Began operations in 1994
23 years
Support
73 employees country wide
Warehouses
multiple warehouses around the
country to be able to service our
clients with power product solutions
Branches
Located in Johannesburg,
Durban, Bloemfontein &
Cape Town, Mbombela, Tshwane
Stock
more than USD2, 500,000 invested in
stock country wide
Growth
The company is growing at
10~20% per year with a turnover
achievement of over
109 Million for 2014.
4 Branches
2 Franchises
JohannesburgBloemfonteinCapetown DurbanMbombelaTshwane
•Additional service
available for
servicing your
system and backup
batteries
• Installing your
Solar System / backup
system
•Project team create a
unique Power
Solution System
• Analysing your
Power usage to create
a system to suit your
daily energy needs
Analysing Solution
ServiceInstalling
R Series
GAIA Series
1 - 3 kVA
1 - 3 kVA
RT Series 5 - 10 kVA
Delta UPS - Amplon Family
Single Phase Online UPS
Up to 12 kVA
Summary
Stored energy
Uninterruptible
power supply
Standard 19 inches rack / tower configuration (2U).
Wide input voltage range reduces battery discharge probability prolongs battery lifetime.
Battery independent function to fulfill backup time by customized battery source. Specially for long backup application.
High recharging capability: Inbuilt 4.5-5A and optional 8A for 1kVA & 5A for 2/3kVA with extra charger box.
SMART slot for mission critical applications.
RS232 connectivity with Vista compatible power management software.
Optional external battery pack.
R Series 1-3 kVA
Applications
– Server Rack
– ATM
– Security
– Long Backup Time
Model R-1K R-2K R-3K
Power Rating 1kVA/700W 2kVA/1400W 3kVA/2100W
Voltage 220/230/240 Vac , single phase
Input Voltage Range 80 ~ 280 Vac. Lower range 80 ~ 175 Vac is acceptable under 50 ~ 100% loading condition.
Input Connection Power cord
Output Receptacle IEC320 C13 x 4 IEC320 C13 x 8 ; IEC320 C19 x 1
Battery Source Rating 36 Vdc 72 Vdc
Battery Charging Max. 5A Max. 4.5A
Optional Charger Board* Max. 8A Max. 5A
Internal Battery None! Customer can connect to their own battery source based on correct rating.
Interface RS232 x 1, SMART slot x 1
Tower Stand Kit Optional
Rack Rail Kit Included
Data Line Surge Protector Optional
External Battery Pack Optional. Connection is by Delta standard battery cable.
WxDxH (mm) 440 x 455.4 x 88.5
Weight (kg) 6.7 9.2
R Series Specifications
Summary
Stored energy
Uninterruptible
power supply
Standard 19 inches rack / tower configuration (2U).
High input power factor (pf > 0.97) saves installation cost.
Wide input voltage range reduces battery discharge probability prolongs battery lifetime.
RS232 and USB connectivity with Vista compatible power management software.
Inbuilt data line surge protector for phone / fax / network.
Programmable output receptacles for efficient energy usage.
SMART slot for mission critical applications.
Optional external battery pack
GAIA Series 1-3 kVA
Applications
– Server Rack
– ATM
– Security
– Audio/Video
Gaia Series Specifications
Model GAIA-1K GAIA-2K GAIA-3K
Power Rating 1kVA/800W 2kVA/1600W 3kVA/2100W
Voltage 200/208/220/230/240Vac, single phase
Input Voltage Range 130~275 Vac (Lower range 130 ~ 160 Vac is acceptable under 70% ~ 100% loading condition)
Power factor > 0.97
Output Receptacle IEC320 C13 x 3 x2 IEC320 C13 x 3 x 2; IEC320 C19 x 1
Internal Battery 12V/8.5Ah x 2 12V/8.5Ah x 4 12V/8.5Ah x 6
Backup Time
> 12 minutes (half load)
> 4 minutes (full load)
> 13 minutes (half load)
> 4 minutes (full load)
> 15 minutes (half load)
> 5 minutes (full load)
EBC Rating 8.5Ah x 2 x 2 8.5Ah x 4 x 2 8.5Ah x 6 x 2
Interface RS232 x 1, USB x 1, SMART slot x 1
Data Line Surge Protector Built-in (RJ11/RJ45, phone and network)
Tower Stand Kit Included in package
Rack Rail Kit Optional
External Battery Pack Optional
WxDxH (mm)
UPS
440 x 335 x 89 440 x 432 x 89 440 x 610 x 89
Battery Pack
Weight (kg)
UPS 13 21 31
Battery Pack 16 29 43
Summary
Stored energy
Uninterruptible
power supply
 Standard 19 inches rack / tower configuration (5/6kVA:2U 10kVA:3U).
 High output power factor 0.9
 1+1 parallel redundancy to increase the reliability and flexibility.
 High input power factor (pf > 0.99) and low input harmonic distortion (iTHD < 5%).
 High recharging capability: Inbuilt 4A and optional 4A extra charger.
 One SMART slot and MINI slot for mission critical applications.
 Multi-language LCD display and status LED.
 Optional maintenance bypass box
 Optional external battery pack and charger box.
RT Series 5-10 kVA
Applications
– IT Room
–Security
–Banking
–Long Backup Time
RT Series Specifications
Model RT-5K RT-6K RT-10K
Power Rating 5kVA/4.5kW 6kVA/5.4kW 10kVA/9kW
Voltage 200/208/220/230/240 Vac , single phase
Input Voltage Range 100 ~ 300 Vac
Input/Output Connection Hard wire (terminal block)
External Battery Pack Rating 12V/5Ah x 16 12V/9Ah or 12V/34W x 20
Battery Charging Max. 4A
Optional Charger Board** Max. 4A
Internal Battery No built-in battery. Customer can connect to their own battery source based on correct rating.
Interface RS232 x 1, SMART slot x 1, MINI slot x 1, Parallel port x 1
Rack Rail Kit Optional (tower stand kit is included)
Parallel Redundancy 1+1
Maintenance Bypass Box Optional
WxDxH (mm)
UPS 440 x 671 x 89 440 x 671 x 89 440 x 623 x 131
Battery Pack 440 x 638 x 89 440 x 638 x 89 440 x 595 x 131
Weight (kg)
UPS 15 15.5 21.3
Battery pack 36 36 66
EH Series 10 -20 kVA
HPH Series 20 - 40 kVA
NT Series 20 - 500 kVA
DPS Series 60 - 400 kVA
Delta UPS – Ultron Family
Three Phase Online UPS
Up to 4000 kVA
Summary
Stored energy
Uninterruptible
power supply
 A true online double-conversion 3phase-1phase UPS
 Advanced DSP controller for fast computation capability and a simplified control circuit for enhanced stability
 Dual input design to allow different power supply sources for enhanced availability
 Built-in manual bypass to ensure continuous power to the load even if the UPS is under maintenance
 A wide input voltage range to reduce battery discharge probability and prolong battery life
 ECO mode efficiency up to 96% to reduce operating costs
 Parallel expansion and N+X redundancy up to 4 units without requiring additional cards or equipment
 Small footprint to save space
EH Series 10-20 kVA
Applications
–Networking
–Data centers
–Telecommunications
–Medical
–Banking
–Retail
–Industrial
EH Series 10-20 kVA
Model EH-10K EH-15K EH-20K
Power Rating 10kVA /8kW 15kVA /12kW 20 kVA/16kW
Voltage 220/380 Vac; 230/400 Vac; 240/415 Vac
Input Voltage Range 208~304 Vac ( 50%~100% load) / 305~477 Vac (100% load)
Output Voltage 220/230/240 Vac
Overload Capability
≤105 %: continuous; 106%~110%: 10 minutes;
111%~125%: 1 minute; 126%~150%: 30 seconds
Efficiency
Online Mode: up to 91%
ECO Mode: up to 96%
Charge Current
Built-in: 4A
Additional charger board (optional): 4A
Charge Voltage
Float charge 272 +/- 2 Vdc
Boost charge 280 Vdc
Interface
SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1,
REPO Port x 1, Charger Detection Port x 1
Maintenance Bypass Switch Built-in
WxDxH (mm) 200 x 490 x 490 mm 250 x 610 x 650 mm
Weight UPS 26 Kg 45Kg
Summary
Stored energy
Uninterruptible
power supply
HPH Series 20-40kW
Applications
–Data centers
–Telecom
–Network
–Banking
–Medical
–Metro
–Industrial
 Fully rated power (kVA=kW) for maximum available power
 Leading AC-AC efficiency up to 96% saves energy costs
 Low harmonic pollution (iTHD<3%) & high input power factor (>0.99) reduce upstream investment costs
 Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life
 DSP based technology enables reduction in the number of electronic components to lower failure rate
 N+X redundancy up to 4 units increases system availability
 Built-in manual bypass ensures continuous power to the load even if the UPS is under maintenance
 Flexible arrangement of battery quantity from 34 to 50 pcs optimizes battery investment
HPH Series 20-40kW
Model
HPH-20K
HPH-20K-BN/B
HPH-30K
HPH-30K-BN/B
HPH-40K
HPH-40K-BN/B
Power Rating 20kVA /20kW 30kVA /30kW 40 kVA/40kW
Voltage 220/380 Vac; 230/400 Vac; 240/415 Vac
Input Voltage Range - 40% ~ 20% (242 ~ 477/140 ~ 276 Vac) * *
Output Voltage 220/380 Vac; 230/400 Vac; 240/415 Vac
Overload Capability
≦105 %: continuous; 106%~≦125%: 10 minutes;
126%~≦150%: 1 minute; >150%: 1 second
Battery Charging (Standard model) 5A 9A
Battery Charging (HPH-BN/B*) 5A, 9A (option)
Charge Voltage
Float charge ±272 V ±2Vdc,
Boost Charge ±280V ±2Vdc
Typical Backup Time (HPH-BN/B*)
(At 70% load with internal battery strings)
15 min 10 min 9.5 min
Efficiency
Online Mode: up to 96%
ECO Mode: up to 99%
Interface
SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1,
REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2,Output Dry Contact x 6
Maintenance Bypass Switch Built-in
*HPH-BN: UPS integrated battery model has no batteries inside
HPH-B: UPS integrated battery model has batteries inside
* *When input voltage is 242 ~ 324/140 ~ 187 Vac, the sustainable loading is
from 70% to 100% of the UPS capacity.
Summary
Stored energy
Uninterruptible
power supply
Applications
–Networking
–Data centers
–Telecommunications
–Medical
–Banking
–Industrial
 N+X parallel reduncancy (up to 8 units) for reliability and flexibility, w/o extra hardware.
 Economic mode for energy and operation cost savings.
 Inbuilt automatic and manual bypass switch.
 Inbuilt SRAM recording maximum 500 real-time event logs.
 Compatible with generator installation.
 6 configurable UPS status dry contact outputs.
 Optional 12-pulse rectifier or filter for lower harmonic distortion.
 Possibility for shared battery source enabling cost savings.
 Custom order voltage rating.
 Optional external battery cabinet.
NT Series 20-500 kVA
NT Series Specifications
NT- 20 K 30 K 40 K 50 K 60K 80K 100K 120 K 160 K 200 K 260 K 320 K 400 K 500 K
WxDxH (mm) 600 x 800 x 1400 800 x 830 x 1700 1200 x 830 x 1700 1600 x 995 x 1950
1900 x
995 x
1950
Weight (kg) 365 365 425 460 506 525 700 745 1050 1085 1680 1720 1920 2410
* The table above is based on 220/380 Vac rating.
** 500kVA model is assembled by two cabinets: Inverter (width=11m, 1760kg) and rectifier (width=8m, 650kg).
***Dimension and weight are for the standard model with 6pulse rectifier.
NT-series generic specification
Voltage 120/208, 220/380, 230/400, 240/415, 277/480 Vac (Three phase, 4 wire plus ground)
Voltage Range ±20 %
Interface RS232 x 1, RS485 x 1, SNMP slot x 1, Dry contact output x 6
Parallel Redundancy Maximum 8 units
Input Harmonic Improvement Optional 12-pulse rectifier or filter
SRAM Event Log Maximum 500 records
Battery Start Yes
Summary
Stored energy
Uninterruptible
power supply
Applications
–Networking
–Data centers
–Telecommunications
–Medical
–Banking
–Industrial
IGBT-based UPS with AC-AC efficiency up to 96%
0.9 output power factor, and supporting leading power factor data
center server, networking equipment
Able to parallel for N+X redundancy, hot stand-by and support
2(N+1) configuration to meet level tier 4 reliability
Wide input voltage range reduces battery discharging
Advanced battery management optimizes battery performance and lifetime
Field programmable sequential start-up 2 to 99 seconds
Hot swappable fan design
Optional Redundant fan design
Ultron DPS Series 60-400 kVA
DPS Series Specifications
Model DPS 60 DPS 80 DPS 100 DPS 120 DPS 160 DPS 200 DPS 300 DPS 400
Power Rating
60kVA /
54kW
80kVA /
72kW
100kVA /
90kW
120kVA /
108kW
160kVA /
144kW
200kVA /
180kW
300kVA /
270kW
400kVA /
360kW
Voltage 380/220, 400/230, 415/240 Vac (3 phase, 4-wire plus ground)
Input Voltage Range 208~477 Vac* 242~477 Vac*
Input Power Factor > 0.99
Current Harmonic
Distortion
< 3% (full load)
Output Voltage 380/220, 400/230, 415/240 Vac (3 phase, 4-wire plus ground)
Output Voltage
Regulation
± 1% (static)
Interface
RS232 x 1, Smart slot x 2, Dry contact output x 6,
Dry contact input x 2, Parallel port x 2,
Battery cabinet temperature sensor x 4,
REPO x 1
RS232 x 1, Smart slot x 2, Dry contact output x 6,
Dry contact input x 2, Parallel port x 2,
Battery cabinet temperature sensor x 4,
Battery status detection x 1, REPO x 1
Parallel Link Up to 4 units Up to 8 units
Efficiency
AC-AC: Up to 96%
ECO mode: Up to 99%
WxDxH (mm) 520 x 975 x 1695 850 x 865 x 1950 1600 x 865 x 1950
Weight (kg) 300 330 360 390 697 1335
* When input voltage is 208~300 / 242~324 Vac,
the sustainable loading is from 70% to 100% of
the UPS capacity.
Delta UPS – Modulon Family
Three Phase Modular Online UPS
- Up to 800 kW online UPS
NH Plus Series 20 - 120kVA
DPH Series 25 - 200 kW
Summary
Stored energy
Uninterruptible
power supply
Applications
–Networking
–Data centers
–Telecommunications
–Medical
–Banking
–Industrial
 Hot-swappable function providing uninterruptible power during module replacement.
 N+X parallel reduncancy(up to 4 units, max. 480kVA) for reliability and flexibility, w/o extra hardware.
 High input power factor (pf > 0.99) and low harmonic distortion (iTHD < 3%).
 94% high efficiency saving operation cost.
 Inbuilt automatic and manual bypass switch.
 Inbuilt SRAM recording maximum 500 real-time event logs.
 Multi-language LCD display and status LED indicators
 Compatible with generator installation.
 6 configurable UPS status dry contact outputs.
 Optional kit for monitoring battery cabinet temperature.
NH Plus Series 20-120 kVA
NH Plus Series 20-120 kVA
* Subject to reconfiguration of the UPS; Delta provides the
configuration service.
** When input voltage is 208~300/120~173 Vac, the sustainable
loading is from 70% to 100% of the UPS capacity.
Model NHP-20K NHP-40K NHP-60K NHP-80K NHP-100K NHP-120K
Power Rating* 20kVA /18kW 40kVA /36kW 60kVA /54kW 80kVA /72kW 100kVA/90kW 120kVA/108kW
Voltage 380/220, 400/230, 415/240 (3 phase, 4-wire plus ground)
Input Voltage
Range
208 ~ 477 Vac (line-line) / 120 ~ 276 Vac (line-neutral)**
Input Power Factor > 0.99
Input Current
Harmonic
Distortion
< 3% (full load)
Output Voltage
380/220, 400/230, 415/240 (3 phase, 4-wire plus ground)
Other rating is available in another cabinet (I/P and O/P transformer is included)
Connection Hard wire (terminal block)
Interface
RS232 x 1, SNMP slot x 2, Dry contact output x 6, Dry contact input x 2, Parallel port x 1,
Battery cabinet temperature sensor x 4, Battery cabinet status detection x 1, Remote emergency power off x 1
Parallel Link Up to 4 units. Maximum 480 kVA
External Battery
Cabinet
Optional
WxDxH (mm) 520 x 910 x 1165 520 x 975 x 1695
Weight (kg) 112.5 128 230 260 350 380
Summary
Stored energy
Uninterruptible
power supply
Applications
–Data centers
–Telecommunications
–Network
–Banking
–Industrial
 Advanced fault tolerance design achieved by self redundancy to guarantee operation
continuity
 Self-synchronization of power and control modules for continuous on-line operation even
in the event of control module failure to avoid downtime caused by single point failure
 Hot-swappable key modules and components to ensure Mean Time To Repair (MTTR)
close to zero
 Vertical expansion from 25kW to 200kW supporting N+X redundancy in a single rack
enclosure to save footprint
 Full rated power (kVA=kW) to maximize power availability
 High operating efficiency of 95% at 30% light load and 96% from 50% load resulting in
marked energy cost savings
 Low harmonic pollution (iTHD<3%) to reduce upstream investment costs and meet
demanding power requirements
DPH Series 25-200kW
DPH Series 25-200kW
Model 25 50 75 100 125 150 175 200
Power Rating* 25kVA/kW 50kVA/kW 75kVA/kW 100kVA/kW 125kVA/kW 150kVA/kW 175kVA/kW 200kVA/kW
Voltage 380/220, 400/230, 415/240 (3 phase, 4-wire plus ground)
Input Voltage
Range
176~276 / 305~477 V
(When input voltage is 140/242~176/305 Vac, the sustainable loading is from 60% to 100% of the UPS capacity)
Input Power
Factor
> 0.99
Input Current
Harmonic
Distortion
< 3%
(when input harmonic distortion is less than 1%)
Output Voltage 380/220, 400/230, 415/240 Vac (3 phase, 4-wire plus ground)
Interface
Parallel port x 2, Smart slot x 2, Dry contact output x 6,
Dry contact input x 6, SNMP card x 2, Battery dry contact x 6
Parallel Link Up to 4 units. Maximum 800 kW
External Battery
Cabinet
Optional
WxDxH (mm) 600 x 1090 x 2000
Weight (kg) 382 414 446 478 510 542 574 606
Delta Rectifiers
Summary
Stored energy Telecommunication
DPR 850-48 DPR 2900-48 DPR 2900-48 DPR 3000-48 DPR 4000-48 DPR 6000-48
Power output 850 W 2900 W 2900 W 3000 W 4000 W 6000 W
Efficiency 95.2% 96.4% 97.2% 98,0% 95.2% 96.5%
Power density 30 W / in3
36.5 W / in3
36.5 W / in3
56,8 W / in3
27.3 W / in3
26.5 W / in3
Control and
monitoring
ORION, ORION eco, ORION c
Hot-pluggable Yes Yes Yes Yes Yes Yes
Dimensions (W x H x D)
51.8 x 40.0
x 247.2 mm
125.5 x 41.0
x 269.9 mm
125.5 x 41.0
x 269.9 mm
84,0 x 41.0
x 270.0 mm
82.0 x 86.9
x 377.9 mm
129.5 x 83.0
x 380.7 mm
Weight 0.6 kg 2.0 kg 2.0 kg 1,4 kg 3.5 kg 5.2 kg
Cooling Fan cooled with speed control
Safety EN / IEC 60950; UL 60950; CAN / CSA – C22.2
EMI (radiated) EN 55022 class B
Environment RoHS compliant
Rectifiers
Self Power - CellD
Summary
Stored energy Telecommunication
CellD Systems
CellD 20 CellD 40 CellD 100 CellD 125 (EVO)
DPS 850B-48-2 DPS 850B-48-3 DPS 850B-48-6 DPS 2900B-48-3 DPS 2900B-48-3
Rectifier module
DPR 850B-48
(max. 2 pcs.)
DPR 850B-48
(max. 3 pcs.)
DPR 850B-48
(max. 6 pcs.)
DPR 2900B-48
(max. 3 pcs.)
DPR 2900B-48
(max. 3 pcs.)
Efficiency 95,2% 95.2% 95.2% 96.4% or 97,2% 96.4% or 97,2%
Install power
(max. config.)
1,7 kW 2.55 kW 5.1 kW 8.7 kW 8.7 kW
Dimensions H x W x D
43.6 (1U) x 484.3(19’)
x 280 mm
43.6 (1U) x 484.3(19’)
x 280 mm
86.8(2U) x 484.3(19’)
x 295 mm
86.8 (2U) x 484.3 (19’)
x 323 mm
133.5 (3U) x 481.5 (19’)
x 329 mm
Weight 4.0 kg 4.1 kg 7.0 kg 7.0 kg 15 kg
Input voltage range 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS
Max. output current /
max. installed power
26 A / 1,7 kW 40 A / 2.55 kW 100A / 5.1 kW 100A / 8.7 kW 125A / 8.7 kW
Controller ORION
Local interface Display, keypad, LEDs
Remote monitoring Alarm relays, modem option, LAN, SNMP protocol
CellD Systems
CellD 300 (EVO2)
DPS 2900B-48-3 19IN-5U DPS 2900B-48-5 19IN-5U DPS 2900B-48-6 19IN-6U DPS 2900B-48-3 21IN-4U DPS 2900B-48-6 21IN-5U
Rectifier module
DPR 2900B-48
(max. 3 pcs.)
DPR 2900B-48
(max. 5 pcs.)
DPR 2900B-48
(max. 6 pcs.)
DPR 2900B-48
(max. 3 pcs.)
DPR 2900B-48
(max. 6 pcs.)
Efficiency 96.4% or 97,2% 96.4% or 97,2% 96.4% or 97,2% 96.4% or 97,2% 96.4% or 97,2%
Install power
(max. config.)
8.7 kW 14.5 kW 17.4 kW 8.7 kW 17.4 kW
Dimensions H x W x D
222 (5U) x 479,7 (19’)
x 315 mm
222 (5U) x 479,7 (19’)
x 315 mm
266 (6U) x 479,7 (19’)
x 315 mm
177 (4U) x 534 (21’)
x 315 mm
222 (5U) x 534 (21’)
x 315 mm
Weight 13 kg 14 kg 14 kg 13 kg 14 kg
Input voltage range 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS
Max. output current /
max. installed power
250 A / 8,7 kW 250 A / 14,5 kW 250 A / 17.4 kW 250 A / 8.7 kW 250 A / 17.4 kW
Controller ORION
Local interface Display, keypad, LEDs
Remote monitoring Alarm relays, modem option, LAN, SNMP protocol
CellD Systems
CellD 600
DPS 2900B-48-12 19IN-9U DPS 4000B-48-5 19IN-7U
Rectifier module DPR 2900B-48 (max. 12 pcs.) DPR 4000B-48 (max. 5 pcs.)
Efficiency 96.4% or 97,2% 95.2%
Install power (max. config.) 34.8 kW 20 kW
Dimensions H x W x D 399 (9U) x 480 (19’) x 375 mm 311 (7U) x 480 (19’) x 465 mm
Weight 30 kg 25 kg
Input voltage range 80 - 300 VRMS 80 - 300 VRMS
Max. output current /
max. installed power
600A / 34.8 kW 600A / 20 kW
Controller ORION
Local interface Display, keypad, LEDs
Remote monitoring Alarm relays, modem option, LAN, SNMP protocol
CellD Additional Elements
Site Support cabinets
SC600 SC770 SC1300 SC1800 SC2000
Internal space 12 U 15 U 27 U 38 U 42 U
Height 620 mm 759 mm 1295 mm 1790 mm 1961 mm
Width 600 mm
Depth 450 or 600 mm
Wall Box
WB 5U WB 8U WB 12U
5 U / 19‘ 8 U / 19‘ 12 U / 19‘
253 mm 387 mm 564 mm
548 mm
475 mm
AC and/or DC Panel
DPD/APD/DAPD 19IN-3U DPD /APD/DAPD 21IN-3U
Operating voltage / Current (max.)
AC: 230 / 400 V (1 or 3 ph) / Related to equipment
DC: 20-60 V / 300A
Internal space 24 modules (18 mm) 27 modules (18 mm)
Dimensions H x W x D 133 (3U) x 480 (19’) x 190 mm 133 (3U) x 530 (21’) x 190 mm
Cabinet Power - CabD
Summary
Stored energy Telecommunication
CabD 600 CabD 1000 CabD 1500 CabD 2000
Standalone / Multicabinet Standalone Cabinet Multicabinet (Parallel option) Multicabinet (Parallel option) Multicabinet (Parallel option)
Rectifier module
DPR 6000 (max. 8 pcs),
DPR 4000 (max.12 pcs),
DPR 2900 (max.12 pcs)
DPR 6000 (max. 12 pcs)
DPR 4000 (max. 18 pcs),
DPR 2900 (max. 24 pcs)
DPR 6000 (max. 16 pcs),
DPR 4000 (max. 24 pcs),
DPR 2900 (max. 28 pcs)
DPR 6000 ( max 20 pcs)
DPR 4000 (max. 30 pcs),
Max. output current /
max. installed power
600A / 34.8 kW 1000 A / 72 Kw 1500A / 96 kW 2000A / 120 kW
Efficiency 95.2% ... 97,2% 95.2% ... 97,2% 95.2 % ... 96,5 % 95.2 % ... 96,5 %
AC configuration 3L+N+PE or 3L+PE
Load and battery
connection
Configurable – modular design
Controlling and
monitoring
ORION
Operating temperature -5 - +45 °C
CabD Systems
CabD Systems
CabD 3000 CabD 3000+
Standalone / Multicabinet Multicabinet (Parallel option) Multicabinet (Parallel option)
Rectifier module
DPR 6000 (max. 24 pcs),
DPR 4000 (max.36 pcs)
DPR 6000 (max. 24 pcs),
DPR 4000 (max. 36 pcs)
Max. output current /
max. installed power
3000 A / 144 Kw 3000 A / 144 kW (scaled up horizontal DC bus bars)
Efficiency 95.2% ... 96,5 % 95.2 % ... 96,5 %
AC configuration 3L+N+PE or 3L+PE
Load and battery
connection
Configurable – modular design
Controlling and
monitoring
ORION
Operating temperature -5 - +45 °C
CabD Systems - options
Controller Battery connection Battery connection Battery connection
Controller shelf 1U
Battery fuse TPS2
up to 4x 1600 A
Battery fuse EFEN NH3
up to 4x 630 A
Battery fuse EFEN NH2
up to 4x 400 A
Load connection Load connection Load connection Load connection
DPD 8x EFEN NH00
2..160 A
DPD 7x NH02
100..400 A
DPD 30x MCB
2..63 A
DPD 13x 22x58
2..100 A
Inverter Systems
Summary
Stored energy Telecommunication
APS 750B-230-8 19IN APS 1500B-230-8 19IN APS 2500B-230-8 19IN APS 2500B-230-24 CabD
Inverter modules
(Max. configuration)
8x TSI NOVA - 230Vac 8x TSI MEDIA - 230Vac 8x TSI BRAVO - 230Vac 24x TSI BRAVO - 230Vac
Max. installed power 6 kVA / 4,2 kW 12 kVA / 9,6 kW 20 kVA / 16 kW 60 kVA / 48 kW
Efficiency (EPC mode) 93 % 94 % 96 % 96 %
AC configuration
Input / Output
One phase / One phase One phase / One phase or
Three phases / three phases
Output loads
AC distribution
Configurable (MCBs, RCDs, bulk type) - modular design
Controlling
and monitoring
T2S - ORION
Manual Bypass optional
Inverter System
Outdoor Systems - OutD
Summary
Stored energy Telecommunication
OutD: V series
OutD V Series
Key
advantages
• Single or Multilayer wall design
• -7dB(A) (lower than standard cabinets with the same cooling capacity)
• Steel or aluminium outside walls
• Flexible configuration - 19’ or 21’ racks, battery shelves, multiple PSU options (power supply systems),
multiple cable management options
• Multiple cooling options (AV, AC, Hybrid AC+AC)
• Battery cooler (Separated battery compartment with advanced thermal insulation 40mm EPS and active cooling (TEC or
AC)
Dimensions
OutD 0.7V H701 x W605 x D530mm - 12HU (plinth H100mm excl.)
OutD 1.2V H1257 x W708 x D752mm - 21HU
OutD 1.8V H1860 x W708 x D752mm - 35HU
OutD 2.0V H2047 x W808 x D852mm - 39HU
OutD 2.2V H2247 x W808 x D852mm - 44HU
Material Steel or Aluminium, Single or multilayer with optional thermal insulation
Lifetime Steel : up to 15 year, Aluminium: up to 20 years
Cooling
options
AV (Air Ventilation), HEX (Heat Exchanger,) AC (Air con), Hybrid AV+AC (Hybrid cooling Air Ventilation
+ Air con)
OutD: M series
OutD M Series
Key
advantages
• Single or Multilayer wall design
• -7dB(A) (lower than standard cabinets with the same cooling capacity)
• Flexible configuration - 19’ or 21’ racks, battery shelves, multiple PSU options (power
supply systems), multiple cable management options
• Battery box extension (battery cooler)
• IP20 equipment extension
• Side by side connection available
Dimensions
OutD 1.5M H1500 x W770 x D852mm - 28HU
OutD 1.8M H1829 x W770 x D852mm - 35HU
OutD 2.0M H2052 x W870 x D952mm - 40HU
Material Steel or Aluminium, Single or multilayer with optional thermal insulation
Lifetime Steel : up to 15 year, Aluminium: up to 20 years
Cooling
Options
AV (Air Ventilation), HEX (Heat Exchanger,) AC (Air con), Hybrid AV+AC (Hybrid cooling +
Air Ventilation + Air con)
Small Cell Power
Summary
Stored energy Telecommunication
Small Cell Power – DPR 1000B-45
Small Cell – Outdoor Rectifier
Dimensions H360 x W209,8 x D88,8mm
EN 60529 class IP65
Material Aluminium
Weight 6,4kg
User Interface Status Indication
Mounting Lamppost, pole or wall mountable
Cooling options Natural Cooling
PSU Power 1000W / 42 - 58Vdc
EMC EN55022, CISPR22, FCC 15 class B
Operating temperature
-40°C to +60 °C
(linear power de-rating to 50% load from 46°C to 60°C)
Humidity (relative) 95%, non-condensing (Max.)
Connectors
AC input: Amphenol PWC-03RMMS-LC7002 x 1
Dc output: Amphenol PWC-03RMFS-LC7002 x 2
Alarms: Amphenol CD-09RMFS-LC7001 x 1
Options Service LED light, Alarm terminals
Small Cell Design - BoxD
Small Cell - BoxD
Dimensions H684 x W489 x D312mm
EN 60529 class up to IP55
Material
Enclosure: Aluminium
Internal Parts: Galvanized steel
Wall structure Single layer with sun radiation screen
Lifetime Steel: 10+ years
Mounting Wall / Pole
Cooling options
HEX (Heat Exchanger) 15W/K
AV (Air Ventilation)*
TEC (Peltier Module)*
PSU Power 2x850W / 48Vdc
Battery supervision
None
LVD only
ORION + Shunt/LVD
Battery backup
19” space
- 14Ah 24Ah
2.5U 1U -
Cable glands 4xPG16 4xPG13.5 2xPG11
Options Service LED light, Alarm terminals
Controller and network monitoring
Summary
Stored energy Telecommunication
Battery management, supervision
and control (Pb/LI) incl. Battery
profile management
Remote communication via LAN,
SNMP, Modbus and I-Phone App
incl. enhanced security by SNMP
V3 and IP filtering
Power System and rectifier
management and control incl.
efficiency mode, alarming and
parameter setting
Easy configuration management
including inventory reporting,
language support and configurable
data logging features
Full site control and management of:
• Gensets
• Batteries
• Cooling devices (Aircon, HEX, fans)
• Hybrid mix
• Site access
• Site inventory
• IP camera
Smart metering and alarming of:
• Site energy consumption
• Temperature & Humidity
• Smoke detector
• Flood detector
• Intrusion detector
• Any kind of other external devices
Easy integration of hybrid energy
sources
• Solar
• Wind
• Genset
2017 update:
• Upgraded with touch panel
• 1GB Lan connection -> IT network integration
• New µC and more memory
• 25% less power consumption
• Micro SD slot -> simplified field service
1
2
3
4
5
6
7
ORION Controller
ORION Controller
ORION c
• Orion ID E1 - TPS1020028A
• Full functionality, all features
• Orion ID C1 - TPS1020029A
• Full functionality, all features
• Used for upgrading systems originally
installed with PSC3 controller
• Orion ID G1 - TPS1020030A
• Limited functionality for low cost
applications
ORION eco
ORION Controller

More Related Content

What's hot

Grid Restoration Challneges and Strategy
Grid Restoration Challneges and Strategy Grid Restoration Challneges and Strategy
Grid Restoration Challneges and Strategy Chandan Kumar
 
FLYBACK CONVERTER PPT
FLYBACK CONVERTER PPTFLYBACK CONVERTER PPT
FLYBACK CONVERTER PPTAjmal Khan
 
Solar rooftop projects primotech
Solar rooftop projects primotechSolar rooftop projects primotech
Solar rooftop projects primotechvimalranaprimotech
 
Active filter iora 2 consul
Active filter iora 2 consulActive filter iora 2 consul
Active filter iora 2 consulrajesh thulasi
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationAmeen San
 
tesla home battery power wall by braj mohan
tesla home battery power wall by braj mohantesla home battery power wall by braj mohan
tesla home battery power wall by braj mohanbrajmohanthakur
 
SHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptx
SHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptxSHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptx
SHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptxJohnLeimarRodriguez
 
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensatorbhupendra kumar
 
UPS (Uninterruptible Power Supply) on oil and gas industry. pdf
UPS (Uninterruptible Power Supply) on oil and gas industry. pdfUPS (Uninterruptible Power Supply) on oil and gas industry. pdf
UPS (Uninterruptible Power Supply) on oil and gas industry. pdflindkw
 
Modificação saida erf_2030_ept3600_mod(2)
Modificação saida erf_2030_ept3600_mod(2)Modificação saida erf_2030_ept3600_mod(2)
Modificação saida erf_2030_ept3600_mod(2)João Pereira
 
Sma company presentation-en
Sma company presentation-enSma company presentation-en
Sma company presentation-enProAkademia
 
1 hvdc systems_in_india
1 hvdc systems_in_india1 hvdc systems_in_india
1 hvdc systems_in_indiaganesh g
 
Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)
Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)
Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)Habro Group
 

What's hot (20)

OPAL-RT Seminar on HYPERSIM
OPAL-RT Seminar on HYPERSIMOPAL-RT Seminar on HYPERSIM
OPAL-RT Seminar on HYPERSIM
 
Grid Restoration Challneges and Strategy
Grid Restoration Challneges and Strategy Grid Restoration Challneges and Strategy
Grid Restoration Challneges and Strategy
 
FLYBACK CONVERTER PPT
FLYBACK CONVERTER PPTFLYBACK CONVERTER PPT
FLYBACK CONVERTER PPT
 
Solar rooftop projects primotech
Solar rooftop projects primotechSolar rooftop projects primotech
Solar rooftop projects primotech
 
Apfc panel
Apfc panelApfc panel
Apfc panel
 
upfc
upfcupfc
upfc
 
Active filter iora 2 consul
Active filter iora 2 consulActive filter iora 2 consul
Active filter iora 2 consul
 
3 phase current source inverter
3 phase  current  source  inverter3 phase  current  source  inverter
3 phase current source inverter
 
Application of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage RegulationApplication of Capacitors to Distribution System and Voltage Regulation
Application of Capacitors to Distribution System and Voltage Regulation
 
Grid Connected PV Systems
Grid Connected PV SystemsGrid Connected PV Systems
Grid Connected PV Systems
 
tesla home battery power wall by braj mohan
tesla home battery power wall by braj mohantesla home battery power wall by braj mohan
tesla home battery power wall by braj mohan
 
SHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptx
SHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptxSHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptx
SHORT-CIRCUIT-CALCULATIONS-ANSI-VS-IEC-F (1).pptx
 
static series synchronus compensator
static series synchronus compensatorstatic series synchronus compensator
static series synchronus compensator
 
UPS (Uninterruptible Power Supply) on oil and gas industry. pdf
UPS (Uninterruptible Power Supply) on oil and gas industry. pdfUPS (Uninterruptible Power Supply) on oil and gas industry. pdf
UPS (Uninterruptible Power Supply) on oil and gas industry. pdf
 
Modificação saida erf_2030_ept3600_mod(2)
Modificação saida erf_2030_ept3600_mod(2)Modificação saida erf_2030_ept3600_mod(2)
Modificação saida erf_2030_ept3600_mod(2)
 
Sma company presentation-en
Sma company presentation-enSma company presentation-en
Sma company presentation-en
 
1 hvdc systems_in_india
1 hvdc systems_in_india1 hvdc systems_in_india
1 hvdc systems_in_india
 
UPS Sizing
UPS SizingUPS Sizing
UPS Sizing
 
Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)
Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)
Manual da caixa Subwoofer SRM1801 (PORTUGUÊS)
 
Fuente de poder lineal
Fuente de poder linealFuente de poder lineal
Fuente de poder lineal
 

Similar to Delta products overview

Modular UPS 10 - 90 KVA.pdf
Modular UPS 10 - 90 KVA.pdfModular UPS 10 - 90 KVA.pdf
Modular UPS 10 - 90 KVA.pdfsuman bala
 
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmElektrumlv
 
Bộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng ItaliaBộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng ItaliaNgoSinh3
 
Huawei UPS 1-3kVA UPS2000A Series Datasheet
Huawei UPS 1-3kVA UPS2000A Series DatasheetHuawei UPS 1-3kVA UPS2000A Series Datasheet
Huawei UPS 1-3kVA UPS2000A Series DatasheetRobin Koffler MBA CDCEP
 
Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)Jason Koffler
 
Presentation gamatronic
Presentation gamatronicPresentation gamatronic
Presentation gamatronichoanv
 
NOVA Double Conversion UPS range
NOVA Double Conversion UPS range NOVA Double Conversion UPS range
NOVA Double Conversion UPS range Mohammed Aggabi
 
Wago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalogWago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalogElectromate
 
Enphase iq7 and iq7plus data sheet iq7 iq7plus-ds-en-us
Enphase iq7 and iq7plus data sheet    iq7 iq7plus-ds-en-usEnphase iq7 and iq7plus data sheet    iq7 iq7plus-ds-en-us
Enphase iq7 and iq7plus data sheet iq7 iq7plus-ds-en-usMu Cephei
 
9900 Presentation
9900 Presentation 9900 Presentation
9900 Presentation harrycan
 
ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303
ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303
ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303Wendy Zhang
 
2009-dec02_OnDuty
2009-dec02_OnDuty2009-dec02_OnDuty
2009-dec02_OnDutyAgora Group
 

Similar to Delta products overview (20)

Delta modulon ups
Delta modulon upsDelta modulon ups
Delta modulon ups
 
Ecopowersupplies: Riello Sentinel Dual High Power UPS
Ecopowersupplies: Riello Sentinel Dual High Power UPSEcopowersupplies: Riello Sentinel Dual High Power UPS
Ecopowersupplies: Riello Sentinel Dual High Power UPS
 
Aet series
Aet seriesAet series
Aet series
 
Modular UPS 10 - 90 KVA.pdf
Modular UPS 10 - 90 KVA.pdfModular UPS 10 - 90 KVA.pdf
Modular UPS 10 - 90 KVA.pdf
 
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
 
Bộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng ItaliaBộ lưu điện ups gtec chính hãng Italia
Bộ lưu điện ups gtec chính hãng Italia
 
Huawei UPS 1-3kVA UPS2000A Series Datasheet
Huawei UPS 1-3kVA UPS2000A Series DatasheetHuawei UPS 1-3kVA UPS2000A Series Datasheet
Huawei UPS 1-3kVA UPS2000A Series Datasheet
 
Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)Huawei ups product and solution 02 (20140318)
Huawei ups product and solution 02 (20140318)
 
Apc surt 4
Apc   surt 4Apc   surt 4
Apc surt 4
 
Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
  Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK  Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
Riello Multi Sentry Uninterruptible Power Supplies Suppliers,London UK
 
Ecopowersupplies: Riello-Multi-Sentry-UPS
Ecopowersupplies: Riello-Multi-Sentry-UPSEcopowersupplies: Riello-Multi-Sentry-UPS
Ecopowersupplies: Riello-Multi-Sentry-UPS
 
Presentation gamatronic
Presentation gamatronicPresentation gamatronic
Presentation gamatronic
 
NOVA Double Conversion UPS range
NOVA Double Conversion UPS range NOVA Double Conversion UPS range
NOVA Double Conversion UPS range
 
Ecopowersupplies: Riello sentinel-pro-ups-datasheet
Ecopowersupplies: Riello sentinel-pro-ups-datasheetEcopowersupplies: Riello sentinel-pro-ups-datasheet
Ecopowersupplies: Riello sentinel-pro-ups-datasheet
 
Wago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalogWago epsitron power_supplies_catalog
Wago epsitron power_supplies_catalog
 
Riello vision-ups-datasheet
Riello vision-ups-datasheetRiello vision-ups-datasheet
Riello vision-ups-datasheet
 
Enphase iq7 and iq7plus data sheet iq7 iq7plus-ds-en-us
Enphase iq7 and iq7plus data sheet    iq7 iq7plus-ds-en-usEnphase iq7 and iq7plus data sheet    iq7 iq7plus-ds-en-us
Enphase iq7 and iq7plus data sheet iq7 iq7plus-ds-en-us
 
9900 Presentation
9900 Presentation 9900 Presentation
9900 Presentation
 
ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303
ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303
ZH/PVII Series UPS 10-600kVA from HRD UPS -20160303
 
2009-dec02_OnDuty
2009-dec02_OnDuty2009-dec02_OnDuty
2009-dec02_OnDuty
 

Recently uploaded

Cloud Management Software Platforms: OpenStack
Cloud Management Software Platforms: OpenStackCloud Management Software Platforms: OpenStack
Cloud Management Software Platforms: OpenStackVICTOR MAESTRE RAMIREZ
 
Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...
Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...
Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...soniya singh
 
What is Fashion PLM and Why Do You Need It
What is Fashion PLM and Why Do You Need ItWhat is Fashion PLM and Why Do You Need It
What is Fashion PLM and Why Do You Need ItWave PLM
 
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed DataAlluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed DataAlluxio, Inc.
 
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASEBATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASEOrtus Solutions, Corp
 
EY_Graph Database Powered Sustainability
EY_Graph Database Powered SustainabilityEY_Graph Database Powered Sustainability
EY_Graph Database Powered SustainabilityNeo4j
 
Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024
Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024
Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024StefanoLambiase
 
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...stazi3110
 
Salesforce Certified Field Service Consultant
Salesforce Certified Field Service ConsultantSalesforce Certified Field Service Consultant
Salesforce Certified Field Service ConsultantAxelRicardoTrocheRiq
 
Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)OPEN KNOWLEDGE GmbH
 
Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...
Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...
Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...MyIntelliSource, Inc.
 
chapter--4-software-project-planning.ppt
chapter--4-software-project-planning.pptchapter--4-software-project-planning.ppt
chapter--4-software-project-planning.pptkotipi9215
 
Intelligent Home Wi-Fi Solutions | ThinkPalm
Intelligent Home Wi-Fi Solutions | ThinkPalmIntelligent Home Wi-Fi Solutions | ThinkPalm
Intelligent Home Wi-Fi Solutions | ThinkPalmSujith Sukumaran
 
Cloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEECloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEEVICTOR MAESTRE RAMIREZ
 
software engineering Chapter 5 System modeling.pptx
software engineering Chapter 5 System modeling.pptxsoftware engineering Chapter 5 System modeling.pptx
software engineering Chapter 5 System modeling.pptxnada99848
 
The Evolution of Karaoke From Analog to App.pdf
The Evolution of Karaoke From Analog to App.pdfThe Evolution of Karaoke From Analog to App.pdf
The Evolution of Karaoke From Analog to App.pdfPower Karaoke
 
Unveiling Design Patterns: A Visual Guide with UML Diagrams
Unveiling Design Patterns: A Visual Guide with UML DiagramsUnveiling Design Patterns: A Visual Guide with UML Diagrams
Unveiling Design Patterns: A Visual Guide with UML DiagramsAhmed Mohamed
 
Asset Management Software - Infographic
Asset Management Software - InfographicAsset Management Software - Infographic
Asset Management Software - InfographicHr365.us smith
 
Advancing Engineering with AI through the Next Generation of Strategic Projec...
Advancing Engineering with AI through the Next Generation of Strategic Projec...Advancing Engineering with AI through the Next Generation of Strategic Projec...
Advancing Engineering with AI through the Next Generation of Strategic Projec...OnePlan Solutions
 
Automate your Kamailio Test Calls - Kamailio World 2024
Automate your Kamailio Test Calls - Kamailio World 2024Automate your Kamailio Test Calls - Kamailio World 2024
Automate your Kamailio Test Calls - Kamailio World 2024Andreas Granig
 

Recently uploaded (20)

Cloud Management Software Platforms: OpenStack
Cloud Management Software Platforms: OpenStackCloud Management Software Platforms: OpenStack
Cloud Management Software Platforms: OpenStack
 
Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...
Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...
Russian Call Girls in Karol Bagh Aasnvi ➡️ 8264348440 💋📞 Independent Escort S...
 
What is Fashion PLM and Why Do You Need It
What is Fashion PLM and Why Do You Need ItWhat is Fashion PLM and Why Do You Need It
What is Fashion PLM and Why Do You Need It
 
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed DataAlluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
 
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASEBATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
 
EY_Graph Database Powered Sustainability
EY_Graph Database Powered SustainabilityEY_Graph Database Powered Sustainability
EY_Graph Database Powered Sustainability
 
Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024
Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024
Dealing with Cultural Dispersion — Stefano Lambiase — ICSE-SEIS 2024
 
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
 
Salesforce Certified Field Service Consultant
Salesforce Certified Field Service ConsultantSalesforce Certified Field Service Consultant
Salesforce Certified Field Service Consultant
 
Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)
 
Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...
Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...
Steps To Getting Up And Running Quickly With MyTimeClock Employee Scheduling ...
 
chapter--4-software-project-planning.ppt
chapter--4-software-project-planning.pptchapter--4-software-project-planning.ppt
chapter--4-software-project-planning.ppt
 
Intelligent Home Wi-Fi Solutions | ThinkPalm
Intelligent Home Wi-Fi Solutions | ThinkPalmIntelligent Home Wi-Fi Solutions | ThinkPalm
Intelligent Home Wi-Fi Solutions | ThinkPalm
 
Cloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEECloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEE
 
software engineering Chapter 5 System modeling.pptx
software engineering Chapter 5 System modeling.pptxsoftware engineering Chapter 5 System modeling.pptx
software engineering Chapter 5 System modeling.pptx
 
The Evolution of Karaoke From Analog to App.pdf
The Evolution of Karaoke From Analog to App.pdfThe Evolution of Karaoke From Analog to App.pdf
The Evolution of Karaoke From Analog to App.pdf
 
Unveiling Design Patterns: A Visual Guide with UML Diagrams
Unveiling Design Patterns: A Visual Guide with UML DiagramsUnveiling Design Patterns: A Visual Guide with UML Diagrams
Unveiling Design Patterns: A Visual Guide with UML Diagrams
 
Asset Management Software - Infographic
Asset Management Software - InfographicAsset Management Software - Infographic
Asset Management Software - Infographic
 
Advancing Engineering with AI through the Next Generation of Strategic Projec...
Advancing Engineering with AI through the Next Generation of Strategic Projec...Advancing Engineering with AI through the Next Generation of Strategic Projec...
Advancing Engineering with AI through the Next Generation of Strategic Projec...
 
Automate your Kamailio Test Calls - Kamailio World 2024
Automate your Kamailio Test Calls - Kamailio World 2024Automate your Kamailio Test Calls - Kamailio World 2024
Automate your Kamailio Test Calls - Kamailio World 2024
 

Delta products overview

  • 1. www.rectifier.co.za / www.solar-solutions.co.za / www.batterysolutions.co.za / www.power-solutions.co.za
  • 2. 01 03 05 02 04 06 Began operations in 1994 23 years Support 73 employees country wide Warehouses multiple warehouses around the country to be able to service our clients with power product solutions Branches Located in Johannesburg, Durban, Bloemfontein & Cape Town, Mbombela, Tshwane Stock more than USD2, 500,000 invested in stock country wide Growth The company is growing at 10~20% per year with a turnover achievement of over 109 Million for 2014.
  • 4. •Additional service available for servicing your system and backup batteries • Installing your Solar System / backup system •Project team create a unique Power Solution System • Analysing your Power usage to create a system to suit your daily energy needs Analysing Solution ServiceInstalling
  • 5. R Series GAIA Series 1 - 3 kVA 1 - 3 kVA RT Series 5 - 10 kVA Delta UPS - Amplon Family Single Phase Online UPS Up to 12 kVA
  • 6. Summary Stored energy Uninterruptible power supply Standard 19 inches rack / tower configuration (2U). Wide input voltage range reduces battery discharge probability prolongs battery lifetime. Battery independent function to fulfill backup time by customized battery source. Specially for long backup application. High recharging capability: Inbuilt 4.5-5A and optional 8A for 1kVA & 5A for 2/3kVA with extra charger box. SMART slot for mission critical applications. RS232 connectivity with Vista compatible power management software. Optional external battery pack. R Series 1-3 kVA Applications – Server Rack – ATM – Security – Long Backup Time
  • 7. Model R-1K R-2K R-3K Power Rating 1kVA/700W 2kVA/1400W 3kVA/2100W Voltage 220/230/240 Vac , single phase Input Voltage Range 80 ~ 280 Vac. Lower range 80 ~ 175 Vac is acceptable under 50 ~ 100% loading condition. Input Connection Power cord Output Receptacle IEC320 C13 x 4 IEC320 C13 x 8 ; IEC320 C19 x 1 Battery Source Rating 36 Vdc 72 Vdc Battery Charging Max. 5A Max. 4.5A Optional Charger Board* Max. 8A Max. 5A Internal Battery None! Customer can connect to their own battery source based on correct rating. Interface RS232 x 1, SMART slot x 1 Tower Stand Kit Optional Rack Rail Kit Included Data Line Surge Protector Optional External Battery Pack Optional. Connection is by Delta standard battery cable. WxDxH (mm) 440 x 455.4 x 88.5 Weight (kg) 6.7 9.2 R Series Specifications
  • 8. Summary Stored energy Uninterruptible power supply Standard 19 inches rack / tower configuration (2U). High input power factor (pf > 0.97) saves installation cost. Wide input voltage range reduces battery discharge probability prolongs battery lifetime. RS232 and USB connectivity with Vista compatible power management software. Inbuilt data line surge protector for phone / fax / network. Programmable output receptacles for efficient energy usage. SMART slot for mission critical applications. Optional external battery pack GAIA Series 1-3 kVA Applications – Server Rack – ATM – Security – Audio/Video
  • 9. Gaia Series Specifications Model GAIA-1K GAIA-2K GAIA-3K Power Rating 1kVA/800W 2kVA/1600W 3kVA/2100W Voltage 200/208/220/230/240Vac, single phase Input Voltage Range 130~275 Vac (Lower range 130 ~ 160 Vac is acceptable under 70% ~ 100% loading condition) Power factor > 0.97 Output Receptacle IEC320 C13 x 3 x2 IEC320 C13 x 3 x 2; IEC320 C19 x 1 Internal Battery 12V/8.5Ah x 2 12V/8.5Ah x 4 12V/8.5Ah x 6 Backup Time > 12 minutes (half load) > 4 minutes (full load) > 13 minutes (half load) > 4 minutes (full load) > 15 minutes (half load) > 5 minutes (full load) EBC Rating 8.5Ah x 2 x 2 8.5Ah x 4 x 2 8.5Ah x 6 x 2 Interface RS232 x 1, USB x 1, SMART slot x 1 Data Line Surge Protector Built-in (RJ11/RJ45, phone and network) Tower Stand Kit Included in package Rack Rail Kit Optional External Battery Pack Optional WxDxH (mm) UPS 440 x 335 x 89 440 x 432 x 89 440 x 610 x 89 Battery Pack Weight (kg) UPS 13 21 31 Battery Pack 16 29 43
  • 10. Summary Stored energy Uninterruptible power supply  Standard 19 inches rack / tower configuration (5/6kVA:2U 10kVA:3U).  High output power factor 0.9  1+1 parallel redundancy to increase the reliability and flexibility.  High input power factor (pf > 0.99) and low input harmonic distortion (iTHD < 5%).  High recharging capability: Inbuilt 4A and optional 4A extra charger.  One SMART slot and MINI slot for mission critical applications.  Multi-language LCD display and status LED.  Optional maintenance bypass box  Optional external battery pack and charger box. RT Series 5-10 kVA Applications – IT Room –Security –Banking –Long Backup Time
  • 11. RT Series Specifications Model RT-5K RT-6K RT-10K Power Rating 5kVA/4.5kW 6kVA/5.4kW 10kVA/9kW Voltage 200/208/220/230/240 Vac , single phase Input Voltage Range 100 ~ 300 Vac Input/Output Connection Hard wire (terminal block) External Battery Pack Rating 12V/5Ah x 16 12V/9Ah or 12V/34W x 20 Battery Charging Max. 4A Optional Charger Board** Max. 4A Internal Battery No built-in battery. Customer can connect to their own battery source based on correct rating. Interface RS232 x 1, SMART slot x 1, MINI slot x 1, Parallel port x 1 Rack Rail Kit Optional (tower stand kit is included) Parallel Redundancy 1+1 Maintenance Bypass Box Optional WxDxH (mm) UPS 440 x 671 x 89 440 x 671 x 89 440 x 623 x 131 Battery Pack 440 x 638 x 89 440 x 638 x 89 440 x 595 x 131 Weight (kg) UPS 15 15.5 21.3 Battery pack 36 36 66
  • 12. EH Series 10 -20 kVA HPH Series 20 - 40 kVA NT Series 20 - 500 kVA DPS Series 60 - 400 kVA Delta UPS – Ultron Family Three Phase Online UPS Up to 4000 kVA
  • 13. Summary Stored energy Uninterruptible power supply  A true online double-conversion 3phase-1phase UPS  Advanced DSP controller for fast computation capability and a simplified control circuit for enhanced stability  Dual input design to allow different power supply sources for enhanced availability  Built-in manual bypass to ensure continuous power to the load even if the UPS is under maintenance  A wide input voltage range to reduce battery discharge probability and prolong battery life  ECO mode efficiency up to 96% to reduce operating costs  Parallel expansion and N+X redundancy up to 4 units without requiring additional cards or equipment  Small footprint to save space EH Series 10-20 kVA Applications –Networking –Data centers –Telecommunications –Medical –Banking –Retail –Industrial
  • 14. EH Series 10-20 kVA Model EH-10K EH-15K EH-20K Power Rating 10kVA /8kW 15kVA /12kW 20 kVA/16kW Voltage 220/380 Vac; 230/400 Vac; 240/415 Vac Input Voltage Range 208~304 Vac ( 50%~100% load) / 305~477 Vac (100% load) Output Voltage 220/230/240 Vac Overload Capability ≤105 %: continuous; 106%~110%: 10 minutes; 111%~125%: 1 minute; 126%~150%: 30 seconds Efficiency Online Mode: up to 91% ECO Mode: up to 96% Charge Current Built-in: 4A Additional charger board (optional): 4A Charge Voltage Float charge 272 +/- 2 Vdc Boost charge 280 Vdc Interface SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1 Maintenance Bypass Switch Built-in WxDxH (mm) 200 x 490 x 490 mm 250 x 610 x 650 mm Weight UPS 26 Kg 45Kg
  • 15. Summary Stored energy Uninterruptible power supply HPH Series 20-40kW Applications –Data centers –Telecom –Network –Banking –Medical –Metro –Industrial  Fully rated power (kVA=kW) for maximum available power  Leading AC-AC efficiency up to 96% saves energy costs  Low harmonic pollution (iTHD<3%) & high input power factor (>0.99) reduce upstream investment costs  Wide input voltage range allows the UPS to operate in harsh electrical environments and extends battery life  DSP based technology enables reduction in the number of electronic components to lower failure rate  N+X redundancy up to 4 units increases system availability  Built-in manual bypass ensures continuous power to the load even if the UPS is under maintenance  Flexible arrangement of battery quantity from 34 to 50 pcs optimizes battery investment
  • 16. HPH Series 20-40kW Model HPH-20K HPH-20K-BN/B HPH-30K HPH-30K-BN/B HPH-40K HPH-40K-BN/B Power Rating 20kVA /20kW 30kVA /30kW 40 kVA/40kW Voltage 220/380 Vac; 230/400 Vac; 240/415 Vac Input Voltage Range - 40% ~ 20% (242 ~ 477/140 ~ 276 Vac) * * Output Voltage 220/380 Vac; 230/400 Vac; 240/415 Vac Overload Capability ≦105 %: continuous; 106%~≦125%: 10 minutes; 126%~≦150%: 1 minute; >150%: 1 second Battery Charging (Standard model) 5A 9A Battery Charging (HPH-BN/B*) 5A, 9A (option) Charge Voltage Float charge ±272 V ±2Vdc, Boost Charge ±280V ±2Vdc Typical Backup Time (HPH-BN/B*) (At 70% load with internal battery strings) 15 min 10 min 9.5 min Efficiency Online Mode: up to 96% ECO Mode: up to 99% Interface SMART Slot x 1, MINI Slot x 1, Parallel Port x 2, RS232 Port x 1, REPO Port x 1, Charger Detection Port x 1, Input Dry Contact x 2,Output Dry Contact x 6 Maintenance Bypass Switch Built-in *HPH-BN: UPS integrated battery model has no batteries inside HPH-B: UPS integrated battery model has batteries inside * *When input voltage is 242 ~ 324/140 ~ 187 Vac, the sustainable loading is from 70% to 100% of the UPS capacity.
  • 17. Summary Stored energy Uninterruptible power supply Applications –Networking –Data centers –Telecommunications –Medical –Banking –Industrial  N+X parallel reduncancy (up to 8 units) for reliability and flexibility, w/o extra hardware.  Economic mode for energy and operation cost savings.  Inbuilt automatic and manual bypass switch.  Inbuilt SRAM recording maximum 500 real-time event logs.  Compatible with generator installation.  6 configurable UPS status dry contact outputs.  Optional 12-pulse rectifier or filter for lower harmonic distortion.  Possibility for shared battery source enabling cost savings.  Custom order voltage rating.  Optional external battery cabinet. NT Series 20-500 kVA
  • 18. NT Series Specifications NT- 20 K 30 K 40 K 50 K 60K 80K 100K 120 K 160 K 200 K 260 K 320 K 400 K 500 K WxDxH (mm) 600 x 800 x 1400 800 x 830 x 1700 1200 x 830 x 1700 1600 x 995 x 1950 1900 x 995 x 1950 Weight (kg) 365 365 425 460 506 525 700 745 1050 1085 1680 1720 1920 2410 * The table above is based on 220/380 Vac rating. ** 500kVA model is assembled by two cabinets: Inverter (width=11m, 1760kg) and rectifier (width=8m, 650kg). ***Dimension and weight are for the standard model with 6pulse rectifier. NT-series generic specification Voltage 120/208, 220/380, 230/400, 240/415, 277/480 Vac (Three phase, 4 wire plus ground) Voltage Range ±20 % Interface RS232 x 1, RS485 x 1, SNMP slot x 1, Dry contact output x 6 Parallel Redundancy Maximum 8 units Input Harmonic Improvement Optional 12-pulse rectifier or filter SRAM Event Log Maximum 500 records Battery Start Yes
  • 19. Summary Stored energy Uninterruptible power supply Applications –Networking –Data centers –Telecommunications –Medical –Banking –Industrial IGBT-based UPS with AC-AC efficiency up to 96% 0.9 output power factor, and supporting leading power factor data center server, networking equipment Able to parallel for N+X redundancy, hot stand-by and support 2(N+1) configuration to meet level tier 4 reliability Wide input voltage range reduces battery discharging Advanced battery management optimizes battery performance and lifetime Field programmable sequential start-up 2 to 99 seconds Hot swappable fan design Optional Redundant fan design Ultron DPS Series 60-400 kVA
  • 20. DPS Series Specifications Model DPS 60 DPS 80 DPS 100 DPS 120 DPS 160 DPS 200 DPS 300 DPS 400 Power Rating 60kVA / 54kW 80kVA / 72kW 100kVA / 90kW 120kVA / 108kW 160kVA / 144kW 200kVA / 180kW 300kVA / 270kW 400kVA / 360kW Voltage 380/220, 400/230, 415/240 Vac (3 phase, 4-wire plus ground) Input Voltage Range 208~477 Vac* 242~477 Vac* Input Power Factor > 0.99 Current Harmonic Distortion < 3% (full load) Output Voltage 380/220, 400/230, 415/240 Vac (3 phase, 4-wire plus ground) Output Voltage Regulation ± 1% (static) Interface RS232 x 1, Smart slot x 2, Dry contact output x 6, Dry contact input x 2, Parallel port x 2, Battery cabinet temperature sensor x 4, REPO x 1 RS232 x 1, Smart slot x 2, Dry contact output x 6, Dry contact input x 2, Parallel port x 2, Battery cabinet temperature sensor x 4, Battery status detection x 1, REPO x 1 Parallel Link Up to 4 units Up to 8 units Efficiency AC-AC: Up to 96% ECO mode: Up to 99% WxDxH (mm) 520 x 975 x 1695 850 x 865 x 1950 1600 x 865 x 1950 Weight (kg) 300 330 360 390 697 1335 * When input voltage is 208~300 / 242~324 Vac, the sustainable loading is from 70% to 100% of the UPS capacity.
  • 21. Delta UPS – Modulon Family Three Phase Modular Online UPS - Up to 800 kW online UPS NH Plus Series 20 - 120kVA DPH Series 25 - 200 kW
  • 22. Summary Stored energy Uninterruptible power supply Applications –Networking –Data centers –Telecommunications –Medical –Banking –Industrial  Hot-swappable function providing uninterruptible power during module replacement.  N+X parallel reduncancy(up to 4 units, max. 480kVA) for reliability and flexibility, w/o extra hardware.  High input power factor (pf > 0.99) and low harmonic distortion (iTHD < 3%).  94% high efficiency saving operation cost.  Inbuilt automatic and manual bypass switch.  Inbuilt SRAM recording maximum 500 real-time event logs.  Multi-language LCD display and status LED indicators  Compatible with generator installation.  6 configurable UPS status dry contact outputs.  Optional kit for monitoring battery cabinet temperature. NH Plus Series 20-120 kVA
  • 23. NH Plus Series 20-120 kVA * Subject to reconfiguration of the UPS; Delta provides the configuration service. ** When input voltage is 208~300/120~173 Vac, the sustainable loading is from 70% to 100% of the UPS capacity. Model NHP-20K NHP-40K NHP-60K NHP-80K NHP-100K NHP-120K Power Rating* 20kVA /18kW 40kVA /36kW 60kVA /54kW 80kVA /72kW 100kVA/90kW 120kVA/108kW Voltage 380/220, 400/230, 415/240 (3 phase, 4-wire plus ground) Input Voltage Range 208 ~ 477 Vac (line-line) / 120 ~ 276 Vac (line-neutral)** Input Power Factor > 0.99 Input Current Harmonic Distortion < 3% (full load) Output Voltage 380/220, 400/230, 415/240 (3 phase, 4-wire plus ground) Other rating is available in another cabinet (I/P and O/P transformer is included) Connection Hard wire (terminal block) Interface RS232 x 1, SNMP slot x 2, Dry contact output x 6, Dry contact input x 2, Parallel port x 1, Battery cabinet temperature sensor x 4, Battery cabinet status detection x 1, Remote emergency power off x 1 Parallel Link Up to 4 units. Maximum 480 kVA External Battery Cabinet Optional WxDxH (mm) 520 x 910 x 1165 520 x 975 x 1695 Weight (kg) 112.5 128 230 260 350 380
  • 24. Summary Stored energy Uninterruptible power supply Applications –Data centers –Telecommunications –Network –Banking –Industrial  Advanced fault tolerance design achieved by self redundancy to guarantee operation continuity  Self-synchronization of power and control modules for continuous on-line operation even in the event of control module failure to avoid downtime caused by single point failure  Hot-swappable key modules and components to ensure Mean Time To Repair (MTTR) close to zero  Vertical expansion from 25kW to 200kW supporting N+X redundancy in a single rack enclosure to save footprint  Full rated power (kVA=kW) to maximize power availability  High operating efficiency of 95% at 30% light load and 96% from 50% load resulting in marked energy cost savings  Low harmonic pollution (iTHD<3%) to reduce upstream investment costs and meet demanding power requirements DPH Series 25-200kW
  • 25. DPH Series 25-200kW Model 25 50 75 100 125 150 175 200 Power Rating* 25kVA/kW 50kVA/kW 75kVA/kW 100kVA/kW 125kVA/kW 150kVA/kW 175kVA/kW 200kVA/kW Voltage 380/220, 400/230, 415/240 (3 phase, 4-wire plus ground) Input Voltage Range 176~276 / 305~477 V (When input voltage is 140/242~176/305 Vac, the sustainable loading is from 60% to 100% of the UPS capacity) Input Power Factor > 0.99 Input Current Harmonic Distortion < 3% (when input harmonic distortion is less than 1%) Output Voltage 380/220, 400/230, 415/240 Vac (3 phase, 4-wire plus ground) Interface Parallel port x 2, Smart slot x 2, Dry contact output x 6, Dry contact input x 6, SNMP card x 2, Battery dry contact x 6 Parallel Link Up to 4 units. Maximum 800 kW External Battery Cabinet Optional WxDxH (mm) 600 x 1090 x 2000 Weight (kg) 382 414 446 478 510 542 574 606
  • 27. DPR 850-48 DPR 2900-48 DPR 2900-48 DPR 3000-48 DPR 4000-48 DPR 6000-48 Power output 850 W 2900 W 2900 W 3000 W 4000 W 6000 W Efficiency 95.2% 96.4% 97.2% 98,0% 95.2% 96.5% Power density 30 W / in3 36.5 W / in3 36.5 W / in3 56,8 W / in3 27.3 W / in3 26.5 W / in3 Control and monitoring ORION, ORION eco, ORION c Hot-pluggable Yes Yes Yes Yes Yes Yes Dimensions (W x H x D) 51.8 x 40.0 x 247.2 mm 125.5 x 41.0 x 269.9 mm 125.5 x 41.0 x 269.9 mm 84,0 x 41.0 x 270.0 mm 82.0 x 86.9 x 377.9 mm 129.5 x 83.0 x 380.7 mm Weight 0.6 kg 2.0 kg 2.0 kg 1,4 kg 3.5 kg 5.2 kg Cooling Fan cooled with speed control Safety EN / IEC 60950; UL 60950; CAN / CSA – C22.2 EMI (radiated) EN 55022 class B Environment RoHS compliant Rectifiers
  • 28. Self Power - CellD Summary Stored energy Telecommunication
  • 29. CellD Systems CellD 20 CellD 40 CellD 100 CellD 125 (EVO) DPS 850B-48-2 DPS 850B-48-3 DPS 850B-48-6 DPS 2900B-48-3 DPS 2900B-48-3 Rectifier module DPR 850B-48 (max. 2 pcs.) DPR 850B-48 (max. 3 pcs.) DPR 850B-48 (max. 6 pcs.) DPR 2900B-48 (max. 3 pcs.) DPR 2900B-48 (max. 3 pcs.) Efficiency 95,2% 95.2% 95.2% 96.4% or 97,2% 96.4% or 97,2% Install power (max. config.) 1,7 kW 2.55 kW 5.1 kW 8.7 kW 8.7 kW Dimensions H x W x D 43.6 (1U) x 484.3(19’) x 280 mm 43.6 (1U) x 484.3(19’) x 280 mm 86.8(2U) x 484.3(19’) x 295 mm 86.8 (2U) x 484.3 (19’) x 323 mm 133.5 (3U) x 481.5 (19’) x 329 mm Weight 4.0 kg 4.1 kg 7.0 kg 7.0 kg 15 kg Input voltage range 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS Max. output current / max. installed power 26 A / 1,7 kW 40 A / 2.55 kW 100A / 5.1 kW 100A / 8.7 kW 125A / 8.7 kW Controller ORION Local interface Display, keypad, LEDs Remote monitoring Alarm relays, modem option, LAN, SNMP protocol
  • 30. CellD Systems CellD 300 (EVO2) DPS 2900B-48-3 19IN-5U DPS 2900B-48-5 19IN-5U DPS 2900B-48-6 19IN-6U DPS 2900B-48-3 21IN-4U DPS 2900B-48-6 21IN-5U Rectifier module DPR 2900B-48 (max. 3 pcs.) DPR 2900B-48 (max. 5 pcs.) DPR 2900B-48 (max. 6 pcs.) DPR 2900B-48 (max. 3 pcs.) DPR 2900B-48 (max. 6 pcs.) Efficiency 96.4% or 97,2% 96.4% or 97,2% 96.4% or 97,2% 96.4% or 97,2% 96.4% or 97,2% Install power (max. config.) 8.7 kW 14.5 kW 17.4 kW 8.7 kW 17.4 kW Dimensions H x W x D 222 (5U) x 479,7 (19’) x 315 mm 222 (5U) x 479,7 (19’) x 315 mm 266 (6U) x 479,7 (19’) x 315 mm 177 (4U) x 534 (21’) x 315 mm 222 (5U) x 534 (21’) x 315 mm Weight 13 kg 14 kg 14 kg 13 kg 14 kg Input voltage range 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS 80 - 300 VRMS Max. output current / max. installed power 250 A / 8,7 kW 250 A / 14,5 kW 250 A / 17.4 kW 250 A / 8.7 kW 250 A / 17.4 kW Controller ORION Local interface Display, keypad, LEDs Remote monitoring Alarm relays, modem option, LAN, SNMP protocol
  • 31. CellD Systems CellD 600 DPS 2900B-48-12 19IN-9U DPS 4000B-48-5 19IN-7U Rectifier module DPR 2900B-48 (max. 12 pcs.) DPR 4000B-48 (max. 5 pcs.) Efficiency 96.4% or 97,2% 95.2% Install power (max. config.) 34.8 kW 20 kW Dimensions H x W x D 399 (9U) x 480 (19’) x 375 mm 311 (7U) x 480 (19’) x 465 mm Weight 30 kg 25 kg Input voltage range 80 - 300 VRMS 80 - 300 VRMS Max. output current / max. installed power 600A / 34.8 kW 600A / 20 kW Controller ORION Local interface Display, keypad, LEDs Remote monitoring Alarm relays, modem option, LAN, SNMP protocol
  • 32. CellD Additional Elements Site Support cabinets SC600 SC770 SC1300 SC1800 SC2000 Internal space 12 U 15 U 27 U 38 U 42 U Height 620 mm 759 mm 1295 mm 1790 mm 1961 mm Width 600 mm Depth 450 or 600 mm Wall Box WB 5U WB 8U WB 12U 5 U / 19‘ 8 U / 19‘ 12 U / 19‘ 253 mm 387 mm 564 mm 548 mm 475 mm AC and/or DC Panel DPD/APD/DAPD 19IN-3U DPD /APD/DAPD 21IN-3U Operating voltage / Current (max.) AC: 230 / 400 V (1 or 3 ph) / Related to equipment DC: 20-60 V / 300A Internal space 24 modules (18 mm) 27 modules (18 mm) Dimensions H x W x D 133 (3U) x 480 (19’) x 190 mm 133 (3U) x 530 (21’) x 190 mm
  • 33. Cabinet Power - CabD Summary Stored energy Telecommunication
  • 34. CabD 600 CabD 1000 CabD 1500 CabD 2000 Standalone / Multicabinet Standalone Cabinet Multicabinet (Parallel option) Multicabinet (Parallel option) Multicabinet (Parallel option) Rectifier module DPR 6000 (max. 8 pcs), DPR 4000 (max.12 pcs), DPR 2900 (max.12 pcs) DPR 6000 (max. 12 pcs) DPR 4000 (max. 18 pcs), DPR 2900 (max. 24 pcs) DPR 6000 (max. 16 pcs), DPR 4000 (max. 24 pcs), DPR 2900 (max. 28 pcs) DPR 6000 ( max 20 pcs) DPR 4000 (max. 30 pcs), Max. output current / max. installed power 600A / 34.8 kW 1000 A / 72 Kw 1500A / 96 kW 2000A / 120 kW Efficiency 95.2% ... 97,2% 95.2% ... 97,2% 95.2 % ... 96,5 % 95.2 % ... 96,5 % AC configuration 3L+N+PE or 3L+PE Load and battery connection Configurable – modular design Controlling and monitoring ORION Operating temperature -5 - +45 °C CabD Systems
  • 35. CabD Systems CabD 3000 CabD 3000+ Standalone / Multicabinet Multicabinet (Parallel option) Multicabinet (Parallel option) Rectifier module DPR 6000 (max. 24 pcs), DPR 4000 (max.36 pcs) DPR 6000 (max. 24 pcs), DPR 4000 (max. 36 pcs) Max. output current / max. installed power 3000 A / 144 Kw 3000 A / 144 kW (scaled up horizontal DC bus bars) Efficiency 95.2% ... 96,5 % 95.2 % ... 96,5 % AC configuration 3L+N+PE or 3L+PE Load and battery connection Configurable – modular design Controlling and monitoring ORION Operating temperature -5 - +45 °C
  • 36. CabD Systems - options Controller Battery connection Battery connection Battery connection Controller shelf 1U Battery fuse TPS2 up to 4x 1600 A Battery fuse EFEN NH3 up to 4x 630 A Battery fuse EFEN NH2 up to 4x 400 A Load connection Load connection Load connection Load connection DPD 8x EFEN NH00 2..160 A DPD 7x NH02 100..400 A DPD 30x MCB 2..63 A DPD 13x 22x58 2..100 A
  • 38. APS 750B-230-8 19IN APS 1500B-230-8 19IN APS 2500B-230-8 19IN APS 2500B-230-24 CabD Inverter modules (Max. configuration) 8x TSI NOVA - 230Vac 8x TSI MEDIA - 230Vac 8x TSI BRAVO - 230Vac 24x TSI BRAVO - 230Vac Max. installed power 6 kVA / 4,2 kW 12 kVA / 9,6 kW 20 kVA / 16 kW 60 kVA / 48 kW Efficiency (EPC mode) 93 % 94 % 96 % 96 % AC configuration Input / Output One phase / One phase One phase / One phase or Three phases / three phases Output loads AC distribution Configurable (MCBs, RCDs, bulk type) - modular design Controlling and monitoring T2S - ORION Manual Bypass optional Inverter System
  • 39. Outdoor Systems - OutD Summary Stored energy Telecommunication
  • 40. OutD: V series OutD V Series Key advantages • Single or Multilayer wall design • -7dB(A) (lower than standard cabinets with the same cooling capacity) • Steel or aluminium outside walls • Flexible configuration - 19’ or 21’ racks, battery shelves, multiple PSU options (power supply systems), multiple cable management options • Multiple cooling options (AV, AC, Hybrid AC+AC) • Battery cooler (Separated battery compartment with advanced thermal insulation 40mm EPS and active cooling (TEC or AC) Dimensions OutD 0.7V H701 x W605 x D530mm - 12HU (plinth H100mm excl.) OutD 1.2V H1257 x W708 x D752mm - 21HU OutD 1.8V H1860 x W708 x D752mm - 35HU OutD 2.0V H2047 x W808 x D852mm - 39HU OutD 2.2V H2247 x W808 x D852mm - 44HU Material Steel or Aluminium, Single or multilayer with optional thermal insulation Lifetime Steel : up to 15 year, Aluminium: up to 20 years Cooling options AV (Air Ventilation), HEX (Heat Exchanger,) AC (Air con), Hybrid AV+AC (Hybrid cooling Air Ventilation + Air con)
  • 41. OutD: M series OutD M Series Key advantages • Single or Multilayer wall design • -7dB(A) (lower than standard cabinets with the same cooling capacity) • Flexible configuration - 19’ or 21’ racks, battery shelves, multiple PSU options (power supply systems), multiple cable management options • Battery box extension (battery cooler) • IP20 equipment extension • Side by side connection available Dimensions OutD 1.5M H1500 x W770 x D852mm - 28HU OutD 1.8M H1829 x W770 x D852mm - 35HU OutD 2.0M H2052 x W870 x D952mm - 40HU Material Steel or Aluminium, Single or multilayer with optional thermal insulation Lifetime Steel : up to 15 year, Aluminium: up to 20 years Cooling Options AV (Air Ventilation), HEX (Heat Exchanger,) AC (Air con), Hybrid AV+AC (Hybrid cooling + Air Ventilation + Air con)
  • 42. Small Cell Power Summary Stored energy Telecommunication
  • 43. Small Cell Power – DPR 1000B-45 Small Cell – Outdoor Rectifier Dimensions H360 x W209,8 x D88,8mm EN 60529 class IP65 Material Aluminium Weight 6,4kg User Interface Status Indication Mounting Lamppost, pole or wall mountable Cooling options Natural Cooling PSU Power 1000W / 42 - 58Vdc EMC EN55022, CISPR22, FCC 15 class B Operating temperature -40°C to +60 °C (linear power de-rating to 50% load from 46°C to 60°C) Humidity (relative) 95%, non-condensing (Max.) Connectors AC input: Amphenol PWC-03RMMS-LC7002 x 1 Dc output: Amphenol PWC-03RMFS-LC7002 x 2 Alarms: Amphenol CD-09RMFS-LC7001 x 1 Options Service LED light, Alarm terminals
  • 44. Small Cell Design - BoxD Small Cell - BoxD Dimensions H684 x W489 x D312mm EN 60529 class up to IP55 Material Enclosure: Aluminium Internal Parts: Galvanized steel Wall structure Single layer with sun radiation screen Lifetime Steel: 10+ years Mounting Wall / Pole Cooling options HEX (Heat Exchanger) 15W/K AV (Air Ventilation)* TEC (Peltier Module)* PSU Power 2x850W / 48Vdc Battery supervision None LVD only ORION + Shunt/LVD Battery backup 19” space - 14Ah 24Ah 2.5U 1U - Cable glands 4xPG16 4xPG13.5 2xPG11 Options Service LED light, Alarm terminals
  • 45. Controller and network monitoring Summary Stored energy Telecommunication
  • 46. Battery management, supervision and control (Pb/LI) incl. Battery profile management Remote communication via LAN, SNMP, Modbus and I-Phone App incl. enhanced security by SNMP V3 and IP filtering Power System and rectifier management and control incl. efficiency mode, alarming and parameter setting Easy configuration management including inventory reporting, language support and configurable data logging features Full site control and management of: • Gensets • Batteries • Cooling devices (Aircon, HEX, fans) • Hybrid mix • Site access • Site inventory • IP camera Smart metering and alarming of: • Site energy consumption • Temperature & Humidity • Smoke detector • Flood detector • Intrusion detector • Any kind of other external devices Easy integration of hybrid energy sources • Solar • Wind • Genset 2017 update: • Upgraded with touch panel • 1GB Lan connection -> IT network integration • New µC and more memory • 25% less power consumption • Micro SD slot -> simplified field service 1 2 3 4 5 6 7 ORION Controller
  • 47. ORION Controller ORION c • Orion ID E1 - TPS1020028A • Full functionality, all features • Orion ID C1 - TPS1020029A • Full functionality, all features • Used for upgrading systems originally installed with PSC3 controller • Orion ID G1 - TPS1020030A • Limited functionality for low cost applications ORION eco ORION Controller