FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED
FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY
CHEMICAL SYSTEMS
FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF
PREP STATIONS UTILIZING ONE OR MORE VINYL CURTAIN WALLS
I) SUMMARY:
The proliferation of automobile Limited Finishing Workstations using vinyl curtains (as
opposed to fixed walls) requires us to re-evaluate dry chemical fire suppression coverage.
There appears to be a lack of clear guidance or agreement in applicable standards, such as UL
1254 “Pre-Engineered Dry Chemical Extinguishing System Units”, or NFPA 17 “Standard
for Dry Chemical Extinguishing Systems”. First we will examine the requirements for
automatic fire protection systems in NFPA 33 – Standard for Spray Application Using
Flammable or Combustible Materials – 2003 Edition.
NFPA 33 2003 EDITION REQUIREMENTS
“3.3.1.3* Spray Area. Any area in which dangerous quantities of flammable or combustible
vapors, mists, residues, dusts or deposits are present due to the operation of spray processes. It
can be either enclosed or unenclosed and includes: (a) any area in the direct path of a spray
application process: (b) the interior of any exhaust plenum an any exhaust duct leading from
the spray process: (c) the interior of any limited finishing workstation, spray booth, or spray
room, as herein defined: (d) the interior of any recirculation particulate filter, solvent
concentrator unit, solvent distillation (recovery) unit, or recirculation air supply unit.”
Limited Finishing Work Stations are therefore considered to be a spray area as defined by
NFPA 33.
Chapter 9 Protection - “9.1* General. Spray areas, which include by definition any
associated exhaust plenums and exhaust ductwork, any particulate filters, any solvent
concentrator units, any recirculation air supply units, and mixing rooms shall be protected
with an approved automatic fire protection system.”
Since Limited Finishing Workstations are defined as a spray area, they require an automatic
fire protection system. Further requirements are found in later in the Standard.
CHAPTER 14 MISCELLANEOUS SPRAY OPERATIONS
“14.3 Limited Finishing Workstations. A limited finishing workstation shall be designed
and operated in accordance with the requirements of 14.3.1 through 14.3.9.”
“14.3.1 A limited finishing workstation shall be designed and constructed to have the
following:
1) A dedicated make-up air supply and air supply plenum
2) Curtains or partitions that are noncombustible or limited combustible, as defined
in NFPA 220, or that can successfully pass Test Method 2 of NFPA 701
3) A dedicated mechanical exhaust and filtration system
4) An approved automatic extinguishing system that meets the requirements of
Chapter 9”
“14.3.2 The amount of material sprayed in a limited finishing workstation shall not exceed
3.8L (1 gal) in any 8 hour period.”
“14.3.3 The limited finishing workstation shall meet all applicable requirements of Chapter 4
through Chapter 10 and Chapter 18 of this standard.”
“14.3.4 Curtains or partitions shall be fully closed during any spray application operations.”
Under Chapter 14, we see that NFPA 33 requires an automatic fire extinguishing system for
Limited Finishing Workstations, the amount of sprayed material is severely limited and that
the curtains are to be closed during spray operations. The amount of material being sprayed
and the closure of the curtains can be very difficult for a local authority to enforce.
Various devices are appearing in the marketplace as curtained “prep stations” leading end
users and some local authorities to believe that these “prep” stations do not require an
automatic fire extinguishing system, even though spraying operations are occurring within
these “prep stations”. NFPA 33 addresses this issue as well.
“14.2 Preparation Workstations. If spraying finishing operations are performed at or in a
preparation workstation, the preparation workstation shall be considered an unenclosed spray
area and shall meet all of the requirements of an unenclosed spray area.
Exception: A preparation workstation that is designed and operated n accordance with
Section 14.3 shall be considered a limited finishing workstation and not an unenclosed spray
area.”
If spray finishing operations are occurring in a curtained “prep station” that has a dedicated
make up air supply or air supply plenum, is using curtains and has a dedicated mechanical
exhaust system, then it is not a “prep station” but in fact is considered to be a Limited
Finishing Workstation, and therefore requires an automatic fire extinguishing system.
FEMA discussed various methods of protecting these hazards including Total Flood, Local
Application Overhead and combinations of both with screening nozzles. Local Application
overhead was deemed unacceptable, since this application is designed for a horizontal surface
fire such as fuel in depth at floor level and does not address accumulation of residue on the
curtains (a vertical surface) nor does it address the possibility of a fire under a vehicle within
the workstation. Total Flood was deemed unacceptable as well. While Total Flood application
addresses the possibility of fire occurring on the vertical surface, it does not address what may
happen with the curtains during a fire scenario, what will happen if one or more curtains are
left open or the possibility of a fire occurring under a vehicle within the workstation.
FEMA contends that it is entirely possible that the many end users would utilize the Limited
Finishing Workstation to paint entire vehicles. FEMA members who market and sell pre-
engineered systems that are UL Listed under UL Standard 1254 for Vehicle Paint Spray
Booth applications have proven that their systems are effective when a vehicle is present,
particularly to the underside of the vehicle. Therefore, a determination was made that our in-
house fire testing would be performed using some variation of UL-listed vehicle paint spray
booth coverage. The desire was to arrive at a method of fire suppression that was both
practical and conservative in nature.
II) TEST METHOD:
a. Test Apparatus: A module based on a FEMA member’s current vehicle paint spray
booth UL listing was employed. (Typically, in most systems, four nozzles protect a
‘standard’ vehicle paint spray booth of dimensions 15’wide x 28’long x 10’ tall.) The
module ceiling was constructed of plywood. The module was surrounded on all four
sides with commercially-available solid vinyl curtains carrying an NFPA 701 flame
resistant rating. The curtains were installed with a 3” air gap at the ceiling, with a 6”
gap at the floor level to represent “worst case scenarios” where more air is allowed
into the spray area to help feed the fire and hinder extinguishment. The module of the
following dimensions was created:
Module Dimensions: 7.5’ wide x 14’ long x 10’ tall. For the Class B Heptane can fire
tests, a barrier of dimensions 3.75’ wide x 10.5’ long x 6’ tall was constructed per UL
1254.
III) Conclusions:
The behavior of the vinyl curtains when exposed to heat is evident from our testing. Although
flame resistant, they will shrink away from flame, thereby leaving an opening correlating to
the size and intensity of the fire. Before any rational approach to fire suppression can be
adopted, certain assumptions must be made:
Assumptions:
1) Entire vehicles will be spray painted inside these prep stations.
2) Fire can spread into the upper corners of the prep station, perhaps into any
ceiling-mounted air intake filters.
3) Some percentage (NOT 100%) of the curtain enclosure will be destroyed
before detection and actuation of the system, thus allowing dry chemical to
escape the perimeter of the prep station.
4) NFPA 33 requires that the curtains be closed during any spray operations
If these assumptions are accepted, then here is how we believe they should be addressed (in
order):
1) Some form of vehicle paint spray booth protection should be adopted ensuring
adequate protection underneath the vehicle.
2) Local application by itself is inadequate to extinguish fires in the upper reaches
of the prep station.
3) In all but the most catastrophic of conditions, there will be enough enclosure
remaining to allow for sufficient build-up of dry chemical.
Expanding further on point 3): The largest hole produced in the vinyl curtain was due to the
crib fires, 12” from the curtain (the same distance tested by UL for solid walls). The area of
the burn opening was approximately 21 ft2
. The total burn area of two cribs would then
account for less than 3% of the total area of the maximum possible prep station size. It is also
important to remember that the pre-burn period for crib fires is 2 minutes. Any thermal
detector of appropriate temperature rating should respond well before 2 minutes.
Based on this argument and the test results, FEMA believes that doubling the amount and
flow rate of dry chemical into a prep station over an equivalently sized vehicle paint spray
booth is conservative fire protection. Therefore, as an example, for any prep station of
maximum dimensions of 15’ wide x 28’ long x 10’ tall, two rows of four nozzles would be
required. This would apply to any number of vinyl-curtained walls, as long as a ceiling exists.
See Figure C as an example. All other parameters for vehicle paint spray booth coverage
should apply, including temperature limitations and maximum nozzle offsets.
.
Figure C
UL Listed nozzle coverages for standard (automobile) sized vehicle paint spray booths may
vary slightly from one manufacturer to another. FEMA recommends that the listed coverage,
regardless of the system manufacturer being used, should be doubled when protecting
Curtained Limited Finishing Work Stations. Only overhead (or “center of module”) nozzle
locations should be used for this application. Listed “sidewall” or “centerline” nozzle
placement is not considered by FEMA to be appropriate for this application based upon the
situation and live fire testing.
Duct and plenum protection would be used according to the individual system’ listed Design,
Installation and Maintenance manual.
Based upon the live fire tests conducted, it is FEMA’s opinion that this approach will provide
superior and conservative fire protection for this unique hazard.
Prepared by the members of FEMA’s Systems Division
Visit our website on Balanced Fire Protection at – www.femalifesafety.org

More Related Content

Viewers also liked

Frequently Asked Questions on UL 300 and Class K Fire Extinguishers
Frequently Asked Questions on UL 300 and Class K Fire ExtinguishersFrequently Asked Questions on UL 300 and Class K Fire Extinguishers
Frequently Asked Questions on UL 300 and Class K Fire Extinguishers
Fire Equipment Manufacturers' Association
 
How to Use a Portable Fire Extinguisher
How to Use a Portable Fire ExtinguisherHow to Use a Portable Fire Extinguisher
How to Use a Portable Fire Extinguisher
Fire Equipment Manufacturers' Association
 
Portable Fire Extinguisher Decision Tree for Maintenance
Portable Fire Extinguisher Decision Tree for MaintenancePortable Fire Extinguisher Decision Tree for Maintenance
Portable Fire Extinguisher Decision Tree for Maintenance
Fire Equipment Manufacturers' Association
 
A Closer Look-Portable Extinguisher
A Closer Look-Portable ExtinguisherA Closer Look-Portable Extinguisher
A Closer Look-Portable Extinguisher
Fire Equipment Manufacturers' Association
 
A Plan to Save Lives - Building Diagram
A Plan to Save Lives - Building DiagramA Plan to Save Lives - Building Diagram
A Plan to Save Lives - Building Diagram
Fire Equipment Manufacturers' Association
 
2829 High Rise Fire Protection: A Tall Order
2829 High Rise Fire Protection: A Tall Order 2829 High Rise Fire Protection: A Tall Order
2829 High Rise Fire Protection: A Tall Order
Fire Equipment Manufacturers' Association
 
Third-Party Training for Pre-Engineered Fire Suppression Systems
Third-Party Training for Pre-Engineered Fire Suppression SystemsThird-Party Training for Pre-Engineered Fire Suppression Systems
Third-Party Training for Pre-Engineered Fire Suppression Systems
Fire Equipment Manufacturers' Association
 
Using a Fire Extinguisher - P.A.S.S. Infographic
Using a Fire Extinguisher - P.A.S.S. InfographicUsing a Fire Extinguisher - P.A.S.S. Infographic
Using a Fire Extinguisher - P.A.S.S. Infographic
Fire Equipment Manufacturers' Association
 
Decision Tree for Servicing Pre-Engineered Systems
Decision Tree for Servicing Pre-Engineered SystemsDecision Tree for Servicing Pre-Engineered Systems
Decision Tree for Servicing Pre-Engineered Systems
Fire Equipment Manufacturers' Association
 
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
Fire Equipment Manufacturers' Association
 
Manufacturer Recommended Parts for Pre-Engineered Systems
Manufacturer Recommended Parts for Pre-Engineered SystemsManufacturer Recommended Parts for Pre-Engineered Systems
Manufacturer Recommended Parts for Pre-Engineered Systems
Fire Equipment Manufacturers' Association
 
A Closer Look: Fire Suppression Systems
A Closer Look: Fire Suppression SystemsA Closer Look: Fire Suppression Systems
A Closer Look: Fire Suppression Systems
Fire Equipment Manufacturers' Association
 
A Closer Look: Standpipe Fire Hose Stations
A Closer Look: Standpipe Fire Hose StationsA Closer Look: Standpipe Fire Hose Stations
A Closer Look: Standpipe Fire Hose Stations
Fire Equipment Manufacturers' Association
 
FEMA Balanced Fire Protection Brochure
FEMA Balanced Fire Protection BrochureFEMA Balanced Fire Protection Brochure
FEMA Balanced Fire Protection Brochure
Fire Equipment Manufacturers' Association
 
Class K Fire Extinguishers
Class K Fire ExtinguishersClass K Fire Extinguishers
Class K Fire Extinguishers
Fire Equipment Manufacturers' Association
 
Rack and Reel Fire Hose Insure Dependability
Rack and Reel Fire Hose Insure DependabilityRack and Reel Fire Hose Insure Dependability
Rack and Reel Fire Hose Insure Dependability
Fire Equipment Manufacturers' Association
 
A Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & MaintenanceA Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & Maintenance
Fire Equipment Manufacturers' Association
 

Viewers also liked (17)

Frequently Asked Questions on UL 300 and Class K Fire Extinguishers
Frequently Asked Questions on UL 300 and Class K Fire ExtinguishersFrequently Asked Questions on UL 300 and Class K Fire Extinguishers
Frequently Asked Questions on UL 300 and Class K Fire Extinguishers
 
How to Use a Portable Fire Extinguisher
How to Use a Portable Fire ExtinguisherHow to Use a Portable Fire Extinguisher
How to Use a Portable Fire Extinguisher
 
Portable Fire Extinguisher Decision Tree for Maintenance
Portable Fire Extinguisher Decision Tree for MaintenancePortable Fire Extinguisher Decision Tree for Maintenance
Portable Fire Extinguisher Decision Tree for Maintenance
 
A Closer Look-Portable Extinguisher
A Closer Look-Portable ExtinguisherA Closer Look-Portable Extinguisher
A Closer Look-Portable Extinguisher
 
A Plan to Save Lives - Building Diagram
A Plan to Save Lives - Building DiagramA Plan to Save Lives - Building Diagram
A Plan to Save Lives - Building Diagram
 
2829 High Rise Fire Protection: A Tall Order
2829 High Rise Fire Protection: A Tall Order 2829 High Rise Fire Protection: A Tall Order
2829 High Rise Fire Protection: A Tall Order
 
Third-Party Training for Pre-Engineered Fire Suppression Systems
Third-Party Training for Pre-Engineered Fire Suppression SystemsThird-Party Training for Pre-Engineered Fire Suppression Systems
Third-Party Training for Pre-Engineered Fire Suppression Systems
 
Using a Fire Extinguisher - P.A.S.S. Infographic
Using a Fire Extinguisher - P.A.S.S. InfographicUsing a Fire Extinguisher - P.A.S.S. Infographic
Using a Fire Extinguisher - P.A.S.S. Infographic
 
Decision Tree for Servicing Pre-Engineered Systems
Decision Tree for Servicing Pre-Engineered SystemsDecision Tree for Servicing Pre-Engineered Systems
Decision Tree for Servicing Pre-Engineered Systems
 
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
Recommended Practice On Upgrading Restaurant Cooking Area Fire Protection Sys...
 
Manufacturer Recommended Parts for Pre-Engineered Systems
Manufacturer Recommended Parts for Pre-Engineered SystemsManufacturer Recommended Parts for Pre-Engineered Systems
Manufacturer Recommended Parts for Pre-Engineered Systems
 
A Closer Look: Fire Suppression Systems
A Closer Look: Fire Suppression SystemsA Closer Look: Fire Suppression Systems
A Closer Look: Fire Suppression Systems
 
A Closer Look: Standpipe Fire Hose Stations
A Closer Look: Standpipe Fire Hose StationsA Closer Look: Standpipe Fire Hose Stations
A Closer Look: Standpipe Fire Hose Stations
 
FEMA Balanced Fire Protection Brochure
FEMA Balanced Fire Protection BrochureFEMA Balanced Fire Protection Brochure
FEMA Balanced Fire Protection Brochure
 
Class K Fire Extinguishers
Class K Fire ExtinguishersClass K Fire Extinguishers
Class K Fire Extinguishers
 
Rack and Reel Fire Hose Insure Dependability
Rack and Reel Fire Hose Insure DependabilityRack and Reel Fire Hose Insure Dependability
Rack and Reel Fire Hose Insure Dependability
 
A Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & MaintenanceA Hands-On Guide for Inspection & Maintenance
A Hands-On Guide for Inspection & Maintenance
 

Similar to Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed Pre-Engineered Dry Chemical Systems

Acaf rimseal
Acaf rimsealAcaf rimseal
Acaf rimseal
qazplm123098
 
Introduction to Process Flares
Introduction to Process FlaresIntroduction to Process Flares
Introduction to Process Flares
Karl Kolmetz
 
Fire dampers installation
Fire dampers installationFire dampers installation
Fire dampers installation
Construction Technical Services Arabia
 
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
gurkanarifyalcinkaya
 
Rms Risk Bulletin Nov 12
Rms Risk Bulletin Nov 12Rms Risk Bulletin Nov 12
Rms Risk Bulletin Nov 12
TBurkittBlack
 
Final Project Textile Class
Final Project Textile ClassFinal Project Textile Class
Final Project Textile Class
Nicole Stebnitz
 
Slide Share Demo
Slide Share DemoSlide Share Demo
Slide Share Demodavidware
 
Crawford Tracey AIA Course: Glazing Design
Crawford Tracey AIA Course: Glazing DesignCrawford Tracey AIA Course: Glazing Design
Crawford Tracey AIA Course: Glazing DesignDonovan and Associates
 
Fire separation requirements in hangar home design and construction
Fire separation requirements in hangar home design and constructionFire separation requirements in hangar home design and construction
Fire separation requirements in hangar home design and construction
MattM80
 
Development of Fire Test for Aircraft Seat Cushions
Development of Fire Test for Aircraft Seat CushionsDevelopment of Fire Test for Aircraft Seat Cushions
Development of Fire Test for Aircraft Seat Cushions
U.S. Consumer Product Safety Commission
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
MarcGajudo
 
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
AnupamaPanoli
 
CPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park Ventilation
Colt UK
 
2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdf2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdf
ssuser9ddbb1
 
Damage Control Brochure
Damage Control BrochureDamage Control Brochure
Damage Control BrochureElizabeth Lenz
 
Bs ii-assignment
Bs ii-assignmentBs ii-assignment
Bs ii-assignment
Lwj Welson
 
An Introduction to NFPA Standard 68 for Metalworking facilities
An Introduction to NFPA Standard 68 for Metalworking facilitiesAn Introduction to NFPA Standard 68 for Metalworking facilities
An Introduction to NFPA Standard 68 for Metalworking facilities
Camfil APC
 
A publication of global asset protection services
A publication of global asset protection servicesA publication of global asset protection services
A publication of global asset protection services
Jose ANSELMO Soares da Silva
 
Natural smoke and_heat_exhaust_systems
Natural smoke and_heat_exhaust_systemsNatural smoke and_heat_exhaust_systems
Natural smoke and_heat_exhaust_systems
jkborade
 

Similar to Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed Pre-Engineered Dry Chemical Systems (20)

Acaf rimseal
Acaf rimsealAcaf rimseal
Acaf rimseal
 
Introduction to Process Flares
Introduction to Process FlaresIntroduction to Process Flares
Introduction to Process Flares
 
Fire smokedampers
Fire smokedampersFire smokedampers
Fire smokedampers
 
Fire dampers installation
Fire dampers installationFire dampers installation
Fire dampers installation
 
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
Guidelines for Engineering Design for Process Safety (Process Safety Guidelin...
 
Rms Risk Bulletin Nov 12
Rms Risk Bulletin Nov 12Rms Risk Bulletin Nov 12
Rms Risk Bulletin Nov 12
 
Final Project Textile Class
Final Project Textile ClassFinal Project Textile Class
Final Project Textile Class
 
Slide Share Demo
Slide Share DemoSlide Share Demo
Slide Share Demo
 
Crawford Tracey AIA Course: Glazing Design
Crawford Tracey AIA Course: Glazing DesignCrawford Tracey AIA Course: Glazing Design
Crawford Tracey AIA Course: Glazing Design
 
Fire separation requirements in hangar home design and construction
Fire separation requirements in hangar home design and constructionFire separation requirements in hangar home design and construction
Fire separation requirements in hangar home design and construction
 
Development of Fire Test for Aircraft Seat Cushions
Development of Fire Test for Aircraft Seat CushionsDevelopment of Fire Test for Aircraft Seat Cushions
Development of Fire Test for Aircraft Seat Cushions
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
 
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
OISD-STD-117 Fire Protection Facilities for Petroleum Depots, Terminals, Pipe...
 
CPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park Ventilation
 
2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdf2.-Deflagration-Flame-Arrester-In-Line.pdf
2.-Deflagration-Flame-Arrester-In-Line.pdf
 
Damage Control Brochure
Damage Control BrochureDamage Control Brochure
Damage Control Brochure
 
Bs ii-assignment
Bs ii-assignmentBs ii-assignment
Bs ii-assignment
 
An Introduction to NFPA Standard 68 for Metalworking facilities
An Introduction to NFPA Standard 68 for Metalworking facilitiesAn Introduction to NFPA Standard 68 for Metalworking facilities
An Introduction to NFPA Standard 68 for Metalworking facilities
 
A publication of global asset protection services
A publication of global asset protection servicesA publication of global asset protection services
A publication of global asset protection services
 
Natural smoke and_heat_exhaust_systems
Natural smoke and_heat_exhaust_systemsNatural smoke and_heat_exhaust_systems
Natural smoke and_heat_exhaust_systems
 

Recently uploaded

The basics of sentences session 5pptx.pptx
The basics of sentences session 5pptx.pptxThe basics of sentences session 5pptx.pptx
The basics of sentences session 5pptx.pptx
heathfieldcps1
 
"Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe..."Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe...
SACHIN R KONDAGURI
 
Guidance_and_Counselling.pdf B.Ed. 4th Semester
Guidance_and_Counselling.pdf B.Ed. 4th SemesterGuidance_and_Counselling.pdf B.Ed. 4th Semester
Guidance_and_Counselling.pdf B.Ed. 4th Semester
Atul Kumar Singh
 
Phrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXX
Phrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXXPhrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXX
Phrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXX
MIRIAMSALINAS13
 
Acetabularia Information For Class 9 .docx
Acetabularia Information For Class 9  .docxAcetabularia Information For Class 9  .docx
Acetabularia Information For Class 9 .docx
vaibhavrinwa19
 
June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...
June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...
June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...
Levi Shapiro
 
CACJapan - GROUP Presentation 1- Wk 4.pdf
CACJapan - GROUP Presentation 1- Wk 4.pdfCACJapan - GROUP Presentation 1- Wk 4.pdf
CACJapan - GROUP Presentation 1- Wk 4.pdf
camakaiclarkmusic
 
Language Across the Curriculm LAC B.Ed.
Language Across the  Curriculm LAC B.Ed.Language Across the  Curriculm LAC B.Ed.
Language Across the Curriculm LAC B.Ed.
Atul Kumar Singh
 
Instructions for Submissions thorugh G- Classroom.pptx
Instructions for Submissions thorugh G- Classroom.pptxInstructions for Submissions thorugh G- Classroom.pptx
Instructions for Submissions thorugh G- Classroom.pptx
Jheel Barad
 
Francesca Gottschalk - How can education support child empowerment.pptx
Francesca Gottschalk - How can education support child empowerment.pptxFrancesca Gottschalk - How can education support child empowerment.pptx
Francesca Gottschalk - How can education support child empowerment.pptx
EduSkills OECD
 
Palestine last event orientationfvgnh .pptx
Palestine last event orientationfvgnh .pptxPalestine last event orientationfvgnh .pptx
Palestine last event orientationfvgnh .pptx
RaedMohamed3
 
Welcome to TechSoup New Member Orientation and Q&A (May 2024).pdf
Welcome to TechSoup   New Member Orientation and Q&A (May 2024).pdfWelcome to TechSoup   New Member Orientation and Q&A (May 2024).pdf
Welcome to TechSoup New Member Orientation and Q&A (May 2024).pdf
TechSoup
 
Model Attribute Check Company Auto Property
Model Attribute  Check Company Auto PropertyModel Attribute  Check Company Auto Property
Model Attribute Check Company Auto Property
Celine George
 
Overview on Edible Vaccine: Pros & Cons with Mechanism
Overview on Edible Vaccine: Pros & Cons with MechanismOverview on Edible Vaccine: Pros & Cons with Mechanism
Overview on Edible Vaccine: Pros & Cons with Mechanism
DeeptiGupta154
 
The Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official PublicationThe Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official Publication
Delapenabediema
 
Supporting (UKRI) OA monographs at Salford.pptx
Supporting (UKRI) OA monographs at Salford.pptxSupporting (UKRI) OA monographs at Salford.pptx
Supporting (UKRI) OA monographs at Salford.pptx
Jisc
 
Honest Reviews of Tim Han LMA Course Program.pptx
Honest Reviews of Tim Han LMA Course Program.pptxHonest Reviews of Tim Han LMA Course Program.pptx
Honest Reviews of Tim Han LMA Course Program.pptx
timhan337
 
Home assignment II on Spectroscopy 2024 Answers.pdf
Home assignment II on Spectroscopy 2024 Answers.pdfHome assignment II on Spectroscopy 2024 Answers.pdf
Home assignment II on Spectroscopy 2024 Answers.pdf
Tamralipta Mahavidyalaya
 
Operation Blue Star - Saka Neela Tara
Operation Blue Star   -  Saka Neela TaraOperation Blue Star   -  Saka Neela Tara
Operation Blue Star - Saka Neela Tara
Balvir Singh
 
Polish students' mobility in the Czech Republic
Polish students' mobility in the Czech RepublicPolish students' mobility in the Czech Republic
Polish students' mobility in the Czech Republic
Anna Sz.
 

Recently uploaded (20)

The basics of sentences session 5pptx.pptx
The basics of sentences session 5pptx.pptxThe basics of sentences session 5pptx.pptx
The basics of sentences session 5pptx.pptx
 
"Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe..."Protectable subject matters, Protection in biotechnology, Protection of othe...
"Protectable subject matters, Protection in biotechnology, Protection of othe...
 
Guidance_and_Counselling.pdf B.Ed. 4th Semester
Guidance_and_Counselling.pdf B.Ed. 4th SemesterGuidance_and_Counselling.pdf B.Ed. 4th Semester
Guidance_and_Counselling.pdf B.Ed. 4th Semester
 
Phrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXX
Phrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXXPhrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXX
Phrasal Verbs.XXXXXXXXXXXXXXXXXXXXXXXXXX
 
Acetabularia Information For Class 9 .docx
Acetabularia Information For Class 9  .docxAcetabularia Information For Class 9  .docx
Acetabularia Information For Class 9 .docx
 
June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...
June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...
June 3, 2024 Anti-Semitism Letter Sent to MIT President Kornbluth and MIT Cor...
 
CACJapan - GROUP Presentation 1- Wk 4.pdf
CACJapan - GROUP Presentation 1- Wk 4.pdfCACJapan - GROUP Presentation 1- Wk 4.pdf
CACJapan - GROUP Presentation 1- Wk 4.pdf
 
Language Across the Curriculm LAC B.Ed.
Language Across the  Curriculm LAC B.Ed.Language Across the  Curriculm LAC B.Ed.
Language Across the Curriculm LAC B.Ed.
 
Instructions for Submissions thorugh G- Classroom.pptx
Instructions for Submissions thorugh G- Classroom.pptxInstructions for Submissions thorugh G- Classroom.pptx
Instructions for Submissions thorugh G- Classroom.pptx
 
Francesca Gottschalk - How can education support child empowerment.pptx
Francesca Gottschalk - How can education support child empowerment.pptxFrancesca Gottschalk - How can education support child empowerment.pptx
Francesca Gottschalk - How can education support child empowerment.pptx
 
Palestine last event orientationfvgnh .pptx
Palestine last event orientationfvgnh .pptxPalestine last event orientationfvgnh .pptx
Palestine last event orientationfvgnh .pptx
 
Welcome to TechSoup New Member Orientation and Q&A (May 2024).pdf
Welcome to TechSoup   New Member Orientation and Q&A (May 2024).pdfWelcome to TechSoup   New Member Orientation and Q&A (May 2024).pdf
Welcome to TechSoup New Member Orientation and Q&A (May 2024).pdf
 
Model Attribute Check Company Auto Property
Model Attribute  Check Company Auto PropertyModel Attribute  Check Company Auto Property
Model Attribute Check Company Auto Property
 
Overview on Edible Vaccine: Pros & Cons with Mechanism
Overview on Edible Vaccine: Pros & Cons with MechanismOverview on Edible Vaccine: Pros & Cons with Mechanism
Overview on Edible Vaccine: Pros & Cons with Mechanism
 
The Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official PublicationThe Challenger.pdf DNHS Official Publication
The Challenger.pdf DNHS Official Publication
 
Supporting (UKRI) OA monographs at Salford.pptx
Supporting (UKRI) OA monographs at Salford.pptxSupporting (UKRI) OA monographs at Salford.pptx
Supporting (UKRI) OA monographs at Salford.pptx
 
Honest Reviews of Tim Han LMA Course Program.pptx
Honest Reviews of Tim Han LMA Course Program.pptxHonest Reviews of Tim Han LMA Course Program.pptx
Honest Reviews of Tim Han LMA Course Program.pptx
 
Home assignment II on Spectroscopy 2024 Answers.pdf
Home assignment II on Spectroscopy 2024 Answers.pdfHome assignment II on Spectroscopy 2024 Answers.pdf
Home assignment II on Spectroscopy 2024 Answers.pdf
 
Operation Blue Star - Saka Neela Tara
Operation Blue Star   -  Saka Neela TaraOperation Blue Star   -  Saka Neela Tara
Operation Blue Star - Saka Neela Tara
 
Polish students' mobility in the Czech Republic
Polish students' mobility in the Czech RepublicPolish students' mobility in the Czech Republic
Polish students' mobility in the Czech Republic
 

Protection of Curtained Limited Finishing Workstations using Ul 1254 Listed Pre-Engineered Dry Chemical Systems

  • 1. FIRE EQUIPMENT MANUFACTURERS' ASSOCIATION                                  Executive Director: THOMAS ASSOCIATES, INC.  1300 Sumner Avenue, Cleveland, Ohio 44115‐2851   •   Telephone: 216‐241‐7333   •   Fax: 216‐241‐0105  E‐Mail:  fema@femalifesafety.org  •  www.femalifesafety.org  •  www.rackhosetraining.com  •  www.firesystemstraining.org   FEMA RECOMMENDATIONS FOR PROTECTION OF CURTAINED LIMITED FINISHING WORKSTATIONS USING UL 1254 LISTED PRE-ENGINEERED DRY CHEMICAL SYSTEMS FEMA RECOMMENDATIONS ARE BASED UPON LIVE FIRE TESTING OF PREP STATIONS UTILIZING ONE OR MORE VINYL CURTAIN WALLS I) SUMMARY: The proliferation of automobile Limited Finishing Workstations using vinyl curtains (as opposed to fixed walls) requires us to re-evaluate dry chemical fire suppression coverage. There appears to be a lack of clear guidance or agreement in applicable standards, such as UL 1254 “Pre-Engineered Dry Chemical Extinguishing System Units”, or NFPA 17 “Standard for Dry Chemical Extinguishing Systems”. First we will examine the requirements for automatic fire protection systems in NFPA 33 – Standard for Spray Application Using Flammable or Combustible Materials – 2003 Edition. NFPA 33 2003 EDITION REQUIREMENTS “3.3.1.3* Spray Area. Any area in which dangerous quantities of flammable or combustible vapors, mists, residues, dusts or deposits are present due to the operation of spray processes. It can be either enclosed or unenclosed and includes: (a) any area in the direct path of a spray application process: (b) the interior of any exhaust plenum an any exhaust duct leading from the spray process: (c) the interior of any limited finishing workstation, spray booth, or spray room, as herein defined: (d) the interior of any recirculation particulate filter, solvent concentrator unit, solvent distillation (recovery) unit, or recirculation air supply unit.” Limited Finishing Work Stations are therefore considered to be a spray area as defined by NFPA 33. Chapter 9 Protection - “9.1* General. Spray areas, which include by definition any associated exhaust plenums and exhaust ductwork, any particulate filters, any solvent concentrator units, any recirculation air supply units, and mixing rooms shall be protected with an approved automatic fire protection system.” Since Limited Finishing Workstations are defined as a spray area, they require an automatic fire protection system. Further requirements are found in later in the Standard.
  • 2. CHAPTER 14 MISCELLANEOUS SPRAY OPERATIONS “14.3 Limited Finishing Workstations. A limited finishing workstation shall be designed and operated in accordance with the requirements of 14.3.1 through 14.3.9.” “14.3.1 A limited finishing workstation shall be designed and constructed to have the following: 1) A dedicated make-up air supply and air supply plenum 2) Curtains or partitions that are noncombustible or limited combustible, as defined in NFPA 220, or that can successfully pass Test Method 2 of NFPA 701 3) A dedicated mechanical exhaust and filtration system 4) An approved automatic extinguishing system that meets the requirements of Chapter 9” “14.3.2 The amount of material sprayed in a limited finishing workstation shall not exceed 3.8L (1 gal) in any 8 hour period.” “14.3.3 The limited finishing workstation shall meet all applicable requirements of Chapter 4 through Chapter 10 and Chapter 18 of this standard.” “14.3.4 Curtains or partitions shall be fully closed during any spray application operations.” Under Chapter 14, we see that NFPA 33 requires an automatic fire extinguishing system for Limited Finishing Workstations, the amount of sprayed material is severely limited and that the curtains are to be closed during spray operations. The amount of material being sprayed and the closure of the curtains can be very difficult for a local authority to enforce. Various devices are appearing in the marketplace as curtained “prep stations” leading end users and some local authorities to believe that these “prep” stations do not require an automatic fire extinguishing system, even though spraying operations are occurring within these “prep stations”. NFPA 33 addresses this issue as well. “14.2 Preparation Workstations. If spraying finishing operations are performed at or in a preparation workstation, the preparation workstation shall be considered an unenclosed spray area and shall meet all of the requirements of an unenclosed spray area. Exception: A preparation workstation that is designed and operated n accordance with Section 14.3 shall be considered a limited finishing workstation and not an unenclosed spray area.” If spray finishing operations are occurring in a curtained “prep station” that has a dedicated make up air supply or air supply plenum, is using curtains and has a dedicated mechanical exhaust system, then it is not a “prep station” but in fact is considered to be a Limited Finishing Workstation, and therefore requires an automatic fire extinguishing system. FEMA discussed various methods of protecting these hazards including Total Flood, Local Application Overhead and combinations of both with screening nozzles. Local Application overhead was deemed unacceptable, since this application is designed for a horizontal surface fire such as fuel in depth at floor level and does not address accumulation of residue on the
  • 3. curtains (a vertical surface) nor does it address the possibility of a fire under a vehicle within the workstation. Total Flood was deemed unacceptable as well. While Total Flood application addresses the possibility of fire occurring on the vertical surface, it does not address what may happen with the curtains during a fire scenario, what will happen if one or more curtains are left open or the possibility of a fire occurring under a vehicle within the workstation. FEMA contends that it is entirely possible that the many end users would utilize the Limited Finishing Workstation to paint entire vehicles. FEMA members who market and sell pre- engineered systems that are UL Listed under UL Standard 1254 for Vehicle Paint Spray Booth applications have proven that their systems are effective when a vehicle is present, particularly to the underside of the vehicle. Therefore, a determination was made that our in- house fire testing would be performed using some variation of UL-listed vehicle paint spray booth coverage. The desire was to arrive at a method of fire suppression that was both practical and conservative in nature. II) TEST METHOD: a. Test Apparatus: A module based on a FEMA member’s current vehicle paint spray booth UL listing was employed. (Typically, in most systems, four nozzles protect a ‘standard’ vehicle paint spray booth of dimensions 15’wide x 28’long x 10’ tall.) The module ceiling was constructed of plywood. The module was surrounded on all four sides with commercially-available solid vinyl curtains carrying an NFPA 701 flame resistant rating. The curtains were installed with a 3” air gap at the ceiling, with a 6” gap at the floor level to represent “worst case scenarios” where more air is allowed into the spray area to help feed the fire and hinder extinguishment. The module of the following dimensions was created: Module Dimensions: 7.5’ wide x 14’ long x 10’ tall. For the Class B Heptane can fire tests, a barrier of dimensions 3.75’ wide x 10.5’ long x 6’ tall was constructed per UL 1254. III) Conclusions: The behavior of the vinyl curtains when exposed to heat is evident from our testing. Although flame resistant, they will shrink away from flame, thereby leaving an opening correlating to the size and intensity of the fire. Before any rational approach to fire suppression can be adopted, certain assumptions must be made: Assumptions: 1) Entire vehicles will be spray painted inside these prep stations. 2) Fire can spread into the upper corners of the prep station, perhaps into any ceiling-mounted air intake filters. 3) Some percentage (NOT 100%) of the curtain enclosure will be destroyed before detection and actuation of the system, thus allowing dry chemical to escape the perimeter of the prep station. 4) NFPA 33 requires that the curtains be closed during any spray operations If these assumptions are accepted, then here is how we believe they should be addressed (in order):
  • 4. 1) Some form of vehicle paint spray booth protection should be adopted ensuring adequate protection underneath the vehicle. 2) Local application by itself is inadequate to extinguish fires in the upper reaches of the prep station. 3) In all but the most catastrophic of conditions, there will be enough enclosure remaining to allow for sufficient build-up of dry chemical. Expanding further on point 3): The largest hole produced in the vinyl curtain was due to the crib fires, 12” from the curtain (the same distance tested by UL for solid walls). The area of the burn opening was approximately 21 ft2 . The total burn area of two cribs would then account for less than 3% of the total area of the maximum possible prep station size. It is also important to remember that the pre-burn period for crib fires is 2 minutes. Any thermal detector of appropriate temperature rating should respond well before 2 minutes. Based on this argument and the test results, FEMA believes that doubling the amount and flow rate of dry chemical into a prep station over an equivalently sized vehicle paint spray booth is conservative fire protection. Therefore, as an example, for any prep station of maximum dimensions of 15’ wide x 28’ long x 10’ tall, two rows of four nozzles would be required. This would apply to any number of vinyl-curtained walls, as long as a ceiling exists. See Figure C as an example. All other parameters for vehicle paint spray booth coverage should apply, including temperature limitations and maximum nozzle offsets. . Figure C UL Listed nozzle coverages for standard (automobile) sized vehicle paint spray booths may vary slightly from one manufacturer to another. FEMA recommends that the listed coverage, regardless of the system manufacturer being used, should be doubled when protecting Curtained Limited Finishing Work Stations. Only overhead (or “center of module”) nozzle locations should be used for this application. Listed “sidewall” or “centerline” nozzle placement is not considered by FEMA to be appropriate for this application based upon the situation and live fire testing.
  • 5. Duct and plenum protection would be used according to the individual system’ listed Design, Installation and Maintenance manual. Based upon the live fire tests conducted, it is FEMA’s opinion that this approach will provide superior and conservative fire protection for this unique hazard. Prepared by the members of FEMA’s Systems Division Visit our website on Balanced Fire Protection at – www.femalifesafety.org