                                                        Slab on Grade Vapor Retarders
                                                                  By Randal J. Reifsnider, AIA, CSI, CCS, LEED AP, SCIP
 ABSTRACT:
 There is a difference between Vapor        VR vs. VB?                            In most cases, only a VR is
 Retarder, Vapor Barrier, and
 Waterproofing and why they are used        Many use the terms vapor retarder     required. However, where a soils
 under a slab on grade. This article
                                            (VR) and vapor barrier (VB)           report indicates there is liquid
 addresses those differences and                                                  subgrade water present or if it is
 focuses on the use of vapor retarders.     interchangeably. However, there is
                                            a difference. A vapor retarder        reasonable to anticipate liquid
 FILING:                                    RETARDS or slows (but does not        subgrade water may be present at
                                            prevent) the transmission of water    some time during the life of the
 UniFormat™
                                            vapor. A vapor barrier BLOCKS the     building, use waterproofing under
 A1030 Slab On Grade
                                            transmission of water vapor.          the slab. A separate VR may be
 MasterFormat™                                                                    required, too, depending on the
                                            VR is a material that has a           selected waterproofing product.
 07 26 00 Vapor Retarders (primary)
                                            permeance of 0.3 perms or less
 03 30 00 Cast-in-Place Concrete
                                            when tested in accordance with        VR's Purpose
 KEYWORDS:                                  ASTM E 96. VB is a material that
                                                                                  VRs are used under a concrete
 Vapor Retarder, Vapor Barrier, Slab on
                                            has a permeance of 0.00 perms.
                                                                                  slab-on-grade to:
 Grade, Waterproofing, Cast-in-Place
                                            VRs are made from a variety of
 Concrete, permeance.                                                                1. Restrict water vapor from
                                            materials including polyethylene
                                                                                        entering a building.
 REFERENCES:                                sheets, asphalt/polyethylene
                                            composite sheets or polymer              2. Minimizes shrinkage
 ACI 302.1R - Guide for Concrete Floor                                                  stresses and cracking.
 and Slab Construction                      modified bitumen sheets.
                                                                                     3. Prevent slab curling.
                                            Polyethylene sheets are often
 ACI 302.2R - Guide for Concrete Slabs                                               4. To keep soil gases, such as
 that Receive Moisture-Sensitive            referred to informally as
                                                                                        radon, from entering a
 Flooring Materials                         "Visqueen." However, "Visqueen" is
                                                                                        building.
                                            a proprietary brand name and
 ASTM E 1745 - Standard Specification       should not be used as a generic       It is particularly important to
 for Water Vapor Retarders Used in
                                            term.                                 restrict moisture entering the
 Contact with Soil or Granular Fill under
 Concrete Slabs                                                                   building through the slab where
                                            Many sheet plastic VR products are
                                                                                  the floor finish will be a moisture-
                                            high density polyethylene (HDPE).
 ASTM E 1643 - Standard Practice for                                              sensitive product such as:
 Selection, Design, Installation, and       These products resist punctures
 Inspection of Water Vapor Retarders        during construction and help             1. Vinyl, linoleum, rubber, and
 Used in Contact with Earth or Granular     ensure the VR remains effective.            other resilient flooring
 Fill Under Concrete Slabs
                                                                                        materials.
                                            VR vs. WP?                               2. Wood.
 National Institute of Building
 Sciences (NIBS), Whole Building            The primary purpose of the VR            3. Carpeting.
 Design Guide, article "Building            under the slab is to prevent water
 Envelope Design Guide - Floor Slabs"                                                4. Sealers, epoxies, and other
 by Mark Postma, PE of Carl Walker, Inc.    vapor migrating from the soil,              impermeable coatings.
 http://www.wbdg.org/design/env_bg_         through the slab, and into the           5. Adhesives used to install
 slab.php                                   building.                                   finished flooring materials.
                                            The primary purpose of                It is also important where there
                                            waterproofing (WP) is to prevent      will be moisture-sensitive
                                            liquid water from entering the        equipment, products, or
                                            building.                             environments.
TECH TIPS
                                                                                               www.conspectusinc.com

Experience, Quality, & Value Beyond Words                                            Vol 10.01.01 ©2010 Conspectus Inc.

                                                                                                               Page 2 of 2



 Water vapor entering a building            ACI 302.2R provides additional        Care should be taken during the
 through a slab-on -grade can               guidance on the materials             placement of reinforcement to
 cause floor tile to dislodge,              properties and locations of VRs       prevent the VR from being
 resilient sheet flooring to bubble,        under concrete slabs that receive     punctured. Reinforcement
 floor coatings to blister, and wood        moisture-sensitive finish flooring.   supports should be bricks or
 to warp.                                   According to ACI302.2R,               should rest on protective pads. VR
                                            specifying a more stringent perm      damaged during placement of
 Standards                                  rating than the 0.3 standard          reinforcement should be
 ASTM E 1745 sets minimum                   maximum has advantages.               immediately repaired.
 product criteria for sheet
 membrane VRs for use under
                                            VR Installation                       Cautions
 slabs-on-grade. It limits the              VRs should be placed directly over    A VR or VB under a slab-on-grade
 maximum water-vapor permeance              a compacted, well-drained             helps the concrete hydration
 to 0.3 perms and establishes three         granular fill (typically, gravel)     process by limiting the surface
 durability classes based on tensile        which has been placed over            area available for evaporation of
 strength and puncture-resistance:          unexcavated or undisturbed earth      water. However, if the evaporation
 Class A (most durable), Class B,           with the longest dimension            rate on top of the slab is too high,
 and Class C (least durable). ASTM          parallel to with direction of slab    the slab could curl and the surface
 E 1745 does not govern material            pour. In addition to providing        can become dry and crusty while
 type nor thickness. Most products          support for the slab, granular fill   the concrete below the surface
 offered as VRs will have perm              provides an area for moisture         remains relatively soft. It is
 ratings significantly less than the        below the slab to accumulate and      important to control the hydration
 standard's maximum.                        be dispersed.                         process to assure the slab's proper
                                                                                  appearance and performance.
 Not all polyethylene sheets have           The National Institute of Building
 been tested according to                   Sciences (NIBS) Whole Building        Measures need to be taken
 ASTM E 1745. When specified, be            Design Guide www.wbdg.org             immediately after concrete
 sure to check submittals for this          recommends using 2 layers of 6        placement to assure the hydration
 requirement before approving.              mils (0.15 mm) polyethylene           process does not occur too
                                            sheets to reduce puncturing and       rapidly.
 ASTM E 1643 sets minimum
                                            provide redundancy at seams. This
 installation criteria for VRs for use                                            Refer to ACI 308R "Guide to
                                            is a different system than the
 under slabs-on-grade and includes                                                Curing Concrete" for
                                            single layer of 10 mils (0.25 mm)
 details and checklists for the field,                                            recommendations of controlling
                                            VR recommended by ACI 302.1.
 and pre-design and design                                                        concrete hydration.
                                            However, NIBS recommendation
 considerations. VR installation
                                            may actually achieve better results
 recommendations below are based                                                  Add Your Comments
                                            since it addresses the same
 on this standard. ASTM E 1643
                                            performance criteria as ACI 302.2R    We invite your comments. Visit our
 also recommends that slabs
                                            and includes built in redundancy.     blog and add your comments to this
 should be tested for moisture
                                                                                  article's announcement.
 emissions prior to placement of            VRs should lap over footings and
                                                                                  www.conspectusinc.com/blog
 finish flooring.                           foundation walls. Seams should
                                            overlap a minimum of 6 inches
 ACI 302.1R provides guidance                                                     The information contained in this
                                            (150 mm) per ASTM E 1643.
 for the materials and installation                                               document is offered for educational
                                            Seams, laps, and penetrations
 of concrete slabs in general. It                                                 purposes, only, and not as technical
                                            should be sealed with
 requires VRs to comply with                                                      advice suitable for any particular
                                            manufacturer’s recommended            project or specific condition. Technical
 ASTM E 1745 and to have a
                                            adhesive, pressure-sensitive tape,    consulting is unique to the facts of a
 minimum thickness of 10 mils
                                            or both. Attention to sealing         particular condition, and Conspectus
 (0.25 mm). This is thicker than the
                                            seams and penetrations is critical    recommends that a specialist be
 6 mils (0.15 mm) traditionally
                                            to preventing soil gases, such as     consulted to determine solutions for
 specified for polyethylene VRs.
                                            radon, from entering the building.    each specific condition.

TECH TIPS Slab on Grade Vapor Retarders

  • 1.
    TECH TIPS www.conspectusinc.com Vol 10.01.01 ©2010 Conspectus Inc. Experience, Quality, & Value Beyond Words Page 1 of 2 Providing: Specifications, Quality Assurance, The Where, When, and Why of Inspections & Investigations for your Construction Projects Slab on Grade Vapor Retarders By Randal J. Reifsnider, AIA, CSI, CCS, LEED AP, SCIP ABSTRACT: There is a difference between Vapor VR vs. VB? In most cases, only a VR is Retarder, Vapor Barrier, and Waterproofing and why they are used Many use the terms vapor retarder required. However, where a soils under a slab on grade. This article (VR) and vapor barrier (VB) report indicates there is liquid addresses those differences and subgrade water present or if it is focuses on the use of vapor retarders. interchangeably. However, there is a difference. A vapor retarder reasonable to anticipate liquid FILING: RETARDS or slows (but does not subgrade water may be present at prevent) the transmission of water some time during the life of the UniFormat™ vapor. A vapor barrier BLOCKS the building, use waterproofing under A1030 Slab On Grade transmission of water vapor. the slab. A separate VR may be MasterFormat™ required, too, depending on the VR is a material that has a selected waterproofing product. 07 26 00 Vapor Retarders (primary) permeance of 0.3 perms or less 03 30 00 Cast-in-Place Concrete when tested in accordance with VR's Purpose KEYWORDS: ASTM E 96. VB is a material that VRs are used under a concrete Vapor Retarder, Vapor Barrier, Slab on has a permeance of 0.00 perms. slab-on-grade to: Grade, Waterproofing, Cast-in-Place VRs are made from a variety of Concrete, permeance. 1. Restrict water vapor from materials including polyethylene entering a building. REFERENCES: sheets, asphalt/polyethylene composite sheets or polymer 2. Minimizes shrinkage ACI 302.1R - Guide for Concrete Floor stresses and cracking. and Slab Construction modified bitumen sheets. 3. Prevent slab curling. Polyethylene sheets are often ACI 302.2R - Guide for Concrete Slabs 4. To keep soil gases, such as that Receive Moisture-Sensitive referred to informally as radon, from entering a Flooring Materials "Visqueen." However, "Visqueen" is building. a proprietary brand name and ASTM E 1745 - Standard Specification should not be used as a generic It is particularly important to for Water Vapor Retarders Used in term. restrict moisture entering the Contact with Soil or Granular Fill under Concrete Slabs building through the slab where Many sheet plastic VR products are the floor finish will be a moisture- high density polyethylene (HDPE). ASTM E 1643 - Standard Practice for sensitive product such as: Selection, Design, Installation, and These products resist punctures Inspection of Water Vapor Retarders during construction and help 1. Vinyl, linoleum, rubber, and Used in Contact with Earth or Granular ensure the VR remains effective. other resilient flooring Fill Under Concrete Slabs materials. VR vs. WP? 2. Wood. National Institute of Building Sciences (NIBS), Whole Building The primary purpose of the VR 3. Carpeting. Design Guide, article "Building under the slab is to prevent water Envelope Design Guide - Floor Slabs" 4. Sealers, epoxies, and other by Mark Postma, PE of Carl Walker, Inc. vapor migrating from the soil, impermeable coatings. http://www.wbdg.org/design/env_bg_ through the slab, and into the 5. Adhesives used to install slab.php building. finished flooring materials. The primary purpose of It is also important where there waterproofing (WP) is to prevent will be moisture-sensitive liquid water from entering the equipment, products, or building. environments.
  • 2.
    TECH TIPS www.conspectusinc.com Experience, Quality, & Value Beyond Words Vol 10.01.01 ©2010 Conspectus Inc. Page 2 of 2 Water vapor entering a building ACI 302.2R provides additional Care should be taken during the through a slab-on -grade can guidance on the materials placement of reinforcement to cause floor tile to dislodge, properties and locations of VRs prevent the VR from being resilient sheet flooring to bubble, under concrete slabs that receive punctured. Reinforcement floor coatings to blister, and wood moisture-sensitive finish flooring. supports should be bricks or to warp. According to ACI302.2R, should rest on protective pads. VR specifying a more stringent perm damaged during placement of Standards rating than the 0.3 standard reinforcement should be ASTM E 1745 sets minimum maximum has advantages. immediately repaired. product criteria for sheet membrane VRs for use under VR Installation Cautions slabs-on-grade. It limits the VRs should be placed directly over A VR or VB under a slab-on-grade maximum water-vapor permeance a compacted, well-drained helps the concrete hydration to 0.3 perms and establishes three granular fill (typically, gravel) process by limiting the surface durability classes based on tensile which has been placed over area available for evaporation of strength and puncture-resistance: unexcavated or undisturbed earth water. However, if the evaporation Class A (most durable), Class B, with the longest dimension rate on top of the slab is too high, and Class C (least durable). ASTM parallel to with direction of slab the slab could curl and the surface E 1745 does not govern material pour. In addition to providing can become dry and crusty while type nor thickness. Most products support for the slab, granular fill the concrete below the surface offered as VRs will have perm provides an area for moisture remains relatively soft. It is ratings significantly less than the below the slab to accumulate and important to control the hydration standard's maximum. be dispersed. process to assure the slab's proper appearance and performance. Not all polyethylene sheets have The National Institute of Building been tested according to Sciences (NIBS) Whole Building Measures need to be taken ASTM E 1745. When specified, be Design Guide www.wbdg.org immediately after concrete sure to check submittals for this recommends using 2 layers of 6 placement to assure the hydration requirement before approving. mils (0.15 mm) polyethylene process does not occur too sheets to reduce puncturing and rapidly. ASTM E 1643 sets minimum provide redundancy at seams. This installation criteria for VRs for use Refer to ACI 308R "Guide to is a different system than the under slabs-on-grade and includes Curing Concrete" for single layer of 10 mils (0.25 mm) details and checklists for the field, recommendations of controlling VR recommended by ACI 302.1. and pre-design and design concrete hydration. However, NIBS recommendation considerations. VR installation may actually achieve better results recommendations below are based Add Your Comments since it addresses the same on this standard. ASTM E 1643 performance criteria as ACI 302.2R We invite your comments. Visit our also recommends that slabs and includes built in redundancy. blog and add your comments to this should be tested for moisture article's announcement. emissions prior to placement of VRs should lap over footings and www.conspectusinc.com/blog finish flooring. foundation walls. Seams should overlap a minimum of 6 inches ACI 302.1R provides guidance The information contained in this (150 mm) per ASTM E 1643. for the materials and installation document is offered for educational Seams, laps, and penetrations of concrete slabs in general. It purposes, only, and not as technical should be sealed with requires VRs to comply with advice suitable for any particular manufacturer’s recommended project or specific condition. Technical ASTM E 1745 and to have a adhesive, pressure-sensitive tape, consulting is unique to the facts of a minimum thickness of 10 mils or both. Attention to sealing particular condition, and Conspectus (0.25 mm). This is thicker than the seams and penetrations is critical recommends that a specialist be 6 mils (0.15 mm) traditionally to preventing soil gases, such as consulted to determine solutions for specified for polyethylene VRs. radon, from entering the building. each specific condition.