. OF THE SPECIFIED
CLASS OF INSULATION
MOTORS
POET CONSULTANTS PVT. LTD.
MOTORS
 STARTING TORQUE SHOULD BE ADEQUATE EVEN
WITH 85% OF NOMINAL VOLTAGE FOR LT MOTORS
AND 80% FOR HT MOTORS.
 FOR NORMAL APPLICATIONS, THE STARTING TORQUE
SHALL BE MINIMUM TWICE THE FULL LOAD TORQUE.
 NORMALLY THE SELECTION OF ONE FRAME SIZE
HIGHER MOTOR THAN THAT RECOMMENDED BY THE
MOTOR SUPPLIER FOR GIVEN DRIVE DUTY WILL TAKE
CARE OF THE ABOVE REQUIREMENTS
POET CONSULTANTS PVT. LTD.
ENCLOSURE:
THIS PLAYS AN IMPORTANT ROLE IN DECIDING THE
LIFE OF THE MOTOR. A WRONG ENCLOSURE LEADS TO
PRE-MATURE FAILURE OF INSULATION OR INCREASED
MAINTENANCE. THE FOLLOWING POINTS ARE TO BE
CONSIDERED:
• IP 54 FOR INDOOR AND IP 55 FOR OUTDOOR
APPLICATIONS (HOWEVER, FOR INDUSTRIES SUCH
AS PAPER, WHERE THE USAGE OF WATER IS VERY
HIGH, IP-55 MAY BE CONSIDERED EVEN FOR
INDOOR APPLICATION.
• FLAMEPROOF FOR HAZARDOUS AREA
MOTORS
POET CONSULTANTS PVT. LTD.
MOTORS
ANY OTHER ENCLOSURE SHALL BE SELECTED WITH
CARE WITH FULL KNOWLEDGE OF SITE CONDITIONS.
SOME OF THEM ARE LISTED BELOW:
• DRIP-PROOF GUARDED FORCE VENTILATED
• DRIP-PROOF GUARDED SEPARATELY VENTILATED
• TOTALLY ENCLOSED AIR OVER-BLOWER COOLED
• TOTALLY ENCLOSED NON VENTILATED
• TOTALLY ENCLOSED FAN COOLED
POET CONSULTANTS PVT. LTD.
MOTORS
• DUST PROOF TACONITE FEATURES ( BEARINGS
PROVIDED WITH PROTECTION AGAINST ABRASIVE
DUST)
• XT FEATURES (PROVIDES PROTECTION AGAINST
CORROSIVE, MOIST AND DUST LADEN ATMOSPHERE
AS ENCOUNTERED IN PAPER, CHEMICAL AND SIMILAR
INDUSTRIES)
• PAPER MILL DUTY FEATURES( FOR OPERATION OF
WET END OF PAPER MILLS)
• TOTALLY ENCLOSED PIPE VENTILATED ( COOLED BY
CUSTOMER SUPPLIED PIPED AIR)
POET CONSULTANTS PVT. LTD.
MOTORS
TERMINATION ARRANGEMENT: GENERALLY IT IS
OBSERVED THAT DUE IMPORTANCE IS NOT GIVEN TO
TERMINATION ARRANGEMENT IN THE MOTORS. THIS
LEADS TO FAILURE OF MOTORS DUE TO INGRESS OF
MOISTURE, DUST, HEATING, RODENT ENTRY, etc. THE
FOLLOWING KEY POINTS SHALL BE TAKEN NOTE OF FOR
PROPER TERMINATION ARRANGEMENT IN A MOTOR:
POET CONSULTANTS PVT. LTD.
• THE TERMINAL BOX SHALL WITHSTAND SPECIFIED
SHORT CIRCUIT CURRENT FOR 0.2 SEC.
• MINIMUM CLEARANCES FOR PHASE TO PHASE AND TO
EARTH BETWEEN CABLE LUGS AND BODY SHALL BE
MAINTAINED.
• FOR HV MOTORS PHASE SEGREGATION TO BE
CONSIDERED
• WHENEVER SEAL OFF BUSHINGS ARE USED, THEY
SHALL HAVE MINIMUM CREEPAGE DISTANCES AS PER
IS.
• TERMINALS HAVE TO BE MADE OF AT LEAST EPOXY
INSULATED, AND FOR HIGH VOLTAGES PORCELAIN
SHALL BE USED. PHENOLIC RESIN AND BAKELITE
SHALL NOT BE USED.
MOTORS
POET CONSULTANTS PVT. LTD.
SIZE OF TERMINAL BLOCK SHALL BE LARGE ENOUGH TO
ACCOMMODATE ALUMINIUM CABLES PROPERLY
DEGREE OF PROTECTION OF TERMINAL BOX SHALL THE
SAME AS THAT OF THE MOTOR BODY.
SAFETY ACCESSORIES:
USE OF CERTAIN AVAILABLE ACCESSORIES ENHANCES
THE SAFETY AND RELIABILITY OF THE SYSTEM AND THE
EQUIPMENT. SOME OR ALL OF THE FOLLOWING
ACCESSORIES CAN BE CONSIDERED DEPENDING ON THE
TYPE OF THE MOTOR, INSTALLATION, etc.,
MOTORS
POET CONSULTANTS PVT. LTD.
• SAFE LIFTING FACILITIES LIKE EYEBOLT, etc., FOR
MOTORS WEIGHING MORE THAN 25KGS.
• GREASING PLUG- RECOMMENDED FOR FRAME SIZE
200 AND ABOVE.
• EFFORTS SHALL BE MADE TO STANDARDISE THE
TYPE OF GREASE USED, PREFERABLY LITHIUM
BASED MP3. USE OF EXCESSIVE GREASE SHALL BE
AVOIDED
• BTD AND RTD FOR HV MOTORS.
MOTORS
POET CONSULTANTS PVT. LTD.
MOTORS
• ANTI CONDENSATION HEATERS FOR MOTORS ABOVE
30KW. THESE SHALL BE INTERLOCKED WITH THE
MOTOR STARTER SUCH THAT THEY SHALL BE ON
ONLY WHEN THE MOTOR IS OFF
• SEPARATE EARTHING TERMINALS FOR BODY (MIN. 2
NOS.) AND EACH TERMINAL BOX.
• LOCAL BEARING TEMPERATURE INDICATORS FOR HV
MOTORS WITH ALARM AND TRIP CONTACTS
POET CONSULTANTS PVT. LTD.
MOTORS
• HOW TO SELECT A MAKE OF MOTOR?
• WHAT ARE THE PARAMETERS WHICH NEED TO BE
LOOKED IN TO WHILE SELECTING A MAKE OF MOTOR:
WHILE SELECTING A PARTICULAR MAKE OF
EQUIPMENT, IT IS SUGGESTED THAT THE FOLLOWING
POINTS BE STUDIED BEFORE MAKING A FINAL
DECISION:
• EXISTING MAKES IN THE INSTALLATION
POET CONSULTANTS PVT. LTD.
• PERFORMANCE OF THE EXISTING MAKES
• STANDARDISATION REQUIREMENTS FOR THE
INSTALLATION
• AVAILABILITY AND SERVICEABILITY AT THE PLACE OF
USAGE
• PREVIOUS EXPERIENCE WITH THE MAKE SELECTED
MOTORS
POET CONSULTANTS PVT. LTD.
SOME OF REPUTED MOTOR MANUFACTURERS IN THE
COUNTRY AND THEIR RANGE OF MANUFACTURE:
MANUFACTURER LT AC HT AC DC
MOTOR MOTOR MOTOR
Crompton Greaves Yes No Yes
Kirloskar Electric co. ltd. Yes Yes Yes
Integrated Electric Co Ltd. No NO Yes
Siemens Yes No No
NGEF Yes Yes Yes
Bhel No Yes Yes
Bharath Bijlee Ltd. Yes No No
MOTORS
POET CONSULTANTS PVT. LTD.
TYPE OF STARTING FOR MOTORS:
• FURTHER, TYPE OF STARTING FOR THE MOTORS HAS TO
BE DECIDED BASED ON THE ALLOWABLE VOLTAGE DIP ON
THE SYSTEM AND MAGNITUDE OF STARTING CURRENT.
• THE FOLLOWING POINTS NEED TO BE CONSIDERED WHILE
SELECTING TYPE OF STARTING/ MOTORS:
MOTORS ORDERED FOR DIRECT ON LINE (DOL) STARTING
ARE NOT SUITABLE FOR ASSISTED STARTING (LIKE STAR-
DELTA). HOWEVER MOTORS ORDERED FOR ASSISTED
START ARE SUITABLE FOR DOL. HENCE, THE TYPE OF
STARTING SHALL BE FIRMED UP BEFORE ORDERING.
MOTORS
POET CONSULTANTS PVT. LTD.
• MOTORS SHALL BE CAPABLE OF STARTING AND
ACCELERATING THE LOAD EVEN AT 85% OF THE RATED
VOLTAGE WITHOUT EXCEEDING ACCEPTABLE WINDING
TEMPERATURE.
• THE STARTING CURRENT SHALL GENERALLY NOT
EXCEED 600% OF THE FULL LOAD CURRENT. HOWEVER
FOR LOW RATING MOTORS STARTING CURRENTS UPTO
800% CAN BE ACCEPTED SUBJECT TO STARTING
VOLTAGE DIPS BEING WITHIN LIMITS AS STATED
ABOVE, IF SUBSTANTIAL COST BENEFITS ARE
AVAILABLE.
• MOTORS SHALL BE DESIGNED TO WITHSTAND 120% OF
RATED SPEED FOR TWO MINUTES WITHOUT ANY
MECHANICAL DAMAGE, IN EITHER DIRECTION OF
ROTATION
MOTORS
POET CONSULTANTS PVT. LTD.
• THE VOLTAGE DROP AT MOTOR TERMINALS DURING
STARTING SHALL NOT EXCEED 20% FOR HT MOTORS
AND 15% FOR LT MOTORS
• A STARTING VOLTAGE DROP CALCULATION SHALL BE
CARRIED OUT THE DECIDE THE TYPE OF STARTING. FOR
VERY LARGE MOTORS, SOFT STARTERS CAN BE
CONSIDERED.
• STAR DELTA STARTER UPTO 100 KW CAN BE WITHOUT
THE RESISTANCE TYPE. HOWEVER, MOTORS LARGER
THAN 100 KW SHALL BE PROVIDED WITH 4-
CONTRACTOR SCHEME WITH EXTERNAL RESISTOR AND
SHORTING CONTRACTOR TO AVOID BREAK IN THE
CURRENT DURING CHANGE FROM STAR TO DELTA.
MOTORS
POET CONSULTANTS PVT. LTD.
• SELECTION OF SOFT STARTER DEPENDS ON THE
FOLLOWING-
• IF THE VOLTAGE DROP DURING STARTING IS HIGHER
THAN THAT DEFINED ABOVE WHILE STARTING ON IN-
HOUSE GENERATION LIKE DG SET OR TG SET
• IF THE NUMBER OF START-STOPS ARE MORE THAN 3
TIMES PER HOUR AS PER PROCESS REQUIREMENT
(HERE THE CONSTRAINT IS THE CIRCUIT BREAKER
WHOSE MECHANICAL LIFE IS ABOUT 5000 OPERATIONS;
THE COST OF SOFT STARTER HAS TO BE WEIGHED
AGAINST THE REPLACEMENT COST OF THE CIRCUIT
BREAKER OVER A FIXED LIFE TIME)
MOTORS
POET CONSULTANTS PVT. LTD.
MOTORS
DC MOTORS:
• WHEN CONSTANT TORQUE AND SPEED CONTROL
APPLICATIONS ARE INVOLVED, DC MOTORS ARE
SELECTED. GENERAL GUIDELINES DETAILED FOR AC
MOTORS ARE ALSO APPLICABLE FOR DC MOTORS. IN
ADDITION TO THIS, THE FOLLOWING GUIDELINES ARE
ALSO APPLICABLE FOR THIS TYPE OF MOTORS:
• MOTORS SHALL BE CAPABLE OF GIVING RATED
OUTPUT WITHOUT REDUCTION IN THE EXPECTED LIFE
SPAN WHEN OPERATED CONTINUOUSLY AT A SUPPLY
VOLTAGE WITHIN 5% FROM THE RATED VALUE.
POET CONSULTANTS PVT. LTD.
MOTORS
• CAPABLE OF STARTING AND ACCELERATING THE LOAD
WITH APPLICABLE METHODS OF STARTING, WITHOUT
EXCEEDING ACCEPTABLE WINDING TEMPERATURE,
WHEN THE SUPPLY VOLTAGE IS 85% OF THE RATED
VALUE.
• MOTORS SHALL BE DESIGNED TO WITH STAND 120%
OF RATED SPEED FOR TWO MINUTES WITHOUT ANY
MECHANICAL DAMAGE IN EITHER DIRECTION OF
ROTATION.
• PROPER DUTY CYCLE SELECTION HAS TO BE DONE.
• THE FIELD WINDINGS FOR THE MOTORS SHALL BE
CONTINUOUSLY RATED WITHOUT FORCED
VENTILATION
POET CONSULTANTS PVT. LTD.
• LARGE SIZE MOTORS SHALL BE OF HORIZONTALLY
SPLIT CONSTRUCTION FOR EASY MAINTENANCE.
• THE FIELD WINDING SHALL NOT BE POWERED
WITHOUT FORCED VENTILATION, UNLESS IT IS A
SPECIAL APPLICATION.
• THE DUTY CLASS AS PER IEC STANDARD SHALL BE
FOLLOWED.
DC MOTOR SELECTION:
• GENERALLY, TYPES OF DRIVES ARE SELECTED BASED
ON THE SPEED TORQUE CHARACTERISTIC OF THE
LOAD, WHICH CAN BE CATEGORIZED AS FOLLOWS:
MOTORS
POET CONSULTANTS PVT. LTD.
MOTORS
• CONSTANT TORQUE APPLICATION – eg. CONVEYOR,
MIXERS, EXTRUDERS, PELLATISERS, FEED MOTORS,
PROCESS-LINE SECTIONS, etc.,
• CONSTANT HORSE-POWER APPLICATION – eg., MACHINE
TOOL SPINDLES, PROCESS LINE CONVEYORS, etc.,
• VARIABLE TORQUE APPLICATION – eg., CENTRIFUGAL
FANS AND PUMPS, COMPRESSORS, etc.,
• RANDOM VARIATION OF TORQUE – eg., CRUSHERS,
GRINDING MILLS, etc.,
• DC MOTORS ARE WELL SUITED FOR THE FIRST TWO
APPLICATIONS CONSIDERING THE SIMPLICITY OF
CONTROLS. THIS IS IN CONTRAST TO AC MOTORS WHERE
THE SAME CAN BE ACHIEVED THROUGH EXPENSIVE
CONTROLS.
POET CONSULTANTS PVT. LTD.
MOTORS
IN ADDITION TO THIS, SPEED CONTROL ALSO PLAYS AN
IMPORTANT ROLE IN THE SELECTION OF DC MOTOR FOR
A GIVEN APPLICATION. THERE ARE BASICALLY THREE
IMPORTANT SELECTION CRITERION, WHICH ARE
DETAILED AS BELOW:
• PERFORMANCE – WHILE SELECTING DC MOTORS
PERFORMANCE PARAMETERS ARE TO CONSIDERED:
• EFFICIENCY
• REDUCED SPEED OPERATION
• SPACE EFFICIENCY,
POET CONSULTANTS PVT. LTD.
MOTORS
• CONSTANT HP
• SPEED RANGE,
• REGENERATION,
• DYNAMIC BRAKING.
• DC MOTOR SCORES OVER AC MOTORS IN MOST OF THE
ABOVE POINTS. IN ADDITION TO THIS THE FIRST COST
ALSO IS LOW WITH THESE FEATURES IN COMPARISON
WITH AC MOTORS.
POET CONSULTANTS PVT. LTD.
MOTORS
LIMITATIONS
DUE TO NON-SINUSOIDAL SOURCE OF POWER SUPPLY,
SMOOTHENING OF RIPPLE REQUIRED FOR DC MOTORS.
WHEN SPEED VARIATION IS WIDE, DC MOTORS HAVE TO
BE COMPENSATED FOR ADVERSE COMMUTATION
CONDITIONS. PROLONGED OPERATION AT LOW SPEEDS
CALLS FOR FORCED COOLING, WHICH NEED TO BE
CONSIDERED FOR LOW SPEED APPLICATIONS,
PREFERABLY WITH AN EXTERNALLY POWERED
COOLING FAN MOTOR.
POET CONSULTANTS PVT. LTD.
MOTORS
• HOWEVER, THE SELECTION OF TYPE OF DRIVE
REQUIRES A DETAILED APPLICATION STUDY
INCLUDING TECHNO-ECONOMIC FEASIBILITY.
• SOME TYPICAL APPLICATIONS OF DC MOTORS ARE
PROCESS INDUSTRIES:
• PAPER
• TEXTILES
POET CONSULTANTS PVT. LTD.
MOTORS
Motor Speed 1500 RPM Efficiency η % Power Factor
Cos
DC Motors 1 to 10KW 70 to 84
11 to 100KW 84 to 92
101 to 1000KW 92 to 95 -
AC Slip Ring
Motors 11 to 100KW 0.79 to 0.87
101 to 500KW 93 to 95 0.87 to 0.91
AC Squirrel Cage
Motor < 1KW 53 to 74 0.67 to 0.78
1 to 11KW 74 to 88 0.81 to 0.85
12 to 132KW 88 to 95 0.86 to 0.88
133 to 400KW 95 to 97 0.88 to 0.89
POET CONSULTANTS PVT. LTD.
MOTORS
CRITERION OF SELECTING THE TERMINAL
VOLTAGE FOR MOTORS:
FOR SQUIRREL CAGE INDUCTION MOTORS:
• MOTORS UP TO 175KW ARE RECOMMENDED TO BE
RATED AT 415 VOLTS.
• MOTORS RATED 175KW AND ABOVE ARE
RECOMMENDED TO BE RATED AT 3.3 KV OR 6.6 KV OR
11 KV DEPENDING ON THE OVERALL COST
ECONOMICS CONSIDERING TRANSFORMER COST, HT
SWITCHGEAR COST, CABLE COST AND MOTOR COST.
POET CONSULTANTS PVT. LTD.
MOTORS
• WHEN THE POWER REQUIREMENTS FOR THE DRIVEN
EQUIPMENT ARE LARGE eg. > 400KW. NOTE: FOR
RATINGS IN THE RANGE OF 175 TO 400 KW COST
ECONOMICS NEEDS TO BE DONE CONSIDERING HV
AND MV MOTORS, WITH ASSISTED OR SOFT STARTERS
FOR MV.
• THE VOLTAGE DIP DUE TO STARTING TO BE LIMITED
TO SAFE LIMITS (SAY WITH IN 15%).
POET CONSULTANTS PVT. LTD.
MOTORS
SALIENT FEATURES OF HV MOTORS:
• EMBEDDED TEMPERATURE DETECTORS – MINIMUM OF
SIX NUMBERS OF RESISTANCE TYPE TEMPERATURE
DETECTORS FOR THE STATOR WINDING AT LOCATIONS
WHERE HIGHEST TEMPERATURES MAY BE EXPECTED.
• BEARING THERMOMETERS – DIAL TYPE THERMOMETERS
HAVING TWO SEPARATE NO CONTACT, SHALL BE
PROVIDED FOR EACH BEARING.
• SPACE HEATERS – TO PREVENT MOISTURE
CONDENSATION ON THE INSULATION DURING SHUT
DOWN PERIODS, 240V, 50HZ OPERATED SPACE HEATERS
OF ADEQUATE CAPACITY TO KEEP THE INTERNAL
TEMPERATURE OF THE MOTOR ABOVE DUE POINT.
POET CONSULTANTS PVT. LTD.
MOTORS
• DRAIN PLUGS – DRAIN PLUGS SHALL BE PROVIDED TO
DRAIN WATER RESULTING FROM CONDENSATION OR
OTHER CAUSES FROM ALL POCKETS IN THE MOTOR
CASING.
• FLOW SWITCHES – IN CASE OF CACW MOTORS, FLOW
SWITCHES TO BE PROVIDED FOR MONITORING COOLING
WATER FLOW.
• TERMINAL BOX – SEPARATE TERMINAL BOXES SHALL BE
PROVIDED FOR STATOR LEADS, SPACE HEATERS,
TEMPERATURE DETECTORS. METAL BARRIERS WITHIN
THE TERMINAL BOXES SHALL SEGREGATE HV PHASE
TERMINALS.
• THE INSULATION CLASS OF HV MOTORS SHALL BE
CLASS F LIMITED TO CLASS B TEMPERATURE RISE
LIMITS
POET CONSULTANTS PVT. LTD.
MOTORS
PROTECTION REQUIREMENTS FOR MOTORS:
WHILE DECIDING ON THE TYPE OF PROTECTIONS FOR A
TYPICAL MOTOR APPLICATION THE FOLLOWING POINTS
CAN BE CONSIDERED AS GUIDELINES:
• DECIDE ON THE TYPE OF STARTING METHOD AND
CONTROL SCHEME FOR THE MOTOR BASED ON THE
APPLICATION.
• IF THE CONTROL GEAR IS REMOTELY LOCATED, ON LOAD
ISOLATOR AND OR LOCAL STOP PUSH BUTTON
STATIONS NEAR THE MOTOR TO BE CONSIDERED AS PER
IE RULES.
• IF THE MOTOR SERVICE IS ESSENTIAL, THEN, SELF-
STARTING FEATURE IS TO BE CONSIDERED FOR THE
CONTROL CIRCUIT.
POET CONSULTANTS PVT. LTD.
MOTORS
• PROPER ANNUNCIATION/ ALARM SCHEMES SHALL BE
CONSIDERED FOR FAULT TRIPS, ABNORMALITIES, etc.,
WITH INDICATIONS AT BOTH LOCAL AND REMOTE ENDS
AS REQUIRED .
• BASIC METERING LIKE AMMETER MAY BE CONSIDERED.
• SPACE HEATERS FOR KEEPING THE WINDINGS WARM TO
AVOID CONDENSATION MAY BE CONSIDERED FOR
MOTORS RATED> 30KW.
• BASIC PROTECTIONS TO BE PROVIDED FOR MOTORS
SHALL INCLUDE SHORT CIRCUIT AND THERMAL
OVERLOAD PROTECTION.
• FOR MOTORS RATED > 100KW, LOCKED ROTOR
PROTECTION SHALL BE PROVIDED.
• SUFFICIENT NUMBER OF AUX. POTENTIAL FREE
CONTACTS TO BE CONSIDERED FOR INTERLOCKING
PURPOSES.
POET CONSULTANTS PVT. LTD.
MOTORS
IN CASE OF HV MOTORS THE FOLLOWING POINTS NEED TO
BE CONSIDERED WHILE DESIGNING THE PROTECTIONS:
• AMMETER SHALL BE PROVIDED.
• SUFFICIENT NUMBER OF AUX. POTENTIAL FREE
CONTACTS TO BE CONSIDERED FOR INTERLOCKING
PURPOSES.
• SHORT CIRCUIT PROTECTION BY INSTANTANEOUS
OVERCURRENT RELAYS IN ALL THREE PHASES.
• OVERLOAD PROTECTION BY THERMAL OVERLOAD
PROTECTION RELAYS ON TWO PHASES. THE OVERLOAD
RELAY SETTING SHALL BE BASED ON THE HOT AND
COLD I2T CHARACTERISTICS OF THE MOTOR.
• LOCKED ROTOR PROTECTION BY TWO OVERCURRENT
INSTANTANEOUS RELAYS (IN R & B PHASES) AND ONE
COMMON TIMER.
POET CONSULTANTS PVT. LTD.
MOTORS
• CENTRIFUGAL TYPE SPEED SWITCH OR OTHER
APPROVED TYPE OF SPEED SENSOR WITH AN
ADDITIONAL TIMER MAY BE USED FOR LOCKED
ROTOR PROTECTION WHERE THE STARTING TIME AT
LOWEST PERMISSIBLE VOLTAGE IS GREATER THAN
THE LOCKED ROTOR WITHSTAND TIME AT HIGHEST
PERMISSIBLE VOLTAGE (110%).
• FOR MOTORS > 1000KW RATING DIFFERENTIAL
PROTECTION BY A HIGH-SPEED TRIPLE POLE RELAY,
WHEN A MOTOR IS STAR WOUND.
• EARTH FAULT PROTECTION BY SINGLE POLE
CURRENT RELAY WHERE THE SYSTEM IS SOLIDLY OR
LOW RESISTANCE GROUNDED.
POET CONSULTANTS PVT. LTD.
MOTORS
• EARTH FAULT PROTECTION BY A SENSITIVE EARTH
FAULT RELAY CONNECTED TO CORE BALANCE CT,
WHERE THE SYSTEM IS GROUNDED THROUGH A HIGH
RESISTANCE.
• UNDER VOLTAGE PROTECTION FOR PROLONGED UNDER
VOLTAGE (LESS THAN 80%) BY TWO NUMBERS BUS
UNDER VOLTAGE RELAYS AND A COMMON TIMER
• OVERLOAD ALARM BY A SINGLE POLE DEFINITE TIME
OVER CURRENT RELAY IN THE Y PHASE.
• COMPOSITE MOTOR PROTECTION RELAY SCHEME CAN
ALSO BE ADOPTED IF IT FULFILS ALL THE ABOVE
PROTECTION REQUIREMENTS
• TEMPERATURE MONITORING – RTD DEVICES IN THE
STATOR WINDINGS TO DETECT THE HOT SPOTS,
SHOULD BE CONNECTED TO TEMPERATURE INDICATOR
WITH ALARM CONTACTS.
POET CONSULTANTS PVT. LTD.
MOTORS
• BEARING TEMP. MONITORING – THE INDICATORS
PROVIDED ON THE BEARINGS SHALL HAVE CONTACT
FOR ALARM PURPOSE.
• FOR CACW MOTORS THE FOLLOWING ADDITIONAL
PROTECTIONS SHALL BE CONSIDERED –
• MOTOR CLOSING CIRCUIT SHALL HAVE
PERMISSIVE INTERLOCK FOR NORMAL WATER
FLOW
• LOW WATER FLOW SHALL GIVE AN ALARM AND
AFTER A TIME DELAY SHALL TRIP THE MOTOR.
• AIR TEMPERATURE INDICATORS, WHEREVER
PROVIDED, SHALL BE CONNECTED FOR ALARM.
POET CONSULTANTS PVT. LTD.
MOTORS
• LUBE OIL PRESSURE MONITOR TO BE CONSIDERED
WHERE FORCED OIL LUBRICATION IS PROVIDED.
MOTOR CLOSING CIRCUIT SHALL HAVE INTERLOCK
FOR NORMAL LUBE OIL PRESSURE.
• FACILITY OF AUTOMATICALLY SWITCHING ON THE
SPACE HEATER WHEN THE MOTOR IS STOPPED TO
PREVENT THE INGRESS OF MOISTURE.
• LOCKABLE TYPE STOP PUSH BUTTONS TO BE
PROVIDED NEAR THE MOTOR WHICH SHALL BE
INCLUDED IN THE CLOSING CIRCUIT.
TESTING OF MOTORS:
• TESTING IS DIVIDED IN TO ROUTINE AND TYPE TEST.
POET CONSULTANTS PVT. LTD.
MOTORS
ROUTINE TESTS:
• MEASUREMENT OF WINDING RESISTANCE
• MEASUREMENT OF NO LOAD LOSS AND CURRENT
• REDUCED VOLTAGE RUNNING UP IN EITHER
DIRECTION OF ROTATION
• LOCKED ROTOR TEST FOR SQUIRREL CAGE
INDUCTION MOTOR
• OPEN CIRCUIT VOLTAGE MEASUREMENT FOR WOUND
ROTOR MOTORS
• INSULATION MEASUREMENT OF WINDINGS
• HIGH VOLTAGE TEST
• IR MEASUREMENT OF SPACE HEATERS, RTD, BTD
• CONTINUITY OF SPACE HEATERS, RTDS, BTDS
POET CONSULTANTS PVT. LTD.
MOTORS
THE FOLLOWING ARE CLASSIFIED AS TYPE TESTS:
• LOAD TEST
• VARIABLE VOLTAGE TEST OR CALIBRATED MACHINE
TEST FOR SEPARATION OF LOSSES.
• TEMPERATURE RISE TEST
• MOMENTARY OVER LOAD TEST
SPECIAL TESTS:
• VIBRATION MEASUREMENT TEST
• DISSIPATION FACTOR
• POLARISATION INDEX
• CAPACITANCE AND LOSS ANGLE MEASUREMENT
POET CONSULTANTS PVT. LTD.
MOTORS
MAINTENANCE OF MOTORS:
PHYSICAL CHECKS NEED TO BE DONE FOR-
• TIGHTNESS OF FOUNDATION/ FIXING BOLTS
• FREE ROTATION OF THE ROTOR IN DE-COUPLED
CONDITION
• SHAFT ALIGNMENT WITH THAT OF THE DRIVEN UNIT.
• ELECTRICAL PARAMETERS TO BE CONSIDERED ARE-
• THE TWO DISTINCT EARTH CONNECTING LEADS FROM
THE BODY OF THE MOTOR TO EARTH MAT ARE IN
GOOD CONDITION.
• CHECK THE IR VALUE OF STATOR WINDING WRIT
EARTH USING 1KV MEGGER (INDIVIDUAL PHASES
ALSO IF AVAILABLE). ALSO CHECK FOR THE
CONTINUITY OF THE WINDINGS.
POET CONSULTANTS PVT. LTD.
MOTORS
• CHECK THE IR VALUE OF ROTOR WINDING WITH
BRUSHES LIFTED USING 500V MEGGER (FOR SLIPRING
MOTOR)
• CHECK THE SEC. CIRCUIT EXTERNAL TO ROTOR
WINDING FOR SLIPRING MOTOR.
• CHECK IR VALUE OF SPACE HEATER WITH RESPECT TO
STATOR WINDING AND EARTH USING A 500V MEGGER.
• CHECK FOR THE SEATING OF BRUSHES IN THE
SLIPRINGS.
POET CONSULTANTS PVT. LTD.
MOTORS
• CHECK FOR THE SEATING OF BRUSHES IN THE
SLIPRINGS.
• CHECK IR VALUES OF CABLE CORES WITH RESPECT
TO EARTH/ ARMOUR/ CORE USING A 1KV MEGGER
AFTER DISCONNECTING THE TERMINATION AT BOTH
THE ENDS. ALSO CHECK FOR THE CONTINUITY OF
THE CABLES.
• CHECK FOR OVERLOAD RELAY SETTINGS (SET AT 90%
OF NAMEPLATE RATING).
POET CONSULTANTS PVT. LTD.
MOTORS
TOTALLY ENCLOSED FAN COOLED
INDUCTION MOTOR
POET CONSULTANTS PVT. LTD.
MOTORS
LARGE INDUCTION MOTOR
POET CONSULTANTS PVT. LTD.
MOTORS
CLOSED AIR CIRCUIT AIR COOLED
INDUCTION MOTOR
POET CONSULTANTS PVT. LTD.
MOTORS
HORIZANTAL FAN MOTOR
WITH TOP CABLE BOX
POET CONSULTANTS PVT. LTD.
MOTORS
TOTALLY ENCLOSED FAN
COOLED MOTOR
POET CONSULTANTS PVT. LTD.
MOTORS
SCREEN PROTECTED
SQUIRREL CAGE MOTOR
POET CONSULTANTS PVT. LTD.
MOTORS
FLAMEPROOF SQUIRREL CAGE
MOTOR
POET CONSULTANTS PVT. LTD.
MOTORS
VERTICALLY MOUNTED MOTORS

More Related Content

Similar to TRAINING AND BASICS ON MOTORS FOR BEGINNERS

5001 101 (ac installation instructions)
5001 101 (ac installation instructions)5001 101 (ac installation instructions)
5001 101 (ac installation instructions)
feryjaya
 
Servo Motors Adjust-English
Servo Motors Adjust-EnglishServo Motors Adjust-English
Servo Motors Adjust-English
Marc Vendrell
 
Kohler courage sv600 vertical crankshaft engine service repair manual
Kohler courage sv600 vertical crankshaft engine service repair manualKohler courage sv600 vertical crankshaft engine service repair manual
Kohler courage sv600 vertical crankshaft engine service repair manual
fjsjekkdmme
 
Kohler courage sv470 vertical crankshaft engine service repair manual
Kohler courage sv470 vertical crankshaft engine service repair manualKohler courage sv470 vertical crankshaft engine service repair manual
Kohler courage sv470 vertical crankshaft engine service repair manual
fjskekqaswdmmem
 
Kohler courage sv620 vertical crankshaft engine service repair manual
Kohler courage sv620 vertical crankshaft engine service repair manualKohler courage sv620 vertical crankshaft engine service repair manual
Kohler courage sv620 vertical crankshaft engine service repair manual
fuekdksmemm
 
Kohler courage sv480 vertical crankshaft engine service repair manual
Kohler courage sv480 vertical crankshaft engine service repair manualKohler courage sv480 vertical crankshaft engine service repair manual
Kohler courage sv480 vertical crankshaft engine service repair manual
fjskekqazdmmem
 
Kohler courage sv530 vertical crankshaft engine service repair manual
Kohler courage sv530 vertical crankshaft engine service repair manualKohler courage sv530 vertical crankshaft engine service repair manual
Kohler courage sv530 vertical crankshaft engine service repair manual
kfdjkskdmm
 
Kohler courage sv540 vertical crankshaft engine service repair manual
Kohler courage sv540 vertical crankshaft engine service repair manualKohler courage sv540 vertical crankshaft engine service repair manual
Kohler courage sv540 vertical crankshaft engine service repair manual
fjskekmmem
 
Kohler courage sv590 vertical crankshaft engine service repair manual
Kohler courage sv590 vertical crankshaft engine service repair manualKohler courage sv590 vertical crankshaft engine service repair manual
Kohler courage sv590 vertical crankshaft engine service repair manual
fjeisldkmemm
 

Similar to TRAINING AND BASICS ON MOTORS FOR BEGINNERS (20)

introductiont to automotive standards.pptx
introductiont to automotive standards.pptxintroductiont to automotive standards.pptx
introductiont to automotive standards.pptx
 
Outboard engine
Outboard engineOutboard engine
Outboard engine
 
Гидромоторы White
Гидромоторы WhiteГидромоторы White
Гидромоторы White
 
Dc vs ac drives
Dc  vs ac  drivesDc  vs ac  drives
Dc vs ac drives
 
IEEE Motor Presentation
IEEE Motor PresentationIEEE Motor Presentation
IEEE Motor Presentation
 
5001 101 (ac installation instructions)
5001 101 (ac installation instructions)5001 101 (ac installation instructions)
5001 101 (ac installation instructions)
 
phev
phevphev
phev
 
Servo Motors Adjust
Servo Motors Adjust Servo Motors Adjust
Servo Motors Adjust
 
Servo Motors Adjust-English
Servo Motors Adjust-EnglishServo Motors Adjust-English
Servo Motors Adjust-English
 
Types of single phase induction motor
Types of single phase induction motorTypes of single phase induction motor
Types of single phase induction motor
 
Kohler courage sv600 vertical crankshaft engine service repair manual
Kohler courage sv600 vertical crankshaft engine service repair manualKohler courage sv600 vertical crankshaft engine service repair manual
Kohler courage sv600 vertical crankshaft engine service repair manual
 
Kohler courage sv470 vertical crankshaft engine service repair manual
Kohler courage sv470 vertical crankshaft engine service repair manualKohler courage sv470 vertical crankshaft engine service repair manual
Kohler courage sv470 vertical crankshaft engine service repair manual
 
Kohler courage sv620 vertical crankshaft engine service repair manual
Kohler courage sv620 vertical crankshaft engine service repair manualKohler courage sv620 vertical crankshaft engine service repair manual
Kohler courage sv620 vertical crankshaft engine service repair manual
 
Kohler courage sv480 vertical crankshaft engine service repair manual
Kohler courage sv480 vertical crankshaft engine service repair manualKohler courage sv480 vertical crankshaft engine service repair manual
Kohler courage sv480 vertical crankshaft engine service repair manual
 
Kohler courage sv530 vertical crankshaft engine service repair manual
Kohler courage sv530 vertical crankshaft engine service repair manualKohler courage sv530 vertical crankshaft engine service repair manual
Kohler courage sv530 vertical crankshaft engine service repair manual
 
Kohler courage sv540 vertical crankshaft engine service repair manual
Kohler courage sv540 vertical crankshaft engine service repair manualKohler courage sv540 vertical crankshaft engine service repair manual
Kohler courage sv540 vertical crankshaft engine service repair manual
 
Kohler courage sv590 vertical crankshaft engine service repair manual
Kohler courage sv590 vertical crankshaft engine service repair manualKohler courage sv590 vertical crankshaft engine service repair manual
Kohler courage sv590 vertical crankshaft engine service repair manual
 
Controlling fip to compensate load in tractor
Controlling fip to compensate load in tractorControlling fip to compensate load in tractor
Controlling fip to compensate load in tractor
 
Sei ppt
Sei pptSei ppt
Sei ppt
 
Sei ppt
Sei pptSei ppt
Sei ppt
 

Recently uploaded

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
ankushspencer015
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 

Recently uploaded (20)

VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Ankleshwar 7001035870 Whatsapp Number, 24/07 Booking
 
chapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineeringchapter 5.pptx: drainage and irrigation engineering
chapter 5.pptx: drainage and irrigation engineering
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)Java Programming :Event Handling(Types of Events)
Java Programming :Event Handling(Types of Events)
 
University management System project report..pdf
University management System project report..pdfUniversity management System project report..pdf
University management System project report..pdf
 
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELLPVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
PVC VS. FIBERGLASS (FRP) GRAVITY SEWER - UNI BELL
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
AKTU Computer Networks notes --- Unit 3.pdf
AKTU Computer Networks notes ---  Unit 3.pdfAKTU Computer Networks notes ---  Unit 3.pdf
AKTU Computer Networks notes --- Unit 3.pdf
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Online banking management system project.pdf
Online banking management system project.pdfOnline banking management system project.pdf
Online banking management system project.pdf
 
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...Bhosari ( Call Girls ) Pune  6297143586  Hot Model With Sexy Bhabi Ready For ...
Bhosari ( Call Girls ) Pune 6297143586 Hot Model With Sexy Bhabi Ready For ...
 
Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024Water Industry Process Automation & Control Monthly - April 2024
Water Industry Process Automation & Control Monthly - April 2024
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
UNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its PerformanceUNIT - IV - Air Compressors and its Performance
UNIT - IV - Air Compressors and its Performance
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
The Most Attractive Pune Call Girls Manchar 8250192130 Will You Miss This Cha...
 

TRAINING AND BASICS ON MOTORS FOR BEGINNERS

  • 1. POET CONSULTANTS PVT. LTD. TRAINING ON
  • 2. POET CONSULTANTS PVT. LTD. TRAINING COURSE ON MOTORS
  • 3. POET CONSULTANTS PVT. LTD. MOTORS • GENERAL • BASIC TECHNICAL REQUIREMENTS • SAFETY ASPECTS • APPROVED MAKES • LV MOTORS • HV MOTORS • SELECTION CRITERION
  • 4. POET CONSULTANTS PVT. LTD. MOTORS • BRIEF SPECIFICATIONS • PROTECTION & CONTROL REQUIREMENTS • ENERGY EFFICIENT MOTORS & EVALUATION CRITERION • MAINTENANCE SCHEDULE • APPLICABLE STANDARDS • APPENDIX – 1 • APPENDIX - 2
  • 5. POET CONSULTANTS PVT. LTD. GENERAL: UNDER THIS HEADING, APPLICABLE STANDARDS AND APPLICATION OF MOTORS ARE COVERED APPLICABLE STANDARDS: • USER COMPANY SAFETY STANDARDS • IE ACTS AND RULES • IS/ BS/ IEC/ IEEE STANDARDS APPLICATION: • TYPE OF INSTALLATION - INDOOR/ OUTDOOR • AREA OF USAGE - FACTORY, WAREHOUSE, OFFICE, OFF-SHORE, HAZARDOUS, etc., • TYPE OF MOTOR - GENERAL PURPOSE OR SPECIAL PURPOSE MOTORS
  • 6. POET CONSULTANTS PVT. LTD. SAFETY ASPECTS: DUE CONSIDERATION FOR THE SAFETY OF PERSONNEL AND THE INSTALLATION IS IMPORTANT. MAIN CATEGORIES ADDRESSED UNDER SAFETY ASPECT ARE:  RATINGS  ENCLOSURE  TERMINATION ARRANGEMENTS  SAFETY ACCESSORIES MOTORS
  • 7. POET CONSULTANTS PVT. LTD. RATING ASPECT: WHILE SELECTING THE RATINGS FOR ANY APPLICATION/ VERIFICATION OF RATING FOR ALREADY EXISTING INSTALLATION THE FOLLOWING KEY CRITERION HAVE TO BE LOOKED INTO:  10% MARGIN OVER DRIVEN EQUIPMENT  VOLTAGE AND FREQUENCY VARIATION SHALL BE +/- 10% AND +/-5% RESPECTIVELY WITH A COMBINED VARIATION OF +/-10%  DESIGN AMBIENT TEMP. SHALL BE PROPERLY SPECIFIED. TEMP. RISE ABOVE DESIGN AMBIENT TO BE AS PER PERMISSIBLE FINAL TEMP. OF THE SPECIFIED CLASS OF INSULATION MOTORS
  • 8. POET CONSULTANTS PVT. LTD. MOTORS  STARTING TORQUE SHOULD BE ADEQUATE EVEN WITH 85% OF NOMINAL VOLTAGE FOR LT MOTORS AND 80% FOR HT MOTORS.  FOR NORMAL APPLICATIONS, THE STARTING TORQUE SHALL BE MINIMUM TWICE THE FULL LOAD TORQUE.  NORMALLY THE SELECTION OF ONE FRAME SIZE HIGHER MOTOR THAN THAT RECOMMENDED BY THE MOTOR SUPPLIER FOR GIVEN DRIVE DUTY WILL TAKE CARE OF THE ABOVE REQUIREMENTS
  • 9. POET CONSULTANTS PVT. LTD. ENCLOSURE: THIS PLAYS AN IMPORTANT ROLE IN DECIDING THE LIFE OF THE MOTOR. A WRONG ENCLOSURE LEADS TO PRE-MATURE FAILURE OF INSULATION OR INCREASED MAINTENANCE. THE FOLLOWING POINTS ARE TO BE CONSIDERED: • IP 54 FOR INDOOR AND IP 55 FOR OUTDOOR APPLICATIONS (HOWEVER, FOR INDUSTRIES SUCH AS PAPER, WHERE THE USAGE OF WATER IS VERY HIGH, IP-55 MAY BE CONSIDERED EVEN FOR INDOOR APPLICATION. • FLAMEPROOF FOR HAZARDOUS AREA MOTORS
  • 10. POET CONSULTANTS PVT. LTD. MOTORS ANY OTHER ENCLOSURE SHALL BE SELECTED WITH CARE WITH FULL KNOWLEDGE OF SITE CONDITIONS. SOME OF THEM ARE LISTED BELOW: • DRIP-PROOF GUARDED FORCE VENTILATED • DRIP-PROOF GUARDED SEPARATELY VENTILATED • TOTALLY ENCLOSED AIR OVER-BLOWER COOLED • TOTALLY ENCLOSED NON VENTILATED • TOTALLY ENCLOSED FAN COOLED
  • 11. POET CONSULTANTS PVT. LTD. MOTORS • DUST PROOF TACONITE FEATURES ( BEARINGS PROVIDED WITH PROTECTION AGAINST ABRASIVE DUST) • XT FEATURES (PROVIDES PROTECTION AGAINST CORROSIVE, MOIST AND DUST LADEN ATMOSPHERE AS ENCOUNTERED IN PAPER, CHEMICAL AND SIMILAR INDUSTRIES) • PAPER MILL DUTY FEATURES( FOR OPERATION OF WET END OF PAPER MILLS) • TOTALLY ENCLOSED PIPE VENTILATED ( COOLED BY CUSTOMER SUPPLIED PIPED AIR)
  • 12. POET CONSULTANTS PVT. LTD. MOTORS TERMINATION ARRANGEMENT: GENERALLY IT IS OBSERVED THAT DUE IMPORTANCE IS NOT GIVEN TO TERMINATION ARRANGEMENT IN THE MOTORS. THIS LEADS TO FAILURE OF MOTORS DUE TO INGRESS OF MOISTURE, DUST, HEATING, RODENT ENTRY, etc. THE FOLLOWING KEY POINTS SHALL BE TAKEN NOTE OF FOR PROPER TERMINATION ARRANGEMENT IN A MOTOR:
  • 13. POET CONSULTANTS PVT. LTD. • THE TERMINAL BOX SHALL WITHSTAND SPECIFIED SHORT CIRCUIT CURRENT FOR 0.2 SEC. • MINIMUM CLEARANCES FOR PHASE TO PHASE AND TO EARTH BETWEEN CABLE LUGS AND BODY SHALL BE MAINTAINED. • FOR HV MOTORS PHASE SEGREGATION TO BE CONSIDERED • WHENEVER SEAL OFF BUSHINGS ARE USED, THEY SHALL HAVE MINIMUM CREEPAGE DISTANCES AS PER IS. • TERMINALS HAVE TO BE MADE OF AT LEAST EPOXY INSULATED, AND FOR HIGH VOLTAGES PORCELAIN SHALL BE USED. PHENOLIC RESIN AND BAKELITE SHALL NOT BE USED. MOTORS
  • 14. POET CONSULTANTS PVT. LTD. SIZE OF TERMINAL BLOCK SHALL BE LARGE ENOUGH TO ACCOMMODATE ALUMINIUM CABLES PROPERLY DEGREE OF PROTECTION OF TERMINAL BOX SHALL THE SAME AS THAT OF THE MOTOR BODY. SAFETY ACCESSORIES: USE OF CERTAIN AVAILABLE ACCESSORIES ENHANCES THE SAFETY AND RELIABILITY OF THE SYSTEM AND THE EQUIPMENT. SOME OR ALL OF THE FOLLOWING ACCESSORIES CAN BE CONSIDERED DEPENDING ON THE TYPE OF THE MOTOR, INSTALLATION, etc., MOTORS
  • 15. POET CONSULTANTS PVT. LTD. • SAFE LIFTING FACILITIES LIKE EYEBOLT, etc., FOR MOTORS WEIGHING MORE THAN 25KGS. • GREASING PLUG- RECOMMENDED FOR FRAME SIZE 200 AND ABOVE. • EFFORTS SHALL BE MADE TO STANDARDISE THE TYPE OF GREASE USED, PREFERABLY LITHIUM BASED MP3. USE OF EXCESSIVE GREASE SHALL BE AVOIDED • BTD AND RTD FOR HV MOTORS. MOTORS
  • 16. POET CONSULTANTS PVT. LTD. MOTORS • ANTI CONDENSATION HEATERS FOR MOTORS ABOVE 30KW. THESE SHALL BE INTERLOCKED WITH THE MOTOR STARTER SUCH THAT THEY SHALL BE ON ONLY WHEN THE MOTOR IS OFF • SEPARATE EARTHING TERMINALS FOR BODY (MIN. 2 NOS.) AND EACH TERMINAL BOX. • LOCAL BEARING TEMPERATURE INDICATORS FOR HV MOTORS WITH ALARM AND TRIP CONTACTS
  • 17. POET CONSULTANTS PVT. LTD. MOTORS • HOW TO SELECT A MAKE OF MOTOR? • WHAT ARE THE PARAMETERS WHICH NEED TO BE LOOKED IN TO WHILE SELECTING A MAKE OF MOTOR: WHILE SELECTING A PARTICULAR MAKE OF EQUIPMENT, IT IS SUGGESTED THAT THE FOLLOWING POINTS BE STUDIED BEFORE MAKING A FINAL DECISION: • EXISTING MAKES IN THE INSTALLATION
  • 18. POET CONSULTANTS PVT. LTD. • PERFORMANCE OF THE EXISTING MAKES • STANDARDISATION REQUIREMENTS FOR THE INSTALLATION • AVAILABILITY AND SERVICEABILITY AT THE PLACE OF USAGE • PREVIOUS EXPERIENCE WITH THE MAKE SELECTED MOTORS
  • 19. POET CONSULTANTS PVT. LTD. SOME OF REPUTED MOTOR MANUFACTURERS IN THE COUNTRY AND THEIR RANGE OF MANUFACTURE: MANUFACTURER LT AC HT AC DC MOTOR MOTOR MOTOR Crompton Greaves Yes No Yes Kirloskar Electric co. ltd. Yes Yes Yes Integrated Electric Co Ltd. No NO Yes Siemens Yes No No NGEF Yes Yes Yes Bhel No Yes Yes Bharath Bijlee Ltd. Yes No No MOTORS
  • 20. POET CONSULTANTS PVT. LTD. TYPE OF STARTING FOR MOTORS: • FURTHER, TYPE OF STARTING FOR THE MOTORS HAS TO BE DECIDED BASED ON THE ALLOWABLE VOLTAGE DIP ON THE SYSTEM AND MAGNITUDE OF STARTING CURRENT. • THE FOLLOWING POINTS NEED TO BE CONSIDERED WHILE SELECTING TYPE OF STARTING/ MOTORS: MOTORS ORDERED FOR DIRECT ON LINE (DOL) STARTING ARE NOT SUITABLE FOR ASSISTED STARTING (LIKE STAR- DELTA). HOWEVER MOTORS ORDERED FOR ASSISTED START ARE SUITABLE FOR DOL. HENCE, THE TYPE OF STARTING SHALL BE FIRMED UP BEFORE ORDERING. MOTORS
  • 21. POET CONSULTANTS PVT. LTD. • MOTORS SHALL BE CAPABLE OF STARTING AND ACCELERATING THE LOAD EVEN AT 85% OF THE RATED VOLTAGE WITHOUT EXCEEDING ACCEPTABLE WINDING TEMPERATURE. • THE STARTING CURRENT SHALL GENERALLY NOT EXCEED 600% OF THE FULL LOAD CURRENT. HOWEVER FOR LOW RATING MOTORS STARTING CURRENTS UPTO 800% CAN BE ACCEPTED SUBJECT TO STARTING VOLTAGE DIPS BEING WITHIN LIMITS AS STATED ABOVE, IF SUBSTANTIAL COST BENEFITS ARE AVAILABLE. • MOTORS SHALL BE DESIGNED TO WITHSTAND 120% OF RATED SPEED FOR TWO MINUTES WITHOUT ANY MECHANICAL DAMAGE, IN EITHER DIRECTION OF ROTATION MOTORS
  • 22. POET CONSULTANTS PVT. LTD. • THE VOLTAGE DROP AT MOTOR TERMINALS DURING STARTING SHALL NOT EXCEED 20% FOR HT MOTORS AND 15% FOR LT MOTORS • A STARTING VOLTAGE DROP CALCULATION SHALL BE CARRIED OUT THE DECIDE THE TYPE OF STARTING. FOR VERY LARGE MOTORS, SOFT STARTERS CAN BE CONSIDERED. • STAR DELTA STARTER UPTO 100 KW CAN BE WITHOUT THE RESISTANCE TYPE. HOWEVER, MOTORS LARGER THAN 100 KW SHALL BE PROVIDED WITH 4- CONTRACTOR SCHEME WITH EXTERNAL RESISTOR AND SHORTING CONTRACTOR TO AVOID BREAK IN THE CURRENT DURING CHANGE FROM STAR TO DELTA. MOTORS
  • 23. POET CONSULTANTS PVT. LTD. • SELECTION OF SOFT STARTER DEPENDS ON THE FOLLOWING- • IF THE VOLTAGE DROP DURING STARTING IS HIGHER THAN THAT DEFINED ABOVE WHILE STARTING ON IN- HOUSE GENERATION LIKE DG SET OR TG SET • IF THE NUMBER OF START-STOPS ARE MORE THAN 3 TIMES PER HOUR AS PER PROCESS REQUIREMENT (HERE THE CONSTRAINT IS THE CIRCUIT BREAKER WHOSE MECHANICAL LIFE IS ABOUT 5000 OPERATIONS; THE COST OF SOFT STARTER HAS TO BE WEIGHED AGAINST THE REPLACEMENT COST OF THE CIRCUIT BREAKER OVER A FIXED LIFE TIME) MOTORS
  • 24. POET CONSULTANTS PVT. LTD. MOTORS DC MOTORS: • WHEN CONSTANT TORQUE AND SPEED CONTROL APPLICATIONS ARE INVOLVED, DC MOTORS ARE SELECTED. GENERAL GUIDELINES DETAILED FOR AC MOTORS ARE ALSO APPLICABLE FOR DC MOTORS. IN ADDITION TO THIS, THE FOLLOWING GUIDELINES ARE ALSO APPLICABLE FOR THIS TYPE OF MOTORS: • MOTORS SHALL BE CAPABLE OF GIVING RATED OUTPUT WITHOUT REDUCTION IN THE EXPECTED LIFE SPAN WHEN OPERATED CONTINUOUSLY AT A SUPPLY VOLTAGE WITHIN 5% FROM THE RATED VALUE.
  • 25. POET CONSULTANTS PVT. LTD. MOTORS • CAPABLE OF STARTING AND ACCELERATING THE LOAD WITH APPLICABLE METHODS OF STARTING, WITHOUT EXCEEDING ACCEPTABLE WINDING TEMPERATURE, WHEN THE SUPPLY VOLTAGE IS 85% OF THE RATED VALUE. • MOTORS SHALL BE DESIGNED TO WITH STAND 120% OF RATED SPEED FOR TWO MINUTES WITHOUT ANY MECHANICAL DAMAGE IN EITHER DIRECTION OF ROTATION. • PROPER DUTY CYCLE SELECTION HAS TO BE DONE. • THE FIELD WINDINGS FOR THE MOTORS SHALL BE CONTINUOUSLY RATED WITHOUT FORCED VENTILATION
  • 26. POET CONSULTANTS PVT. LTD. • LARGE SIZE MOTORS SHALL BE OF HORIZONTALLY SPLIT CONSTRUCTION FOR EASY MAINTENANCE. • THE FIELD WINDING SHALL NOT BE POWERED WITHOUT FORCED VENTILATION, UNLESS IT IS A SPECIAL APPLICATION. • THE DUTY CLASS AS PER IEC STANDARD SHALL BE FOLLOWED. DC MOTOR SELECTION: • GENERALLY, TYPES OF DRIVES ARE SELECTED BASED ON THE SPEED TORQUE CHARACTERISTIC OF THE LOAD, WHICH CAN BE CATEGORIZED AS FOLLOWS: MOTORS
  • 27. POET CONSULTANTS PVT. LTD. MOTORS • CONSTANT TORQUE APPLICATION – eg. CONVEYOR, MIXERS, EXTRUDERS, PELLATISERS, FEED MOTORS, PROCESS-LINE SECTIONS, etc., • CONSTANT HORSE-POWER APPLICATION – eg., MACHINE TOOL SPINDLES, PROCESS LINE CONVEYORS, etc., • VARIABLE TORQUE APPLICATION – eg., CENTRIFUGAL FANS AND PUMPS, COMPRESSORS, etc., • RANDOM VARIATION OF TORQUE – eg., CRUSHERS, GRINDING MILLS, etc., • DC MOTORS ARE WELL SUITED FOR THE FIRST TWO APPLICATIONS CONSIDERING THE SIMPLICITY OF CONTROLS. THIS IS IN CONTRAST TO AC MOTORS WHERE THE SAME CAN BE ACHIEVED THROUGH EXPENSIVE CONTROLS.
  • 28. POET CONSULTANTS PVT. LTD. MOTORS IN ADDITION TO THIS, SPEED CONTROL ALSO PLAYS AN IMPORTANT ROLE IN THE SELECTION OF DC MOTOR FOR A GIVEN APPLICATION. THERE ARE BASICALLY THREE IMPORTANT SELECTION CRITERION, WHICH ARE DETAILED AS BELOW: • PERFORMANCE – WHILE SELECTING DC MOTORS PERFORMANCE PARAMETERS ARE TO CONSIDERED: • EFFICIENCY • REDUCED SPEED OPERATION • SPACE EFFICIENCY,
  • 29. POET CONSULTANTS PVT. LTD. MOTORS • CONSTANT HP • SPEED RANGE, • REGENERATION, • DYNAMIC BRAKING. • DC MOTOR SCORES OVER AC MOTORS IN MOST OF THE ABOVE POINTS. IN ADDITION TO THIS THE FIRST COST ALSO IS LOW WITH THESE FEATURES IN COMPARISON WITH AC MOTORS.
  • 30. POET CONSULTANTS PVT. LTD. MOTORS LIMITATIONS DUE TO NON-SINUSOIDAL SOURCE OF POWER SUPPLY, SMOOTHENING OF RIPPLE REQUIRED FOR DC MOTORS. WHEN SPEED VARIATION IS WIDE, DC MOTORS HAVE TO BE COMPENSATED FOR ADVERSE COMMUTATION CONDITIONS. PROLONGED OPERATION AT LOW SPEEDS CALLS FOR FORCED COOLING, WHICH NEED TO BE CONSIDERED FOR LOW SPEED APPLICATIONS, PREFERABLY WITH AN EXTERNALLY POWERED COOLING FAN MOTOR.
  • 31. POET CONSULTANTS PVT. LTD. MOTORS • HOWEVER, THE SELECTION OF TYPE OF DRIVE REQUIRES A DETAILED APPLICATION STUDY INCLUDING TECHNO-ECONOMIC FEASIBILITY. • SOME TYPICAL APPLICATIONS OF DC MOTORS ARE PROCESS INDUSTRIES: • PAPER • TEXTILES
  • 32. POET CONSULTANTS PVT. LTD. MOTORS Motor Speed 1500 RPM Efficiency η % Power Factor Cos DC Motors 1 to 10KW 70 to 84 11 to 100KW 84 to 92 101 to 1000KW 92 to 95 - AC Slip Ring Motors 11 to 100KW 0.79 to 0.87 101 to 500KW 93 to 95 0.87 to 0.91 AC Squirrel Cage Motor < 1KW 53 to 74 0.67 to 0.78 1 to 11KW 74 to 88 0.81 to 0.85 12 to 132KW 88 to 95 0.86 to 0.88 133 to 400KW 95 to 97 0.88 to 0.89
  • 33. POET CONSULTANTS PVT. LTD. MOTORS CRITERION OF SELECTING THE TERMINAL VOLTAGE FOR MOTORS: FOR SQUIRREL CAGE INDUCTION MOTORS: • MOTORS UP TO 175KW ARE RECOMMENDED TO BE RATED AT 415 VOLTS. • MOTORS RATED 175KW AND ABOVE ARE RECOMMENDED TO BE RATED AT 3.3 KV OR 6.6 KV OR 11 KV DEPENDING ON THE OVERALL COST ECONOMICS CONSIDERING TRANSFORMER COST, HT SWITCHGEAR COST, CABLE COST AND MOTOR COST.
  • 34. POET CONSULTANTS PVT. LTD. MOTORS • WHEN THE POWER REQUIREMENTS FOR THE DRIVEN EQUIPMENT ARE LARGE eg. > 400KW. NOTE: FOR RATINGS IN THE RANGE OF 175 TO 400 KW COST ECONOMICS NEEDS TO BE DONE CONSIDERING HV AND MV MOTORS, WITH ASSISTED OR SOFT STARTERS FOR MV. • THE VOLTAGE DIP DUE TO STARTING TO BE LIMITED TO SAFE LIMITS (SAY WITH IN 15%).
  • 35. POET CONSULTANTS PVT. LTD. MOTORS SALIENT FEATURES OF HV MOTORS: • EMBEDDED TEMPERATURE DETECTORS – MINIMUM OF SIX NUMBERS OF RESISTANCE TYPE TEMPERATURE DETECTORS FOR THE STATOR WINDING AT LOCATIONS WHERE HIGHEST TEMPERATURES MAY BE EXPECTED. • BEARING THERMOMETERS – DIAL TYPE THERMOMETERS HAVING TWO SEPARATE NO CONTACT, SHALL BE PROVIDED FOR EACH BEARING. • SPACE HEATERS – TO PREVENT MOISTURE CONDENSATION ON THE INSULATION DURING SHUT DOWN PERIODS, 240V, 50HZ OPERATED SPACE HEATERS OF ADEQUATE CAPACITY TO KEEP THE INTERNAL TEMPERATURE OF THE MOTOR ABOVE DUE POINT.
  • 36. POET CONSULTANTS PVT. LTD. MOTORS • DRAIN PLUGS – DRAIN PLUGS SHALL BE PROVIDED TO DRAIN WATER RESULTING FROM CONDENSATION OR OTHER CAUSES FROM ALL POCKETS IN THE MOTOR CASING. • FLOW SWITCHES – IN CASE OF CACW MOTORS, FLOW SWITCHES TO BE PROVIDED FOR MONITORING COOLING WATER FLOW. • TERMINAL BOX – SEPARATE TERMINAL BOXES SHALL BE PROVIDED FOR STATOR LEADS, SPACE HEATERS, TEMPERATURE DETECTORS. METAL BARRIERS WITHIN THE TERMINAL BOXES SHALL SEGREGATE HV PHASE TERMINALS. • THE INSULATION CLASS OF HV MOTORS SHALL BE CLASS F LIMITED TO CLASS B TEMPERATURE RISE LIMITS
  • 37. POET CONSULTANTS PVT. LTD. MOTORS PROTECTION REQUIREMENTS FOR MOTORS: WHILE DECIDING ON THE TYPE OF PROTECTIONS FOR A TYPICAL MOTOR APPLICATION THE FOLLOWING POINTS CAN BE CONSIDERED AS GUIDELINES: • DECIDE ON THE TYPE OF STARTING METHOD AND CONTROL SCHEME FOR THE MOTOR BASED ON THE APPLICATION. • IF THE CONTROL GEAR IS REMOTELY LOCATED, ON LOAD ISOLATOR AND OR LOCAL STOP PUSH BUTTON STATIONS NEAR THE MOTOR TO BE CONSIDERED AS PER IE RULES. • IF THE MOTOR SERVICE IS ESSENTIAL, THEN, SELF- STARTING FEATURE IS TO BE CONSIDERED FOR THE CONTROL CIRCUIT.
  • 38. POET CONSULTANTS PVT. LTD. MOTORS • PROPER ANNUNCIATION/ ALARM SCHEMES SHALL BE CONSIDERED FOR FAULT TRIPS, ABNORMALITIES, etc., WITH INDICATIONS AT BOTH LOCAL AND REMOTE ENDS AS REQUIRED . • BASIC METERING LIKE AMMETER MAY BE CONSIDERED. • SPACE HEATERS FOR KEEPING THE WINDINGS WARM TO AVOID CONDENSATION MAY BE CONSIDERED FOR MOTORS RATED> 30KW. • BASIC PROTECTIONS TO BE PROVIDED FOR MOTORS SHALL INCLUDE SHORT CIRCUIT AND THERMAL OVERLOAD PROTECTION. • FOR MOTORS RATED > 100KW, LOCKED ROTOR PROTECTION SHALL BE PROVIDED. • SUFFICIENT NUMBER OF AUX. POTENTIAL FREE CONTACTS TO BE CONSIDERED FOR INTERLOCKING PURPOSES.
  • 39. POET CONSULTANTS PVT. LTD. MOTORS IN CASE OF HV MOTORS THE FOLLOWING POINTS NEED TO BE CONSIDERED WHILE DESIGNING THE PROTECTIONS: • AMMETER SHALL BE PROVIDED. • SUFFICIENT NUMBER OF AUX. POTENTIAL FREE CONTACTS TO BE CONSIDERED FOR INTERLOCKING PURPOSES. • SHORT CIRCUIT PROTECTION BY INSTANTANEOUS OVERCURRENT RELAYS IN ALL THREE PHASES. • OVERLOAD PROTECTION BY THERMAL OVERLOAD PROTECTION RELAYS ON TWO PHASES. THE OVERLOAD RELAY SETTING SHALL BE BASED ON THE HOT AND COLD I2T CHARACTERISTICS OF THE MOTOR. • LOCKED ROTOR PROTECTION BY TWO OVERCURRENT INSTANTANEOUS RELAYS (IN R & B PHASES) AND ONE COMMON TIMER.
  • 40. POET CONSULTANTS PVT. LTD. MOTORS • CENTRIFUGAL TYPE SPEED SWITCH OR OTHER APPROVED TYPE OF SPEED SENSOR WITH AN ADDITIONAL TIMER MAY BE USED FOR LOCKED ROTOR PROTECTION WHERE THE STARTING TIME AT LOWEST PERMISSIBLE VOLTAGE IS GREATER THAN THE LOCKED ROTOR WITHSTAND TIME AT HIGHEST PERMISSIBLE VOLTAGE (110%). • FOR MOTORS > 1000KW RATING DIFFERENTIAL PROTECTION BY A HIGH-SPEED TRIPLE POLE RELAY, WHEN A MOTOR IS STAR WOUND. • EARTH FAULT PROTECTION BY SINGLE POLE CURRENT RELAY WHERE THE SYSTEM IS SOLIDLY OR LOW RESISTANCE GROUNDED.
  • 41. POET CONSULTANTS PVT. LTD. MOTORS • EARTH FAULT PROTECTION BY A SENSITIVE EARTH FAULT RELAY CONNECTED TO CORE BALANCE CT, WHERE THE SYSTEM IS GROUNDED THROUGH A HIGH RESISTANCE. • UNDER VOLTAGE PROTECTION FOR PROLONGED UNDER VOLTAGE (LESS THAN 80%) BY TWO NUMBERS BUS UNDER VOLTAGE RELAYS AND A COMMON TIMER • OVERLOAD ALARM BY A SINGLE POLE DEFINITE TIME OVER CURRENT RELAY IN THE Y PHASE. • COMPOSITE MOTOR PROTECTION RELAY SCHEME CAN ALSO BE ADOPTED IF IT FULFILS ALL THE ABOVE PROTECTION REQUIREMENTS • TEMPERATURE MONITORING – RTD DEVICES IN THE STATOR WINDINGS TO DETECT THE HOT SPOTS, SHOULD BE CONNECTED TO TEMPERATURE INDICATOR WITH ALARM CONTACTS.
  • 42. POET CONSULTANTS PVT. LTD. MOTORS • BEARING TEMP. MONITORING – THE INDICATORS PROVIDED ON THE BEARINGS SHALL HAVE CONTACT FOR ALARM PURPOSE. • FOR CACW MOTORS THE FOLLOWING ADDITIONAL PROTECTIONS SHALL BE CONSIDERED – • MOTOR CLOSING CIRCUIT SHALL HAVE PERMISSIVE INTERLOCK FOR NORMAL WATER FLOW • LOW WATER FLOW SHALL GIVE AN ALARM AND AFTER A TIME DELAY SHALL TRIP THE MOTOR. • AIR TEMPERATURE INDICATORS, WHEREVER PROVIDED, SHALL BE CONNECTED FOR ALARM.
  • 43. POET CONSULTANTS PVT. LTD. MOTORS • LUBE OIL PRESSURE MONITOR TO BE CONSIDERED WHERE FORCED OIL LUBRICATION IS PROVIDED. MOTOR CLOSING CIRCUIT SHALL HAVE INTERLOCK FOR NORMAL LUBE OIL PRESSURE. • FACILITY OF AUTOMATICALLY SWITCHING ON THE SPACE HEATER WHEN THE MOTOR IS STOPPED TO PREVENT THE INGRESS OF MOISTURE. • LOCKABLE TYPE STOP PUSH BUTTONS TO BE PROVIDED NEAR THE MOTOR WHICH SHALL BE INCLUDED IN THE CLOSING CIRCUIT. TESTING OF MOTORS: • TESTING IS DIVIDED IN TO ROUTINE AND TYPE TEST.
  • 44. POET CONSULTANTS PVT. LTD. MOTORS ROUTINE TESTS: • MEASUREMENT OF WINDING RESISTANCE • MEASUREMENT OF NO LOAD LOSS AND CURRENT • REDUCED VOLTAGE RUNNING UP IN EITHER DIRECTION OF ROTATION • LOCKED ROTOR TEST FOR SQUIRREL CAGE INDUCTION MOTOR • OPEN CIRCUIT VOLTAGE MEASUREMENT FOR WOUND ROTOR MOTORS • INSULATION MEASUREMENT OF WINDINGS • HIGH VOLTAGE TEST • IR MEASUREMENT OF SPACE HEATERS, RTD, BTD • CONTINUITY OF SPACE HEATERS, RTDS, BTDS
  • 45. POET CONSULTANTS PVT. LTD. MOTORS THE FOLLOWING ARE CLASSIFIED AS TYPE TESTS: • LOAD TEST • VARIABLE VOLTAGE TEST OR CALIBRATED MACHINE TEST FOR SEPARATION OF LOSSES. • TEMPERATURE RISE TEST • MOMENTARY OVER LOAD TEST SPECIAL TESTS: • VIBRATION MEASUREMENT TEST • DISSIPATION FACTOR • POLARISATION INDEX • CAPACITANCE AND LOSS ANGLE MEASUREMENT
  • 46. POET CONSULTANTS PVT. LTD. MOTORS MAINTENANCE OF MOTORS: PHYSICAL CHECKS NEED TO BE DONE FOR- • TIGHTNESS OF FOUNDATION/ FIXING BOLTS • FREE ROTATION OF THE ROTOR IN DE-COUPLED CONDITION • SHAFT ALIGNMENT WITH THAT OF THE DRIVEN UNIT. • ELECTRICAL PARAMETERS TO BE CONSIDERED ARE- • THE TWO DISTINCT EARTH CONNECTING LEADS FROM THE BODY OF THE MOTOR TO EARTH MAT ARE IN GOOD CONDITION. • CHECK THE IR VALUE OF STATOR WINDING WRIT EARTH USING 1KV MEGGER (INDIVIDUAL PHASES ALSO IF AVAILABLE). ALSO CHECK FOR THE CONTINUITY OF THE WINDINGS.
  • 47. POET CONSULTANTS PVT. LTD. MOTORS • CHECK THE IR VALUE OF ROTOR WINDING WITH BRUSHES LIFTED USING 500V MEGGER (FOR SLIPRING MOTOR) • CHECK THE SEC. CIRCUIT EXTERNAL TO ROTOR WINDING FOR SLIPRING MOTOR. • CHECK IR VALUE OF SPACE HEATER WITH RESPECT TO STATOR WINDING AND EARTH USING A 500V MEGGER. • CHECK FOR THE SEATING OF BRUSHES IN THE SLIPRINGS.
  • 48. POET CONSULTANTS PVT. LTD. MOTORS • CHECK FOR THE SEATING OF BRUSHES IN THE SLIPRINGS. • CHECK IR VALUES OF CABLE CORES WITH RESPECT TO EARTH/ ARMOUR/ CORE USING A 1KV MEGGER AFTER DISCONNECTING THE TERMINATION AT BOTH THE ENDS. ALSO CHECK FOR THE CONTINUITY OF THE CABLES. • CHECK FOR OVERLOAD RELAY SETTINGS (SET AT 90% OF NAMEPLATE RATING).
  • 49. POET CONSULTANTS PVT. LTD. MOTORS TOTALLY ENCLOSED FAN COOLED INDUCTION MOTOR
  • 50. POET CONSULTANTS PVT. LTD. MOTORS LARGE INDUCTION MOTOR
  • 51. POET CONSULTANTS PVT. LTD. MOTORS CLOSED AIR CIRCUIT AIR COOLED INDUCTION MOTOR
  • 52. POET CONSULTANTS PVT. LTD. MOTORS HORIZANTAL FAN MOTOR WITH TOP CABLE BOX
  • 53. POET CONSULTANTS PVT. LTD. MOTORS TOTALLY ENCLOSED FAN COOLED MOTOR
  • 54. POET CONSULTANTS PVT. LTD. MOTORS SCREEN PROTECTED SQUIRREL CAGE MOTOR
  • 55. POET CONSULTANTS PVT. LTD. MOTORS FLAMEPROOF SQUIRREL CAGE MOTOR
  • 56. POET CONSULTANTS PVT. LTD. MOTORS VERTICALLY MOUNTED MOTORS