CASE STUDY – COMMERCIAL
Current Filtration Situation
Cushman & Wakefield of Texas has been a loyal AAF
International customer for many years. When Cushman &
Wakefield began investigating ways to improve its building
efficiency at 777 Main Street in 2009, AAF was there to
assist with proven filtration solution options.
The building at this time utilized MERV 8 PerfectPleat®
Ultra
filters. In order to obtain a Leadership in Energy and
Environmental Design (LEED®
) certification for the building,
the plaza would need to upgarde its filtration in order to
reach this goal.
Sustainable Filtration
Rising energy costs and the current economic downturn
are increasing the pressure on commercial buildings to
cut energy costs and create more sustainable properties.
The LEED Green Building Rating System™
, administered by
the U.S. Green Building Council, is the nationally accepted
benchmark for designing and sustaining green buildings.
LEED provides third-party verification that a building is
designed and built using strategies aimed at improving
performance across all the metrics that matter most: energy
savings, water efficiency, CO2 emissions reduction, improved
indoor environmental quality, and stewardship of resources
and sensitivity to their impacts.
LEED provides building owners and operators the framework
for identifying and implementing practical and measurable
design, construction, operations, and maintenance solutions.
Proper air filtration strategies can contribute to credits toward
certification. One activity involves increasing the efficiency
of the air filtration, thereby reducing the particulate being
distributed.
The AAF Solution
A complete survey was done to find economical solutions to
upgrade the efficiency level of the current filtration without a
significant impact on the budget.
AAF recommended MERV 13 VariCel®
M-Pak filters to
upgrade efficiency in the large recirculation units inside the
building. The dual-density media design of the VariCel M-Pak
utilizes the full filtering potential of the media and maximizes
dust holding. Maximized dust holding capacity extends the
life of the filter and minimizes operating costs.
Cushman & Wakefield was presented with AAF’s Life Cycle
Valuation (LCV) report comparing the overall costs of the
PerfectPleat Ultra filter in combination with the VariCel
M-Pak filter, and
the VariCel M-Pak
filter alone. The
most economical
outcome was
to install VariCel
M-Pak filters
without the
prefilters. No
costly fan
modifications
were required
with this choice,
and energy
savings would
be greater.
Additionally, AAF recommended MERV 14 DriPak®
2000
filters with no prefilter for the new fresh air intakes that were
added on the roof. These fresh air intakes are exposed to
lots of moisture, and DriPak 2000 filters will not block off the
airflow if they get wet. This also minimized pressure drop
across the filter.
Office Building Upgrades Filtration -
Achieves LEED®
Certification; Receives NAFA Clean Air Award
BETTER AIR IS OUR BUSINESS®
Customer Profile
•	777 Main Street: 40-story, Class A office building
totaling 954,895 rentable square feet
•	Located in the heart of downtown Fort Worth
•	Owned by F7 Sssm LLC and managed by
Cushman & Wakefield, Inc.
Life Cycle Valuation (LCV) Report
Lower
Total
Cost
9920 Corporate Campus Drive, Suite 2200, Louisville, KY 40223-5690
888.223.2003 Fax 888.223.6500 | www.aafintl.com
AAF has a policy of continuous product research and
improvement and reserves the right to change design
and specifications without notice.
ISO Certified Firm
AFP-6-103B 08/15
©2015 AAF International
Office Building Upgrades Filtration
The Results
Cushman & Wakefield decided to run a six month trial on air
handlers with the heaviest dirt load in the building. The trial
revealed they could get one year of life from the VariCel M-Pak
filters without using a prefilter.
Over a twelve month period, all interior and exterior air
handling units in 777 Main Street were refurbished and all
MERV 8 filters were upgraded to MERV 13 VariCel M-Pak
filters or MERV 14 DriPak 2000 filters.
As a result of the improvements, the particulate matter
was reduced 62% in 777 Main Street. The industry
assumption for this type of improvement is a 40% reduction
in absenteeism, due to a reduction in upper respiratory
problems for people who work in the building.
777 Main Street achieved LEED EB certification in 2009. In
addition, the building was awarded the National Air Filter
Association (NAFA) Clean Air Award for 2010. The purpose of
the Clean Air Award is to recognize leadership and excellence
in air filtration by selected air filter users, and to promote the
National Air Filtration Association and its member companies.
Any facility or company that has demonstrated a concerted
effort to provide a clear indoor air environment by using
proper filtration and has a minimum score of 52 is eligible for
the award. 777 Main Street scored an astounding 67. In the
past, no more that eight facilities per year nationally are
recognized for this accomplishment.
VariCel®
M-Pak filters installed in recirculation units (top) and DriPak®
2000
filters installed in fresh air intakes (bottom) at 777 Main Street,
Fort Worth, TX.
777 Main Street.
PerfectPleat®
, VariCel®
, and DriPak®
are registered trademarks of
AAF International in the U.S. and other countries.

More Related Content

What's hot

Gorrell_Gene_Res_Final
Gorrell_Gene_Res_FinalGorrell_Gene_Res_Final
Gorrell_Gene_Res_Final
Gene Gorrell
 
02 08 04-05-25
02 08 04-05-2502 08 04-05-25
02 08 04-05-25
Edward Somgal
 
Improving The Reliability Of Differential Pressure Level Instrumentation
Improving The Reliability Of Differential Pressure Level InstrumentationImproving The Reliability Of Differential Pressure Level Instrumentation
Improving The Reliability Of Differential Pressure Level Instrumentation
Osemhen Akhibi
 
Fmi plenaryv4
Fmi plenaryv4Fmi plenaryv4
Fmi plenaryv4
Cinta Cinta
 
Pankaj 1
Pankaj 1Pankaj 1
Pankaj 1
Pankaj Kumar
 
Raja_Ratnam_All Energy Oct 2011 abstract
Raja_Ratnam_All Energy Oct 2011 abstractRaja_Ratnam_All Energy Oct 2011 abstract
Raja_Ratnam_All Energy Oct 2011 abstract
Raja Ratnam
 

What's hot (6)

Gorrell_Gene_Res_Final
Gorrell_Gene_Res_FinalGorrell_Gene_Res_Final
Gorrell_Gene_Res_Final
 
02 08 04-05-25
02 08 04-05-2502 08 04-05-25
02 08 04-05-25
 
Improving The Reliability Of Differential Pressure Level Instrumentation
Improving The Reliability Of Differential Pressure Level InstrumentationImproving The Reliability Of Differential Pressure Level Instrumentation
Improving The Reliability Of Differential Pressure Level Instrumentation
 
Fmi plenaryv4
Fmi plenaryv4Fmi plenaryv4
Fmi plenaryv4
 
Pankaj 1
Pankaj 1Pankaj 1
Pankaj 1
 
Raja_Ratnam_All Energy Oct 2011 abstract
Raja_Ratnam_All Energy Oct 2011 abstractRaja_Ratnam_All Energy Oct 2011 abstract
Raja_Ratnam_All Energy Oct 2011 abstract
 

Similar to Office Building Upgrades Filtration Case Study AFP=

Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...
Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...
Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...
UniqueIndoorComfortLibertyville
 
Cardiff University : AHU - Low Energy Air Filter Case Study
Cardiff University : AHU - Low Energy Air Filter Case StudyCardiff University : AHU - Low Energy Air Filter Case Study
Cardiff University : AHU - Low Energy Air Filter Case Study
Camfil UK
 
Comparing griha with breeam for new construction
Comparing griha with breeam for new constructionComparing griha with breeam for new construction
Comparing griha with breeam for new construction
khushal tadas
 
AMWAY GRAND Hotel Case Study SSF
AMWAY GRAND Hotel Case Study SSFAMWAY GRAND Hotel Case Study SSF
AMWAY GRAND Hotel Case Study SSF
Steve Fournier
 
Scalable Hydrogen Energy Platform (SHEP).pdf
Scalable Hydrogen Energy Platform (SHEP).pdfScalable Hydrogen Energy Platform (SHEP).pdf
Scalable Hydrogen Energy Platform (SHEP).pdf
HNO International
 
Sustainable Aviation - Cleaner, Quieter , Smarter
Sustainable Aviation - Cleaner, Quieter , Smarter  Sustainable Aviation - Cleaner, Quieter , Smarter
Sustainable Aviation - Cleaner, Quieter , Smarter
Akshaykumar More
 
Veolia Hickory Meadows LEED Project Profile | Miron Construction
Veolia Hickory Meadows LEED Project Profile | Miron ConstructionVeolia Hickory Meadows LEED Project Profile | Miron Construction
Veolia Hickory Meadows LEED Project Profile | Miron Construction
Miron Construction
 
Astec in Bangladesh - Increasing Sustainability
Astec in Bangladesh - Increasing SustainabilityAstec in Bangladesh - Increasing Sustainability
Astec in Bangladesh - Increasing Sustainability
Tony Loup
 
Garland_Sustainable_Brochure914
Garland_Sustainable_Brochure914Garland_Sustainable_Brochure914
Garland_Sustainable_Brochure914
Tom Townsend
 
Energy Savings for the London Refrigeration Society
Energy Savings for the London Refrigeration SocietyEnergy Savings for the London Refrigeration Society
Energy Savings for the London Refrigeration Society
Camfil UK
 
CASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCE
CASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCECASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCE
CASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCE
UnivarSC
 
Spotlights_booklet_lo
Spotlights_booklet_loSpotlights_booklet_lo
Spotlights_booklet_lo
Amy Patel
 
Low Energy - Indoor Air Quality for Buildings
Low Energy - Indoor Air Quality for BuildingsLow Energy - Indoor Air Quality for Buildings
Low Energy - Indoor Air Quality for Buildings
Camfil UK
 
Green buildings.docx
Green buildings.docxGreen buildings.docx
Green buildings.docx
abirami232268
 
Volker Wehber, Evonik
Volker Wehber, EvonikVolker Wehber, Evonik
Why Consider a Green Roof?
Why Consider a Green Roof?Why Consider a Green Roof?
Why Consider a Green Roof?
Sustainable Performance Institute
 
Aquatis brochure A4-lowres
Aquatis brochure A4-lowresAquatis brochure A4-lowres
Aquatis brochure A4-lowres
Jean-Christophe Schrotter
 
Deif profile
Deif profileDeif profile
Deif profile
Tuan Anh
 
Usgbc intro
Usgbc introUsgbc intro
Usgbc intro
Krashan Singhal
 
leed_doc_print
leed_doc_printleed_doc_print
leed_doc_print
soludsnake
 

Similar to Office Building Upgrades Filtration Case Study AFP= (20)

Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...
Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...
Air Cleaning System Dynamic V8 for HVAC Systems Carried by Unique Indoor Comf...
 
Cardiff University : AHU - Low Energy Air Filter Case Study
Cardiff University : AHU - Low Energy Air Filter Case StudyCardiff University : AHU - Low Energy Air Filter Case Study
Cardiff University : AHU - Low Energy Air Filter Case Study
 
Comparing griha with breeam for new construction
Comparing griha with breeam for new constructionComparing griha with breeam for new construction
Comparing griha with breeam for new construction
 
AMWAY GRAND Hotel Case Study SSF
AMWAY GRAND Hotel Case Study SSFAMWAY GRAND Hotel Case Study SSF
AMWAY GRAND Hotel Case Study SSF
 
Scalable Hydrogen Energy Platform (SHEP).pdf
Scalable Hydrogen Energy Platform (SHEP).pdfScalable Hydrogen Energy Platform (SHEP).pdf
Scalable Hydrogen Energy Platform (SHEP).pdf
 
Sustainable Aviation - Cleaner, Quieter , Smarter
Sustainable Aviation - Cleaner, Quieter , Smarter  Sustainable Aviation - Cleaner, Quieter , Smarter
Sustainable Aviation - Cleaner, Quieter , Smarter
 
Veolia Hickory Meadows LEED Project Profile | Miron Construction
Veolia Hickory Meadows LEED Project Profile | Miron ConstructionVeolia Hickory Meadows LEED Project Profile | Miron Construction
Veolia Hickory Meadows LEED Project Profile | Miron Construction
 
Astec in Bangladesh - Increasing Sustainability
Astec in Bangladesh - Increasing SustainabilityAstec in Bangladesh - Increasing Sustainability
Astec in Bangladesh - Increasing Sustainability
 
Garland_Sustainable_Brochure914
Garland_Sustainable_Brochure914Garland_Sustainable_Brochure914
Garland_Sustainable_Brochure914
 
Energy Savings for the London Refrigeration Society
Energy Savings for the London Refrigeration SocietyEnergy Savings for the London Refrigeration Society
Energy Savings for the London Refrigeration Society
 
CASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCE
CASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCECASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCE
CASE STUDY - ENVIRONMENTALLY COMPLIANT SURFACE CLEANING WITH MAXIMUM PERFORMANCE
 
Spotlights_booklet_lo
Spotlights_booklet_loSpotlights_booklet_lo
Spotlights_booklet_lo
 
Low Energy - Indoor Air Quality for Buildings
Low Energy - Indoor Air Quality for BuildingsLow Energy - Indoor Air Quality for Buildings
Low Energy - Indoor Air Quality for Buildings
 
Green buildings.docx
Green buildings.docxGreen buildings.docx
Green buildings.docx
 
Volker Wehber, Evonik
Volker Wehber, EvonikVolker Wehber, Evonik
Volker Wehber, Evonik
 
Why Consider a Green Roof?
Why Consider a Green Roof?Why Consider a Green Roof?
Why Consider a Green Roof?
 
Aquatis brochure A4-lowres
Aquatis brochure A4-lowresAquatis brochure A4-lowres
Aquatis brochure A4-lowres
 
Deif profile
Deif profileDeif profile
Deif profile
 
Usgbc intro
Usgbc introUsgbc intro
Usgbc intro
 
leed_doc_print
leed_doc_printleed_doc_print
leed_doc_print
 

Office Building Upgrades Filtration Case Study AFP=

  • 1. T H E W O R L D L E A D E R I N C L E A N A I R S O L U T I O N S CASE STUDY – COMMERCIAL Current Filtration Situation Cushman & Wakefield of Texas has been a loyal AAF International customer for many years. When Cushman & Wakefield began investigating ways to improve its building efficiency at 777 Main Street in 2009, AAF was there to assist with proven filtration solution options. The building at this time utilized MERV 8 PerfectPleat® Ultra filters. In order to obtain a Leadership in Energy and Environmental Design (LEED® ) certification for the building, the plaza would need to upgarde its filtration in order to reach this goal. Sustainable Filtration Rising energy costs and the current economic downturn are increasing the pressure on commercial buildings to cut energy costs and create more sustainable properties. The LEED Green Building Rating System™ , administered by the U.S. Green Building Council, is the nationally accepted benchmark for designing and sustaining green buildings. LEED provides third-party verification that a building is designed and built using strategies aimed at improving performance across all the metrics that matter most: energy savings, water efficiency, CO2 emissions reduction, improved indoor environmental quality, and stewardship of resources and sensitivity to their impacts. LEED provides building owners and operators the framework for identifying and implementing practical and measurable design, construction, operations, and maintenance solutions. Proper air filtration strategies can contribute to credits toward certification. One activity involves increasing the efficiency of the air filtration, thereby reducing the particulate being distributed. The AAF Solution A complete survey was done to find economical solutions to upgrade the efficiency level of the current filtration without a significant impact on the budget. AAF recommended MERV 13 VariCel® M-Pak filters to upgrade efficiency in the large recirculation units inside the building. The dual-density media design of the VariCel M-Pak utilizes the full filtering potential of the media and maximizes dust holding. Maximized dust holding capacity extends the life of the filter and minimizes operating costs. Cushman & Wakefield was presented with AAF’s Life Cycle Valuation (LCV) report comparing the overall costs of the PerfectPleat Ultra filter in combination with the VariCel M-Pak filter, and the VariCel M-Pak filter alone. The most economical outcome was to install VariCel M-Pak filters without the prefilters. No costly fan modifications were required with this choice, and energy savings would be greater. Additionally, AAF recommended MERV 14 DriPak® 2000 filters with no prefilter for the new fresh air intakes that were added on the roof. These fresh air intakes are exposed to lots of moisture, and DriPak 2000 filters will not block off the airflow if they get wet. This also minimized pressure drop across the filter. Office Building Upgrades Filtration - Achieves LEED® Certification; Receives NAFA Clean Air Award BETTER AIR IS OUR BUSINESS® Customer Profile • 777 Main Street: 40-story, Class A office building totaling 954,895 rentable square feet • Located in the heart of downtown Fort Worth • Owned by F7 Sssm LLC and managed by Cushman & Wakefield, Inc. Life Cycle Valuation (LCV) Report Lower Total Cost
  • 2. 9920 Corporate Campus Drive, Suite 2200, Louisville, KY 40223-5690 888.223.2003 Fax 888.223.6500 | www.aafintl.com AAF has a policy of continuous product research and improvement and reserves the right to change design and specifications without notice. ISO Certified Firm AFP-6-103B 08/15 ©2015 AAF International Office Building Upgrades Filtration The Results Cushman & Wakefield decided to run a six month trial on air handlers with the heaviest dirt load in the building. The trial revealed they could get one year of life from the VariCel M-Pak filters without using a prefilter. Over a twelve month period, all interior and exterior air handling units in 777 Main Street were refurbished and all MERV 8 filters were upgraded to MERV 13 VariCel M-Pak filters or MERV 14 DriPak 2000 filters. As a result of the improvements, the particulate matter was reduced 62% in 777 Main Street. The industry assumption for this type of improvement is a 40% reduction in absenteeism, due to a reduction in upper respiratory problems for people who work in the building. 777 Main Street achieved LEED EB certification in 2009. In addition, the building was awarded the National Air Filter Association (NAFA) Clean Air Award for 2010. The purpose of the Clean Air Award is to recognize leadership and excellence in air filtration by selected air filter users, and to promote the National Air Filtration Association and its member companies. Any facility or company that has demonstrated a concerted effort to provide a clear indoor air environment by using proper filtration and has a minimum score of 52 is eligible for the award. 777 Main Street scored an astounding 67. In the past, no more that eight facilities per year nationally are recognized for this accomplishment. VariCel® M-Pak filters installed in recirculation units (top) and DriPak® 2000 filters installed in fresh air intakes (bottom) at 777 Main Street, Fort Worth, TX. 777 Main Street. PerfectPleat® , VariCel® , and DriPak® are registered trademarks of AAF International in the U.S. and other countries.