2. SALTEK®
is a leading Czech company specialised in the development and production of surge protection devices.
It offers a broad range of lightning current arresters and surge protection type 1–3 according to EN 61643-11 (or B, C
and D according to E DIN VDE 0675-6) and surge protection for information technology, measurement and control and
telecommunications.
SALTEK®
products provide protection against the lightning and technological overvoltage and thereby rise the safety and
trouble-free operation of the technologies, machinery and appliances at the industry, telecommunications, data centers, office
buildings even in ordinary houses.
SALTEK®
was founded in 1995. Successful business activities abroad, in many countries of three continents, are provided by
subsidiaries SALTEK®
TRADE.
The principle of dynamic company expansion consists in its own product development. A team of experienced development
engineers works in test development laboratory with unique devices and technologies. The sophisticated materials, design
processes, technologies and measurement methods are used for the development of SALTEK®
products. Production is
equipped with automatic and robotized assembly lines.
Special attention is focused on the quality of products. SALTEK®
has implemented Integrated Management System IMS,
according to international standards, which consists of Quality management system under EN ISO 9001, Environmental
protection management under EN ISO 14001 and Health and safety management system under OHSAS 18001.
System IMS is annually verified by external auditing company TÜV NORD Czech.
SALTEK®
is focused on quality, but also to design of products. Line of surge protection devices with unique color coding
has been awarded a design prize Red Dot®
2014.
3. SALTEK
Choose from our comprehensive range of surge
protection devices:
1
SPD type 1 – lightning current arresters
SPD type 1 and 2 – B+C combined arresters
SPD type 2 – surge arresters
SPD type 3 – surge arresters
SPD type 3 – surge protective devices with a RFI filter
SPD type 3 – surge protective devices for additional mounting
Surge separation inductor
SPD for photovoltaic systems
Surge arresters for measurement and control,
electronic security systems, EPS and telecommunications
Surge arresters for Ethernet and video lines
Lightning arresters and surge arresters for coaxial lines
Accessories
page 16
page 19
page 37
page 47
page 50
page 60
page 63
page 65
page 74
page 95
page 103
page 108
4. 1. Introduction – Legislative
The use of modern sophisticated equipment,
consumer electronics and control systems
places high demands on their electromagnetic
compatibility. Modern electronic control
systems provided with circuits with a very high
integration level are becoming more and more
sensitive to electromagnetic disturbance and
overvoltage. The installation of surge protections
according to effective legal standards will
reduce the danger of their being damaged to a
minimum.
Technical designs are defined by standards
harmonised with EU standards:
a) Protective bonding to the same potential
including the conductor cross section for the
main and additional bonding is defined by
standards EN 50310 ed. 2. , IEC 60364-5-54,
IEC 60364-4-41
b) Lightning protection is specified in the
EN 62305 collection of new standards,
harmonised with European standards.
EN 62305 – 1 deals with general principles.
Lightning
protection
level
Maximum lightning
parameter according to LPL
LPL First short discharge
LPL I 200 kA
LPL II 150 kA
LPL III 100 kA
LPL IV 100 kA
IEC/EN 62305 – 2 – deals with the risk
assessment for buildings or engineering
networks struck by lightning.
IEC/EN 62305 – 3 – deals with the proposal
for external lightning protection (lightning
conductor).
IEC/EN 62305 – 4 – deals with protective
measures resulting in the reduction of failures
of electrical and electronic systems inside the
building (zone protection)
c) Classification of protections is set forth in
standard EN 61643-11.
Devices are classified into three basic categories:
SPD type 1 – lightning current arresters
SPD type 2 – surge arresters
SPD type 3 – surge arresters
d) Classification of low-voltage distribution
into impulse resistance categories, including
specification of the maximum allowed
overvoltage is determined in standard
EN 60664-1
Protection against lightning and overvoltage
Rated impulse for equipment (acc. to EN 60664-1) or Impulse-withstand voltage.
Lightning protection zones
The standard EN 62305-4 defines lightning
protection zones LPZ in view of the direct and
indirect (electromagnetic pulse – LEMP) lightning
effect:
LPZ 0A – free area (possibility of a direct
lightning strike, non-attenuated LEMP)
LPZ 0B – lightning conductor receiver
protection area (direct lightning strike
protection, non-attenuated LEMP)
LPZ 1 – inside a building (direct lightning strike
is eliminated, attenuated LEMP – depending
upon shielding)
LPZ 2 – inside a room – e.g. a server room with
a conductive floor, FeAl floors and wall lining
(further attenuation of LEMP in connection with
a higher shielding level)
LPZ 3 – inside a metal box (e.g. 19“ RACK)
Lightning and surge protection
Example of main and additional bonding
telephone cable
gas pipeline
water pipeline
base ground
main protective bonding bar
2
Insulation coordination
lift
flats appliance
appliances
5. Protection against lightning and overvoltage
2. Connection of surge protection devices in networks
TN-S
3
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
TN-C-S
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
TN-C
*F3
Sub-distribution board (1)
SPD type 2
SPD type 2
SPD type 2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board (2)
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar Local earth bonding bar
*F4*F2
Entrance part
of the structure
L1
L2
L3
N
PE
F1
RCD
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2
Sub-distribution board
SPD type 2
Fine protection
SPD type 3
63A
16A
16A
LPZ 0 LPZ 1
Local earth bonding bar
*F3
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Entrance part
of the structure
L1
L2
L3
PEN
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD type 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Sub-distribution board
Local earth bonding bar
*F4
*F2
Fine protection
63A
16A
16A
Fine protection
63A
16A
16A
equipment
* SPD back-up – see item 4
TT
SPD in 3+1 mode SPD in 4+0 mode
SPD in 3+1 mode SPD in 4+0 mode
SPD in 3+0 mode
SPD in 3+1 mode
6. Protection against lightning and overvoltage
4
3. SPD dimensioning and their use
Application of SALTEK SPD type 1
EN 62305
Location of SPD type 1: at the boundary of LPZ0 and LPZ1 zones
in main distribution board
LPL Lightning Total SPD
I. to 200 kA 100 kA
Conditions met by:
FLP-SG50 V(S)/1
FLP-B+C MAXI V(S)/1
- large industrial facilities
- structures of special importance
- technological facilities
- administrative structures
- administrative structures
- civic amenities
- family houses
- near transformer stations
LPL Lightning Total SPD
III. to 100 kA 50 kA
Conditions met by:
FLP-12,5 V/1(S) - family houses w/o down conductor system
With a cable connector in the housing and in the
LPS III class
- structures in LPS IV class, i.e. structures and halls
without persons and interior equipment, structures
only with heavy current wiring
- on LW earthing supply cables to the structure
where the connection is not directly to the public
distribution network (i.e. interconnection between
2 structures)
- to sub-distribution boards within the structure,
With a cable length from the last SPD of over 50 m
Aplication of SALTEK SPD type 2
EN 62305
Location of SPD type 2: at the boundary of LPZ1 and LPZ2 zones
or sub-distribution board
Conditions met by:
SLP-xxx - all types of wiring
- type of network (TN, IT, T T)
- connection method
- nominal voltage
Application of SALTEK SPD type 3
EN 62305
Location of SPD type 3: at the boundary of LPZ2 and LPZ3 zones
(technology)
Conditions met by:
DA-275
(with DIN bar)
- all types of wiring (if the equipment is in the
clamp or distribution board)
DA-275 …, CZ… - all types of wiring (sockets with overvoltage
protection at the shortest possible distance from
the appliance)
xxx-OVERDRIVE - all types of wiring
adapters for plugs with overvoltage protection
4. Principle of SPD backing
For the design of an SPD back-up, it is important if we consider the protection priority principle, found in most installations, or the supply priority principle.
Example of an SPD FLP-B+C MAXI V back-up in different supply networks.
The catalogue value of the maximum back-up for FLP-B+C MAXI V is 250 A, for a“V”connection it is 125 A.
Connection in parallel Connection in„V“
TN-C
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up: 1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up: 1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up: 1,5 kV
F1 ≤ 125 A
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up: 1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up: 1,5 kV
FLP-B+C MAXI V
SPD T1 T2
červená – porucha
red – defect
250 A
Uc: 260 V~
Iimp: 25 kA
In: 30 kA
Imax: 60 kA
Up: 1,5 kV
F1 250 A → F2
F1 ≤ 250 A → F2
F1 125 A
F1 ≤ 125 A
×
7. 5
Protection against lightning and overvoltage
5. Principles for positioning and connecting of lightning and surge arresters
Surge protection devices and lightning current arresters cannot be positioned in the distribution board at random. It should be noted that protection
should be located in the closest proximity to the entry feed cable of the distribution board to minimize the area of the induction loop, see the image below.
Examples of SPDs located in a distribution board.
overhead, PEN (PE) at the bottom overhead, PEN (PE) at the top bottom supply, PEN (PE) at the bottom bottom supply, PEN (PE) at the top
Another important condition for connecting the SPD is to minimize the impedance of connecting conductors. Stranded conductors or strip lines are
preferentially used for connecting SPD type 1. It is also important that the length of the connecting conductors is as small as possible – see IEC 60364-5-534
(the total length of connecting conductors must not exceed 1 m). The cross-section of the connecting conductors should be as large as possible – maximum
up to the cross-section according to the type of connector. In SPD type 1 (lightning arresters) the connecting conductors are an integral part of the main
bonding – as determined by the IEC60364-4-41 standard, while minimum cross-sections of the connecting conductors are specified in IEC60364-5-54.
If SPDs are located in circuits where residual current devices are installed, the SPD should be positioned before the residual current device (not in the
residual current device circuit), to prevent spontaneous overload tripping of the RCD affected by surge arresters or lightning current arresters.
Should an overvoltage protection be located in the residual current devices circuit, RCD type S or G should be used. Even in this case it should be noted that
the resistance of these residual current devices is not high (5 to 8 kA in wave 8/20 μs) which makes it impossible to use any SPD in the circuit of the residual
current device. If you want to prevent a residual current device type S or G responding to surge protection by overload tripping, only a protection SPD type
3 can be used in the circuit of the residual current device.
Example of SPD FLP-12,5 V back-up in different supply networks.
The catalogue value of the maximum back-up for FLP-12,5 V is F2 =160 A.
F2’– the SPD back-up value established by the calculation
TN-C
PEN
PEN
FLP-12,5Včervená
porucha
red
defect
SPDT1T2
FLP-12,5Včervená
porucha
red
defect
SPDT1T2
FLP-12,5Včervená
porucha
red
defect
SPDT1T2
L1 L2 L3
L3L2L1
F2 = 160 A
F1 160 A
≥ 160 A → F2
8. 6
6. SPD dimensioning
Dimensioning is only provided for SPD type 1. The basis for that is the calculation of the lightning protection level (LPL) for the down conductor (LPS).
The table below is taken from CLC/TS 61643-12 and shows the minimum value of the current withstand per pole according to the lightning protection level
(LPL) structure classification.
If LPL is not known, the worst
case shall be answered LV system
LPL
Maximum
current for the
LPL
No. of
conductors
(n)
TT TN-C TN-S
IT
w/o neutral
conductor
IT
with neutral
Connection mode Connection mode Connection mode
CT1 CT2 CT1 CT2 CT1 CT2
L-PE
N-PE L-N N-PE L-PEN
L-PE
N-PE L-N N-PE L-PE L-N N-PE
1
or
unknown
200 kA
Iimp (kA)
5 N/A N/A N/A N/A 20,0 20,0 80,0 N/A N/A N/A
4 25,0 25,0 100,0 25,0 N/A N/A N/A N/A 25,0 100,0
3 N/A N/A N/A N/A 33,3 33,3 66,7 33,3 N/A N/A
2 50,0 50,0 100,0 50,0 N/A N/A N/A N/A 50,0 100,0
2 150 kA
Iimp (kA)
5 N/A N/A N/A N/A 15,0 15,0 60,0 N/A N/A N/A
4 18,8 18,8 75,0 18,8 N/A N/A N/A N/A 18,8 75,0
3 N/A N/A N/A N/A 25,0 25,0 50,0 25,0 N/A N/A
2 37,5 37,5 75,0 37,5 N/A N/A N/A N/A 37,5 75,0
3 or 4 100 kA
Iimp (kA)
5 N/A N/A N/A N/A 10,0 10,0 40,0 N/A N/A N/A
4 12,5 12,5 50,0 12,5 N/A N/A N/A N/A 12,5 50,0
3 N/A N/A N/A N/A 16,7 16,7 33,3 16,7 N/A N/A
2 25,0 25,0 50,0 25,0 N/A N/A N/A N/A 25,0 50,0
Comment: CT1 – connection of an SPD in the X+0 mode; CT2 – connection of an SPD in the X+1mode
CT1 – (TN-C) 3+0 CT1 – (TN-S) 4+0 CT2 (TT or TNS) 3+1
Protection against lightning and overvoltage
9. 7
Protection against lightning and overvoltage
7. Reducing overvoltage using LPZ zones
The principle of reducing overvoltage using zones lies in the progressive reduction of the overvoltage level to a safe value that will not damage
the specific equipment or technology. To obtain a safe overvoltage value, the whole structure is divided into individual zones and an SPD is installed
at the boundary between the zones..
*F3
Podružný rozváděč (1)
SPD typ 2
SPD type 2
SPD typ 2
Vstupní část
instalace
L1
L2
L3
N
PE
F1
RCD
Hlavní zemní přípojnice
Externíochranaprotiblesku
Hlavní rozváděč
SPD typ 1 nebo 1+2
Podružný rozváděč (2)
SPD typ 2
Jemná ochrana
SPD typ 3
63A
16A
16A
LPZ 0 LPZ 2LPZ 1 LPZ 2
Lokální zemní přípojnice Lokální zemní přípojnice
*F4*F2
LPZ 2
Entrance part
of the structure
L1
L2
L3
N
PEN PE
F1
Main earth bonding bar
Externalprotectionagainstlightning
Main distribution board
SPD type 1 or 1+2LPZ 0
*F2
Vstupní část
instalace
L1
L2
L3
PEN
F1
Hlavní rozváděč
SPD typ 1 nebo 1+2LPZ 0
*F2
RCD
Sub-distribution board (2)
SPD type 2 SPD type 3
SPD typ 3
LPZ 1
LPZ 1
Local earth bonding bar
*F3
Sub-distribution board (1)
Local earth bonding bar
*F3
Podružný rozváděč
*F4
Fine protection
63A
16A
16A
Jemná ochrana
63A
16A
16A
equipment
* back-up of SPD – see page.7
LPZ 0A
LPZ 0BLPZ 0B
LPZ 0A
T2
T1
(T1+T2)LPZ 1
T3
T3
T3
LPZ 1
T3
T3
T3
T3
T1
10. Protection against lightning and overvoltage
Examples of SPD applications
Modern family houses feature more and more electronic equipment. If the owner of the structure wants to watch TV, be in contact with the world via the
Internet, control the heating in the structure automatically, use various electronic equipment without any trouble, it is necessary to protect such equipment
against atmospheric events. Lightning strikes hitting the structure or near the structure and overvoltage in the mains can destroy or damage such electronic
devices or otherwise make use of such sensitive appliances uncomfortable.
Internal protection against lightning and overvoltage must be considered as an integrated system. For most family houses it is OK to install SPD type 1 and
2 at the line entry in the structure (the main distribution board where the circuit breakers for the whole house are located), i.e. FLP-B+C MAXI V(S)/3 for the
wiring connected in TN-C or TN-C-S, or FLP-B+C MAXI V(S)/4 for the wiring in the TN-S network. For sensitive appliances inside the structure, it is sufficient to
use overvoltage protection - SPD type 3, in combination with respective data protection.
It should further be noted that antenna down conductors at the structure entry must also be considered. For such cases, we use the FX-090 F75 T current
arrester.
If the structure has ESS, EPS, or electronics to control the heating system, overvoltage protection SPD type 3 with vf filter type DA-275 DF 6 will be used to
protect the supply 230 V AC, which will be installed in close proximity to the protected equipment.
If the structure has photovoltaic panels installed on the roof, you need to protect the panels as well as the DC/AC inverter. Protection for photovoltaic
equipment, e.g. the SLP-PV500 V/U type, is used to protect the DC part.
The following examples show various options for connecting the structure to the distribution network.
8
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
DA-275 A CZ-275 A
T3 T3 T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
T1 T2
Family houses
❶ A family house in a built-up area or a detached structure
with or without a down conductor and external line on posts
❷ A family house in a built-up area without a down conductor and
cable connection
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
DA-275 A CZ-275 A
T3 T3 T2
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
11. 9
Protection against lightning and overvoltage
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
T1 T2
Terraced houses
❸ Terrace houses with a common down conductor and external line
❹ Terrace houses with a common down conductor and cable connection
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
DA-275 A
DA-275 A
CZ-275 A
CZ-275 A
T3
T3
T3
T3
T2
T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
12. 10
Protection against lightning and overvoltage
T1 T2T
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
or SLP-275 V/4
T2
TN-C – SLP-275 V/1
TN-C-S – SLP-275 V/1
TN-S – SLP-275 V/1+1
T2
DA-275 A
T3
CZ-275 A
T3
T1 T2T
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – FLP-12,5 V/3
TN-C-S – FLP-12,5 V/3
TN-S – FLP-12,5 V/4
T1 T2
TN-C – FLP-12,5 V/1
TN-C-S – FLP-12,5 V/1
TN-S – FLP-12,5 V/2
T1 T2
DA-275 A
CZ-275 A
T3
T3
Blocks of flats
❺ Blocks of flats with a cable connection without the possibility to install SPD type 1 in the unmeasured part
❻ Blocks of flats with a cable connection with the possibility to install SPD type 1 in the unmeasured part
13. 11
Protection against lightning and overvoltage
❼ Administrative buildings
DA-275 A
T3
CZ-275 A
T3
or
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
T2
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/3+1
or SLP-275 V/4
T2
T1 T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
Remember
protection of data, signal
and communication lines
see page 72 -73
14. Protection against lightning and overvoltage
12
❽ Administrative and industrial structures
T1 T2
TN-C – FLP-B+C MAXI V(S)/3
TN-C-S – FLP-B+C MAXI V(S)/3
TN-S – FLP-B+C MAXI V(S)/4
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/4
T2
DA-275 A T3
CZ-275 A
T3
nebo
TN-S – DA-275 DF25
T3
TN-S – DA-275 DF16
T3
TN-C – SLP-275 V/3
TN-C-S – SLP-275 V/3
TN-S – SLP-275 V/4
T2
15. Protection against lightning and overvoltage
13
T1
TN-C – 3 pcs FLP-SG50 V(S)
TN-C-S – 3 pcs FLP-SG50 V(S)
TN-S – 4 pcs FLP-SG50 V(S)
TN-S – DA-275 V/3+1
T3
TN-S – SLP-275 V/3+1
T2
TN-S – DA-275 V/3+1
T3
TN-S – DA-275 DF16
T3
TN-S – DA-275 DF25
T3
TN-S – SLP-275 V/3+1
T2
TN-S – SLP-275 V/3+1
T2
TN-S – FLP-12,5 V/3+1
T1 T2
Remember
protection of data, signal
and communication lines
see page 72 -73
16. 14
SPD SALTEK application in LV distribution networks
Type of structure system main distribution board (in the structure)
sub-distribution board
(in the same structure)
close to the equipment
Family houses, administrative
buildings, technologic units,
industrial structures
3-phase TN-C FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3 distance 10 m
SLP-275 V/3(S)
distance 5 m
overvoltage protection
to DIN rail:
DA-275 V/1(S)+1 (to 63 A)
DA-275 V/3(S)+1 (to 63 A)
DA-275 DJ (to 16 A)
overvoltage protection to a
DIN rail with a vf filter
DA-275 DFx (S)
(x = 2, 6, 10, 16 A)
DA-275 DF 25 for 25 A
DA-275 DFIx
(x = 1, 6, 10, 16 A)
RACK-PROTECTOR
multiple sockets to
19“stands
CZ-275 A, DA-275 CZS
DA-275 A, DA-275 S
for additional assembly to
the sockets and appliances
sockets with overvoltage
protection (ABB)
XX-OVERDRIVE
socket adapters
distance 5 m
place before the
overvoltage protection
RTO-xx
(xx – rated current
16, 35 or 63 A)
Number according to the
connection type
1-phase TN-C
1x RTO-xx
1-phase TN-S
2x RTO-xx
3-phase TN-C
3x RTO-xx
3-phase TN-S
4x RTO-xx
distance 50 m
FLP-12,5 V/3(S)
distance 100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3
(also with terminals to the equipment)
distance 10 m
SLP-275 V/3(S)
distance 50 m
FLP-12,5 V/3(S)
distance 100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
3-phase TN-S FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4
FLP-25-T1-VS/4, FLP-25-T1-V/4
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
FLP-B+C MAXI VS/4, FLP-B+C MAXI V/4
(also with terminals to the equipment)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
3-phase TN-C-S FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3
FLP-25-T1-VS/3, FLP-25-T1-V/3
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
FLP-B+C MAXI VS/3, FLP-B+C MAXI V/3
(also with terminals to the equipment)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
Blocks of flats with 12 or more
apartments (SPD located in the
apart. Distr. boards)
3-phase TN-C FLP-12,5 V/3(S)
3-phase TN-S FLP-12,5 V/4(S)
3-phase TN-C-S division in the apartment distr. board FLP-12,5 V/3(S)
1-phase TN-C FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1
1-phase TN-S FLP-12,5 V/2(S)
Demanding applications
(structures – operations clas-
sified at the risk of explosion,
chemical plants…, structures of
a very high importance)
3-phase TN-C 3× FLP-SG50 V(S)/1
with terminals to the equipment
3× FLP-SG50 V(S)/1 + 1× SLP-275 V/3(S)
distance 10 m
1× SLP-275 V/3(S)
distance 10 m
SLP-275 V/3(S)
distance 50 m
FLP-12,5 V/3(S)
distance 100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
3-phase TN-S 4× FLP-SG50 V(S)/1
with terminals to the equipment
4× FLP-SG50 V(S)/1 + 1× SLP-275 V/4(S)
distance 10 m
1× SLP-275 V/4(S)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
3-phase TN-C-S division in the main distribution board
3× FLP-SG50 V(S)/1
with terminals to the equipment
3× FLP-SG50 V(S)/1 + 1× SLP-275 V/4(S)
distance 10 m
1× SLP-385 V/4(S)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
17. 15
SPD SALTEK application in LV distribution networks
Type of structure system main distribution board (in the structure)
sub-distribution board
(in the same structure)
close to the equipment
Structures equipped with ESE
(active down conductor)
3-phase TN-C 3x FLP-SG50 V(S)/1 distance 10 m
SLP-275 V/3(S)
distance 5 m
overvoltage protection
to DIN rail:
DA-275 V/1(S)+1 (to 63 A)
DA-275 V/3(S)+1 (to 63 A)
DA-275 DJ (to 16 A)
overvoltage protection to
DIN rail with vf filter:
DA-275 DFx (S)
(x = 2, 6, 10, 16 A)
DA-275 DF 25 for 25 A
DA-275 DFIx
(x = 1, 6, 10, 16 A)
RACK-PROTECTOR
multiple sockets for
19“ stands
CZ-275 A, DA-275 CZS
DA-275 A, DA-275 S
For additional mounting to
sockets and appliances
Sockets with overvoltage
protection (ABB)
XX-OVERDRIVE
Socket adapters
distance 5 m
SPD back-up
RTO-xx
(xx – rated current
16, 35 or 63 A)
Number according to the
connection type
1-phase TN-C
1x RTO-xx
1-phase TN-S
2x RTO-xx
3-phase TN-C
3x RTO-xx
3-phase TN-S
4x RTO-xx
distance 10 m
SLP-275 V/3(S)
distance 50 m
FLP-12,5 V/3(S)
distance 100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
also with terminals to the equipment
3x FLP-SG50 V(S)/1 + SLP-275 V/3(S)
distance 10 m
SLP-275 V/3(S)
distance 50 m
FLP-12,5 V/3(S)
distance 100 m
FLP-B+C MAXI V/3, FLP-B+C MAXI VS/3
3-phase TN-S 4x FLP-SG50 V(S)/1 distance 10 m
SLP-275 V/4(S)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
also with terminals to the equipment
4x FLP-SG50 V(S)/1 + SLP-275 V/4(S)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
3-phase TN-C-S 3x FLP-SG50 V(S)/1 distance 10 m
SLP-275 V/4(S)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
also with terminals to the equipment
3x FLP-SG50 V(S)/1 + SLP-275 V/3(S)
distance 10 m
SLP-275 V/4(S)
distance 50 m
FLP-12,5 V/4(S)
distance 100 m
FLP-B+C MAXI V/4, FLP-B+C MAXI VS/4
Technology with 1-phase
connection
1-phase TN-C FLP-SG50 V(S)/1
with terminals to the equipment
FLP-SG50 V(S)/1 + SLP-275 V/1(S)
distance 10 m
SLP-275 V/1(S)
distance 10 m
SLP-275 V/1(S)
distance 50 m
FLP-12,5 V/1(S)
distance 100 m
FLP-B+C MAXI V/1, FLP-B+C MAXI VS/1
1-phase TN-S 2× FLP-SG50 V(S)/1
with terminals to the equipment
2× FLP-SG50 V(S)/1 + 1× SLP-275 V/2(S)
distance 10 m
1× SLP-275 V/2(S)
distance 10 m
1× SLP-275 V/2(S)
distance 50 m
1× FLP-12,5 V/2(S)
distance 100 m
FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2
1-phase TN-C-S Division in the main distribution board
FLP-SG50 V(S)/1
with terminals to the equipment
FLP-SG50 V(S)/1 + SLP-275 V/1(S)
distance 10 m
1× SLP-275 V/2(S)
distance 10 m
1× SLP-275 V/2(S)
distance 50 m
1× FLP-12,5 V/2(S)
distance 100 m
FLP-B+C MAXI V/2, FLP-B+C MAXI VS/2
18. FLP-SG50 V/1
FLP-SG50 VS/1
SPD type 1 – lightning current arrester
Encapsulated high-performance spark gap with replaceable
module, visual fault signalling
To be installed in low-voltage distributions at the boundary of
LPZ 0A and LPZ 1 zones to prevent overvoltage effects of direct
or indirect lightning strikes in the most demanding applications
in the heavy and chemicals industry, power stations, etc.
Remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
connection
of signalization
terminal
Lightning Current Arresters
16
FLP-SG50 VS/1
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 255 V AC
Nominal discharge current (8/20 μs) In 50 kA
Lightning impulse current (10/350 μs) Iimp 50 kA
Voltage protection level Up 2,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi 50 kA
Nominal short circuit current ISCCR 50 kArms
Maximum overcurrent protection 315 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
TOV voltage UT 335 V/5 sec.
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard EN 61643-11:2012
Ordering number
FLP-SG50 V/1 8595090540540
FLP-SG50 VS/1 8595090540533
Technical data
3666
45
90
9
15
L/N( )
L/N()
(L/N)
(L/N)
19. Lightning Current Arresters
SPD type 1 – lightning current arrester
N-PE module, replaceable module
To be installed in low-voltage distributions at the boundary of
LPZ 0A–LPZ 1 zones and higher to prevent overvoltage effects of
direct or indirect lightning strikes for the connection of SPD type
1 in the mode 1+1.
Dimension drawing Basic circuit diagram
FLP-A50N VS/NPE
Technical data
FLP-A50N VS/NPE
Nominal voltage Un —
Maximum operating voltage Uc 255V AC
Nominal discharge current (8/20 μs) In 50 kA
Maximum discharge current (8/20 μs) Imax 100 kA
Lightning impulse current (10/350 μs) Iimp 50 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Abilitytoindependentlyswitchoffthefollowingcurrent Ifi 100 A
Short-circuitproofatmaximumovercurrentprotection —
Maximum overcurrent protection —
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication no
Remote indication * potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090535737
* Remote signalling of N-PE module shows the presence of the replaceable module
17
90
45
66 36
9
15
N( )
N()
(N)
(N) connection
of signalization
terminal
20. Lightning Current Arresters
SPD type 1 – lightning current arrester
N-PE module, replaceable module
To be installed in low-voltage distributions at the boundary of
LPZ 0A and LPZ 1 zones to prevent overvoltage effects of direct or
indirect lightning strikes for the connection
of SPD type 1 in the mode 3+1.
Dimension drawing Basic circuit diagram
FLP-A100N VS/NPE
Technical data
FLP-A100N VS/NPE
Nominal voltage Un —
Maximum operating voltage Uc 255V AC
Nominal discharge current (8/20 μs)/pole In 100 kA
Maximum discharge current (8/20 μs) Imax 100 kA
Lighting impulse current (10/350 μs)/pole Iimp 100 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Abilitytoindependentlyswitchoffthefollowingcurrent Ifi 100 A
Short-circuit proof at maximum overcurrent protection —
Maximum overcurrent protection —
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication no
Remote indication * potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090535744
* Remote signalling of N-PE module shows the presence of the replaceable module
18
90
45
66 36
9
15
N( )
N()
(N)
(N) connection
of signalization
terminal
21. Lightning Current Arresters
FLP-B+C MAXI V/1
FLP-B+C MAXI VS/1
Dimension drawing Basic circuit diagram
SPD type 1 and type 2
versatile single-pole arrester
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of low-voltage
(230/400 V AC) networks and connected appliances against surge voltages due to direct or indirect
lightning strikes in the concept of zone lightning protection at the boundary of the LPZ 0 and LPZ 1
(or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT) rated at 25 kA
(10/350 μsec pulse) with high energy varistors block. This proven technology guarantee no follow
current, no leakage current and low residual voltage.
Remote status signalling contact – version„S“.
FLP-B+C MAXI VS/1
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs) In 30 kA
Maximum discharge current (8/20 μs) Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG : 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/1 8595090550914
FLP-B+C MAXI VS/1 8595090535331
connection
of signalization
terminal
19
3666
45
90
9
15
(L/N)
L/N( )
L/N()
(L/N)
Technical data
22. SPD type 1 and type 2
2-pole (1+NPE) arrester for single phase TT (TNS) networks
Total Iimp = 50 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection of
low-voltage (230/400 V AC) networks and connected appliances against surge voltages
due to direct or indirect lightning strikes in the concept of zone lightning protection at
the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT)
rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven
technology guarantee no follow current, no leakage current and low residual voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 260 V AC 255 V AC
Nominal discharge current (8/20 μs) In 30 kA 50 kA
Maximum discharge current Imax 60 kA 100 kA
Lighting impulse current Iimp 25 kA 50 kA
Voltage protection level Up 1,5 kV 1,5 kV
Response time ta 100 ns 100 ns
Abilitytoindependentlyswitchoffthe followingcurrent Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 250 A gL/gG —
Maximum overcurrent protection for serial connection 125 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1 ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2 ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field no
Remote indication* potential-free change-over contact potential-free change-over contact*
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
max. 1,5 mm2
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/1+1 8595090550952
FLP-B+C MAXI VS/1+1 8595090537830
* Remote signalling of N-PE module shows the presence of the replaceable module
FLP-B+C MAXI V/1+1
FLP-B+C MAXI VS/1+1
connection of
signalization terminal
Lightning Current Arresters
20
15
PE
PE
7266
45
90
9
15
L
L
N
N
N
N
23. SPD type 1 and type 2
2-pole arrester for single phase TNS networks
Total Iimp= 50 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against surge
voltages due to direct or indirect lightning strikes in the concept of zone lightning
protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT)
rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven
technology guarantee no follow current, no leakage current and low residual
voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
Technical data
FLP-B+C MAXI VS/2
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/2 8595090550921
FLP-B+C MAXI VS/2 8595090537847
FLP-B+C MAXI V/2
FLP-B+C MAXI VS/2
connection of
signalization terminal
Lightning Current Arresters
21
15
7266
45
90
9
15
PE
L/N
L/N
L/N
L/N
PE
PE
PE
24. SPD type 1 and type 2
3-pole arrester for 3-phase TNC networks
Total Iimp= 75 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against surge
voltages due to direct or indirect lightning strikes in the concept of zone lightning
protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube (GDT)
rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This proven
technology guarantee no follow current, no leakage current and low residual
voltage.
Remote status signalling contact – version„S“.
Technical data
FLP-B+C MAXI VS/3
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/3 8595090550938
FLP-B+C MAXI VS/3 8595090535706
FLP-B+C MAXI V/3
FLP-B+C MAXI VS/3
connection of
signalization terminal
Dimension drawing Basic circuit diagram
Lightning Current Arresters
22
90
45
66 108
9
15
25. SPD type 1 and type 2
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Total Iimp= 100 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against
surge voltages due to direct or indirect lightning strikes in the concept of zone
lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube
(GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This
proven technology guarantee no follow current, no leakage current and low
residual voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 260V AC 255V AC
Nominal discharge current (8/20 μs)/pole In 30 kA 100 kA
Maximum discharge current (8/20 μs) Imax 60 kA 100 kA
Lighting impulse current (10/350 μs)/pole Iimp 25 kA 100 kA
Voltage protection level Up 1,5 kV
Voltage protection level (L - PE) Up 2,2 kV
Response time ta 100 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 250 A gL/gG —
Maximum overcurrent protection for serial connection 125 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1 ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2 ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field no
Remote indication* potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC61643-11ed.1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXIV/3+1 8595090550969
FLP-B+C MAXIVS/3+1 8595090535720
* Remote signalling of N-PE module shows the presence of the replaceable module
FLP-B+C MAXI V/3+1
FLP-B+C MAXI VS/3+1
connection of
signalization terminal
Lightning Current Arresters
23
Technical data
90
45
66 144
9
15
26. Lightning Current Arresters
SPD type 1 and type 2
4-pole arrester for 3-phase TNS networks
Total Iimp= 100 kA (10/350)
Surge protective devices (SPD) type 1 and type 2 (class B+C) serve for protection
of low-voltage (230/400 V AC) networks and connected appliances against
surge voltages due to direct or indirect lightning strikes in the concept of zone
lightning protection at the boundary of the LPZ 0 and LPZ 1 (or higher) zones.
Replaceable module offers a combination of heavy duty gas discharge tube
(GDT) rated at 25 kA (10/350 μsec pulse) with high energy varistors block. This
proven technology guarantee no follow current, no leakage current and low
residual voltage.
Remote status signalling contact – version„S“.
Dimension drawing Basic circuit diagram
FLP-B+C MAXI V/4
FLP-B+C MAXI VS/4
connection of
signalization terminal
Technical data
FLP-B+C MAXI VS/4
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 260 V AC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lighting impulse current (10/350 μs)/pole Iimp 25 kA
Voltage protection level Up 1,5 kV
Response time ta 100 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 250 A gL/gG
Maximum overcurrent protection for serial connection 125 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 2,5/50 mm2
; AWG: 13/1
Stranded min/max ISO: 2,5/35 mm2
; AWG: 13/2
Visual fault indication red indication field
Remote indication potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-B+C MAXI V/4 8595090550945
FLP-B+C MAXI VS/4 8595090535713
24
66
45
90
144
9
15
27. Lightning Current Arresters
SPD type 1 and type 2
versatile single-pole arrester
Varistor lightning and surge current arrester to be installed in
low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
FLP-12,5 V/1 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 30 kA
Maximal discharge current Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/1 8595090534211
FLP-12,5 V/1 S 8595090534228
FLP-12,5 V/1
FLP-12,5 V/1 S
connection of
signalization terminal
25
28. L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs) In 30 kA 30 kA
Maximal discharge current (8/20 μs) Imax 60 kA 60 kA
Lightning impulse current (10/350 μs) Iimp 12,5 kA 25 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level@I =5kA(8/20μs) Up 0,9 kV —
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Abilityindependentlyswitchoffthefollowingcurrent Ifi no following current 100 A
Short-circuitproofatmaximumovercurrentprotection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-sectionofremoteindicationconductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Orderingnumber
FLP-12,5V/1+1 8595090534235
FLP-12,5V/1S+1 8595090534242
Lightning Current Arresters
SPD type 1 and type 2
2-pole (1+NPE) arrester for single phase TT(TNS) networks
Total Iimp= 25 kA (10/350)
Varistor lightning and surge current arrester and heavy
duty encapsulated spark gap to be installed in low-voltage
distributions at the boundary of LPZ 0–LPZ 1 zones and higher
to prevent overvoltage effects induced during a lightning
strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
FLP-12,5 V/1+1
FLP-12,5 V/1S+1
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
26
29. Lightning Current Arresters
SPD type 1 and type 2 – lightning current arrester
Replaceable varistor module, visual fault signalling
2-pole varistor lightning current arrester to be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1
zones and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling (S).
Dimension drawing Basic circuit diagram
FLP-12,5 V/2
FLP-12,5 V/2S
connection of
signalization terminal
Technical data
FLP-12,5 V/2
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximal discharge current/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures - 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/2 8595090538097
FLP-12,5 V/2S 8595090551829
27
L
PE
N
30. FLP-12,5 V/3 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximal discharge current/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/3 8595090534259
FLP-12,5 V/3 S 8595090534266
Lightning Current Arresters
SPD type 1 and type 2
3-pole arrester for 3-phase TNC networks
Total Iimp= 37,5 kA (10/350)
Varistor lightning and surge current arresters to be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1
zones and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Technical data
FLP-12,5 V/3
FLP-12,5 V/3 S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
28
31. L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs) In 30 kA 50 kA
Maximal discharge current (8/20 μs) Imax 60 kA 100 kA
Lightning impulse current (10/350 μs) Iimp 12,5 kA 50 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level@I =5kA(8/20μs) Up 0,9 kV —
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Abilityindependentlyswitchoffthefollowingcurrent Ifi no following current 100 A
Short-circuitproofatmaximumovercurrentprotection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-sectionofremoteindicationconductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Orderingnumber
FLP-12,5V/3+1 8595090534273
FLP-12,5V/3S+1 8595090534280
Lightning Current Arresters
SPD type 1 and type 2
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Total Iimp= 50 kA (10/350)
Varistor lightning and surge current arresters and fixed N-PE
modul with heavy duty encapsulated spark gap. To be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
FLP-12,5 V/3+1
FLP-12,5 V/3S+1
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
29
32. Lightning Current Arresters
SPD type 1 and type 2
4-pole arrester for 3-phase TNS networks
Total Iimp= 50 kA (10/350)
Varistor lightning and surge current arresters to be installed
in low-voltage distributions at the boundary of LPZ 0–LPZ 1
zones and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
FLP-12,5 V/4 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximal discharge current/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 12,5 kA
Voltage protection level Up 1,2 kV
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
FLP-12,5 V/4 8595090534297
FLP-12,5 V/4 S 8595090534303
FLP-12,5 V/4
FLP-12,5 V/4 S
connection of
signalization terminal
30
33. Lightning Current Arresters
SPD type 1 and type 2
versatile single-pole arrester
Varistor lightning and surge current arrester to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
Dimension drawing Basic circuit diagram
FLP-7-V/1
FLP-7-V/1 S
FLP-7-V/1 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 30 kA
Maximum discharge current Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
connection of
signalization terminal
31
Technical data
34. Lightning Current Arresters
SPD type 1 and type 2
2-pole (1+NPE) arrester for single phase TT (TNS) networks
Varistor lightning and surge current arrester and heavy duty
encapsulated spark gap in the mode 1+1. To be installed
in low-voltage distributions at the boundary of LPZ 0B
and LPZ 1 zones to protect distributions and equipment against
the overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
FLP-7-V/1+1
FLP-7-V/1S+1
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs) In 30 kA 30 kA
Maximum discharge current (8/20 μs) Imax 60 kA 60 kA
Lighting impulse current (10/350 μs) Iimp 7 kA 25 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 25 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field ne
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
32
35. Lightning Current Arresters
SPD type 1 and type 2
2-pole arrester for 3-phase TNC networks
Varistor lightning and surge current arresters to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
FLP-7-V/2
FLP-7-V/2 S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
L
PE
N
FLP-7-V/2 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 30 kA
Maximum discharge current Imax 60 kA
Lightning impulse current (10/350 μs) Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Technical data
33
36. Lightning Current Arresters
SPD type 1 and type 2
3-pole arrester for 3-phase TNC networks
Total Iimp= 21 kA (10/350)
Varistor lightning and surge current arresters to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1 zones
and higher to prevent overvoltage effects induced during
a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
Dimension drawing Basic circuit diagram
Technical data
FLP-7-V/3
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lightning impulse current (10/350 μs)/pole Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
FLP-7-V/3
FLP-7-V/3 S
connection of
signalization terminal
34
37. Lightning Current Arresters
SPD type 1 and type 2
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Total Iimp= 25 kA (10/350)
Varistor lightning and surge current arresters and heavy duty
encapsulated spark gap connected in the mode 3+1. To be
installed in low-voltage distributions at the boundary of LPZ 0B
and LPZ 1 zones to protect distributions and equipment against
the overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
FLP-7-V/3+1
FLP-7-V/3S+1
Technical data
L-N N-PE
Nominal voltage Un 230V AC —
Maximum operating voltage Uc 275V AC 255V AC
Nominal discharge current (8/20 μs)/pole In 30 kA 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA 60 kA
Lighting impulse current (10/350 μs)/pole Iimp 7 kA 25 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Dimension drawing Basic circuit diagram
connection of
signalization terminal
35
38. Lightning Current Arresters
SPD type 1 and type 2
4-pole arrester for 3-phase TNS networks
Total Iimp= 28 kA (10/350)
Varistor lightning and surge current arresters to be installed in
low-voltage distributions at the boundary of LPZ 0B–LPZ 1
zones and higher to prevent overvoltage effects induced
during a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
* Version UC =385 V available on request
Dimension drawing Basic circuit diagram
Technical data
FLP-7-V/4
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 30 kA
Maximum discharge current (8/20 μs)/pole Imax 60 kA
Lighting impulse current (10/350 μs)/pole Iimp 7 kA
Voltage protection level Up 1,2 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected condutors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
FLP-7-V/4
FLP-7-V/4 S
connection of
signalization terminal
36
39. Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 V/1 SLP-150 V/1 SLP-275 V/1 SLP-385 V/1 SLP-440 V/1 SLP-600 V/1
Nominal voltage Un — 120V AC 230V AC — 400V AC —
Maximum operating voltage Uc 75V AC / 100V DC 150V AC / 200V DC 275V AC / 350V DC 385V AC / 500V DC 440V AC / 585V DC 600V AC
Maximum operating voltage of varistor — — — — — 880V AC
Nominal discharge current (8/20 μs) In 15 kA 15 kA 20 kA 20 kA 20 kA 15 kA
Maximum discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA
Voltageprotectionlevel @I=5kA(8/20μs) Up 0,3 kV 0,45 kV 0,9 kV 1,3 kV 1,5 kV 2,7 kV
Voltage protection level Up 0,4 kV 0,6 kV 1,35 kV 1,8 kV 1,9 kV 3,2 kV
Response time ta 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns
Short-circuitproofatmaximumovercurrentprotection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms
Maximum overcurrent protection 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gG 125 A gL/gG 100 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090518150 8595090551850 8595090516170 8595090519553 8595090518174 8595090533016
SLP-075 V/1
SLP-150 V/1
SLP-275 V/1
SLP-385 V/1
SLP-440 V/1
SLP-600 V/1
37
SPD type 2
versatile single-pole arrester
Varistor surge protection to be installed in
low-voltage distributions at the boundary
of LPZ 1 and LPZ 2 zones to protect the
distributions and equipment against
overvoltage effects induced during a
lightning strike and to prevent switching
overvoltage.
40. connection of
signalization terminal
Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 V/1 S SLP-150 V/1 S SLP-275 V/1 S SLP-385 V/1 S SLP-440 V/1 S SLP-600 V/1 S
Nominal voltage Un — 120V AC 230V AC — 400V AC —
Maximum operating voltage Uc 75V AC / 100V DC 150V AC / 200V DC 275V AC / 350V DC 385V AC / 500V DC 440V AC / 585V DC 600V AC
Maximum operating voltage of varistor — — — — — 880V AC
Nominal discharge current (8/20 μs) In 15 kA 15 kA 20 kA 20 kA 20 kA 15 kA
Maximum discharge current (8/20 μs) Imax 40 kA 40 kA 40 kA 40 kA 40 kA 40 kA
Voltageprotectionlevel @I=5kA(8/20μs) Up 0,3 kV 0,45 kV 0,9 kV 1,3 kV 1,5 kV 2,7 kV
Voltage protection level Up 0,4 kV 0,6 kV 1,35 kV 1,8 kV 1,9 kV 3,2 kV
Response time ta 25 ns 25 ns 25 ns 25 ns 25 ns 25 ns
Short-circuitproofatmaximumovercurrentprotection 50 kArms 50 kArms 50 kArms 50 kArms 25 kArms 25 kArms
Maximum overcurrent protection 160 A gL/gG 160 A gL/gG 160 A gL/gG 160 A gL/gG 125 A gL/gG 100 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S version potential-free change-over contact
Remote indication contacts 250V / 0,5 A AC, 250V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard IEC 61643-11 ed. 1.0 EN 61643-11:2012
Ordering number 8595090518235 8595090551867 8595090516187 8595090527718 8595090518259 8595090533023
SLP-075 V/1 S
SLP-150 V/1 S
SLP-275 V/1 S
SLP-385 V/1 S
SLP-440 V/1 S
SLP-600 V/1 S
38
SPD type 2
versatile single-pole arrester
Varistor surge protection to be installed in
low-voltage distributions at the boundary
of LPZ 1 and LPZ 2 zones to protect the
distributions and equipment against
overvoltage effects induced during a
lightning strike and to prevent switching
overvoltage.
Remote status signalling – version„S“.
41. Surge Arresters
SPD type 2 – surge arrester
2-pole (1+NPE) arrester for single phase TT (TNS) networks
Combination of varistor surge protection and an encapsulated spark
gap connected in the mode 1+1. To be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
distributions and equipment against the overvoltage effects induced
during a lightning strike and to prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs) In 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 40 kA 40 kA
Lighting impulse current (10/350 μs) Iimp — 12 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —
Voltage protection level Up 1,35 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/1+1 8595090519485
SLP-275 V/1S+1 8595090524915
SLP-275 V/1+1
SLP-275 V/1S+1
connection of
signalization terminal
39
42. Surge Arresters
SPD type 2 – surge arrester
Replaceable varistor module, visual fault signalling
2-pole varistor surge protection to be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
the distributions and equipment against overvoltage effects
induced during a lightning strike and to prevent switching
overvoltage. Optional remote status signalling(S).
SLP-275 V/2
SLP-275 V/2 S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
SLP-275 V/2 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA
Lighting impulse current (10/350 μs) Iimp —
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Voltage protection level Up 1,35 kV
Response time ta 25 ns
Ability to independently switch off the following current Ifi no following current
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 6163-11:2012
Ordering number
SLP-275 V/3 8595090516194
SLP-275 V/3S 8595090551836
40
L
PE
N
43. Surge Arresters
SPD type 2 – surge arrester
3-pole arrester for 3-phase TNC networks
3-pole varistor surge protection to be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
the distributions and equipment against overvoltage effects
induced during a lightning strike and to prevent switching
overvoltage.
Optional remote status signalling – version„S“.
SLP-275 V/3
SLP-275 V/3S
Dimension drawing Basic circuit diagram
connection of
signalization terminal
Technical data
SLP-275 V/3 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Voltage protection level Up 1,35 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/3 8595090517603
SLP-275 V/3 S 8595090517610
41
44. Surge Arresters
SPD type 2 – surge arrester
4-pole (3+NPE) arrester for 3-phase TT (TNS) networks
Combination of 3-pole varistor surge protection and an
encapsulated spark gap connected in the mode 3+1. To be
installed in low-voltage distributions at the boundary of LPZ 1
and LPZ 2 zones to protect distributions and equipment against
the overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs)/pole In 20 kA 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA 40 kA
Lighting impulse current (10/350 μs) Iimp — 12 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV —
Voltage protection level Up 1,35 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 50 kArms —
Maximum overcurrent protection 160 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/3+1 8595090519461
SLP-275 V/3S+1 8595090520023
SLP-275 V/3+1
SLP-275 V/3S+1
connection of
signalization
terminal
42
45. Surge Arresters
SPD type 2 – surge arrester
4-pole arrester for 3-phase TNS networks
4-pole varistor surge protection to be installed in low-voltage
distributions at the boundary of LPZ 1 and LPZ 2 zones to protect
the distributions and equipment against overvoltage effects
induced during a lightning strike and to prevent switching
overvoltage.
Optional remote status signalling – version„S“.
SLP-275 V/4
SLP-275 V/4S
Dimension drawing Basic circuit diagram
connection of
signalization
terminal
Technical data
SLP-275 V/4 S
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC / 350 V DC
Nominal discharge current (8/20 μs)/pole In 20 kA
Maximum discharge current (8/20 μs)/pole Imax 40 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,9 kV
Voltage protection level Up 1,35 kV
Response time ta 25 ns
Short-circuit proof at maximum overcurrent protection 50 kArms
Maximum overcurrent protection 160 A gL/gG
Degree of protection IP 20
Range of operating temperatures – 40 °C … + 80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number
SLP-275 V/4 8595090517221
SLP-275 V/4 S 8595090517634
43
46. Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 VB/1 SLP-130 VB/1 SLP-275 VB/1
Nominal voltage Un — 110 V AC 230 V AC
Maximum operating voltage Uc 75 V AC / 100 V DC 135 V AC / 175 V DC 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,5 kV 0,9 kV
Voltage protection level Up 0,6 kV 0,7 kV 1,2 kV
Response time ta 100 ns 100 ns 100 ns
Short-circuit proof at maximum overcurrent protection 35 kArms 35 kArms 35 kArms
Maximum overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Degree of protection IP 20 IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field red indication field red indication field
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number 8595090521556 8595090521822 8595090519447
SLP-075 VB/1
SLP-130 VB/1
SLP-275 VB/1
SPD type 2 – surge arrester
Replaceable module, visual fault signalling
Efficient varistor connected in series with an encapsulated spark gap. To be installed
in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to
protect distributions and equipment against the overvoltage effects induced during
a lightning strike and to prevent switching overvoltage in areas with higher storm
activity or to protect measuring circuits as a 1st protection level. In idle state it has
very little leakage current, which remains stable for the duration of the service life;
protective elements are not subject to ageing.
44
47. Surge Arresters
Dimension drawing Basic circuit diagram
Technical data
SLP-075 VB/1 S SLP-130 VB/1 S SLP-275 VB/1 S
Nominal voltage Un — 110 V AC 230 V AC
Maximum operating voltage Uc 75 V AC / 100 V DC 135 V AC / 175 V DC 275 V AC / 350 V DC
Nominal discharge current (8/20 μs) In 15 kA 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 25 kA 25 kA 25 kA
Voltage protection level @ I = 5 kA (8/20 μs) Up 0,3 kV 0,5 kV 0,9 kV
Voltage protection level Up 0,6 kV 0,7 kV 1,2 kV
Response time ta 100 ns 100 ns 100 ns
Short-circuit proof at maximum overcurrent protection 35 kArms 35 kArms 35 kArms
Maximum overcurrent protection 125 A gL/gG 125 A gL/gG 125 A gL/gG
Degree of protection IP 20 IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field red indication field red indication field
Remote indication – S design potential-free change-over contact
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC
Cross-section of remote indication conductors max. 1,5 mm2
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
IEC 61643-11 ed. 1.0
EN 61643-11:2012
Ordering number 8595090521563 8595090529965 8595090519454
SLP-075 VB/1 S
SLP-130 VB/1 S
SLP-275 VB/1 S
SPD type 2 – surge arrester
Replaceable module, visual fault signalling
Efficient varistor connected in series with an encapsulated spark gap. To be installed
in low-voltage distributions at the boundary of LPZ 1 and LPZ 2 zones. Designed to
protect distributions and equipment against the overvoltage effects induced during
a lightning strike and to prevent switching overvoltage in areas with higher storm
activity or to protect measuring circuits as a 1st protection level. In idle state it has
very little leakage current, which remains stable for the duration of the service life;
protective elements are not subject to ageing.
Remote status signalling – version„S“.
connection of
signalization
terminal
45
48. Surge Arresters
SPD type 2 – surge arrester
Efficient varistor connected in series with an encapsulated spark gap.
To be installed in low-voltage distributions at the boundary of LPZ 1
and LPZ 2 zones. Designed to protect distributions and equipment
against the overvoltage effects induced during a lightning strike and
to prevent switching overvoltage in areas with higher storm activity or
to protect measuring circuits as a 1st
protection level. In idle state it has
very little leakage current, which remains stable for the duration of the
service life; protective elements are not subject to ageing.
Optional remote status signalling (S).
Technical data
L-N N-PE
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs) In 20 kA 20 kA
Maximum discharge current (8/20 μs) Imax 25 kA 40 kA
Voltage protection level Up 1,2 kV 1,5 kV
Voltage protection level (L-PE) Up 2,0 kV
Response time ta 100 ns 100 ns
Ability to independently switch off the following current Ifi no following current 100 A
Short-circuit proof at maximum overcurrent protection 35 kArms —
Maximum overcurrent protection 125 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard
IEC 61643-11 ed. 1.0
EN 6163-11:2012
IEC 61643-11 ed. 1.0
EN 6163-11:2012
Ordering number
SLP-275 VB/3+1 8595090533108
SLP-275 VB/3S+1 8595090533115
SLP-275 VB/3+1
SLP-275 VB/3S+1
Dimension drawing Basic circuit diagram
connection of
signalization
terminal
46
49. Surge Arresters
SPD type 3 – surge arrester
Replaceable module, visual fault signalling
Combination of varistor surge protection and an encapsulated
spark gap connected in the mode 1+1. To be installed in low-
voltage distributions at the boundary of LPZ 2 and LPZ 3 zones
to protect distributions and equipment against overvoltage
effects induced during a lightning strike and to prevent
switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technical data
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs) In 5 kA 10 kA
Test voltage Uoc 10 kV 20 kV
Voltage protection level Up 1 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Maximum overcurrent protection 63 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012
Ordering number
DA-275 V/1+1 8595090518723
DA-275 V/1S+1 8595090519751
DA-275 V/1+1
DA-275 V/1S+1
connection of
signalization terminal
47
50. Surge Arresters
SPD type 3 – surge arrester
Replaceable module, visual fault signalling
Combination of 3-pole varistor surge protection and an
encapsulated spark gap connected in the mode 3+1. To be
installed in low-voltage distributions at the boundary of LPZ 2
and LPZ 3 zones to protect distributions and equipment against
overvoltage effects induced during a lightning strike and to
prevent switching overvoltage.
Optional remote status signalling – version„S“.
Dimension drawing Basic circuit diagram
Technické parametry
L-N N-PE
Nominal voltage Un 230 V AC —
Maximum operating voltage Uc 275 V AC 255 V AC
Nominal discharge current (8/20 μs)/pole In 5 kA 10 kA
Test voltage Uoc 10 kV 20 kV
Voltage protection level Up 1 kV 1,5 kV
Voltage protection level (L - PE) Up 1,5 kV
Response time ta 25 ns 100 ns
Maximum overcurrent protection 63 A gL/gG —
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid min/max ISO: 1/35 mm2
; AWG: 17/2 ISO: 1/35 mm2
; AWG: 17/2
Stranded min/max ISO: 1/25 mm2
; AWG: 17/4 ISO: 1/25 mm2
; AWG: 17/4
Fault indication red indication field no
Remote indication – S design potential-free change-over contact —
Remote indication contacts 250 V / 0,5 A AC, 250 V / 0,1 A DC —
Cross-section of remote indication conductors max. 1,5 mm2
—
Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012
Ordering number
DA-275 V/3+1 8595090518488
DA-275 V/3S+1 8595090518495
DA-275 V/3+1
DA-275 V/3S+1
connection of
signalization
terminal
48
51. Surge Arresters
SPD type 3 – surge arrester
Visual fault signalling
Surge protection designed to protect all types of electric and
electronic equipment connected to a low-voltage distribution
against pulse overvoltage.
Dimension drawing Basic circuit diagram
Technical data
DA-075 DJ DA-130 DJ DA-275 DJ
Nominal voltage Un — 110 V AC 230 V AC
Maximum operating voltage Uc 75 V AC 130 V AC 275 V AC
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 2 kA, 2 kA, 4 kA 2,5 kA, 2,5 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 4 kV, 4 kV, 8 kV 5 kV, 5 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 0,4 kV, 1,2 kV 0,6 kV, 1,5 kV 1,2 kV, 1,6 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns 25 ns, 100 ns
Short-circuit proof at maximum overcurrent protection 6 kArms 6 kArms 6 kArms
Maximum overcurrent protection 16 A gL/gG; B 16 A 16 A gL/gG; B 16 A 16 A gL/gG; B 16 A
Degree of protection IP 20 IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 6 mm2
; AWG: 10 ISO: 6 mm2
; AWG: 10 ISO: 6 mm2
; AWG: 10
Stranded max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Fault indication red indicator red indicator red indicator
Meets the requirements of standard EN 61643-11:2012 EN 61643-11:2012 EN 61643-11:2012
Ordering number 8595090533191 8595090521891 8595090506362
DA-075 DJ
DA-130 DJ
DA-275 DJ
49
52. Surge Arresters
Dimension drawing Basic circuit diagram
SPD type 3 – surge arrester with RFI filter
Visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
DA-275 DF2 DA-275 DF6
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 2 A 6 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 2 kA, 2 kA, 4 kA 2 kA, 2 kA, 4 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 4 kV, 4 kV, 8 kV 4 kV, 4 kV, 8 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 2 A gL/gG or B 2 A 6 A gL/gG or B 6 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090506706 8595090506713
Technické parametry
DA-275 DF 2
DA-275 DF 6
50
53. DA-275 DF2 S DA-275 DF6 S
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 2 A 6 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 2 A gL/gG or B 2 A 6 A gL/gG or B 6 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Remote indication – S design potential-free change-over contact potential-free change-over contact
Remote indication contacts AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090516248 8595090516255
Technical data
Surge Arresters
Dimension drawing Basic circuit diagram
SPD type 3 – surge arrester with RFI filter
Remote and visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
DA-275 DF 2 S
DA-275 DF 6 S
51
Dálková signalizace
54. Surge Arresters
SPD type 3 – surge arrester with RFI filter
Visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
Dimension drawing Basic circuit diagram
Technical data
DA-275 DF10 DA-275 DF16
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 10 A 16 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 10 A gL/gG nebo C10 A 16 A gL/gG nebo C16 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090506720 8595090506737
DA-275 DF 10
DA-275 DF 16
52
55. Technical data
DA-275 DF10 S DA-275 DF16 S
Nominal voltage Un 230 V AC 230 V AC
Maximum operating voltage Uc 275 V AC 275 V AC
Nominal load current IL 10 A 16 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns 25 ns, 100 ns
Maximum overcurrent protection 10 A gL/gG or B 10 A 16 A gL/gG or B 16 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB 30 dB
Degree of protection IP 20 IP 20
Range of operating temperatures – 40 °C … + 80 °C – 40 °C … + 80 °C
Mounting on DIN rail 35 mm DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Fault indication red indicator red indicator
Remote indication potential-free change-over contact potential-free change-over contact
Remote indication contacts AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A AC: 250 V/ 0,5 A; DC: 250 V / 0,1 A
Cross-section of connected conductors
Solid max ISO: 4 mm2
; AWG: 11 ISO: 4 mm2
; AWG: 11
Stranded max ISO: 2,5 mm2
; AWG: 13 ISO: 2,5 mm2
; AWG: 13
Meets the requirements of standard EN 61643-11 + A11 EN 61643-11 + A11
Ordering number 8595090516262 8595090516279
Dimension drawing Basic circuit diagram
Surge Arresters
SPD type 3 – surge arrester with RFI filter
Remote fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
DA-275 DF 10 S
DA-275 DF 16 S
53
Dálková signalizace
56. Surge Arresters
SPD type 3 – surge arrester with RFI filter
Visual fault signalling
Surge protection with an integrated RFI filter designed to
protect MC, ESS, EFS, etc. control systems against pulse
overvoltage and RF disturbance.
Dimension drawing Basic circuit diagram
Technical data
DA-275 DF25
Nominal voltage Un 230 V AC
Maximum operating voltage Uc 275 V AC
Nominal load current IL 25 A
Nominal discharge current (8/20 μs) L-N, L(N)-PE, L+N-PE In 3 kA, 3 kA, 5 kA
Test voltage L-N, L(N)-PE, L+N-PE Uoc 6 kV, 6 kV, 10 kV
Voltage protection level L-N, L(N)-PE Up 1,2 kV, 1,5 kV
Response time L-N, L(N)-PE ta 25 ns, 100 ns
Maximum overcurrent protection 25 A gL/gG or C 25 A
Filter attenuation at 1 MHz (50 Ω/50 Ω) unsymmetrical 30 dB
Degree of protection IP 20
Range of operating temperatures –40 °C … +80 °C
Mounting on DIN rail 35 mm
Cross-section of connected conductors
Solid max ISO: 1/50 mm2
; AWG: 17/1
Stranded max ISO: 1/35 mm2
; AWG: 17/2
Fault indication red indicator
Meets the requirements of standard EN 61643-11 + A11
Ordering number 8595090537328
DA-275 DF 25
54
72