AC Voltage Test System with Resonant Reactor


Applications                                                  The main advantage of resonant test systems is the low
                                                              power demand, because only the losses in the test circuit
Resonant Test Systems is applied for the generation of        must be replaced from the power supply. The quality
a continuously variable alternating (AC) voltage of a fixed   factor Q which is the relation between the test power S
frequency (mainly 50 or 60 Hz) for high-voltage (HV)          and the loss power P ranges between Q = 10 and values
routine, type and development testing of capacitive test      up to 100, this means only 10 to 1 % of the test power
objects. They can also be applied for HV on-site tests, but   must be supplied. A resonant test system is remarkably
POWER offers for that application the more economic           lighter, cheaper and more economic than an AC
solution of frequency-tuned resonant test systems             transformer test system and should be applied if the test
.                                                             objects are capacitive. In case of a disruptive discharge
Capacitive test objects are cables, capacitors, gas           the test object is not destroyed, because the systems
insulated switchgear (GIS), but also large rotating           goes out of resonance. POWER resonant test systems
machines, instrument and power transformers (for applied      are characterized by a very modern system configuration
voltage tests). Resonant test systems enable not only         and have proven highest reliability.
HVAC tests at 50/60 Hz, but also at higher or lower
frequency (10-300 HZ) and dynamic tests with fast             Tunable inductance reactor modules for series resonant
voltage changes (e. g. for capacitors). Because of their      circuits are available between 250 and 1200 kV and test
precise sine-wave, resonant test systems are very well        power between 1000 and 20000 kVA
suited for the combinations of HVAC withstand tests with
partial discharge (PD) measurement. POWER adapts the          Tunable frequency modules for series resonant circuits
resonant test systems to the requirements of the relevant     are available between 100 and 1600 kV and test power
standards and the demand of the customer.                     between 50 and 9000kVA.(Typical Frequency adjustment
                                                              between 20-300 Hz)




    1600kV 10A Module Tunable             350kV 10A Tank Type Tunable              1000kV 5A Tunable Frequency
    Reactor Resonant System               Reactor Resonant System                  Reactor Resonant System(Oil
                                                                                   immersed Type)
Fig. 1:
                                                                                       Principle circuit diagrams (Te-exciter
                                                                                       transformer; RT and RL-loss resistors;
                                                                                       L-variable       inductance;   THV-HV
                                                                                       transformer; C-test object; RP and
                                                                                       RS-loss resistors; CO-basic load)




Fundamentals

The connection of an HV reactor (inductance L) to an capacitive test object (C) forms an oscillating circuit with the natural
frequency.
f = 1/2π   √ LC.
By a variable inductance this frequency can be tuned to that of the power supply (e. g. 50 Hz) which means resonance
(Fig. 1). The capacitive test power S exceeds the feeding power P according to the quality factor Q. The quality factor Q of
the whole circuit is the combination of that of the test system QA and that of the test object QP by:
Q = QA × QP / (QA + QP) (1)
For the more important series resonant circuits (Fig. 1a) resonance is connected with the increase of the voltage from the
exciting voltage Ue to the test voltage U:
U = Q × Ue. (2)
Parallel resonant circuits can be understood as HV current compensation by a variable inductance in parallel to a HV
test transformer (Fig. 1b). In that case the voltage is determined by the ratio of the HV transformer. Parallel resonance is
only applied if capacitances or losses of the test object are not stable (e. g. at rotating machines) or if the tests include
dynamic processes.


The inductance of the HV reactor can be varied only in a certain range (e. g. Lmax = 20 Lmin), for series resonance circuits
the load capacitance can be varied in a corresponding limited load range (Cmax = 20 Cmin). The system must be equipped
with a basic load capacitor CO >Cmin which enables no-load operation, but reduces the test object capacitance to (Cmax –
CO). Fig. 2 shows the load voltage characteristic for a system with two taps at the reactor, each corresponding to a certain
inductance and voltage. In the double logarithmic load-voltage characteristic (Fig. 2) both, powers S and currents I, are
given by straight lines. When the system is e. g. be designed according to the constant current of I1, the hatched area
cannot be used because of too high current I2. A clear definition of the necessary load-voltage requirement including duty
cycle is the basis for an economic selection of a resonant circuit.
Fig. 2: Load-voltage characteristic of a series resonant system with a reactor of two taps

Standards:

GB10229                        《 Reactor 》

JB/T964.1                       《Test Transformer》

GB1094.3                        《Electric Transformer》Third Part Insulation Level and Insulation Test

GB/T 16927.1                    《High Voltage Test Technology》 First Part Common Test Requirements

GB/T 16927.2                    《High Voltage Test Technology》 Second Part Measurement System

GB/7354                         《Partial Discharge Test》

GB/7328                          《Transformer and Reactor’s Sound Level Measurement》

JB 8749                         《Voltage Regulator’s General Technologies’ Requirements》

JB/T8638                         《Voltage Regulator Test Guidelines》First Part

JB/T563                         《Coupling Capacitor and Capacitor Divider Placing Order Technology Requirement》

GB2536                          《Transformer Oil》


Ambient Conditions for the AC Test Equipment

- Height above sea level                                                       ≤1000 m
 for each add. 100 m, the HV rating must be decreased by                       1%

- Relative humidity in main hall under non condensing conditions               90 %

- Temperature averaged over 24 h for H.V. components                           min. 0 °C, max. + 30 °C

- Extreme temperatures for H.V. components                                     min. - 5 °C, max. + 40 °C

- Temperature for electronic controls
   (equipment to operate with the specified measuring errors)                  min. + 15 °C, max. + 25 °C
The test system includes following main components:

 1. Tunable series resonant reactor (50Hz/60Hz) of (20-300Hz)
 2. Voltage Regulator (50Hz/60Hz) or Tunable Frequency Power Source (20-300Hz)
 3. Capacitive Voltage Divider (adding Inductance is a High Voltage Filter)
 4.    Resonant capacitor(also coupling capacitor for PD Measuring System)
 5. Manual or Automatic Control and Measuring System
 6. Power Noise Filter (50Hz/60Hz)
 7.    Exciter transformer




Available Options
      Air-cushion base frame (AeroGo)
      HV filter inductance for coupling capacitor
      Additional HV connections
      Partial Discharge detectors
      Other devices upon request




Technical Data



Tunable Inductance Reactor:


             Type              Rated Power          Rated current     Rated Voltage   Weight
                                    (kVA)                (A)                  (kV)     (kg)
         XZL-300/200                300                  1.5                  200     2325
         XZL-250/250                250                  1                    250     2675
         XZL-500/250                500                  2                    250     2890
         XZL-350/350                350                  1                    350     4520
         XZL-400/400                400                  1                    400     4600
         XZL-800/400                800                  2                    400     4750
        XZL-1200/400                1200                 3                    400     7500
         XZL-600/600                600                  1                    600     5250
        XZL-1200/600                1200                 2                    600     7200
        XZL-1800/600                1800                 3                    600     9600
        XZL-2400/600                2400                 4                    600     15510
         XZL-800/800                800                  1                    800     9600
        XZL-1600/800                160                  2                    800     9900
        XZL-3200/800                3200                 4                    800     19650
Tunable Frequency Reactor:


                           Rated          Rated      Rated          Nominal      Frequency   Weight
            Type           Power     Current(A)    Voltage(kV)   Inductance(H)   Range(Hz)    (kg)
                           (kVA)
        XZF-200/200         200            1           200            600                     850
        XZF-250/250         250            1           250            800                    1450
        XZF-500/250         500            2           250            400                    1850
        XZF-400/400         400            1           400           1200                    2200
        XZF-800/400         800            2           400            640                    2800
       XZF-1600/400        1600            4           400            329                    3100
       XZF-2400/600        2400            4           600            480         20-300     4100
       XZF-3600/600        3600            6           600            320                    4300
       XZF-3200/800        3200            4           800            600                    5200
       XZF-4800/800        4800            6           800            400                    6000
       XZF-6250/250        6250            25          250            35                     5100
       XZF-3750/250        3750            15          250            60                     4750
       XZF-2500/250        2500            10          250            90                     3900
       XZF-1250/250        1250            5           250            150                    2200




For further information please contact:


Power Electric Co ., Ltd
Add: No.9 longchuan North Road, Jiangdu,Yangzhou City, Jiangsu province,China
Tel: :+86-514-86688088
Fax: 86- 514-86688588
E-mail: sales@powerhv.com
Http:// www.powerhv.com

More Related Content

What's hot

Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityParth Patel
 
The admittance model and network calculation
The admittance model and network calculationThe admittance model and network calculation
The admittance model and network calculationBalaram Das
 
Dc motor speed controller by pwm technique
Dc motor speed controller by pwm techniqueDc motor speed controller by pwm technique
Dc motor speed controller by pwm techniqueWeb Design & Development
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.Hemendra Kumar Rajput
 
Impulse testing of transformer
Impulse testing of transformerImpulse testing of transformer
Impulse testing of transformerPreet_patel
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEJamil Abdullah
 
Power factor correction
Power factor correctionPower factor correction
Power factor correctionAbdur rehman
 
Presentation on Power Transformer
Presentation on Power TransformerPresentation on Power Transformer
Presentation on Power TransformerAjay Maurya
 
Mathematical models of electric machines
Mathematical models of electric machinesMathematical models of electric machines
Mathematical models of electric machinesvijayabhaskar83
 
Report On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationReport On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationEkram Bin Mamun
 
Ee 791 drives lab maual
Ee 791 drives lab maualEe 791 drives lab maual
Ee 791 drives lab maualDivya15121983
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensationVikas Saini
 
A Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv SubstationA Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv SubstationSubhrajit Ghosh
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Power System Operation
 

What's hot (20)

Impacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power QualityImpacts of Distributed Generation on Power Quality
Impacts of Distributed Generation on Power Quality
 
The admittance model and network calculation
The admittance model and network calculationThe admittance model and network calculation
The admittance model and network calculation
 
Dc motor speed controller by pwm technique
Dc motor speed controller by pwm techniqueDc motor speed controller by pwm technique
Dc motor speed controller by pwm technique
 
presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.presentation on substation layout and BUS bar arrangement.
presentation on substation layout and BUS bar arrangement.
 
Impulse testing of transformer
Impulse testing of transformerImpulse testing of transformer
Impulse testing of transformer
 
GENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGEGENERATING OF HIGH ALTERNATING VOLTAGE
GENERATING OF HIGH ALTERNATING VOLTAGE
 
Substation overview
Substation overviewSubstation overview
Substation overview
 
Power factor correction
Power factor correctionPower factor correction
Power factor correction
 
Unit5:- D.C Machines
Unit5:- D.C MachinesUnit5:- D.C Machines
Unit5:- D.C Machines
 
Fault level calculations
Fault level calculationsFault level calculations
Fault level calculations
 
Presentation on Power Transformer
Presentation on Power TransformerPresentation on Power Transformer
Presentation on Power Transformer
 
Mathematical models of electric machines
Mathematical models of electric machinesMathematical models of electric machines
Mathematical models of electric machines
 
Harmonics
HarmonicsHarmonics
Harmonics
 
Report On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-StationReport On Industrial Tour At Khulshi Grid Sub-Station
Report On Industrial Tour At Khulshi Grid Sub-Station
 
Generador
GeneradorGenerador
Generador
 
Ee 791 drives lab maual
Ee 791 drives lab maualEe 791 drives lab maual
Ee 791 drives lab maual
 
66 kv substation
66 kv substation66 kv substation
66 kv substation
 
Reactive power compensation
Reactive power compensationReactive power compensation
Reactive power compensation
 
A Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv SubstationA Training Report Of Saltlake 132/33kv Substation
A Training Report Of Saltlake 132/33kv Substation
 
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
Short Circuit Calculation Symmetrical & Asymmetrical Fault Currents ?
 

Similar to Resonant Test System

Himalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-SystemHimalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-SystemFang Sam
 
Power Distribution Report of THE NEOTIA UNIVERSITY CAMPUS
Power Distribution Report of  THE NEOTIA UNIVERSITY CAMPUSPower Distribution Report of  THE NEOTIA UNIVERSITY CAMPUS
Power Distribution Report of THE NEOTIA UNIVERSITY CAMPUSSaikat Bhandari
 
Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)FunExplode
 
Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination designNaresh Surisetti
 
Ac Test Transformer
Ac Test TransformerAc Test Transformer
Ac Test Transformerkennypowerhv
 
Output power meter
Output power meterOutput power meter
Output power meterajeet singh
 
Power transformers rating
Power transformers ratingPower transformers rating
Power transformers ratingLeonardo ENERGY
 
350kV 8000KVA series resonant cable test system
350kV 8000KVA series resonant cable test system350kV 8000KVA series resonant cable test system
350kV 8000KVA series resonant cable test systemJohnny Chan
 
Power Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPower Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPoornima D
 
KG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meterKG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meterNIHON DENKEI SINGAPORE
 
Kg catalogue dc electronic load distributed by Nihon Denkei
Kg catalogue dc electronic load  distributed by Nihon DenkeiKg catalogue dc electronic load  distributed by Nihon Denkei
Kg catalogue dc electronic load distributed by Nihon DenkeiNIHON DENKEI SINGAPORE
 

Similar to Resonant Test System (20)

Ct & pt specification
Ct & pt specificationCt & pt specification
Ct & pt specification
 
Himalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-SystemHimalayal-AC-Resonant-Test-System
Himalayal-AC-Resonant-Test-System
 
Power Distribution Report of THE NEOTIA UNIVERSITY CAMPUS
Power Distribution Report of  THE NEOTIA UNIVERSITY CAMPUSPower Distribution Report of  THE NEOTIA UNIVERSITY CAMPUS
Power Distribution Report of THE NEOTIA UNIVERSITY CAMPUS
 
Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)Installation testing and_commissioning_o (1)
Installation testing and_commissioning_o (1)
 
Insulation co cordination design
Insulation co cordination designInsulation co cordination design
Insulation co cordination design
 
Aec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTUAec manual for III SEM ECE Students VTU
Aec manual for III SEM ECE Students VTU
 
Lsa50.2
Lsa50.2Lsa50.2
Lsa50.2
 
Ac Test Transformer
Ac Test TransformerAc Test Transformer
Ac Test Transformer
 
RGPV EX7102 UNIT II
RGPV EX7102 UNIT IIRGPV EX7102 UNIT II
RGPV EX7102 UNIT II
 
Output power meter
Output power meterOutput power meter
Output power meter
 
Power transformers rating
Power transformers ratingPower transformers rating
Power transformers rating
 
General Power Quality
General Power QualityGeneral Power Quality
General Power Quality
 
350kV 8000KVA series resonant cable test system
350kV 8000KVA series resonant cable test system350kV 8000KVA series resonant cable test system
350kV 8000KVA series resonant cable test system
 
Sub station design
Sub station designSub station design
Sub station design
 
Sub station training
Sub station trainingSub station training
Sub station training
 
Power Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptxPower Electronics - Phase Controlled Converters.pptx
Power Electronics - Phase Controlled Converters.pptx
 
Transformer basic
Transformer basicTransformer basic
Transformer basic
 
KG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meterKG Electronic load DC power supply Ripple and Noise meter
KG Electronic load DC power supply Ripple and Noise meter
 
Kg catalogue dc electronic load
Kg catalogue dc electronic loadKg catalogue dc electronic load
Kg catalogue dc electronic load
 
Kg catalogue dc electronic load distributed by Nihon Denkei
Kg catalogue dc electronic load  distributed by Nihon DenkeiKg catalogue dc electronic load  distributed by Nihon Denkei
Kg catalogue dc electronic load distributed by Nihon Denkei
 

Resonant Test System

  • 1. AC Voltage Test System with Resonant Reactor Applications The main advantage of resonant test systems is the low power demand, because only the losses in the test circuit Resonant Test Systems is applied for the generation of must be replaced from the power supply. The quality a continuously variable alternating (AC) voltage of a fixed factor Q which is the relation between the test power S frequency (mainly 50 or 60 Hz) for high-voltage (HV) and the loss power P ranges between Q = 10 and values routine, type and development testing of capacitive test up to 100, this means only 10 to 1 % of the test power objects. They can also be applied for HV on-site tests, but must be supplied. A resonant test system is remarkably POWER offers for that application the more economic lighter, cheaper and more economic than an AC solution of frequency-tuned resonant test systems transformer test system and should be applied if the test . objects are capacitive. In case of a disruptive discharge Capacitive test objects are cables, capacitors, gas the test object is not destroyed, because the systems insulated switchgear (GIS), but also large rotating goes out of resonance. POWER resonant test systems machines, instrument and power transformers (for applied are characterized by a very modern system configuration voltage tests). Resonant test systems enable not only and have proven highest reliability. HVAC tests at 50/60 Hz, but also at higher or lower frequency (10-300 HZ) and dynamic tests with fast Tunable inductance reactor modules for series resonant voltage changes (e. g. for capacitors). Because of their circuits are available between 250 and 1200 kV and test precise sine-wave, resonant test systems are very well power between 1000 and 20000 kVA suited for the combinations of HVAC withstand tests with partial discharge (PD) measurement. POWER adapts the Tunable frequency modules for series resonant circuits resonant test systems to the requirements of the relevant are available between 100 and 1600 kV and test power standards and the demand of the customer. between 50 and 9000kVA.(Typical Frequency adjustment between 20-300 Hz) 1600kV 10A Module Tunable 350kV 10A Tank Type Tunable 1000kV 5A Tunable Frequency Reactor Resonant System Reactor Resonant System Reactor Resonant System(Oil immersed Type)
  • 2. Fig. 1: Principle circuit diagrams (Te-exciter transformer; RT and RL-loss resistors; L-variable inductance; THV-HV transformer; C-test object; RP and RS-loss resistors; CO-basic load) Fundamentals The connection of an HV reactor (inductance L) to an capacitive test object (C) forms an oscillating circuit with the natural frequency. f = 1/2π √ LC. By a variable inductance this frequency can be tuned to that of the power supply (e. g. 50 Hz) which means resonance (Fig. 1). The capacitive test power S exceeds the feeding power P according to the quality factor Q. The quality factor Q of the whole circuit is the combination of that of the test system QA and that of the test object QP by: Q = QA × QP / (QA + QP) (1) For the more important series resonant circuits (Fig. 1a) resonance is connected with the increase of the voltage from the exciting voltage Ue to the test voltage U: U = Q × Ue. (2) Parallel resonant circuits can be understood as HV current compensation by a variable inductance in parallel to a HV test transformer (Fig. 1b). In that case the voltage is determined by the ratio of the HV transformer. Parallel resonance is only applied if capacitances or losses of the test object are not stable (e. g. at rotating machines) or if the tests include dynamic processes. The inductance of the HV reactor can be varied only in a certain range (e. g. Lmax = 20 Lmin), for series resonance circuits the load capacitance can be varied in a corresponding limited load range (Cmax = 20 Cmin). The system must be equipped with a basic load capacitor CO >Cmin which enables no-load operation, but reduces the test object capacitance to (Cmax – CO). Fig. 2 shows the load voltage characteristic for a system with two taps at the reactor, each corresponding to a certain inductance and voltage. In the double logarithmic load-voltage characteristic (Fig. 2) both, powers S and currents I, are given by straight lines. When the system is e. g. be designed according to the constant current of I1, the hatched area cannot be used because of too high current I2. A clear definition of the necessary load-voltage requirement including duty cycle is the basis for an economic selection of a resonant circuit.
  • 3. Fig. 2: Load-voltage characteristic of a series resonant system with a reactor of two taps Standards: GB10229 《 Reactor 》 JB/T964.1 《Test Transformer》 GB1094.3 《Electric Transformer》Third Part Insulation Level and Insulation Test GB/T 16927.1 《High Voltage Test Technology》 First Part Common Test Requirements GB/T 16927.2 《High Voltage Test Technology》 Second Part Measurement System GB/7354 《Partial Discharge Test》 GB/7328 《Transformer and Reactor’s Sound Level Measurement》 JB 8749 《Voltage Regulator’s General Technologies’ Requirements》 JB/T8638 《Voltage Regulator Test Guidelines》First Part JB/T563 《Coupling Capacitor and Capacitor Divider Placing Order Technology Requirement》 GB2536 《Transformer Oil》 Ambient Conditions for the AC Test Equipment - Height above sea level ≤1000 m for each add. 100 m, the HV rating must be decreased by 1% - Relative humidity in main hall under non condensing conditions 90 % - Temperature averaged over 24 h for H.V. components min. 0 °C, max. + 30 °C - Extreme temperatures for H.V. components min. - 5 °C, max. + 40 °C - Temperature for electronic controls (equipment to operate with the specified measuring errors) min. + 15 °C, max. + 25 °C
  • 4. The test system includes following main components: 1. Tunable series resonant reactor (50Hz/60Hz) of (20-300Hz) 2. Voltage Regulator (50Hz/60Hz) or Tunable Frequency Power Source (20-300Hz) 3. Capacitive Voltage Divider (adding Inductance is a High Voltage Filter) 4. Resonant capacitor(also coupling capacitor for PD Measuring System) 5. Manual or Automatic Control and Measuring System 6. Power Noise Filter (50Hz/60Hz) 7. Exciter transformer Available Options Air-cushion base frame (AeroGo) HV filter inductance for coupling capacitor Additional HV connections Partial Discharge detectors Other devices upon request Technical Data Tunable Inductance Reactor: Type Rated Power Rated current Rated Voltage Weight (kVA) (A) (kV) (kg) XZL-300/200 300 1.5 200 2325 XZL-250/250 250 1 250 2675 XZL-500/250 500 2 250 2890 XZL-350/350 350 1 350 4520 XZL-400/400 400 1 400 4600 XZL-800/400 800 2 400 4750 XZL-1200/400 1200 3 400 7500 XZL-600/600 600 1 600 5250 XZL-1200/600 1200 2 600 7200 XZL-1800/600 1800 3 600 9600 XZL-2400/600 2400 4 600 15510 XZL-800/800 800 1 800 9600 XZL-1600/800 160 2 800 9900 XZL-3200/800 3200 4 800 19650
  • 5. Tunable Frequency Reactor: Rated Rated Rated Nominal Frequency Weight Type Power Current(A) Voltage(kV) Inductance(H) Range(Hz) (kg) (kVA) XZF-200/200 200 1 200 600 850 XZF-250/250 250 1 250 800 1450 XZF-500/250 500 2 250 400 1850 XZF-400/400 400 1 400 1200 2200 XZF-800/400 800 2 400 640 2800 XZF-1600/400 1600 4 400 329 3100 XZF-2400/600 2400 4 600 480 20-300 4100 XZF-3600/600 3600 6 600 320 4300 XZF-3200/800 3200 4 800 600 5200 XZF-4800/800 4800 6 800 400 6000 XZF-6250/250 6250 25 250 35 5100 XZF-3750/250 3750 15 250 60 4750 XZF-2500/250 2500 10 250 90 3900 XZF-1250/250 1250 5 250 150 2200 For further information please contact: Power Electric Co ., Ltd Add: No.9 longchuan North Road, Jiangdu,Yangzhou City, Jiangsu province,China Tel: :+86-514-86688088 Fax: 86- 514-86688588 E-mail: sales@powerhv.com Http:// www.powerhv.com