UL, ULC Listed; FM, CSFM, MAPNET II® and IDNet™ Communicating Devices, 
and MEA (NYC) Approved* Individual Addressable Module (IAM) 4090-9001 
Features 
MAPNET II or IDNet addressable communications 
supply both data and power over a single wire pair 
to provide**: 
• Supervised Class B monitoring of normally open, 
dry contacts 
• Total wiring distance from IAM to supervision 
resistor(s) of up to 500 ft (152 m) 
• Monitored connection is compatible with Simplex 
2081-9044 Overvoltage Protectors for outdoor or 
electrically noisy applications 
Compatible with Simplex: 
• Model Series 4010/4100/4120/4020 fire alarm 
control panels equipped with either IDNet or 
MAPNET II communications 
• Model Series 2120 communicating device 
transponders (CDTs) equipped with MAPNET II 
communications 
Compact, sealed construction: 
• Enclosed design minimizes dust infiltration 
• Mounts in standard single gang electrical box 
• Screw terminals for wiring connections 
• Visible LED flashes to indicate communications 
• Optional covers are available to allow LED to be 
viewed after installation (requires mounting 
bracket, ordered separately) 
Provides current limited monitoring (for use with 
IDNet communications): 
• To monitor tamper switch (trouble) and waterflow 
switch (alarm) on same circuit using one point 
Multiple operation modes are available and are 
selectable at the control panel: 
• Contact closure status can be tracked 
• Momentary contact closure conditions can be 
latched, such as from rate-of-rise heat detectors 
UL listed to Standard 864 
* This product has been approved by the California State Fire Marshal (CSFM) pursuant to 
Section 13144.1 of the California Health and Safety Code. See CSFM Listing 
7300-0026:223 for allowable values and/or conditions concerning material presented in this 
document. It is subject to re-examination, revision, and possible cancellation. Accepted for 
use – City of New York Department of Buildings – MEA35-93E. Additional listings may be 
applicable, contact Simplex for the latest status. 
** MAPNET II and IDNet addressable communications designs are protected by U.S. 
Patent No. 4,796,025. 
Multi-Application Peripherals 
- IDNET IN+ 
+IDNET IN - 
4090-9001 Supervised IAM 
(shown approximately full size) 
Description 
The 4090-9001 is an individual addressable module 
(IAM) with both power and communications supplied by 
a two-wire MAPNET II or IDNet circuit. It provides 
location specific addressability to a single initiating 
device (such as single station smoke detector alarm 
contacts or heat detector contacts) or multiple devices at 
the same location by monitoring normally open dry 
contacts and the wiring to an end-of-line resistor. 
Closure of the monitored contacts initiates an alarm or 
other response as programmed at the fire alarm control 
panel. An open in the monitored circuit wiring will cause 
a trouble to be reported. 
Selections can be made at the control panel to maintain 
the alarm condition if the initiating device contacts are 
momentary, such as from a rate-of-rise heat detector, or to 
track the device contact status (not applicable with 2120 
CDT). 
Current Limited Operation Applications 
For use with IDNet communications only, the 4090-9001 
can sense normal, open circuit, short circuit, and current 
limited conditions. With the proper end-of-line and 
current limiting resistors, dual functions such as tamper 
switch and waterflow switch monitoring can be 
determined and communicated by a single addressable 
point. 
© 2000 Simplex Time Recorder Co. All rights reserved. S4090-0001-4 8/00
Product Selection 
IAM Module 
Model Number Description 
4090-9001 Supervised IAM module 
Optional Trim Plates and Mounting Bracket 
Model Number Description 
4090-9806 Trim plate with LED viewing window, requires 4090-9810 
For semi-flush mounted box 
4090-9807 
mounting bracket, includes mounting screws For surface mounted box 
4090-9810 Mounting bracket, mounts IAM to electrical box and provides screw holes for trim plate, required for 
optional trim plates 
Specifications 
Electrical 
Power and Communications MAPNET II or IDNet, auto selected, 1 address per IAM 
Input Requirements Normally open, dry contacts 
Wire Connections Screw terminals for in/out wiring, 18 to 14 AWG wire 
Supervision Resistor 6.8 kΩ, 1/2 W 
Resistors for Current Limited Operation 
(for use with IDNet communications only ) 1.8 kΩ and 4.7 kΩ, 1/2 W 
NOTE: Refer to installation instructions 
574-331 and field wiring diagrams 
841-804 and 842-073 for additional 
information. 
Wiring Distances 
500 ft (152 m) maximum without protectors 
Distance from IAM to Contacts 
400 ft (122 m) maximum with 2081-9044 Overvoltage Protectors 
Wiring Distance, MAPNET II or IDNet, 2500 ft (762 m) maximum from fire alarm control panel 
per Channel 10,000 ft (3048 m) maximum total wiring distance (including T-Taps) 
Mechanical 
Dimensions 1 9/16” W x 1 3/4” H x 1 1/4” D (40 mm x 44 mm x 32 mm) 
Housing Material Black thermoplastic 
Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation 
Humidity Range Up to 93% RH at 100° F (38° C) 
Simplex Time Recorder Co. 2 S4090-0001-4 8/00
Field wiring shown 
for reference 
LED viewing port 
Single gang electrical 
box 2 1/2" (64mm) 
minimum depth 
(supplied by others) 
Address setting under resealable label 
- IDNET IN + 
+IDNET IN - 
Single gang blank cover plate and mounting screws, for use when 
LED is not required to be externally viewed (supplied by others) 
Mounting Information 
4090-9001 IDNet 
supervised IAM 
Mounting Reference, Single Gang Blank Cover Plate 
4090-9806, Trim plate for 
semi-flush mounted box 
4090-9807, Trim plate for 
surface mounted box 
Optional Trim Plates and Mounting Bracket for Visible LED 
4 1/4" 
(108 mm) 
2 1/2" 
(64 mm) 
2 13/16" 
(72 mm) 
4 1/2" 
Light pipe for (114 mm) 
LED viewing 
NOTE: These mounting plates require mounting bracket 4090-9810. 
4090-9810 Mounting 
bracket, ordered 
separately 
Simplex Time Recorder Co. 3 S4090-0001-4 8/00
S4090-0001-4 8/00 
Simplex, the Simplex logo, MAPNET II, and IDNet are either trademarks or registered trademarks of Simplex Time Recorder Co. 
in the U.S. and/or other countries. 
Westminster, Massachusetts 01441-0001 USA 
visit us on the world wide web at www.simplexnet.com 
All specifications and other information shown were current as of printing and are subject to change without notice.

More Related Content

What's hot

Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specificationsLeviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Alarm Grid
 
Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013
ifm electronic gmbh
 
Leviton vrr15 1 lz product specification bulletin
Leviton vrr15 1 lz product specification bulletinLeviton vrr15 1 lz product specification bulletin
Leviton vrr15 1 lz product specification bulletin
Alarm Grid
 
Leviton vrs15 1 lz installation manual and setup guide
Leviton vrs15 1 lz installation manual and setup guideLeviton vrs15 1 lz installation manual and setup guide
Leviton vrs15 1 lz installation manual and setup guide
Alarm Grid
 
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Maxpromotion
 
Leviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllersLeviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllers
Alarm Grid
 

What's hot (19)

Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
 
Vertx v100 ds_en
Vertx v100 ds_enVertx v100 ds_en
Vertx v100 ds_en
 
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specificationsLeviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
Leviton vrcz4 mr, vrcs4-mr, and vrc52-mr product specifications
 
Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013Ifm Technology for Mining Industries English 2013
Ifm Technology for Mining Industries English 2013
 
Edgereadererp40 ds en
Edgereadererp40 ds enEdgereadererp40 ds en
Edgereadererp40 ds en
 
Amit hart presentation
Amit hart presentationAmit hart presentation
Amit hart presentation
 
Leviton vrr15 1 lz product specification bulletin
Leviton vrr15 1 lz product specification bulletinLeviton vrr15 1 lz product specification bulletin
Leviton vrr15 1 lz product specification bulletin
 
I 9300
I 9300I 9300
I 9300
 
Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!Pepperl + Fuchs' Emerson Global User Exchange highlights!
Pepperl + Fuchs' Emerson Global User Exchange highlights!
 
Leviton vrs15 1 lz installation manual and setup guide
Leviton vrs15 1 lz installation manual and setup guideLeviton vrs15 1 lz installation manual and setup guide
Leviton vrs15 1 lz installation manual and setup guide
 
Edgereaderesrp40 ds en
Edgereaderesrp40 ds enEdgereaderesrp40 ds en
Edgereaderesrp40 ds en
 
Trio tm-50.0 60.0-bcd.00658_en_rev_e
Trio tm-50.0 60.0-bcd.00658_en_rev_eTrio tm-50.0 60.0-bcd.00658_en_rev_e
Trio tm-50.0 60.0-bcd.00658_en_rev_e
 
Yokogawa Field Wireless Solution
Yokogawa Field Wireless SolutionYokogawa Field Wireless Solution
Yokogawa Field Wireless Solution
 
BLH Nobel G5 Tech Manual
BLH Nobel G5 Tech ManualBLH Nobel G5 Tech Manual
BLH Nobel G5 Tech Manual
 
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
Mcb price list_electrical_installations_a_to_z_w.e.f_1st_sep_2016
 
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentationPepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
 
Vertx v200 ds_en
Vertx v200 ds_enVertx v200 ds_en
Vertx v200 ds_en
 
Leviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllersLeviton dimmers, switches and fan speed controllers
Leviton dimmers, switches and fan speed controllers
 
Acb1
Acb1Acb1
Acb1
 

Similar to Modulo dirreccionable

Athens Datacentres And 10 G
Athens Datacentres And 10 GAthens Datacentres And 10 G
Athens Datacentres And 10 G
Gianluca Musetti
 
ES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdfES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdf
eduard10
 

Similar to Modulo dirreccionable (20)

Input Module-4090-0001 - Individual Addressable Modules-4090-9001.pdf
Input Module-4090-0001 - Individual Addressable Modules-4090-9001.pdfInput Module-4090-0001 - Individual Addressable Modules-4090-9001.pdf
Input Module-4090-0001 - Individual Addressable Modules-4090-9001.pdf
 
Fault Isolator Base - 4098-9793.pdf
Fault Isolator Base - 4098-9793.pdfFault Isolator Base - 4098-9793.pdf
Fault Isolator Base - 4098-9793.pdf
 
tac_mn_controllers_MNL10-15-20 2024 .pdf
tac_mn_controllers_MNL10-15-20 2024 .pdftac_mn_controllers_MNL10-15-20 2024 .pdf
tac_mn_controllers_MNL10-15-20 2024 .pdf
 
Add. Manual Station - 9006.pdf
Add. Manual Station - 9006.pdfAdd. Manual Station - 9006.pdf
Add. Manual Station - 9006.pdf
 
4904-0006 - Add. Wall mount Strobe - 4904-9350, 51, 52, 53, 54, 55.pdf
4904-0006 - Add. Wall mount Strobe - 4904-9350, 51, 52, 53, 54, 55.pdf4904-0006 - Add. Wall mount Strobe - 4904-9350, 51, 52, 53, 54, 55.pdf
4904-0006 - Add. Wall mount Strobe - 4904-9350, 51, 52, 53, 54, 55.pdf
 
Horn 49AO-WRF.pdf
Horn 49AO-WRF.pdfHorn 49AO-WRF.pdf
Horn 49AO-WRF.pdf
 
Railroad Industry Connectivity Solutions
Railroad Industry Connectivity SolutionsRailroad Industry Connectivity Solutions
Railroad Industry Connectivity Solutions
 
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
IECS-1116-DI Industrial EtherCAT Slave I/O Module with Isolated 16-ch Digital...
 
Programmable Limit Alarm Trips with Intrinsically-Safe Field Connections
Programmable Limit Alarm Trips with Intrinsically-Safe Field ConnectionsProgrammable Limit Alarm Trips with Intrinsically-Safe Field Connections
Programmable Limit Alarm Trips with Intrinsically-Safe Field Connections
 
ComNet FDXT1E1M1A Data Sheet
ComNet FDXT1E1M1A Data SheetComNet FDXT1E1M1A Data Sheet
ComNet FDXT1E1M1A Data Sheet
 
ComNet FDC8ISOTM1 Data Sheet
ComNet FDC8ISOTM1 Data SheetComNet FDC8ISOTM1 Data Sheet
ComNet FDC8ISOTM1 Data Sheet
 
Littelfuse Smart Thermostat Capabilities
Littelfuse Smart Thermostat CapabilitiesLittelfuse Smart Thermostat Capabilities
Littelfuse Smart Thermostat Capabilities
 
Building Automation,Networking & Communication Presentation by LVS 2022.pdf
Building Automation,Networking & Communication Presentation by LVS 2022.pdfBuilding Automation,Networking & Communication Presentation by LVS 2022.pdf
Building Automation,Networking & Communication Presentation by LVS 2022.pdf
 
Athens Datacentres And 10 G
Athens Datacentres And 10 GAthens Datacentres And 10 G
Athens Datacentres And 10 G
 
Bezprzewodowa komunikacja w procesie - produkty i rozwiązania
Bezprzewodowa komunikacja w procesie - produkty i rozwiązaniaBezprzewodowa komunikacja w procesie - produkty i rozwiązania
Bezprzewodowa komunikacja w procesie - produkty i rozwiązania
 
Signal Fire Wireless Telemetry Catalog
Signal Fire Wireless Telemetry CatalogSignal Fire Wireless Telemetry Catalog
Signal Fire Wireless Telemetry Catalog
 
ABB-TRIO-TM-50.0-400-POWER-MODULE
ABB-TRIO-TM-50.0-400-POWER-MODULEABB-TRIO-TM-50.0-400-POWER-MODULE
ABB-TRIO-TM-50.0-400-POWER-MODULE
 
ABB Terra AC Wallbox EV Charger
ABB Terra AC Wallbox EV ChargerABB Terra AC Wallbox EV Charger
ABB Terra AC Wallbox EV Charger
 
Littelfuse Solutions for Security Cameras and Video Doorbells
Littelfuse Solutions for Security Cameras and Video DoorbellsLittelfuse Solutions for Security Cameras and Video Doorbells
Littelfuse Solutions for Security Cameras and Video Doorbells
 
ES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdfES-200X Ficha técnica.pdf
ES-200X Ficha técnica.pdf
 

Modulo dirreccionable

  • 1. UL, ULC Listed; FM, CSFM, MAPNET II® and IDNet™ Communicating Devices, and MEA (NYC) Approved* Individual Addressable Module (IAM) 4090-9001 Features MAPNET II or IDNet addressable communications supply both data and power over a single wire pair to provide**: • Supervised Class B monitoring of normally open, dry contacts • Total wiring distance from IAM to supervision resistor(s) of up to 500 ft (152 m) • Monitored connection is compatible with Simplex 2081-9044 Overvoltage Protectors for outdoor or electrically noisy applications Compatible with Simplex: • Model Series 4010/4100/4120/4020 fire alarm control panels equipped with either IDNet or MAPNET II communications • Model Series 2120 communicating device transponders (CDTs) equipped with MAPNET II communications Compact, sealed construction: • Enclosed design minimizes dust infiltration • Mounts in standard single gang electrical box • Screw terminals for wiring connections • Visible LED flashes to indicate communications • Optional covers are available to allow LED to be viewed after installation (requires mounting bracket, ordered separately) Provides current limited monitoring (for use with IDNet communications): • To monitor tamper switch (trouble) and waterflow switch (alarm) on same circuit using one point Multiple operation modes are available and are selectable at the control panel: • Contact closure status can be tracked • Momentary contact closure conditions can be latched, such as from rate-of-rise heat detectors UL listed to Standard 864 * This product has been approved by the California State Fire Marshal (CSFM) pursuant to Section 13144.1 of the California Health and Safety Code. See CSFM Listing 7300-0026:223 for allowable values and/or conditions concerning material presented in this document. It is subject to re-examination, revision, and possible cancellation. Accepted for use – City of New York Department of Buildings – MEA35-93E. Additional listings may be applicable, contact Simplex for the latest status. ** MAPNET II and IDNet addressable communications designs are protected by U.S. Patent No. 4,796,025. Multi-Application Peripherals - IDNET IN+ +IDNET IN - 4090-9001 Supervised IAM (shown approximately full size) Description The 4090-9001 is an individual addressable module (IAM) with both power and communications supplied by a two-wire MAPNET II or IDNet circuit. It provides location specific addressability to a single initiating device (such as single station smoke detector alarm contacts or heat detector contacts) or multiple devices at the same location by monitoring normally open dry contacts and the wiring to an end-of-line resistor. Closure of the monitored contacts initiates an alarm or other response as programmed at the fire alarm control panel. An open in the monitored circuit wiring will cause a trouble to be reported. Selections can be made at the control panel to maintain the alarm condition if the initiating device contacts are momentary, such as from a rate-of-rise heat detector, or to track the device contact status (not applicable with 2120 CDT). Current Limited Operation Applications For use with IDNet communications only, the 4090-9001 can sense normal, open circuit, short circuit, and current limited conditions. With the proper end-of-line and current limiting resistors, dual functions such as tamper switch and waterflow switch monitoring can be determined and communicated by a single addressable point. © 2000 Simplex Time Recorder Co. All rights reserved. S4090-0001-4 8/00
  • 2. Product Selection IAM Module Model Number Description 4090-9001 Supervised IAM module Optional Trim Plates and Mounting Bracket Model Number Description 4090-9806 Trim plate with LED viewing window, requires 4090-9810 For semi-flush mounted box 4090-9807 mounting bracket, includes mounting screws For surface mounted box 4090-9810 Mounting bracket, mounts IAM to electrical box and provides screw holes for trim plate, required for optional trim plates Specifications Electrical Power and Communications MAPNET II or IDNet, auto selected, 1 address per IAM Input Requirements Normally open, dry contacts Wire Connections Screw terminals for in/out wiring, 18 to 14 AWG wire Supervision Resistor 6.8 kΩ, 1/2 W Resistors for Current Limited Operation (for use with IDNet communications only ) 1.8 kΩ and 4.7 kΩ, 1/2 W NOTE: Refer to installation instructions 574-331 and field wiring diagrams 841-804 and 842-073 for additional information. Wiring Distances 500 ft (152 m) maximum without protectors Distance from IAM to Contacts 400 ft (122 m) maximum with 2081-9044 Overvoltage Protectors Wiring Distance, MAPNET II or IDNet, 2500 ft (762 m) maximum from fire alarm control panel per Channel 10,000 ft (3048 m) maximum total wiring distance (including T-Taps) Mechanical Dimensions 1 9/16” W x 1 3/4” H x 1 1/4” D (40 mm x 44 mm x 32 mm) Housing Material Black thermoplastic Temperature Range 32° to 120° F (0° to 49° C) intended for indoor operation Humidity Range Up to 93% RH at 100° F (38° C) Simplex Time Recorder Co. 2 S4090-0001-4 8/00
  • 3. Field wiring shown for reference LED viewing port Single gang electrical box 2 1/2" (64mm) minimum depth (supplied by others) Address setting under resealable label - IDNET IN + +IDNET IN - Single gang blank cover plate and mounting screws, for use when LED is not required to be externally viewed (supplied by others) Mounting Information 4090-9001 IDNet supervised IAM Mounting Reference, Single Gang Blank Cover Plate 4090-9806, Trim plate for semi-flush mounted box 4090-9807, Trim plate for surface mounted box Optional Trim Plates and Mounting Bracket for Visible LED 4 1/4" (108 mm) 2 1/2" (64 mm) 2 13/16" (72 mm) 4 1/2" Light pipe for (114 mm) LED viewing NOTE: These mounting plates require mounting bracket 4090-9810. 4090-9810 Mounting bracket, ordered separately Simplex Time Recorder Co. 3 S4090-0001-4 8/00
  • 4. S4090-0001-4 8/00 Simplex, the Simplex logo, MAPNET II, and IDNet are either trademarks or registered trademarks of Simplex Time Recorder Co. in the U.S. and/or other countries. Westminster, Massachusetts 01441-0001 USA visit us on the world wide web at www.simplexnet.com All specifications and other information shown were current as of printing and are subject to change without notice.