4. HPM 3/3 Module
Model Power Dimension Weight
HPM3310-RM 10KVA 443x580x131mm 3U 26.0 kg
HPM3315-RM 15KVA 443x580x131mm 3U 30.0 kg
HPM3320-RM 20KVA 443x580x131mm 3U 31.0 kg
HPM3325-RM 25KVA 443x580x131mm 3U 32.0 kg
HPM3330-RM 30KVA 443x580x131mm 3U 33.0 kg
HPM3340-RM 40KVA 443x580x131mm 3U 34.0 kg
5. HPM UPS Cabinet (3/3)
Model Application
Dimension (W*D*H)
mm
Net Weight
HPM3300-60K
max. (3+1) x 10/15/20KVA
Modules
600x840x1400 145 kg
HPM3300-100K max. 5 x 10/15/20KVA Modules 600x840x1400 170 kg
HPM3300-200K max. 10 x 10/15/20KVA Modules 600x1100x2000 270 kg
HPM3300-250K max. 10 x 25KVA modules 600x1100x2000 290 kg
HPM 3300-90k max. (3+1) x 30KVA Modules 600x840x1400 149 kg
HPM 3300-150K max. 5 x 30KVA Modules 600x840x1400 152 kg
HPM 3300-300K max. 10 x 30KVA modules 600x1100x2000 310 kg
HPM3300-200K max. 5 x 40KVA Modules 600x860x1600 205 kg
HPM3300-320k max. 8 x 40KVA Modules 600x860x2000 310 kg
HPM3300-400/520k max. 8/13 x 40KVA Modules 1200x860x2000 450 kg
7. Main Features
Fit into standard 19” Rack Cabinet
Decentralized Parallel Structure Concept
Compact in Size, only 3U Height
Modular N+X Parallel Redundancy
Parallel Operation up to 10 Units for each Rack
Invest as You Grow
High Power Density to 520KVA per Rack
Common Battery
8. Main Features
Wide input voltage: 208~478Vac (3/3)
Sinusoidal input current THDI <3%
High input power factor up to 1 (0,99)
High efficiency up to 95.5%
Output power factor up to 1
Plug-and-Play Hot Swappable Module
Remote EPO Function
Control Monitoring with Touch-screen LCD Graphic Display
9. Main Features
Superior MTBF (> 220,000 hrs) and MTTR ( < 30 min. )
Powerful Charger Built-in Module and UPS Cabinet
Matching Battery Module also Available
Megatec/Mod Bus Protocol
Versatile Communication Interface
11. Single Line Module Diagram
I/P O/P
EMI AC/DC Converter BUS
DC/AC
Inverter
Static
Bypass
DC/DC Converter Charger
Battery
EMI
12. Compact in Size
Only 3U Height
10KVA/15KVA/20KVA/25KVA/30KVA/40KVA Modules Available
13. Modular N + X Parallel Redundancy
Parallel up to 13 Modules
Load Sharing
More than 1 Module can be set at Redundancy
Pay as you grow H=1.4M H=2.0M
14. Parallel up to 13 Units for Each Rack
H=1.4M/1.6M : up to 5 Modules
H=2.0M : up to 13 Modules
UPS Modules/Battery Modules
System Parallel Maximum: 4
UPS Modules Battery Modules
15. Invest as You Grow
Sizing What You Need Now
Pay as You Grow
Flexibility/Scalability for Future
Expansion
Low Service Contracts
No over-sizing UPS &
Add power w/o increasing footprint
16. High Power Density
Footprint Reduction, less Surface Costs
Easy to upgrade from 10KVA up to 520KVA per Rack
21. Plug-and-Play Hot Swappable Module
High Power Density
Reduced Footprint
Flexibility/Scalability
Lowest Service Cost
Lowest Installation Cost
30. Full-Screen status for Input, Output,
Battery, Modules
ONLINE
30KVA 22-12-
2008
ID:01 08:30
◄ Outpu
t
Modul
e
Inpu
t Batt Stat
e ►
A
Phase Voltage (v) 220
Phase Current (A) 1
Frequency (HZ) 50
Active Power ( KW) 0.0
Apparent Power (KVA) 0.0
Load percent(%) 0
Load crest factor 0.0
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Outpu
t
Modul
e
Inpu
t
Batt Stat
e
►
Module01 A B C
Invert Voltage (V) 380 380 380
Invert Current (A) 220 220 220
Frequency (HZ) 50
Positive Bus Voltage (V) 400
Negative Bus Voltage (V) 400
Code 8000-8000 D800-8000
0000-0000 0000-0000
Back
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Outpu
t
Modul
e
Inpu
t
Batt Stat
e
►
Mains A B C
Phase Voltage (V) 380 380 380
Phase Current (A) 220 220 220
Frequency (HZ) 50
Power Factor 0.97 0.97 0.97
Bypass
Phase Voltage (V) 220 220 220
Frequency (HZ) 50
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Outpu
t
Modul
e
Inpu
t
Batt Stat
e
►
Positive Battery Voltage (V) 240.0
Negative Battery Voltage (V) 240.0
Positive Battery Current (A) 10.0
Negative Battery Current (A) 10.0
Battery State Charge
Battery Temperature (℃) 28
Lasting (min) 90
31. Command
Battery Test
Buzzer Set
Default Set
ONLINE
30KVA 22-12-
2008
ID:01 08:30
◄ Comma
nd
Setti
ng
Record Versio
n
►
Battery Test
Buzzer Set Mute
Default Set
Self-Test Date
Mode: Weekly ▲
Week: SAT
Time: 18:36 ▼
Lasting: 60min
Ensure Cancel
LBS Group Setting
▼Master▲
Ensure Cancel
32. Setting
Language
System Parameters
Working Modes
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Comman
d
Setting Record Versio
n
►
Language
Change Password
Date Setting 2008-12-22 08:30:00
Back-Light Delay 10Min
Contrast 20
Self-Test Date STA 18:36
FOR:60min Back
Timing of ON/OFF ON:MON 08:48
OFF:SUN 17:25 Next
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Comman
d
Settin
g
Recor
d
Version ►
Work Mode Single
LBS Group Setting Master
System Voltage Level 220V
System Frequency Level 50HZ
Auto Turn-on Enable
Bypass Frequency Range 2%
Bypass Volt. Upper Limit 10% Back
Bypass Volt. Lower Limit -30%
O/P Volt Micro tuning 0% Next
33. Setting
Parallel ID
Battery Voltage/Capacity
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Comman
d
Setting Record Version ►
Parallel ID 01
M/S hot standby Cyc. 6 Mon
UPS Output Enable
Pre-Alarm Time 14 Min
Float Volt Revise 0.001
Parallel Amount 04
Parallel Redundancy 01 Back
Next
ONLINE
30KVA 22-12-
2008
ID:01
08:30
◄ Command Setting Record Version ►
Single Battery Volt. 12V
Battery Number 20
Battery Group 1
Single Battery Capa. 100AH
Boost Upper Limit Volt. 2.31
Float Base Volt. 2.25
Battery Protect Volt. 1.70
Boost Charge Enable Back
Boost Last Time 231 Min
Max Charge Current 25A Next
34. Record All Events/Alarm Message
Display Up to 49 events
50 alarm messages
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Volt. 12V
Battery Number 20
Battery Group 1
Single Battery Capa. 100AH
Boost Upper Limit Volt. 2.31
Float Base Volt. 2.25
Battery Protect Volt. 1.70
Boost Charge Enable Back
Boost Last Time 231 Min
Max Charge Current 25A Next
35. Hot Standby Mode
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Command Setting Record Version ►
Parallel ID 01
M/S hotstandby Cyc. 6 M
UPS Output Ena
Pre-Alarm Time 14
Float Volt Revise 0.00
Parallel Amount 04
Parallel Redundancy 01 Back
Next
M/S hot standby Cyc.
▼ 3 ▲
Ensure Cancel
36. Battery Setting
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Volt. 12V
Battery Number 20
Battery Group 1
Single Battery Capa. 100AH
Boost Upper Limit Volt. 2.31
Float Base Volt. 2.25
Battery Protect Volt. 1.70
Boost Charge Enable Back
Boost Last Time 231 Min
Max Charge Current 25A Next
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Volt. 12V
Battery Number 20
Battery Group 1
Single Battery Capa. 100AH
Boost Upper Limit Volt. 2.31
Float Base Volt. 2.25
Battery Protect Volt. 1.70
Boost Charge Enable Back
Boost Last Time 231 Min
Max Charge Current 25A
Next
Battery Number
▼ 20 ▲
Ensure Cancel
ONLINE
30KVA 22-12-2008
ID:01 08:30
◄ Command Setting Record Version ►
Single Battery Capa.
1000
7 8 9 Can
cel
4 5 6 ←
1 2 3 →
. 0 Ens
ure
Battery Group
▼ 1 ▲
Ensure Cancel
39. Versatile Communication Interfaces
RS485 Ports
RS232 Port
Mod Bus Port
2 x Intelligent slot (SNMP, relay option)
Network Management Card replacement
1: Dry Contact Relay
2: SNMP port
53. Special Models HPM-SA for Standard 19” Frame
can be used as a single unit
Model HPM3315/HPM3320/HPM3325-SA
Capacity 15KVA/13.5KW, 20KVA/18KW, 25KVA/22.5KW
Input Voltage 208Vac~478Vac
Output Voltage 380/400/415Vac
Battery Voltage 384V/408V/432/480Vdc Settable
Parallel Quantity 4(default), 5~6 or 7~10 Settable(remove J31 & J31/J30)
Dimension(WxHxD) 443x131x580
Net Weight(w/o battery) 31.0
Model HPM-BR32007
Battery Type/Quantity HC1221W(12V/21W)/32pcs
Dimension 483x132x680mm
Net Weight(w/o battery) 76.0
54. Standard 19” Rack Solution
The HPM3300-SA is designed to be the most
versatile UPS on the market and provides the
best technical & commercial solutions to
meet individual power protection needs.
It fixes in various depths of standard
19” rack cabinet.