Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
1078 5690.ppt
1. Chapter 8: The Cooling Load
Cooling load is the rate at which energy must be removed from a space to
maintain the temperature and humidity at the design values.
Cooling load is determined by internal and external heat gains as well as
structure variable heat storage, all of which are transient in nature
Instantaneous heat gain
is the heat received by
the space being
conditioned.
Instantaneous cooling
load is the heat gain by
the air in the space
2. The Cooling Load
This figure is for solar heat gain (TSHG:
total solar heat gain) and the associated
cooling load. A heavy weight (HW)
construction has the benefit of reducing
the peak cooling load, which reduces the
size of required coolers.
Cooling load attributed to
lights. Actual cooling load will
approach the heat gain if lights
remain on for a sufficiently
long time.
5. Internal Heat gain -People Adjusted heat gain is a nominal value,
based on the normal percentage of
men, women, and children for the
application listed.
20. Design Condition
• Indoor design conditions: For average jobs in the United States and
Canada, a condition of 75 F or 24 C dry bulb temperature and relative
humidity of 50% is typical when activity and dress of the occupants are
light.
• Outdoor design temperatures would depend on the selection of the
high end temperatures that equal or exceed a percentage of the hours that
occurred during a year. A smaller percentage may result in a greater excess
cooling capacity to be installed.
(Table B-1 (1a: English/1b: SI): MWS = mean coincident wind speed,
MWD = mean coincident wind direction, MWB = mean coincident wet
bulb temperature, MDB = mean coincident dry bulb temperature, HR:
humidity ratio, in grains of water per pound of air (7000 grains equal 1
pound), Range = daily range of db temperature (the difference between the
average maximum and average minimum for the warmest month).
21. HvacLoadExplorer Software
• Based on the heat balance method (HBM).
• It allows a user to run a cooling or heating load calculation for an entire building
to determine the cooling or heating loads and airflow rate of all the rooms in a
building or zone.
• It allows a user to calculate the conduction transfer function coefficients,
response factors, radiant time series factors.
• For purposes of load calculations, a building may be thought of as being
organized in a hierarchical fashion. That is, a building is made up of zones, zones
are made up of rooms, and rooms are made up of walls, roofs, floors, and other
heat gain elements such as people, lighting, equipment, and infiltration.
• Zones are collections of one or more rooms, all controlled to the same air
temperature to allow the user to compute total loads for collections of rooms.
• A user may wish to include all rooms served by a particular cooling coil in a
single zone so that the peak load on the coil can be readily determined.
• Double-clicking on a zone will show all of the rooms in the zone; double-clicking
on a room will show all of the heat gain elements in the room.
22. Quick Start Guide
• First, to start describing a new building, go to the File menu and select “New”. This
will ask you to specify a file name. After this step, zones may be added to the building,
rooms may be added to the zone, and heat gain elements may be added to the room,
with the “Add Node” button shown in Figure 1.1.
• Jumping ahead (assuming many of the additional steps are intuitive) users need to
be aware that when they specify a wall, roof, or floor, it is important to specify an
external boundary condition, as shown in Fig. 1-2. “TOS” should be used for exterior
surfaces; “TA” for interior surfaces
SW absorptivity = short wave absorptivity, related to solar irradiation
LW emissivity = long wave emissivity, related to thermal radiation
24. Tree view
•
•First, to start describing a new building, go to the File menu and select “New”. This
will ask you to specify a file name. After this step, zones may be added to the building,
rooms may be added to the zone, and heat gain elements may be added to the room,
with the “Add Node” button shown in Figure 1.1.
• Jumping ahead (assuming many of the additional steps are intuitive) users need to
be aware that when they specify a wall, roof, or floor, it is important to specify an
external boundary condition, as shown in Fig. 1-2. “TOS” should be used for exterior
surfaces; “TA” for interior surfaces
SW absorptivity = short wave absorptivity, related to solar irradiation
LW emissivity = long wave emissivity, related to thermal radiation