Three-phase transformer Three-Phase Power  For a transformer the power-factor of the load is not known, therefore the formula becomes, Three-Phase Volt-Amps For a Power Transformer  Therefore the Secondary Full Load Current Prospective fault current
Example 2 Consider a 300 kVA, 11 kV/415-240 V three-phase distribution transformer with a percentage impedance of 5% Full Load Current   = 417.4 A Prospective fault current

2.5.3three Phase

  • 1.
    Three-phase transformer Three-PhasePower For a transformer the power-factor of the load is not known, therefore the formula becomes, Three-Phase Volt-Amps For a Power Transformer Therefore the Secondary Full Load Current Prospective fault current
  • 2.
    Example 2 Considera 300 kVA, 11 kV/415-240 V three-phase distribution transformer with a percentage impedance of 5% Full Load Current = 417.4 A Prospective fault current