2. 2
Product Lis ngs
LED Emergency Driver: Linear Case ………...……………………..….…..…………………...4
LED Emergency Driver: Rectangular Case ………………….………………………………..12
LED Emergency Driver: Extra Compact ………………...………..…………………………..18
Driverless LED Emergency …………………………………………………………………………..24
Addi onal Resources
Other Product Lines ………...……………………………………………………………………...
Limited Warranty ...………...………………………………………………………………………..
Table of Contents
3. McWong’s LEM series of LED Emergency Drivers
is designed to provide emergency backup power
for safety compliance to UL 924; CAN/CSA-C22.2
No. 141-10 and NFPA requirements for 90 mi-
nute egress. This product replaces emergency
uorescent ballasts when xtures are converted
from uorescent to LED light sources, or for new
LED luminaires.
Standard installa ons require three separate
parts to func on:
• One non-emergency LED driver (AC input)
• One LEM series LED emergency driver
• One set of two NiCd ba ery packs
Emergency-only installa ons require two sepa-
rate parts:
• One LEM series LED emergency driver
• One set of two NiCd ba ery packs
Standard Features:
• Safety compliance to UL 924; CAN/CSA-
C22.2 No. 141-10 and NFPA requirements
for 90 minute egress
• Open circuit / short circuit protec on
• Opera ng temperature: 32°F/0°C to
122F/50°C
• Test switch / charging indicator light
• Emergency reac on me 1 sec
• Powder coat steel, stainless or galvannealed
case
• Field-replaceable NiCd ba ery pack (x2) with
quick connect
• Min. Lead length: 6” UL1452 solid/18AWG
1000V/90°C
4
LED Emergency Drivers: Linear Case
E467188
5
LEM
*Each LED emergency driver model is assigned a default set of ba ery packs, which are automa cally included with your order. Other ba ery pack
op ons are available, but must be special ordered. This product series is op mized for use with McWong’s LED modules. For ques ons regarding
compa bility with light sources from other manufacturers please contact technical support.
LEM = LED Emergency Driver
018 026 0700 U-
Product Series:
Wa age & Case Type:
Max Output Voltage:
Opera ng Current:
Input Voltage
0xx = Linear Case
026 = 26VDC
0700 = 700mA
U = Universal 120-277VAC
How to Order
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Mxx = Rectangular Case
x07 = 7W
- - -
x18 = 18W
Model No.*
Input
Voltage
Output
Power
Output
Voltage
Output
Current
Ba ery
Voltage
Ba ery
Capacity
Recharge
Time
Default
Ba ery Pack*
UL
(VAC) (W) (VDC) (mA) (VDC) (Ah) (hr)
LEM-010-028-0350-U 120-277 9.8 12-28 350 2 x 9.6 1.2 24 BCP-NiCd-9.6-1.2-L
LEM-018-026-0700-U 120-277 18.2 18-26 700 2 x 8.4 2.5 24 BCP-NiCd-8.4-2.5-L
LEM-020-056-0350-U 120-277 19.6 12-56 350 2 x 9.6 2.5 24 BCP-NiCd-9.6-2.5-L
028 = 28VDC
056 = 56VDC
Cxx = Extra Compact Case
Dxx = Driverless
4 5
4. LED Emergency Drivers: Linear Case
6
*The driver and ba ery packs are a matched set, which are automa cally paired together when you order. Other ba ery pack op ons are available,
but must be special ordered.
Dimensions: LEM-010-028-0350-U
LEM Driver LEM-010-028-0350-U
Ba ery Pack BCP-NiCd-9.6-1.2-L
31 mm
337 mm
356 mm
25 mm
320 mm
Dia. 21 mm
2 mm
270 mm
20mm
E467188
Model No. Max Overall Length Width Height Moun ng Centers WeightMin Lead Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-010-028-0350-U 14 356 1.2 31 1 25 13.6 346 10.2 260 1.0
BCP-NiCd-9.6-1.2-L* 12.6 320 0.8 21 0.9 23 11.8 300 6 152 0.8
7
LED Emergency Drivers: Linear Case
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Wiring Diagrams: LEM-010-028-0350-U
Conguraon#3:
SeparateEmergency/ACLoads
Conguraon#2:
ParalLoad
Conguraon#1:
SharedLoad
E467188
6 7
5. LED Emergency Drivers: Linear Case
8
*The driver and ba ery packs are a matched set, which are automa cally paired together when you order. Other ba ery pack op ons are available,
but must be special ordered.
E467188
Dimensions: LEM-018-026-0700-U
LEM Driver LEM-018-026-0700-U
Ba ery Pack BCP-NiCd-8.4-2.5-L
31 mm
337 mm
356 mm
25 mm
388 mm
Dia. 25 mm
2 mm
340 mm
21mm
Model No. Max Overall Length Width Height Moun ng Centers WeightMin Lead Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-018-026-0700-U 14 356 1.2 31 1 25 13.6 346 10.2 260 1.0
BCP-NiCd-8.4-2.5-L* 15.3 388 1 25 1.1 27 14.8 375 15.7 400 1.2
9
LED Emergency Drivers: Linear Case E467188
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Wiring Diagrams: LEM-018-026-0700-U
Conguraon#3:
SeparateEmergency/ACLoads
Conguraon#2:
ParalLoad
Conguraon#1:
SharedLoad8 9
6. 11
LED Emergency Drivers: Linear Case
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Wiring Diagrams: LEM-020-056-0350-U
Conguraon#3:
SeparateEmergency/ACLoads
Conguraon#2:
ParalLoad
Conguraon#1:
SharedLoad
E467188
LED Emergency Drivers: Linear Case
10
*The driver and ba ery packs are a matched set, which are automa cally paired together when you order. Other ba ery pack op ons are available,
but must be special ordered.
Dimensions: LEM-020-056-0350-U
LEM Driver LEM-020-056-0350-U
Ba ery Pack BCP-NiCd-9.6-2.5-L
31 mm
337 mm
356 mm
25 mm
440 mm
Dia. 25 mm
2 mm
388 mm
20mm
E467188
Model No. Max Overall Length Width Height Moun ng Centers WeightMin Lead Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-020-056-0350-U 14 356 1.2 31 1 25 13.6 346 10.2 260 1.0
BCP-NiCd-9.6-2.5-L* 17.3 440 1 25 1.1 27 16.7 423 15.7 400 1.4
10 11
7. McWong’s LEM series of LED Emergency Drivers
is designed to provide emergency backup power
for safety compliance to UL 924; CAN/CSA-C22.2
No. 141-10 and NFPA requirements for 90 mi-
nute egress. This product replaces emergency
uorescent ballasts when xtures are converted
from uorescent to LED light sources, or for new
LED luminaires.
Standard installa ons require three separate
parts to func on:
• One non-emergency LED driver (AC input)
• One LEM series LED emergency driver
• One set of two NiCd ba ery packs
Emergency-only installa ons require two sepa-
rate parts:
• One LEM series LED emergency driver
• Once set of two NiCd ba ery packs
Standard Features:
• Safety compliance to UL 924; CAN/CSA-
C22.2 No. 141-10 and NFPA requirements
for 90 minute egress
• Open circuit / short circuit protec on
• Opera ng temperature: 32°F/0°C to
122F/50°C
• Test switch / charging indicator light
• Emergency reac on me 1 sec
• Powder coat steel, stainless or galvannealed
case
• Field-replaceable NiCd ba ery pack (x2) with
quick connect
• Min. Lead length: 6” UL1452 solid/18AWG
1000V/90°C
12
LED Emergency Drivers: Rectangular Case
13
LEM
*Each LED emergency driver model is assigned a default set of ba ery packs, which are automa cally included with your order. Other ba ery pack
op ons are available, but must be special ordered. This product series is op mized for use with McWong’s LED modules. For ques ons regarding
compa bility with light sources from other manufacturers please contact technical support.
LEM = LED Emergency Driver
M2 056 0350 U-
Product Series:
Wa age & Case Type:
Max Output Voltage:
Opera ng Current:
Input Voltage
056 = 56VDC
0350 = 350mA
U = Universal 120-277VAC
How to Order
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
- - -
Model No.*
Input
Voltage
Output
Power
Output
Voltage
Output
Current
Ba ery
Voltage
Ba ery
Capacity
Recharge
Time
Default
Ba ery Pack*
UL
(VAC) (W) (VDC) (mA) (VDC) (Ah) (hr)
LEM-M20-056-0350-U 120-277 19.6 12-56 350 2 x 9.6 2.5 24 BCP-NiCd-9.6-2.5-M
LEM-M10-028-0350-U 120-277 9.8 12-28 350 2 x 9.6 1.2 24 BCP-NiCd-9.6-1.2-M
0xx = Linear Case
Mxx = Rectangular Case
x07 = 7W
x18 = 18W
Cxx = Extra Compact Case
Dxx = Driverless
12 13
8. LED Emergency Drivers: Rectangular Case
14
*The driver and ba ery packs are a matched set, which are automa cally paired together when you order. Other ba ery pack op ons are available,
but must be special ordered.
Dimensions: LEM-M10-028-0350-U
LEM Driver LEM-M10-056-0350-U
Ba ery Pack BCP-NiCd-9.6-1.2-M
400
MAX 133
45
49.6
MAX 21
E467188
Model No. Max Overall Length Width Height Moun ng Centers WeightMin Lead Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-M10-028-0350-U 7.8 199 2.1 53 1.3 33 7.6 193 10.2 260 0.9
BCP-NiCd-9.6-1.2-M* 5.2 133 1.8 45 0.9 21 6.5 165 15.7 400 0.7
15
LED Emergency Drivers: Rectangular Case
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Wiring Diagrams: LEM-M10-028-0350-U
Conguraon#1:
SharedLoad
Conguraon#2:
ParalLoad
Conguraon#3:
SeparateEmergency/ACLoads
E467188
14 15
9. 17
LED Emergency Drivers: Rectangular Case
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Wiring Diagrams: LEM-M20-056-0350-U
Conguraon#1:
SharedLoad
Conguraon#2:
ParalLoad
Conguraon#3:
SeparateEmergency/ACLoads
E467188
LED Emergency Drivers: Rectangular Case
16
*The driver and ba ery packs are a matched set, which are automa cally paired together when you order. Other ba ery pack op ons are available,
but must be special ordered.
Dimensions: LEM-M20-056-0350-U
LEM Driver LEM-M20-056-0350-U
Ba ery Pack BCP-NiCd-9.6-2.5-M
E467188
Model No. Max Overall Length Width Height Moun ng Centers WeightMin Lead Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-M20-056-0350-U 7.8 199 2.1 53 1.3 33 7.6 193 10.2 260 0.9
BCP-NiCd-9.6-2.5-M* 9.5 240 2.2 56 1.1 28 8.9 226 15.7 400 1.8
16 17
10. LED Emergency Drivers: Extra Compact
McWong’s LEM series of LED Emergency Drivers
is designed to provide emergency backup power
for safety compliance to UL 924; CAN/CSA-C22.2
No. 141-10 and NFPA requirements for 90 mi-
nute egress. This product replaces emergency
uorescent ballasts when xtures are converted
from uorescent to LED light sources, or for new
LED luminaires.
Standard installa ons require three separate
parts to func on:
• One non-emergency LED driver (AC input)
• One LEM series LED emergency driver
• One NiMH ba ery pack
Emergency-only installa ons require two sepa-
rate parts:
• One LEM series LED emergency driver
• One NiMH ba ery pack
Standard Features:
• Safety compliance to UL 924; CAN/CSA-
C22.2 No. 141-10 and NFPA requirements
for 90 minute egress
• Open circuit / short circuit protec on
• Opera ng temperature: 32°F/0°C to
122F/50°C
• Test switch / charging indicator light
• Emergency reac on me 1 sec
• Powder coat steel, stainless or galvannealed
case
• Field-replaceable NiMH ba ery pack (x1)
with quick connect
• Min. Lead length: 6” UL1452 solid/18AWG
1000V/90°C
18 19
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
LEM
*Each LED emergency driver model is assigned a default set of ba ery packs, which are automa cally included with your order. Other ba ery pack
op ons are available, but must be special ordered. This product series is op mized for use with McWong’s LED modules. For ques ons regarding
compa bility with light sources from other manufacturers please contact technical support.
LEM = LED Emergency Driver
C07 036 0200 U-
Product Series:
Wa age & Case Type:
Max Output Voltage:
Opera ng Current:
Input Voltage
036 = 36VDC
0200 = 200mA
U = Universal 120-277VAC
How to Order
- - -
Model No.*
Input
Voltage
Output
Power
Output
Voltage
Output
Current
Ba ery
Voltage
Ba ery
Capacity
Recharge
Time
Default
Ba ery Pack*
UL
(VAC) (W) (VDC) (mA) (VDC) (Ah) (hr)
LEM-C07-036-0200-U 120-277 7.2 12-36 200 1 x 7.2 2.1 24 BCP-NiMH-7.2-2.1-C
LEM-C14-036-0400-U 120-277 14.4 12-36 400 1 x 7.2 4.0 24 BCP-NiMH-7.2-4.0-C
0400 = 400mA
0xx = Linear Case
Mxx = Rectangular Case
x07 = 7W
x18 = 18W
Cxx = Extra Compact Case
Dxx = Driverless
1918
√
√
11. LED Emergency Drivers: Extra Compact
20
*The driver and ba ery packs are a matched set, which are automa cally paired together when you order. Other ba ery pack op ons are available,
but must be special ordered.
Dimensions: LEM-C07-036-0200-U
LEM Driver LEM-C07-036-0200-U
Ba ery Pack BCP-NiMH-7.2-2.1-C
305
MAX 17MAX 150
49.6
35
Model No. Max Overall Length Width Height Moun ng Centers WeightMin Lead Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-C07-036-0200-U 6.3 160 1.6 40 1.1 29 6 152 15.7 400 0.4
BCP-NiMH-7.2-2.1-C* 5.9 150 1.4 35 0.7 17 N/A N/A 12 305 0.5
21
LED Emergency Drivers: Extra Compact
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Wiring Diagrams: LEM-C07-036-0200-U
Conguraon#3:
SeparateEmergency/ACLoads
Conguraon#2:
ParalLoad
Conguraon#1:
SharedLoad20 21
12. 23
LED Emergency Drivers: Extra Compact
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Wiring Diagrams: LEM-C14-036-0400-U
Conguraon#3:
SeparateEmergency/ACLoads
Conguraon#2:
ParalLoad
Conguraon#1:
SharedLoad
LED Emergency Drivers: Extra Compact
22
*The driver and ba ery packs are a matched set, which are automa cally paired together when you order. Other ba ery pack op ons are available,
but must be special ordered.
Dimensions: LEM-C14-036-0400-U
LEM Driver LEM-C14-036-0400-U
Ba ery Pack BCP-NiMH-7.2-4.0-C
Model No. Max Overall Length Width Height Moun ng Centers WeightMin Lead Length
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-C14-036-0400-U 6.3 160 1.6 40 1.1 29 6 152 15.7 400 0.4
BCP-NiMH-7.2-4.0-C* 5.9 150 2 50 1 25 N/A N/A 5.9 150 1.1
22 23
13. Driverless LED Emergency
McWong’s LEM-Dxx series of “Driverless” LED emergency
products is designed to provide emergency backup power
for safety compliance to UL 924; CAN/CSA-C22.2 No. 141-
10 and NFPA requirements for 90 minute egress. This
product replaces emergency fluorescent ballasts when
fixtures are converted from fluorescent to LED light
sources, or for new LED luminaires.
Standard installa ons of the driverless models require
two separate parts to func on:
One LEM-Dxx series LED emergency driver
One NiCd ba ery pack
Standard Features:
Safety compliance to UL 924; CAN/CSA-C22.2 No. 141
-10 and NFPA requirements for 90 minute egress
Open circuit / short circuit protec on
Opera ng temperature: 32°F/0°C to 122F/50°C
Test switch / charging indicator light
Normal mode LED so start, emergency mode con-
version within 1 second
Aluminum low profile housing
Field-replaceable NiCd ba ery pack with quick con-
nect
Constant current, mul -current selectable output
0-10V dimmable
Emergency mode DIP se ngs for 150mA, 300mA,
450mA, or 600mA output current
Class I CE & UL Recognized for US and Canada. Suita-
ble for indoor, dry and damp applica ons
RoHS compliant (NiCd ba ery excepted)
24 25
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
LEM
*Output current se ngs must be limited such that the product of the Emergency LED Array Voltage mes the Emergency Output Current does
not exceed Ba ery Max Emergency Power ra ng. The driverless LED emergency series is designed for maximum adaptability to accommodate a
wide range of outputs. “Driverless” means that there is no need for a separate AC LED driver; i.e., both normal power and emergency power are
regulated by a single self-contained, hybrid AC/emergency driver. The models in this table can be paired with several different ba ery packs.
When ordering, you must include a suffix code to indicate the ba ery type desired. For ques ons please contact technical support.
Toll Free: (888) 600-9188 Email: Support@McWonginc.com
LEM = LED Emergency Driver
D25 042 P0600 U-
Product Series:
Normal Power & Case Type:
Max Output Voltage:
Max Opera ng Current:
Input Voltage
042 = 42VDC
0600 = 600mA
U = Universal 120-277VAC
How to Order
- -
Model No.*
Input
Voltage
Max
Output
Power
Output
Voltage
Range
Max
Output
Current
Ba ery
Voltage
Ba ery
Capacity
Recharge
Time
Ba ery Pack Op ons
(See Emergency Power
Limits above)
UL
Rec.
Emergency Opera on (VAC) (W) (VDC) (mA) (VDC) (Ah) (hr)
LEM-D25-042P0600-U 120-277 17* 6—38* 600* 9.6 See specs 24 4.0, 2.0, 1.0 Ah √
LEM-D42-042P1000-U 120-277 17* 6—42* 600* 9.6 See specs 24 4.0, 2.0, 1.0 Ah √
Normal Opera on (VAC) (W) (VDC) (mA) (VDC) (Ah) (hr)
LEM-D25-042P0600-U 120-277 25 6—38 600 - - - - √
LEM-D42-042P1000-U 120-277 42 6—42 1000 - - - - √
0xx = Linear Case
Mxx = Rectangular Case
x07 = 7W
x18 = 18W
Cxx =
g
Extra Compact Case
Dxx =
p
Driverless
4.0
Ba ery Amp-Hour Suffix Code
and Max Emergency Power*
1.0 NiCd1.0Ah 9.6V (AA) Max 4W
2.0 NiCd 2.0Ah 9.6V (sC) Max 8W
4.0
( )
NiCd 4.0Ah 9.6V (D) Max 17W
-
24 25
P = Programmable (DIP switch)
14. 27
McWong Interna onal, Inc. 1921 Arena Blvd., Sacramento, CA 95834
Tel: 916-371-8080 | Email: support@mcwonginc.com | Web: www.mcwonginc.com
Driverless LED Emergency
Wiring Diagrams: LEM-D25-042P0600-U and LEM-D42-042P1000-U
DriverlessLEDEmergency
*Output current se ngs must be limited such that the product of the Emergency LED Array Voltage mes the
Emergency Output Current does not exceed Ba ery Max Emergency Power ra ng.
Dipswitch Se ngs:
LEM-D25-042P0600-U LEM-D42-042P1000-U
E467188
4 5 Iemergency Req’d Ba ery Typical Ra ng
0 0 150mA
1.0Ah 2W @ 12V
1.0Ah 4W @ 24V
2.0Ah 6W @ 36V
1 0 300mA
1.0Ah 4W @ 12V
2.0Ah 7W @ 24V
2.0Ah 11W @ 36V
0 1 450mA
2.0Ah 6W @ 12V
2.0Ah 11W @ 24V
4.0Ah 16W @ 36V
1 1 600mA
2.0Ah 7W @ 12V
4.0Ah 14W @ 24V
Dipswitches 4 and 5 set various emergency
current values.
LEM-Dxx-042Pxxxx-U Ba ery Op ons at
Typical Voltages
Dipswitches 1-3 determine the normal mode output current.
LEM-D25-042P0600-U/
LEM-D42-042P1000-U
RED
BLK
L Switched
L Unswitched
X
X
0-10V
0-10V
26
Driverless LED Emergency
Dimensions: LEM-D25-042P0600-U and LEM-D42-042P1000-U
LEM Driver LEM-D25-042P0600-U and LEM-D42-042P1000-U
Ba ery Pack BCP-NiCd-9.6-1.0, BCP-NiCd-9.6-2.0, and BCP-NiCd-9.6-4.0
202012.5
W
4.2
H
L
A
L
A
BE
C
D
W
*The driverless LED emergency series is designed for maximum adaptability to accommodate a wide range of outputs. “Driverless” means that there is
no need for a separate AC LED driver; i.e., both normal power and emergency power are regulated by a single self-contained, hybrid AC/emergency
driver.
E467188
Model No. L W H A B C D
Weigh
t
E
(in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (in) (mm) (lbs)
LEM-D25-042P0600-U 6.9 175 2.6 65 0.9 22 6.8 167 - - - - - - - - 0.6
LEM-D42-042P1000-U 7.7 195 2.6 65 0.9 22 7.4 187 - - - - - - - - 0.6
BCP-NiCd-9.6-1.0 7.7 195 1.1 28.5 0.6 14.5 6.5 165 1.6 39.5 0.6 15.8 1.2 31.5 0.01 1.5 0.4
BCP-NiCd-9.6-2.0 6.7 171 1.8 45 0.9 22.6 5.6 141 2.2 56 0.9 23.8 1.9 48 0.01 1.5 0.9
BCP-NiCd-9.6-4.0 9.3 237 2.6 65.2 1.3 32.8 8.3 211.5 3.1 78.8 1.4 35 2.8 70.2 0.1 2.5 2.026 27
16. 29
Limited Warranty — LED Emergency Drivers
McWong Interna onal, Inc. (herea er referred to as “MCWONG”),
corporate headquarters located at 1921 Arena Blvd., Sacramento, CA
95834, warrants its products to be free from defects in materials and
workmanship from the date of manufacture for the following me
periods:
MCWONG cannot assume any obliga ons or liabili es for consequen al
or incidental damages arising from, or in connec on with, the use or
performance of its products or other indirect damages with respect to
loss of property, revenue or pro t, or cost of removal, installa on or
reinstalla on.
This limited warranty is not applicable to any product subjected to
abnormal stress, such as improper storage, installa on, use and/or
maintenance. This warranty is invalid for any product not installed and
operated in accordance with all relevant federal, state, and local
government regula ons, established industry safety standards,
published electrical and temperature ra ngs, and any speci c
instruc ons provided by MCWONG for the installa on of the product(s).
This limited warranty is extended by MCWONG only to the original or
rst end-user purchaser.
The standards and condi ons of any tests performed on any MCWONG
product(s) by the original purchaser, or by any third party ac ng on
behalf of the original purchaser, shall be mutually agreed upon in
wri ng and MCWONG shall be no ed of, and may be represented at
any such tests.
Should defects occur a er installa on, and within the warranty period,
they should be speci cally described to a MCWONG representa ve.
MCWONG shall correct any defects, at MCWONG’s op on, by furnishing
materials to repair or replace any product(s) that may prove defec ve in
materials or workmanship within the warranty period, or by extending a
credit in the amount of the purchase price. This does not apply to: (1)
damage caused by accident, abuse, mishandling, or dropping; (2)
materials which have been subject to unauthorized repair; (3) materials
not used in accordance with instruc ons; (4) ordinary wear and tear.
MCWONG will be limited to the furnishing of new parts, free of charge,
or extending credit for in the amount of the purchase price, in exchange
for parts proven to be defec ve and does not include any other costs of
removal or installa on.
This limited warranty cons tutes the sole and exclusive remedy of the
purchase and the exclusive liability of MCWONG, and is in lieu of any
and all other warran es, expressed, implied, or statutory as to
merchantability, tness for purpose sold, descrip on, quality
produc veness, or any other ma er. NO IMPLIED STATUTORY
WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE SHALL APPLY BEYOND THE AFOREMENTIONED WARRANTY
PERIOD.
Warranty claims can be submi ed by calling our toll free technical
support hotline (888) 600-9188 or by visi ng our website
www.McWonginc.com and lling out a Warranty Replacement Form
(Click on Support >> Warranty Statements). Completed forms should be
faxed to (916) 371-6666 or emailed to Support@McWonginc.com.
Product Series Warranty
LED Emergency Drivers (all types) 60 months
30 31