Safeguarding our future
with consistent energy efficiency!
Rittal – System climate control
Rittal is your value-creating partner for comprehensive
technology packaging solutions. We offer individual
system benefits based on our complete product range,
extensive expertise and global customer service – cross-
sector, value-maximising solutions that are one hundred
percent benefit-focussed.
Rittal system climate control is proven to boost energy
efficiency by up to 45 percent – while ensuring optimum
cooling performance for all control and IT components.
Thanks to the significant reduction in energy consumption,
Rittal’s innovative cooling concepts are major contributors
to cost efficiency in your company, while at the same time
helping to cut CO2 emissions in the environment.
From system to solution:
Comprehensively individual
However individual your business, you can be sure
that all Rittal climate control systems provide a
comprehensive expert package:
● Exemplary energy efficiency
● Plus special project engineering
● Plus permanent innovative strength
● Plus typical Rittal high-quality production.
Rittal never loses sight of a project’s particular
customer requirements. The aim is always the same:
to produce maximum benefits for the customer.
Expertise Efficiency Engineering Innovation High quality+ + + +
3Rittal System Climate Control
Outdoor climate control from page 157
Cooling units for CS modular enclosures .......................................160
Heat exchangers for CS modular enclosures ................................161
Climate control units for Toptec CR............................................... 163
Ex-proof climate control systems ...................................................164
Liquid cooling IE from page 99
Air/water heat exchangers, roof-mounted .....................................100
Air/water heat exchangers, wall-mounted .................................... 100
Direct Cooling Package (mounting plate cooling)......................... 110
Recooling systems for water ..........................................................116
Recooling systems for oil............................................................... 130
Immersible recooling systems for oil/emulsion ............................. 132
System solutions from page 15
For mechanical engineering .............................................................15
For the IT sector................................................................................19
For various ambient conditions.........................................................23
For final assembly/handling systems................................................27
Project planning from page 31
Basic principles for the use of climate control components ............32
Cooling with ambient air ...................................................................35
Cooling units .....................................................................................36
Liquid cooling IE/IT ...........................................................................37
Enclosure heaters .............................................................................39
Enclosure heaters from page 167
Enclosure heaters ..........................................................................168
System accessories from page 171
Air routing....................................................................................... 174
Control/regulation........................................................................... 177
Mounting accessories.................................................................... 181
Cold Plate....................................................................................... 184
Liquid Cooling Package ................................................................ 186
Filter technology ............................................................................ 189
General .......................................................................................... 192
Software service........................................................................... 195
Cooling with ambient air from page 41
Fan-and-filter units ............................................................................42
Rack-mounted fans...........................................................................50
Tangential fans..................................................................................50
Fan systems......................................................................................54
Air/air heat exchangers.....................................................................60
Cooling units from page 67
Modular climate control concept ......................................................68
Roof-mounted cooling units..............................................................72
Wall-mounted cooling units ..............................................................80
Thermoelectric coolers .....................................................................96
Tips and tricks from page 197
Cooling with ambient air .................................................................198
Cooling units ...................................................................................207
Liquid cooling IE .............................................................................217
Liquid cooling IT .............................................................................230
Enclosure heaters ...........................................................................234
Monitoring .......................................................................................235
Technical details from page 239
Cooling with ambient air .................................................................240
Cooling units ...................................................................................245
Liquid cooling IE .............................................................................251
Liquid cooling IT .............................................................................266
Enclosure heaters ...........................................................................267
System accessories........................................................................268
Overview of products and approvals from page 271
Overview of products and approvals .............................................272
Service .......................................................................................... 298
List of model numbers................................................................. 300
Index.............................................................................................. 303
Liquid cooling IT from page 135
CRAC systems................................................................................136
Aisle containment........................................................................... 139
Liquid Cooling Package (rack cooling) ......................................... 140
Chillers for IT cooling ......................................................................146
Water/water heat exchangers ........................................................150
Piping systems................................................................................154
4
Rittal climate expertise
5
Rittal climate expertise –
Outstanding breadth and quality.
Rittal cooling concepts are
synonymous with guaranteed
quality, from the product itself
right through to customer service.
Global availability, globally sought-
after. International approvals are
just as much part of the Rittal
“system concept” as uniform
system platforms for cooling units
and heat exchangers. Rittal’s
winning formula for climate control
expertise centres around one
basic idea, with infinite
possibilities. Flexible, inexpensive,
and exceptionally efficient. Rittal
cooling concepts are complete
solutions, precisely tailored to
your requirements and offering
exceptional added-value.
6
Total efficiency
7
Rittal efficiency – A fresh take on
creativity and value-added.
Thanks to its intensive research
and development work with
Pro Ozone cooling units, Rittal
has helped to focus the world’s
attention on “efficiency”. With a
host of innovative ideas such as
nano surface protection, the
Liquid Cooling product family and
coolants based on environmentally
neutral CO2, Rittal is renowned as
a world leader in this field.
Less is more, is our guiding
principle: Less consumption of
energy and resources on the
one hand, and more cost-
effectiveness and productivity
for customers on the other. Rittal’s
solutions successfully unite these
two principles.
Engineering partners
9
Rittal engineering – Building on
cooperation for a shared future.
Whether you require analysis of an
existing climate control concept,
or help planning a new one, Rittal
is a partner you can rely on. As
well as manufacturing system com-
ponents, Rittal also collaborates
closely with customers in the
research and development field.
We act as engineering partners
to our clients. A combination of
practical experience and project
planning leads to innovative,
comprehensive climate control
concepts.
Rittal’s customer service and main-
tenance divisions guarantee com-
plete customer satisfaction from
start to finish.
10
Innovative strength
11
Rittal’s innovative strength –
Deriving fresh growth from
ideas.
Innovation cannot be planned,
but it can be continuously re-
evaluated. This is Rittal’s approach
when tackling any new task. In an
instant, an idea is born, which the
Rittal laboratories then develop
into a new product solution. The
thermoelectric cooler, which cuts
energy consumption by more than
60 % compared with conventional
systems, is just one innovative
high-end example among many.
Rittal’s engineers are encouraged
to think outside the box and come
up with new solutions. These ideas
add value and help to make our
customers more competitive.
12
High quality production
13
Rittal high quality production –
Top quality begins with the
tiniest detail.
Rittal achieves outstanding high-
quality at its own production sites
and in-house research depart-
ments, development units and test
laboratories. This in turn enables
us to guarantee outstanding pro-
duct quality, because our process
quality is second to none. Every
department is broken down into
individual process units, each of
which plays a vital role in Rittal’s
overall quality. High quality pro-
duction relies on a perfect quality
assurance chain. This quality
standard reflects Rittal’s 100 %
customer dedication.
14
15Rittal System Climate Control
Systemsolutions/Mechanicalengineering
Rittal DCP –
Direct Cooling Package
Direct cooling of power electronics
inside the enclosure
● Using liquid-cooled mounting
plates, with or without fans
● No impairment to the protection
category
● With efficient frequency converter
cooling.
Air/water heat exchangers
The classic liquid cooling solution
● For extremely hot and dusty ambient
conditions
● To dissipate high heat loads without putting
thermal pressure on the ambient air.
Rittal recooling systems
Energy-efficient cooling of liquid
cooling media.
● A high level of temperature
accuracy.
● Powerful performance.
● Individual system solutions.
Rittal system climate control for mechanical engineering
Precision scores
an ace
Whenever a higher enclosure protection category is required due to hot, metal dust-
laden or oily ambient conditions, Rittal liquid cooling concepts really come up
trumps.
Precise temperature control of machine and process cooling is another priority.
When cooling spindles with 40,000 rpm, for example, Rittal recooling systems
supply volumetric flows and coolant temperatures at precisely the required level.
Rittal system climate control is the key to a high level of dimensional accuracy,
consistently perfect workpieces, and stable production conditions.
16 Rittal System Climate Control
Systemexample
System example
Rittal system climate control for mechanical engineering
5
A
C
B
2
6
1011 812
19 20
9
13 16
16
14 15
26 27 28 25 2123 24 22
7
4
17
18
29
31
32
35
30
33
34
3 1
Example: Rittal system climate
control for mechanical and plant
engineering
The air inside the hall is contaminated with
metal swarf and oil mist, and is unable to
absorb waste heat from the controllers and
machine cooling system. A comprehensive
Rittal liquid cooling concept with central
recooling (1) provides a particularly efficient
solution.
All function and safety-relevant components
are remotely monitored with Rittal CMC-TC
(3). The benefit to you: Added perfection and
increased productivity.
Machining centre, welding robot
● The coolant temperature of the process
emulsion is precisely coordinated with the
machining cycle of the spindle rotating at
high speed, thanks to the immersion
recooling system (7).
● Process heat from the welding robot and
heat loss from the PC case of the robot
controller (18) – case based on TS 8,
equipped with air/water heat exchanger
(17) – is effectively dissipated via Rittal
recooling systems (1).
● The twin-doored enclosure ES 5000 with
air/water heat exchanger, wall-mounted
(8), is integrated into the design of the
machines.
● Rittal thermoelectric coolers (16) are a
particularly compact, efficient solution
for cooling the Rittal Comfort Panel (13)
command panels.
The enclosure is custom-built and
equipped to order, with a support arm
system (15) tailored to your individual
requirements.
Machine controller, low-voltage distributor
● Bayed Top enclosure system TS 8 (24).
● Rittal DCP: Liquid-cooled mounting plates
(Cold Plate) (21) for efficient frequency
converter cooling and
● TopTherm air/water heat exchangers, roof-
mounted (23) and wall-mounted (22), with
internal controllers for monitoring and
control, reliably dissipate the heat loss.
● The modular power supply is type-tested
for global use (28).
Industrial IT and control room
● Network enclosures are effectively climate-
controlled with a special, low-noise office
cooling unit (29).
● EMC fan-and-filter units (30) cool the
command controller in the pedestals of the
TopConsole systems (33).
A
C
B
17Rittal System Climate Control
Systemexample
Rittal system climate control for mechanical engineering
System example
System-wide
Components Page
Central recooling system for
enclosure and machine cooling
148
Piping systems 154
CMC-TC for monitoring
access, climate, power supply
Cat. 32, p. 808
Test workstation: Rittal Industrial Workstation
with support arm CP-S, TFT screen, membrane
keyboard
Cat. 32, p. 172
Air/water heat exchanger on the IW pedestal 63
Ex overpressure enclosure, climate-controlled 164
Ex overpressure enclosure with
integral enclosure cooling unit
for zone II, gas (6)
1
2
3
4
5
6
Machining centre, welding robot
Components Page
Immersible recooling system for process emulsion 132
Air/water heat exchanger, wall-mounted 104
Free-standing enclosure ES 5000, twin-door Cat. 32, p. 155
Cable entry, cable routing Cat. 32, p. 1045
Interior installation, mounting levels Cat. 32, p. 988
Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125
Rittal Comfort Panel command panel Cat. 32, p. 192
Monitors, keyboards, handles for the Comfort Panel Cat. 32, p. 1133
CP-L support arm system for Comfort Panel Cat. 32, p. 250
Thermoelectric cooler for Comfort Panel 97
Air/water heat exchanger, space-saving
accommodated on the roof of the PC case
74
PS enclosure system, based on TS 8 Cat. 32, p. 168
Base/plinth for PC case system Cat. 32, p. 892
Bus enclosure Cat. 32, p. 120
More compact, lightweight and
efficient.
The powerful thermoelectric
cooling unit in a lightweight
design (16).
The eco-friendly climate control
solution for command panels
and small enclosures – an
energy saving of more than
60 % compared with conven-
tional industry systems.
A
7
8
9
10
11
12
13
14
15
16
17
18
19
20
Machine controller, low-voltage distributor
Components Page
Rittal DCP Cold Plate – Liquid-cooled mounting
plates
112
Air/water heat exchanger, wall-mounted 104
Air/water heat exchanger, roof-mounted 102
Baying enclosure system TS 8 Cat. 32, p. 136
System accessories (base/plinth, walls, baying
technique, locks, interior installation, cable routing)
Cat. 32, p. 926
Ri4Power Form 1, heavy current power distributor Cat. 32, p. 438
Ri4Power Form 2-4, form separation for low-voltage
switchgear
Cat. 32, p. 472
RiLine60, busbar systems Cat. 32, p. 350
Rittal DCP Cold Plate – Liquid-
cooled mounting plates (21)
B
21
22
23
24
25
26
27
28
Industrial IT and control room
Components Page
Office cooling units for network enclosures 76
EMC fan-and-filter units for console systems 48
Network enclosures, based on TS 8 Cat. 32, p. 745
System accessories for IT (patch panels,
component shelves)
Cat. 32, p. 1013
TopConsole system Cat. 32, p. 156
System accessories for consoles (base/plinth,
interior installation)
Cat. 32, p. 890
System accessories for the human/machine
interface (keyboard drawers, TFT monitors,
keyboards)
Cat. 32, p. 1115
Quiet performance: Office
cooling units for network
enclosures (29)
C
29
30
31
32
33
34
35
19Rittal System Climate Control
Systemsolutions/ITsector
Rittal system climate control for data centres and IT
Cool and efficient!
A high performance server in the data centre or in the middle of the office? Without
putting additional thermal pressure on the air-conditioning system? Without the
irritating noise of high-speed fan-and-filter units? All that can now be achieved very
easily!
Because Rittal Liquid Cooling concepts offer new framework conditions for your
IT infrastructures in terms of flexibility, safety and cost-efficiency. Independent of the
room situation, with almost zero heat and noise emissions, individual server CPUs
and complete server units or electronic components receive direct, highly effective
cooling.
Modular concepts, tailored precisely to your current requirements, and easily
scalable to meet future needs.
Rittal CRAC systems
By using Rittal aisle containment,
● you can optimise air-conditioning of
the room
● in conjunction with the Rittal CRAC
system
● in terms of energy efficiency and
cooling output.
LCP – Liquid Cooling Package
Rittal solves the problem of climate control for
high heat losses per rack with this system
family.
● Extremely high heat loads are dissipated
from the rack via the LCP (air/water heat
exchanger).
● Additionally, this system also allows
temperature-neutral expansion of the
data centre.
Piping systems
The Rittal piping system provides the
link between the equipment and the
refrigeration system.
● An optimum design and targeted
media supply ensure efficient oper-
ation of all cooling components.
20 Rittal System Climate Control
Systemexample
System example
Rittal system climate control for the IT sector
C
A
B
3
2
1
9
30
4
1.1
5
6
8
10
13
14
17
15
16
18
19
22
20
21
11
12
7
292824 23272625
Example: Rittal system climate
control for data centres and IT
High heat loads in modern data centres,
maximum availability, and the most energy-
efficient climate control system available.
To accommodate all three requirements, you
will need an individual concept:
Rittal liquid cooling IT. Redundant chillers
(1), free cooling (1.1) and heat recovery (7).
Piping systems are designed on a project-
specific basis.
Data centre
● At the heart of this concept are server
racks (9) with the option of aisle
containment (8).
● The cold air required is blasted in via the
raised floor by two CRAC systems (10).
● Other LCP-cooled (11) computer cases
also operate without dissipating heat to
the ambient air.
Development server room, UPS
● The server systems are cooled via LCPs
(14), without a raised floor and without
putting pressure on the climate control
system. The heat is dissipated completely
silently via the piping system.
● All server racks are based on the TS 8
enclosure platform (15).
● The dissipation of heat loss from the UPS
is also integrated into the liquid cooling
concept via the air/water heat exchanger.
● Alternative recooling via LCP Inline or
LCP Extend.
Administration, monitoring
● All function and safety-relevant
components are remotely monitored with
Rittal CMC-TC. Messages and controls
occur centrally in the control room (23).
● Super-low-noise roof-mounted fans (23)
cool the network enclosures in the office.
An even quieter alternative are air/water
heat exchangers integrated into the
coolant cycle.
● EMC fan-and-filter units with speed
control (24) ensure fault-free operation
and cooling of the control room consoles.
The result: Targeted, low-noise, energy
efficient!
A
B
C
21Rittal System Climate Control
Systemexample
Rittal system climate control for the IT sector
System example
System-wide
Components Page
IT chiller, redundant configuration,
also with free cooling device
146
or external free cooling function 147
Double pump unit 147
Water/water heat exchanger 152
Buffer store
Water/water heat exchanger 152
Emergency water supply
Heat recovery
IT chiller, redundant
configuration, also with
free cooling (1).
1
1.1
2
3
4
5
6
7
Data centre with raised floor
Components Page
Rittal aisle containment 139
Server racks for aisle containment
CRAC systems for raised floor and aisle flooding 138
Room temperature-neutral server extension,
cooling with LCP Standard, Plus or Smart
Cat. 32, p. 726
Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777
System accessories for server racks (cable
management devices, monitor/keyboard unit,
KVM switch, power distribution, plug-in modules,
component shelves, base/plinths and much more
besides)
Cat. 32, p. 890
CRAC systems for raised floor
and aisle flooding (10)
A
8
9
10
11
12
13
Server room without raised floor, UPS
Components Page
Separate servers in the development department,
cooling with LCP Standard, Plus or Smart
140
LCP Inline 145
LCP Extend 143
Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777
System accessories for server racks Cat. 32, p. 787
Air/water heat exchangers for UPS cooling 104
UPS: Power Modular Concept PMC,
rack basis TS 8
Cat. 32, p. 786
Power distribution: Power Distribution Rack PDR Cat. 32, p. 787
Socket strips: Power System Module PSM Cat. 32, p. 789
Ambient air-neutral server
cooling with LCP air/water
heat exchangers (14)
B
14
15
16
17
18
19
20
21
22
Server and network administration, video monitoring
Components Page
Roof-mounted fan for the office sector 76
EMC fan-and-filter units for console systems
with speed control
48
CMC-TC, modular system for monitoring
climate, access and power supply
Cat. 32, p. 806
Network enclosures, based on TS 8 Cat. 32, p. 745
System accessories for IT (patch panels,
component shelves)
Cat. 32, p. 1013
TopConsole system Cat. 32, p. 156
System accessories for consoles (base/plinth,
interior installation)
Cat. 32, p. 890
System accessories for the human/machine
interface (keyboard drawers, TFT monitors,
keyboards)
Cat. 32, p. 1115
Roof-mounted fan for the office
sector (23)
C
23
24
25
26
27
28
29
30
23Rittal System Climate Control
Systemsolutions/Variousambientconditions
Rittal system climate control for various ambient conditions
TopTherm-Plus
Cleaning, phosphating, dipcoat-priming, spray-finishing, drying. The process
chain in a spray-finishing plant creates extremely varied ambient conditions – and
this also affects climate control of the controllers. Whether humidity, paint dust or
drying heat – these varying requirements are met by a single product range:
Rittal TopTherm-Plus cooling units.
With nano-coating of the heat exchanger surfaces, this ensures a high level of
efficiency and exceptional durability.
Rittal cooling units – Masters of energy efficiency
TopTherm-Plus cooling units
Cooling units keep the enclosure
internal temperature at a constant
level, even to below room tempera-
ture, with the air routing being tai-
lored to individual requirements. Two
separate circuits prevent the ingress
of dust into the enclosure.
● Climate control doors
● Roof-mounted cooling units
● Wall-mounted cooling units
Electronic condensate evaporation
Any condensate incurred is effectively
evaporated and doesn’t need to be
collected or dissipated.
Your value-added:
● Enhanced safety – No condensate drips
onto the floor.
● Time savings – No need to empty
condensate containers.
● Cost benefits – No need to lay condensate
tubing.
Master/slave mode
In open bayed enclosure systems,
cooling units or air/water heat
exchangers with Comfort control
are set to master/slave mode via a
bus cable:
● Even temperature distribution
across all sections of the enclosure.
● Simultaneous activation and
deactivation of the devices.
● Parallel system and door limit
switch function.
24 Rittal System Climate Control
Systemexample
System example
Rittal system climate control for various ambient conditions
1 2 6
10
8
19
91211 7
5
4
14
16
15
17
18
20
23
24
21
22
3
13
A
B
D
C
Example: Rittal system climate
control for various ambient
conditions
Rittal TopTherm-Plus cooling units define
the performance class of the future. Even
under extremely varied ambient conditions,
the control electronics are climate-controlled
at a stable level and with a high degree of
reliability.
This is supplemented by plant-wide remote
monitoring with Rittal CMC-TC (23) – this
ensures availability and also saves money.
Control of the cleaning and
priming line – high humidity
● Roof-mounted cooling units (1) and wall-
mounted cooling units (2) in master/slave
mode (3). The cooling output of several
cooling units in a bayed enclosure suite is
carefully coordinated to boost efficiency.
● Wall-mounted cooling units (2) may be
internally mounted, partially internally
mounted or externally mounted.
● Design variants: Standard, stainless steel
(4), NEMA 4x, all including RiNano
coating and condensate management.
Control of the spray-finishing and drying
line – paint dust and heat
● Perfection in cooling and design with the
modular climate control concept (7). The
enclosure door and climate components
are combined into one – no need for time-
consuming assembly.
● Comfort controller (8) – the ideal control
and safety electronics.
● Bayed EMC systems TS 8 (9) with a high
level of RF attenuation.
Control and inspection workstations
● Test workstation with mini-cooling units
(14).
● Individual configuration from IW modules
(15) (Industrial Workstation).
● Command Panel (Optipanel) (17) with
thermoelectric cooler (18) and individual
panel design.
Support arm system CP-XL.
Configured entirely to your requirements.
Control room for the entire production
process
● Server enclosures – based on TS 8 (21) –
in the control room, bayed with LCP
cooling (20).
● The central recooling system (19).
supplies cooling medium in a particularly
energy-efficient manner.
A
B
C
D
25Rittal System Climate Control
Systemexample
Rittal system climate control for various ambient conditions
System example
Control of the cleaning and priming line
Components Page
TopTherm-Plus cooling units, roof-mounted 74
TopTherm-Plus cooling units, wall-mounted 83
Master/slave mode 235
Cooling units in stainless steel 74
Bayed Top enclosure system TS 8 Cat. 32, p. 136
System accessories for TS 8 (base/plinth, walls,
doors, baying system, rail systems for interior
installation, cable entry and much more besides)
Cat. 32, p. 926
Cooling units also available in
stainless steel. TopTherm-Plus
cooling units (1, 2) ensure
constant temperatures for
control electronics, regardless
of variations in the ambient
conditions.
A
1
2
3
4
5
6
Control of the spray-finishing and drying line
Components Page
TopTherm-Plus climate control doors combined with
TS 8
70
Comfort controller 70
Bayed Top enclosure system TS 8 with EMC
shielding
Cat. 32, p. 329
Base/plinth (100/200 mm) for TS 8, compulsory
when using climate control doors (modular climate
control concept)
Cat. 32, p. 893
EMC system accessories Cat. 32, p. 572
Signal pillars Cat. 32, p. 1125
Recooling system to cool the robot controller 127
TopTherm-Plus climate control
doors combined with TS 8
enclosure system: Optimum
airflow, no assembly work (7)
B
7
8
9
10
11
12
13
Control and inspection workstations
Components Page
Mini-cooling unit, wall-mounted, on IW and
TopConsole
83
Industrial Workstation (IW) Cat. 32, p. 172
TopConsole system (pedestal, desk unit) with TFT
monitor in the Optipanel (CP-S support arm system)
Cat. 32, p. 156
Comfort-Panel command panel
on CP-XL support arm system
Cat. 32, p. 192
Thermoelectric cooler 97
Mini-cooling unit, wall-mounted
for efficient cooling of small
control and computer units (14)
C
14
15
16
17
18
Control room for the entire production process
Components Page
IT chiller with integral free cooling device 148
Server cooling with LCP 141
Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 774
System accessories for server racks Cat. 32, p. 890
CMC-TC, modular system for monitoring climate,
access and power supply
Cat. 32, p. 806
System accessories for the human/machine
interface (keyboard drawers, TFT monitors,
keyboards)
Cat. 32, p. 1115
Server cooling with LCP:
Horizontal cold air routing, no
thermal pressure on the room,
cost-effective, central recooling
(19)
D
19
20
21
22
23
24
27Rittal System Climate Control
Systemsolutions/finalassembly,handlingsystems
System climate control for final assembly and handling systems
Air versus heat
Even in apparently non-critical ambient conditions, for example when there is an
adequate supply of clean, cool air, it is still worthwhile to provide climate control.
Here too, the aim is to achieve maximum reliability with exceptional efficiency.
Reliability and efficiency with fan-and-filter units: Temperature-dependent speed
control plus temperature and airflow monitoring.
Reliability and efficiency with air/air heat exchangers: Thanks to separate air
circuits (external/internal), dust remains excluded, while a micro-controller
provides temperature-dependent control and monitoring of key parameters.
The benefit to you: Efficient reliability at all times.
Fan-and-filter units
Fan-and-filter units are ideal for
dissipating heat loads cost-effectively.
● The prerequisite is that the ambient
air must be relatively clean with a
temperature below the desired
enclosure internal temperature.
● The entire range of fan-and-filter
units is also available with EMC
shielding.
Air/air heat exchangers
The requirement for using air/air heat
exchangers is that the ambient temperature
must be below the required enclosure internal
temperature.
● Dust and contaminated ambient air is
unable to ingress the enclosure, thanks
to the two separate air circuits.
Machine, process and
enclosure cooling
● Operational reliability thanks
to liquid cooling e.g. of high-
frequency motor spindles and
other drive technology.
● Precise workpiece machining
thanks to precise, constant
temperatures of the cooling media.
● In this way, temperature peaks
inside enclosures – for example,
in summer – can be effectively
dissipated via air/water heat
exchangers.
28 Rittal System Climate Control
Systemexample
System example
Rittal system climate control for final assembly/handling systems
D
A
C
B
18
1 2
3
4
6
8
10
9
13
12
15
14
22
20
21
17
16
23
18
19
24
26
25
30
27
31
28
29
11
5
B 7
System climate control
for final assembly and handling
systems
Air versus heat – Even in non-critical
ambient conditions, it is still worthwhile
providing systematic climate control.
Here too, the aim is to achieve maximum
reliability with exceptional efficiency.
Control of production plant and handling
systems
Reliability and efficiency with air/air heat
exchangers (1) to cool the free-standing
enclosures ES 5000 (3).
● Thanks to separate air circuits (external/
internal), dust is unable to ingress.
● A high operating ratio and minimal
cleaning required.
● Monitoring of key parameters via a micro-
controller.
Robot: Effective liquid cooling of
controller and process
A central recooling system (7) “kills two
birds with one stone”:
● Effective cooling of the PC case (8)
via air/water heat exchangers (6).
● Precise cooling of machine spindles
and/or welding heads.
Machine operation,
quality assurance
Reliability and efficiency thanks to fan-and-
filter units (21) for Industrial Workstations IW
(20):
● Temperature-dependent speed control.
● Temperature and airflow monitoring.
Exceptionally energy-efficient cooling of
command panels with thermoelectric
coolers (17).
Control room
The aim is to minimise the level of noise
pollution in offices:
● This can be achieved with Office roof-
mounted fans (24) and speed-controlled
fan-and-filter units (27).
● Zero emissions of heat and noise, thanks
to a liquid cooling concept.
A
B
C
D
29Rittal System Climate Control
Systemexample
Rittal system climate control for final assembly/handling systems
System example
Control of production plant and handling systems
Components Page
Air/air heat exchangers, wall-mounted 62
Alternatively or additionally: Rittal TopTherm-Plus
cooling units, wall-mounted
83
Free-standing enclosure ES 5000 Cat. 32, p. 154
Viewing window Cat. 32, p. 944
System accessories (base/plinth, cable entry and
interior installation)
Cat. 32, p. 890
Platform concept:
Air/air heat exchangers, wall-
mounted, have the same
mounting interface as
TopTherm-Plus (1, 2)
A
1
2
3
4
5
Robot control and process cooling
Components Page
Air/water heat exchanger, wall-mounted
on the rear door of the PC case
104
Recooling system for central enclosure and process
cooling
116
PS enclosure system, based on TS 8 Cat. 32, p. 168
Base/plinth for PC case system Cat. 32, p. 892
Bus enclosure Cat. 32, p. 120
Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125
Rittal Comfort Panel command panel Cat. 32, p. 192
Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133
CP-L support arm system for Comfort Panel Cat. 32, p. 250
Thermoelectric cooler for Comfort Panel 97
Recooling system for
central enclosure and
process cooling (7)
B
6
7
8
9
10
11
12
13
14
15
Machine operation, quality assurance
Components Page
Rittal Comfort Panel command panel Cat. 32, p. 192
Thermoelectric cooler for Comfort Panel 97
Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133
CP-L support arm system for Comfort Panel Cat. 32, p. 250
Industrial workstation IW Cat. 32, p. 172
Fan-and-filter unit, speed-controlled 44
Optipanel with TFT monitor, CP-S support arm
system
Cat. 32, p. 204
Compact Panel, CP-S support arm system Cat. 32, p. 231
Thermoelectric cooler for
Comfort Panel (15, 17)
C
16
17
18
19
20
21
22
23
Control room
Components Page
Office roof-mounted fans for network enclosures 55
Network enclosures, based on TS 8 Cat. 32, p. 745
System accessories for IT (patch panels,
component shelves)
Cat. 32, p. 1013
EMC fan-and-filter units for console systems 48
TopConsole system Cat. 32, p. 156
System accessories for consoles (base/plinth,
interior installation)
Cat. 32, p. 890
System accessories for the human/machine
interface (keyboard drawers, TFT monitors,
keyboards)
Cat. 32, p. 1115
CMC-TC for monitoring
access, climate, power supply
Cat. 32, p. 806
Effective cooling, on request
with RF shielding:
EMC fan-and-filter unit (27)
D
24
25
26
27
28
29
30
31
30
31Rittal System Climate Control
Projectplanning
Project planning
Cooling with ambient air from page 35
Fan-and-filter units ............................................................................35
Air/air heat exchangers.....................................................................35
Cooling units from page 36
Condensation and dehumidification of the enclosure air .................36
Practical tips .....................................................................................36
Liquid cooling IE/IT from page 37
Air/water heat exchangers................................................................37
Notes on water quality ......................................................................37
Recooling systems/chillers ...............................................................38
Cooling water....................................................................................38
Form for designing recooling systems .............................................38
Enclosure heaters from page 39
Heating performance diagram..........................................................39
Basic principles for the use of climate control components from page 32
Guide to selecting suitable units.......................................................32
Heat dissipation ................................................................................33
Calculation basis for enclosure climate control................................34
Project planning software .................................................................34
Interactive performance diagrams ...................................................34
Project planning
Basic principles for the use of climate control components
32 Rittal System Climate Control
Projectplanning
Ambient conditions Enclosure interior
problems
Heat Heat loss
Dust Condensate
Cool
Heat conduction
Convection Radiation
There are three basic forms of heat transfer:
Thermal conduction:
Heat is transported by matter, without the matter itself being
moved. The energy is passed from particle to particle.
Convection:
Energy flows with the matter. The transport medium, e.g. a
liquid or gas, takes up energy in the form of heat and
dissipates energy as heat.
Radiation:
Heat is passed from one body to another in the form of
radiation energy, without a medium material.
The decisive factor for the type of heat dissipation to be used
in enclosures is whether they are open (air-permeable) or
closed (air-tight). Whereas in open enclosures, the heat is
dissipated by means of air circulation, in closed enclosures
the heat can only be dissipated via the enclosure wall.
Rittal cooling units provide the ideal system solution for
ensuring an optimum operating temperature inside an air-
tight enclosure, even at high external temperatures.
On the following pages, you will find a chrono-
logical guide to help you to easily find the most
suitable climate control solution.
Guide to selecting suitable units
As electronic components become ever smaller and are
more densely packed in enclosures and electronic cases,
systems are becoming increasingly sensitive to external
factors such as dust, oil, moisture and temperature.
Heat in particular is a deadly enemy of sensitive
microelectronics.
For example, a general rule of thumb for semi-conductors
is that an increase in the operating temperature of 10°C,
in relation to the maximum permissible operating
temperature, will shorten its service life by half.
In order to guarantee proper functioning of the electronics,
this heat needs to be dissipated.
Fast selection
Project planning
33Rittal System Climate Control
Projectplanning
Heat dissipation
Before you start, please consider your peripheral
conditions such as external temperature, internal
temperature and protection category.
In order to achieve targeted, effective cooling, it is important
to ensure correct calculation of the required climate control
components and possible thermal analysis using computer-
assisted flow models (CFD – Computational Fluid Dynamics).
Protection category
IP 54 important
Ti target > Tu max.
Cooling water cycle
available at the
installation site
No Integrated louvres, air inlet/outlet grille
Roof ventilation, fan-and-filter unit
Air/air heat exchanger
Yes
Air/water heat exchanger
Yes
Cooling unit
No
Ti target < or = Tu max.
Basic selection:
Ti = Required internal temperature of enclosure [°C]
Tu = Ambient temperature of enclosure [°C]
Recooling system
The following pages contain detailed calculation formulae for your chosen option.
Calculation of effective enclosure surface area
Of the variables required for calculation purposes, the effec-
tive enclosure surface area A requires special explanation.
The thermal output dissipated by the enclosure not only
depends on its actual surface area; the installation type of
the enclosure also plays a decisive role.
An enclosure which stands in a room unobstructed on all
sides may dissipate more heat than one sited against a wall
or in a niche. For this reason, there are precise specifications
on how to calculate the effective enclosure surface area
depending on the type of installation site. The formulae
for calculating A are specified in DIN 57 660, part 500 and
IEC 890 (see table below).
Enclosure installation type to IEC 890
Single enclosure, free-standing on all sides
Single enclosure for wall mounting
First or last enclosure in a suite, free-standing
First or last enclosure in a suite, for wall
mounting
Enclosure within a suite, free-standing
Enclosure within a suite, for wall mounting
Enclosure within a suite, for wall mounting,
covered roof surfaces
Installation type
to IEC 890
Formula for calculating A [m2]
A = 1.8 x H x (W + D) + 1.4 x W x D
A = 1.4 x W x (H + D) + 1.8 x D x H
A = 1.4 x D x (H + W) + 1.8 x W x H
A = 1.4 x H x (W + D) + 1.4 x W x D
A = 1.8 x W x H + 1.4 x W x D + D x H
A = 1.4 x W x (H + D) + D x H
A = 1.4 x W x H + 0.7 x W x D + D x H
A = Effective enclosure surface area
W = Enclosure width [m]
H = Enclosure height [m]
D = Enclosure depth [m]
Project planning
General information
34 Rittal System Climate Control
Projectplanning
Calculation basis for enclosure climate
control
In natural convection, heat loss is dissipated to the outside
via the enclosure panels. The prerequisite for this is that the
ambient temperature must be lower than the temperature
inside the enclosure. The maximum temperature increase
(ΔT)max. which may occur inside an enclosure compared with
the ambient air is calculated as follows:
Note:
If the heat loss inside the enclosure is not known, this
basic formula can be used to calculate actual heat loss,
by measuring the ambient temperature Tu and the en-
closure internal temperature Ti
QV = Heat loss installed in the enclosure [W]
QS = Heat emitted by the enclosure surface [W]
QS > 0: Radiation (Ti > Tu)
QS < 0: Irradiation (Ti < Tu)
QE = Required cooling output of an enclosure cooling unit [W]
QH = Required thermal output of an enclosure heater [W]
qw = Specific thermal output of a heat exchanger [W/K]
V = Required volumetric air flow of a fan-and-filter unit to
maintain the maximum permissible temperature difference
between the extracted air and the emitted air [m3/h]
ΔT = Ti – Tu = Max. admissible temperature difference [K]
A = Effective, heat loss-dissipating enclosure surface area to
IEC 890 [m2]
k = Heat transfer coefficient [W/m2K]
for sheet steel k = 5.5 W/m2K
.
.
.
.
.
.
.
(ΔT)max. =
QV
.
k ⅐ A
QS = A ⅐ k ⅐ ΔT (watts)
.
Project planning software
Rittal Therm
Make calculation even easier and faster by using our project
planning software Rittal Therm.
Model No. see page 195.
EPLAN Cabinet
Tool for the planning of enclosures and defining data for
climate control calculations.
Order information see page 195.
Interactive performance diagrams
Interactive performance diagrams may be found on the
Internet at www.rittal.com on the respective component data
sheets in the “Downloads” section, under the heading
“Characteristic curve”.
Enter your required interior temperature and the maximum
exterior temperature in the relevant boxes, then click on
“Calculate”. The heat loss that may be dissipated under
these conditions will be displayed.
Fan-and-filter units, air/air heat exchangers
Project planning
35Rittal System Climate Control
Projectplanning
Fan-and-filter units
The following applies when calculating the volumetric air flow:
Performance diagram SK 3325. . . .
f = 3.1 m3 ⅐ K/Wh at h = ( 0 to 100)
f = 3.2 m3 ⅐ K/Wh at h = (100 to 250)
f = 3.3 m3 ⅐ K/Wh at h = (250 to 500)
f = 3.4 m3 ⅐ K/Wh at h = (500 to 750)
f = 3.5 m3 ⅐ K/Wh at h = (750 to 1000)
f = Compensating factor
h = Height above sea level [m]
V
.
QV
.
30 50 70 90 300 500700
10 20 40 60 80100 200 400 600800
100
200
300
400
500
600
800
1000
1500
2000
3000
2500
Δ
T
40K
Δ
T
35K
Δ
T
30K
Δ
T
25K
Δ
T
20K
Δ
T
15K
Δ
T
10KΔ
T
5K
Selection diagram
The styling of the
vent louvres in Rittal
fan-and-filter units
guarantees exemplary
stability of the air vol-
umes in relation to
pressure loss. The
correct fan-and-filter
unit has been chosen
if the specified heat
loss is dissipated
whilst complying with
the desired maximum
enclosure internal
temperature.
V = Volumetric flow (m3/h)
QV = Heat loss (W)
.
.
100 200 300
20
40
60
80
100
120
140
0
0
ΔPst
V
.
50 Hz
60 Hz
V = Volumetric flow (m3/h)
ΔPst = Stat. pressure difference
(Pa)
.
V = f ⅐
QV
ΔT
.
.
Air/air heat exchangers
Calculate the specific thermal output
of the heat exchanger:
Selection diagram
Note:
For ambient temperatures that are lower than the desired
enclosure internal temperature, the use of air/air heat
exchangers may be appropriate, particularly in cases where
there are dust, oil and aggressive substances in the ambient
air which must not be allowed to ingress the enclosure under
any circumstances.
ΔT = Temperature difference (K)
QV = Heat loss (W)
qw = Specific thermal output (W/K)
A = Enclosure surface area to IEC 890 (m2)
k = Heat transfer coefficient (W/m2 K)
for sheet steel k = 5.5 W/m2 K
qw
ΔT
A
5 010152025
30
40
50
60
70
10 30 50 70
0
2
4
6
8
10
12
3000 2000 1000 0 20 40 60 80
QV
.
.
qw =
QV – (A ⅐ ΔT ⅐ k)
ΔT
.
Project planning
Cooling units
36 Rittal System Climate Control
Projectplanning
Cooling units
Condensation and dehumidification of enclosure air
when using cooling units
One unavoidable side-effect of using cooling units is the
dehumidification of the enclosure’s interior air. As it cools
down, part of the humidity contained in the air condenses
on the evaporator coil. This condensate must be reliably
discharged from the enclosure. The amount of condensate
occurring depends on relative humidity, the air temperature
inside the enclosure and on the evaporator coil, and the air
volume present in the enclosure. The Mollier h-x diagram
shows the water content of air depending on its temperature
and relative air humidity.
Mollier h-x diagram
for calculating the water content of air.
Pd
T
x
50
45
40
35
30
25
20
15
10
5
0
– 5
– 10
– 15
– 20
0
50 10 15 20 25
x2 x1
30 35 40
6030 45155 10 20 25 35 40 50 55
10%
20%
30%
40%
50%
60%
70%
80%
100%
➀
90%
Pd = Water vapour partial pressure (mbar)
T = Air temperature (°C)
x = Water content (g/kg dry air)
➀ = Relative humidity
Practical tips
In all situations where optimum operating temperatures
are required inside an enclosure, even at high external
temperatures, a Rittal enclosure cooling unit can provide
the right solution. It is even possible to cool the interior
temperature of the enclosure to well below the ambient
temperature.
The favourable aerodynamic arrangement of the air inlet and
outlet openings in the internal and external circuits ensures
optimum air circulation inside the enclosure. This sample
calculation will show you a quick, time-saving method for
calculating a cooling unit.
For example:
A cooling unit with a refrigeration output of 1500 watts
commences operation with a temperature setting of
Ti = 35°C.
The relative ambient air humidity is 70 %. If air at 35°C is
passed over the evaporator coil, the surface temperature
of the evaporator coil (evaporation temperature of the
refrigerant) is approximately 18°C.
At the boundary layer adhering to the surface of the
evaporator coil, water is deposited at the dew point. The
difference Δx = x1 – x2 indicates how much condensation is
incurred per kg of air with complete dehumidification. The
leak-tightness of the enclosure has a decisive effect on the
quantity of condensation.
Enclosure door closed:
Only the enclosure volume is dehumidified.
Poorly sealed cable designs, damaged door seals and the
attachment of display media to enclosure surfaces lead to
increased rates of leakage in the enclosure. Hence, with a
leakage rate of, say, 5 m3/h, a continuous condensate
volume of up to 80 ml/h may occur.
Summary:
Enclosure cooling units should only operate with the door
closed.
● Seal the enclosure on all sides.
● Use a door limit switch.
● Use TÜV-tested equipment.
● Only set the enclosure internal temperature as low as is
actually needed.
W = Water quantity in g
V = Volume of the enclosure in m3
ρ = Density of air kg/m3
Δx = Difference of water content in g/kg dry air
(from the Mollier h-x diagram)
V = width ⅐ height ⅐ depth = 0.6 m ⅐ 2 m ⅐ 0.5 m
V = 0.6 m3
W = V ⅐ ρ ⅐ Δx
= 0.6 m3 ⅐ 1.2 kg/m3 ⅐ 11 g/kg
W = 7.92 g 8 ml
Calculate your required cooling output.
The quantity of condensation is calculated from the following
equation:
QE = QV – k ⅐ A ⅐ ΔT
. .
W = V ⅐ ρ ⅐ Δx
Air/water heat exchangers
Project planning
37Rittal System Climate Control
Projectplanning
Air/water heat exchangers
Calculate your required cooling output:
e.g. performance diagram
Air/water heat exchanger 1000 W
TW
Ti
5
250
10 15 20 25 30
500
750
1000
1250
1500
1750
QK
.
45°C
35°C
25°C
VW = 400 l/h
VW = 200 l/h
VW = 100 l/h
.
.
.
Tw = Water inlet temperature (°C)
QK = Continuous useful cooling output (W)
Ti = Enclosure internal temperature (°C)
.
Notes on water quality
For safe operation of the equipment, it is essential to observe
the VGB guidelines on cooling water (VGB-R 455 P).
Cooling water must not contain any limescale deposits or
loose debris; in other words, it should have a low level of
hardness, particularly a low level of calcium hardness. For
recooling within the plant, the calcium hardness should not
be too high. On the other hand, however, the water should
not be so soft that it attacks the operating materials. When
recooling the cooling water, the salt content should not be
allowed to increase excessively due to the evaporation of
large quantities of water, since electrical conductivity
increases as the concentration of dissolved substances
rises, and the water thereby becomes more corrosive. For
this reason, not only is it always necessary to add a
corresponding quantity of fresh water, but also to remove
part of the enriched water.
Gypsiferous water is unsuitable for cooling purposes
because it has a tendency to form boiler scale, which is
particularly difficult to remove. Furthermore, cooling water
should be free from iron and manganese, because otherwise
deposits may occur which settle in the pipes and block them.
At best, organic substances should only be present in small
quantities, because otherwise sludge deposits and
microbiological contamination may occur.
Material of the water-carrying parts
Hydrological data CuAl V4A1)
pH value 7 – 8.5 6 – 9
Calcium hardness > 3 < 8° dH 1 – 12° dH
Free carbonic acid 8 – 15 mg/dm3 1 – 100 mg/dm3
Accompanying carbonic acid 8 – 15 mg/dm3 free
Aggressive carbonic acid 0 mg/dm3 0 – 400 mg/dm3
Sulphides free free
Oxygen < 10 mg/dm3 < 10 mg/dm3
Chloride ions < 50 mg/dm3 < 200 mg/dm3
Sulphate ions < 250 mg/dm3 < 500 mg/dm3
Nitrates and nitrites < 10 mg/dm3 < 100 mg/dm3
COD < 7 mg/dm3 < 40 mg/dm3
Ammonia < 5 mg/dm3 < 20 mg/dm3
Iron < 0.2 mg/dm3 free
Manganese < 0.2 mg/dm3 free
Conductivity < 2200 μS/cm < 4000 μS/cm
Residue on evaporation < 500 mg/dm3 < 200 mg/dm3
Potassium permanganate
consumption
< 25 mg/dm3 < 40 mg/dm3
Suspended matter
< 3 mg/dm3
> 3 < 15 mg/dm3 partial current
purification recommended
> 15 mg/dm3 continuous purification
recommended
1) The complete absence of corrosion under experimental conditions suggests
that solutions with a significantly higher salt content and greater corrosion
potential (such as seawater) may still be tolerated.
QE = QV – k ⅐ A ⅐ ΔT
. .
Project planning
Recooling systems/chillers
38 Rittal System Climate Control
Projectplanning
Recooling systems/chillers
Recooling systems may be used in all situations where a
high cooling load is required, e.g. in process and machine
cooling, in media cooling or when dissipating heat loss from
enclosures via air/water heat exchangers.
Our project engineers will be happy to help you design
a recooling system for your specific application area. An
overview of the planning data required for this purpose
can also be found on the Internet at www.rittal.com in the
section on system climate control/process and machine
cooling.
Cooling water
Preparation and maintenance of the water in recooling
systems
Depending on the type of installation to be cooled, certain
requirements are placed on the cooling water with respect
to purity. According to the level of contamination and the size
and design of the recooling systems, a suitable process is
used to prepare and/or maintain the water.
The most common types of contamination and most
frequently used techniques to eliminate them in industrial
cooling are:
Contamination of the water Procedure
Mechanical contamination
Filtering of water via
– Mesh filter
– Gravel filter
– Cartridge filter
– Precoated filter
Excessive hardness
Water softening via
ion exchange
Moderate content of mechanical
contaminants and hardeners
Addition of stabilisers and/or
dispersing agents to the water
Moderate content of chemical
contaminants
Addition of passifiers and/or
inhibitors to the water
Biological contaminants, slime
bacteria and algae
Addition of biocides to the water
Form for designing recooling systems
Simply tick the type of system, and select or enter the criteria
to suit your requirements. Please also include your name,
company and address. Once you have completed the form,
you can generate a PDF to print out or send via e-mail as an
enquiry. The form for the design of recooling systems may be
found on the Internet at:
www.rittal.com
–> Products
–> System climate control
–> Product portfolio
–> Process and machine cooling
–> Recooling systems
–> Form for designing recooling systems
Enclosure heaters
Project planning
39Rittal System Climate Control
Projectplanning
Enclosure heaters
The required thermal output is calculated from:
Heating performance diagram
QH = Thermal output (W)
A = Enclosure surface area to IEC 890 (m2)
ΔT = Temperature difference (K)
Based on:
Interior siting, static air, heat transfer coefficient k = 5.5 W/m2 K
For exterior siting (moving air):
Double the determined thermal output
A
ΔT
1
1.5
2
3
4
5
6
8
10
15 30 50 150 300 50010 20 40 60 80 100 200
20
30
2 5 7.5 10
15
QH
.
.
QH = A ⅐ ΔT ⅐ k
.
41Rittal System Climate Control
Coolingwithambientair
Fan-and-filter units from page 42
Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . 20/55 m3/h. . . . . . . . 44
Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 105/180 m3/h. . . . . . . . 45
Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . . .230 m3/h. . . . . . . . 46
Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 550/700 m3/h. . . . . . . . 47
Ⅲ Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 20 – 105 m3/h. . . . . . . . 48
Ⅲ Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . 180 – 700 m3/h. . . . . . . . 49
Rack-mounted fans from page 50
Ⅲ Ⅲ for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . 320/480 m3/h. . . . . . . . 52
Tangential fans from page 50
Ⅲ Ⅲ for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . . . . .320 m3/h. . . . . . . . 53
Fan systems from page 50
Ⅲ Ⅲ RTT roof-mounted fan and vent attachment. . . . . 400/800 m3/h. . . . . . . . 54
Ⅲ Ⅲ Roof-mounted fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . .360 m3/h. . . . . . . . 54
Ⅲ Roof-mounted fan for the office sector. . . . . . . . . . . 1500 m3/h. . . . . . . . 55
Ⅲ Enclosure internal fan . . . . . . . . . . . . . . . . . . . . . . . . .160 m3/h. . . . . . . . 55
Ⅲ Fan mounting plate. . . . . . . . . . . . . . . . . . . . . . . . . . . 180 m3/h. . . . . . . . 56
Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . 108/184 m3/h. . . . . . . . 56
Ⅲ Fan mounting plate DC . . . . . . . . . . . . . . . . . . . . . . . 990 m3/h. . . . . . . . 57
Ⅲ Fan roof, modular, two-piece . . . . . . . . . . . . . . . . . . . .180 m3/h. . . . . . . . 58
Ⅲ Fan unit, active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 m3/h. . . . . . . . 58
Ⅲ Ⅲ Door-mounted fan . . . . . . . . . . . . . . . . . . . . . . . . . . . .600 m3/h. . . . . . . . 59
Ⅲ Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . .300 m3/h. . . . . . . . 59
With EMC shielding
Interchangeable airflow
direction
Standardised installation
Passive ventilation
482.6 mm (19˝) installation
Cooling with ambient air
Air/air heat exchangers from page 60
Ⅲ Ⅲ Ⅲ Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12/62 W/K. . . . . . . . 62
Ⅲ Ⅲ Wall-mounted with controller . . . . . . . . . . . . . . . 17.5 to 90 W/K. . . . . . . . 63
Ⅲ Ⅲ Wall-mounted, railway-compatible version . . . . . .27 to 98 W/K. . . . . . . . 64
Ⅲ Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 W/K. . . . . . . . 65
Standardised installation
Suitable for command panels
Wall-mounted
Roof-mounted
24 V DC and 110 V DC
42 Rittal System Climate Control
Fan-and-filterunits
Fan-and-filter units
Fan-and-filter units are ideal for dissipating heat loads
cost-effectively. The prerequisite is that the ambient air
must be relatively clean with a temperature below the
desired enclosure internal temperature. The entire
range of fan-and-filter units is now also available with
EMC shielding and all required rated voltages.
43Rittal System Climate Control
Fan-and-filterunits
Aesthetics and
function
Typical of the Rittal fan-and-filter
unit design is the extremely low
build height. The super-slimline
vent grille guarantees optimum
air throughput with low noise
generation. Combined with the
technical features, Rittal fan-and-
filter units meet all application
requirements.
Benefits at a glance
● Air throughput from 20 m3/h to 700 m3/h
● Super-fast assembly
● IP 54 as standard
● Air flow direction may be reversed from
draw-in (default setting) to extracting
● All fans also available with EMC shielding
● Minimal installation depth
● Fan also bayable
Important
● The prescribed heat loss and the
maximum anticipated ambient
temperature define the required
volumetric flow
● Always use the fan-and-filter units
and outlet filters together
Tips and tricks
Applications see page 198
Selection criteria see page 199
Assembly see page 200
Application diversity and
functions
Particularly for applications in the food
industry, the hose-proof hood prevents the
ingress of damp. The protection category
of IP 56 is achieved in conjunction with filter
mats.
Not always full power!
At lower ambient temperatures, the air
throughput may be reduced. By adapting
the fan-and-filter speed to match the
temperature using a controller, noise
generation is reduced.
Also available with EMC shielding
All fan-and-filter units and outlet filters are
alternatively available with EMC shielding.
The required conductive connection is
achieved via a metallic coating on the fan-
and-filter unit housing and a special sealing
frame.
Fast assembly
Super-fast clip-on mounting
This guarantees fast, completely secure
attachment of the fan-and-filter unit. The
prerequisites for protection category
IP 54 are met as standard. Screws are not
required. Removal of the louvred grille, like-
wise without any screws, means that filter
mat changes can be achieved in next to no
time.
Draw-in or extract?
The air direction may be quickly reversed
from draw-in (default setting) to extracting.
Simply rotate the fan through 180°.
Fan-and-filter units
Air throughput 20/55 m3/h
44 Rittal System Climate Control
Fan-and-filterunits
H2
B2
T2
B1
T1
H1
B = Width
T = Depth
Supply includes:
Fan-and-filter units ready for
installation, including filter mats.
German registered design
no. M 93 04 846
Approvals,
see page 272.
Performance diagrams,
available on the Internet.
Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195
Model No. SK fan-and-filter unit 3321.107 3321.117 3321.027 3321.0471) 3322.107 3322.117 3322.027 3322.0471)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC)
Dimensions in mm
B1/H1 116.5 148.5
B2/H2 92 + 0.82) 1242)
T1 10 10.5
Max. installation depth mm T2 42 57
Air throughput, unimpeded air flow 20/25 m3/h 20 m3/h 55/66 m3/h 55 m3/h
Air throughput with outlet filter
including standard filter mat
1 x SK 3321.207: 15/18 m3/h 1 x SK 3322.207: 43/50 m3/h
Axial fan
Self-starting
shaded pole motor
DC motor
Self-starting
shaded pole motor
DC motor
Rated current max.
69 mA
58 mA
138 mA
115 mA
125 mA 90 mA
0.12 A
0.11 A
0.24 A
0.23 A
170 mA 90 mA
Power 12.5 W/10.3 W 3.0 W 4.1 W 19.0 W/18.0 W 4.0 W 4.4 W
Noise level 41/46 dB (A) 41 dB (A) 46/49 dB (A) 42 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
Protection category to EN 60 529
IP 54 standard
IP 56 when using a hose-proof hood
Model No. SK outlet filter 3321.207 3322.207
Accessories Packs of Page
Spare filter mats 5 3321.700 3322.700 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177
Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179
Hose-proof hood 1 3321.800 3322.800 193
1) Delivery times on request.
2) For metal thickness > 2.5 mm the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.
Air throughput 105/180 m3/h
Fan-and-filter units
45Rittal System Climate Control
Fan-and-filterunits
H2
B2
T2
B1
T1
H1
B = Width
T = Depth
Supply includes:
Fan-and-filter units ready for
installation, including filter mats.
German registered design
no. M 93 04 846
Approvals,
see page 272.
Performance diagrams,
available on the Internet.
Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195
Model No. SK fan-and-filter unit 3323.107 3323.117 3323.027 3323.0471) 3324.107 3324.117 3324.027 3324.0471)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC)
Dimensions in mm
B1/H1 204 255
B2/H2 1772) 2242)
T1 12.5 12.5
Max. installation depth mm T2 82.5 105
Air throughput, unimpeded air flow 105/120 m3/h 105 m3/h 180/160 m3/h 180 m3/h
Air throughput with outlet filter
including standard filter mat
1 x SK 3323.207: 71/82 m3/h
2 x SK 3323.207: 85/98 m3/h
1 x SK 3325.207: 78/90 m3/h
1 x SK 3325.207: 115/95 m3/h
2 x SK 3325.207: 165/140 m3/h
1 x SK 3326.207: 155/130 m3/h
Axial fan
Self-starting
shaded pole motor
DC motor
Self-starting
shaded pole motor
DC motor
Rated current max.
0.12 A
0.11 A
0.24 A
0.23 A
170 mA 90 mA
0.19 A
0.20 A
0.38 A
0.40 A
0.3 A 0.34 A
Power 19.0 W/18.0 W 4.0 W 4.3 W 30.0 W/35.0 W 7.2 W 14.0 W
Noise level 46/49 dB (A) 42 dB (A) 52/48 dB (A) 52 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
Protection category to EN 60 529
IP 54 standard
IP 55 when using an additional fine filter mat
IP 56 when using an additional fine filter mat and hose-proof hood
Model No. SK outlet filter 3323.207 3325.207
Accessories Packs of Page
Spare filter mats 5 3171.100 3172.100 191
Fine filter mats 5 3181.100 3182.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177
Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179
Hose-proof hood 1 3323.800 3324.800 193
1) Delivery times available on request.
2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.
Fan-and-filter units
Air throughput 230 m3/h
46 Rittal System Climate Control
Fan-and-filterunits
H2
B2
T2
B1
T1
H1
B = Width
T = Depth
Supply includes:
Fan-and-filter units ready for
installation, including filter mats.
German registered design
no. M 93 04 846
Approvals,
see page 272.
Performance diagrams,
available on the Internet.
Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195
Model No. SK fan-and-filter unit 3325.107 3325.117 3325.027 3325.0471)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC)
Dimensions in mm
B1/H1 255
B2/H2 2242)
T1 12.5
Max. installation depth mm T2 105
Air throughput, unimpeded air flow 230/265 m3/h 230 m3/h
Air throughput with outlet filter
including standard filter mat
1 x SK 3325.207: 170/205 m3/h
2 x SK 3325.207: 200/230 m3/h
1 x SK 3326.207: 190/215 m3/h
Axial fan Self-starting shaded pole motor DC motor
Rated current max.
0.28 A
0.24 A
0.53 A
0.49 A
0.59 A 0.31 A
Power 41.0 W/38.0 W 14.0 W 15.0 W
Noise level 54/56 dB (A) 54 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
Protection category
to EN 60 529
IP 54 standard
IP 55 when using an additional fine filter mat
IP 56 when using an additional fine filter mat and hose-proof hood
Model No. SK outlet filter 3325.207
Accessories Packs of Page
Spare filter mats 5 3172.100 191
Fine filter mats 5 3182.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.024 – 177
Speed control 1 3120.000 3120.115 – – 179
Hose-proof hood 1 3324.800 193
1) Delivery times available on request.
2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.
Air throughput 550/700 m3/h
Fan-and-filter units
47Rittal System Climate Control
Fan-and-filterunits
H2
B2
T2
B1
T1
H1
B = Width
T = Depth
Supply includes:
Fan-and-filter units ready for
installation, including filter mats.
German registered design
no. M 93 04 846
Approvals,
see page 272.
Performance diagrams,
available on the Internet.
Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195
Model No. SK fan-and-filter unit 3326.107 3326.117 3327.107 3327.117 3327.147
Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 400/460, 3~, 50/60
Dimensions in mm
B1/H1 323
B2/H2 2921)
T1 12.5
Max. installation depth mm T2 129 145
Air throughput, unimpeded air flow 550/600 m3/h 700/720 m3/h
Air throughput with outlet filter
including standard filter mat
1 x SK 3326.207: 360/390 m3/h
2 x SK 3326.207: 440/495 m3/h
1 x SK 3326.207: 525/575 m3/h
Axial fan Capacitor motor Rotary current motor
Rated current max.
0.29 A
0.35 A
0.58 A
0.70 A
0.65 A
0.95 A
1.5 A
2.0 A
0.27 A
0.37 A
Power 64.0 W/80.0 W 115.0 W/212.0 W 167.0 W/230.0 W 146.0 W/220.0 W
Noise level 59/61 dB (A) 75/76 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70352)
Protection category
to EN 60 529
IP 54 standard
IP 55 when using an additional fine filter mat
IP 56 when using an additional fine filter mat and hose-proof hood
Model No. SK outlet filter 3326.207
Accessories Packs of Page
Spare filter mats 5 3173.100 3327.700 191
Fine filter mats 5 3183.100 191
Thermostat 1 3110.000 – 178
Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 – 177
Speed control 1 3120.000 3120.115 3120.000 – – 179
Hose-proof hood 1 3326.800 193
1) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
2) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.
Fan-and-filter units – EMC
Air throughput 20 – 105 m3/h
48 Rittal System Climate Control
Fan-and-filterunits–EMC
H2
B2
T2
B1
T1
H1
B = Width
T = Depth
Supply includes:
Complete fan-and-filter units
ready for installation,
including drilling template, filter
mat and assembly parts.
Approvals,
see page 273.
Performance diagrams,
available on the Internet.
Accessories Page 171 Configuration software Page 195
Model No. SK fan-and-filter unit 3321.607 3321.6171) 3322.607 3322.6171) 3323.607 3323.6171)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60
Dimensions in mm
B1/H1 116.5 148.5 204
B2/H2 92 + 0.82) 1242) 1772)
T1 10 10.5 12.5
Max. installation depth mm T2 42 57 82.5
Air throughput, unimpeded air flow 20/25 m3/h 55/66 m3/h 105/120 m3/h
Air throughput with outlet filter
including standard filter mat
1 x 3321.267: 15/18 m3/h
1 x 3322.267: 43/50 m3/h
2 x 3322.267: 48/55 m3/h
1 x 3323.267: 48/55 m3/h
1 x 3323.267: 71/82 m3/h
2 x 3323.267: 85/98 m3/h
1 x 3325.267: 78/90 m3/h
Axial fan Self-starting shaded pole motor
Rated current max.
69 mA/
58 mA
138 mA/
115 mA
0.12 A/
0.11 A
0.24 A/
0.23 A
0.12 A/
0.11 A
0.24 A/
0.23 A
Power 12.5 W/10.3 W 19.0 W/18.0 W
Noise level 41/46 dB (A) 46/49 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
Protection category to EN 60 529 IP 54 standard
Model No. SK outlet filter – EMC 3321.267 3322.267 3323.267
Accessories Packs of Page
Spare filter mats 5 3321.700 3322.700 3171.100 191
Fine filter mats 5 – 3181.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177
Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179
Hose-proof hood 1 3321.800 3322.800 3323.800 193
1) Delivery times available on request.
2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.
Air throughput 180 – 700 m3/h
Fan-and-filter units – EMC
49Rittal System Climate Control
Fan-and-filterunits–EMC
H2
B2
T2
B1
T1
H1
B = Width
T = Depth
Supply includes:
Complete fan-and-filter units
ready for installation,
including drilling template, filter
mat and assembly parts.
Approvals,
see page 273.
Performance diagrams,
available on the Internet.
Accessories Page 171 Configuration software Page 195
Model No. SK fan-and-filter unit 3324.607 3324.6171) 3325.607 3325.6171) 3326.607 3326.6171) 3327.607 3327.6171)
Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60
Dimensions in mm
B1/H1 255 323
B2/H2 2242) 2922)
T1 12.5 12.5
Max. installation depth mm T2 105 129 145
Air throughput, unimpeded air flow 180/160 m3/h 230/265 m3/h 550/600 m3/h 700/720 m3/h
Air throughput with outlet filter
including standard filter mat
1 x 3325.267:
115/95 m3/h
2 x 3325.267:
165/140 m3/h
1 x 3326.267:
155/130 m3/h
1 x 3325.267:
170/205 m3/h
2 x 3325.267:
200/230 m3/h
1 x 3326.267:
190/215 m3/h
1 x 3325.267:
170/205 m3/h
2 x 3325.267:
200/230 m3/h
1 x 3326.267:
360/390 m3/h
1 x 3326.267:
525/575 m3/h
Axial fan Self-starting shaded pole motor Capacitor motor
Rated current max.
0.19 A/
0.20 A
0.38 A/
0.40 A
0.28 A/
0.24 A
0.53 A/
0.49 A
0.29 A/
0.35 A
0.58 A/
0.70 A
0.65 A/
0.95 A
1.50 A/
2.00 A
Power
30.0 W/
35.0 W
41.0 W/
38.0 W
64.0 W/
80.0 W
155.0 W/
212.0 W
167.0 W/
230.0 W
Noise level 52/48 dB (A) 54/56 dB (A) 59/61 dB (A) 75/76 dB (A)
Temperature range –10°C to +55°C
Colour RAL 70353)
Protection category to EN 60 529 IP 54 standard
Model No. SK outlet filter – EMC 3325.267 3326.267
Accessories Packs of Page
Spare filter mats 5 3172.100 3173.100 3327.700 191
Fine filter mats 5 3182.100 3183.100 191
Thermostat 1 3110.000 178
Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177
Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179
Hose-proof hood 1 3324.800 3326.800 193
1) Delivery times available on request.
2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger.
3) RAL 7032 on request.
Special voltages available on request. We reserve the right to make technical modifications.
50 Rittal System Climate Control
Rack-mounted/tangentialfans,fansystems
Rack-mounted/tangential fans,
fan systems
All rack-mounted climate control components are fitted
directly onto the 482.6 mm (19˝) mounting level for
subracks. Positioning directly beneath the electronic
components ensures effective cooling, and prevents
the formation of hot-spots.
Ready-to-use, wired modules equipped with fans for
numerous Rittal enclosure system platforms offer
effective air throughput and minimal assembly work.
Fan roofs, door-mounted fans for server enclosures,
internal fan mounting panels and enclosure internal
fans are all available.
51Rittal System Climate Control
Rack-mounted/tangentialfans,fansystems
Benefits at a glance
Rack-mounted/tangential fans
● Rapid installation on 482.6 mm (19˝)
mounting levels
● Direct, effective dissipation of heat loss,
thanks to positioning beneath the
assemblies
● No externally mounted equipment to
disrupt the aesthetic appearance of
the enclosure
Fan systems
● Fast assembly
● Targeted air routing to avoid hot-spots
● Perfect system integration
Tips and tricks
Applications see page 201
Rack-mounted fan
module
The rack-mounted fan slides into
the guide frame like a drawer.
Connectors on the rear ensure
immediate contact. Installation
options for the guide frame:
Directly in the subrack, via
two mounting brackets on the
482.6 mm (19˝) mounting angles.
Ideal for avoiding hot-spots in fully
populated enclosures.
Tangential fans
320 m3/h air throughput, 2 U
The high air throughput means that Rittal
tangential fans are capable of dissipating
large heat losses from the enclosure. The
minimal noise generation of 52 dB creates a
pleasant working environment. Front outlet
grille 2 U for hot air outlet to the outside in
the upper section of the enclosure.
For the office sector:
Roof-mounted fan
Low noise generation and high performance
for sensitive office areas.
Unit consisting of TS roof plate and fan.
Rack-mounted fans
for 482.6 mm (19˝), air throughput 320/480 m3/h
52 Rittal System Climate Control
Rack-mountedfans
426
482.6 (19˝)
206214
55
432
120
1HE
482.6 (19˝)
180200
73
410
100
1HE
1 2
Rack-mounted fan/Vario rack-
mounted fan supply includes:
Wired unit ready for connection,
including terminal strip and
assembly parts.
Guide frame supply includes:
Guide frame including connec-
tor and fitted connection cable
(3 m), bracket for optional
attachment to the 482.6 mm
(19˝) system, assembly parts.
Also required:
Remember to order the
appropriate guide frame for your
chosen application.
Approvals,
see page 273.
Detailed drawing,
see page 240.
Performance diagrams,
available on the Internet.
Accessories Page 171 Configuration software Page 195
Rack-mounted fans Vario rack-mounted fans
Model No. SK Model No. SK
2 fans
Distance between axes 85 mm
3340.0241) 3340.1151) 3340.230 – – 3350.0241) 3350.1151) 3350.2301) –
3 fans
Distance between axes 85 mm
3341.0241) 3341.115 3341.230 – 9769.0021)2) 3351.0241) 3351.1151) 3351.230 –
3 fans
Distance between axes 105 mm
3342.024 3342.1151) 3342.230 3342.5002)3) – 3352.0241) 3352.1151) 3352.230 3352.5003)
Rated operating voltage V 24 V (DC) 115 V (AC) 230 V (AC)
24 V (DC)
115 – 230 V
(AC)
36 V (DC)
up to
72 V (DC)
24 V (DC) 115 V (AC) 230 V (AC)
24 V (DC)
115 – 230 V
(AC)
Model No. SK
matching guide frame
– – – – – 3356.1001) 3355.100 3355.100 3357.100
Accessories Page
Temperature indicator
230 V (AC)
714 3114.100 3114.115 3114.100 3114.024 – 3114.100 3114.115 3114.100 3114.024
Thermostat 715 3110.000
Speed control 716 3120.000 3120.115 3120.000 – – 3120.000 3120.115 3120.000 –
1 2
Technical specifications
Model No. SK/CS
3340.230
3350.230
3340.115
3350.115
3340.024
3350.024
3341.230
3351.230
3342.230
3352.230
3341.115
3351.115
3342.115
3352.115
3341.024
3351.024
3342.024
3352.024
3342.5002)
3352.5002) 9769.002
Rated operating voltage
V, Hz
AC 230 V
50/60 Hz
AC 115 V
50/60 Hz
DC 24 V
–
AC 230 V
50/60 Hz
AC 115 V
50/60 Hz
DC 24 V
–
DC 24 V
AC 115 – 230 V
50/60 Hz
36 V (DC)
up to
72 V (DC)
Rated current max.
0.24 A/
0.22 A
0.46 A/
0.46 A
0.49 A
0.36 A/
0.33 A
0.69 A/
0.69 A
0.74 A 0.85 A 0.28 A
Pre-fuse T 6.0 A 6.0 A
Number of fans 2 3 3
Air throughput, unimpeded air flow 320 m3/h 480 m3/h 250 m3/h
Temperature range –10°C to +55°C
–33°C to
+55°C
Noise level 51 dB (A) 52 dB (A) 51 dB (A) 51 dB (A) 52 dB (A) 51 dB (A) 52 dB (A)
1) Delivery times available on request.
2) Rack-mounted fan for metric mounting angles available on request.
3) Version with monitoring
for 482.6 mm (19˝), air throughput 320 m3/h
Tangential fans
53Rittal System Climate Control
Tangentialfans
88
482.6 (19˝)
163
380
17
Supply includes:
Fully assembled and wired unit,
ready for connection, including
filter mat.
Approvals,
see page 274.
Detailed drawing,
see page 240.
Performance diagrams,
available on the Internet.
Accessories Page 171 Configuration software Page 195
Model No. SK 3145.000 3144.000
Rated operating voltage V/Hz 115, 50/60 230, 50/60
Dimensions in mm
W
H
D
482.6 (19˝)
88 (2 U)
158
Air throughput, unimpeded air flow 320 m3/h
Rated current max. 0.32 A 0.16 A
Power 37 W
Noise level 52 dB (A)
Speed 2245 rpm–1
Temperature range –10°C to +55°C
Maximum static pressure difference 65 – 70 Pa
Accessories Packs of Page
Temperature indicator 1 3114.115 3114.100 177
Thermostat 1 3110.000 178
Filter mats 5 3177.000 189
Front outlet grille 2 U 1 3176.000 193
Roof vent 1 3148.007 54
Speed control 1 3120.115 3120.000 179
Special voltages available on request. We reserve the right to make technical modifications.
Fan systems
54 Rittal System Climate Control
Fansystems
RTT roof-mounted fan
and vent attachment
for TS
The active roof-mounted fan and the passive vent
attachment (TS 8801.380) integrate perfectly into
the system-wide mounting concept of the Rittal
TopTherm platform. They fit precisely onto the cut-
outs of the small and medium performance cate-
gory of TopTherm roof-mounted cooling units.
Of course, they may also be mounted on any suffi-
ciently large roof surface.
TS roof plates with prepared mounting cut-outs
are additionally available.
Roof-mounted fan supply includes:
Unit ready to connect with built-in radial fan,
sealing material and assembly parts.
Vent attachment:
see page 182.
Protection category:
IP 43 to EN 60 529
Detailed drawing,
see page 240.
T
B
290
500
370
550
125
Model No. SK 3149.410 3149.420 3149.440 3149.810 3149.820 3149.840 8801.380 Page
Rated operating voltage V/Hz 115, 50/60 230, 50/60
400, 3~, 50/60
460, 3~, 60
115, 50/60 230, 50/60
400, 3~, 50/60
460, 3~, 60
Roof vent
Air throughput, unimpeded air flow 400 m3/h 800 m3/h
Without
motor
Required mounting cut-out W x D mm 475 x 260 490 x 390
Power consumption of fan 120 W/170 W 95 W/140 W 170 W/225 W 180 W/310 W
Rated current of fan 1.1/1.6 A 0.55/0.88 A 0.35/0.35 A 1.5/2.2 A 0.75/1.1 A 0.35/0.55 A
Temperature range –10°C to +55°C
Noise level 68/69 dB (A) 69/70 dB (A)
Weight 10 kg 11 kg 6 kg
Colour shade RAL 7035
Accessories
Roof plate 600 x 600 mm for TS 8 with cut-out 8801.300 8801.310 181
Roof plate 600 x 800 mm for TS 8 with cut-out 8801.320 8801.330 181
Roof plate 1200 x 600 mm for TS 8 with cut-out – 8801.350 181
Temperature indicator 3114.115 3114.100 – 3114.115 3114.100 – – 177
Speed control 3120.115 3120.100 – 3120.115 3120.100 – – 179
B = Width
T = Depth
Roof-mounted fan
● The roof-mounted fan is easily installed using
6 screws. The sealing tape supplied can be
used to seal it against the enclosure.
● The attachment screws are invisible from the
outside.
● The roof-mounted fan casing has a large air
outlet surface and labyrinth air ducting.
Protection category:
IP 43 to EN 60 529. By additionally installing the
filter holder with filter mat SK 3175.000, with roof
vent SK 3148.007 a protection category of IP 44 is
achieved.
Fully wired unit ready for connection with built-in
radial fan, sealing material and assembly parts,
connection cable (3 m), drilling template.
Accessories:
Filter holder,
see page 194.
Detailed drawing,
see page 240.
50
265
345
340 420
Model No. SK 3149.007 3169.007 3148.007
Rated operating voltage V/Hz 230, 50/60 115, 50/60 Without fan motor
Air throughput 360 m3/h
Rated current max. 0.2 A 0.55 A
Power consumption 42 W 65 W
Temperature range –10°C to +60°C
Noise level 53 dB (A)
Weight 7.8 kg
Colour1) RAL 7035, textured enamel
1) To order the version in RAL 7032, please add extension .000 to the Model No.
Special voltages available on request. We reserve the right to make technical modifications.
Fan systems
55Rittal System Climate Control
Fansystems
Roof-mounted fan
for TS/FR(i) for the office sector
This new roof ventilation concept offers a wealth
of performance, assembly and cost benefits
associated with the use of integrated ventilation
systems. This roof-mounted fan may be ordered
with and without a roof plate. Another outstanding
feature is the enormous volumetric flow in propor-
tion to exceptionally low noise levels, making it
ideal for use in sensitive office areas.
Technical specifications:
● Fitted onto a roof plate based on TS.
● Easy assembly; mounting cut-outs have been
provided.
● Radial fan.
Supply includes:
Fully wired ready for connection,
including assembly parts.
T
H
B
511 511
410
450450
410
H
13.5
T B
20
2424
225
205
410
450
Ø
6.5(8x)
Model No. SK 3164.610 3164.620 3164.810 3164.820 3164.115 3164.230 Page
Rated operating voltage V/Hz 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60
Air throughput (unimpeded air flow) 1500 m3/h1)
Version With roof plate without roof plate
Dimensions in mm
W
H
D
800
240
800
800
240
900
511
227
511
Power consumption 68 W/81 W
Rated current 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 A
Radial fan –
Noise level 40 dB (A)
Temperature range +20°C to +55°C
Colour RAL 7035
Accessories
Temperature indicator in 1 U patch panel 7109.035 177
Temperature indicator 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 177
Thermostat 3110.000 178
1) 800 m3/h at 40 Pa counterpressure using two integrated louvres, type DK 7825.801, in the enclosure base/plinth.
Special voltages available on request. We reserve the right to make technical modifications.
Mounting cut-out
only required for fans wtihout roof plate
B = Width
T = Depth
Enclosure internal fan
for TS
To prevent hot-spots and support the air routing
of active enclosure climate control components.
Adjustable in two axes. Attached to the TS 8
frame section. Several fans may be cascaded
using the quick-release clamping strip.
Supply includes:
Fully wired unit ready for connection with radial
fan and lockable swivel device, as well as
assembly parts.
213.5
100
120
Ø6(2x)
Air through-
put (unim-
peded air
flow)
Power
consump-
tion
W
Rated
current
A
Rated
voltage
V, Hz
Model No.
SK
160 m3/h 19.0/18.0 0.12/0.11 230, 50/60 3108.100
160 m3/h 19.0/18.0 0.24/0.23 115, 50/60 3108.115
160 m3/h 3.5 0.15 24 V (DC) 3108.024
Fan systems
56 Rittal System Climate Control
Fansystems
Fan mounting plate
for TS
The fan mounting plate may be retro-fitted in all
TS 8 network enclosures from above. The plate
is mounted at the front of the enclosure, whilst the
rear section is left free for cable entry. A rubber
cable clamp strip is supplied loose for optional
sealing at the rear.
The following combinations are also possible:
● Solid roof plate raised with 20 or 50 mm roof
spacers.
● Roof plate for cable entry raised with 20 or
50 mm roof spacers.
● Vented roof plate for cable entry.
In conjunction with the large swing frame, usage
is only possible from an enclosure depth of
800 mm, in conjunction with a roof plate for cable
entry from 900 mm.
Note:
Not suitable for crane transportation. Not suitable
for combination with 482.6 mm (19˝) mounting
frame.
The air throughput can be increased with the fan
expansion kit DK 7980.000.
Technical specifications for one fan:
Rated operating voltage: 230 V
Power consumption: 15/14 W at 50/60 Hz
Air throughput (unimpeded air flow):
160/180 m3/h, 50/60 Hz
Temperature range: –10°C to +55°C
Technical specifications of thermostat:
Rated operating voltage: 250 V
Temperature range: +5°C to +55°C
Colour:
RAL 7035
Supply includes:
2 fans, 2/4 cut-outs to extend to 4/6 fans,
thermostat, rubber cable clamp strip.
Thermostat and fan fully wired to connection
cable (2.5 m).
Accessories:
Fan expansion kit,
see page 56.
Rubber cable clamp strip SZ 2573.000 for sealing
at the sides and targeted air routing when bayed,
see Cat. 32 page 1047.
385/585
525/725
40
For enclosures
Number
of fans
Max.
number of
fans
Model No.
DKWidth
mm
Depth
mm
600 600 2 4 7966.035
600
800
900
1000
1200
2 6 7968.035
800 600 2 6 7986.035
800
800
900
1000
1200
2 6 7988.035
Fan expansion kit
For retro-fitting various fan units or to supplement
the fan mounting plate and modular fan roof.
Technical specifications DK 7980.000:
Rated operating voltage: 230 V~
Power consumption: 15/14 W at 50/60 Hz
Air throughput (unimpeded air flow):
160/180 m3/h, 50/60 Hz
Noise level (unimpeded air flow): 37 dB (A)
Temperature range: –10°C to +55°C
Technical specifications DK 7980.100:
Rated operating voltage: 230 V~
Power consumption: 14/12 W at 50/60 Hz
Air throughput (unimpeded air flow):
108/120 m3/h, 50/60 Hz
Noise level (unimpeded air flow): 34 dB (A)
Temperature range: –20°C to +70°C
Technical specifications DK 7980.148:
Rated operating voltage: 48 V (DC)
Power consumption: 7.7 W
Air throughput (unimpeded air flow): 184 m3/h
Noise level (unimpeded air flow): 43 dB (A)
Temperature range: –20°C to +70°C
Supply includes:
Fan, including assembly parts and connection
cable (0.61 m).
Dimensions
W x H x D mm
Packs of Model No. DK
119 x 119 x 38 1 set 7980.000
119 x 119 x 25 1 set 7980.100
119 x 119 x 25 1 set 7980.148
Fan systems
57Rittal System Climate Control
Fansystems
Cover plates for fan panels
for FlatBox
To cover unused fan panels when using fans in
the FlatBox.
Material:
Sheet steel
Surface finish:
Powder coated in RAL 7035
Supply includes:
Assembly parts.
Packs of Model No. DK
6 7507.760
Fan mounting plate DC
for TS
Super-low noise thanks to FCS speed control,
fully fitted
Suitable for TS 8 enclosures with a raised roof
(> 20 mm) or TS 8 roof plate, vented. The fan
mounting plate may be used as an alternative to
fan mounting plate 7988.035. It is installed from
above. Cable entry is prepared in the rear section
of the plate.
Not suitable for combination with 482.6 mm (19˝)
mounting frame.
Advantages of the DC fan mounting plate with
FCS technology:
● Super-low noise thanks to speed control.
● All fans are monitored for failure.
● High air throughput thanks to DC technology
(unimpeded airflow 6 x 175 m3/h = 990 m3/h).
● EMC compatibility.
● Temperature monitoring and control.
● High level of safety (low safety voltage with
24 V DC power supply).
● Visual and acoustic alarm messages, plus relay
alarm output.
● Freely selectable installation location for the
FCS control unit (included with the supply of the
fan mounting plate, in 482.6 mm (19˝) with
7320.440 or on the frame with 7320.450).
● Suitable for international use, thanks to wide-
range power supply 100 – 240 V AC and socket
to IEC 320.
● Pre-configured.
● Network-compatible via CMC-TC processing
unit II 7320.100 (all relevant data such as
temperature etc. are displayed in the web
browser, or alarms are sent in the form of an
SNMP trap).
Technical specifications:
Power pack rated voltage:
100 – 240 V AC, 50/60 Hz
Power supply rated current: max. 1.5 A
Power supply secondary range: 24 V DC, 3 A
Temperature range: +5°C to +40°C
Total air throughput (unimpeded air flow):
6 x 175 m3/h = 990 m3/h
Technical specifications for one fan:
Rated voltage: 24 V DC
Rated current: max. 0.3 A
Air throughput (unimpeded air flow): 175 m3/h
Speed: 2650 rpm
Noise level: up to 45 dB (A)
at maximum speed activation
Also required:
Connection cable 230/115 V.
Example D version, Model No. 7200.210,
see Cat. 32, page 818.
Accessories:
1 U mounting unit, Model No. 7320.440,
see Cat. 32, page 821.
Mounting module, Model No. 7320.450,
see Cat. 32, page 821.
For
enclosures
width
mm
For
enclosures
depth
mm
Number of
DC fans
Model No.
DK
800
800
900
1000
6 7858.488
Note:
For more information on the FCS system,
see Cat. 32, page 813.
Fan systems
58 Rittal System Climate Control
Fansystems
Fan roof, modular, two-piece
for TS, FR(i)
The modular roof plate consists of individual com-
ponents and can be configured for the ventilation
of the enclosures in various ways.
The modules consist of:
Roof plate, two-piece with cut-out
For fan mounting and cable entry at the rear via a
sliding angular bracket with rubber cable clamp
strip. Replacing the existing roof plate. The two-
piece design allows convenient retrofitting of
cables at any time.
Cover plate
To cover the cut-out, optionally solid or vented
options. The top-mounted cover plate may be
raised for extra air throughput using the supplied
spacers.
Fan insert
For active ventilation:
A fully pre-wired fan tray including 2.5 m connec-
tion cable, with two fan motors and additional cut-
outs. The air throughput may be increased with a
fan expansion kit.
Material:
Sheet steel, spray finished
Colour:
RAL 7035
Technical specifications for one fan:
Rated operating voltage: 230 V
Power consumption: 15/14 W at 50/60 Hz
Air throughput (unimpeded air flow):
160/180 m3/h at 50/60 Hz
Temperature range: –10°C to +55°C
Detailed drawing,
see page 241.
Accessories:
Fan expansion kit DK 7980.000,
see page 56.
Thermostat SK 3110.000,
see page 178.
Speed control SK 3120.000,
see page 179.
1
2
1 2
3 4
5
For enclosures
Model No. DK
Fan insertRoof plate
FR(i)
Roof plate
TS
Cover plate
Width
mm
Depth
mm With
cut-out
With
cut-out Solid Vented Fan insert
Fans
pre-wired
Maximum
no. of fans
600 600 7856.3661) 7826.366 2102.1801) 2102.400 2102.320 2 2
600 800 7856.3681) 7826.368 2102.1901) 2102.410 2102.490 2 6
600 900 – 7826.369 2102.1901) 2102.410 2102.490 2 6
600 1000 7856.3601) 7826.360 2102.1901) 2102.410 2102.490 2 6
600 1200 7856.3621) 7826.362 2102.1901) 2102.410 2102.490 2 6
800 600 – 7826.486 7885.100 7885.200 7885.000 2 3
800 800 7856.3881) 7826.488 7886.100 7886.200 7886.000 2 8
800 900 – 7826.489 7886.100 7886.200 7886.000 2 8
800 1000 7856.3801) 7826.480 7886.100 7886.200 7886.000 2 8
800 1200 – 7826.382 7886.100 7886.200 7886.000 2 8
1) Delivery times available on request.
Design panel FR(i) already included with the supply of the standard roof plate.
1 2 4 5 3
Fan unit, active
for TE
For active ventilation of the TE 7000. The fan
unit is installed in the prepunched cut-out. An
additional fan may optionally be integrated.
Supply includes:
Fan unit including assembly parts, 2 fans,
1 thermostat and open connection cable.
Technical specifications for one fan:
Fan extension kit, 7980.000,
see page 56.
Technical specifications of thermostat:
Rated operating voltage: 250 V
Temperature range: +5°C to +55°C
Note:
Connection via distributor box or country-specific
connector.
Accessories:
Fan expansion kit,
see page 56.
For enclosures
W x D
mm
Number of
pre-wired
fans
Possible
number of
fans
Model No.
TE
All
dimensions
2 3 7000.670
Active kit
for TE
consisting of fan unit including thermostat, com-
plete, wired ready for connection, socket strip
(DK 7000.630) for up to 8 earthing pin plugs,
version D and connection cable (DK 7200.210).
Packs of Model No. DK
1 set 7000.680
Fan systems
59Rittal System Climate Control
Fansystems
Door-mounted fan
for server enclosures TS, TE
Specifically for installing in perforated doors.
The growing packaging density in data
communications and network enclosures make
active, direct ventilation of the enclosure indispen-
sable. The door-mounted fan, which is attached to
the rear or front door, supports horizontal air rout-
ing via the servers and therefore facilitates faster
heat dissipation from active components.
Technical specifications:
● Standard assembly with two fans.
● Air throughput, unimpeded air flow 600 m3/h.
● By adding two fan extension kits, the air
throughput is increased to 1200 m3/h.
● The direction of air flow is easily reversed by
rotating the fan.
● Several units may be positioned in a cascade
arrangement.
● Simple mounting on the tubular door frame.
Supply includes:
Wired ready for connection with 2.5 m connection
cable, including assembly parts.
Accessories:
Fan expansion kit,
see page 59.
Note:
Only for mounting on the tubular door frame!
Door configuration for installation in 2 and 4-door
ISP racks available on request.
B
T
H
552
27
230 (350)
Ø 4.5
475 (675)
493 (693)
606
9
59.5
5
Model No. SK 3165.6241) 3165.6481) 3165.6151) 3165.630 3165.8241) 3165.8481) 3165.8151) 3165.830 Page
Rated operating voltage V/Hz 24 (DC) 48 (DC) 115, 50/60 230, 50/60 24 (DC) 48 (DC) 115, 50/60 230, 50/60
Air throughput (unimpeded air flow) 600 m3/h
Power consumption for two fans 40 W 48 W 70 W/64 W 70 W/70 W 40 W 48 W 70 W/64 W 70 W/70 W
Rated current of fan 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A
Dimensions in mm
W
H
D
493
606
64.5
693
606
64.5
For doors with width (mm) 600 800
Noise level 55 dB (A)
Temperature range +20°C to +55°C
Colour RAL 7035
Accessories
Temperature indicator 3114.024 – 3114.115 3114.100 3114.024 – 3114.115 3114.100 177
Thermostat 3110.000 178
1) Delivery times on request.
Special voltages available on request. Technical modifications reserved.
B = Width
T = Depth
Fan expansion kit
for door-mounted fan
To increase the air throughput of the door-
mounted fan.
To fit door-mounted fan Model No. SK
SK 3165.624, SK 3165.824 3165.024
SK 3165.648, SK 3165.848 3165.048
SK 3165.615, SK 3165.815 3165.115
SK 3165.630, SK 3165.830 3165.230
60 Rittal System Climate Control
Air/airheatexchangers
Air/air heat exchangers
The requirement for using air/air heat exchangers is
that the ambient temperature must be below the
required enclosure internal temperature. Dust and any
aggressive ambient air is unable to ingress the
enclosure interior, thanks to the two separate air
circuits.
61Rittal System Climate Control
Air/airheatexchangers
Platform strategy/
installation
Identical installation cut-outs
for various output classes.
Easily retrofitted
Thanks to the low weight, simple
assembly cut-outs and problem-
free attachment of the heat
exchangers, a cabinet or
enclosure is easily retro-fitted.
Benefits at a glance
● Specific thermal output from 17.5 W/K to
90 W/K
● External and internal circuit may be
controlled separately
● Mounting cut-outs and enclosure
dimensions identical to TopTherm
wall-mounted cooling units
● Suitable for external and internal
mounting
● Top design identical to TopTherm wall-
mounted cooling units
Important
The temperature difference between the
room temperature and enclosure internal
temperature will have a decisive effect on
the heat loss that may be dissipated.
Tips and tricks
Applications see page 202
Selection criteria see page 203
Assembly see page 204
Air routing see page 205
Electrical connection
and control see page 206
Safety
High protection category
Thanks to the seamlessly sealed heat
exchanger module, a protection category
of IP 54 to EN 60 529 is achieved.
High load capacity
The motors of the fans are equipped with
thermal winding protection.
Top quality: Guaranteed protection for
your electronics.
All devices in the Rittal TopTherm-Plus series
are tested in accordance with the interna-
tionally valid approvals (GS, UL).
Simple maintenance
The heat exchanger unit is very easily
removed and cleaned. The cleverly thought-
out structure enables fast, economical main-
tenance.
Air/air heat exchangers
Wall-mounted
62 Rittal System Climate Control
Air/airheatexchangers
T
H
B
B
H
T
B
H
T
Supply includes:
Fully wired unit ready for con-
nection.
Detailed drawing,
see page 241.
Performance diagrams,
available on the Internet.
SK 3125.800
Compact wall-mounted air/air
heat exchanger. Ideal for small
enclosures and command
panels.
Suitable for external and inter-
nal mounting.
SK 3129.800
Super-slimline air/air heat
exchangers. Ideal for external
door mounting.
Model No. SK 3125.800 3129.800
Rated operating voltage V/Hz 230, 1~, 50/60
Dimensions in mm
W
H
D
200
400
146
400
1360
110
Specific thermal output 12 W/K 62 W/K
Fans 2 per heat exchanger
Max. rated current per fan 0.11 A/0.13 A 0.45 A/0.55 A
Pre-fuse T 2.0 A
Output per fan 25 W/30 W 100 W/130 W
Air throughput of fans (unimpeded air flow)
External circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/h
Internal circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/h
Temperature range –5°C to +55°C
Type of connection Connection cable
Weight 8 kg 30 kg
Colour RAL 7035
Protection category to EN 60 529 Internal circuit IP 54
Accessories Packs of Page
Thermostat 1 3110.000 178
Temperature display 1 3114.100 177
Speed control 1 3120.000 179
Special voltages available on request. We reserve the right to make technical modifications.
Accessories Page 171 Recooling systems From page 116 Configuration software Page 195
B = Width
T = Depth
Wall-mounted with controller
Air/air heat exchangers
63Rittal System Climate Control
Air/airheatexchangers
T2
50
950
T1
400
108
42
550
150
280
1580
215
400 165
50
T = Depth
● With controller and digital
temperature display
● Floating fault signal contact
in case of overtemperature
Supply includes:
Fully wired unit ready for con-
nection.
Approvals,
see page 276.
Detailed drawing,
see page 244.
Performance diagrams,
available on the Internet.
Model No. SK
230 V 3126.100 3127.100 3128.100 3129.100 3130.100
115 V 3126.115 3127.115 3128.115 3129.115 3130.115
Rated operating voltage V/Hz 230/115, 1~, 50/60
Dimensions in mm
W
H
T1
T2
280
550
150
–
400
950
205
155
400
950
225
175
400
1580
215
–
Specific thermal output 17.5 W/K 30 W/K 45 W/K 60 W/K 90 W/K
Fans 2 per heat exchanger
Max. rated current per fan
230 V 0.11 A/0.13 A 0.28 A/0.34 A 0.3 A/0.4 A 0.38 A/0.4 A 0.67 A/0.88 A
115 V 0.23 A/0.25 A 0.55 A/0.7 A 0.6 A/0.8 A 0.65 A/0.8 A 1.3 A/1.8 A
Pre-fuse T 2.0 A 4.0 A
Output per fan 23 W/27 W 60 W/75 W 70 W/90 W 85 W/90 W 150 W/200 W
Air throughput of fans
(unimpeded air flow)
External circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/h
Internal circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/h
Temperature range –5°C to +55°C
Type of connection Plug-in terminal strip
Weight 10 kg 18 kg 19 kg 21 kg 34 kg
Colour RAL 7035
Protection category to EN 60 529 Internal circuit IP 54
Accessories Packs of Page
Filter mats 3 3286.300 3286.400 189
Metal filters 1 3286.310 3286.410 190
Special voltages available on request. We reserve the right to make technical modifications.
Accessories Page 171 Recooling systems From page 116 Configuration software Page 195
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb
Erdinc  klima sk_broschuere_gb

More Related Content

Similar to Erdinc klima sk_broschuere_gb

Yeni Rittal Global Hand Book 34
Yeni Rittal Global Hand Book 34Yeni Rittal Global Hand Book 34
Yeni Rittal Global Hand Book 34Eeu SC
 
Rittal - İklimlendirme ve Soğutma Ürünleri 001 023
Rittal - İklimlendirme ve Soğutma Ürünleri  001 023Rittal - İklimlendirme ve Soğutma Ürünleri  001 023
Rittal - İklimlendirme ve Soğutma Ürünleri 001 023erdinc klima
 
Daikin retail brochure
Daikin retail brochureDaikin retail brochure
Daikin retail brochureCanzonet Ltd
 
Transtherm Partner with Schneider for Smart Cooling - 05-2105
Transtherm Partner with Schneider for Smart Cooling - 05-2105Transtherm Partner with Schneider for Smart Cooling - 05-2105
Transtherm Partner with Schneider for Smart Cooling - 05-2105Tim Bound
 
Tewis Industrial Solutions
Tewis Industrial SolutionsTewis Industrial Solutions
Tewis Industrial SolutionsTewis Smart
 
alspa_solution_overview_brochure
alspa_solution_overview_brochurealspa_solution_overview_brochure
alspa_solution_overview_brochureJérôme PENAUD
 
Energy Efficiency through Hygienic Design
Energy Efficiency through Hygienic DesignEnergy Efficiency through Hygienic Design
Energy Efficiency through Hygienic Designsselchow
 
Embracing Change with Green IT
Embracing Change with Green ITEmbracing Change with Green IT
Embracing Change with Green ITGreg Aldrich
 
Brochure-Overview-Industrial-and-IT-Enclosure-Systems
Brochure-Overview-Industrial-and-IT-Enclosure-SystemsBrochure-Overview-Industrial-and-IT-Enclosure-Systems
Brochure-Overview-Industrial-and-IT-Enclosure-SystemsVinoulia Botha
 
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan DirikKoeppen Halvart
 
European Green IT Webinar 2014 - MicroPro Computers (Ireland)
European Green IT Webinar 2014 - MicroPro Computers (Ireland)European Green IT Webinar 2014 - MicroPro Computers (Ireland)
European Green IT Webinar 2014 - MicroPro Computers (Ireland)GreenLabCenter
 
Nautiz x7 manual_1.0
Nautiz x7 manual_1.0Nautiz x7 manual_1.0
Nautiz x7 manual_1.0Nguyễn An
 
Specification Guide: Modular Casework
Specification Guide: Modular CaseworkSpecification Guide: Modular Casework
Specification Guide: Modular CaseworkSignUp.com
 
Daikin commercial heating brochure
Daikin commercial  heating brochureDaikin commercial  heating brochure
Daikin commercial heating brochureCanzonet Ltd
 
Driving business performance through sustainability: From strategy to impleme...
Driving business performance through sustainability: From strategy to impleme...Driving business performance through sustainability: From strategy to impleme...
Driving business performance through sustainability: From strategy to impleme...Schneider Electric
 
Brochure (M&N BD Tech)
Brochure (M&N BD Tech)Brochure (M&N BD Tech)
Brochure (M&N BD Tech)Abu Musa
 

Similar to Erdinc klima sk_broschuere_gb (20)

Yeni Rittal Global Hand Book 34
Yeni Rittal Global Hand Book 34Yeni Rittal Global Hand Book 34
Yeni Rittal Global Hand Book 34
 
Rittal - İklimlendirme ve Soğutma Ürünleri 001 023
Rittal - İklimlendirme ve Soğutma Ürünleri  001 023Rittal - İklimlendirme ve Soğutma Ürünleri  001 023
Rittal - İklimlendirme ve Soğutma Ürünleri 001 023
 
Daikin retail brochure
Daikin retail brochureDaikin retail brochure
Daikin retail brochure
 
Transtherm Partner with Schneider for Smart Cooling - 05-2105
Transtherm Partner with Schneider for Smart Cooling - 05-2105Transtherm Partner with Schneider for Smart Cooling - 05-2105
Transtherm Partner with Schneider for Smart Cooling - 05-2105
 
Tewis Industrial Solutions
Tewis Industrial SolutionsTewis Industrial Solutions
Tewis Industrial Solutions
 
alspa_solution_overview_brochure
alspa_solution_overview_brochurealspa_solution_overview_brochure
alspa_solution_overview_brochure
 
Energy Efficiency through Hygienic Design
Energy Efficiency through Hygienic DesignEnergy Efficiency through Hygienic Design
Energy Efficiency through Hygienic Design
 
REVAMP HVAC
REVAMP  HVACREVAMP  HVAC
REVAMP HVAC
 
Embracing Change with Green IT
Embracing Change with Green ITEmbracing Change with Green IT
Embracing Change with Green IT
 
Brochure-Overview-Industrial-and-IT-Enclosure-Systems
Brochure-Overview-Industrial-and-IT-Enclosure-SystemsBrochure-Overview-Industrial-and-IT-Enclosure-Systems
Brochure-Overview-Industrial-and-IT-Enclosure-Systems
 
iCool CO2 transcritical condensing units
iCool CO2 transcritical condensing unitsiCool CO2 transcritical condensing units
iCool CO2 transcritical condensing units
 
Chiller daikin datos tecnicos
Chiller daikin datos tecnicosChiller daikin datos tecnicos
Chiller daikin datos tecnicos
 
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
07 Pepsi Cola Cooler Sustainability With Hydrocarbons Soykan Dirik
 
European Green IT Webinar 2014 - MicroPro Computers (Ireland)
European Green IT Webinar 2014 - MicroPro Computers (Ireland)European Green IT Webinar 2014 - MicroPro Computers (Ireland)
European Green IT Webinar 2014 - MicroPro Computers (Ireland)
 
Nautiz x7 manual_1.0
Nautiz x7 manual_1.0Nautiz x7 manual_1.0
Nautiz x7 manual_1.0
 
Specification Guide: Modular Casework
Specification Guide: Modular CaseworkSpecification Guide: Modular Casework
Specification Guide: Modular Casework
 
Specification Guide: Modular Casework & Mailroom Furniture
Specification Guide: Modular Casework & Mailroom FurnitureSpecification Guide: Modular Casework & Mailroom Furniture
Specification Guide: Modular Casework & Mailroom Furniture
 
Daikin commercial heating brochure
Daikin commercial  heating brochureDaikin commercial  heating brochure
Daikin commercial heating brochure
 
Driving business performance through sustainability: From strategy to impleme...
Driving business performance through sustainability: From strategy to impleme...Driving business performance through sustainability: From strategy to impleme...
Driving business performance through sustainability: From strategy to impleme...
 
Brochure (M&N BD Tech)
Brochure (M&N BD Tech)Brochure (M&N BD Tech)
Brochure (M&N BD Tech)
 

More from erdinc klima

Tlc temperature-limit-controller
Tlc temperature-limit-controllerTlc temperature-limit-controller
Tlc temperature-limit-controllererdinc klima
 
T ex universal-controller
T ex universal-controllerT ex universal-controller
T ex universal-controllererdinc klima
 
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruTcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruerdinc klima
 
Tcx 12062-universal-controller
Tcx 12062-universal-controllerTcx 12062-universal-controller
Tcx 12062-universal-controllererdinc klima
 
Tcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllerTcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllererdinc klima
 
Tci universal-controller
Tci universal-controllerTci universal-controller
Tci universal-controllererdinc klima
 
M6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllerM6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllererdinc klima
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controllererdinc klima
 
Ec 300-energy-controller
Ec 300-energy-controllerEc 300-energy-controller
Ec 300-energy-controllererdinc klima
 
Tcy3 universa-controller
Tcy3 universa-controllerTcy3 universa-controller
Tcy3 universa-controllererdinc klima
 
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarKontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarerdinc klima
 
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisiKontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisierdinc klima
 
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisiKontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisiKontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisiKontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisierdinc klima
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisierdinc klima
 
Duyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostatDuyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostaterdinc klima
 
Duyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorDuyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorerdinc klima
 
Duyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlerDuyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlererdinc klima
 

More from erdinc klima (20)

Tlc temperature-limit-controller
Tlc temperature-limit-controllerTlc temperature-limit-controller
Tlc temperature-limit-controller
 
T ex universal-controller
T ex universal-controllerT ex universal-controller
T ex universal-controller
 
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloruTcx 14062-hrv-isi-ger-havalandirma-kontroloru
Tcx 14062-hrv-isi-ger-havalandirma-kontroloru
 
Tcx 12062-universal-controller
Tcx 12062-universal-controllerTcx 12062-universal-controller
Tcx 12062-universal-controller
 
Tcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controllerTcx2 40863 u-opa2-universal-controller
Tcx2 40863 u-opa2-universal-controller
 
Tci universal-controller
Tci universal-controllerTci universal-controller
Tci universal-controller
 
M6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controllerM6000 t1-t2-an-air-conditione-controller
M6000 t1-t2-an-air-conditione-controller
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controller
 
Ec 300-energy-controller
Ec 300-energy-controllerEc 300-energy-controller
Ec 300-energy-controller
 
Tcy3 universa-controller
Tcy3 universa-controllerTcy3 universa-controller
Tcy3 universa-controller
 
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalarKontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
Kontrol vanası ve servomotorlar watts v2 bm-v3bm-lineer-vanalar
 
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisiKontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
Kontrol vanası ve servomotorlar gruner kureselmotorluvanalar225serisi
 
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisiKontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
Kontrol vanası ve servomotorlar gruner kuresel motorluvanalar224-235serisi
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-90-serisi
 
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisiKontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
Kontrol vanası ve servomotorlar esbe rotary-kontrol-vanalari-3 f-serisi
 
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisiKontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
Kontrol vanası ve servomotorlar esbe lineer-vana-motorlari-ala-serisi
 
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisiKontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
Kontrol vanası ve servomotorlar esbe rotary-vana-motorlari-ara600-serisi
 
Duyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostatDuyar Elemanlar St fr ex-donma-termostat
Duyar Elemanlar St fr ex-donma-termostat
 
Duyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensorDuyar Elemanlar Sensi co px300-co-sensor
Duyar Elemanlar Sensi co px300-co-sensor
 
Duyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorlerDuyar Elemanlar Vector sensorler
Duyar Elemanlar Vector sensorler
 

Recently uploaded

(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCRsoniya singh
 
Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756
Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756
Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756dollysharma2066
 
Call Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any TimeCall Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any Timedelhimodelshub1
 
(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCRsoniya singh
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewasmakika9823
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Roomdivyansh0kumar0
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,noida100girls
 
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / NcrCall Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncrdollysharma2066
 
Islamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in IslamabadIslamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in IslamabadAyesha Khan
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsApsara Of India
 
Non Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxNon Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxAbhayThakur200703
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
Investment analysis and portfolio management
Investment analysis and portfolio managementInvestment analysis and portfolio management
Investment analysis and portfolio managementJunaidKhan750825
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechNewman George Leech
 
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...lizamodels9
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...lizamodels9
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst SummitHolger Mueller
 
(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCRsoniya singh
 

Recently uploaded (20)

Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCREnjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
 
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
 
Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756
Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756
Call Girls In ⇛⇛Chhatarpur⇚⇚. Brings Offer Delhi Contact Us 8377877756
 
Call Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any TimeCall Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any Time
 
(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Hauz Khas 🔝 Delhi NCR
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
 
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
BEST Call Girls In Greater Noida ✨ 9773824855 ✨ Escorts Service In Delhi Ncr,
 
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / NcrCall Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
Call Girls in DELHI Cantt, ( Call Me )-8377877756-Female Escort- In Delhi / Ncr
 
Islamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in IslamabadIslamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in Islamabad
 
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call GirlsCash Payment 9602870969 Escort Service in Udaipur Call Girls
Cash Payment 9602870969 Escort Service in Udaipur Call Girls
 
Non Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptxNon Text Magic Studio Magic Design for Presentations L&P.pptx
Non Text Magic Studio Magic Design for Presentations L&P.pptx
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
Investment analysis and portfolio management
Investment analysis and portfolio managementInvestment analysis and portfolio management
Investment analysis and portfolio management
 
RE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman LeechRE Capital's Visionary Leadership under Newman Leech
RE Capital's Visionary Leadership under Newman Leech
 
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
Lowrate Call Girls In Laxmi Nagar Delhi ❤️8860477959 Escorts 100% Genuine Ser...
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
 
Progress Report - Oracle Database Analyst Summit
Progress  Report - Oracle Database Analyst SummitProgress  Report - Oracle Database Analyst Summit
Progress Report - Oracle Database Analyst Summit
 
(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Mahipalpur 🔝 Delhi NCR
 

Erdinc klima sk_broschuere_gb

  • 1. Safeguarding our future with consistent energy efficiency! Rittal – System climate control
  • 2. Rittal is your value-creating partner for comprehensive technology packaging solutions. We offer individual system benefits based on our complete product range, extensive expertise and global customer service – cross- sector, value-maximising solutions that are one hundred percent benefit-focussed.
  • 3. Rittal system climate control is proven to boost energy efficiency by up to 45 percent – while ensuring optimum cooling performance for all control and IT components. Thanks to the significant reduction in energy consumption, Rittal’s innovative cooling concepts are major contributors to cost efficiency in your company, while at the same time helping to cut CO2 emissions in the environment.
  • 4. From system to solution: Comprehensively individual However individual your business, you can be sure that all Rittal climate control systems provide a comprehensive expert package: ● Exemplary energy efficiency ● Plus special project engineering ● Plus permanent innovative strength ● Plus typical Rittal high-quality production. Rittal never loses sight of a project’s particular customer requirements. The aim is always the same: to produce maximum benefits for the customer. Expertise Efficiency Engineering Innovation High quality+ + + +
  • 5. 3Rittal System Climate Control Outdoor climate control from page 157 Cooling units for CS modular enclosures .......................................160 Heat exchangers for CS modular enclosures ................................161 Climate control units for Toptec CR............................................... 163 Ex-proof climate control systems ...................................................164 Liquid cooling IE from page 99 Air/water heat exchangers, roof-mounted .....................................100 Air/water heat exchangers, wall-mounted .................................... 100 Direct Cooling Package (mounting plate cooling)......................... 110 Recooling systems for water ..........................................................116 Recooling systems for oil............................................................... 130 Immersible recooling systems for oil/emulsion ............................. 132 System solutions from page 15 For mechanical engineering .............................................................15 For the IT sector................................................................................19 For various ambient conditions.........................................................23 For final assembly/handling systems................................................27 Project planning from page 31 Basic principles for the use of climate control components ............32 Cooling with ambient air ...................................................................35 Cooling units .....................................................................................36 Liquid cooling IE/IT ...........................................................................37 Enclosure heaters .............................................................................39 Enclosure heaters from page 167 Enclosure heaters ..........................................................................168 System accessories from page 171 Air routing....................................................................................... 174 Control/regulation........................................................................... 177 Mounting accessories.................................................................... 181 Cold Plate....................................................................................... 184 Liquid Cooling Package ................................................................ 186 Filter technology ............................................................................ 189 General .......................................................................................... 192 Software service........................................................................... 195 Cooling with ambient air from page 41 Fan-and-filter units ............................................................................42 Rack-mounted fans...........................................................................50 Tangential fans..................................................................................50 Fan systems......................................................................................54 Air/air heat exchangers.....................................................................60 Cooling units from page 67 Modular climate control concept ......................................................68 Roof-mounted cooling units..............................................................72 Wall-mounted cooling units ..............................................................80 Thermoelectric coolers .....................................................................96 Tips and tricks from page 197 Cooling with ambient air .................................................................198 Cooling units ...................................................................................207 Liquid cooling IE .............................................................................217 Liquid cooling IT .............................................................................230 Enclosure heaters ...........................................................................234 Monitoring .......................................................................................235 Technical details from page 239 Cooling with ambient air .................................................................240 Cooling units ...................................................................................245 Liquid cooling IE .............................................................................251 Liquid cooling IT .............................................................................266 Enclosure heaters ...........................................................................267 System accessories........................................................................268 Overview of products and approvals from page 271 Overview of products and approvals .............................................272 Service .......................................................................................... 298 List of model numbers................................................................. 300 Index.............................................................................................. 303 Liquid cooling IT from page 135 CRAC systems................................................................................136 Aisle containment........................................................................... 139 Liquid Cooling Package (rack cooling) ......................................... 140 Chillers for IT cooling ......................................................................146 Water/water heat exchangers ........................................................150 Piping systems................................................................................154
  • 7. 5 Rittal climate expertise – Outstanding breadth and quality. Rittal cooling concepts are synonymous with guaranteed quality, from the product itself right through to customer service. Global availability, globally sought- after. International approvals are just as much part of the Rittal “system concept” as uniform system platforms for cooling units and heat exchangers. Rittal’s winning formula for climate control expertise centres around one basic idea, with infinite possibilities. Flexible, inexpensive, and exceptionally efficient. Rittal cooling concepts are complete solutions, precisely tailored to your requirements and offering exceptional added-value.
  • 9. 7 Rittal efficiency – A fresh take on creativity and value-added. Thanks to its intensive research and development work with Pro Ozone cooling units, Rittal has helped to focus the world’s attention on “efficiency”. With a host of innovative ideas such as nano surface protection, the Liquid Cooling product family and coolants based on environmentally neutral CO2, Rittal is renowned as a world leader in this field. Less is more, is our guiding principle: Less consumption of energy and resources on the one hand, and more cost- effectiveness and productivity for customers on the other. Rittal’s solutions successfully unite these two principles.
  • 11. 9 Rittal engineering – Building on cooperation for a shared future. Whether you require analysis of an existing climate control concept, or help planning a new one, Rittal is a partner you can rely on. As well as manufacturing system com- ponents, Rittal also collaborates closely with customers in the research and development field. We act as engineering partners to our clients. A combination of practical experience and project planning leads to innovative, comprehensive climate control concepts. Rittal’s customer service and main- tenance divisions guarantee com- plete customer satisfaction from start to finish.
  • 13. 11 Rittal’s innovative strength – Deriving fresh growth from ideas. Innovation cannot be planned, but it can be continuously re- evaluated. This is Rittal’s approach when tackling any new task. In an instant, an idea is born, which the Rittal laboratories then develop into a new product solution. The thermoelectric cooler, which cuts energy consumption by more than 60 % compared with conventional systems, is just one innovative high-end example among many. Rittal’s engineers are encouraged to think outside the box and come up with new solutions. These ideas add value and help to make our customers more competitive.
  • 15. 13 Rittal high quality production – Top quality begins with the tiniest detail. Rittal achieves outstanding high- quality at its own production sites and in-house research depart- ments, development units and test laboratories. This in turn enables us to guarantee outstanding pro- duct quality, because our process quality is second to none. Every department is broken down into individual process units, each of which plays a vital role in Rittal’s overall quality. High quality pro- duction relies on a perfect quality assurance chain. This quality standard reflects Rittal’s 100 % customer dedication.
  • 16. 14
  • 17. 15Rittal System Climate Control Systemsolutions/Mechanicalengineering Rittal DCP – Direct Cooling Package Direct cooling of power electronics inside the enclosure ● Using liquid-cooled mounting plates, with or without fans ● No impairment to the protection category ● With efficient frequency converter cooling. Air/water heat exchangers The classic liquid cooling solution ● For extremely hot and dusty ambient conditions ● To dissipate high heat loads without putting thermal pressure on the ambient air. Rittal recooling systems Energy-efficient cooling of liquid cooling media. ● A high level of temperature accuracy. ● Powerful performance. ● Individual system solutions. Rittal system climate control for mechanical engineering Precision scores an ace Whenever a higher enclosure protection category is required due to hot, metal dust- laden or oily ambient conditions, Rittal liquid cooling concepts really come up trumps. Precise temperature control of machine and process cooling is another priority. When cooling spindles with 40,000 rpm, for example, Rittal recooling systems supply volumetric flows and coolant temperatures at precisely the required level. Rittal system climate control is the key to a high level of dimensional accuracy, consistently perfect workpieces, and stable production conditions.
  • 18. 16 Rittal System Climate Control Systemexample System example Rittal system climate control for mechanical engineering 5 A C B 2 6 1011 812 19 20 9 13 16 16 14 15 26 27 28 25 2123 24 22 7 4 17 18 29 31 32 35 30 33 34 3 1 Example: Rittal system climate control for mechanical and plant engineering The air inside the hall is contaminated with metal swarf and oil mist, and is unable to absorb waste heat from the controllers and machine cooling system. A comprehensive Rittal liquid cooling concept with central recooling (1) provides a particularly efficient solution. All function and safety-relevant components are remotely monitored with Rittal CMC-TC (3). The benefit to you: Added perfection and increased productivity. Machining centre, welding robot ● The coolant temperature of the process emulsion is precisely coordinated with the machining cycle of the spindle rotating at high speed, thanks to the immersion recooling system (7). ● Process heat from the welding robot and heat loss from the PC case of the robot controller (18) – case based on TS 8, equipped with air/water heat exchanger (17) – is effectively dissipated via Rittal recooling systems (1). ● The twin-doored enclosure ES 5000 with air/water heat exchanger, wall-mounted (8), is integrated into the design of the machines. ● Rittal thermoelectric coolers (16) are a particularly compact, efficient solution for cooling the Rittal Comfort Panel (13) command panels. The enclosure is custom-built and equipped to order, with a support arm system (15) tailored to your individual requirements. Machine controller, low-voltage distributor ● Bayed Top enclosure system TS 8 (24). ● Rittal DCP: Liquid-cooled mounting plates (Cold Plate) (21) for efficient frequency converter cooling and ● TopTherm air/water heat exchangers, roof- mounted (23) and wall-mounted (22), with internal controllers for monitoring and control, reliably dissipate the heat loss. ● The modular power supply is type-tested for global use (28). Industrial IT and control room ● Network enclosures are effectively climate- controlled with a special, low-noise office cooling unit (29). ● EMC fan-and-filter units (30) cool the command controller in the pedestals of the TopConsole systems (33). A C B
  • 19. 17Rittal System Climate Control Systemexample Rittal system climate control for mechanical engineering System example System-wide Components Page Central recooling system for enclosure and machine cooling 148 Piping systems 154 CMC-TC for monitoring access, climate, power supply Cat. 32, p. 808 Test workstation: Rittal Industrial Workstation with support arm CP-S, TFT screen, membrane keyboard Cat. 32, p. 172 Air/water heat exchanger on the IW pedestal 63 Ex overpressure enclosure, climate-controlled 164 Ex overpressure enclosure with integral enclosure cooling unit for zone II, gas (6) 1 2 3 4 5 6 Machining centre, welding robot Components Page Immersible recooling system for process emulsion 132 Air/water heat exchanger, wall-mounted 104 Free-standing enclosure ES 5000, twin-door Cat. 32, p. 155 Cable entry, cable routing Cat. 32, p. 1045 Interior installation, mounting levels Cat. 32, p. 988 Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125 Rittal Comfort Panel command panel Cat. 32, p. 192 Monitors, keyboards, handles for the Comfort Panel Cat. 32, p. 1133 CP-L support arm system for Comfort Panel Cat. 32, p. 250 Thermoelectric cooler for Comfort Panel 97 Air/water heat exchanger, space-saving accommodated on the roof of the PC case 74 PS enclosure system, based on TS 8 Cat. 32, p. 168 Base/plinth for PC case system Cat. 32, p. 892 Bus enclosure Cat. 32, p. 120 More compact, lightweight and efficient. The powerful thermoelectric cooling unit in a lightweight design (16). The eco-friendly climate control solution for command panels and small enclosures – an energy saving of more than 60 % compared with conven- tional industry systems. A 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Machine controller, low-voltage distributor Components Page Rittal DCP Cold Plate – Liquid-cooled mounting plates 112 Air/water heat exchanger, wall-mounted 104 Air/water heat exchanger, roof-mounted 102 Baying enclosure system TS 8 Cat. 32, p. 136 System accessories (base/plinth, walls, baying technique, locks, interior installation, cable routing) Cat. 32, p. 926 Ri4Power Form 1, heavy current power distributor Cat. 32, p. 438 Ri4Power Form 2-4, form separation for low-voltage switchgear Cat. 32, p. 472 RiLine60, busbar systems Cat. 32, p. 350 Rittal DCP Cold Plate – Liquid- cooled mounting plates (21) B 21 22 23 24 25 26 27 28 Industrial IT and control room Components Page Office cooling units for network enclosures 76 EMC fan-and-filter units for console systems 48 Network enclosures, based on TS 8 Cat. 32, p. 745 System accessories for IT (patch panels, component shelves) Cat. 32, p. 1013 TopConsole system Cat. 32, p. 156 System accessories for consoles (base/plinth, interior installation) Cat. 32, p. 890 System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards) Cat. 32, p. 1115 Quiet performance: Office cooling units for network enclosures (29) C 29 30 31 32 33 34 35
  • 20.
  • 21. 19Rittal System Climate Control Systemsolutions/ITsector Rittal system climate control for data centres and IT Cool and efficient! A high performance server in the data centre or in the middle of the office? Without putting additional thermal pressure on the air-conditioning system? Without the irritating noise of high-speed fan-and-filter units? All that can now be achieved very easily! Because Rittal Liquid Cooling concepts offer new framework conditions for your IT infrastructures in terms of flexibility, safety and cost-efficiency. Independent of the room situation, with almost zero heat and noise emissions, individual server CPUs and complete server units or electronic components receive direct, highly effective cooling. Modular concepts, tailored precisely to your current requirements, and easily scalable to meet future needs. Rittal CRAC systems By using Rittal aisle containment, ● you can optimise air-conditioning of the room ● in conjunction with the Rittal CRAC system ● in terms of energy efficiency and cooling output. LCP – Liquid Cooling Package Rittal solves the problem of climate control for high heat losses per rack with this system family. ● Extremely high heat loads are dissipated from the rack via the LCP (air/water heat exchanger). ● Additionally, this system also allows temperature-neutral expansion of the data centre. Piping systems The Rittal piping system provides the link between the equipment and the refrigeration system. ● An optimum design and targeted media supply ensure efficient oper- ation of all cooling components.
  • 22. 20 Rittal System Climate Control Systemexample System example Rittal system climate control for the IT sector C A B 3 2 1 9 30 4 1.1 5 6 8 10 13 14 17 15 16 18 19 22 20 21 11 12 7 292824 23272625 Example: Rittal system climate control for data centres and IT High heat loads in modern data centres, maximum availability, and the most energy- efficient climate control system available. To accommodate all three requirements, you will need an individual concept: Rittal liquid cooling IT. Redundant chillers (1), free cooling (1.1) and heat recovery (7). Piping systems are designed on a project- specific basis. Data centre ● At the heart of this concept are server racks (9) with the option of aisle containment (8). ● The cold air required is blasted in via the raised floor by two CRAC systems (10). ● Other LCP-cooled (11) computer cases also operate without dissipating heat to the ambient air. Development server room, UPS ● The server systems are cooled via LCPs (14), without a raised floor and without putting pressure on the climate control system. The heat is dissipated completely silently via the piping system. ● All server racks are based on the TS 8 enclosure platform (15). ● The dissipation of heat loss from the UPS is also integrated into the liquid cooling concept via the air/water heat exchanger. ● Alternative recooling via LCP Inline or LCP Extend. Administration, monitoring ● All function and safety-relevant components are remotely monitored with Rittal CMC-TC. Messages and controls occur centrally in the control room (23). ● Super-low-noise roof-mounted fans (23) cool the network enclosures in the office. An even quieter alternative are air/water heat exchangers integrated into the coolant cycle. ● EMC fan-and-filter units with speed control (24) ensure fault-free operation and cooling of the control room consoles. The result: Targeted, low-noise, energy efficient! A B C
  • 23. 21Rittal System Climate Control Systemexample Rittal system climate control for the IT sector System example System-wide Components Page IT chiller, redundant configuration, also with free cooling device 146 or external free cooling function 147 Double pump unit 147 Water/water heat exchanger 152 Buffer store Water/water heat exchanger 152 Emergency water supply Heat recovery IT chiller, redundant configuration, also with free cooling (1). 1 1.1 2 3 4 5 6 7 Data centre with raised floor Components Page Rittal aisle containment 139 Server racks for aisle containment CRAC systems for raised floor and aisle flooding 138 Room temperature-neutral server extension, cooling with LCP Standard, Plus or Smart Cat. 32, p. 726 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777 System accessories for server racks (cable management devices, monitor/keyboard unit, KVM switch, power distribution, plug-in modules, component shelves, base/plinths and much more besides) Cat. 32, p. 890 CRAC systems for raised floor and aisle flooding (10) A 8 9 10 11 12 13 Server room without raised floor, UPS Components Page Separate servers in the development department, cooling with LCP Standard, Plus or Smart 140 LCP Inline 145 LCP Extend 143 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 777 System accessories for server racks Cat. 32, p. 787 Air/water heat exchangers for UPS cooling 104 UPS: Power Modular Concept PMC, rack basis TS 8 Cat. 32, p. 786 Power distribution: Power Distribution Rack PDR Cat. 32, p. 787 Socket strips: Power System Module PSM Cat. 32, p. 789 Ambient air-neutral server cooling with LCP air/water heat exchangers (14) B 14 15 16 17 18 19 20 21 22 Server and network administration, video monitoring Components Page Roof-mounted fan for the office sector 76 EMC fan-and-filter units for console systems with speed control 48 CMC-TC, modular system for monitoring climate, access and power supply Cat. 32, p. 806 Network enclosures, based on TS 8 Cat. 32, p. 745 System accessories for IT (patch panels, component shelves) Cat. 32, p. 1013 TopConsole system Cat. 32, p. 156 System accessories for consoles (base/plinth, interior installation) Cat. 32, p. 890 System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards) Cat. 32, p. 1115 Roof-mounted fan for the office sector (23) C 23 24 25 26 27 28 29 30
  • 24.
  • 25. 23Rittal System Climate Control Systemsolutions/Variousambientconditions Rittal system climate control for various ambient conditions TopTherm-Plus Cleaning, phosphating, dipcoat-priming, spray-finishing, drying. The process chain in a spray-finishing plant creates extremely varied ambient conditions – and this also affects climate control of the controllers. Whether humidity, paint dust or drying heat – these varying requirements are met by a single product range: Rittal TopTherm-Plus cooling units. With nano-coating of the heat exchanger surfaces, this ensures a high level of efficiency and exceptional durability. Rittal cooling units – Masters of energy efficiency TopTherm-Plus cooling units Cooling units keep the enclosure internal temperature at a constant level, even to below room tempera- ture, with the air routing being tai- lored to individual requirements. Two separate circuits prevent the ingress of dust into the enclosure. ● Climate control doors ● Roof-mounted cooling units ● Wall-mounted cooling units Electronic condensate evaporation Any condensate incurred is effectively evaporated and doesn’t need to be collected or dissipated. Your value-added: ● Enhanced safety – No condensate drips onto the floor. ● Time savings – No need to empty condensate containers. ● Cost benefits – No need to lay condensate tubing. Master/slave mode In open bayed enclosure systems, cooling units or air/water heat exchangers with Comfort control are set to master/slave mode via a bus cable: ● Even temperature distribution across all sections of the enclosure. ● Simultaneous activation and deactivation of the devices. ● Parallel system and door limit switch function.
  • 26. 24 Rittal System Climate Control Systemexample System example Rittal system climate control for various ambient conditions 1 2 6 10 8 19 91211 7 5 4 14 16 15 17 18 20 23 24 21 22 3 13 A B D C Example: Rittal system climate control for various ambient conditions Rittal TopTherm-Plus cooling units define the performance class of the future. Even under extremely varied ambient conditions, the control electronics are climate-controlled at a stable level and with a high degree of reliability. This is supplemented by plant-wide remote monitoring with Rittal CMC-TC (23) – this ensures availability and also saves money. Control of the cleaning and priming line – high humidity ● Roof-mounted cooling units (1) and wall- mounted cooling units (2) in master/slave mode (3). The cooling output of several cooling units in a bayed enclosure suite is carefully coordinated to boost efficiency. ● Wall-mounted cooling units (2) may be internally mounted, partially internally mounted or externally mounted. ● Design variants: Standard, stainless steel (4), NEMA 4x, all including RiNano coating and condensate management. Control of the spray-finishing and drying line – paint dust and heat ● Perfection in cooling and design with the modular climate control concept (7). The enclosure door and climate components are combined into one – no need for time- consuming assembly. ● Comfort controller (8) – the ideal control and safety electronics. ● Bayed EMC systems TS 8 (9) with a high level of RF attenuation. Control and inspection workstations ● Test workstation with mini-cooling units (14). ● Individual configuration from IW modules (15) (Industrial Workstation). ● Command Panel (Optipanel) (17) with thermoelectric cooler (18) and individual panel design. Support arm system CP-XL. Configured entirely to your requirements. Control room for the entire production process ● Server enclosures – based on TS 8 (21) – in the control room, bayed with LCP cooling (20). ● The central recooling system (19). supplies cooling medium in a particularly energy-efficient manner. A B C D
  • 27. 25Rittal System Climate Control Systemexample Rittal system climate control for various ambient conditions System example Control of the cleaning and priming line Components Page TopTherm-Plus cooling units, roof-mounted 74 TopTherm-Plus cooling units, wall-mounted 83 Master/slave mode 235 Cooling units in stainless steel 74 Bayed Top enclosure system TS 8 Cat. 32, p. 136 System accessories for TS 8 (base/plinth, walls, doors, baying system, rail systems for interior installation, cable entry and much more besides) Cat. 32, p. 926 Cooling units also available in stainless steel. TopTherm-Plus cooling units (1, 2) ensure constant temperatures for control electronics, regardless of variations in the ambient conditions. A 1 2 3 4 5 6 Control of the spray-finishing and drying line Components Page TopTherm-Plus climate control doors combined with TS 8 70 Comfort controller 70 Bayed Top enclosure system TS 8 with EMC shielding Cat. 32, p. 329 Base/plinth (100/200 mm) for TS 8, compulsory when using climate control doors (modular climate control concept) Cat. 32, p. 893 EMC system accessories Cat. 32, p. 572 Signal pillars Cat. 32, p. 1125 Recooling system to cool the robot controller 127 TopTherm-Plus climate control doors combined with TS 8 enclosure system: Optimum airflow, no assembly work (7) B 7 8 9 10 11 12 13 Control and inspection workstations Components Page Mini-cooling unit, wall-mounted, on IW and TopConsole 83 Industrial Workstation (IW) Cat. 32, p. 172 TopConsole system (pedestal, desk unit) with TFT monitor in the Optipanel (CP-S support arm system) Cat. 32, p. 156 Comfort-Panel command panel on CP-XL support arm system Cat. 32, p. 192 Thermoelectric cooler 97 Mini-cooling unit, wall-mounted for efficient cooling of small control and computer units (14) C 14 15 16 17 18 Control room for the entire production process Components Page IT chiller with integral free cooling device 148 Server cooling with LCP 141 Server racks, based on TS 8, bayed with LCPs Cat. 32, p. 774 System accessories for server racks Cat. 32, p. 890 CMC-TC, modular system for monitoring climate, access and power supply Cat. 32, p. 806 System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards) Cat. 32, p. 1115 Server cooling with LCP: Horizontal cold air routing, no thermal pressure on the room, cost-effective, central recooling (19) D 19 20 21 22 23 24
  • 28.
  • 29. 27Rittal System Climate Control Systemsolutions/finalassembly,handlingsystems System climate control for final assembly and handling systems Air versus heat Even in apparently non-critical ambient conditions, for example when there is an adequate supply of clean, cool air, it is still worthwhile to provide climate control. Here too, the aim is to achieve maximum reliability with exceptional efficiency. Reliability and efficiency with fan-and-filter units: Temperature-dependent speed control plus temperature and airflow monitoring. Reliability and efficiency with air/air heat exchangers: Thanks to separate air circuits (external/internal), dust remains excluded, while a micro-controller provides temperature-dependent control and monitoring of key parameters. The benefit to you: Efficient reliability at all times. Fan-and-filter units Fan-and-filter units are ideal for dissipating heat loads cost-effectively. ● The prerequisite is that the ambient air must be relatively clean with a temperature below the desired enclosure internal temperature. ● The entire range of fan-and-filter units is also available with EMC shielding. Air/air heat exchangers The requirement for using air/air heat exchangers is that the ambient temperature must be below the required enclosure internal temperature. ● Dust and contaminated ambient air is unable to ingress the enclosure, thanks to the two separate air circuits. Machine, process and enclosure cooling ● Operational reliability thanks to liquid cooling e.g. of high- frequency motor spindles and other drive technology. ● Precise workpiece machining thanks to precise, constant temperatures of the cooling media. ● In this way, temperature peaks inside enclosures – for example, in summer – can be effectively dissipated via air/water heat exchangers.
  • 30. 28 Rittal System Climate Control Systemexample System example Rittal system climate control for final assembly/handling systems D A C B 18 1 2 3 4 6 8 10 9 13 12 15 14 22 20 21 17 16 23 18 19 24 26 25 30 27 31 28 29 11 5 B 7 System climate control for final assembly and handling systems Air versus heat – Even in non-critical ambient conditions, it is still worthwhile providing systematic climate control. Here too, the aim is to achieve maximum reliability with exceptional efficiency. Control of production plant and handling systems Reliability and efficiency with air/air heat exchangers (1) to cool the free-standing enclosures ES 5000 (3). ● Thanks to separate air circuits (external/ internal), dust is unable to ingress. ● A high operating ratio and minimal cleaning required. ● Monitoring of key parameters via a micro- controller. Robot: Effective liquid cooling of controller and process A central recooling system (7) “kills two birds with one stone”: ● Effective cooling of the PC case (8) via air/water heat exchangers (6). ● Precise cooling of machine spindles and/or welding heads. Machine operation, quality assurance Reliability and efficiency thanks to fan-and- filter units (21) for Industrial Workstations IW (20): ● Temperature-dependent speed control. ● Temperature and airflow monitoring. Exceptionally energy-efficient cooling of command panels with thermoelectric coolers (17). Control room The aim is to minimise the level of noise pollution in offices: ● This can be achieved with Office roof- mounted fans (24) and speed-controlled fan-and-filter units (27). ● Zero emissions of heat and noise, thanks to a liquid cooling concept. A B C D
  • 31. 29Rittal System Climate Control Systemexample Rittal system climate control for final assembly/handling systems System example Control of production plant and handling systems Components Page Air/air heat exchangers, wall-mounted 62 Alternatively or additionally: Rittal TopTherm-Plus cooling units, wall-mounted 83 Free-standing enclosure ES 5000 Cat. 32, p. 154 Viewing window Cat. 32, p. 944 System accessories (base/plinth, cable entry and interior installation) Cat. 32, p. 890 Platform concept: Air/air heat exchangers, wall- mounted, have the same mounting interface as TopTherm-Plus (1, 2) A 1 2 3 4 5 Robot control and process cooling Components Page Air/water heat exchanger, wall-mounted on the rear door of the PC case 104 Recooling system for central enclosure and process cooling 116 PS enclosure system, based on TS 8 Cat. 32, p. 168 Base/plinth for PC case system Cat. 32, p. 892 Bus enclosure Cat. 32, p. 120 Signal pillar (in conjunction with CMC-TC) Cat. 32, p. 1125 Rittal Comfort Panel command panel Cat. 32, p. 192 Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133 CP-L support arm system for Comfort Panel Cat. 32, p. 250 Thermoelectric cooler for Comfort Panel 97 Recooling system for central enclosure and process cooling (7) B 6 7 8 9 10 11 12 13 14 15 Machine operation, quality assurance Components Page Rittal Comfort Panel command panel Cat. 32, p. 192 Thermoelectric cooler for Comfort Panel 97 Monitors, keyboards, handles for Comfort Panel Cat. 32, p. 1133 CP-L support arm system for Comfort Panel Cat. 32, p. 250 Industrial workstation IW Cat. 32, p. 172 Fan-and-filter unit, speed-controlled 44 Optipanel with TFT monitor, CP-S support arm system Cat. 32, p. 204 Compact Panel, CP-S support arm system Cat. 32, p. 231 Thermoelectric cooler for Comfort Panel (15, 17) C 16 17 18 19 20 21 22 23 Control room Components Page Office roof-mounted fans for network enclosures 55 Network enclosures, based on TS 8 Cat. 32, p. 745 System accessories for IT (patch panels, component shelves) Cat. 32, p. 1013 EMC fan-and-filter units for console systems 48 TopConsole system Cat. 32, p. 156 System accessories for consoles (base/plinth, interior installation) Cat. 32, p. 890 System accessories for the human/machine interface (keyboard drawers, TFT monitors, keyboards) Cat. 32, p. 1115 CMC-TC for monitoring access, climate, power supply Cat. 32, p. 806 Effective cooling, on request with RF shielding: EMC fan-and-filter unit (27) D 24 25 26 27 28 29 30 31
  • 32. 30
  • 33. 31Rittal System Climate Control Projectplanning Project planning Cooling with ambient air from page 35 Fan-and-filter units ............................................................................35 Air/air heat exchangers.....................................................................35 Cooling units from page 36 Condensation and dehumidification of the enclosure air .................36 Practical tips .....................................................................................36 Liquid cooling IE/IT from page 37 Air/water heat exchangers................................................................37 Notes on water quality ......................................................................37 Recooling systems/chillers ...............................................................38 Cooling water....................................................................................38 Form for designing recooling systems .............................................38 Enclosure heaters from page 39 Heating performance diagram..........................................................39 Basic principles for the use of climate control components from page 32 Guide to selecting suitable units.......................................................32 Heat dissipation ................................................................................33 Calculation basis for enclosure climate control................................34 Project planning software .................................................................34 Interactive performance diagrams ...................................................34
  • 34. Project planning Basic principles for the use of climate control components 32 Rittal System Climate Control Projectplanning Ambient conditions Enclosure interior problems Heat Heat loss Dust Condensate Cool Heat conduction Convection Radiation There are three basic forms of heat transfer: Thermal conduction: Heat is transported by matter, without the matter itself being moved. The energy is passed from particle to particle. Convection: Energy flows with the matter. The transport medium, e.g. a liquid or gas, takes up energy in the form of heat and dissipates energy as heat. Radiation: Heat is passed from one body to another in the form of radiation energy, without a medium material. The decisive factor for the type of heat dissipation to be used in enclosures is whether they are open (air-permeable) or closed (air-tight). Whereas in open enclosures, the heat is dissipated by means of air circulation, in closed enclosures the heat can only be dissipated via the enclosure wall. Rittal cooling units provide the ideal system solution for ensuring an optimum operating temperature inside an air- tight enclosure, even at high external temperatures. On the following pages, you will find a chrono- logical guide to help you to easily find the most suitable climate control solution. Guide to selecting suitable units As electronic components become ever smaller and are more densely packed in enclosures and electronic cases, systems are becoming increasingly sensitive to external factors such as dust, oil, moisture and temperature. Heat in particular is a deadly enemy of sensitive microelectronics. For example, a general rule of thumb for semi-conductors is that an increase in the operating temperature of 10°C, in relation to the maximum permissible operating temperature, will shorten its service life by half. In order to guarantee proper functioning of the electronics, this heat needs to be dissipated.
  • 35. Fast selection Project planning 33Rittal System Climate Control Projectplanning Heat dissipation Before you start, please consider your peripheral conditions such as external temperature, internal temperature and protection category. In order to achieve targeted, effective cooling, it is important to ensure correct calculation of the required climate control components and possible thermal analysis using computer- assisted flow models (CFD – Computational Fluid Dynamics). Protection category IP 54 important Ti target > Tu max. Cooling water cycle available at the installation site No Integrated louvres, air inlet/outlet grille Roof ventilation, fan-and-filter unit Air/air heat exchanger Yes Air/water heat exchanger Yes Cooling unit No Ti target < or = Tu max. Basic selection: Ti = Required internal temperature of enclosure [°C] Tu = Ambient temperature of enclosure [°C] Recooling system The following pages contain detailed calculation formulae for your chosen option. Calculation of effective enclosure surface area Of the variables required for calculation purposes, the effec- tive enclosure surface area A requires special explanation. The thermal output dissipated by the enclosure not only depends on its actual surface area; the installation type of the enclosure also plays a decisive role. An enclosure which stands in a room unobstructed on all sides may dissipate more heat than one sited against a wall or in a niche. For this reason, there are precise specifications on how to calculate the effective enclosure surface area depending on the type of installation site. The formulae for calculating A are specified in DIN 57 660, part 500 and IEC 890 (see table below). Enclosure installation type to IEC 890 Single enclosure, free-standing on all sides Single enclosure for wall mounting First or last enclosure in a suite, free-standing First or last enclosure in a suite, for wall mounting Enclosure within a suite, free-standing Enclosure within a suite, for wall mounting Enclosure within a suite, for wall mounting, covered roof surfaces Installation type to IEC 890 Formula for calculating A [m2] A = 1.8 x H x (W + D) + 1.4 x W x D A = 1.4 x W x (H + D) + 1.8 x D x H A = 1.4 x D x (H + W) + 1.8 x W x H A = 1.4 x H x (W + D) + 1.4 x W x D A = 1.8 x W x H + 1.4 x W x D + D x H A = 1.4 x W x (H + D) + D x H A = 1.4 x W x H + 0.7 x W x D + D x H A = Effective enclosure surface area W = Enclosure width [m] H = Enclosure height [m] D = Enclosure depth [m]
  • 36. Project planning General information 34 Rittal System Climate Control Projectplanning Calculation basis for enclosure climate control In natural convection, heat loss is dissipated to the outside via the enclosure panels. The prerequisite for this is that the ambient temperature must be lower than the temperature inside the enclosure. The maximum temperature increase (ΔT)max. which may occur inside an enclosure compared with the ambient air is calculated as follows: Note: If the heat loss inside the enclosure is not known, this basic formula can be used to calculate actual heat loss, by measuring the ambient temperature Tu and the en- closure internal temperature Ti QV = Heat loss installed in the enclosure [W] QS = Heat emitted by the enclosure surface [W] QS > 0: Radiation (Ti > Tu) QS < 0: Irradiation (Ti < Tu) QE = Required cooling output of an enclosure cooling unit [W] QH = Required thermal output of an enclosure heater [W] qw = Specific thermal output of a heat exchanger [W/K] V = Required volumetric air flow of a fan-and-filter unit to maintain the maximum permissible temperature difference between the extracted air and the emitted air [m3/h] ΔT = Ti – Tu = Max. admissible temperature difference [K] A = Effective, heat loss-dissipating enclosure surface area to IEC 890 [m2] k = Heat transfer coefficient [W/m2K] for sheet steel k = 5.5 W/m2K . . . . . . . (ΔT)max. = QV . k ⅐ A QS = A ⅐ k ⅐ ΔT (watts) . Project planning software Rittal Therm Make calculation even easier and faster by using our project planning software Rittal Therm. Model No. see page 195. EPLAN Cabinet Tool for the planning of enclosures and defining data for climate control calculations. Order information see page 195. Interactive performance diagrams Interactive performance diagrams may be found on the Internet at www.rittal.com on the respective component data sheets in the “Downloads” section, under the heading “Characteristic curve”. Enter your required interior temperature and the maximum exterior temperature in the relevant boxes, then click on “Calculate”. The heat loss that may be dissipated under these conditions will be displayed.
  • 37. Fan-and-filter units, air/air heat exchangers Project planning 35Rittal System Climate Control Projectplanning Fan-and-filter units The following applies when calculating the volumetric air flow: Performance diagram SK 3325. . . . f = 3.1 m3 ⅐ K/Wh at h = ( 0 to 100) f = 3.2 m3 ⅐ K/Wh at h = (100 to 250) f = 3.3 m3 ⅐ K/Wh at h = (250 to 500) f = 3.4 m3 ⅐ K/Wh at h = (500 to 750) f = 3.5 m3 ⅐ K/Wh at h = (750 to 1000) f = Compensating factor h = Height above sea level [m] V . QV . 30 50 70 90 300 500700 10 20 40 60 80100 200 400 600800 100 200 300 400 500 600 800 1000 1500 2000 3000 2500 Δ T 40K Δ T 35K Δ T 30K Δ T 25K Δ T 20K Δ T 15K Δ T 10KΔ T 5K Selection diagram The styling of the vent louvres in Rittal fan-and-filter units guarantees exemplary stability of the air vol- umes in relation to pressure loss. The correct fan-and-filter unit has been chosen if the specified heat loss is dissipated whilst complying with the desired maximum enclosure internal temperature. V = Volumetric flow (m3/h) QV = Heat loss (W) . . 100 200 300 20 40 60 80 100 120 140 0 0 ΔPst V . 50 Hz 60 Hz V = Volumetric flow (m3/h) ΔPst = Stat. pressure difference (Pa) . V = f ⅐ QV ΔT . . Air/air heat exchangers Calculate the specific thermal output of the heat exchanger: Selection diagram Note: For ambient temperatures that are lower than the desired enclosure internal temperature, the use of air/air heat exchangers may be appropriate, particularly in cases where there are dust, oil and aggressive substances in the ambient air which must not be allowed to ingress the enclosure under any circumstances. ΔT = Temperature difference (K) QV = Heat loss (W) qw = Specific thermal output (W/K) A = Enclosure surface area to IEC 890 (m2) k = Heat transfer coefficient (W/m2 K) for sheet steel k = 5.5 W/m2 K qw ΔT A 5 010152025 30 40 50 60 70 10 30 50 70 0 2 4 6 8 10 12 3000 2000 1000 0 20 40 60 80 QV . . qw = QV – (A ⅐ ΔT ⅐ k) ΔT .
  • 38. Project planning Cooling units 36 Rittal System Climate Control Projectplanning Cooling units Condensation and dehumidification of enclosure air when using cooling units One unavoidable side-effect of using cooling units is the dehumidification of the enclosure’s interior air. As it cools down, part of the humidity contained in the air condenses on the evaporator coil. This condensate must be reliably discharged from the enclosure. The amount of condensate occurring depends on relative humidity, the air temperature inside the enclosure and on the evaporator coil, and the air volume present in the enclosure. The Mollier h-x diagram shows the water content of air depending on its temperature and relative air humidity. Mollier h-x diagram for calculating the water content of air. Pd T x 50 45 40 35 30 25 20 15 10 5 0 – 5 – 10 – 15 – 20 0 50 10 15 20 25 x2 x1 30 35 40 6030 45155 10 20 25 35 40 50 55 10% 20% 30% 40% 50% 60% 70% 80% 100% ➀ 90% Pd = Water vapour partial pressure (mbar) T = Air temperature (°C) x = Water content (g/kg dry air) ➀ = Relative humidity Practical tips In all situations where optimum operating temperatures are required inside an enclosure, even at high external temperatures, a Rittal enclosure cooling unit can provide the right solution. It is even possible to cool the interior temperature of the enclosure to well below the ambient temperature. The favourable aerodynamic arrangement of the air inlet and outlet openings in the internal and external circuits ensures optimum air circulation inside the enclosure. This sample calculation will show you a quick, time-saving method for calculating a cooling unit. For example: A cooling unit with a refrigeration output of 1500 watts commences operation with a temperature setting of Ti = 35°C. The relative ambient air humidity is 70 %. If air at 35°C is passed over the evaporator coil, the surface temperature of the evaporator coil (evaporation temperature of the refrigerant) is approximately 18°C. At the boundary layer adhering to the surface of the evaporator coil, water is deposited at the dew point. The difference Δx = x1 – x2 indicates how much condensation is incurred per kg of air with complete dehumidification. The leak-tightness of the enclosure has a decisive effect on the quantity of condensation. Enclosure door closed: Only the enclosure volume is dehumidified. Poorly sealed cable designs, damaged door seals and the attachment of display media to enclosure surfaces lead to increased rates of leakage in the enclosure. Hence, with a leakage rate of, say, 5 m3/h, a continuous condensate volume of up to 80 ml/h may occur. Summary: Enclosure cooling units should only operate with the door closed. ● Seal the enclosure on all sides. ● Use a door limit switch. ● Use TÜV-tested equipment. ● Only set the enclosure internal temperature as low as is actually needed. W = Water quantity in g V = Volume of the enclosure in m3 ρ = Density of air kg/m3 Δx = Difference of water content in g/kg dry air (from the Mollier h-x diagram) V = width ⅐ height ⅐ depth = 0.6 m ⅐ 2 m ⅐ 0.5 m V = 0.6 m3 W = V ⅐ ρ ⅐ Δx = 0.6 m3 ⅐ 1.2 kg/m3 ⅐ 11 g/kg W = 7.92 g 8 ml Calculate your required cooling output. The quantity of condensation is calculated from the following equation: QE = QV – k ⅐ A ⅐ ΔT . . W = V ⅐ ρ ⅐ Δx
  • 39. Air/water heat exchangers Project planning 37Rittal System Climate Control Projectplanning Air/water heat exchangers Calculate your required cooling output: e.g. performance diagram Air/water heat exchanger 1000 W TW Ti 5 250 10 15 20 25 30 500 750 1000 1250 1500 1750 QK . 45°C 35°C 25°C VW = 400 l/h VW = 200 l/h VW = 100 l/h . . . Tw = Water inlet temperature (°C) QK = Continuous useful cooling output (W) Ti = Enclosure internal temperature (°C) . Notes on water quality For safe operation of the equipment, it is essential to observe the VGB guidelines on cooling water (VGB-R 455 P). Cooling water must not contain any limescale deposits or loose debris; in other words, it should have a low level of hardness, particularly a low level of calcium hardness. For recooling within the plant, the calcium hardness should not be too high. On the other hand, however, the water should not be so soft that it attacks the operating materials. When recooling the cooling water, the salt content should not be allowed to increase excessively due to the evaporation of large quantities of water, since electrical conductivity increases as the concentration of dissolved substances rises, and the water thereby becomes more corrosive. For this reason, not only is it always necessary to add a corresponding quantity of fresh water, but also to remove part of the enriched water. Gypsiferous water is unsuitable for cooling purposes because it has a tendency to form boiler scale, which is particularly difficult to remove. Furthermore, cooling water should be free from iron and manganese, because otherwise deposits may occur which settle in the pipes and block them. At best, organic substances should only be present in small quantities, because otherwise sludge deposits and microbiological contamination may occur. Material of the water-carrying parts Hydrological data CuAl V4A1) pH value 7 – 8.5 6 – 9 Calcium hardness > 3 < 8° dH 1 – 12° dH Free carbonic acid 8 – 15 mg/dm3 1 – 100 mg/dm3 Accompanying carbonic acid 8 – 15 mg/dm3 free Aggressive carbonic acid 0 mg/dm3 0 – 400 mg/dm3 Sulphides free free Oxygen < 10 mg/dm3 < 10 mg/dm3 Chloride ions < 50 mg/dm3 < 200 mg/dm3 Sulphate ions < 250 mg/dm3 < 500 mg/dm3 Nitrates and nitrites < 10 mg/dm3 < 100 mg/dm3 COD < 7 mg/dm3 < 40 mg/dm3 Ammonia < 5 mg/dm3 < 20 mg/dm3 Iron < 0.2 mg/dm3 free Manganese < 0.2 mg/dm3 free Conductivity < 2200 μS/cm < 4000 μS/cm Residue on evaporation < 500 mg/dm3 < 200 mg/dm3 Potassium permanganate consumption < 25 mg/dm3 < 40 mg/dm3 Suspended matter < 3 mg/dm3 > 3 < 15 mg/dm3 partial current purification recommended > 15 mg/dm3 continuous purification recommended 1) The complete absence of corrosion under experimental conditions suggests that solutions with a significantly higher salt content and greater corrosion potential (such as seawater) may still be tolerated. QE = QV – k ⅐ A ⅐ ΔT . .
  • 40. Project planning Recooling systems/chillers 38 Rittal System Climate Control Projectplanning Recooling systems/chillers Recooling systems may be used in all situations where a high cooling load is required, e.g. in process and machine cooling, in media cooling or when dissipating heat loss from enclosures via air/water heat exchangers. Our project engineers will be happy to help you design a recooling system for your specific application area. An overview of the planning data required for this purpose can also be found on the Internet at www.rittal.com in the section on system climate control/process and machine cooling. Cooling water Preparation and maintenance of the water in recooling systems Depending on the type of installation to be cooled, certain requirements are placed on the cooling water with respect to purity. According to the level of contamination and the size and design of the recooling systems, a suitable process is used to prepare and/or maintain the water. The most common types of contamination and most frequently used techniques to eliminate them in industrial cooling are: Contamination of the water Procedure Mechanical contamination Filtering of water via – Mesh filter – Gravel filter – Cartridge filter – Precoated filter Excessive hardness Water softening via ion exchange Moderate content of mechanical contaminants and hardeners Addition of stabilisers and/or dispersing agents to the water Moderate content of chemical contaminants Addition of passifiers and/or inhibitors to the water Biological contaminants, slime bacteria and algae Addition of biocides to the water Form for designing recooling systems Simply tick the type of system, and select or enter the criteria to suit your requirements. Please also include your name, company and address. Once you have completed the form, you can generate a PDF to print out or send via e-mail as an enquiry. The form for the design of recooling systems may be found on the Internet at: www.rittal.com –> Products –> System climate control –> Product portfolio –> Process and machine cooling –> Recooling systems –> Form for designing recooling systems
  • 41. Enclosure heaters Project planning 39Rittal System Climate Control Projectplanning Enclosure heaters The required thermal output is calculated from: Heating performance diagram QH = Thermal output (W) A = Enclosure surface area to IEC 890 (m2) ΔT = Temperature difference (K) Based on: Interior siting, static air, heat transfer coefficient k = 5.5 W/m2 K For exterior siting (moving air): Double the determined thermal output A ΔT 1 1.5 2 3 4 5 6 8 10 15 30 50 150 300 50010 20 40 60 80 100 200 20 30 2 5 7.5 10 15 QH . . QH = A ⅐ ΔT ⅐ k .
  • 42.
  • 43. 41Rittal System Climate Control Coolingwithambientair Fan-and-filter units from page 42 Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . 20/55 m3/h. . . . . . . . 44 Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 105/180 m3/h. . . . . . . . 45 Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . . . . .230 m3/h. . . . . . . . 46 Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 550/700 m3/h. . . . . . . . 47 Ⅲ Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . . 20 – 105 m3/h. . . . . . . . 48 Ⅲ Ⅲ Ⅲ Fan-and-filter units . . . . . . . . . . . . . . . . . . . . . . . 180 – 700 m3/h. . . . . . . . 49 Rack-mounted fans from page 50 Ⅲ Ⅲ for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . 320/480 m3/h. . . . . . . . 52 Tangential fans from page 50 Ⅲ Ⅲ for 482.6 mm (19˝) . . . . . . . . . . . . . . . . . . . . . . . . . . . .320 m3/h. . . . . . . . 53 Fan systems from page 50 Ⅲ Ⅲ RTT roof-mounted fan and vent attachment. . . . . 400/800 m3/h. . . . . . . . 54 Ⅲ Ⅲ Roof-mounted fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . .360 m3/h. . . . . . . . 54 Ⅲ Roof-mounted fan for the office sector. . . . . . . . . . . 1500 m3/h. . . . . . . . 55 Ⅲ Enclosure internal fan . . . . . . . . . . . . . . . . . . . . . . . . .160 m3/h. . . . . . . . 55 Ⅲ Fan mounting plate. . . . . . . . . . . . . . . . . . . . . . . . . . . 180 m3/h. . . . . . . . 56 Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . 108/184 m3/h. . . . . . . . 56 Ⅲ Fan mounting plate DC . . . . . . . . . . . . . . . . . . . . . . . 990 m3/h. . . . . . . . 57 Ⅲ Fan roof, modular, two-piece . . . . . . . . . . . . . . . . . . . .180 m3/h. . . . . . . . 58 Ⅲ Fan unit, active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 160 m3/h. . . . . . . . 58 Ⅲ Ⅲ Door-mounted fan . . . . . . . . . . . . . . . . . . . . . . . . . . . .600 m3/h. . . . . . . . 59 Ⅲ Fan expansion kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . .300 m3/h. . . . . . . . 59 With EMC shielding Interchangeable airflow direction Standardised installation Passive ventilation 482.6 mm (19˝) installation Cooling with ambient air Air/air heat exchangers from page 60 Ⅲ Ⅲ Ⅲ Wall-mounted . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12/62 W/K. . . . . . . . 62 Ⅲ Ⅲ Wall-mounted with controller . . . . . . . . . . . . . . . 17.5 to 90 W/K. . . . . . . . 63 Ⅲ Ⅲ Wall-mounted, railway-compatible version . . . . . .27 to 98 W/K. . . . . . . . 64 Ⅲ Roof-mounted. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66 W/K. . . . . . . . 65 Standardised installation Suitable for command panels Wall-mounted Roof-mounted 24 V DC and 110 V DC
  • 44. 42 Rittal System Climate Control Fan-and-filterunits Fan-and-filter units Fan-and-filter units are ideal for dissipating heat loads cost-effectively. The prerequisite is that the ambient air must be relatively clean with a temperature below the desired enclosure internal temperature. The entire range of fan-and-filter units is now also available with EMC shielding and all required rated voltages.
  • 45. 43Rittal System Climate Control Fan-and-filterunits Aesthetics and function Typical of the Rittal fan-and-filter unit design is the extremely low build height. The super-slimline vent grille guarantees optimum air throughput with low noise generation. Combined with the technical features, Rittal fan-and- filter units meet all application requirements. Benefits at a glance ● Air throughput from 20 m3/h to 700 m3/h ● Super-fast assembly ● IP 54 as standard ● Air flow direction may be reversed from draw-in (default setting) to extracting ● All fans also available with EMC shielding ● Minimal installation depth ● Fan also bayable Important ● The prescribed heat loss and the maximum anticipated ambient temperature define the required volumetric flow ● Always use the fan-and-filter units and outlet filters together Tips and tricks Applications see page 198 Selection criteria see page 199 Assembly see page 200 Application diversity and functions Particularly for applications in the food industry, the hose-proof hood prevents the ingress of damp. The protection category of IP 56 is achieved in conjunction with filter mats. Not always full power! At lower ambient temperatures, the air throughput may be reduced. By adapting the fan-and-filter speed to match the temperature using a controller, noise generation is reduced. Also available with EMC shielding All fan-and-filter units and outlet filters are alternatively available with EMC shielding. The required conductive connection is achieved via a metallic coating on the fan- and-filter unit housing and a special sealing frame. Fast assembly Super-fast clip-on mounting This guarantees fast, completely secure attachment of the fan-and-filter unit. The prerequisites for protection category IP 54 are met as standard. Screws are not required. Removal of the louvred grille, like- wise without any screws, means that filter mat changes can be achieved in next to no time. Draw-in or extract? The air direction may be quickly reversed from draw-in (default setting) to extracting. Simply rotate the fan through 180°.
  • 46. Fan-and-filter units Air throughput 20/55 m3/h 44 Rittal System Climate Control Fan-and-filterunits H2 B2 T2 B1 T1 H1 B = Width T = Depth Supply includes: Fan-and-filter units ready for installation, including filter mats. German registered design no. M 93 04 846 Approvals, see page 272. Performance diagrams, available on the Internet. Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195 Model No. SK fan-and-filter unit 3321.107 3321.117 3321.027 3321.0471) 3322.107 3322.117 3322.027 3322.0471) Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC) Dimensions in mm B1/H1 116.5 148.5 B2/H2 92 + 0.82) 1242) T1 10 10.5 Max. installation depth mm T2 42 57 Air throughput, unimpeded air flow 20/25 m3/h 20 m3/h 55/66 m3/h 55 m3/h Air throughput with outlet filter including standard filter mat 1 x SK 3321.207: 15/18 m3/h 1 x SK 3322.207: 43/50 m3/h Axial fan Self-starting shaded pole motor DC motor Self-starting shaded pole motor DC motor Rated current max. 69 mA 58 mA 138 mA 115 mA 125 mA 90 mA 0.12 A 0.11 A 0.24 A 0.23 A 170 mA 90 mA Power 12.5 W/10.3 W 3.0 W 4.1 W 19.0 W/18.0 W 4.0 W 4.4 W Noise level 41/46 dB (A) 41 dB (A) 46/49 dB (A) 42 dB (A) Temperature range –10°C to +55°C Colour RAL 70353) Protection category to EN 60 529 IP 54 standard IP 56 when using a hose-proof hood Model No. SK outlet filter 3321.207 3322.207 Accessories Packs of Page Spare filter mats 5 3321.700 3322.700 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177 Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179 Hose-proof hood 1 3321.800 3322.800 193 1) Delivery times on request. 2) For metal thickness > 2.5 mm the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.
  • 47. Air throughput 105/180 m3/h Fan-and-filter units 45Rittal System Climate Control Fan-and-filterunits H2 B2 T2 B1 T1 H1 B = Width T = Depth Supply includes: Fan-and-filter units ready for installation, including filter mats. German registered design no. M 93 04 846 Approvals, see page 272. Performance diagrams, available on the Internet. Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195 Model No. SK fan-and-filter unit 3323.107 3323.117 3323.027 3323.0471) 3324.107 3324.117 3324.027 3324.0471) Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) 230, 50/60 115, 50/60 24 (DC) 48 (DC) Dimensions in mm B1/H1 204 255 B2/H2 1772) 2242) T1 12.5 12.5 Max. installation depth mm T2 82.5 105 Air throughput, unimpeded air flow 105/120 m3/h 105 m3/h 180/160 m3/h 180 m3/h Air throughput with outlet filter including standard filter mat 1 x SK 3323.207: 71/82 m3/h 2 x SK 3323.207: 85/98 m3/h 1 x SK 3325.207: 78/90 m3/h 1 x SK 3325.207: 115/95 m3/h 2 x SK 3325.207: 165/140 m3/h 1 x SK 3326.207: 155/130 m3/h Axial fan Self-starting shaded pole motor DC motor Self-starting shaded pole motor DC motor Rated current max. 0.12 A 0.11 A 0.24 A 0.23 A 170 mA 90 mA 0.19 A 0.20 A 0.38 A 0.40 A 0.3 A 0.34 A Power 19.0 W/18.0 W 4.0 W 4.3 W 30.0 W/35.0 W 7.2 W 14.0 W Noise level 46/49 dB (A) 42 dB (A) 52/48 dB (A) 52 dB (A) Temperature range –10°C to +55°C Colour RAL 70353) Protection category to EN 60 529 IP 54 standard IP 55 when using an additional fine filter mat IP 56 when using an additional fine filter mat and hose-proof hood Model No. SK outlet filter 3323.207 3325.207 Accessories Packs of Page Spare filter mats 5 3171.100 3172.100 191 Fine filter mats 5 3181.100 3182.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.024 – 3114.100 3114.115 3114.024 – 177 Speed control 1 3120.000 3120.115 – – 3120.000 3120.115 – – 179 Hose-proof hood 1 3323.800 3324.800 193 1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.
  • 48. Fan-and-filter units Air throughput 230 m3/h 46 Rittal System Climate Control Fan-and-filterunits H2 B2 T2 B1 T1 H1 B = Width T = Depth Supply includes: Fan-and-filter units ready for installation, including filter mats. German registered design no. M 93 04 846 Approvals, see page 272. Performance diagrams, available on the Internet. Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195 Model No. SK fan-and-filter unit 3325.107 3325.117 3325.027 3325.0471) Rated operating voltage V/Hz 230, 50/60 115, 50/60 24 (DC) 48 (DC) Dimensions in mm B1/H1 255 B2/H2 2242) T1 12.5 Max. installation depth mm T2 105 Air throughput, unimpeded air flow 230/265 m3/h 230 m3/h Air throughput with outlet filter including standard filter mat 1 x SK 3325.207: 170/205 m3/h 2 x SK 3325.207: 200/230 m3/h 1 x SK 3326.207: 190/215 m3/h Axial fan Self-starting shaded pole motor DC motor Rated current max. 0.28 A 0.24 A 0.53 A 0.49 A 0.59 A 0.31 A Power 41.0 W/38.0 W 14.0 W 15.0 W Noise level 54/56 dB (A) 54 dB (A) Temperature range –10°C to +55°C Colour RAL 70353) Protection category to EN 60 529 IP 54 standard IP 55 when using an additional fine filter mat IP 56 when using an additional fine filter mat and hose-proof hood Model No. SK outlet filter 3325.207 Accessories Packs of Page Spare filter mats 5 3172.100 191 Fine filter mats 5 3182.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.024 – 177 Speed control 1 3120.000 3120.115 – – 179 Hose-proof hood 1 3324.800 193 1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.
  • 49. Air throughput 550/700 m3/h Fan-and-filter units 47Rittal System Climate Control Fan-and-filterunits H2 B2 T2 B1 T1 H1 B = Width T = Depth Supply includes: Fan-and-filter units ready for installation, including filter mats. German registered design no. M 93 04 846 Approvals, see page 272. Performance diagrams, available on the Internet. Accessories Page 171 EMC-protected design Page 48 Configuration software Page 195 Model No. SK fan-and-filter unit 3326.107 3326.117 3327.107 3327.117 3327.147 Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 400/460, 3~, 50/60 Dimensions in mm B1/H1 323 B2/H2 2921) T1 12.5 Max. installation depth mm T2 129 145 Air throughput, unimpeded air flow 550/600 m3/h 700/720 m3/h Air throughput with outlet filter including standard filter mat 1 x SK 3326.207: 360/390 m3/h 2 x SK 3326.207: 440/495 m3/h 1 x SK 3326.207: 525/575 m3/h Axial fan Capacitor motor Rotary current motor Rated current max. 0.29 A 0.35 A 0.58 A 0.70 A 0.65 A 0.95 A 1.5 A 2.0 A 0.27 A 0.37 A Power 64.0 W/80.0 W 115.0 W/212.0 W 167.0 W/230.0 W 146.0 W/220.0 W Noise level 59/61 dB (A) 75/76 dB (A) Temperature range –10°C to +55°C Colour RAL 70352) Protection category to EN 60 529 IP 54 standard IP 55 when using an additional fine filter mat IP 56 when using an additional fine filter mat and hose-proof hood Model No. SK outlet filter 3326.207 Accessories Packs of Page Spare filter mats 5 3173.100 3327.700 191 Fine filter mats 5 3183.100 191 Thermostat 1 3110.000 – 178 Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 – 177 Speed control 1 3120.000 3120.115 3120.000 – – 179 Hose-proof hood 1 3326.800 193 1) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 2) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.
  • 50. Fan-and-filter units – EMC Air throughput 20 – 105 m3/h 48 Rittal System Climate Control Fan-and-filterunits–EMC H2 B2 T2 B1 T1 H1 B = Width T = Depth Supply includes: Complete fan-and-filter units ready for installation, including drilling template, filter mat and assembly parts. Approvals, see page 273. Performance diagrams, available on the Internet. Accessories Page 171 Configuration software Page 195 Model No. SK fan-and-filter unit 3321.607 3321.6171) 3322.607 3322.6171) 3323.607 3323.6171) Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 Dimensions in mm B1/H1 116.5 148.5 204 B2/H2 92 + 0.82) 1242) 1772) T1 10 10.5 12.5 Max. installation depth mm T2 42 57 82.5 Air throughput, unimpeded air flow 20/25 m3/h 55/66 m3/h 105/120 m3/h Air throughput with outlet filter including standard filter mat 1 x 3321.267: 15/18 m3/h 1 x 3322.267: 43/50 m3/h 2 x 3322.267: 48/55 m3/h 1 x 3323.267: 48/55 m3/h 1 x 3323.267: 71/82 m3/h 2 x 3323.267: 85/98 m3/h 1 x 3325.267: 78/90 m3/h Axial fan Self-starting shaded pole motor Rated current max. 69 mA/ 58 mA 138 mA/ 115 mA 0.12 A/ 0.11 A 0.24 A/ 0.23 A 0.12 A/ 0.11 A 0.24 A/ 0.23 A Power 12.5 W/10.3 W 19.0 W/18.0 W Noise level 41/46 dB (A) 46/49 dB (A) Temperature range –10°C to +55°C Colour RAL 70353) Protection category to EN 60 529 IP 54 standard Model No. SK outlet filter – EMC 3321.267 3322.267 3323.267 Accessories Packs of Page Spare filter mats 5 3321.700 3322.700 3171.100 191 Fine filter mats 5 – 3181.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177 Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179 Hose-proof hood 1 3321.800 3322.800 3323.800 193 1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.
  • 51. Air throughput 180 – 700 m3/h Fan-and-filter units – EMC 49Rittal System Climate Control Fan-and-filterunits–EMC H2 B2 T2 B1 T1 H1 B = Width T = Depth Supply includes: Complete fan-and-filter units ready for installation, including drilling template, filter mat and assembly parts. Approvals, see page 273. Performance diagrams, available on the Internet. Accessories Page 171 Configuration software Page 195 Model No. SK fan-and-filter unit 3324.607 3324.6171) 3325.607 3325.6171) 3326.607 3326.6171) 3327.607 3327.6171) Rated operating voltage V/Hz 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 Dimensions in mm B1/H1 255 323 B2/H2 2242) 2922) T1 12.5 12.5 Max. installation depth mm T2 105 129 145 Air throughput, unimpeded air flow 180/160 m3/h 230/265 m3/h 550/600 m3/h 700/720 m3/h Air throughput with outlet filter including standard filter mat 1 x 3325.267: 115/95 m3/h 2 x 3325.267: 165/140 m3/h 1 x 3326.267: 155/130 m3/h 1 x 3325.267: 170/205 m3/h 2 x 3325.267: 200/230 m3/h 1 x 3326.267: 190/215 m3/h 1 x 3325.267: 170/205 m3/h 2 x 3325.267: 200/230 m3/h 1 x 3326.267: 360/390 m3/h 1 x 3326.267: 525/575 m3/h Axial fan Self-starting shaded pole motor Capacitor motor Rated current max. 0.19 A/ 0.20 A 0.38 A/ 0.40 A 0.28 A/ 0.24 A 0.53 A/ 0.49 A 0.29 A/ 0.35 A 0.58 A/ 0.70 A 0.65 A/ 0.95 A 1.50 A/ 2.00 A Power 30.0 W/ 35.0 W 41.0 W/ 38.0 W 64.0 W/ 80.0 W 155.0 W/ 212.0 W 167.0 W/ 230.0 W Noise level 52/48 dB (A) 54/56 dB (A) 59/61 dB (A) 75/76 dB (A) Temperature range –10°C to +55°C Colour RAL 70353) Protection category to EN 60 529 IP 54 standard Model No. SK outlet filter – EMC 3325.267 3326.267 Accessories Packs of Page Spare filter mats 5 3172.100 3173.100 3327.700 191 Fine filter mats 5 3182.100 3183.100 191 Thermostat 1 3110.000 178 Temperature indicator 1 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 3114.115 177 Speed control 1 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 3120.000 3120.115 179 Hose-proof hood 1 3324.800 3326.800 193 1) Delivery times available on request. 2) For metal thickness > 2.5 mm, the cut-out B2/H2 must be 1 mm larger. 3) RAL 7032 on request. Special voltages available on request. We reserve the right to make technical modifications.
  • 52. 50 Rittal System Climate Control Rack-mounted/tangentialfans,fansystems Rack-mounted/tangential fans, fan systems All rack-mounted climate control components are fitted directly onto the 482.6 mm (19˝) mounting level for subracks. Positioning directly beneath the electronic components ensures effective cooling, and prevents the formation of hot-spots. Ready-to-use, wired modules equipped with fans for numerous Rittal enclosure system platforms offer effective air throughput and minimal assembly work. Fan roofs, door-mounted fans for server enclosures, internal fan mounting panels and enclosure internal fans are all available.
  • 53. 51Rittal System Climate Control Rack-mounted/tangentialfans,fansystems Benefits at a glance Rack-mounted/tangential fans ● Rapid installation on 482.6 mm (19˝) mounting levels ● Direct, effective dissipation of heat loss, thanks to positioning beneath the assemblies ● No externally mounted equipment to disrupt the aesthetic appearance of the enclosure Fan systems ● Fast assembly ● Targeted air routing to avoid hot-spots ● Perfect system integration Tips and tricks Applications see page 201 Rack-mounted fan module The rack-mounted fan slides into the guide frame like a drawer. Connectors on the rear ensure immediate contact. Installation options for the guide frame: Directly in the subrack, via two mounting brackets on the 482.6 mm (19˝) mounting angles. Ideal for avoiding hot-spots in fully populated enclosures. Tangential fans 320 m3/h air throughput, 2 U The high air throughput means that Rittal tangential fans are capable of dissipating large heat losses from the enclosure. The minimal noise generation of 52 dB creates a pleasant working environment. Front outlet grille 2 U for hot air outlet to the outside in the upper section of the enclosure. For the office sector: Roof-mounted fan Low noise generation and high performance for sensitive office areas. Unit consisting of TS roof plate and fan.
  • 54. Rack-mounted fans for 482.6 mm (19˝), air throughput 320/480 m3/h 52 Rittal System Climate Control Rack-mountedfans 426 482.6 (19˝) 206214 55 432 120 1HE 482.6 (19˝) 180200 73 410 100 1HE 1 2 Rack-mounted fan/Vario rack- mounted fan supply includes: Wired unit ready for connection, including terminal strip and assembly parts. Guide frame supply includes: Guide frame including connec- tor and fitted connection cable (3 m), bracket for optional attachment to the 482.6 mm (19˝) system, assembly parts. Also required: Remember to order the appropriate guide frame for your chosen application. Approvals, see page 273. Detailed drawing, see page 240. Performance diagrams, available on the Internet. Accessories Page 171 Configuration software Page 195 Rack-mounted fans Vario rack-mounted fans Model No. SK Model No. SK 2 fans Distance between axes 85 mm 3340.0241) 3340.1151) 3340.230 – – 3350.0241) 3350.1151) 3350.2301) – 3 fans Distance between axes 85 mm 3341.0241) 3341.115 3341.230 – 9769.0021)2) 3351.0241) 3351.1151) 3351.230 – 3 fans Distance between axes 105 mm 3342.024 3342.1151) 3342.230 3342.5002)3) – 3352.0241) 3352.1151) 3352.230 3352.5003) Rated operating voltage V 24 V (DC) 115 V (AC) 230 V (AC) 24 V (DC) 115 – 230 V (AC) 36 V (DC) up to 72 V (DC) 24 V (DC) 115 V (AC) 230 V (AC) 24 V (DC) 115 – 230 V (AC) Model No. SK matching guide frame – – – – – 3356.1001) 3355.100 3355.100 3357.100 Accessories Page Temperature indicator 230 V (AC) 714 3114.100 3114.115 3114.100 3114.024 – 3114.100 3114.115 3114.100 3114.024 Thermostat 715 3110.000 Speed control 716 3120.000 3120.115 3120.000 – – 3120.000 3120.115 3120.000 – 1 2 Technical specifications Model No. SK/CS 3340.230 3350.230 3340.115 3350.115 3340.024 3350.024 3341.230 3351.230 3342.230 3352.230 3341.115 3351.115 3342.115 3352.115 3341.024 3351.024 3342.024 3352.024 3342.5002) 3352.5002) 9769.002 Rated operating voltage V, Hz AC 230 V 50/60 Hz AC 115 V 50/60 Hz DC 24 V – AC 230 V 50/60 Hz AC 115 V 50/60 Hz DC 24 V – DC 24 V AC 115 – 230 V 50/60 Hz 36 V (DC) up to 72 V (DC) Rated current max. 0.24 A/ 0.22 A 0.46 A/ 0.46 A 0.49 A 0.36 A/ 0.33 A 0.69 A/ 0.69 A 0.74 A 0.85 A 0.28 A Pre-fuse T 6.0 A 6.0 A Number of fans 2 3 3 Air throughput, unimpeded air flow 320 m3/h 480 m3/h 250 m3/h Temperature range –10°C to +55°C –33°C to +55°C Noise level 51 dB (A) 52 dB (A) 51 dB (A) 51 dB (A) 52 dB (A) 51 dB (A) 52 dB (A) 1) Delivery times available on request. 2) Rack-mounted fan for metric mounting angles available on request. 3) Version with monitoring
  • 55. for 482.6 mm (19˝), air throughput 320 m3/h Tangential fans 53Rittal System Climate Control Tangentialfans 88 482.6 (19˝) 163 380 17 Supply includes: Fully assembled and wired unit, ready for connection, including filter mat. Approvals, see page 274. Detailed drawing, see page 240. Performance diagrams, available on the Internet. Accessories Page 171 Configuration software Page 195 Model No. SK 3145.000 3144.000 Rated operating voltage V/Hz 115, 50/60 230, 50/60 Dimensions in mm W H D 482.6 (19˝) 88 (2 U) 158 Air throughput, unimpeded air flow 320 m3/h Rated current max. 0.32 A 0.16 A Power 37 W Noise level 52 dB (A) Speed 2245 rpm–1 Temperature range –10°C to +55°C Maximum static pressure difference 65 – 70 Pa Accessories Packs of Page Temperature indicator 1 3114.115 3114.100 177 Thermostat 1 3110.000 178 Filter mats 5 3177.000 189 Front outlet grille 2 U 1 3176.000 193 Roof vent 1 3148.007 54 Speed control 1 3120.115 3120.000 179 Special voltages available on request. We reserve the right to make technical modifications.
  • 56. Fan systems 54 Rittal System Climate Control Fansystems RTT roof-mounted fan and vent attachment for TS The active roof-mounted fan and the passive vent attachment (TS 8801.380) integrate perfectly into the system-wide mounting concept of the Rittal TopTherm platform. They fit precisely onto the cut- outs of the small and medium performance cate- gory of TopTherm roof-mounted cooling units. Of course, they may also be mounted on any suffi- ciently large roof surface. TS roof plates with prepared mounting cut-outs are additionally available. Roof-mounted fan supply includes: Unit ready to connect with built-in radial fan, sealing material and assembly parts. Vent attachment: see page 182. Protection category: IP 43 to EN 60 529 Detailed drawing, see page 240. T B 290 500 370 550 125 Model No. SK 3149.410 3149.420 3149.440 3149.810 3149.820 3149.840 8801.380 Page Rated operating voltage V/Hz 115, 50/60 230, 50/60 400, 3~, 50/60 460, 3~, 60 115, 50/60 230, 50/60 400, 3~, 50/60 460, 3~, 60 Roof vent Air throughput, unimpeded air flow 400 m3/h 800 m3/h Without motor Required mounting cut-out W x D mm 475 x 260 490 x 390 Power consumption of fan 120 W/170 W 95 W/140 W 170 W/225 W 180 W/310 W Rated current of fan 1.1/1.6 A 0.55/0.88 A 0.35/0.35 A 1.5/2.2 A 0.75/1.1 A 0.35/0.55 A Temperature range –10°C to +55°C Noise level 68/69 dB (A) 69/70 dB (A) Weight 10 kg 11 kg 6 kg Colour shade RAL 7035 Accessories Roof plate 600 x 600 mm for TS 8 with cut-out 8801.300 8801.310 181 Roof plate 600 x 800 mm for TS 8 with cut-out 8801.320 8801.330 181 Roof plate 1200 x 600 mm for TS 8 with cut-out – 8801.350 181 Temperature indicator 3114.115 3114.100 – 3114.115 3114.100 – – 177 Speed control 3120.115 3120.100 – 3120.115 3120.100 – – 179 B = Width T = Depth Roof-mounted fan ● The roof-mounted fan is easily installed using 6 screws. The sealing tape supplied can be used to seal it against the enclosure. ● The attachment screws are invisible from the outside. ● The roof-mounted fan casing has a large air outlet surface and labyrinth air ducting. Protection category: IP 43 to EN 60 529. By additionally installing the filter holder with filter mat SK 3175.000, with roof vent SK 3148.007 a protection category of IP 44 is achieved. Fully wired unit ready for connection with built-in radial fan, sealing material and assembly parts, connection cable (3 m), drilling template. Accessories: Filter holder, see page 194. Detailed drawing, see page 240. 50 265 345 340 420 Model No. SK 3149.007 3169.007 3148.007 Rated operating voltage V/Hz 230, 50/60 115, 50/60 Without fan motor Air throughput 360 m3/h Rated current max. 0.2 A 0.55 A Power consumption 42 W 65 W Temperature range –10°C to +60°C Noise level 53 dB (A) Weight 7.8 kg Colour1) RAL 7035, textured enamel 1) To order the version in RAL 7032, please add extension .000 to the Model No. Special voltages available on request. We reserve the right to make technical modifications.
  • 57. Fan systems 55Rittal System Climate Control Fansystems Roof-mounted fan for TS/FR(i) for the office sector This new roof ventilation concept offers a wealth of performance, assembly and cost benefits associated with the use of integrated ventilation systems. This roof-mounted fan may be ordered with and without a roof plate. Another outstanding feature is the enormous volumetric flow in propor- tion to exceptionally low noise levels, making it ideal for use in sensitive office areas. Technical specifications: ● Fitted onto a roof plate based on TS. ● Easy assembly; mounting cut-outs have been provided. ● Radial fan. Supply includes: Fully wired ready for connection, including assembly parts. T H B 511 511 410 450450 410 H 13.5 T B 20 2424 225 205 410 450 Ø 6.5(8x) Model No. SK 3164.610 3164.620 3164.810 3164.820 3164.115 3164.230 Page Rated operating voltage V/Hz 115, 50/60 230, 50/60 115, 50/60 230, 50/60 115, 50/60 230, 50/60 Air throughput (unimpeded air flow) 1500 m3/h1) Version With roof plate without roof plate Dimensions in mm W H D 800 240 800 800 240 900 511 227 511 Power consumption 68 W/81 W Rated current 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 A 0.6 A/0.7 A 0.3 A/0.35 A Radial fan – Noise level 40 dB (A) Temperature range +20°C to +55°C Colour RAL 7035 Accessories Temperature indicator in 1 U patch panel 7109.035 177 Temperature indicator 3114.115 3114.100 3114.115 3114.100 3114.115 3114.100 177 Thermostat 3110.000 178 1) 800 m3/h at 40 Pa counterpressure using two integrated louvres, type DK 7825.801, in the enclosure base/plinth. Special voltages available on request. We reserve the right to make technical modifications. Mounting cut-out only required for fans wtihout roof plate B = Width T = Depth Enclosure internal fan for TS To prevent hot-spots and support the air routing of active enclosure climate control components. Adjustable in two axes. Attached to the TS 8 frame section. Several fans may be cascaded using the quick-release clamping strip. Supply includes: Fully wired unit ready for connection with radial fan and lockable swivel device, as well as assembly parts. 213.5 100 120 Ø6(2x) Air through- put (unim- peded air flow) Power consump- tion W Rated current A Rated voltage V, Hz Model No. SK 160 m3/h 19.0/18.0 0.12/0.11 230, 50/60 3108.100 160 m3/h 19.0/18.0 0.24/0.23 115, 50/60 3108.115 160 m3/h 3.5 0.15 24 V (DC) 3108.024
  • 58. Fan systems 56 Rittal System Climate Control Fansystems Fan mounting plate for TS The fan mounting plate may be retro-fitted in all TS 8 network enclosures from above. The plate is mounted at the front of the enclosure, whilst the rear section is left free for cable entry. A rubber cable clamp strip is supplied loose for optional sealing at the rear. The following combinations are also possible: ● Solid roof plate raised with 20 or 50 mm roof spacers. ● Roof plate for cable entry raised with 20 or 50 mm roof spacers. ● Vented roof plate for cable entry. In conjunction with the large swing frame, usage is only possible from an enclosure depth of 800 mm, in conjunction with a roof plate for cable entry from 900 mm. Note: Not suitable for crane transportation. Not suitable for combination with 482.6 mm (19˝) mounting frame. The air throughput can be increased with the fan expansion kit DK 7980.000. Technical specifications for one fan: Rated operating voltage: 230 V Power consumption: 15/14 W at 50/60 Hz Air throughput (unimpeded air flow): 160/180 m3/h, 50/60 Hz Temperature range: –10°C to +55°C Technical specifications of thermostat: Rated operating voltage: 250 V Temperature range: +5°C to +55°C Colour: RAL 7035 Supply includes: 2 fans, 2/4 cut-outs to extend to 4/6 fans, thermostat, rubber cable clamp strip. Thermostat and fan fully wired to connection cable (2.5 m). Accessories: Fan expansion kit, see page 56. Rubber cable clamp strip SZ 2573.000 for sealing at the sides and targeted air routing when bayed, see Cat. 32 page 1047. 385/585 525/725 40 For enclosures Number of fans Max. number of fans Model No. DKWidth mm Depth mm 600 600 2 4 7966.035 600 800 900 1000 1200 2 6 7968.035 800 600 2 6 7986.035 800 800 900 1000 1200 2 6 7988.035 Fan expansion kit For retro-fitting various fan units or to supplement the fan mounting plate and modular fan roof. Technical specifications DK 7980.000: Rated operating voltage: 230 V~ Power consumption: 15/14 W at 50/60 Hz Air throughput (unimpeded air flow): 160/180 m3/h, 50/60 Hz Noise level (unimpeded air flow): 37 dB (A) Temperature range: –10°C to +55°C Technical specifications DK 7980.100: Rated operating voltage: 230 V~ Power consumption: 14/12 W at 50/60 Hz Air throughput (unimpeded air flow): 108/120 m3/h, 50/60 Hz Noise level (unimpeded air flow): 34 dB (A) Temperature range: –20°C to +70°C Technical specifications DK 7980.148: Rated operating voltage: 48 V (DC) Power consumption: 7.7 W Air throughput (unimpeded air flow): 184 m3/h Noise level (unimpeded air flow): 43 dB (A) Temperature range: –20°C to +70°C Supply includes: Fan, including assembly parts and connection cable (0.61 m). Dimensions W x H x D mm Packs of Model No. DK 119 x 119 x 38 1 set 7980.000 119 x 119 x 25 1 set 7980.100 119 x 119 x 25 1 set 7980.148
  • 59. Fan systems 57Rittal System Climate Control Fansystems Cover plates for fan panels for FlatBox To cover unused fan panels when using fans in the FlatBox. Material: Sheet steel Surface finish: Powder coated in RAL 7035 Supply includes: Assembly parts. Packs of Model No. DK 6 7507.760 Fan mounting plate DC for TS Super-low noise thanks to FCS speed control, fully fitted Suitable for TS 8 enclosures with a raised roof (> 20 mm) or TS 8 roof plate, vented. The fan mounting plate may be used as an alternative to fan mounting plate 7988.035. It is installed from above. Cable entry is prepared in the rear section of the plate. Not suitable for combination with 482.6 mm (19˝) mounting frame. Advantages of the DC fan mounting plate with FCS technology: ● Super-low noise thanks to speed control. ● All fans are monitored for failure. ● High air throughput thanks to DC technology (unimpeded airflow 6 x 175 m3/h = 990 m3/h). ● EMC compatibility. ● Temperature monitoring and control. ● High level of safety (low safety voltage with 24 V DC power supply). ● Visual and acoustic alarm messages, plus relay alarm output. ● Freely selectable installation location for the FCS control unit (included with the supply of the fan mounting plate, in 482.6 mm (19˝) with 7320.440 or on the frame with 7320.450). ● Suitable for international use, thanks to wide- range power supply 100 – 240 V AC and socket to IEC 320. ● Pre-configured. ● Network-compatible via CMC-TC processing unit II 7320.100 (all relevant data such as temperature etc. are displayed in the web browser, or alarms are sent in the form of an SNMP trap). Technical specifications: Power pack rated voltage: 100 – 240 V AC, 50/60 Hz Power supply rated current: max. 1.5 A Power supply secondary range: 24 V DC, 3 A Temperature range: +5°C to +40°C Total air throughput (unimpeded air flow): 6 x 175 m3/h = 990 m3/h Technical specifications for one fan: Rated voltage: 24 V DC Rated current: max. 0.3 A Air throughput (unimpeded air flow): 175 m3/h Speed: 2650 rpm Noise level: up to 45 dB (A) at maximum speed activation Also required: Connection cable 230/115 V. Example D version, Model No. 7200.210, see Cat. 32, page 818. Accessories: 1 U mounting unit, Model No. 7320.440, see Cat. 32, page 821. Mounting module, Model No. 7320.450, see Cat. 32, page 821. For enclosures width mm For enclosures depth mm Number of DC fans Model No. DK 800 800 900 1000 6 7858.488 Note: For more information on the FCS system, see Cat. 32, page 813.
  • 60. Fan systems 58 Rittal System Climate Control Fansystems Fan roof, modular, two-piece for TS, FR(i) The modular roof plate consists of individual com- ponents and can be configured for the ventilation of the enclosures in various ways. The modules consist of: Roof plate, two-piece with cut-out For fan mounting and cable entry at the rear via a sliding angular bracket with rubber cable clamp strip. Replacing the existing roof plate. The two- piece design allows convenient retrofitting of cables at any time. Cover plate To cover the cut-out, optionally solid or vented options. The top-mounted cover plate may be raised for extra air throughput using the supplied spacers. Fan insert For active ventilation: A fully pre-wired fan tray including 2.5 m connec- tion cable, with two fan motors and additional cut- outs. The air throughput may be increased with a fan expansion kit. Material: Sheet steel, spray finished Colour: RAL 7035 Technical specifications for one fan: Rated operating voltage: 230 V Power consumption: 15/14 W at 50/60 Hz Air throughput (unimpeded air flow): 160/180 m3/h at 50/60 Hz Temperature range: –10°C to +55°C Detailed drawing, see page 241. Accessories: Fan expansion kit DK 7980.000, see page 56. Thermostat SK 3110.000, see page 178. Speed control SK 3120.000, see page 179. 1 2 1 2 3 4 5 For enclosures Model No. DK Fan insertRoof plate FR(i) Roof plate TS Cover plate Width mm Depth mm With cut-out With cut-out Solid Vented Fan insert Fans pre-wired Maximum no. of fans 600 600 7856.3661) 7826.366 2102.1801) 2102.400 2102.320 2 2 600 800 7856.3681) 7826.368 2102.1901) 2102.410 2102.490 2 6 600 900 – 7826.369 2102.1901) 2102.410 2102.490 2 6 600 1000 7856.3601) 7826.360 2102.1901) 2102.410 2102.490 2 6 600 1200 7856.3621) 7826.362 2102.1901) 2102.410 2102.490 2 6 800 600 – 7826.486 7885.100 7885.200 7885.000 2 3 800 800 7856.3881) 7826.488 7886.100 7886.200 7886.000 2 8 800 900 – 7826.489 7886.100 7886.200 7886.000 2 8 800 1000 7856.3801) 7826.480 7886.100 7886.200 7886.000 2 8 800 1200 – 7826.382 7886.100 7886.200 7886.000 2 8 1) Delivery times available on request. Design panel FR(i) already included with the supply of the standard roof plate. 1 2 4 5 3 Fan unit, active for TE For active ventilation of the TE 7000. The fan unit is installed in the prepunched cut-out. An additional fan may optionally be integrated. Supply includes: Fan unit including assembly parts, 2 fans, 1 thermostat and open connection cable. Technical specifications for one fan: Fan extension kit, 7980.000, see page 56. Technical specifications of thermostat: Rated operating voltage: 250 V Temperature range: +5°C to +55°C Note: Connection via distributor box or country-specific connector. Accessories: Fan expansion kit, see page 56. For enclosures W x D mm Number of pre-wired fans Possible number of fans Model No. TE All dimensions 2 3 7000.670 Active kit for TE consisting of fan unit including thermostat, com- plete, wired ready for connection, socket strip (DK 7000.630) for up to 8 earthing pin plugs, version D and connection cable (DK 7200.210). Packs of Model No. DK 1 set 7000.680
  • 61. Fan systems 59Rittal System Climate Control Fansystems Door-mounted fan for server enclosures TS, TE Specifically for installing in perforated doors. The growing packaging density in data communications and network enclosures make active, direct ventilation of the enclosure indispen- sable. The door-mounted fan, which is attached to the rear or front door, supports horizontal air rout- ing via the servers and therefore facilitates faster heat dissipation from active components. Technical specifications: ● Standard assembly with two fans. ● Air throughput, unimpeded air flow 600 m3/h. ● By adding two fan extension kits, the air throughput is increased to 1200 m3/h. ● The direction of air flow is easily reversed by rotating the fan. ● Several units may be positioned in a cascade arrangement. ● Simple mounting on the tubular door frame. Supply includes: Wired ready for connection with 2.5 m connection cable, including assembly parts. Accessories: Fan expansion kit, see page 59. Note: Only for mounting on the tubular door frame! Door configuration for installation in 2 and 4-door ISP racks available on request. B T H 552 27 230 (350) Ø 4.5 475 (675) 493 (693) 606 9 59.5 5 Model No. SK 3165.6241) 3165.6481) 3165.6151) 3165.630 3165.8241) 3165.8481) 3165.8151) 3165.830 Page Rated operating voltage V/Hz 24 (DC) 48 (DC) 115, 50/60 230, 50/60 24 (DC) 48 (DC) 115, 50/60 230, 50/60 Air throughput (unimpeded air flow) 600 m3/h Power consumption for two fans 40 W 48 W 70 W/64 W 70 W/70 W 40 W 48 W 70 W/64 W 70 W/70 W Rated current of fan 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A 1.5 A 1.0 A 0.76 A/0.72 A 0.38 A/0.36 A Dimensions in mm W H D 493 606 64.5 693 606 64.5 For doors with width (mm) 600 800 Noise level 55 dB (A) Temperature range +20°C to +55°C Colour RAL 7035 Accessories Temperature indicator 3114.024 – 3114.115 3114.100 3114.024 – 3114.115 3114.100 177 Thermostat 3110.000 178 1) Delivery times on request. Special voltages available on request. Technical modifications reserved. B = Width T = Depth Fan expansion kit for door-mounted fan To increase the air throughput of the door- mounted fan. To fit door-mounted fan Model No. SK SK 3165.624, SK 3165.824 3165.024 SK 3165.648, SK 3165.848 3165.048 SK 3165.615, SK 3165.815 3165.115 SK 3165.630, SK 3165.830 3165.230
  • 62. 60 Rittal System Climate Control Air/airheatexchangers Air/air heat exchangers The requirement for using air/air heat exchangers is that the ambient temperature must be below the required enclosure internal temperature. Dust and any aggressive ambient air is unable to ingress the enclosure interior, thanks to the two separate air circuits.
  • 63. 61Rittal System Climate Control Air/airheatexchangers Platform strategy/ installation Identical installation cut-outs for various output classes. Easily retrofitted Thanks to the low weight, simple assembly cut-outs and problem- free attachment of the heat exchangers, a cabinet or enclosure is easily retro-fitted. Benefits at a glance ● Specific thermal output from 17.5 W/K to 90 W/K ● External and internal circuit may be controlled separately ● Mounting cut-outs and enclosure dimensions identical to TopTherm wall-mounted cooling units ● Suitable for external and internal mounting ● Top design identical to TopTherm wall- mounted cooling units Important The temperature difference between the room temperature and enclosure internal temperature will have a decisive effect on the heat loss that may be dissipated. Tips and tricks Applications see page 202 Selection criteria see page 203 Assembly see page 204 Air routing see page 205 Electrical connection and control see page 206 Safety High protection category Thanks to the seamlessly sealed heat exchanger module, a protection category of IP 54 to EN 60 529 is achieved. High load capacity The motors of the fans are equipped with thermal winding protection. Top quality: Guaranteed protection for your electronics. All devices in the Rittal TopTherm-Plus series are tested in accordance with the interna- tionally valid approvals (GS, UL). Simple maintenance The heat exchanger unit is very easily removed and cleaned. The cleverly thought- out structure enables fast, economical main- tenance.
  • 64. Air/air heat exchangers Wall-mounted 62 Rittal System Climate Control Air/airheatexchangers T H B B H T B H T Supply includes: Fully wired unit ready for con- nection. Detailed drawing, see page 241. Performance diagrams, available on the Internet. SK 3125.800 Compact wall-mounted air/air heat exchanger. Ideal for small enclosures and command panels. Suitable for external and inter- nal mounting. SK 3129.800 Super-slimline air/air heat exchangers. Ideal for external door mounting. Model No. SK 3125.800 3129.800 Rated operating voltage V/Hz 230, 1~, 50/60 Dimensions in mm W H D 200 400 146 400 1360 110 Specific thermal output 12 W/K 62 W/K Fans 2 per heat exchanger Max. rated current per fan 0.11 A/0.13 A 0.45 A/0.55 A Pre-fuse T 2.0 A Output per fan 25 W/30 W 100 W/130 W Air throughput of fans (unimpeded air flow) External circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/h Internal circuit 265 m3/h / 315 m3/h 860 m3/h / 900 m3/h Temperature range –5°C to +55°C Type of connection Connection cable Weight 8 kg 30 kg Colour RAL 7035 Protection category to EN 60 529 Internal circuit IP 54 Accessories Packs of Page Thermostat 1 3110.000 178 Temperature display 1 3114.100 177 Speed control 1 3120.000 179 Special voltages available on request. We reserve the right to make technical modifications. Accessories Page 171 Recooling systems From page 116 Configuration software Page 195 B = Width T = Depth
  • 65. Wall-mounted with controller Air/air heat exchangers 63Rittal System Climate Control Air/airheatexchangers T2 50 950 T1 400 108 42 550 150 280 1580 215 400 165 50 T = Depth ● With controller and digital temperature display ● Floating fault signal contact in case of overtemperature Supply includes: Fully wired unit ready for con- nection. Approvals, see page 276. Detailed drawing, see page 244. Performance diagrams, available on the Internet. Model No. SK 230 V 3126.100 3127.100 3128.100 3129.100 3130.100 115 V 3126.115 3127.115 3128.115 3129.115 3130.115 Rated operating voltage V/Hz 230/115, 1~, 50/60 Dimensions in mm W H T1 T2 280 550 150 – 400 950 205 155 400 950 225 175 400 1580 215 – Specific thermal output 17.5 W/K 30 W/K 45 W/K 60 W/K 90 W/K Fans 2 per heat exchanger Max. rated current per fan 230 V 0.11 A/0.13 A 0.28 A/0.34 A 0.3 A/0.4 A 0.38 A/0.4 A 0.67 A/0.88 A 115 V 0.23 A/0.25 A 0.55 A/0.7 A 0.6 A/0.8 A 0.65 A/0.8 A 1.3 A/1.8 A Pre-fuse T 2.0 A 4.0 A Output per fan 23 W/27 W 60 W/75 W 70 W/90 W 85 W/90 W 150 W/200 W Air throughput of fans (unimpeded air flow) External circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/h Internal circuit 265 m3/h / 315 m3/h 480 m3/h / 525 m3/h 600 m3/h / 625 m3/h 860 m3/h / 900 m3/h 850 m3/h / 945 m3/h Temperature range –5°C to +55°C Type of connection Plug-in terminal strip Weight 10 kg 18 kg 19 kg 21 kg 34 kg Colour RAL 7035 Protection category to EN 60 529 Internal circuit IP 54 Accessories Packs of Page Filter mats 3 3286.300 3286.400 189 Metal filters 1 3286.310 3286.410 190 Special voltages available on request. We reserve the right to make technical modifications. Accessories Page 171 Recooling systems From page 116 Configuration software Page 195