Solenoid Valve Troubleshooting Checklist
Solenoid valve fails to open Probable Causes of Failure
Failed power supply
Check if valve is normally closed or normally open
Use magnetic detector or touch with insulated metal screwdriver to detect
any magnetic field
Lift coil slightly to check if magnetic field is present but do not move when coil
energized overheat quickly
Check contacts
Check wire connections and DIN connector
Check fuses
Wrong Voltage
Check coil marked voltage is correct for the voltage being suppled.
Check voltage tolerances normally +/- 10%
Some coils work on the principle of creating an inrush condition to open the
valve, check your power supply is rated for the coil current requirements.
Most valves will have cable plugs rated to IP65 DIN43560 electrical
connector, make sure cable gland and cable diameter are matched, plug
connecting screw correctly tightened and allow cable to drop under cable
gland to help prevent ingress of water droplet
Coil Burnt Out Check coil burnt section
Pressure Too High
Check coil power rating, higher power version may be required. Reduce inlet
pressure in line with valve specification as shown in solenoid-valve catalogue.
Pressure Too Low
Check inlet/ outlet pressure difference (Differential) is in line with design
conditions of the valve. If too low valve will need replacing with 0 rated
version. Remember that the downstream side will rise to a higher tank or
system, so should also be subtracted from the supply side pressure. Other
system demands may also reduce the overall supply pressure and further
reduce differentials.
Damaged Armature tube Replace armature tube. See spare parts list in xpneumatic.com
Dirt ingress under diaphragm or seals
Clean diaphragm or replace if damaged. Remember to take a photo of sea
position for installation correctly. maybe fit Y type strainer upstream to filter
out suspended particles.
Corrosion
Replace damaged components and check media compatibility with valve. If
the armature is pitted due to Cleaning or dosing fluid? Some acids will attack
the 430F stainless armature, which is corrosion resistant but not guaranteed
to withstand all fluids.
Missing components after
maintenance
Replace parts according to spares listing as per xpneumatic.com catalogue
Solenoid valve opens slightly Probable Cause
Low pressure
Check inlet/ outlet pressure difference (Differential) is in line with valve
specification. If too low valve will need replacing with 0 rated version.
Remember that the downstream side will rise to a higher tank or system, so
should also be subtracted from the supply side pressure. Other system
demands may also reduce the overall supply pressure and further reduce
differentials.
Damaged or bent armature tube Replace tube. See spare parts available in solenoid-valve catalogue
Dirt ingress under diaphragm
Clean diaphragm or replace if damaged. See spare parts list in solenoid-
valve catalogue, maybe fit Y type strainer upstream. Remember to take a
photo of sea position for installation correctly.
Corrosion
Replace damaged components and check media compatibility with valve. Do
not use EPDM seals on Oils or Fats as the seals will swell and restrict flow.
Call technical help line or soak seals overnight to see if it swells up.
Missing components after
maintenance
Replace parts according to spares listing as per solenoid-valve catalogue.
Solenoid valve fails to close or partly
closes
Probable Cause
Residual power to coil
Lift coil slightly to check if magnetic field is present. Do not completely
remove coil if energised as IT WILL BURN OUT.
Check wiring and diagram
Check lead connections.
Dirt ingress in pilot hole under coil
armature
Clean orifice with pin or compressed air.
Manual over ride Check position of manual over ride and adjust if required.
Pressure pulse upstream.
check inlet and outlet pressure differential and flow and correct for the
solenoid valve being used. Check other valve downstream in the system are
not generating excess back pressure
Pressure difference in/out too high
install pressure reducing valve or install correct solenoid valve to meet the
system pressure
Outlet pressure occasionally higher
than inlet pressure
Install check valve downstream of solenoid valve to prevent back flow
Check pressure control valves in system are correctly set up.
Install bi-directional solenoid valve, coaxial valve or angle seat piston valve
that are designed to control flow in both directions.
Damaged or bent armature tube Replace tube. See spare parts available in solenoid-valve catalogue
Damaged diaphram or valve seat
Refit diaphragm correctly or replace with new part. See valve spares in
solenoid-valve catalogue.
Dirt ingress in armature tube
Clean valve armature or replace. If hard water scale build up install water
softener or dry armature valve from solenoid-valve catalogue.
Corrosion in pilot orifice Replace damaged components
Valve installed wrong way around
Check flow direction is in line with flow direction arrow or in/out markings on
ports.
Missing components after
maintenance
Replace parts according to spares listing manufacture offers.
Valve Noise Appears Incorrect Probable Cause.
Buzz
50 or 60Hz AC buzz. Install a DC (Direct current) solenoid valve coil and
supply a DC voltage. Engineers can install a DC coil with a bridge rectified
DIN43650 electrical connector that will convert the incoming AC voltage to
DC. WE stock DIN2R rectified DIN electrical connectors.
Water hammer when valve opens
Caused by high liquid velocity and high pressure through small pipe bore.
Install a closed vertical T piece pipe in before the valve to trap an air pocket
to dampen noise.
Reduce inlet pressure.
Increase pipe size to reduce velocity.
Water hammer when valve closes
Caused by high liquid velocity and high pressure through small pipe bore.
Ask supplier to reduce closing time of valve. This can be done carefully by
increasing slightly (10-20%) the size of the pilot pressure equalising hole in
the diaphragm. Too much and valve will not open.
Reduce inlet pressure
Increase pipe size to reduce velocity.
Difference in inlet/ outlet pressure too
high or pulsating pressure line
Check valve specification in solenoid-valve catalogue. Check pressure and
flow.
Check solenoid-valve catalogue for more suitable valve for application.
Check other items in installation.
Coil Burnt / Melted or Cold with Power
On
Probable Cause
Wrong Voltage
Check coil marked voltage is correct with power supply.
Change coil for correct one if required. See coils section in solenoid-valves
catalogue.
Check wiring and wiring diagram
Check voltage tolerance, normally +/- 10% consult solenoid-valve catalogue.
Coil Short Circuit
Check remaining installation for short circuit
Check lead connections at coil and DIN connector
Check for moisture in coil, replace as required. Check IP rating according to
technical data in solenoid-valve catalogue
Coil Armature Slow
Replace damaged armature, see spares section in solenoid-valve catalogue.
Check media compatibility with valve.
Bent armature tube, replace accordingly.
Dirt in armature tube, clean and fit Y type strainer.
Media Temperature Too High
Check media temperature against valve technical data in solenoid-valve
catalogue.
Move valve to cooler area or increase ventilation around valve & coil.
Check you have correct function normally closed or normally open

More Related Content

What's hot

Quality aspects in Cross Country Pipeline construction
Quality aspects in Cross Country Pipeline constructionQuality aspects in Cross Country Pipeline construction
Quality aspects in Cross Country Pipeline constructionSuresh Zanwar
 
Precommisioning and commissioning updated
Precommisioning and commissioning updatedPrecommisioning and commissioning updated
Precommisioning and commissioning updatedPersonal Secret
 
Calculation Of Pump Head
Calculation Of Pump HeadCalculation Of Pump Head
Calculation Of Pump HeadHashim Khan
 
Hot Tapping Requirement
Hot Tapping RequirementHot Tapping Requirement
Hot Tapping Requirementwael el ariny
 
Flange management presentation
Flange management presentationFlange management presentation
Flange management presentationMohamed Gaafar
 
ASPE CEU Pipe Hangers and Supports
ASPE CEU Pipe Hangers and SupportsASPE CEU Pipe Hangers and Supports
ASPE CEU Pipe Hangers and SupportsJim LeStage
 
Pr 1159 - commissioning and start-up procedure
Pr 1159 - commissioning and start-up procedurePr 1159 - commissioning and start-up procedure
Pr 1159 - commissioning and start-up procedureRagul Selvam
 
what is process piping
what is process pipingwhat is process piping
what is process pipingVarun Patel
 
Mechanical Seals Piping Plans Api 628
Mechanical Seals Piping Plans   Api 628Mechanical Seals Piping Plans   Api 628
Mechanical Seals Piping Plans Api 628IONEL DUTU
 

What's hot (20)

Quality aspects in Cross Country Pipeline construction
Quality aspects in Cross Country Pipeline constructionQuality aspects in Cross Country Pipeline construction
Quality aspects in Cross Country Pipeline construction
 
Precommisioning and commissioning updated
Precommisioning and commissioning updatedPrecommisioning and commissioning updated
Precommisioning and commissioning updated
 
Orifice plate
Orifice plateOrifice plate
Orifice plate
 
Wire rope slings
Wire rope slingsWire rope slings
Wire rope slings
 
Wellheads and Flow Lines.pdf
Wellheads and Flow Lines.pdfWellheads and Flow Lines.pdf
Wellheads and Flow Lines.pdf
 
Wire rope
Wire ropeWire rope
Wire rope
 
Calculation Of Pump Head
Calculation Of Pump HeadCalculation Of Pump Head
Calculation Of Pump Head
 
Hot Tapping Requirement
Hot Tapping RequirementHot Tapping Requirement
Hot Tapping Requirement
 
Flange management presentation
Flange management presentationFlange management presentation
Flange management presentation
 
Control valve
Control valveControl valve
Control valve
 
Control valve
Control valveControl valve
Control valve
 
ASPE CEU Pipe Hangers and Supports
ASPE CEU Pipe Hangers and SupportsASPE CEU Pipe Hangers and Supports
ASPE CEU Pipe Hangers and Supports
 
Piping Introduction
Piping IntroductionPiping Introduction
Piping Introduction
 
Pr 1159 - commissioning and start-up procedure
Pr 1159 - commissioning and start-up procedurePr 1159 - commissioning and start-up procedure
Pr 1159 - commissioning and start-up procedure
 
Control valve ppt
Control valve pptControl valve ppt
Control valve ppt
 
Piping presentation part ii 2
Piping presentation part ii 2Piping presentation part ii 2
Piping presentation part ii 2
 
what is process piping
what is process pipingwhat is process piping
what is process piping
 
A Presentation on Field Instrumentation.
A Presentation on Field Instrumentation.A Presentation on Field Instrumentation.
A Presentation on Field Instrumentation.
 
Pipeline hydraulic calculation
Pipeline hydraulic calculationPipeline hydraulic calculation
Pipeline hydraulic calculation
 
Mechanical Seals Piping Plans Api 628
Mechanical Seals Piping Plans   Api 628Mechanical Seals Piping Plans   Api 628
Mechanical Seals Piping Plans Api 628
 

Similar to Solenoid valve troubleshooting checklist

Hydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingHydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingCMA/Flodyne/Hydradyne
 
1 hydraulic troubleshooting
1 hydraulic troubleshooting1 hydraulic troubleshooting
1 hydraulic troubleshootingDr.R. SELVAM
 
Service_C-CC-CW-Valve.pdf
Service_C-CC-CW-Valve.pdfService_C-CC-CW-Valve.pdf
Service_C-CC-CW-Valve.pdfrheri1
 
Control Valves .pdf
Control Valves .pdfControl Valves .pdf
Control Valves .pdfmarcos849547
 
Pneumatics
PneumaticsPneumatics
Pneumaticsleotvrde
 
Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...
Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...
Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...miscott57
 
Instalação em terminais _ Milton Roy
Instalação em terminais _ Milton RoyInstalação em terminais _ Milton Roy
Instalação em terminais _ Milton RoyVibropac
 
The Humble Check Valve
The Humble Check ValveThe Humble Check Valve
The Humble Check Valveblenrayaust
 
ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101 ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101 ROTEX Controls USA
 
Hydraulic Ram Made from Standard Plumbing Parts - University of Georgia
Hydraulic Ram Made from Standard Plumbing Parts - University of GeorgiaHydraulic Ram Made from Standard Plumbing Parts - University of Georgia
Hydraulic Ram Made from Standard Plumbing Parts - University of GeorgiaFatin62c
 
A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...
A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...
A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...Das Services Inc
 
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14Water Works
 

Similar to Solenoid valve troubleshooting checklist (20)

Hydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and TroubleshootingHydraulic Maintenance and Troubleshooting
Hydraulic Maintenance and Troubleshooting
 
1 hydraulic troubleshooting
1 hydraulic troubleshooting1 hydraulic troubleshooting
1 hydraulic troubleshooting
 
089414 2
089414 2089414 2
089414 2
 
Industrial valves
Industrial valvesIndustrial valves
Industrial valves
 
Hydraulic Ram Made from Standard Plumbing Parts
Hydraulic Ram Made from Standard Plumbing PartsHydraulic Ram Made from Standard Plumbing Parts
Hydraulic Ram Made from Standard Plumbing Parts
 
Service_C-CC-CW-Valve.pdf
Service_C-CC-CW-Valve.pdfService_C-CC-CW-Valve.pdf
Service_C-CC-CW-Valve.pdf
 
Final Control Element
Final Control ElementFinal Control Element
Final Control Element
 
VALVE AND TESTING.pdf
VALVE AND TESTING.pdfVALVE AND TESTING.pdf
VALVE AND TESTING.pdf
 
Control Valve.pdf
Control Valve.pdfControl Valve.pdf
Control Valve.pdf
 
Control Valves .pdf
Control Valves .pdfControl Valves .pdf
Control Valves .pdf
 
Pneumatics
PneumaticsPneumatics
Pneumatics
 
Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...
Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...
Rain Soft Gold Series Water Treatment System Installation & Service Manual (w...
 
Instalação em terminais _ Milton Roy
Instalação em terminais _ Milton RoyInstalação em terminais _ Milton Roy
Instalação em terminais _ Milton Roy
 
The Humble Check Valve
The Humble Check ValveThe Humble Check Valve
The Humble Check Valve
 
ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101 ROTEX Controls USA: Valve Automation 101
ROTEX Controls USA: Valve Automation 101
 
HCK5D
HCK5DHCK5D
HCK5D
 
Hydraulic Ram Made from Standard Plumbing Parts - University of Georgia
Hydraulic Ram Made from Standard Plumbing Parts - University of GeorgiaHydraulic Ram Made from Standard Plumbing Parts - University of Georgia
Hydraulic Ram Made from Standard Plumbing Parts - University of Georgia
 
A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...
A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...
A List of Steps to Shortlist Solenoid Valve based on Your Desired Technical S...
 
Valves and Testing .pdf
Valves and Testing .pdfValves and Testing .pdf
Valves and Testing .pdf
 
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
Colorado Water Purification US Water Fusion Backwashing Filter Manual 1110 8 14
 

More from XHnotion Pneumatic

Xhnotion directional control valve 2017
Xhnotion directional control valve 2017Xhnotion directional control valve 2017
Xhnotion directional control valve 2017XHnotion Pneumatic
 
Xhnotion catalogue modular tubes
Xhnotion catalogue   modular tubesXhnotion catalogue   modular tubes
Xhnotion catalogue modular tubesXHnotion Pneumatic
 
Xhnotion cartridge check valve
Xhnotion cartridge check valveXhnotion cartridge check valve
Xhnotion cartridge check valveXHnotion Pneumatic
 
pneumatic fittings catalogue 2017-2
pneumatic fittings catalogue   2017-2pneumatic fittings catalogue   2017-2
pneumatic fittings catalogue 2017-2XHnotion Pneumatic
 
Help you choose pneumatic air fittings from china – untapped tips
Help you choose pneumatic air fittings from china – untapped tipsHelp you choose pneumatic air fittings from china – untapped tips
Help you choose pneumatic air fittings from china – untapped tipsXHnotion Pneumatic
 
Tuv ROHS certificate --plastic pneumatic push in fittings
Tuv ROHS certificate --plastic pneumatic  push in fittingsTuv ROHS certificate --plastic pneumatic  push in fittings
Tuv ROHS certificate --plastic pneumatic push in fittingsXHnotion Pneumatic
 
How to choose correct pneumatic air fitting
How to choose correct pneumatic air fittingHow to choose correct pneumatic air fitting
How to choose correct pneumatic air fittingXHnotion Pneumatic
 
Xhnotion ss316 l push in fittings catalogue 2016
Xhnotion ss316 l push in fittings catalogue 2016Xhnotion ss316 l push in fittings catalogue 2016
Xhnotion ss316 l push in fittings catalogue 2016XHnotion Pneumatic
 
Xhnotion ss316 push in fittings catalogue 2016
Xhnotion ss316 push in fittings catalogue 2016Xhnotion ss316 push in fittings catalogue 2016
Xhnotion ss316 push in fittings catalogue 2016XHnotion Pneumatic
 

More from XHnotion Pneumatic (17)

XHnotion Frl catalogue 2017
XHnotion Frl catalogue 2017XHnotion Frl catalogue 2017
XHnotion Frl catalogue 2017
 
Xhnotion directional control valve 2017
Xhnotion directional control valve 2017Xhnotion directional control valve 2017
Xhnotion directional control valve 2017
 
Xhnotion catalogue modular tubes
Xhnotion catalogue   modular tubesXhnotion catalogue   modular tubes
Xhnotion catalogue modular tubes
 
Xhnotion air cylinder 2016
Xhnotion air cylinder 2016Xhnotion air cylinder 2016
Xhnotion air cylinder 2016
 
Xhnotion solenoid valve 2016
Xhnotion solenoid valve 2016Xhnotion solenoid valve 2016
Xhnotion solenoid valve 2016
 
Xhnotion cartridge check valve
Xhnotion cartridge check valveXhnotion cartridge check valve
Xhnotion cartridge check valve
 
pneumatic fittings catalogue 2017-2
pneumatic fittings catalogue   2017-2pneumatic fittings catalogue   2017-2
pneumatic fittings catalogue 2017-2
 
water latching solenoid valve
water latching solenoid valvewater latching solenoid valve
water latching solenoid valve
 
water latching solenoid valve
water latching solenoid valvewater latching solenoid valve
water latching solenoid valve
 
Help you choose pneumatic air fittings from china – untapped tips
Help you choose pneumatic air fittings from china – untapped tipsHelp you choose pneumatic air fittings from china – untapped tips
Help you choose pneumatic air fittings from china – untapped tips
 
Tuv ROHS certificate --plastic pneumatic push in fittings
Tuv ROHS certificate --plastic pneumatic  push in fittingsTuv ROHS certificate --plastic pneumatic  push in fittings
Tuv ROHS certificate --plastic pneumatic push in fittings
 
Din74324 polyamide tubing
Din74324  polyamide tubingDin74324  polyamide tubing
Din74324 polyamide tubing
 
How to choose solenoid valve
How to choose solenoid valveHow to choose solenoid valve
How to choose solenoid valve
 
How to choose air tubes
How to choose air tubesHow to choose air tubes
How to choose air tubes
 
How to choose correct pneumatic air fitting
How to choose correct pneumatic air fittingHow to choose correct pneumatic air fitting
How to choose correct pneumatic air fitting
 
Xhnotion ss316 l push in fittings catalogue 2016
Xhnotion ss316 l push in fittings catalogue 2016Xhnotion ss316 l push in fittings catalogue 2016
Xhnotion ss316 l push in fittings catalogue 2016
 
Xhnotion ss316 push in fittings catalogue 2016
Xhnotion ss316 push in fittings catalogue 2016Xhnotion ss316 push in fittings catalogue 2016
Xhnotion ss316 push in fittings catalogue 2016
 

Recently uploaded

FULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | DelhiFULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | DelhiMalviyaNagarCallGirl
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...lizamodels9
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...lizamodels9
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.Aaiza Hassan
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024christinemoorman
 
A.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry BelcherA.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry BelcherPerry Belcher
 
Call Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any TimeCall Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any Timedelhimodelshub1
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
rishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfrishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfmuskan1121w
 
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfCatalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfOrient Homes
 
2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis UsageNeil Kimberley
 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth MarketingShawn Pang
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfpollardmorgan
 
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / NcrCall Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncrdollysharma2066
 
Investment analysis and portfolio management
Investment analysis and portfolio managementInvestment analysis and portfolio management
Investment analysis and portfolio managementJunaidKhan750825
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation SlidesKeppelCorporation
 

Recently uploaded (20)

FULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | DelhiFULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
 
Best Practices for Implementing an External Recruiting Partnership
Best Practices for Implementing an External Recruiting PartnershipBest Practices for Implementing an External Recruiting Partnership
Best Practices for Implementing an External Recruiting Partnership
 
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
Call Girls In Connaught Place Delhi ❤️88604**77959_Russian 100% Genuine Escor...
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.
 
The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024The CMO Survey - Highlights and Insights Report - Spring 2024
The CMO Survey - Highlights and Insights Report - Spring 2024
 
A.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry BelcherA.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry Belcher
 
KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)KestrelPro Flyer Japan IT Week 2024 (English)
KestrelPro Flyer Japan IT Week 2024 (English)
 
Call Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any TimeCall Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any Time
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
rishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfrishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdf
 
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfCatalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
 
2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage2024 Numerator Consumer Study of Cannabis Usage
2024 Numerator Consumer Study of Cannabis Usage
 
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
Tech Startup Growth Hacking 101  - Basics on Growth MarketingTech Startup Growth Hacking 101  - Basics on Growth Marketing
Tech Startup Growth Hacking 101 - Basics on Growth Marketing
 
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdfIntro to BCG's Carbon Emissions Benchmark_vF.pdf
Intro to BCG's Carbon Emissions Benchmark_vF.pdf
 
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / NcrCall Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
 
Investment analysis and portfolio management
Investment analysis and portfolio managementInvestment analysis and portfolio management
Investment analysis and portfolio management
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCREnjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
 

Solenoid valve troubleshooting checklist

  • 1. Solenoid Valve Troubleshooting Checklist Solenoid valve fails to open Probable Causes of Failure Failed power supply Check if valve is normally closed or normally open Use magnetic detector or touch with insulated metal screwdriver to detect any magnetic field Lift coil slightly to check if magnetic field is present but do not move when coil energized overheat quickly Check contacts Check wire connections and DIN connector Check fuses Wrong Voltage Check coil marked voltage is correct for the voltage being suppled. Check voltage tolerances normally +/- 10% Some coils work on the principle of creating an inrush condition to open the valve, check your power supply is rated for the coil current requirements. Most valves will have cable plugs rated to IP65 DIN43560 electrical connector, make sure cable gland and cable diameter are matched, plug connecting screw correctly tightened and allow cable to drop under cable gland to help prevent ingress of water droplet Coil Burnt Out Check coil burnt section Pressure Too High Check coil power rating, higher power version may be required. Reduce inlet pressure in line with valve specification as shown in solenoid-valve catalogue. Pressure Too Low Check inlet/ outlet pressure difference (Differential) is in line with design conditions of the valve. If too low valve will need replacing with 0 rated version. Remember that the downstream side will rise to a higher tank or system, so should also be subtracted from the supply side pressure. Other system demands may also reduce the overall supply pressure and further reduce differentials. Damaged Armature tube Replace armature tube. See spare parts list in xpneumatic.com Dirt ingress under diaphragm or seals Clean diaphragm or replace if damaged. Remember to take a photo of sea position for installation correctly. maybe fit Y type strainer upstream to filter out suspended particles. Corrosion Replace damaged components and check media compatibility with valve. If the armature is pitted due to Cleaning or dosing fluid? Some acids will attack the 430F stainless armature, which is corrosion resistant but not guaranteed to withstand all fluids. Missing components after maintenance Replace parts according to spares listing as per xpneumatic.com catalogue
  • 2. Solenoid valve opens slightly Probable Cause Low pressure Check inlet/ outlet pressure difference (Differential) is in line with valve specification. If too low valve will need replacing with 0 rated version. Remember that the downstream side will rise to a higher tank or system, so should also be subtracted from the supply side pressure. Other system demands may also reduce the overall supply pressure and further reduce differentials. Damaged or bent armature tube Replace tube. See spare parts available in solenoid-valve catalogue Dirt ingress under diaphragm Clean diaphragm or replace if damaged. See spare parts list in solenoid- valve catalogue, maybe fit Y type strainer upstream. Remember to take a photo of sea position for installation correctly. Corrosion Replace damaged components and check media compatibility with valve. Do not use EPDM seals on Oils or Fats as the seals will swell and restrict flow. Call technical help line or soak seals overnight to see if it swells up. Missing components after maintenance Replace parts according to spares listing as per solenoid-valve catalogue. Solenoid valve fails to close or partly closes Probable Cause Residual power to coil Lift coil slightly to check if magnetic field is present. Do not completely remove coil if energised as IT WILL BURN OUT. Check wiring and diagram Check lead connections. Dirt ingress in pilot hole under coil armature Clean orifice with pin or compressed air. Manual over ride Check position of manual over ride and adjust if required. Pressure pulse upstream. check inlet and outlet pressure differential and flow and correct for the solenoid valve being used. Check other valve downstream in the system are not generating excess back pressure Pressure difference in/out too high install pressure reducing valve or install correct solenoid valve to meet the system pressure Outlet pressure occasionally higher than inlet pressure Install check valve downstream of solenoid valve to prevent back flow Check pressure control valves in system are correctly set up. Install bi-directional solenoid valve, coaxial valve or angle seat piston valve that are designed to control flow in both directions. Damaged or bent armature tube Replace tube. See spare parts available in solenoid-valve catalogue Damaged diaphram or valve seat Refit diaphragm correctly or replace with new part. See valve spares in solenoid-valve catalogue.
  • 3. Dirt ingress in armature tube Clean valve armature or replace. If hard water scale build up install water softener or dry armature valve from solenoid-valve catalogue. Corrosion in pilot orifice Replace damaged components Valve installed wrong way around Check flow direction is in line with flow direction arrow or in/out markings on ports. Missing components after maintenance Replace parts according to spares listing manufacture offers. Valve Noise Appears Incorrect Probable Cause. Buzz 50 or 60Hz AC buzz. Install a DC (Direct current) solenoid valve coil and supply a DC voltage. Engineers can install a DC coil with a bridge rectified DIN43650 electrical connector that will convert the incoming AC voltage to DC. WE stock DIN2R rectified DIN electrical connectors. Water hammer when valve opens Caused by high liquid velocity and high pressure through small pipe bore. Install a closed vertical T piece pipe in before the valve to trap an air pocket to dampen noise. Reduce inlet pressure. Increase pipe size to reduce velocity. Water hammer when valve closes Caused by high liquid velocity and high pressure through small pipe bore. Ask supplier to reduce closing time of valve. This can be done carefully by increasing slightly (10-20%) the size of the pilot pressure equalising hole in the diaphragm. Too much and valve will not open. Reduce inlet pressure Increase pipe size to reduce velocity. Difference in inlet/ outlet pressure too high or pulsating pressure line Check valve specification in solenoid-valve catalogue. Check pressure and flow. Check solenoid-valve catalogue for more suitable valve for application. Check other items in installation. Coil Burnt / Melted or Cold with Power On Probable Cause Wrong Voltage Check coil marked voltage is correct with power supply. Change coil for correct one if required. See coils section in solenoid-valves catalogue. Check wiring and wiring diagram Check voltage tolerance, normally +/- 10% consult solenoid-valve catalogue. Coil Short Circuit Check remaining installation for short circuit Check lead connections at coil and DIN connector Check for moisture in coil, replace as required. Check IP rating according to technical data in solenoid-valve catalogue
  • 4. Coil Armature Slow Replace damaged armature, see spares section in solenoid-valve catalogue. Check media compatibility with valve. Bent armature tube, replace accordingly. Dirt in armature tube, clean and fit Y type strainer. Media Temperature Too High Check media temperature against valve technical data in solenoid-valve catalogue. Move valve to cooler area or increase ventilation around valve & coil. Check you have correct function normally closed or normally open