Fire Protection & Prevention
1
PPT-116-01
CFR 1926 Subpart F
Bureau of Workers’ Compensation
PA Training for Health & Safety
(PATHS)
PPT-116-01 2
Subpart F - Fire Protection &
Prevention
(1926.150 - 159)
33
26
18
15
15
150(c)(1)(i)
152(a)(1)
153(j)
150(a)(1)
150(c)(1)(vi)
Standard
-
1926.
Flammables/combustibles - Approved containers
Fire protection program/equipment
2A fire extinguishers - Building area
Storage of LPG containers
10B fire extinguisher within 50 ft. of flammable/combustible liquids
Fire Protection & Prevention
PPT-116-01 3
Definitions
"Combustible liquid" means any liquid having a
flash point at or above 140 deg. F., and below 200
deg. F
"Flammable liquid" means any liquid having a flash
point below 140 deg. F and having a vapor pressure
not exceeding 40 pounds per square inch (absolute)
at 100 deg. F.
PPT-116-01 4
Combustible & Flammable Liquids
200 Fº
140 Fº
100 Fº
73 Fº
Boiling Point Fº
IA IB
IC
II
III
Combustible
Flash point > 100 Fº
Flammable
Flash point < 100 Fº
PPT-116-01 5
Definitions
• The minimum temperature at which a liquid
gives off vapor within a test vessel in sufficient
concentration to form an ignitable mixture
with air near the surface of the liquid.
• The flash point is normally an indication of
susceptibility to ignition.
Flash Point
PPT-116-01 6
Definitions
Flammable (Explosive) Limits
• The flammable range includes all concentrations
of flammable vapor or gas in air, in which a flash
will occur or a flame will travel if the mixture is
ignited.
PPT-116-01 7
Flammable (Explosive) Limits
Explosion
Pressure
LEL UEL
Vapor/Gas Concentration in Air (%)
Flammable Range
• Safety can shall mean an approved container, of
not more than 5 gallons capacity, having a
spring-closing lid and spout cover and so
designed that it will safely relieve internal
pressure when subjected to fire exposure.
PPT-116-01 8
Safety Can
Employer responsibility:
• Development and maintenance of an effective
fire protection and prevention program
• At the jobsite
• Throughout all phases of construction
• Comply with provisions of Subpart F
PPT-116-01 9
1926.24 Fire Protection and Prevention
PPT-116-01 10
1926.150 General Requirements
• Maintain access to fire
fighting equipment at all
times
• Conspicuously located
• Periodically inspected
• Defective replaced
PPT-116-01 11
1926.150 General Requirements
• Fire brigade provided
as warranted
• Provide water supply
to protect against
combustibles
PPT-116-01 12
Subpart F - Fire Protection
• Know what to look for
when inspecting!
– Type of extinguisher
– Labeling
– Pins in place?
– Charged?
– Heft test
– Annual Hydrostatic test
PPT-116-01 13
1926.150 General Requirements
Fire extinguishers:
• Fire extinguisher provided every
3000 ft²
• In protected areas travel distance
to extinguisher < 100 feet
• Minimum one extinguisher per
floor
• Multi-story at least one near
stairway
PPT-116-01 14
1926.150 General Requirements
• Minimum 10B
extinguisher within 50
feet of 5 gallons
flammable liquid or 5
pounds flammable gas
• Extinguishers inspected
and maintained in
accordance with NFPA
No. 10A-1970.
PPT-116-01 15
Subpart F - Fire Protection
Types of Fires
• Class A - Ordinary materials such as paper,
wood, cloth
• Class B - Flammable liquids or Combustible
liquids such as gasoline, paint, thinners,
propane, kerosene
• Class C - Electrical equipment fires,
appliances, switches, panels
• Class D - Certain metals such as magnesium,
sodium, that could explode!
PPT-116-01 16
Fire Extinguishers
PPT-116-01 17
Subpart F - Fire Protection
PPT-116-01 18
1926.150 General Requirements
• Alarm system established for emergencies:
- Alert employees
- Alert fire department
• Reporting instructions conspicuously posted by
phones and worker entrances
PPT-116-01 19
1926.150 General Requirements
Fire Cutoffs:
• Fire walls & exit
stairways given
construction
priority
• For demolition,
retain fire walls
until removal
required
PPT-116-01 20
1926.151 Fire Prevention
• Electrical for light, heat, and power complies
with Subpart K
• Engine combustion well away from combustibles
• No smoking around fire hazards and signs
posted
PPT-116-01 21
1926.151 Fire Prevention
• Combustible piles no
higher than 20 feet
• Driveways around
combustible piles
minimum 15 feet
wide
• Maximum
driveway grid
50' by 150'
15'
150'
50'
20'
PPT-116-01 22
1926.151 Fire Prevention
150'
50'
20'
15'
• No piles
within ten
feet of
buildings
• Fire
extinguisher
provided
within 100
feet
10'
PPT-116-01 23
1926.151 Fire Prevention
Indoor Storage:
• No obstruction to exit
• Appropriate
management of all
fire hazard materials
• Segregate non-
compatibles
• Three feet clearance
maintained to
sprinklers
PPT-116-01 24
1926.152 Flammable & Combustible Liquids
• Flammable liquids > 1 gallon
requires safety can
• Flammables not stored near
exits or stairways
PPT-116-01 25
1926.152 Flammable & Combustible Liquids
Inside Storage:
• Max 25 gallons
stored outside
flammable cabinet
• Cabinets labeled
“Flammable -
Keep Fire Away”
PPT-116-01 26
1926.152 Flammable & Combustible Liquids
• Dispensing 5 gallons
or more, segregate
25 feet from other
operations
• Bonding required for
container transfer
PPT-116-01 27
1926.152 Flammable & Combustible Liquids
• The dispensing units shall be protected against
collision damage
• Containers closed when not in use
PPT-116-01 28
1926.153 Liquefied petroleum gas (LP-Gas)
• Systems, valves, connectors of approved type
• Welding is prohibited on containers
• Storage of LPG within buildings is prohibited
• Filling of portable containers or containers
mounted on skids from storage containers shall
be performed not less than 50 feet from the
nearest building.
PPT-116-01 29
Contact Information
Health & Safety Training Specialists
1171 South Cameron Street, Room 324
Harrisburg, PA 17104-2501
(717) 772-1635
RA-LI-BWC-PATHS@pa.gov
Like us on Facebook! -
https://www.facebook.com/BWCPATHS
PPT-116-01 30
Questions

More Related Content

Similar to Fire Safety - Fire Prevention and Protection training

Fire_Protection_Subpart_L_GA_Tech.ppt
Fire_Protection_Subpart_L_GA_Tech.pptFire_Protection_Subpart_L_GA_Tech.ppt
Fire_Protection_Subpart_L_GA_Tech.pptJuliusSagcal1
 
Fire_Protection_Subpart_L_GA_Tech (1).ppt
Fire_Protection_Subpart_L_GA_Tech (1).pptFire_Protection_Subpart_L_GA_Tech (1).ppt
Fire_Protection_Subpart_L_GA_Tech (1).pptVersatileEngiSafe
 
Welding_Safety.pptx.pptx of all the world
Welding_Safety.pptx.pptx of all the worldWelding_Safety.pptx.pptx of all the world
Welding_Safety.pptx.pptx of all the worldLeonardMendez4
 
Fire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafeFire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafeAtlantic Training, LLC.
 
ICS flue system installation instructions
ICS flue system installation instructionsICS flue system installation instructions
ICS flue system installation instructionsSchiedel UK
 
Concept of Fire damper by Md Yusuf
Concept of Fire damper by Md Yusuf Concept of Fire damper by Md Yusuf
Concept of Fire damper by Md Yusuf Yusufyn
 
Flammable-Combustible Liquids.pptx
Flammable-Combustible Liquids.pptxFlammable-Combustible Liquids.pptx
Flammable-Combustible Liquids.pptxSholaEsho3
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfMarcGajudo
 

Similar to Fire Safety - Fire Prevention and Protection training (13)

Fire_Protection_Subpart_L_GA_Tech.ppt
Fire_Protection_Subpart_L_GA_Tech.pptFire_Protection_Subpart_L_GA_Tech.ppt
Fire_Protection_Subpart_L_GA_Tech.ppt
 
Fire_Protection_Subpart_L_GA_Tech (1).ppt
Fire_Protection_Subpart_L_GA_Tech (1).pptFire_Protection_Subpart_L_GA_Tech (1).ppt
Fire_Protection_Subpart_L_GA_Tech (1).ppt
 
Welding_Safety.pptx.pptx of all the world
Welding_Safety.pptx.pptx of all the worldWelding_Safety.pptx.pptx of all the world
Welding_Safety.pptx.pptx of all the world
 
Welding_Safety.pptx
Welding_Safety.pptxWelding_Safety.pptx
Welding_Safety.pptx
 
Fire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafeFire Protection and Prevention Training by RoofSafe
Fire Protection and Prevention Training by RoofSafe
 
Welding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&IWelding Safety by Pennsylvania L&I
Welding Safety by Pennsylvania L&I
 
ICS flue system installation instructions
ICS flue system installation instructionsICS flue system installation instructions
ICS flue system installation instructions
 
Fire fighting -1 By Er. Ezaz
Fire fighting -1 By Er. EzazFire fighting -1 By Er. Ezaz
Fire fighting -1 By Er. Ezaz
 
Concept of Fire damper by Md Yusuf
Concept of Fire damper by Md Yusuf Concept of Fire damper by Md Yusuf
Concept of Fire damper by Md Yusuf
 
SAPPHIRE
SAPPHIRESAPPHIRE
SAPPHIRE
 
Flammable-Combustible Liquids.pptx
Flammable-Combustible Liquids.pptxFlammable-Combustible Liquids.pptx
Flammable-Combustible Liquids.pptx
 
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdfashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
ashraeqatar_16.04.09_s_p_introduction_to_car_park_jetfan_ventilation_1.pdf
 
Polaris FID
Polaris FIDPolaris FID
Polaris FID
 

Recently uploaded

Student login on Anyboli platform.helpin
Student login on Anyboli platform.helpinStudent login on Anyboli platform.helpin
Student login on Anyboli platform.helpinRaunakKeshri1
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionSafetyChain Software
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introductionMaksud Ahmed
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsTechSoup
 
Arihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfArihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfchloefrazer622
 
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...Sapna Thakur
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13Steve Thomason
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...EduSkills OECD
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxiammrhaywood
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)eniolaolutunde
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Krashi Coaching
 
The byproduct of sericulture in different industries.pptx
The byproduct of sericulture in different industries.pptxThe byproduct of sericulture in different industries.pptx
The byproduct of sericulture in different industries.pptxShobhayan Kirtania
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactdawncurless
 
APM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAPM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAssociation for Project Management
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104misteraugie
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxGaneshChakor2
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfciinovamais
 

Recently uploaded (20)

Student login on Anyboli platform.helpin
Student login on Anyboli platform.helpinStudent login on Anyboli platform.helpin
Student login on Anyboli platform.helpin
 
Mastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory InspectionMastering the Unannounced Regulatory Inspection
Mastering the Unannounced Regulatory Inspection
 
microwave assisted reaction. General introduction
microwave assisted reaction. General introductionmicrowave assisted reaction. General introduction
microwave assisted reaction. General introduction
 
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptxINDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
INDIA QUIZ 2024 RLAC DELHI UNIVERSITY.pptx
 
Introduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The BasicsIntroduction to Nonprofit Accounting: The Basics
Introduction to Nonprofit Accounting: The Basics
 
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
Mattingly "AI & Prompt Design: Structured Data, Assistants, & RAG"
 
Arihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdfArihant handbook biology for class 11 .pdf
Arihant handbook biology for class 11 .pdf
 
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
BAG TECHNIQUE Bag technique-a tool making use of public health bag through wh...
 
The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13The Most Excellent Way | 1 Corinthians 13
The Most Excellent Way | 1 Corinthians 13
 
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
Presentation by Andreas Schleicher Tackling the School Absenteeism Crisis 30 ...
 
Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1Código Creativo y Arte de Software | Unidad 1
Código Creativo y Arte de Software | Unidad 1
 
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptxSOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
SOCIAL AND HISTORICAL CONTEXT - LFTVD.pptx
 
Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)Software Engineering Methodologies (overview)
Software Engineering Methodologies (overview)
 
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
Kisan Call Centre - To harness potential of ICT in Agriculture by answer farm...
 
The byproduct of sericulture in different industries.pptx
The byproduct of sericulture in different industries.pptxThe byproduct of sericulture in different industries.pptx
The byproduct of sericulture in different industries.pptx
 
Accessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impactAccessible design: Minimum effort, maximum impact
Accessible design: Minimum effort, maximum impact
 
APM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across SectorsAPM Welcome, APM North West Network Conference, Synergies Across Sectors
APM Welcome, APM North West Network Conference, Synergies Across Sectors
 
Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104Nutritional Needs Presentation - HLTH 104
Nutritional Needs Presentation - HLTH 104
 
CARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptxCARE OF CHILD IN INCUBATOR..........pptx
CARE OF CHILD IN INCUBATOR..........pptx
 
Activity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdfActivity 01 - Artificial Culture (1).pdf
Activity 01 - Artificial Culture (1).pdf
 

Fire Safety - Fire Prevention and Protection training

  • 1. Fire Protection & Prevention 1 PPT-116-01 CFR 1926 Subpart F Bureau of Workers’ Compensation PA Training for Health & Safety (PATHS)
  • 2. PPT-116-01 2 Subpart F - Fire Protection & Prevention (1926.150 - 159) 33 26 18 15 15 150(c)(1)(i) 152(a)(1) 153(j) 150(a)(1) 150(c)(1)(vi) Standard - 1926. Flammables/combustibles - Approved containers Fire protection program/equipment 2A fire extinguishers - Building area Storage of LPG containers 10B fire extinguisher within 50 ft. of flammable/combustible liquids Fire Protection & Prevention
  • 3. PPT-116-01 3 Definitions "Combustible liquid" means any liquid having a flash point at or above 140 deg. F., and below 200 deg. F "Flammable liquid" means any liquid having a flash point below 140 deg. F and having a vapor pressure not exceeding 40 pounds per square inch (absolute) at 100 deg. F.
  • 4. PPT-116-01 4 Combustible & Flammable Liquids 200 Fº 140 Fº 100 Fº 73 Fº Boiling Point Fº IA IB IC II III Combustible Flash point > 100 Fº Flammable Flash point < 100 Fº
  • 5. PPT-116-01 5 Definitions • The minimum temperature at which a liquid gives off vapor within a test vessel in sufficient concentration to form an ignitable mixture with air near the surface of the liquid. • The flash point is normally an indication of susceptibility to ignition. Flash Point
  • 6. PPT-116-01 6 Definitions Flammable (Explosive) Limits • The flammable range includes all concentrations of flammable vapor or gas in air, in which a flash will occur or a flame will travel if the mixture is ignited.
  • 7. PPT-116-01 7 Flammable (Explosive) Limits Explosion Pressure LEL UEL Vapor/Gas Concentration in Air (%) Flammable Range
  • 8. • Safety can shall mean an approved container, of not more than 5 gallons capacity, having a spring-closing lid and spout cover and so designed that it will safely relieve internal pressure when subjected to fire exposure. PPT-116-01 8 Safety Can
  • 9. Employer responsibility: • Development and maintenance of an effective fire protection and prevention program • At the jobsite • Throughout all phases of construction • Comply with provisions of Subpart F PPT-116-01 9 1926.24 Fire Protection and Prevention
  • 10. PPT-116-01 10 1926.150 General Requirements • Maintain access to fire fighting equipment at all times • Conspicuously located • Periodically inspected • Defective replaced
  • 11. PPT-116-01 11 1926.150 General Requirements • Fire brigade provided as warranted • Provide water supply to protect against combustibles
  • 12. PPT-116-01 12 Subpart F - Fire Protection • Know what to look for when inspecting! – Type of extinguisher – Labeling – Pins in place? – Charged? – Heft test – Annual Hydrostatic test
  • 13. PPT-116-01 13 1926.150 General Requirements Fire extinguishers: • Fire extinguisher provided every 3000 ft² • In protected areas travel distance to extinguisher < 100 feet • Minimum one extinguisher per floor • Multi-story at least one near stairway
  • 14. PPT-116-01 14 1926.150 General Requirements • Minimum 10B extinguisher within 50 feet of 5 gallons flammable liquid or 5 pounds flammable gas • Extinguishers inspected and maintained in accordance with NFPA No. 10A-1970.
  • 15. PPT-116-01 15 Subpart F - Fire Protection Types of Fires • Class A - Ordinary materials such as paper, wood, cloth • Class B - Flammable liquids or Combustible liquids such as gasoline, paint, thinners, propane, kerosene • Class C - Electrical equipment fires, appliances, switches, panels • Class D - Certain metals such as magnesium, sodium, that could explode!
  • 17. PPT-116-01 17 Subpart F - Fire Protection
  • 18. PPT-116-01 18 1926.150 General Requirements • Alarm system established for emergencies: - Alert employees - Alert fire department • Reporting instructions conspicuously posted by phones and worker entrances
  • 19. PPT-116-01 19 1926.150 General Requirements Fire Cutoffs: • Fire walls & exit stairways given construction priority • For demolition, retain fire walls until removal required
  • 20. PPT-116-01 20 1926.151 Fire Prevention • Electrical for light, heat, and power complies with Subpart K • Engine combustion well away from combustibles • No smoking around fire hazards and signs posted
  • 21. PPT-116-01 21 1926.151 Fire Prevention • Combustible piles no higher than 20 feet • Driveways around combustible piles minimum 15 feet wide • Maximum driveway grid 50' by 150' 15' 150' 50' 20'
  • 22. PPT-116-01 22 1926.151 Fire Prevention 150' 50' 20' 15' • No piles within ten feet of buildings • Fire extinguisher provided within 100 feet 10'
  • 23. PPT-116-01 23 1926.151 Fire Prevention Indoor Storage: • No obstruction to exit • Appropriate management of all fire hazard materials • Segregate non- compatibles • Three feet clearance maintained to sprinklers
  • 24. PPT-116-01 24 1926.152 Flammable & Combustible Liquids • Flammable liquids > 1 gallon requires safety can • Flammables not stored near exits or stairways
  • 25. PPT-116-01 25 1926.152 Flammable & Combustible Liquids Inside Storage: • Max 25 gallons stored outside flammable cabinet • Cabinets labeled “Flammable - Keep Fire Away”
  • 26. PPT-116-01 26 1926.152 Flammable & Combustible Liquids • Dispensing 5 gallons or more, segregate 25 feet from other operations • Bonding required for container transfer
  • 27. PPT-116-01 27 1926.152 Flammable & Combustible Liquids • The dispensing units shall be protected against collision damage • Containers closed when not in use
  • 28. PPT-116-01 28 1926.153 Liquefied petroleum gas (LP-Gas) • Systems, valves, connectors of approved type • Welding is prohibited on containers • Storage of LPG within buildings is prohibited • Filling of portable containers or containers mounted on skids from storage containers shall be performed not less than 50 feet from the nearest building.
  • 29. PPT-116-01 29 Contact Information Health & Safety Training Specialists 1171 South Cameron Street, Room 324 Harrisburg, PA 17104-2501 (717) 772-1635 RA-LI-BWC-PATHS@pa.gov Like us on Facebook! - https://www.facebook.com/BWCPATHS

Editor's Notes

  1. The afore mentioned definitions for classification of flammable and combustible liquids are quite complex. The diagram above should aid in their understanding.
  2. Since it is the vapor of the liquid, not the liquid itself, that burns, vapor generation becomes the primary factor in determining the fire hazard. The expression "low flash - high hazard" applies. Liquids having flash points below ambient storage temperatures generally display a rapid rate of flame spread over the surface of the liquid, since it is not necessary for the heat of the fire to expend its energy in heating the liquid to generate more vapor.
  3. There is a minimum concentration of vapor or gas in air below which propagation of flame does not occur on contact with a source of ignition. There is also a maximum proportion of vapor in air above which propagation of flame does not occur.
  4. These boundary-line mixtures of vapor with air are known as the lower and upper flammable or explosive limits (LEL or UEL) respectively, and they are usually expressed in terms of percentage by volume of vapor in air.
  5. The employer shall be responsible for the development and maintenance of an effective fire protection and prevention program at the job site throughout all phases of the construction, repair, alteration, or demolition work. The employer shall ensure the availability of the fire protection and suppression equipment required by Subpart F of this part.
  6. The employer shall be responsible for the development and maintenance of an effective fire protection and prevention program at the job site throughout all phases of the construction, repair, alteration, or demolition work. The employer shall ensure the availability of the fire protection and suppression equipment required by Subpart F of this part.
  7. A temporary or permanent water supply, of sufficient volume, duration, and pressure, required to properly operate the firefighting equipment shall be made available as soon as combustible materials accumulate. Where underground water mains are to be provided, they shall be installed, completed, and made available for use as soon as practicable.
  8. A fire extinguisher, rated not less than 2A, shall be provided for each 3,000 square feet of the protected building area, or major fraction thereof. Travel distance from any point of the protected area to the nearest fire extinguisher shall not exceed 100 feet. One 55-gallon open drum of water with two fire pails may be substituted for a fire extinguisher having a 2A rating. A 1/2-inch diameter garden-type hose line, not to exceed 100 feet in length and equipped with a nozzle, may be substituted for a 2A-rated fire extinguisher, providing it is capable of discharging a minimum of 5 gallons per minute with a minimum hose stream range of 30 feet horizontally. The garden-type hose lines shall be mounted on conventional racks or reels. The number and location of hose racks or reels shall be such that at least one hose stream can be applied to all points in the area. One or more fire extinguishers, rated not less than 2A, shall be provided on each floor. In multistory buildings, at least one fire extinguisher shall be located adjacent to stairway. Extinguishers and water drums, subject to freezing, shall be protected from freezing.
  9. A fire extinguisher, rated not less than 10B, shall be provided within 50 feet of wherever more than 5 gallons of flammable or combustible liquids or 5 pounds of flammable gas are being used on the jobsite. This requirement does not apply to the integral fuel tanks of motor vehicles.
  10. An alarm system, e.g., telephone system, siren, etc., shall be established by the employer whereby employees on the site and the local fire department can be alerted for an emergency. The alarm code and reporting instructions shall be conspicuously posted at phones and at employee entrances.
  11. Electrical wiring and equipment for light, heat, or power purposes shall be installed in compliance with the requirements of Subpart K of this part. Internal combustion engine powered equipment shall be so located that the exhausts are well away from combustible materials. When the exhausts are piped to outside the building under construction, a clearance of at least 6 inches shall be maintained between such piping and combustible material. Smoking shall be prohibited at or in the vicinity of operations which constitute a fire hazard, and shall be conspicuously posted: "No Smoking or Open Flame.” Portable battery powered lighting equipment, used in connection with the storage, handling, or use of flammable gases or liquids, shall be of the type approved for the hazardous locations.
  12. Combustible materials shall be piled with due regard to the stability of piles and in no case higher than 20 feet. Driveways between and around combustible storage piles shall be at least 15 feet wide and maintained free from accumulation of rubbish, equipment, or other articles or materials. Driveways shall be so spaced that a maximum grid system unit of 50 feet by 150 feet is produced. The entire storage site shall be kept free from accumulation of unnecessary combustible materials. Weeds and grass shall be kept down and a regular procedure provided for the periodic cleanup of the entire area. When there is a danger of an underground fire, that land shall not be used for combustible or flammable storage.
  13. Method of piling shall be solid wherever possible and in orderly and regular piles. No combustible material shall be stored outdoors within 10 feet of a building or structure. Portable fire extinguishing equipment, suitable for the fire hazard involved, shall be provided at convenient, conspicuously accessible locations in the yard area. Portable fire extinguishers, rated not less than 2A, shall be placed so that maximum travel distance to the nearest unit shall not exceed 100 feet.
  14. Storage shall not obstruct, or adversely affect, means of exit. All materials shall be stored, handled, and piled with due regard to their fire characteristics. Noncompatible materials, which may create a fire hazard, shall be segregated by a barrier having a fire resistance of at least 1 hour. Material shall be piled to minimize the spread of fire internally and to permit convenient access for firefighting. Stable piling shall be maintained at all times. Aisle space shall be maintained to safely accommodate the widest vehicle that may be used within the building for firefighting purposes. Clearance of at least 36 inches shall be maintained between the top level of the stored material and the sprinkler deflectors. Clearance shall be maintained around lights and heating units to prevent ignition of combustible materials. A clearance of 24 inches shall be maintained around the path of travel of fire doors unless a barricade is provided, in which case no clearance is needed. Material shall not be stored within 36 inches of a fire door opening.
  15. Only approved containers and portable tanks shall be used for storage and handling of flammable and combustible liquids. Approved metal safety cans shall be used for the handling and use of flammable liquids in quantities greater than one gallon, except that this shall not apply to those flammable liquid materials which are highly viscid (extremely hard to pour), which may be used and handled in original shipping containers. For quantities of one gallon or less, only the original container or approved metal safety cans shall be used for storage, use, and handling of flammable liquids. Flammable or combustible liquids shall not be stored in areas used for exits, stairways, or normally used for the safe passage of people.
  16. No more than 25 gallons of flammable or combustible liquids shall be stored in a room outside of an approved storage cabinet. For storage of liquefied petroleum gas, see 1926.153. Quantities of flammable and combustible liquid in excess of 25 gallons shall be stored in an acceptable or approved cabinet meeting the following requirements: Acceptable wooden storage cabinets shall be constructed in the following manner, or equivalent: The bottom, sides, and top shall be constructed of an exterior grade of plywood at least 1 inch in thickness, which shall not break down or delaminate under standard fire test conditions. All joints shall be rabbeted and shall be fastened in two directions with flathead wood screws. When more than one door is used, there shall be a rabbeted overlap of not less than 1 inch. Steel hinges shall be mounted in such a manner as to not lose their holding capacity due to loosening or burning out of the screws when subjected to fire. Such cabinets shall be painted inside and out with fire retardant paint. Approved metal storage cabinets will be acceptable. Cabinets shall be labeled in conspicuous lettering, "Flammable-Keep Fire Away."
  17. Areas in which flammable or combustible liquids are transferred at one time, in quantities greater than 5 gallons from one tank or container to another tank or container, shall be separated from other operations by 25-feet distance or by construction having a fire resistance of at least 1 hour. Drainage or other means shall be provided to control spills. Adequate natural or mechanical ventilation shall be provided to maintain the concentration of flammable vapor at or below 10 percent of the lower flammable limit. Transfer of flammable liquids from one container to another shall be done only when containers are electrically interconnected (bonded).
  18. The dispensing units shall be protected against collision damage. Flammable liquids shall be kept in closed containers when not actually in use. Leakage or spillage of flammable or combustible liquids shall be disposed of promptly and safely.