Catalogue
Surge Protection Devices
SALTEK®
is a leading Czech company specialised in the development and production of surge protection devices.
It offers a broad range of lightning current arresters and surge protection type 1–3 according to EN 61643-11 (or B, C
and D according to E DIN VDE 0675-6) and surge protection for information technology, measurement and control and
telecommunications.
SALTEK®
products provide protection against the lightning and technological overvoltage and thereby rise the safety and
trouble-free operation of the technologies, machinery and appliances at the industry, telecommunications, data centers, office
buildings even in ordinary houses.
SALTEK®
was founded in 1995. Successful business activities abroad, in many countries of three continents, are provided by
subsidiaries SALTEK®
TRADE.
The principle of dynamic company expansion consists in its own product development. A team of experienced development
engineers works in test development laboratory with unique devices and technologies. The sophisticated materials, design
processes, technologies and measurement methods are used for the development of SALTEK®
products. Production is
equipped with automatic and robotized assembly lines.
Special attention is focused on the quality of products. SALTEK®
has implemented Integrated Management System IMS,
according to international standards, which consists of Quality management system under EN ISO 9001, Environmental
protection management under EN ISO 14001 and Health and safety management system under OHSAS 18001.
System IMS is annually verified by external auditing company TÜV NORD Czech.
SALTEK®
is focused on quality, but also to design of products. Line of surge protection devices with unique color coding
has been awarded a design prize Red Dot®
2014.
SALTEK
Choose from our comprehensive range of surge
protection devices:
1
SPD type 1 – lightning current arresters
SPD type 1 and 2 – B+C combined arresters
SPD type 2 – surge arresters
SPD type 3 – surge arresters
SPD type 3 – surge protective devices with a RFI filter
SPD type 3 – surge protective devices for additional mounting
Surge separation inductor
SPD for photovoltaic systems
Surge arresters for measurement and control,
electronic security systems, EPS and telecommunications
Surge arresters for Ethernet and video lines
Lightning arresters and surge arresters for coaxial lines
Accessories
page 16
page 19
page 37
page 47
page 50
page 60
page 63
page 65
page 74
page 95
page 103
page 108
1. Introduction – Legislative
The use of modern sophisticated equipment,
consumer electronics and control systems
places high demands on their electromagnetic
compatibility. Modern electronic control
systems provided with circuits with a very high
integration level are becoming more and more
sensitive to electromagnetic disturbance and
overvoltage. The installation of surge protections
according to effective legal standards will
reduce the danger of their being damaged to a
minimum.
Technical designs are defined by standards
harmonised with EU standards:
a) Protective bonding to the same potential
including the conductor cross section for the
main and additional bonding is defined by
standards EN 50310 ed. 2. , IEC 60364-5-54,
IEC 60364-4-41
b) Lightning protection is specified in the
EN 62305 collection of new standards,
harmonised with European standards.
EN 62305 – 1 deals with general principles.
Lightning
protection
level
Maximum lightning
parameter according to LPL
LPL First short discharge
LPL I 200 kA
LPL II 150 kA
LPL III 100 kA
LPL IV 100 kA
IEC/EN 62305 – 2 – deals with the risk
assessment for buildings or engineering
networks struck by lightning.
IEC/EN 62305 – 3 – deals with the proposal
for external lightning protection (lightning
conductor).
IEC/EN 62305 – 4 – deals with protective
measures resulting in the reduction of failures
of electrical and electronic systems inside the
building (zone protection)
c) Classification of protections is set forth in
standard EN 61643-11.
Devices are classified into three basic categories:
SPD type 1 – lightning current arresters
SPD type 2 – surge arresters
SPD type 3 – surge arresters
d) Classification of low-voltage distribution
into impulse resistance categories, including
specification of the maximum allowed
overvoltage is determined in standard
EN 60664-1
Protection against lightning and overvoltage
Rated impulse for equipment (acc. to EN 60664-1) or Impulse-withstand voltage.
Lightning protection zones
The standard EN 62305-4 defines lightning
protection zones LPZ in view of the direct and
indirect (electromagnetic pulse – LEMP) lightning
effect:
LPZ 0A – free area (possibility of a direct
lightning strike, non-attenuated LEMP)
LPZ 0B – lightning conductor receiver
protection area (direct lightning strike
protection, non-attenuated LEMP)
LPZ 1 – inside a building (direct lightning strike
is eliminated, attenuated LEMP – depending
upon shielding)
LPZ 2 – inside a room – e.g. a server room with
a conductive floor, FeAl floors and wall lining
(further attenuation of LEMP in connection with
a higher shielding level)
LPZ 3 – inside a metal box (e.g. 19“ RACK)
Lightning and surge protection
Example of main and additional bonding
telephone cable
gas pipeline
water pipeline
base ground
main protective bonding bar
2
Insulation coordination
lift
flats appliance
appliances
Protection against lightning and overvoltage
2. Connection of surge protection devices in networks
TN-S
3
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
TN-C-S
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
TN-C
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
TT
SPD in 3+1 mode SPD in 4+0 mode
SPD in 3+1 mode SPD in 4+0 mode
SPD in 3+0 mode
SPD in 3+1 mode
Protection against lightning and overvoltage
4
3. SPD dimensioning and their use
Application of SALTEK SPD type 1
EN 62305
Location of SPD type 1: at the boundary of LPZ0 and LPZ1 zones
in main distribution board
LPL Lightning Total SPD
I. to 200 kA 100 kA
Conditions met by:
FLP-SG50 V(S)/1
FLP-B+C MAXI V(S)/1
- large industrial facilities
- structures of special importance
- technological facilities
- administrative structures
- administrative structures
- civic amenities
- family houses
- near transformer stations
LPL Lightning Total SPD
III. to 100 kA 50 kA
Conditions met by:
FLP-12,5 V/1(S) - family houses w/o down conductor system
With a cable connector in the housing and in the
LPS III class
- structures in LPS IV class, i.e. structures and halls
without persons and interior equipment, structures
only with heavy current wiring
- on LW earthing supply cables to the structure
where the connection is not directly to the public
distribution network (i.e. interconnection between
2 structures)
- to sub-distribution boards within the structure,
With a cable length from the last SPD of over 50 m
Aplication of SALTEK SPD type 2
EN 62305
Location of SPD type 2: at the boundary of LPZ1 and LPZ2 zones
or sub-distribution board
Conditions met by:
SLP-xxx	 - all types of wiring
	 - type of network (TN, IT, T T)
	 - connection method
	 - nominal voltage
Application of SALTEK SPD type 3
EN 62305
Location of SPD type 3: at the boundary of LPZ2 and LPZ3 zones
(technology)
Conditions met by:
DA-275
(with DIN bar)
- all types of wiring (if the equipment is in the
clamp or distribution board)
DA-275 …, CZ… - all types of wiring (sockets with overvoltage
protection at the shortest possible distance from
the appliance)
xxx-OVERDRIVE - all types of wiring
adapters for plugs with overvoltage protection
4. Principle of SPD backing
For the design of an SPD back-up, it is important if we consider the protection priority principle, found in most installations, or the supply priority principle.
Example of an SPD FLP-B+C MAXI V back-up in different supply networks.
The catalogue value of the maximum back-up for FLP-B+C MAXI V is 250 A, for a“V”connection it is 125 A.
Connection in parallel	 Connection in„V“
TN-C	
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up:  1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up:  1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up:  1,5 kV
F1 ≤ 125 A
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up:  1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up:  1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up:  1,5 kV
F1  250 A → F2
F1 ≤ 250 A → F2
F1  125 A
F1 ≤ 125 A
×
5
Protection against lightning and overvoltage
5. Principles for positioning and connecting of lightning and surge arresters
Surge protection devices and lightning current arresters cannot be positioned in the distribution board at random. It should be noted that protection
should be located in the closest proximity to the entry feed cable of the distribution board to minimize the area of the induction loop, see the image below.
Examples of SPDs located in a distribution board.
overhead, PEN (PE) at the bottom overhead, PEN (PE) at the top bottom supply, PEN (PE) at the bottom bottom supply, PEN (PE) at the top
Another important condition for connecting the SPD is to minimize the impedance of connecting conductors. Stranded conductors or strip lines are
preferentially used for connecting SPD type 1. It is also important that the length of the connecting conductors is as small as possible – see IEC 60364-5-534
(the total length of connecting conductors must not exceed 1 m). The cross-section of the connecting conductors should be as large as possible – maximum
up to the cross-section according to the type of connector. In SPD type 1 (lightning arresters) the connecting conductors are an integral part of the main
bonding – as determined by the IEC60364-4-41 standard, while minimum cross-sections of the connecting conductors are specified in IEC60364-5-54.
If SPDs are located in circuits where residual current devices are installed, the SPD should be positioned before the residual current device (not in the
residual current device circuit), to prevent spontaneous overload tripping of the RCD affected by surge arresters or lightning current arresters.
Should an overvoltage protection be located in the residual current devices circuit, RCD type S or G should be used. Even in this case it should be noted that
the resistance of these residual current devices is not high (5 to 8 kA in wave 8/20 μs) which makes it impossible to use any SPD in the circuit of the residual
current device. If you want to prevent a residual current device type S or G responding to surge protection by overload tripping, only a protection SPD type
3 can be used in the circuit of the residual current device.
Example of SPD FLP-12,5 V back-up in different supply networks.
The catalogue value of the maximum back-up for FLP-12,5 V is F2 =160 A.
F2’– the SPD back-up value established by the calculation
TN-C	
PEN
PEN
FLP-12,5Včervená
porucha
red
defect
SPDT1T2
FLP-12,5Včervená
porucha
red
defect
SPDT1T2
FLP-12,5Včervená
porucha
red
defect
SPDT1T2
L1 L2 L3
L3L2L1
F2 = 160 A
F1  160 A
≥ 160 A → F2
6
6. SPD dimensioning
Dimensioning is only provided for SPD type 1. The basis for that is the calculation of the lightning protection level (LPL) for the down conductor (LPS).
The table below is taken from CLC/TS 61643-12 and shows the minimum value of the current withstand per pole according to the lightning protection level
(LPL) structure classification.
If LPL is not known, the worst
case shall be answered LV system
LPL
Maximum
current for the
LPL
No. of
conductors
(n)
TT TN-C TN-S
IT
w/o neutral
conductor
IT
with neutral
Connection mode Connection mode Connection mode
CT1 CT2 CT1 CT2 CT1 CT2
L-PE
N-PE L-N N-PE L-PEN
L-PE
N-PE L-N N-PE L-PE L-N N-PE
1
or
unknown
200 kA
Iimp (kA)
5 N/A N/A N/A N/A 20,0 20,0 80,0 N/A N/A N/A
4 25,0 25,0 100,0 25,0 N/A N/A N/A N/A 25,0 100,0
3 N/A N/A N/A N/A 33,3 33,3 66,7 33,3 N/A N/A
2 50,0 50,0 100,0 50,0 N/A N/A N/A N/A 50,0 100,0
2 150 kA
Iimp (kA)
5 N/A N/A N/A N/A 15,0 15,0 60,0 N/A N/A N/A
4 18,8 18,8 75,0 18,8 N/A N/A N/A N/A 18,8 75,0
3 N/A N/A N/A N/A 25,0 25,0 50,0 25,0 N/A N/A
2 37,5 37,5 75,0 37,5 N/A N/A N/A N/A 37,5 75,0
3 or 4 100 kA
Iimp (kA)
5 N/A N/A N/A N/A 10,0 10,0 40,0 N/A N/A N/A
4 12,5 12,5 50,0 12,5 N/A N/A N/A N/A 12,5 50,0
3 N/A N/A N/A N/A 16,7 16,7 33,3 16,7 N/A N/A
2 25,0 25,0 50,0 25,0 N/A N/A N/A N/A 25,0 50,0
Comment: CT1 – connection of an SPD in the X+0 mode; CT2 – connection of an SPD in the X+1mode
CT1 – (TN-C) 3+0 CT1 – (TN-S) 4+0 CT2 (TT or TNS) 3+1
Protection against lightning and overvoltage
7
Protection against lightning and overvoltage
7. Reducing overvoltage using LPZ zones
The principle of reducing overvoltage using zones lies in the progressive reduction of the overvoltage level to a safe value that will not damage
the specific equipment or technology. To obtain a safe overvoltage value, the whole structure is divided into individual zones and an SPD is installed
at the boundary between the zones..
*F3
Podružný rozváděč (1)
SPD typ 2
SPD type 2
SPD typ 2
Vstupní část
instalace
L1
L2
L3
N
PE
F1
RCD
Hlavní zemní přípojnice
Externíochranaprotiblesku
Hlavní rozváděč
SPD typ 1 nebo 1+2
Podružný rozváděč (2)
SPD typ 2
Jemná ochrana
SPD typ 3
63A
16A
16A
LPZ 0 LPZ 2LPZ 1 LPZ 2
Lokální zemní přípojnice Lokální zemní přípojnice
*F4*F2
LPZ 2
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Vstupní část
instalace
L1
L2
L3
PEN
F1
Hlavní rozváděč
SPD typ 1 nebo 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD typ 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Podružný rozváděč
*F4
Fine protection
63A
16A
16A
Jemná ochrana
63A
16A
16A
equipment
* back-up of SPD – see page.7
LPZ 0A
LPZ 0BLPZ 0B
LPZ 0A
T2
T1
(T1+T2)LPZ 1
T3
T3
T3
LPZ 1
T3
T3
T3
T3
T1
Protection against lightning and overvoltage
Examples of SPD applications
Modern family houses feature more and more electronic equipment. If the owner of the structure wants to watch TV, be in contact with the world via the
Internet, control the heating in the structure automatically, use various electronic equipment without any trouble, it is necessary to protect such equipment
against atmospheric events. Lightning strikes hitting the structure or near the structure and overvoltage in the mains can destroy or damage such electronic
devices or otherwise make use of such sensitive appliances uncomfortable.
Internal protection against lightning and overvoltage must be considered as an integrated system. For most family houses it is OK to install SPD type 1 and
2 at the line entry in the structure (the main distribution board where the circuit breakers for the whole house are located), i.e. FLP-B+C MAXI V(S)/3 for the
wiring connected in TN-C or TN-C-S, or FLP-B+C MAXI V(S)/4 for the wiring in the TN-S network. For sensitive appliances inside the structure, it is sufficient to
use overvoltage protection - SPD type 3, in combination with respective data protection.
It should further be noted that antenna down conductors at the structure entry must also be considered. For such cases, we use the FX-090 F75 T current
arrester.
If the structure has ESS, EPS, or electronics to control the heating system, overvoltage protection SPD type 3 with vf filter type DA-275 DF 6 will be used to
protect the supply 230 V AC, which will be installed in close proximity to the protected equipment.
If the structure has photovoltaic panels installed on the roof, you need to protect the panels as well as the DC/AC inverter. Protection for photovoltaic
equipment, e.g. the SLP-PV500 V/U type, is used to protect the DC part.
The following examples show various options for connecting the structure to the distribution network.
8
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
DA-275 A CZ-275 A
T3 T3 T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
T1 T2
Family houses
❶ A family house in a built-up area or a detached structure
	 with or without a down conductor and external line on posts
❷ A family house in a built-up area without a down conductor and
cable connection
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
DA-275 A CZ-275 A
T3 T3 T2
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
9
Protection against lightning and overvoltage
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
T1 T2
Terraced houses
❸ Terrace houses with a common down conductor and external line
❹ Terrace houses with a common down conductor and cable connection
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
DA-275 A
DA-275 A
CZ-275 A
CZ-275 A
T3
T3
T3
T3
T2
T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
10
Protection against lightning and overvoltage
T1 T2T
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
or SLP-275 V/4
T2
TN-C – SLP-275 V/1
TN-C-S – SLP-275 V/1
TN-S – SLP-275 V/1+1
T2
DA-275 A
T3
CZ-275 A
T3
T1 T2T
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
TN-C – FLP-12,5 V/1
TN-C-S – FLP-12,5 V/1
TN-S – FLP-12,5 V/2
T1 T2
DA-275 A
CZ-275 A
T3
T3
Blocks of flats
❺ Blocks of flats with a cable connection without the possibility to install SPD type 1 in the unmeasured part
❻ Blocks of flats with a cable connection with the possibility to install SPD type 1 in the unmeasured part
11
Protection against lightning and overvoltage
❼ Administrative buildings
DA-275 A
T3
CZ-275 A
T3
or
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
T2
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
T2
T1 T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
Remember
protection of data, signal
and communication lines
see page 72 -73
Protection against lightning and overvoltage
12
❽ Administrative and industrial structures
T1 T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/4
T2
DA-275 A T3
CZ-275 A
T3
nebo
TN-S – DA-275 DF25
T3
TN-S – DA-275 DF16
T3
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/4
T2
Protection against lightning and overvoltage
13
T1
TN-C – 3 pcs FLP-SG50 V(S)
TN-C-S – 3 pcs FLP-SG50 V(S)
TN-S – 4 pcs FLP-SG50 V(S)
TN-S – DA-275 V/3+1
T3
TN-S – SLP-275 V/3+1
T2
TN-S – DA-275 V/3+1
T3
TN-S – DA-275 DF16
T3
TN-S – DA-275 DF25
T3
TN-S – SLP-275 V/3+1
T2
TN-S – SLP-275 V/3+1
T2
TN-S – FLP-12,5 V/3+1
T1 T2
Remember
protection of data, signal
and communication lines
see page 72 -73
14
SPD SALTEK application in LV distribution networks
Type of structure system main distribution board (in the structure)
sub-distribution board
(in the same structure)
close to the equipment
Family houses, administrative
buildings, technologic units,
industrial structures
3-phase TN-C FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 distance  10 m
SLP-275 V/3(S)
distance  5 m
overvoltage protection
to DIN rail:
DA-275 V/1(S)+1 (to 63 A)
DA-275 V/3(S)+1 (to 63 A)
DA-275 DJ (to 16 A)
overvoltage protection to a
DIN rail with a vf filter
DA-275 DFx (S)
(x = 2, 6, 10, 16 A)
DA-275 DF 25 for 25 A
DA-275 DFIx
(x = 1, 6, 10, 16 A)
RACK-PROTECTOR
multiple sockets to
19“stands
CZ-275 A, DA-275 CZS
DA-275 A, DA-275 S
for additional assembly to
the sockets and appliances
sockets with overvoltage
protection (ABB)
XX-OVERDRIVE
socket adapters
distance  5 m
place before the
overvoltage protection
RTO-xx
(xx – rated current
16, 35 or 63 A)
Number according to the
connection type
1-phase TN-C
1x RTO-xx
1-phase TN-S
2x RTO-xx
3-phase TN-C
3x RTO-xx
3-phase TN-S
4x RTO-xx
distance  50 m
FLP-12,5 V/3(S)
distance  100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3
(also with terminals to the equipment)
distance  10 m
SLP-275 V/3(S)
distance  50 m
FLP-12,5 V/3(S)
distance  100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
3-phase TN-S FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4
FLP-25-T1-VS/4, FLP-25-T1-V/4
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4
(also with terminals to the equipment)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
3-phase TN-C-S FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3
FLP-25-T1-VS/3, FLP-25-T1-V/3
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3
(also with terminals to the equipment)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
Blocks of flats with 12 or more
apartments (SPD located in the
apart. Distr. boards)
3-phase TN-C FLP-12,5 V/3(S)
3-phase TN-S FLP-12,5 V/4(S)
3-phase TN-C-S division in the apartment distr. board FLP-12,5 V/3(S)
1-phase TN-C FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1
1-phase TN-S FLP-12,5 V/2(S)
Demanding applications
(structures – operations clas-
sified at the risk of explosion,
chemical plants…, structures of
a very high importance)
3-phase TN-C 3× FLP-SG50 V(S)/1
with terminals to the equipment
3× FLP-SG50 V(S)/1 + 1× SLP-275 V/3(S)
distance  10 m
1× SLP-275 V/3(S)
distance  10 m
SLP-275 V/3(S)
distance  50 m
FLP-12,5 V/3(S)
distance  100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
3-phase TN-S 4× FLP-SG50 V(S)/1
with terminals to the equipment
4× FLP-SG50 V(S)/1 + 1× SLP-275 V/4(S)
distance  10 m
1× SLP-275 V/4(S)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
3-phase TN-C-S division in the main distribution board
3× FLP-SG50 V(S)/1
with terminals to the equipment
3× FLP-SG50 V(S)/1 + 1× SLP-275 V/4(S)
distance  10 m
1× SLP-385 V/4(S)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
15
SPD SALTEK application in LV distribution networks
Type of structure system main distribution board (in the structure)
sub-distribution board
(in the same structure)
close to the equipment
Structures equipped with ESE
(active down conductor)
3-phase TN-C 3x FLP-SG50 V(S)/1 distance  10 m
SLP-275 V/3(S)
distance  5 m
overvoltage protection
to DIN rail:
DA-275 V/1(S)+1 (to 63 A)
DA-275 V/3(S)+1 (to 63 A)
DA-275 DJ (to 16 A)
overvoltage protection to
DIN rail with vf filter:
DA-275 DFx (S)
(x = 2, 6, 10, 16 A)
DA-275 DF 25 for 25 A
DA-275 DFIx
(x = 1, 6, 10, 16 A)
RACK-PROTECTOR
multiple sockets for
19“ stands
CZ-275 A, DA-275 CZS
DA-275 A, DA-275 S
For additional mounting to
sockets and appliances
Sockets with overvoltage
protection (ABB)
XX-OVERDRIVE
Socket adapters
distance  5 m
SPD back-up
RTO-xx
(xx – rated current
16, 35 or 63 A)
Number according to the
connection type
1-phase TN-C
1x RTO-xx
1-phase TN-S
2x RTO-xx
3-phase TN-C
3x RTO-xx
3-phase TN-S
4x RTO-xx
distance  10 m
SLP-275 V/3(S)
distance  50 m
FLP-12,5 V/3(S)
distance  100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
also with terminals to the equipment
3x FLP-SG50 V(S)/1 + SLP-275 V/3(S)
distance  10 m
SLP-275 V/3(S)
distance  50 m
FLP-12,5 V/3(S)
distance  100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
3-phase TN-S 4x FLP-SG50 V(S)/1 distance  10 m
SLP-275 V/4(S)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
also with terminals to the equipment
4x FLP-SG50 V(S)/1 + SLP-275 V/4(S)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
3-phase TN-C-S 3x FLP-SG50 V(S)/1 distance  10 m
SLP-275 V/4(S)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
also with terminals to the equipment
3x FLP-SG50 V(S)/1 + SLP-275 V/3(S)
distance  10 m
SLP-275 V/4(S)
distance  50 m
FLP-12,5 V/4(S)
distance  100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
Technology with 1-phase
connection
1-phase TN-C FLP-SG50 V(S)/1
with terminals to the equipment
FLP-SG50 V(S)/1 + SLP-275 V/1(S)
distance  10 m
SLP-275 V/1(S)
distance  10 m
SLP-275 V/1(S)
distance  50 m
FLP-12,5 V/1(S)
distance  100 m
FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1
1-phase TN-S 2× FLP-SG50 V(S)/1
with terminals to the equipment
2× FLP-SG50 V(S)/1 + 1× SLP-275 V/2(S)
distance  10 m
1× SLP-275 V/2(S)
distance  10 m
1× SLP-275 V/2(S)
distance  50 m
1× FLP-12,5 V/2(S)
distance  100 m
FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2
1-phase TN-C-S Division in the main distribution board
FLP-SG50 V(S)/1
with terminals to the equipment
FLP-SG50 V(S)/1 + SLP-275 V/1(S)
distance  10 m
1× SLP-275 V/2(S)
distance  10 m
1× SLP-275 V/2(S)
distance  50 m
1× FLP-12,5 V/2(S)
distance  100 m
FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2
FLP-SG50 V/1
FLP-SG50 VS/1
SPD type 1 – lightning current arrester
Encapsulated high-performance spark gap with replaceable
module, visual fault signalling
To be installed in low-voltage distributions at the boundary of
LPZ 0A and LPZ 1 zones to prevent overvoltage effects of direct
or indirect lightning strikes in the most demanding applications
in the heavy and chemicals industry, power stations, etc.
Remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
connection
of signalization
terminal
Lightning Current Arresters
16
FLP-SG50 VS/1
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 255 V AC
Nominal discharge current (8/20 μs) In 50 kA
Lightning impulse current (10/350 μs) Iimp 50 kA
Voltage protection level Up 2,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi 50 kA
Nominal short circuit current ISCCR 50 kArms
Maximum overcurrent protection 315 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
TOV voltage UT 335 V/5 sec.
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard EN 61643-11:2012
Ordering number
FLP-SG50 V/1 8595090540540
FLP-SG50 VS/1 8595090540533
Technical data
3666
45
90
9
15
L/N( )
L/N()
(L/N)
(L/N)
Lightning Current Arresters
SPD type 1 – lightning current arrester
N-PE module, replaceable module
To be installed in low-voltage distributions at the boundary of
LPZ 0A–LPZ 1 zones and higher to prevent overvoltage effects of
direct or indirect lightning strikes for the connection of SPD type
1 in the mode 1+1.
Dimension drawing Basic circuit diagram
FLP-A50N VS/NPE
Technical data
FLP-A50N VS/NPE
Nominal voltage Un —
Maximum operating voltage Uc 255V AC
Nominal discharge current (8/20 μs) In 50 kA
Maximum discharge current (8/20 μs) Imax 100 kA
Lightning impulse current (10/350 μs) Iimp 50 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Abilitytoindependentlyswitchoffthefollowingcurrent Ifi 100 A
Short-circuitproofatmaximumovercurrentprotection —
Maximum overcurrent protection —
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication no
Remote indication * potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090535737
* Remote signalling of N-PE module shows the presence of the replaceable module
17
90
45
66 36
9
15
N( )
N()
(N)
(N) connection
of signalization
terminal
Lightning Current Arresters
SPD type 1 – lightning current arrester
N-PE module, replaceable module
To be installed in low-voltage distributions at the boundary of
LPZ 0A and LPZ 1 zones to prevent overvoltage effects of direct or
indirect lightning strikes for the connection
of SPD type 1 in the mode 3+1.
Dimension drawing Basic circuit diagram
FLP-A100N VS/NPE
Technical data
FLP-A100N VS/NPE
Nominal voltage Un —
Maximum operating voltage Uc 255V AC
Nominal discharge current (8/20 μs)/pole In 100 kA
Maximum discharge current (8/20 μs) Imax 100 kA
Lighting impulse current (10/350 μs)/pole Iimp 100 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Abilitytoindependentlyswitchoffthefollowingcurrent Ifi 100 A
Short-circuit proof at maximum overcurrent protection —
Maximum overcurrent protection —
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication no
Remote indication * potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090535744
* Remote signalling of N-PE module shows the presence of the replaceable module
18
90
45
66 36
9
15
N( )
N()
(N)
(N) connection
of signalization
terminal
Lightning Current Arresters
FLP-B+C MAXI V/1
FLP-B+C MAXI VS/1
Dimension drawing Basic circuit diagram
SPD type 1 and type 2
versatile single-pole arrester
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage
(230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect
lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1
(or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA
(10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow
current, no leakage current and low residual voltage.
Remote status signalling contact – version„S“.
FLP-B+C MAXI VS/1
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs) In 30 kA
Maximum discharge current (8/20 μs) Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG : 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/1 8595090550914
FLP-B+C MAXI VS/1 8595090535331
connection
of signalization
terminal
19
3666
45
90
9
15
(L/N)
L/N( )
L/N()
(L/N)
Technical data
SPD type 1 and type 2
2-pole (1+NPE) arrester for single phase TT (TNS) networks
Total Iimp = 50 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of
low-voltage (230/400 V AC) networks and connected appliances against surge voltages
due to direct or indirect lightning strikes in the concept of zone lightning protection at
the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT)
rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven
technology guarantee no follow current, no leakage current and low residual voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 260 V AC 255 V AC
Nominal discharge current (8/20 μs) In 30 kA 50 kA
Maximum discharge current Imax 60 kA 100 kA
Lighting impulse current Iimp 25 kA 50 kA
Voltage protection level Up 1,5 kV 1,5 kV
Response time ta 100 ns 100 ns
Abilitytoindependentlyswitchoffthe followingcurrent Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 250 A gL/gG —
Maximum overcurrent protection for serial connection 125 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1 ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2 ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field no
Remote indication* potential-free change-over contact potential-free change-over contact*
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
max. 1,5 mm2
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/1+1 8595090550952
FLP-B+C MAXI VS/1+1 8595090537830
* Remote signalling of N-PE module shows the presence of the replaceable module
FLP-B+C MAXI V/1+1
FLP-B+C MAXI VS/1+1
connection of
signalization terminal
Lightning Current Arresters
20
15
PE
PE
7266
45
90
9
15
L
L
N
N
N
N
SPD type 1 and type 2
2-pole arrester for single phase TNS networks
Total Iimp= 50 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against surge
voltages due to direct or indirect lightning strikes in the concept of zone lightning
protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT)
rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven
technology guarantee no follow current, no leakage current and low residual
voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
Technical data
FLP-B+C MAXI VS/2
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/2 8595090550921
FLP-B+C MAXI VS/2 8595090537847
FLP-B+C MAXI V/2
FLP-B+C MAXI VS/2
connection of
signalization terminal
Lightning Current Arresters
21
15
7266
45
90
9
15
PE
L/N
L/N
L/N
L/N
PE
PE
PE
SPD type 1 and type 2
3-pole arrester for 3-phase TNC networks
Total Iimp= 75 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against surge
voltages due to direct or indirect lightning strikes in the concept of zone lightning
protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT)
rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven
technology guarantee no follow current, no leakage current and low residual
voltage.
Remote status signalling contact – version„S“.
Technical data
FLP-B+C MAXI VS/3
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/3 8595090550938
FLP-B+C MAXI VS/3 8595090535706
FLP-B+C MAXI V/3
FLP-B+C MAXI VS/3
connection of
signalization terminal
Dimension drawing Basic circuit diagram
Lightning Current Arresters
22
90
45
66 108
9
15
SPD type 1 and type 2
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Total Iimp= 100 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against
surge voltages due to direct or indirect lightning strikes in the concept of zone
lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube
(GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This
proven technology guarantee no follow current, no leakage current and low
residual voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 260V AC 255V AC
Nominal discharge current (8/20 μs)/pole In 30 kA 100 kA
Maximum discharge current (8/20 μs) Imax 60 kA 100 kA
Lighting impulse current (10/350 μs)/pole Iimp 25 kA 100 kA
Voltage protection level Up 1,5 kV
Voltage protection level (L - PE) Up 2,2 kV
Response time ta 100 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 250 A gL/gG —
Maximum overcurrent protection for serial connection 125 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1 ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2 ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field no
Remote indication* potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC61643-11ed.1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXIV/3+1 8595090550969
FLP-B+C MAXIVS/3+1 8595090535720
* Remote signalling of N-PE module shows the presence of the replaceable module
FLP-B+C MAXI V/3+1
FLP-B+C MAXI VS/3+1
connection of
signalization terminal
Lightning Current Arresters
23
Technical data
90
45
66 144
9
15
Lightning Current Arresters
SPD type 1 and type 2
4-pole arrester for 3-phase TNS networks
Total Iimp= 100 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against
surge voltages due to direct or indirect lightning strikes in the concept of zone
lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube
(GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This
proven technology guarantee no follow current, no leakage current and low
residual voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
FLP-B+C MAXI V/4
FLP-B+C MAXI VS/4
connection of
signalization terminal
Technical data
FLP-B+C MAXI VS/4
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lighting impulse current (10/350 μs)/pole Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/4 8595090550945
FLP-B+C MAXI VS/4 8595090535713
24
66
45
90
144
9
15
Lightning Current Arresters
SPD type 1 and type 2
versatile single-pole arrester
Varistor lightning and surge current arrester to be installed in
low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
FLP-12,5 V/1 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 30 kA
Maximal discharge current Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/1 8595090534211
FLP-12,5 V/1 S 8595090534228
FLP-12,5 V/1
FLP-12,5 V/1 S
connection of
signalization terminal
25
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs) In 30 kA 30 kA
Maximal discharge current (8/20 μs) Imax 60 kA 60 kA
Lightning impulse current (10/350 μs) Iimp 12,5 kA 25 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level@I =5kA(8/20μs) Up 0,9 kV —
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Abilityindependentlyswitchoffthefollowingcurrent Ifi no following current 100 A
Short-circuitproofatmaximumovercurrentprotection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-sectionofremoteindicationconductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Orderingnumber
FLP-12,5V/1+1 8595090534235
FLP-12,5V/1S+1 8595090534242
Lightning Current Arresters
SPD type 1 and type 2
2-pole (1+NPE) arrester for single phase TT(TNS) networks
Total Iimp= 25 kA (10/350)
Varistor lightning and surge current arrester and heavy
duty encapsulated spark gap to be installed in low-voltage
distributions at the boundary of LPZ 0–LPZ 1 zones and higher
to prevent overvoltage effects induced during a lightning
strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
FLP-12,5 V/1+1
FLP-12,5 V/1S+1
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
26
Lightning Current Arresters
SPD type 1 and type 2 – lightning current arrester
Replaceable varistor module, visual fault signalling
2-pole varistor lightning current arrester to be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1
zones and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling (S).
Dimension drawing Basic circuit diagram
FLP-12,5 V/2
FLP-12,5 V/2S
connection of
signalization terminal
Technical data
FLP-12,5 V/2
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximal discharge current/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures - 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/2 8595090538097
FLP-12,5 V/2S 8595090551829
27
L
PE
N
FLP-12,5 V/3 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximal discharge current/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/3 8595090534259
FLP-12,5 V/3 S 8595090534266
Lightning Current Arresters
SPD type 1 and type 2
3-pole arrester for 3-phase TNC networks
Total Iimp= 37,5 kA (10/350)
Varistor lightning and surge current arresters to be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1
zones and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Technical data
FLP-12,5 V/3
FLP-12,5 V/3 S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
28
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs) In 30 kA 50 kA
Maximal discharge current (8/20 μs) Imax 60 kA 100 kA
Lightning impulse current (10/350 μs) Iimp 12,5 kA 50 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level@I =5kA(8/20μs) Up 0,9 kV —
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Abilityindependentlyswitchoffthefollowingcurrent Ifi no following current 100 A
Short-circuitproofatmaximumovercurrentprotection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-sectionofremoteindicationconductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Orderingnumber
FLP-12,5V/3+1 8595090534273
FLP-12,5V/3S+1 8595090534280
Lightning Current Arresters
SPD type 1 and type 2
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Total Iimp= 50 kA (10/350)
Varistor lightning and surge current arresters and fixed N-PE
modul with heavy duty encapsulated spark gap. To be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
FLP-12,5 V/3+1
FLP-12,5 V/3S+1
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
29
Lightning Current Arresters
SPD type 1 and type 2
4-pole arrester for 3-phase TNS networks
Total Iimp= 50 kA (10/350)
Varistor lightning and surge current arresters to be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1
zones and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
FLP-12,5 V/4 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximal discharge current/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/4 8595090534297
FLP-12,5 V/4 S 8595090534303
FLP-12,5 V/4
FLP-12,5 V/4 S
connection of
signalization terminal
30
Lightning Current Arresters
SPD type 1 and type 2
versatile single-pole arrester
Varistor lightning and surge current arrester to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
Dimension drawing Basic circuit diagram
FLP-7-V/1
FLP-7-V/1 S
FLP-7-V/1 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 30 kA
Maximum discharge current Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
connection of
signalization terminal
31
Technical data
Lightning Current Arresters
SPD type 1 and type 2
2-pole (1+NPE) arrester for single phase TT (TNS) networks
Varistor lightning and surge current arrester and heavy duty
encapsulated spark gap in the mode 1+1. To be installed
in low-voltage distributions at the boundary of LPZ 0B
and LPZ 1 zones to protect distributions and equipment against
the overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
FLP-7-V/1+1
FLP-7-V/1S+1
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs) In 30 kA 30 kA
Maximum discharge current (8/20 μs) Imax 60 kA 60 kA
Lighting impulse current (10/350 μs) Iimp 7 kA 25 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 25 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field ne
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
32
Lightning Current Arresters
SPD type 1 and type 2
2-pole arrester for 3-phase TNC networks
Varistor lightning and surge current arresters to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
FLP-7-V/2
FLP-7-V/2 S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
L
PE
N
FLP-7-V/2 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 30 kA
Maximum discharge current Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Technical data
33
Lightning Current Arresters
SPD type 1 and type 2
3-pole arrester for 3-phase TNC networks
Total Iimp= 21 kA (10/350)
Varistor lightning and surge current arresters to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
Dimension drawing Basic circuit diagram
Technical data
FLP-7-V/3
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
FLP-7-V/3
FLP-7-V/3 S
connection of
signalization terminal
34
Lightning Current Arresters
SPD type 1 and type 2
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Total Iimp= 25 kA (10/350)
Varistor lightning and surge current arresters and heavy duty
encapsulated spark gap connected in the mode 3+1. To be
installed in low-voltage distributions at the boundary of LPZ 0B
and LPZ 1 zones to protect distributions and equipment against
the overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
FLP-7-V/3+1
FLP-7-V/3S+1
Technical data
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs)/pole In 30 kA 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA 60 kA
Lighting impulse current (10/350 μs)/pole Iimp 7 kA 25 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Dimension drawing Basic circuit diagram
connection of
signalization terminal
35
Lightning Current Arresters
SPD type 1 and type 2
4-pole arrester for 3-phase TNS networks
Total Iimp= 28 kA (10/350)
Varistor lightning and surge current arresters to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1
zones and higher to prevent overvoltage effects induced
during a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
Dimension drawing Basic circuit diagram
Technical data
FLP-7-V/4
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lighting impulse current (10/350 μs)/pole Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
FLP-7-V/4
FLP-7-V/4 S
connection of
signalization terminal
36
Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 V/1 SLP-150 V/1 SLP-275 V/1 SLP-385 V/1 SLP-440 V/1 SLP-600 V/1
Nominal voltage Un — 120V AC 230V AC — 400V AC —
Maximum operating voltage Uc 75V AC / 100V DC 150V AC / 200V DC 275V AC / 350V DC 385V AC / 500V DC 440V AC / 585V DC 600V AC
Maximum operating voltage of varistor — — — — — 880V AC
Nominal discharge current (8/20 μs) In 15 kA 15 kA 20 kA 20 kA 20 kA 15 kA
Maximum discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA
Voltageprotectionlevel @I=5kA(8/20μs) Up 0,3 kV 0,45 kV 0,9 kV 1,3 kV 1,5 kV 2,7 kV
Voltage protection level Up 0,4 kV 0,6 kV 1,35 kV 1,8 kV 1,9 kV 3,2 kV
Response time ta 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns
Short-circuitproofatmaximumovercurrentprotection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms
Maximum overcurrent protection 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gG 125 A gL/gG 100 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090518150 8595090551850 8595090516170 8595090519553 8595090518174 8595090533016
SLP-075 V/1
SLP-150 V/1
SLP-275 V/1
SLP-385 V/1
SLP-440 V/1
SLP-600 V/1
37
SPD type 2
versatile single-pole arrester
Varistor surge protection to be installed in
low-voltage distributions at the boundary
of LPZ 1 and LPZ 2 zones to protect the
distributions and equipment against
overvoltage effects induced during a
lightning strike and to prevent switching
overvoltage.
connection of
signalization terminal
Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 V/1 S SLP-150 V/1 S SLP-275 V/1 S SLP-385 V/1 S SLP-440 V/1 S SLP-600 V/1 S
Nominal voltage Un — 120V AC 230V AC — 400V AC —
Maximum operating voltage Uc 75V AC / 100V DC 150V AC / 200V DC 275V AC / 350V DC 385V AC / 500V DC 440V AC / 585V DC 600V AC
Maximum operating voltage of varistor — — — — — 880V AC
Nominal discharge current (8/20 μs) In 15 kA 15 kA 20 kA 20 kA 20 kA 15 kA
Maximum discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA
Voltageprotectionlevel @I=5kA(8/20μs) Up 0,3 kV 0,45 kV 0,9 kV 1,3 kV 1,5 kV 2,7 kV
Voltage protection level Up 0,4 kV 0,6 kV 1,35 kV 1,8 kV 1,9 kV 3,2 kV
Response time ta 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns
Short-circuitproofatmaximumovercurrentprotection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms
Maximum overcurrent protection 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gG 125 A gL/gG 100 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S version potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090518235 8595090551867 8595090516187 8595090527718 8595090518259 8595090533023
SLP-075 V/1 S
SLP-150 V/1 S
SLP-275 V/1 S
SLP-385 V/1 S
SLP-440 V/1 S
SLP-600 V/1 S
38
SPD type 2
versatile single-pole arrester
Varistor surge protection to be installed in
low-voltage distributions at the boundary
of LPZ 1 and LPZ 2 zones to protect the
distributions and equipment against
overvoltage effects induced during a
lightning strike and to prevent switching
overvoltage.
Remote status signalling – version„S“.
Surge Arresters
SPD type 2 – surge arrester
2-pole (1+NPE) arrester for single phase TT (TNS) networks
Combination of varistor surge protection and an encapsulated spark
gap connected in the mode 1+1. To be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
distributions and equipment against the overvoltage effects induced
during a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs) In 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 40 kA 40 kA
Lighting impulse current (10/350 μs) Iimp — 12 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —
Voltage protection level Up 1,35 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/1+1 8595090519485
SLP-275 V/1S+1 8595090524915
SLP-275 V/1+1
SLP-275 V/1S+1
connection of
signalization terminal
39
Surge Arresters
SPD type 2 – surge arrester
Replaceable varistor module, visual fault signalling
2-pole varistor surge protection to be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
the distributions and equipment against overvoltage effects
induced during a lightning strike and to prevent switching
overvoltage. Optional remote status signalling(S).
SLP-275 V/2
SLP-275 V/2 S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
SLP-275 V/2 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA
Lighting impulse current (10/350 μs) Iimp —
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Voltage protection level Up 1,35 kV
Response time ta 25 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 6163-11:2012
Ordering number
SLP-275 V/3 8595090516194
SLP-275 V/3S 8595090551836
40
L
PE
N
Surge Arresters
SPD type 2 – surge arrester
3-pole arrester for 3-phase TNC networks
3-pole varistor surge protection to be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
the distributions and equipment against overvoltage effects
induced during a lightning strike and to prevent switching
overvoltage.
Optional remote status signalling – version„S“.
SLP-275 V/3
SLP-275 V/3S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
SLP-275 V/3 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Voltage protection level Up 1,35 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/3 8595090517603
SLP-275 V/3 S 8595090517610
41
Surge Arresters
SPD type 2 – surge arrester
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Combination of 3-pole varistor surge protection and an
encapsulated spark gap connected in the mode 3+1. To be
installed in low-voltage distributions at the boundary of LPZ 1
and LPZ 2 zones to protect distributions and equipment against
the overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs)/pole In 20 kA 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA 40 kA
Lighting impulse current (10/350 μs) Iimp — 12 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —
Voltage protection level Up 1,35 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/3+1 8595090519461
SLP-275 V/3S+1 8595090520023
SLP-275 V/3+1
SLP-275 V/3S+1
connection of
signalization
terminal
42
Surge Arresters
SPD type 2 – surge arrester
4-pole arrester for 3-phase TNS networks
4-pole varistor surge protection to be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
the distributions and equipment against overvoltage effects
induced during a lightning strike and to prevent switching
overvoltage.
Optional remote status signalling – version„S“.
SLP-275 V/4
SLP-275 V/4S
Dimension drawing Basic circuit diagram
connection of
signalization
terminal
Technical data
SLP-275 V/4 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Voltage protection level Up 1,35 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/4 8595090517221
SLP-275 V/4 S 8595090517634
43
Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 VB/1 SLP-130 VB/1 SLP-275 VB/1
Nominal voltage Un — 110 V AC 230 V AC
Maximum operating voltage Uc 75 V AC / 100 V DC 135 V AC / 175 V DC 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,5 kV 0,9 kV
Voltage protection level Up 0,6 kV 0,7 kV 1,2 kV
Response time ta 100 ns 100 ns 100 ns
Short-circuit proof at maximum overcurrent protection 35 kArms 35 kArms 35 kArms
Maximum overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Degree of protection IP 20 IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field red indication field red indication field
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number 8595090521556 8595090521822 8595090519447
SLP-075 VB/1
SLP-130 VB/1
SLP-275 VB/1
SPD type 2 – surge arrester
Replaceable module, visual fault signalling
Efficient varistor connected in series with an encapsulated spark gap. To be installed
in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to
protect distributions and equipment against the overvoltage effects induced during
a lightning strike and to prevent switching overvoltage in areas with higher storm
activity or to protect measuring circuits as a 1st protection level. In idle state it has
very little leakage current, which remains stable for the duration of the service life;
protective elements are not subject to ageing.
44
Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 VB/1 S SLP-130 VB/1 S SLP-275 VB/1 S
Nominal voltage Un — 110 V AC 230 V AC
Maximum operating voltage Uc 75 V AC / 100 V DC 135 V AC / 175 V DC 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,5 kV 0,9 kV
Voltage protection level Up 0,6 kV 0,7 kV 1,2 kV
Response time ta 100 ns 100 ns 100 ns
Short-circuit proof at maximum overcurrent protection 35 kArms 35 kArms 35 kArms
Maximum overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Degree of protection IP 20 IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field red indication field red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number 8595090521563 8595090529965 8595090519454
SLP-075 VB/1 S
SLP-130 VB/1 S
SLP-275 VB/1 S
SPD type 2 – surge arrester
Replaceable module, visual fault signalling
Efficient varistor connected in series with an encapsulated spark gap. To be installed
in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to
protect distributions and equipment against the overvoltage effects induced during
a lightning strike and to prevent switching overvoltage in areas with higher storm
activity or to protect measuring circuits as a 1st protection level. In idle state it has
very little leakage current, which remains stable for the duration of the service life;
protective elements are not subject to ageing.
Remote status signalling – version„S“.
connection of
signalization
terminal
45
Surge Arresters
SPD type 2 – surge arrester
Efficient varistor connected in series with an encapsulated spark gap.
To be installed in low-voltage distributions at the boundary of LPZ 1
and LPZ 2 zones. Designed to protect distributions and equipment
against the overvoltage effects induced during a lightning strike and
to prevent switching overvoltage in areas with higher storm activity or
to protect measuring circuits as a 1st
protection level. In idle state it has
very little leakage current, which remains stable for the duration of the
service life; protective elements are not subject to ageing.
Optional remote status signalling (S).
Technical data
L-N N-PE
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs) In 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 25 kA 40 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level (L-PE) Up 2,0 kV
Response time ta 100 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 35 kArms —
Maximum overcurrent protection 125 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 6163-11:2012
IEC 61643-11 ed. 1.0
EN 6163-11:2012
Ordering number
SLP-275 VB/3+1 8595090533108
SLP-275 VB/3S+1 8595090533115
SLP-275 VB/3+1
SLP-275 VB/3S+1
Dimension drawing Basic circuit diagram
connection of
signalization
terminal
46
Surge Arresters
SPD type 3 – surge arrester
Replaceable module, visual fault signalling
Combination of varistor surge protection and an encapsulated
spark gap connected in the mode 1+1. To be installed in low-
voltage distributions at the boundary of LPZ 2 and LPZ 3 zones
to protect distributions and equipment against overvoltage
effects induced during a lightning strike and to prevent
switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs) In 5 kA 10 kA
Test voltage Uoc 10 kV 20 kV
Voltage protection level Up 1 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Maximum overcurrent protection 63 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012
Ordering number
DA-275 V/1+1 8595090518723
DA-275 V/1S+1 8595090519751
DA-275 V/1+1
DA-275 V/1S+1
connection of
signalization terminal
47
Surge Arresters
SPD type 3 – surge arrester
Replaceable module, visual fault signalling	
Combination of 3-pole varistor surge protection and an
encapsulated spark gap connected in the mode 3+1. To be
installed in low-voltage distributions at the boundary of LPZ 2
and LPZ 3 zones to protect distributions and equipment against
overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technické parametry
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs)/pole In 5 kA 10 kA
Test voltage Uoc 10 kV 20 kV
Voltage protection level Up 1 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Maximum overcurrent protection 63 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012
Ordering number
DA-275 V/3+1 8595090518488
DA-275 V/3S+1 8595090518495
DA-275 V/3+1
DA-275 V/3S+1
connection of
signalization
terminal
48
Surge Arresters
SPD type 3 – surge arrester
Visual fault signalling
Surge protection designed to protect all types of electric and
electronic equipment connected to a low-voltage distribution
against pulse overvoltage.
Dimension drawing Basic circuit diagram
Technical data
DA-075 DJ DA-130 DJ DA-275 DJ
Nominal voltage Un — 110 V AC 230 V AC
Maximum operating voltage Uc 75 V AC 130 V AC 275 V AC
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 2 kA, 2 kA, 4 kA 2,5 kA, 2,5 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 4 kV, 4 kV, 8 kV 5 kV, 5 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 0,4 kV, 1,2 kV 0,6 kV, 1,5 kV 1,2 kV, 1,6 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns 25 ns, 100 ns
Short-circuit proof at maximum overcurrent protection 6 kArms 6 kArms 6 kArms
Maximum overcurrent protection 16 A gL/gG; B 16 A 16 A gL/gG; B 16 A 16 A gL/gG; B 16 A
Degree of protection IP 20 IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 6 mm2
; AWG: 10 ISO: 6 mm2
; AWG: 10 ISO: 6 mm2
; AWG: 10
Stranded max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Fault indication red indicator red indicator red indicator
Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012 EN 61643-11:2012
Ordering number 8595090533191 8595090521891 8595090506362
DA-075 DJ
DA-130 DJ
DA-275 DJ
49
Surge Arresters
Dimension drawing Basic circuit diagram
SPD type 3 – surge arrester with RFI filter
Visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
DA-275 DF2 DA-275 DF6
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 2 A 6 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 2 kA, 2 kA, 4 kA 2 kA, 2 kA, 4 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 4 kV, 4 kV, 8 kV 4 kV, 4 kV, 8 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 2 A gL/gG or B 2 A 6 A gL/gG or B 6 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090506706 8595090506713
Technické parametry
DA-275 DF 2
DA-275 DF 6
50
DA-275 DF2 S DA-275 DF6 S
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 2 A 6 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 2 A gL/gG or B 2 A 6 A gL/gG or B 6 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Remote indication – S design potential-free change-over contact potential-free change-over contact
Remote indication contacts AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090516248 8595090516255
Technical data
Surge Arresters
Dimension drawing Basic circuit diagram
SPD type 3 – surge arrester with RFI filter
Remote and visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
DA-275 DF 2 S
DA-275 DF 6 S
51
Dálková signalizace
Surge Arresters
SPD type 3 – surge arrester with RFI filter
Visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
Dimension drawing Basic circuit diagram
Technical data
DA-275 DF10 DA-275 DF16
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 10 A 16 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 10 A gL/gG nebo C10 A 16 A gL/gG nebo C16 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090506720 8595090506737
DA-275 DF 10
DA-275 DF 16
52
Technical data
DA-275 DF10 S DA-275 DF16 S
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 10 A 16 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 10 A gL/gG or B 10 A 16 A gL/gG or B 16 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Remote indication potential-free change-over contact potential-free change-over contact
Remote indication contacts AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090516262 8595090516279
Dimension drawing Basic circuit diagram
Surge Arresters
SPD type 3 – surge arrester with RFI filter
Remote fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
DA-275 DF 10 S
DA-275 DF 16 S
53
Dálková signalizace
Surge Arresters
SPD type 3 – surge arrester with RFI filter
Visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
Dimension drawing Basic circuit diagram
Technical data
DA-275 DF25
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC
Nominal load current IL 25 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns
Maximum overcurrent protection 25 A gL/gG or C 25 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB
Degree of protection IP 20
Range of operating temperatures –40 °C … +80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 1/50 mm2
; AWG: 17/1
Stranded max ISO: 1/35 mm2
; AWG: 17/2
Fault indication red indicator
Meets the requirements of standard EN 61643-11 + A11
Ordering number 8595090537328
DA-275 DF 25
54
72
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application
Surge Protection Catalogue: SPDs for Any Application

More Related Content

What's hot

Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentationPepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentationKristen_Barbour_PF
 
Degree of protection provided by an ASSEMBLY enclosure (IP & IK)
Degree of protection provided by an ASSEMBLY enclosure (IP & IK)Degree of protection provided by an ASSEMBLY enclosure (IP & IK)
Degree of protection provided by an ASSEMBLY enclosure (IP & IK)Mustafa Ismail
 
Advance security system (ppt)
Advance security system (ppt)Advance security system (ppt)
Advance security system (ppt)Komal Kumra
 
Access control basics-5
Access control basics-5Access control basics-5
Access control basics-5grantlerc
 
Lunch And Learn Presentation
Lunch And Learn PresentationLunch And Learn Presentation
Lunch And Learn Presentationrlaverne
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchMiller Energy, Inc.
 
Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...
Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...
Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...Thorne & Derrick International
 
Safety for operators and machinery 2011
Safety for operators and machinery 2011Safety for operators and machinery 2011
Safety for operators and machinery 2011ifm electronic gmbh
 
Safety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 EnglishSafety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 Englishifm electronic gmbh
 
Apt 3rd Edition Presentation
Apt 3rd Edition PresentationApt 3rd Edition Presentation
Apt 3rd Edition Presentationvisak123
 
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson IndustrialHazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson IndustrialThorne & Derrick International
 
System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetJMAC Supply
 
K39 Controller
K39 ControllerK39 Controller
K39 ControllerJoseph
 
OFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 EN
OFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 ENOFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 EN
OFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 ENLika Electronic
 
Security Alarm Systems blaze automation
Security Alarm Systems blaze automationSecurity Alarm Systems blaze automation
Security Alarm Systems blaze automationBlaze Automation
 
Access control basics-6
Access control basics-6Access control basics-6
Access control basics-6grantlerc
 

What's hot (20)

Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentationPepperl+Fuchs  2011 Emerson Global Users Exchange fieldbus presentation
Pepperl+Fuchs 2011 Emerson Global Users Exchange fieldbus presentation
 
Degree of protection provided by an ASSEMBLY enclosure (IP & IK)
Degree of protection provided by an ASSEMBLY enclosure (IP & IK)Degree of protection provided by an ASSEMBLY enclosure (IP & IK)
Degree of protection provided by an ASSEMBLY enclosure (IP & IK)
 
Advance security system (ppt)
Advance security system (ppt)Advance security system (ppt)
Advance security system (ppt)
 
Access control basics-5
Access control basics-5Access control basics-5
Access control basics-5
 
Exloc is hj
Exloc is hjExloc is hj
Exloc is hj
 
Acb1
Acb1Acb1
Acb1
 
Lunch And Learn Presentation
Lunch And Learn PresentationLunch And Learn Presentation
Lunch And Learn Presentation
 
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-SwitchOne Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
One Series Safety Transmitter - Pressure and Temperature Transmitter-Switch
 
Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...
Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...
Hazardous Area Zones & Explosion Protection - An Overview of Potentially Expl...
 
Safety for operators and machinery 2011
Safety for operators and machinery 2011Safety for operators and machinery 2011
Safety for operators and machinery 2011
 
Thông số kĩ thuật Siemens-ACB-3 WL
Thông số kĩ thuật Siemens-ACB-3 WLThông số kĩ thuật Siemens-ACB-3 WL
Thông số kĩ thuật Siemens-ACB-3 WL
 
Catalogue Siemens ACB3 WN
Catalogue Siemens ACB3 WNCatalogue Siemens ACB3 WN
Catalogue Siemens ACB3 WN
 
Safety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 EnglishSafety technology – Sensors and system solutions from ifm 2016 English
Safety technology – Sensors and system solutions from ifm 2016 English
 
Apt 3rd Edition Presentation
Apt 3rd Edition PresentationApt 3rd Edition Presentation
Apt 3rd Edition Presentation
 
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson IndustrialHazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
Hazardous Area Location Guide - IEC NEC CEC & ATEX By Emerson Industrial
 
System Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data SheetSystem Sensor 2WTR-B Data Sheet
System Sensor 2WTR-B Data Sheet
 
K39 Controller
K39 ControllerK39 Controller
K39 Controller
 
OFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 EN
OFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 ENOFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 EN
OFFSHORE HEAVY-DUTY CATALOG LIKA ELECTRONIC 2016 EN
 
Security Alarm Systems blaze automation
Security Alarm Systems blaze automationSecurity Alarm Systems blaze automation
Security Alarm Systems blaze automation
 
Access control basics-6
Access control basics-6Access control basics-6
Access control basics-6
 

Viewers also liked

Tiyatro kursu-kadikoy
Tiyatro kursu-kadikoyTiyatro kursu-kadikoy
Tiyatro kursu-kadikoyzeynep_zyn84
 
Argumentación.
Argumentación. Argumentación.
Argumentación. nestorio62
 
Personal Statement
Personal StatementPersonal Statement
Personal StatementClive Rogers
 
Los Valores
Los ValoresLos Valores
Los ValoresOkcar777
 
Juan F Parks Resume
Juan F Parks ResumeJuan F Parks Resume
Juan F Parks ResumeJuan Parks
 
How overtime lawyer can assist you getting your overtime wages?
How overtime lawyer can assist you getting your overtime wages?How overtime lawyer can assist you getting your overtime wages?
How overtime lawyer can assist you getting your overtime wages?JTB Law Group, LLC
 
İkinci El Lcd Led Plazma Televizyon Alanlar
İkinci El Lcd Led Plazma Televizyon Alanlar  İkinci El Lcd Led Plazma Televizyon Alanlar
İkinci El Lcd Led Plazma Televizyon Alanlar Eski buzdolabı alanlar
 
Symion kompas
Symion kompasSymion kompas
Symion kompasSymion
 

Viewers also liked (11)

Tiyatro kursu-kadikoy
Tiyatro kursu-kadikoyTiyatro kursu-kadikoy
Tiyatro kursu-kadikoy
 
Argumentación.
Argumentación. Argumentación.
Argumentación.
 
Smart televizyon alanlar
Smart televizyon alanlarSmart televizyon alanlar
Smart televizyon alanlar
 
Plugin demo
Plugin demoPlugin demo
Plugin demo
 
Personal Statement
Personal StatementPersonal Statement
Personal Statement
 
Los Valores
Los ValoresLos Valores
Los Valores
 
Juan F Parks Resume
Juan F Parks ResumeJuan F Parks Resume
Juan F Parks Resume
 
How overtime lawyer can assist you getting your overtime wages?
How overtime lawyer can assist you getting your overtime wages?How overtime lawyer can assist you getting your overtime wages?
How overtime lawyer can assist you getting your overtime wages?
 
İkinci El Lcd Led Plazma Televizyon Alanlar
İkinci El Lcd Led Plazma Televizyon Alanlar  İkinci El Lcd Led Plazma Televizyon Alanlar
İkinci El Lcd Led Plazma Televizyon Alanlar
 
Symion kompas
Symion kompasSymion kompas
Symion kompas
 
VIPIN R CV
VIPIN R CVVIPIN R CV
VIPIN R CV
 

Similar to Surge Protection Catalogue: SPDs for Any Application

Early warning surge&lightning (electrical safety ) for valuable equipment...
Early warning surge&lightning (electrical safety ) for valuable equipment...Early warning surge&lightning (electrical safety ) for valuable equipment...
Early warning surge&lightning (electrical safety ) for valuable equipment...Mahesh Chandra Manav
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueThorne & Derrick International
 
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...Thorne & Derrick International
 
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd  Electrical Equipment & Human SafetyMake India Safer with JMV LPS Ltd  Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd Electrical Equipment & Human SafetyMahesh Chandra Manav
 
HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)Allied Power APS
 
JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...
JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...
JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...Mahesh Chandra Manav
 
Best Practices for Surge Protection on a Tank Battery
Best Practices for Surge Protection on a Tank BatteryBest Practices for Surge Protection on a Tank Battery
Best Practices for Surge Protection on a Tank BatteryPetro Guardian
 
Lightning and surge transfer to systems presentation by jmv lps
Lightning and surge  transfer to systems presentation by jmv lpsLightning and surge  transfer to systems presentation by jmv lps
Lightning and surge transfer to systems presentation by jmv lpsMahesh Chandra Manav
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices Pratik Rasam
 
ESP D1 Series - Enhanced mains power protectors
ESP D1 Series - Enhanced mains power protectorsESP D1 Series - Enhanced mains power protectors
ESP D1 Series - Enhanced mains power protectorsFurse
 
Programmable Limit Alarm Trips with Intrinsically-Safe Field Connections
Programmable Limit Alarm Trips with Intrinsically-Safe Field ConnectionsProgrammable Limit Alarm Trips with Intrinsically-Safe Field Connections
Programmable Limit Alarm Trips with Intrinsically-Safe Field ConnectionsArjay Automation
 
Littelfuse Smart Thermostat Capabilities
Littelfuse Smart Thermostat CapabilitiesLittelfuse Smart Thermostat Capabilities
Littelfuse Smart Thermostat CapabilitiesLittelfuse
 
ST on 96Boards OpenHours - System level ESD protection
ST on 96Boards OpenHours - System level ESD protectionST on 96Boards OpenHours - System level ESD protection
ST on 96Boards OpenHours - System level ESD protection96Boards
 
Protection of Photovoltaic (PV) systems
Protection of Photovoltaic (PV) systemsProtection of Photovoltaic (PV) systems
Protection of Photovoltaic (PV) systemsFurse
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection DevicesJason Koffler
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Thorne & Derrick International
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protectionSy Thinhbk
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protectionSy Thinhbk
 

Similar to Surge Protection Catalogue: SPDs for Any Application (20)

Early warning surge&lightning (electrical safety ) for valuable equipment...
Early warning surge&lightning (electrical safety ) for valuable equipment...Early warning surge&lightning (electrical safety ) for valuable equipment...
Early warning surge&lightning (electrical safety ) for valuable equipment...
 
Bussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices CatalogueBussmann By Eaton - Surge Protection Devices Catalogue
Bussmann By Eaton - Surge Protection Devices Catalogue
 
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
Surge Protection - Main Incoming Supply Sub Distribution Boards Socket Outlet...
 
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd  Electrical Equipment & Human SafetyMake India Safer with JMV LPS Ltd  Electrical Equipment & Human Safety
Make India Safer with JMV LPS Ltd Electrical Equipment & Human Safety
 
HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)HAKEL_-_Surge_Protection_Device (1) (1)
HAKEL_-_Surge_Protection_Device (1) (1)
 
JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...
JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...
JMV LPS Ltd Make in India Product for SolarPv,High Energy Storage and Electri...
 
Best Practices for Surge Protection on a Tank Battery
Best Practices for Surge Protection on a Tank BatteryBest Practices for Surge Protection on a Tank Battery
Best Practices for Surge Protection on a Tank Battery
 
Lightning and surge transfer to systems presentation by jmv lps
Lightning and surge  transfer to systems presentation by jmv lpsLightning and surge  transfer to systems presentation by jmv lps
Lightning and surge transfer to systems presentation by jmv lps
 
Power surge protection devices
Power surge protection devices Power surge protection devices
Power surge protection devices
 
ESP D1 Series - Enhanced mains power protectors
ESP D1 Series - Enhanced mains power protectorsESP D1 Series - Enhanced mains power protectors
ESP D1 Series - Enhanced mains power protectors
 
Programmable Limit Alarm Trips with Intrinsically-Safe Field Connections
Programmable Limit Alarm Trips with Intrinsically-Safe Field ConnectionsProgrammable Limit Alarm Trips with Intrinsically-Safe Field Connections
Programmable Limit Alarm Trips with Intrinsically-Safe Field Connections
 
Littelfuse Smart Thermostat Capabilities
Littelfuse Smart Thermostat CapabilitiesLittelfuse Smart Thermostat Capabilities
Littelfuse Smart Thermostat Capabilities
 
ST on 96Boards OpenHours - System level ESD protection
ST on 96Boards OpenHours - System level ESD protectionST on 96Boards OpenHours - System level ESD protection
ST on 96Boards OpenHours - System level ESD protection
 
PROFIBUS lightning surge protection - Peter Thomas, CSL - 10 june 2020
PROFIBUS lightning surge protection -  Peter Thomas, CSL - 10 june 2020 PROFIBUS lightning surge protection -  Peter Thomas, CSL - 10 june 2020
PROFIBUS lightning surge protection - Peter Thomas, CSL - 10 june 2020
 
Protection of Photovoltaic (PV) systems
Protection of Photovoltaic (PV) systemsProtection of Photovoltaic (PV) systems
Protection of Photovoltaic (PV) systems
 
Guide to Surge Protection Devices
Guide to Surge Protection DevicesGuide to Surge Protection Devices
Guide to Surge Protection Devices
 
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
Hadar - Hadar Lighting For Hazardous Areas (Zone 1 & Zone 2 - ATEX Certified)
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
 
Ground fault protection
Ground fault protectionGround fault protection
Ground fault protection
 
Surge Protection
Surge ProtectionSurge Protection
Surge Protection
 

Surge Protection Catalogue: SPDs for Any Application

  • 2. SALTEK® is a leading Czech company specialised in the development and production of surge protection devices. It offers a broad range of lightning current arresters and surge protection type 1–3 according to EN 61643-11 (or B, C and D according to E DIN VDE 0675-6) and surge protection for information technology, measurement and control and telecommunications. SALTEK® products provide protection against the lightning and technological overvoltage and thereby rise the safety and trouble-free operation of the technologies, machinery and appliances at the industry, telecommunications, data centers, office buildings even in ordinary houses. SALTEK® was founded in 1995. Successful business activities abroad, in many countries of three continents, are provided by subsidiaries SALTEK® TRADE. The principle of dynamic company expansion consists in its own product development. A team of experienced development engineers works in test development laboratory with unique devices and technologies. The sophisticated materials, design processes, technologies and measurement methods are used for the development of SALTEK® products. Production is equipped with automatic and robotized assembly lines. Special attention is focused on the quality of products. SALTEK® has implemented Integrated Management System IMS, according to international standards, which consists of Quality management system under EN ISO 9001, Environmental protection management under EN ISO 14001 and Health and safety management system under OHSAS 18001. System IMS is annually verified by external auditing company TÜV NORD Czech. SALTEK® is focused on quality, but also to design of products. Line of surge protection devices with unique color coding has been awarded a design prize Red Dot® 2014.
  • 3. SALTEK Choose from our comprehensive range of surge protection devices: 1 SPD type 1 – lightning current arresters SPD type 1 and 2 – B+C combined arresters SPD type 2 – surge arresters SPD type 3 – surge arresters SPD type 3 – surge protective devices with a RFI filter SPD type 3 – surge protective devices for additional mounting Surge separation inductor SPD for photovoltaic systems Surge arresters for measurement and control, electronic security systems, EPS and telecommunications Surge arresters for Ethernet and video lines Lightning arresters and surge arresters for coaxial lines Accessories page 16 page 19 page 37 page 47 page 50 page 60 page 63 page 65 page 74 page 95 page 103 page 108
  • 4. 1. Introduction – Legislative The use of modern sophisticated equipment, consumer electronics and control systems places high demands on their electromagnetic compatibility. Modern electronic control systems provided with circuits with a very high integration level are becoming more and more sensitive to electromagnetic disturbance and overvoltage. The installation of surge protections according to effective legal standards will reduce the danger of their being damaged to a minimum. Technical designs are defined by standards harmonised with EU standards: a) Protective bonding to the same potential including the conductor cross section for the main and additional bonding is defined by standards EN 50310 ed. 2. , IEC 60364-5-54, IEC 60364-4-41 b) Lightning protection is specified in the EN 62305 collection of new standards, harmonised with European standards. EN 62305 – 1 deals with general principles. Lightning protection level Maximum lightning parameter according to LPL LPL First short discharge LPL I 200 kA LPL II 150 kA LPL III 100 kA LPL IV 100 kA IEC/EN 62305 – 2 – deals with the risk assessment for buildings or engineering networks struck by lightning. IEC/EN 62305 – 3 – deals with the proposal for external lightning protection (lightning conductor). IEC/EN 62305 – 4 – deals with protective measures resulting in the reduction of failures of electrical and electronic systems inside the building (zone protection) c) Classification of protections is set forth in standard EN 61643-11. Devices are classified into three basic categories: SPD type 1 – lightning current arresters SPD type 2 – surge arresters SPD type 3 – surge arresters d) Classification of low-voltage distribution into impulse resistance categories, including specification of the maximum allowed overvoltage is determined in standard EN 60664-1 Protection against lightning and overvoltage Rated impulse for equipment (acc. to EN 60664-1) or Impulse-withstand voltage. Lightning protection zones The standard EN 62305-4 defines lightning protection zones LPZ in view of the direct and indirect (electromagnetic pulse – LEMP) lightning effect: LPZ 0A – free area (possibility of a direct lightning strike, non-attenuated LEMP) LPZ 0B – lightning conductor receiver protection area (direct lightning strike protection, non-attenuated LEMP) LPZ 1 – inside a building (direct lightning strike is eliminated, attenuated LEMP – depending upon shielding) LPZ 2 – inside a room – e.g. a server room with a conductive floor, FeAl floors and wall lining (further attenuation of LEMP in connection with a higher shielding level) LPZ 3 – inside a metal box (e.g. 19“ RACK) Lightning and surge protection Example of main and additional bonding telephone cable gas pipeline water pipeline base ground main protective bonding bar 2 Insulation coordination lift flats appliance appliances
  • 5. Protection against lightning and overvoltage 2. Connection of surge protection devices in networks TN-S 3 *F3 Sub-distribution board (1) SPD type 2 SPD type 2 SPD type 2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board (2) SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar Local earth bonding bar *F4*F2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar *F3 Entrance part of the structure L1 L2 L3 N PEN PE F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 Entrance part of the structure L1 L2 L3 PEN F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 RCD Sub-distribution board (2) SPD type 2 SPD type 3 SPD type 3 LPZ 1 LPZ 1 Local earth bonding bar *F3 Sub-distribution board (1) Local earth bonding bar *F3 Sub-distribution board Local earth bonding bar *F4 *F2 Fine protection 63A 16A 16A Fine protection 63A 16A 16A equipment * SPD back-up – see item 4 *F3 Sub-distribution board (1) SPD type 2 SPD type 2 SPD type 2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board (2) SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar Local earth bonding bar *F4*F2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar *F3 Entrance part of the structure L1 L2 L3 N PEN PE F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 Entrance part of the structure L1 L2 L3 PEN F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 RCD Sub-distribution board (2) SPD type 2 SPD type 3 SPD type 3 LPZ 1 LPZ 1 Local earth bonding bar *F3 Sub-distribution board (1) Local earth bonding bar *F3 Sub-distribution board Local earth bonding bar *F4 *F2 Fine protection 63A 16A 16A Fine protection 63A 16A 16A equipment * SPD back-up – see item 4 TN-C-S *F3 Sub-distribution board (1) SPD type 2 SPD type 2 SPD type 2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board (2) SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar Local earth bonding bar *F4*F2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar *F3 Entrance part of the structure L1 L2 L3 N PEN PE F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 Entrance part of the structure L1 L2 L3 PEN F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 RCD Sub-distribution board (2) SPD type 2 SPD type 3 SPD type 3 LPZ 1 LPZ 1 Local earth bonding bar *F3 Sub-distribution board (1) Local earth bonding bar *F3 Sub-distribution board Local earth bonding bar *F4 *F2 Fine protection 63A 16A 16A Fine protection 63A 16A 16A equipment * SPD back-up – see item 4 TN-C *F3 Sub-distribution board (1) SPD type 2 SPD type 2 SPD type 2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board (2) SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar Local earth bonding bar *F4*F2 Entrance part of the structure L1 L2 L3 N PE F1 RCD Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2 Sub-distribution board SPD type 2 Fine protection SPD type 3 63A 16A 16A LPZ 0 LPZ 1 Local earth bonding bar *F3 Entrance part of the structure L1 L2 L3 N PEN PE F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 Entrance part of the structure L1 L2 L3 PEN F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 RCD Sub-distribution board (2) SPD type 2 SPD type 3 SPD type 3 LPZ 1 LPZ 1 Local earth bonding bar *F3 Sub-distribution board (1) Local earth bonding bar *F3 Sub-distribution board Local earth bonding bar *F4 *F2 Fine protection 63A 16A 16A Fine protection 63A 16A 16A equipment * SPD back-up – see item 4 TT SPD in 3+1 mode SPD in 4+0 mode SPD in 3+1 mode SPD in 4+0 mode SPD in 3+0 mode SPD in 3+1 mode
  • 6. Protection against lightning and overvoltage 4 3. SPD dimensioning and their use Application of SALTEK SPD type 1 EN 62305 Location of SPD type 1: at the boundary of LPZ0 and LPZ1 zones in main distribution board LPL Lightning Total SPD I. to 200 kA 100 kA Conditions met by: FLP-SG50 V(S)/1 FLP-B+C MAXI V(S)/1 - large industrial facilities - structures of special importance - technological facilities - administrative structures - administrative structures - civic amenities - family houses - near transformer stations LPL Lightning Total SPD III. to 100 kA 50 kA Conditions met by: FLP-12,5 V/1(S) - family houses w/o down conductor system With a cable connector in the housing and in the LPS III class - structures in LPS IV class, i.e. structures and halls without persons and interior equipment, structures only with heavy current wiring - on LW earthing supply cables to the structure where the connection is not directly to the public distribution network (i.e. interconnection between 2 structures) - to sub-distribution boards within the structure, With a cable length from the last SPD of over 50 m Aplication of SALTEK SPD type 2 EN 62305 Location of SPD type 2: at the boundary of LPZ1 and LPZ2 zones or sub-distribution board Conditions met by: SLP-xxx - all types of wiring - type of network (TN, IT, T T) - connection method - nominal voltage Application of SALTEK SPD type 3 EN 62305 Location of SPD type 3: at the boundary of LPZ2 and LPZ3 zones (technology) Conditions met by: DA-275 (with DIN bar) - all types of wiring (if the equipment is in the clamp or distribution board) DA-275 …, CZ… - all types of wiring (sockets with overvoltage protection at the shortest possible distance from the appliance) xxx-OVERDRIVE - all types of wiring adapters for plugs with overvoltage protection 4. Principle of SPD backing For the design of an SPD back-up, it is important if we consider the protection priority principle, found in most installations, or the supply priority principle. Example of an SPD FLP-B+C MAXI V back-up in different supply networks. The catalogue value of the maximum back-up for FLP-B+C MAXI V is 250 A, for a“V”connection it is 125 A. Connection in parallel Connection in„V“ TN-C FLP-B+C MAXI V SPD T1 T2 červená – porucha red – defect 250 A Uc: 260 V~ Iimp: 25 kA In: 30 kA Imax: 60 kA Up: 1,5 kV FLP-B+C MAXI V SPD T1 T2 červená – porucha red – defect 250 A Uc: 260 V~ Iimp: 25 kA In: 30 kA Imax: 60 kA Up: 1,5 kV FLP-B+C MAXI V SPD T1 T2 červená – porucha red – defect 250 A Uc: 260 V~ Iimp: 25 kA In: 30 kA Imax: 60 kA Up: 1,5 kV F1 ≤ 125 A FLP-B+C MAXI V SPD T1 T2 červená – porucha red – defect 250 A Uc: 260 V~ Iimp: 25 kA In: 30 kA Imax: 60 kA Up: 1,5 kV FLP-B+C MAXI V SPD T1 T2 červená – porucha red – defect 250 A Uc: 260 V~ Iimp: 25 kA In: 30 kA Imax: 60 kA Up: 1,5 kV FLP-B+C MAXI V SPD T1 T2 červená – porucha red – defect 250 A Uc: 260 V~ Iimp: 25 kA In: 30 kA Imax: 60 kA Up: 1,5 kV F1 250 A → F2 F1 ≤ 250 A → F2 F1 125 A F1 ≤ 125 A ×
  • 7. 5 Protection against lightning and overvoltage 5. Principles for positioning and connecting of lightning and surge arresters Surge protection devices and lightning current arresters cannot be positioned in the distribution board at random. It should be noted that protection should be located in the closest proximity to the entry feed cable of the distribution board to minimize the area of the induction loop, see the image below. Examples of SPDs located in a distribution board. overhead, PEN (PE) at the bottom overhead, PEN (PE) at the top bottom supply, PEN (PE) at the bottom bottom supply, PEN (PE) at the top Another important condition for connecting the SPD is to minimize the impedance of connecting conductors. Stranded conductors or strip lines are preferentially used for connecting SPD type 1. It is also important that the length of the connecting conductors is as small as possible – see IEC 60364-5-534 (the total length of connecting conductors must not exceed 1 m). The cross-section of the connecting conductors should be as large as possible – maximum up to the cross-section according to the type of connector. In SPD type 1 (lightning arresters) the connecting conductors are an integral part of the main bonding – as determined by the IEC60364-4-41 standard, while minimum cross-sections of the connecting conductors are specified in IEC60364-5-54. If SPDs are located in circuits where residual current devices are installed, the SPD should be positioned before the residual current device (not in the residual current device circuit), to prevent spontaneous overload tripping of the RCD affected by surge arresters or lightning current arresters. Should an overvoltage protection be located in the residual current devices circuit, RCD type S or G should be used. Even in this case it should be noted that the resistance of these residual current devices is not high (5 to 8 kA in wave 8/20 μs) which makes it impossible to use any SPD in the circuit of the residual current device. If you want to prevent a residual current device type S or G responding to surge protection by overload tripping, only a protection SPD type 3 can be used in the circuit of the residual current device. Example of SPD FLP-12,5 V back-up in different supply networks. The catalogue value of the maximum back-up for FLP-12,5 V is F2 =160 A. F2’– the SPD back-up value established by the calculation TN-C PEN PEN FLP-12,5Včervená porucha red defect SPDT1T2 FLP-12,5Včervená porucha red defect SPDT1T2 FLP-12,5Včervená porucha red defect SPDT1T2 L1 L2 L3 L3L2L1 F2 = 160 A F1 160 A ≥ 160 A → F2
  • 8. 6 6. SPD dimensioning Dimensioning is only provided for SPD type 1. The basis for that is the calculation of the lightning protection level (LPL) for the down conductor (LPS). The table below is taken from CLC/TS 61643-12 and shows the minimum value of the current withstand per pole according to the lightning protection level (LPL) structure classification. If LPL is not known, the worst case shall be answered LV system LPL Maximum current for the LPL No. of conductors (n) TT TN-C TN-S IT w/o neutral conductor IT with neutral Connection mode Connection mode Connection mode CT1 CT2 CT1 CT2 CT1 CT2 L-PE N-PE L-N N-PE L-PEN L-PE N-PE L-N N-PE L-PE L-N N-PE 1 or unknown 200 kA Iimp (kA) 5 N/A N/A N/A N/A 20,0 20,0 80,0 N/A N/A N/A 4 25,0 25,0 100,0 25,0 N/A N/A N/A N/A 25,0 100,0 3 N/A N/A N/A N/A 33,3 33,3 66,7 33,3 N/A N/A 2 50,0 50,0 100,0 50,0 N/A N/A N/A N/A 50,0 100,0 2 150 kA Iimp (kA) 5 N/A N/A N/A N/A 15,0 15,0 60,0 N/A N/A N/A 4 18,8 18,8 75,0 18,8 N/A N/A N/A N/A 18,8 75,0 3 N/A N/A N/A N/A 25,0 25,0 50,0 25,0 N/A N/A 2 37,5 37,5 75,0 37,5 N/A N/A N/A N/A 37,5 75,0 3 or 4 100 kA Iimp (kA) 5 N/A N/A N/A N/A 10,0 10,0 40,0 N/A N/A N/A 4 12,5 12,5 50,0 12,5 N/A N/A N/A N/A 12,5 50,0 3 N/A N/A N/A N/A 16,7 16,7 33,3 16,7 N/A N/A 2 25,0 25,0 50,0 25,0 N/A N/A N/A N/A 25,0 50,0 Comment: CT1 – connection of an SPD in the X+0 mode; CT2 – connection of an SPD in the X+1mode CT1 – (TN-C) 3+0 CT1 – (TN-S) 4+0 CT2 (TT or TNS) 3+1 Protection against lightning and overvoltage
  • 9. 7 Protection against lightning and overvoltage 7. Reducing overvoltage using LPZ zones The principle of reducing overvoltage using zones lies in the progressive reduction of the overvoltage level to a safe value that will not damage the specific equipment or technology. To obtain a safe overvoltage value, the whole structure is divided into individual zones and an SPD is installed at the boundary between the zones.. *F3 Podružný rozváděč (1) SPD typ 2 SPD type 2 SPD typ 2 Vstupní část instalace L1 L2 L3 N PE F1 RCD Hlavní zemní přípojnice Externíochranaprotiblesku Hlavní rozváděč SPD typ 1 nebo 1+2 Podružný rozváděč (2) SPD typ 2 Jemná ochrana SPD typ 3 63A 16A 16A LPZ 0 LPZ 2LPZ 1 LPZ 2 Lokální zemní přípojnice Lokální zemní přípojnice *F4*F2 LPZ 2 Entrance part of the structure L1 L2 L3 N PEN PE F1 Main earth bonding bar Externalprotectionagainstlightning Main distribution board SPD type 1 or 1+2LPZ 0 *F2 Vstupní část instalace L1 L2 L3 PEN F1 Hlavní rozváděč SPD typ 1 nebo 1+2LPZ 0 *F2 RCD Sub-distribution board (2) SPD type 2 SPD type 3 SPD typ 3 LPZ 1 LPZ 1 Local earth bonding bar *F3 Sub-distribution board (1) Local earth bonding bar *F3 Podružný rozváděč *F4 Fine protection 63A 16A 16A Jemná ochrana 63A 16A 16A equipment * back-up of SPD – see page.7 LPZ 0A LPZ 0BLPZ 0B LPZ 0A T2 T1 (T1+T2)LPZ 1 T3 T3 T3 LPZ 1 T3 T3 T3 T3 T1
  • 10. Protection against lightning and overvoltage Examples of SPD applications Modern family houses feature more and more electronic equipment. If the owner of the structure wants to watch TV, be in contact with the world via the Internet, control the heating in the structure automatically, use various electronic equipment without any trouble, it is necessary to protect such equipment against atmospheric events. Lightning strikes hitting the structure or near the structure and overvoltage in the mains can destroy or damage such electronic devices or otherwise make use of such sensitive appliances uncomfortable. Internal protection against lightning and overvoltage must be considered as an integrated system. For most family houses it is OK to install SPD type 1 and 2 at the line entry in the structure (the main distribution board where the circuit breakers for the whole house are located), i.e. FLP-B+C MAXI V(S)/3 for the wiring connected in TN-C or TN-C-S, or FLP-B+C MAXI V(S)/4 for the wiring in the TN-S network. For sensitive appliances inside the structure, it is sufficient to use overvoltage protection - SPD type 3, in combination with respective data protection. It should further be noted that antenna down conductors at the structure entry must also be considered. For such cases, we use the FX-090 F75 T current arrester. If the structure has ESS, EPS, or electronics to control the heating system, overvoltage protection SPD type 3 with vf filter type DA-275 DF 6 will be used to protect the supply 230 V AC, which will be installed in close proximity to the protected equipment. If the structure has photovoltaic panels installed on the roof, you need to protect the panels as well as the DC/AC inverter. Protection for photovoltaic equipment, e.g. the SLP-PV500 V/U type, is used to protect the DC part. The following examples show various options for connecting the structure to the distribution network. 8 TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/3+1 or SLP-275 V/4 DA-275 A CZ-275 A T3 T3 T2 TN-C – FLP-B+C MAXI V(S)/3 TN-C-S – FLP-B+C MAXI V(S)/3 TN-S – FLP-B+C MAXI V(S)/4 TN-C – FLP-12,5 V/3 TN-C-S – FLP-12,5 V/3 TN-S – FLP-12,5 V/4 T1 T2 T1 T2 Family houses ❶ A family house in a built-up area or a detached structure with or without a down conductor and external line on posts ❷ A family house in a built-up area without a down conductor and cable connection TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/3+1 or SLP-275 V/4 DA-275 A CZ-275 A T3 T3 T2 TN-C – FLP-12,5 V/3 TN-C-S – FLP-12,5 V/3 TN-S – FLP-12,5 V/4 T1 T2
  • 11. 9 Protection against lightning and overvoltage TN-C – FLP-12,5 V/3 TN-C-S – FLP-12,5 V/3 TN-S – FLP-12,5 V/4 T1 T2 T1 T2 Terraced houses ❸ Terrace houses with a common down conductor and external line ❹ Terrace houses with a common down conductor and cable connection TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/3+1 or SLP-275 V/4 TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/3+1 or SLP-275 V/4 DA-275 A DA-275 A CZ-275 A CZ-275 A T3 T3 T3 T3 T2 T2 TN-C – FLP-B+C MAXI V(S)/3 TN-C-S – FLP-B+C MAXI V(S)/3 TN-S – FLP-B+C MAXI V(S)/4
  • 12. 10 Protection against lightning and overvoltage T1 T2T TN-C – FLP-B+C MAXI V(S)/3 TN-C-S – FLP-B+C MAXI V(S)/3 TN-S – FLP-B+C MAXI V(S)/4 TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/3+1 or SLP-275 V/4 or SLP-275 V/4 T2 TN-C – SLP-275 V/1 TN-C-S – SLP-275 V/1 TN-S – SLP-275 V/1+1 T2 DA-275 A T3 CZ-275 A T3 T1 T2T TN-C – FLP-B+C MAXI V(S)/3 TN-C-S – FLP-B+C MAXI V(S)/3 TN-S – FLP-B+C MAXI V(S)/4 TN-C – FLP-12,5 V/3 TN-C-S – FLP-12,5 V/3 TN-S – FLP-12,5 V/4 T1 T2 TN-C – FLP-12,5 V/1 TN-C-S – FLP-12,5 V/1 TN-S – FLP-12,5 V/2 T1 T2 DA-275 A CZ-275 A T3 T3 Blocks of flats ❺ Blocks of flats with a cable connection without the possibility to install SPD type 1 in the unmeasured part ❻ Blocks of flats with a cable connection with the possibility to install SPD type 1 in the unmeasured part
  • 13. 11 Protection against lightning and overvoltage ❼ Administrative buildings DA-275 A T3 CZ-275 A T3 or TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/3+1 or SLP-275 V/4 T2 TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/3+1 or SLP-275 V/4 T2 T1 T2 TN-C – FLP-B+C MAXI V(S)/3 TN-C-S – FLP-B+C MAXI V(S)/3 TN-S – FLP-B+C MAXI V(S)/4 Remember protection of data, signal and communication lines see page 72 -73
  • 14. Protection against lightning and overvoltage 12 ❽ Administrative and industrial structures T1 T2 TN-C – FLP-B+C MAXI V(S)/3 TN-C-S – FLP-B+C MAXI V(S)/3 TN-S – FLP-B+C MAXI V(S)/4 TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/4 T2 DA-275 A T3 CZ-275 A T3 nebo TN-S – DA-275 DF25 T3 TN-S – DA-275 DF16 T3 TN-C – SLP-275 V/3 TN-C-S – SLP-275 V/3 TN-S – SLP-275 V/4 T2
  • 15. Protection against lightning and overvoltage 13 T1 TN-C – 3 pcs FLP-SG50 V(S) TN-C-S – 3 pcs FLP-SG50 V(S) TN-S – 4 pcs FLP-SG50 V(S) TN-S – DA-275 V/3+1 T3 TN-S – SLP-275 V/3+1 T2 TN-S – DA-275 V/3+1 T3 TN-S – DA-275 DF16 T3 TN-S – DA-275 DF25 T3 TN-S – SLP-275 V/3+1 T2 TN-S – SLP-275 V/3+1 T2 TN-S – FLP-12,5 V/3+1 T1 T2 Remember protection of data, signal and communication lines see page 72 -73
  • 16. 14 SPD SALTEK application in LV distribution networks Type of structure system main distribution board (in the structure) sub-distribution board (in the same structure) close to the equipment Family houses, administrative buildings, technologic units, industrial structures 3-phase TN-C FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 distance 10 m SLP-275 V/3(S) distance 5 m overvoltage protection to DIN rail: DA-275 V/1(S)+1 (to 63 A) DA-275 V/3(S)+1 (to 63 A) DA-275 DJ (to 16 A) overvoltage protection to a DIN rail with a vf filter DA-275 DFx (S) (x = 2, 6, 10, 16 A) DA-275 DF 25 for 25 A DA-275 DFIx (x = 1, 6, 10, 16 A) RACK-PROTECTOR multiple sockets to 19“stands CZ-275 A, DA-275 CZS DA-275 A, DA-275 S for additional assembly to the sockets and appliances sockets with overvoltage protection (ABB) XX-OVERDRIVE socket adapters distance 5 m place before the overvoltage protection RTO-xx (xx – rated current 16, 35 or 63 A) Number according to the connection type 1-phase TN-C 1x RTO-xx 1-phase TN-S 2x RTO-xx 3-phase TN-C 3x RTO-xx 3-phase TN-S 4x RTO-xx distance 50 m FLP-12,5 V/3(S) distance 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 (also with terminals to the equipment) distance 10 m SLP-275 V/3(S) distance 50 m FLP-12,5 V/3(S) distance 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 3-phase TN-S FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4 FLP-25-T1-VS/4, FLP-25-T1-V/4 distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4 (also with terminals to the equipment) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 3-phase TN-C-S FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 FLP-25-T1-VS/3, FLP-25-T1-V/3 distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 (also with terminals to the equipment) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 Blocks of flats with 12 or more apartments (SPD located in the apart. Distr. boards) 3-phase TN-C FLP-12,5 V/3(S) 3-phase TN-S FLP-12,5 V/4(S) 3-phase TN-C-S division in the apartment distr. board FLP-12,5 V/3(S) 1-phase TN-C FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1 1-phase TN-S FLP-12,5 V/2(S) Demanding applications (structures – operations clas- sified at the risk of explosion, chemical plants…, structures of a very high importance) 3-phase TN-C 3× FLP-SG50 V(S)/1 with terminals to the equipment 3× FLP-SG50 V(S)/1 + 1× SLP-275 V/3(S) distance 10 m 1× SLP-275 V/3(S) distance 10 m SLP-275 V/3(S) distance 50 m FLP-12,5 V/3(S) distance 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 3-phase TN-S 4× FLP-SG50 V(S)/1 with terminals to the equipment 4× FLP-SG50 V(S)/1 + 1× SLP-275 V/4(S) distance 10 m 1× SLP-275 V/4(S) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 3-phase TN-C-S division in the main distribution board 3× FLP-SG50 V(S)/1 with terminals to the equipment 3× FLP-SG50 V(S)/1 + 1× SLP-275 V/4(S) distance 10 m 1× SLP-385 V/4(S) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
  • 17. 15 SPD SALTEK application in LV distribution networks Type of structure system main distribution board (in the structure) sub-distribution board (in the same structure) close to the equipment Structures equipped with ESE (active down conductor) 3-phase TN-C 3x FLP-SG50 V(S)/1 distance 10 m SLP-275 V/3(S) distance 5 m overvoltage protection to DIN rail: DA-275 V/1(S)+1 (to 63 A) DA-275 V/3(S)+1 (to 63 A) DA-275 DJ (to 16 A) overvoltage protection to DIN rail with vf filter: DA-275 DFx (S) (x = 2, 6, 10, 16 A) DA-275 DF 25 for 25 A DA-275 DFIx (x = 1, 6, 10, 16 A) RACK-PROTECTOR multiple sockets for 19“ stands CZ-275 A, DA-275 CZS DA-275 A, DA-275 S For additional mounting to sockets and appliances Sockets with overvoltage protection (ABB) XX-OVERDRIVE Socket adapters distance 5 m SPD back-up RTO-xx (xx – rated current 16, 35 or 63 A) Number according to the connection type 1-phase TN-C 1x RTO-xx 1-phase TN-S 2x RTO-xx 3-phase TN-C 3x RTO-xx 3-phase TN-S 4x RTO-xx distance 10 m SLP-275 V/3(S) distance 50 m FLP-12,5 V/3(S) distance 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 also with terminals to the equipment 3x FLP-SG50 V(S)/1 + SLP-275 V/3(S) distance 10 m SLP-275 V/3(S) distance 50 m FLP-12,5 V/3(S) distance 100 m FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3 3-phase TN-S 4x FLP-SG50 V(S)/1 distance 10 m SLP-275 V/4(S) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 also with terminals to the equipment 4x FLP-SG50 V(S)/1 + SLP-275 V/4(S) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 3-phase TN-C-S 3x FLP-SG50 V(S)/1 distance 10 m SLP-275 V/4(S) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 also with terminals to the equipment 3x FLP-SG50 V(S)/1 + SLP-275 V/3(S) distance 10 m SLP-275 V/4(S) distance 50 m FLP-12,5 V/4(S) distance 100 m FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4 Technology with 1-phase connection 1-phase TN-C FLP-SG50 V(S)/1 with terminals to the equipment FLP-SG50 V(S)/1 + SLP-275 V/1(S) distance 10 m SLP-275 V/1(S) distance 10 m SLP-275 V/1(S) distance 50 m FLP-12,5 V/1(S) distance 100 m FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1 1-phase TN-S 2× FLP-SG50 V(S)/1 with terminals to the equipment 2× FLP-SG50 V(S)/1 + 1× SLP-275 V/2(S) distance 10 m 1× SLP-275 V/2(S) distance 10 m 1× SLP-275 V/2(S) distance 50 m 1× FLP-12,5 V/2(S) distance 100 m FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2 1-phase TN-C-S Division in the main distribution board FLP-SG50 V(S)/1 with terminals to the equipment FLP-SG50 V(S)/1 + SLP-275 V/1(S) distance 10 m 1× SLP-275 V/2(S) distance 10 m 1× SLP-275 V/2(S) distance 50 m 1× FLP-12,5 V/2(S) distance 100 m FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2
  • 18. FLP-SG50 V/1 FLP-SG50 VS/1 SPD type 1 – lightning current arrester Encapsulated high-performance spark gap with replaceable module, visual fault signalling To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects of direct or indirect lightning strikes in the most demanding applications in the heavy and chemicals industry, power stations, etc. Remote status signalling – version„S“. Dimension drawing Basic circuit diagram connection of signalization terminal Lightning Current Arresters 16 FLP-SG50 VS/1 Nominal voltage Un 230 V AC Maximum operating voltage Uc 255 V AC Nominal discharge current (8/20 μs) In 50 kA Lightning impulse current (10/350 μs) Iimp 50 kA Voltage protection level Up 2,5 kV Response time ta 100 ns Ability to independently switch off the following current Ifi 50 kA Nominal short circuit current ISCCR 50 kArms Maximum overcurrent protection 315 A gL/gG Maximum overcurrent protection for serial connection 125 A gL/gG TOV voltage UT 335 V/5 sec. Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard EN 61643-11:2012 Ordering number FLP-SG50 V/1 8595090540540 FLP-SG50 VS/1 8595090540533 Technical data 3666 45 90 9 15 L/N( ) L/N() (L/N) (L/N)
  • 19. Lightning Current Arresters SPD type 1 – lightning current arrester N-PE module, replaceable module To be installed in low-voltage distributions at the boundary of LPZ 0A–LPZ 1 zones and higher to prevent overvoltage effects of direct or indirect lightning strikes for the connection of SPD type 1 in the mode 1+1. Dimension drawing Basic circuit diagram FLP-A50N VS/NPE Technical data FLP-A50N VS/NPE Nominal voltage Un — Maximum operating voltage Uc 255V AC Nominal discharge current (8/20 μs) In 50 kA Maximum discharge current (8/20 μs) Imax 100 kA Lightning impulse current (10/350 μs) Iimp 50 kA Voltage protection level Up 1,5 kV Response time ta 100 ns Abilitytoindependentlyswitchoffthefollowingcurrent Ifi 100 A Short-circuitproofatmaximumovercurrentprotection — Maximum overcurrent protection — Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication no Remote indication * potential-free change-over contact Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090535737 * Remote signalling of N-PE module shows the presence of the replaceable module 17 90 45 66 36 9 15 N( ) N() (N) (N) connection of signalization terminal
  • 20. Lightning Current Arresters SPD type 1 – lightning current arrester N-PE module, replaceable module To be installed in low-voltage distributions at the boundary of LPZ 0A and LPZ 1 zones to prevent overvoltage effects of direct or indirect lightning strikes for the connection of SPD type 1 in the mode 3+1. Dimension drawing Basic circuit diagram FLP-A100N VS/NPE Technical data FLP-A100N VS/NPE Nominal voltage Un — Maximum operating voltage Uc 255V AC Nominal discharge current (8/20 μs)/pole In 100 kA Maximum discharge current (8/20 μs) Imax 100 kA Lighting impulse current (10/350 μs)/pole Iimp 100 kA Voltage protection level Up 1,5 kV Response time ta 100 ns Abilitytoindependentlyswitchoffthefollowingcurrent Ifi 100 A Short-circuit proof at maximum overcurrent protection — Maximum overcurrent protection — Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication no Remote indication * potential-free change-over contact Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090535744 * Remote signalling of N-PE module shows the presence of the replaceable module 18 90 45 66 36 9 15 N( ) N() (N) (N) connection of signalization terminal
  • 21. Lightning Current Arresters FLP-B+C MAXI V/1 FLP-B+C MAXI VS/1 Dimension drawing Basic circuit diagram SPD type 1 and type 2 versatile single-pole arrester Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage. Remote status signalling contact – version„S“. FLP-B+C MAXI VS/1 Nominal voltage Un 230 V AC Maximum operating voltage Uc 260 V AC Nominal discharge current (8/20 μs) In 30 kA Maximum discharge current (8/20 μs) Imax 60 kA Lightning impulse current (10/350 μs) Iimp 25 kA Voltage protection level Up 1,5 kV Response time ta 100 ns Ability to independently switch off the following current Ifi no following current Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 250 A gL/gG Maximum overcurrent protection for serial connection 125 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG : 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication red indication field Remote indication potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-B+C MAXI V/1 8595090550914 FLP-B+C MAXI VS/1 8595090535331 connection of signalization terminal 19 3666 45 90 9 15 (L/N) L/N( ) L/N() (L/N) Technical data
  • 22. SPD type 1 and type 2 2-pole (1+NPE) arrester for single phase TT (TNS) networks Total Iimp = 50 kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage. Remote status signalling contact – version„S“. Dimension drawing Basic circuit diagram Technical data L-N N-PE Nominal voltage Un 230 V AC — Maximum operating voltage Uc 260 V AC 255 V AC Nominal discharge current (8/20 μs) In 30 kA 50 kA Maximum discharge current Imax 60 kA 100 kA Lighting impulse current Iimp 25 kA 50 kA Voltage protection level Up 1,5 kV 1,5 kV Response time ta 100 ns 100 ns Abilitytoindependentlyswitchoffthe followingcurrent Ifi no following current 100 A Short-circuit proof at maximum overcurrent protection 50 kArms — Maximum overcurrent protection 250 A gL/gG — Maximum overcurrent protection for serial connection 125 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication red indication field no Remote indication* potential-free change-over contact potential-free change-over contact* Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 max. 1,5 mm2 Meets the requirements of standard EN 61643-11 + A11 EN 61643-11:2012 Ordering number FLP-B+C MAXI V/1+1 8595090550952 FLP-B+C MAXI VS/1+1 8595090537830 * Remote signalling of N-PE module shows the presence of the replaceable module FLP-B+C MAXI V/1+1 FLP-B+C MAXI VS/1+1 connection of signalization terminal Lightning Current Arresters 20 15 PE PE 7266 45 90 9 15 L L N N N N
  • 23. SPD type 1 and type 2 2-pole arrester for single phase TNS networks Total Iimp= 50 kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage. Remote status signalling contact – version„S“. Dimension drawing Basic circuit diagram Technical data FLP-B+C MAXI VS/2 Nominal voltage Un 230 V AC Maximum operating voltage Uc 260 V AC Nominal discharge current (8/20 μs)/pole In 30 kA Maximum discharge current (8/20 μs)/pole Imax 60 kA Lightning impulse current (10/350 μs)/pole Iimp 25 kA Voltage protection level Up 1,5 kV Response time ta 100 ns Ability to independently switch off the following current Ifi no following current Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 250 A gL/gG Maximum overcurrent protection for serial connection 125 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication red indication field Remote indication potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-B+C MAXI V/2 8595090550921 FLP-B+C MAXI VS/2 8595090537847 FLP-B+C MAXI V/2 FLP-B+C MAXI VS/2 connection of signalization terminal Lightning Current Arresters 21 15 7266 45 90 9 15 PE L/N L/N L/N L/N PE PE PE
  • 24. SPD type 1 and type 2 3-pole arrester for 3-phase TNC networks Total Iimp= 75 kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage. Remote status signalling contact – version„S“. Technical data FLP-B+C MAXI VS/3 Nominal voltage Un 230 V AC Maximum operating voltage Uc 260 V AC Nominal discharge current (8/20 μs)/pole In 30 kA Maximum discharge current (8/20 μs)/pole Imax 60 kA Lightning impulse current (10/350 μs)/pole Iimp 25 kA Voltage protection level Up 1,5 kV Response time ta 100 ns Ability to independently switch off the following current Ifi no following current Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 250 A gL/gG Maximum overcurrent protection for serial connection 125 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication red indication field Remote indication potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-B+C MAXI V/3 8595090550938 FLP-B+C MAXI VS/3 8595090535706 FLP-B+C MAXI V/3 FLP-B+C MAXI VS/3 connection of signalization terminal Dimension drawing Basic circuit diagram Lightning Current Arresters 22 90 45 66 108 9 15
  • 25. SPD type 1 and type 2 4-pole (3+NPE) arrester for 3-phase TT (TNS) networks Total Iimp= 100 kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage. Remote status signalling contact – version„S“. Dimension drawing Basic circuit diagram Technical data L-N N-PE Nominal voltage Un 230V AC — Maximum operating voltage Uc 260V AC 255V AC Nominal discharge current (8/20 μs)/pole In 30 kA 100 kA Maximum discharge current (8/20 μs) Imax 60 kA 100 kA Lighting impulse current (10/350 μs)/pole Iimp 25 kA 100 kA Voltage protection level Up 1,5 kV Voltage protection level (L - PE) Up 2,2 kV Response time ta 100 ns 100 ns Ability to independently switch off the following current Ifi no following current 100 A Short-circuit proof at maximum overcurrent protection 50 kArms — Maximum overcurrent protection 250 A gL/gG — Maximum overcurrent protection for serial connection 125 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication red indication field no Remote indication* potential-free change-over contact Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC61643-11ed.1.0 EN 61643-11:2012 Ordering number FLP-B+C MAXIV/3+1 8595090550969 FLP-B+C MAXIVS/3+1 8595090535720 * Remote signalling of N-PE module shows the presence of the replaceable module FLP-B+C MAXI V/3+1 FLP-B+C MAXI VS/3+1 connection of signalization terminal Lightning Current Arresters 23 Technical data 90 45 66 144 9 15
  • 26. Lightning Current Arresters SPD type 1 and type 2 4-pole arrester for 3-phase TNS networks Total Iimp= 100 kA (10/350) Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage (230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones. Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow current, no leakage current and low residual voltage. Remote status signalling contact – version„S“. Dimension drawing Basic circuit diagram FLP-B+C MAXI V/4 FLP-B+C MAXI VS/4 connection of signalization terminal Technical data FLP-B+C MAXI VS/4 Nominal voltage Un 230 V AC Maximum operating voltage Uc 260 V AC Nominal discharge current (8/20 μs)/pole In 30 kA Maximum discharge current (8/20 μs)/pole Imax 60 kA Lighting impulse current (10/350 μs)/pole Iimp 25 kA Voltage protection level Up 1,5 kV Response time ta 100 ns Ability to independently switch off the following current Ifi no following current Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 250 A gL/gG Maximum overcurrent protection for serial connection 125 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected condutors Solid min/max ISO: 2,5/50 mm2 ; AWG: 13/1 Stranded min/max ISO: 2,5/35 mm2 ; AWG: 13/2 Visual fault indication red indication field Remote indication potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-B+C MAXI V/4 8595090550945 FLP-B+C MAXI VS/4 8595090535713 24 66 45 90 144 9 15
  • 27. Lightning Current Arresters SPD type 1 and type 2 versatile single-pole arrester Varistor lightning and surge current arrester to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. Dimension drawing Basic circuit diagram Technical data FLP-12,5 V/1 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs) In 30 kA Maximal discharge current Imax 60 kA Lightning impulse current (10/350 μs) Iimp 12,5 kA Voltage protection level Up 1,2 kV Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-12,5 V/1 8595090534211 FLP-12,5 V/1 S 8595090534228 FLP-12,5 V/1 FLP-12,5 V/1 S connection of signalization terminal 25
  • 28. L-N N-PE Nominal voltage Un 230V AC — Maximum operating voltage Uc 275V AC 255V AC Nominal discharge current (8/20 μs) In 30 kA 30 kA Maximal discharge current (8/20 μs) Imax 60 kA 60 kA Lightning impulse current (10/350 μs) Iimp 12,5 kA 25 kA Voltage protection level Up 1,2 kV 1,5 kV Voltage protection level@I =5kA(8/20μs) Up 0,9 kV — Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 100 ns Abilityindependentlyswitchoffthefollowingcurrent Ifi no following current 100 A Short-circuitproofatmaximumovercurrentprotection 50 kArms — Maximum overcurrent protection 160 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC — Cross-sectionofremoteindicationconductors max. 1,5 mm2 — Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 Orderingnumber FLP-12,5V/1+1 8595090534235 FLP-12,5V/1S+1 8595090534242 Lightning Current Arresters SPD type 1 and type 2 2-pole (1+NPE) arrester for single phase TT(TNS) networks Total Iimp= 25 kA (10/350) Varistor lightning and surge current arrester and heavy duty encapsulated spark gap to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. FLP-12,5 V/1+1 FLP-12,5 V/1S+1 Dimension drawing Basic circuit diagram connection of signalization terminal Technical data 26
  • 29. Lightning Current Arresters SPD type 1 and type 2 – lightning current arrester Replaceable varistor module, visual fault signalling 2-pole varistor lightning current arrester to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling (S). Dimension drawing Basic circuit diagram FLP-12,5 V/2 FLP-12,5 V/2S connection of signalization terminal Technical data FLP-12,5 V/2 Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 30 kA Maximal discharge current/pole Imax 60 kA Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA Voltage protection level Up 1,2 kV Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures - 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-12,5 V/2 8595090538097 FLP-12,5 V/2S 8595090551829 27 L PE N
  • 30. FLP-12,5 V/3 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 30 kA Maximal discharge current/pole Imax 60 kA Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA Voltage protection level Up 1,2 kV Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-12,5 V/3 8595090534259 FLP-12,5 V/3 S 8595090534266 Lightning Current Arresters SPD type 1 and type 2 3-pole arrester for 3-phase TNC networks Total Iimp= 37,5 kA (10/350) Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. Technical data FLP-12,5 V/3 FLP-12,5 V/3 S Dimension drawing Basic circuit diagram connection of signalization terminal 28
  • 31. L-N N-PE Nominal voltage Un 230V AC — Maximum operating voltage Uc 275V AC 255V AC Nominal discharge current (8/20 μs) In 30 kA 50 kA Maximal discharge current (8/20 μs) Imax 60 kA 100 kA Lightning impulse current (10/350 μs) Iimp 12,5 kA 50 kA Voltage protection level Up 1,2 kV 1,5 kV Voltage protection level@I =5kA(8/20μs) Up 0,9 kV — Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 100 ns Abilityindependentlyswitchoffthefollowingcurrent Ifi no following current 100 A Short-circuitproofatmaximumovercurrentprotection 50 kArms — Maximum overcurrent protection 160 A gL/gG — Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC — Cross-sectionofremoteindicationconductors max. 1,5 mm2 — Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 Orderingnumber FLP-12,5V/3+1 8595090534273 FLP-12,5V/3S+1 8595090534280 Lightning Current Arresters SPD type 1 and type 2 4-pole (3+NPE) arrester for 3-phase TT (TNS) networks Total Iimp= 50 kA (10/350) Varistor lightning and surge current arresters and fixed N-PE modul with heavy duty encapsulated spark gap. To be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. FLP-12,5 V/3+1 FLP-12,5 V/3S+1 Dimension drawing Basic circuit diagram connection of signalization terminal Technical data 29
  • 32. Lightning Current Arresters SPD type 1 and type 2 4-pole arrester for 3-phase TNS networks Total Iimp= 50 kA (10/350) Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. Dimension drawing Basic circuit diagram Technical data FLP-12,5 V/4 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 30 kA Maximal discharge current/pole Imax 60 kA Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA Voltage protection level Up 1,2 kV Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number FLP-12,5 V/4 8595090534297 FLP-12,5 V/4 S 8595090534303 FLP-12,5 V/4 FLP-12,5 V/4 S connection of signalization terminal 30
  • 33. Lightning Current Arresters SPD type 1 and type 2 versatile single-pole arrester Varistor lightning and surge current arrester to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. * Version UC =385 V available on request Dimension drawing Basic circuit diagram FLP-7-V/1 FLP-7-V/1 S FLP-7-V/1 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs) In 30 kA Maximum discharge current Imax 60 kA Lightning impulse current (10/350 μs) Iimp 7 kA Voltage protection level Up 1,2 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 connection of signalization terminal 31 Technical data
  • 34. Lightning Current Arresters SPD type 1 and type 2 2-pole (1+NPE) arrester for single phase TT (TNS) networks Varistor lightning and surge current arrester and heavy duty encapsulated spark gap in the mode 1+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. * Version UC =385 V available on request FLP-7-V/1+1 FLP-7-V/1S+1 Dimension drawing Basic circuit diagram connection of signalization terminal Technical data L-N N-PE Nominal voltage Un 230V AC — Maximum operating voltage Uc 275V AC 255V AC Nominal discharge current (8/20 μs) In 30 kA 30 kA Maximum discharge current (8/20 μs) Imax 60 kA 60 kA Lighting impulse current (10/350 μs) Iimp 7 kA 25 kA Voltage protection level Up 1,2 kV 1,5 kV Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 25 ns Ability to independently switch off the following current Ifi no following current 100 A Short-circuit proof at maximum overcurrent protection 50 kArms — Maximum overcurrent protection 160 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected condutors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field ne Remote indication – S design potential-free change-over contact — Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC — Cross-section of remote indication conductors max. 1,5 mm2 — Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 32
  • 35. Lightning Current Arresters SPD type 1 and type 2 2-pole arrester for 3-phase TNC networks Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. * Version UC =385 V available on request FLP-7-V/2 FLP-7-V/2 S Dimension drawing Basic circuit diagram connection of signalization terminal L PE N FLP-7-V/2 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs) In 30 kA Maximum discharge current Imax 60 kA Lightning impulse current (10/350 μs) Iimp 7 kA Voltage protection level Up 1,2 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Technical data 33
  • 36. Lightning Current Arresters SPD type 1 and type 2 3-pole arrester for 3-phase TNC networks Total Iimp= 21 kA (10/350) Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. * Version UC =385 V available on request Dimension drawing Basic circuit diagram Technical data FLP-7-V/3 Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 30 kA Maximum discharge current (8/20 μs)/pole Imax 60 kA Lightning impulse current (10/350 μs)/pole Iimp 7 kA Voltage protection level Up 1,2 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 FLP-7-V/3 FLP-7-V/3 S connection of signalization terminal 34
  • 37. Lightning Current Arresters SPD type 1 and type 2 4-pole (3+NPE) arrester for 3-phase TT (TNS) networks Total Iimp= 25 kA (10/350) Varistor lightning and surge current arresters and heavy duty encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 0B and LPZ 1 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. * Version UC =385 V available on request FLP-7-V/3+1 FLP-7-V/3S+1 Technical data L-N N-PE Nominal voltage Un 230V AC — Maximum operating voltage Uc 275V AC 255V AC Nominal discharge current (8/20 μs)/pole In 30 kA 30 kA Maximum discharge current (8/20 μs)/pole Imax 60 kA 60 kA Lighting impulse current (10/350 μs)/pole Iimp 7 kA 25 kA Voltage protection level Up 1,2 kV 1,5 kV Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 100 ns Ability to independently switch off the following current Ifi no following current 100 A Short-circuit proof at maximum overcurrent protection 50 kArms — Maximum overcurrent protection 160 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected condutors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC — Cross-section of remote indication conductors max. 1,5 mm2 — Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 Dimension drawing Basic circuit diagram connection of signalization terminal 35
  • 38. Lightning Current Arresters SPD type 1 and type 2 4-pole arrester for 3-phase TNS networks Total Iimp= 28 kA (10/350) Varistor lightning and surge current arresters to be installed in low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones and higher to prevent overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. * Version UC =385 V available on request Dimension drawing Basic circuit diagram Technical data FLP-7-V/4 Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 30 kA Maximum discharge current (8/20 μs)/pole Imax 60 kA Lighting impulse current (10/350 μs)/pole Iimp 7 kA Voltage protection level Up 1,2 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected condutors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 FLP-7-V/4 FLP-7-V/4 S connection of signalization terminal 36
  • 39. Surge Arresters Dimension drawing Basic circuit diagram Technical data SLP-075 V/1 SLP-150 V/1 SLP-275 V/1 SLP-385 V/1 SLP-440 V/1 SLP-600 V/1 Nominal voltage Un — 120V AC 230V AC — 400V AC — Maximum operating voltage Uc 75V AC / 100V DC 150V AC / 200V DC 275V AC / 350V DC 385V AC / 500V DC 440V AC / 585V DC 600V AC Maximum operating voltage of varistor — — — — — 880V AC Nominal discharge current (8/20 μs) In 15 kA 15 kA 20 kA 20 kA 20 kA 15 kA Maximum discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA Voltageprotectionlevel @I=5kA(8/20μs) Up 0,3 kV 0,45 kV 0,9 kV 1,3 kV 1,5 kV 2,7 kV Voltage protection level Up 0,4 kV 0,6 kV 1,35 kV 1,8 kV 1,9 kV 3,2 kV Response time ta 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns Short-circuitproofatmaximumovercurrentprotection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms Maximum overcurrent protection 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gG 125 A gL/gG 100 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090518150 8595090551850 8595090516170 8595090519553 8595090518174 8595090533016 SLP-075 V/1 SLP-150 V/1 SLP-275 V/1 SLP-385 V/1 SLP-440 V/1 SLP-600 V/1 37 SPD type 2 versatile single-pole arrester Varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage.
  • 40. connection of signalization terminal Surge Arresters Dimension drawing Basic circuit diagram Technical data SLP-075 V/1 S SLP-150 V/1 S SLP-275 V/1 S SLP-385 V/1 S SLP-440 V/1 S SLP-600 V/1 S Nominal voltage Un — 120V AC 230V AC — 400V AC — Maximum operating voltage Uc 75V AC / 100V DC 150V AC / 200V DC 275V AC / 350V DC 385V AC / 500V DC 440V AC / 585V DC 600V AC Maximum operating voltage of varistor — — — — — 880V AC Nominal discharge current (8/20 μs) In 15 kA 15 kA 20 kA 20 kA 20 kA 15 kA Maximum discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA Voltageprotectionlevel @I=5kA(8/20μs) Up 0,3 kV 0,45 kV 0,9 kV 1,3 kV 1,5 kV 2,7 kV Voltage protection level Up 0,4 kV 0,6 kV 1,35 kV 1,8 kV 1,9 kV 3,2 kV Response time ta 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns Short-circuitproofatmaximumovercurrentprotection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms Maximum overcurrent protection 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gG 125 A gL/gG 100 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S version potential-free change-over contact Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090518235 8595090551867 8595090516187 8595090527718 8595090518259 8595090533023 SLP-075 V/1 S SLP-150 V/1 S SLP-275 V/1 S SLP-385 V/1 S SLP-440 V/1 S SLP-600 V/1 S 38 SPD type 2 versatile single-pole arrester Varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Remote status signalling – version„S“.
  • 41. Surge Arresters SPD type 2 – surge arrester 2-pole (1+NPE) arrester for single phase TT (TNS) networks Combination of varistor surge protection and an encapsulated spark gap connected in the mode 1+1. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. Dimension drawing Basic circuit diagram Technical data L-N N-PE Nominal voltage Un 230 V AC — Maximum operating voltage Uc 275 V AC 255 V AC Nominal discharge current (8/20 μs) In 20 kA 20 kA Maximum discharge current (8/20 μs) Imax 40 kA 40 kA Lighting impulse current (10/350 μs) Iimp — 12 kA Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV — Voltage protection level Up 1,35 kV 1,5 kV Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 100 ns Ability to independently switch off the following current Ifi no following current 100 A Short-circuit proof at maximum overcurrent protection 50 kArms — Maximum overcurrent protection 160 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC — Cross-section of remote indication conductors max. 1,5 mm2 — Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number SLP-275 V/1+1 8595090519485 SLP-275 V/1S+1 8595090524915 SLP-275 V/1+1 SLP-275 V/1S+1 connection of signalization terminal 39
  • 42. Surge Arresters SPD type 2 – surge arrester Replaceable varistor module, visual fault signalling 2-pole varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling(S). SLP-275 V/2 SLP-275 V/2 S Dimension drawing Basic circuit diagram connection of signalization terminal Technical data SLP-275 V/2 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 20 kA Maximum discharge current (8/20 μs)/pole Imax 40 kA Lighting impulse current (10/350 μs) Iimp — Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV Voltage protection level Up 1,35 kV Response time ta 25 ns Ability to independently switch off the following current Ifi no following current Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 6163-11:2012 Ordering number SLP-275 V/3 8595090516194 SLP-275 V/3S 8595090551836 40 L PE N
  • 43. Surge Arresters SPD type 2 – surge arrester 3-pole arrester for 3-phase TNC networks 3-pole varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. SLP-275 V/3 SLP-275 V/3S Dimension drawing Basic circuit diagram connection of signalization terminal Technical data SLP-275 V/3 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 20 kA Maximum discharge current (8/20 μs)/pole Imax 40 kA Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV Voltage protection level Up 1,35 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number SLP-275 V/3 8595090517603 SLP-275 V/3 S 8595090517610 41
  • 44. Surge Arresters SPD type 2 – surge arrester 4-pole (3+NPE) arrester for 3-phase TT (TNS) networks Combination of 3-pole varistor surge protection and an encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. Dimension drawing Basic circuit diagram Technical data L-N N-PE Nominal voltage Un 230 V AC — Maximum operating voltage Uc 275 V AC 255 V AC Nominal discharge current (8/20 μs)/pole In 20 kA 20 kA Maximum discharge current (8/20 μs)/pole Imax 40 kA 40 kA Lighting impulse current (10/350 μs) Iimp — 12 kA Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV — Voltage protection level Up 1,35 kV 1,5 kV Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 100 ns Ability to independently switch off the following current Ifi no following current 100 A Short-circuit proof at maximum overcurrent protection 50 kArms — Maximum overcurrent protection 160 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC — Cross-section of remote indication conductors max. 1,5 mm2 — Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number SLP-275 V/3+1 8595090519461 SLP-275 V/3S+1 8595090520023 SLP-275 V/3+1 SLP-275 V/3S+1 connection of signalization terminal 42
  • 45. Surge Arresters SPD type 2 – surge arrester 4-pole arrester for 3-phase TNS networks 4-pole varistor surge protection to be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones to protect the distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. SLP-275 V/4 SLP-275 V/4S Dimension drawing Basic circuit diagram connection of signalization terminal Technical data SLP-275 V/4 S Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC / 350 V DC Nominal discharge current (8/20 μs)/pole In 20 kA Maximum discharge current (8/20 μs)/pole Imax 40 kA Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV Voltage protection level Up 1,35 kV Response time ta 25 ns Short-circuit proof at maximum overcurrent protection 50 kArms Maximum overcurrent protection 160 A gL/gG Degree of protection IP 20 Range of operating temperatures – 40 °C … + 80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number SLP-275 V/4 8595090517221 SLP-275 V/4 S 8595090517634 43
  • 46. Surge Arresters Dimension drawing Basic circuit diagram Technical data SLP-075 VB/1 SLP-130 VB/1 SLP-275 VB/1 Nominal voltage Un — 110 V AC 230 V AC Maximum operating voltage Uc 75 V AC / 100 V DC 135 V AC / 175 V DC 275 V AC / 350 V DC Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA Maximum discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA Voltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,5 kV 0,9 kV Voltage protection level Up 0,6 kV 0,7 kV 1,2 kV Response time ta 100 ns 100 ns 100 ns Short-circuit proof at maximum overcurrent protection 35 kArms 35 kArms 35 kArms Maximum overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG Degree of protection IP 20 IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field red indication field red indication field Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090521556 8595090521822 8595090519447 SLP-075 VB/1 SLP-130 VB/1 SLP-275 VB/1 SPD type 2 – surge arrester Replaceable module, visual fault signalling Efficient varistor connected in series with an encapsulated spark gap. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage in areas with higher storm activity or to protect measuring circuits as a 1st protection level. In idle state it has very little leakage current, which remains stable for the duration of the service life; protective elements are not subject to ageing. 44
  • 47. Surge Arresters Dimension drawing Basic circuit diagram Technical data SLP-075 VB/1 S SLP-130 VB/1 S SLP-275 VB/1 S Nominal voltage Un — 110 V AC 230 V AC Maximum operating voltage Uc 75 V AC / 100 V DC 135 V AC / 175 V DC 275 V AC / 350 V DC Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA Maximum discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA Voltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,5 kV 0,9 kV Voltage protection level Up 0,6 kV 0,7 kV 1,2 kV Response time ta 100 ns 100 ns 100 ns Short-circuit proof at maximum overcurrent protection 35 kArms 35 kArms 35 kArms Maximum overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG Degree of protection IP 20 IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field red indication field red indication field Remote indication – S design potential-free change-over contact Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC Cross-section of remote indication conductors max. 1,5 mm2 Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 IEC 61643-11 ed. 1.0 EN 61643-11:2012 Ordering number 8595090521563 8595090529965 8595090519454 SLP-075 VB/1 S SLP-130 VB/1 S SLP-275 VB/1 S SPD type 2 – surge arrester Replaceable module, visual fault signalling Efficient varistor connected in series with an encapsulated spark gap. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage in areas with higher storm activity or to protect measuring circuits as a 1st protection level. In idle state it has very little leakage current, which remains stable for the duration of the service life; protective elements are not subject to ageing. Remote status signalling – version„S“. connection of signalization terminal 45
  • 48. Surge Arresters SPD type 2 – surge arrester Efficient varistor connected in series with an encapsulated spark gap. To be installed in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to protect distributions and equipment against the overvoltage effects induced during a lightning strike and to prevent switching overvoltage in areas with higher storm activity or to protect measuring circuits as a 1st protection level. In idle state it has very little leakage current, which remains stable for the duration of the service life; protective elements are not subject to ageing. Optional remote status signalling (S). Technical data L-N N-PE Maximum operating voltage Uc 275 V AC 255 V AC Nominal discharge current (8/20 μs) In 20 kA 20 kA Maximum discharge current (8/20 μs) Imax 25 kA 40 kA Voltage protection level Up 1,2 kV 1,5 kV Voltage protection level (L-PE) Up 2,0 kV Response time ta 100 ns 100 ns Ability to independently switch off the following current Ifi no following current 100 A Short-circuit proof at maximum overcurrent protection 35 kArms — Maximum overcurrent protection 125 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC — Cross-section of remote indication conductors max. 1,5 mm2 — Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 6163-11:2012 IEC 61643-11 ed. 1.0 EN 6163-11:2012 Ordering number SLP-275 VB/3+1 8595090533108 SLP-275 VB/3S+1 8595090533115 SLP-275 VB/3+1 SLP-275 VB/3S+1 Dimension drawing Basic circuit diagram connection of signalization terminal 46
  • 49. Surge Arresters SPD type 3 – surge arrester Replaceable module, visual fault signalling Combination of varistor surge protection and an encapsulated spark gap connected in the mode 1+1. To be installed in low- voltage distributions at the boundary of LPZ 2 and LPZ 3 zones to protect distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. Dimension drawing Basic circuit diagram Technical data L-N N-PE Nominal voltage Un 230 V AC — Maximum operating voltage Uc 275 V AC 255 V AC Nominal discharge current (8/20 μs) In 5 kA 10 kA Test voltage Uoc 10 kV 20 kV Voltage protection level Up 1 kV 1,5 kV Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 100 ns Maximum overcurrent protection 63 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC — Cross-section of remote indication conductors max. 1,5 mm2 — Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012 Ordering number DA-275 V/1+1 8595090518723 DA-275 V/1S+1 8595090519751 DA-275 V/1+1 DA-275 V/1S+1 connection of signalization terminal 47
  • 50. Surge Arresters SPD type 3 – surge arrester Replaceable module, visual fault signalling Combination of 3-pole varistor surge protection and an encapsulated spark gap connected in the mode 3+1. To be installed in low-voltage distributions at the boundary of LPZ 2 and LPZ 3 zones to protect distributions and equipment against overvoltage effects induced during a lightning strike and to prevent switching overvoltage. Optional remote status signalling – version„S“. Dimension drawing Basic circuit diagram Technické parametry L-N N-PE Nominal voltage Un 230 V AC — Maximum operating voltage Uc 275 V AC 255 V AC Nominal discharge current (8/20 μs)/pole In 5 kA 10 kA Test voltage Uoc 10 kV 20 kV Voltage protection level Up 1 kV 1,5 kV Voltage protection level (L - PE) Up 1,5 kV Response time ta 25 ns 100 ns Maximum overcurrent protection 63 A gL/gG — Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid min/max ISO: 1/35 mm2 ; AWG: 17/2 ISO: 1/35 mm2 ; AWG: 17/2 Stranded min/max ISO: 1/25 mm2 ; AWG: 17/4 ISO: 1/25 mm2 ; AWG: 17/4 Fault indication red indication field no Remote indication – S design potential-free change-over contact — Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC — Cross-section of remote indication conductors max. 1,5 mm2 — Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012 Ordering number DA-275 V/3+1 8595090518488 DA-275 V/3S+1 8595090518495 DA-275 V/3+1 DA-275 V/3S+1 connection of signalization terminal 48
  • 51. Surge Arresters SPD type 3 – surge arrester Visual fault signalling Surge protection designed to protect all types of electric and electronic equipment connected to a low-voltage distribution against pulse overvoltage. Dimension drawing Basic circuit diagram Technical data DA-075 DJ DA-130 DJ DA-275 DJ Nominal voltage Un — 110 V AC 230 V AC Maximum operating voltage Uc 75 V AC 130 V AC 275 V AC Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 2 kA, 2 kA, 4 kA 2,5 kA, 2,5 kA, 5 kA 3 kA, 3 kA, 5 kA Test voltage L-N, L(N)-PE, L+N-PE Uoc 4 kV, 4 kV, 8 kV 5 kV, 5 kV, 10 kV 6 kV, 6 kV, 10 kV Voltage protection level L-N, L(N)-PE Up 0,4 kV, 1,2 kV 0,6 kV, 1,5 kV 1,2 kV, 1,6 kV Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns 25 ns, 100 ns Short-circuit proof at maximum overcurrent protection 6 kArms 6 kArms 6 kArms Maximum overcurrent protection 16 A gL/gG; B 16 A 16 A gL/gG; B 16 A 16 A gL/gG; B 16 A Degree of protection IP 20 IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid max ISO: 6 mm2 ; AWG: 10 ISO: 6 mm2 ; AWG: 10 ISO: 6 mm2 ; AWG: 10 Stranded max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 Fault indication red indicator red indicator red indicator Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012 EN 61643-11:2012 Ordering number 8595090533191 8595090521891 8595090506362 DA-075 DJ DA-130 DJ DA-275 DJ 49
  • 52. Surge Arresters Dimension drawing Basic circuit diagram SPD type 3 – surge arrester with RFI filter Visual fault signalling Surge protection with an integrated RFI filter designed to protect MC, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance. DA-275 DF2 DA-275 DF6 Nominal voltage Un 230 V AC 230 V AC Maximum operating voltage Uc 275 V AC 275 V AC Nominal load current IL 2 A 6 A Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 2 kA, 2 kA, 4 kA 2 kA, 2 kA, 4 kA Test voltage L-N, L(N)-PE, L+N-PE Uoc 4 kV, 4 kV, 8 kV 4 kV, 4 kV, 8 kV Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns Maximum overcurrent protection 2 A gL/gG or B 2 A 6 A gL/gG or B 6 A Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 Stranded max ISO: 2,5 mm2 ; AWG: 13 ISO: 2,5 mm2 ; AWG: 13 Fault indication red indicator red indicator Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11 Ordering number 8595090506706 8595090506713 Technické parametry DA-275 DF 2 DA-275 DF 6 50
  • 53. DA-275 DF2 S DA-275 DF6 S Nominal voltage Un 230 V AC 230 V AC Maximum operating voltage Uc 275 V AC 275 V AC Nominal load current IL 2 A 6 A Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns Maximum overcurrent protection 2 A gL/gG or B 2 A 6 A gL/gG or B 6 A Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 Stranded max ISO: 2,5 mm2 ; AWG: 13 ISO: 2,5 mm2 ; AWG: 13 Fault indication red indicator red indicator Remote indication – S design potential-free change-over contact potential-free change-over contact Remote indication contacts AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A Cross-section of connected conductors Solid max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 Stranded max ISO: 2,5 mm2 ; AWG: 13 ISO: 2,5 mm2 ; AWG: 13 Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11 Ordering number 8595090516248 8595090516255 Technical data Surge Arresters Dimension drawing Basic circuit diagram SPD type 3 – surge arrester with RFI filter Remote and visual fault signalling Surge protection with an integrated RFI filter designed to protect MC, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance. DA-275 DF 2 S DA-275 DF 6 S 51 Dálková signalizace
  • 54. Surge Arresters SPD type 3 – surge arrester with RFI filter Visual fault signalling Surge protection with an integrated RFI filter designed to protect MC, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance. Dimension drawing Basic circuit diagram Technical data DA-275 DF10 DA-275 DF16 Nominal voltage Un 230 V AC 230 V AC Maximum operating voltage Uc 275 V AC 275 V AC Nominal load current IL 10 A 16 A Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns Maximum overcurrent protection 10 A gL/gG nebo C10 A 16 A gL/gG nebo C16 A Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 Stranded max ISO: 2,5 mm2 ; AWG: 13 ISO: 2,5 mm2 ; AWG: 13 Fault indication red indicator red indicator Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11 Ordering number 8595090506720 8595090506737 DA-275 DF 10 DA-275 DF 16 52
  • 55. Technical data DA-275 DF10 S DA-275 DF16 S Nominal voltage Un 230 V AC 230 V AC Maximum operating voltage Uc 275 V AC 275 V AC Nominal load current IL 10 A 16 A Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns Maximum overcurrent protection 10 A gL/gG or B 10 A 16 A gL/gG or B 16 A Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB Degree of protection IP 20 IP 20 Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C Mounting on DIN rail 35 mm DIN rail 35 mm Cross-section of connected conductors Solid max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 Stranded max ISO: 2,5 mm2 ; AWG: 13 ISO: 2,5 mm2 ; AWG: 13 Fault indication red indicator red indicator Remote indication potential-free change-over contact potential-free change-over contact Remote indication contacts AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A Cross-section of connected conductors Solid max ISO: 4 mm2 ; AWG: 11 ISO: 4 mm2 ; AWG: 11 Stranded max ISO: 2,5 mm2 ; AWG: 13 ISO: 2,5 mm2 ; AWG: 13 Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11 Ordering number 8595090516262 8595090516279 Dimension drawing Basic circuit diagram Surge Arresters SPD type 3 – surge arrester with RFI filter Remote fault signalling Surge protection with an integrated RFI filter designed to protect MC, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance. DA-275 DF 10 S DA-275 DF 16 S 53 Dálková signalizace
  • 56. Surge Arresters SPD type 3 – surge arrester with RFI filter Visual fault signalling Surge protection with an integrated RFI filter designed to protect MC, ESS, EFS, etc. control systems against pulse overvoltage and RF disturbance. Dimension drawing Basic circuit diagram Technical data DA-275 DF25 Nominal voltage Un 230 V AC Maximum operating voltage Uc 275 V AC Nominal load current IL 25 A Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV Response time L-N, L(N)-PE ta 25 ns, 100 ns Maximum overcurrent protection 25 A gL/gG or C 25 A Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB Degree of protection IP 20 Range of operating temperatures –40 °C … +80 °C Mounting on DIN rail 35 mm Cross-section of connected conductors Solid max ISO: 1/50 mm2 ; AWG: 17/1 Stranded max ISO: 1/35 mm2 ; AWG: 17/2 Fault indication red indicator Meets the requirements of standard EN 61643-11 + A11 Ordering number 8595090537328 DA-275 DF 25 54 72