Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66
www.ijera.com 62 | P a g e
Comparative Study of Response of Structures Subjected To Blast
and Earthquake Loading
Aditya C. Bhatt1
, Snehal V. Mevada2
, Sumant B. Patel3
1
P.G. Student, 2
Assistant Professor, 3
Associate Professor,
Structural Engineering Department,
Birla Vishvakarma Mahavidyalaya [Engineering College], Vallabh Vidyanagar, Gujarat, India.
ABSTRACT
The increase in the number of terrorist attacks especially in the last few years has shown that the effect of blast
load on building is a serious challenge that should be taken in to consideration for designing of structures. This
type of loading damages the structures, externally as well as internally. Hence the blast load should be
considered with same importance as earthquake load. The present study includes the comparative performance
of G+3 storey building subjected to blast and earthquake loading using ETABS. For four storey building using
different input parameters like charge explosive, stand-off distance and layout of building the blast pressure are
conducted and linear time history analysis is carried out. Comparative study for blast and earthquake loading is
carried out for different parameters like maximum storey displacement, storey drift and quantity of materials.
Safe charge explosive and safe stand-off distance are obtained for the RCC structure with the sections of
structural elements same as per the requirement for earthquake resistance. Displacement is higher for the blast
loading as compared to earthquake loading and very high for the storey at which blast load is applied. Quantity
of concrete is 40 percentages higher for blast resistant building than the earthquake resistant building.
Keywords: blast, earthquake, explosion, charge weight, safe stand-off distance
I. INTRODUCTION
Protecting civilian buildings from the threat of
terrorist activities is one of the most essential
challenges for structural engineers. Events of the
past decades have greatly increased the
attentiveness of structural designers about the threat
of terrorist attacks using explosive devices.
Extensive research into structural analysis
considering blast effects and techniques to protect
buildings has been initiated in many countries to
build up methods for protecting critical
infrastructure and the built environment. There are
a number of means available to prevent a booming
terrorist attack on a building [3]
. Structures analysed
for blast loads are subjected to entirely different
types of load than that considered in conventional
design. Here structures are subjected to quickly
moving shock wave which may exert pressures
many times greater than those experienced under
the greatest of hurricanes. However, in blast
phenomenon, the peak intensity lasts for a very
small duration only [1]
. The blast can generally
categorize as external and internal blast. External
blast can further recognized as surface burst or air
burst.
An explosion which is located at a distance from
and above the structure is known as air burst
explosion, while surface blast will occur when
detonation is situated close to or on the ground. An
internal or confined explosion will produce shock
loads or, gas pressure loads from the confinement
of the products of the explosion. This pressure has
a long duration in comparison to that of the shock
pressure, due to external explosion. Due to highly
uncertainty in predicting blast loads, it is difficult
to construct blast proof building. But various
structural and non-structural precautions can be
taken to minimize structural damage and physical
injuries [5]
.
Shallan et al. [3]
showed that the effect of blast load
decrease with increasing the standoff distance from
the building and with variation of the aspect ratios
of the buildings there is no variation in the
displacement of the column in the face of the blast
load but with increasing the aspect ratio the effect
of blast load decrease in other element in the
building. Kashif and Varma (2015) [1]
analysed a
five storey RCC symmetric building for blast load
for 100 kg and 500 kg of Tri-Nitro-Toluene placed
at 30 m distance from point of explosion. It was
concluded that building was not behaving as a
RESEARCH ARTICLE OPEN ACCESS
Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66
www.ijera.com 63 | P a g e
cantilever structure under blast load, which is
different from the earthquake and wind. Results of
the performance level of building, maximum
displacement , plastic hinges locations were
defined and compared for both 100 kg and 500 kg
TNT explosives.
Based on the literature review carried out, it is
observed that some researchers have investigated
the effect of blast load on structures. However there
is a need for detail parametric investigation in this
area. Following are the main objective of the
present study. i ) To obtain the response of multi
storied structures under blast and earthquake
loading. ii) To obtain the safe standoff distance for
multi storied building which is safe in earthquake.
1.1 Blast Load And Earthquake Load
Similarities and differences between seismic and
blast loading are noticeable. Both of these loads are
dynamic loads and they produce dynamic structural
response. The structural behavior in response to
these loads is inelastic as well. The focus of
structural design against these loads is on life safety
as opposed to preventing structural damage.
Differences between blast and seismic loading are
presented in Figure 1. [7]
II. NUMERICAL STUDY
In the numerical study carried out herein, the G + 3
storied RCC building is considered.. Figure 2
shows the plan and 3D view of the building
considered. Table 1 represents the physical
properties and input parameters of the considered
building. The analysis and design is carried out in
ETABS software.
For G+3 storied RCC building, both blast and
earthquake loading are applied. Comparative study
has been carried out for the same for different
criteria like storey displacement, storey drift and
quantity of concrete. For the earthquake resistant
building, calculation of both safe charge-explosive
and safe stand-off distance have been carried out
2.1 Methodology
First of all consider the buildings subjected to a
blast equivalent in yield to some tonne of TNT at a
certain standoff distance. For the dynamic analysis
of structures, the blast effects are most
conveniently represented by a loading-time history
which is applied to the structural members as
transient loading. The magnitude and the pressure-
time history of the blast load is calculated as per IS
4991-1968. Then pressure calculated is applied as
UDL on column. Linear time history analysis is
carried out and the response of structure is obtained
subjected to blast loading.
2.2 Blast Load Calculation as per the IS
4991:1968.
For the study carried out herein explosive of 0.1
tonne TNT equivalent is considered. Building is
situated 21 m from the ground zero. Analysis of the
same building is carried out for Blast load
combinations. Table 2 shows the blast parameters
for 0.1 Tonne TNT and 21 m stand-off distance.
Table 3 reprents the load combination considered
in the present study.
2.2.1 Characteristics of the blast load
Scaled distance = 21/ (0.1) (1/3)
= 45.243 m
Assuming pa = 1 kg/cm² ( From IS 4991:1968,
Table: 1)
Sr.
No.
Parameter Value
1 Height of the story 3.5 m
2 Span of each bay 5 m
3 Plan dimension of
building
15 m x 15
m
4 Number of storey G+3
5 Grade of concrete M25
6 Height of plinth 1.5 m
7 Zone V
8 Importance factor 1
9 Soil type Medium
Figure 1: BLAST AND SEISMIC WAVES
Table 1: PROPERTIES OF BUILDING
Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66
www.ijera.com 64 | P a g e
q0 = 0.142 kg/cm2
t0 =31.25 * (0.1) 0.33
= 14.505 milliseconds
td =21.6 * (0.1) 0.33
= 10.026 milliseconds
M = 1.25
a = 344 m/s
U = 0.43 m/milliseconds
2.2.2 Blast Pressure on the building
S is lesser of H or B/2 = 7 m
tc = 3S/U = 10.026 milliseconds
tt = l/U = 34.884 milliseconds
tr = 4S/U = 65.116 milliseconds
As tr>td there is no pressure on back face
For roof & sides (from IS 4991:1968 Table 2)
For front face Cd = 1
For roof and side face Cd = -0.4
ps0 + Cdq0 = 59.15 kN/m²
EARTHQUAKE BLAST
1.5*DL+1.5*LL 1.5*DL+1.5*LL
1.2*DL+1.2*LL±1.2*EQX±1
.2*EQY
1.2*DL+1.2*LL+
1*BL
1.5*DL+±1.5*EQX±1.5*EQ
Y
1.5*DL+1*BL
0.9*DL+±1.5*EQX±1.5*EQ
Y
0.9*DL+1*BL
Figure 3 shows the isometric view of the building
in which blast load is applied as udl to the column.
Figure 4 shows the pressure-time diagram for the
front and side faces for the considered blast
loading. For the earthquake loading linear static
analysis is considered.
2.3 Comparative Study of G+3 Storied Building
For Blast And Earthquake Loading
2.3.1 Displacement Comparison
Figure 5 shows the storey displacement for blast
and earthquake loading. Total four cases are
discussed here. „BLAST-EQ SECTION‟ means,
the blast load is applied in the building which is
designed for Earthquake resistance. „BLAST-
REVISED SECTION‟ means the section provided
are revised based on the representation of blast
resistance, In this case, 0.1 Tonne TNT is
considered. The third case of „EQ-section‟, the
Table 3 : LOAD COMBINATIONS FOR EARTHQUAKE AND
BLAST LOAD
Figure 3: BLAST LOAD APLLIED AS UDL AT FRONT FACE
Table 2 : BLAST PARAMETERS FOR 0.1 TONNE TNT AND
21 M STAND-OFF DISTANCE
Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66
www.ijera.com 65 | P a g e
sections are designed only for earthquake loading.
In the last case of „EQ SECTION SAFE IN
BLAT‟, the maximum charge weight is obtained to
make the earthquake resistant building safe during
blast. The charge weight for each case in
mentioned in the bracket From the figure 5, it is
observed that the storey displacement for blast
loading is higher than the same for earthquake and
at level 1st
and 2nd
storey displacements are higher
in comparison to other storey level. But in case of
Earthquake load the displacement is proportionally
increasing.
2.3.2 Storey Drift Comparison
As far as the structural as well as non structural
safety of building in terms of functional aspect is
concerned the storey drift is a critical parameter.
Figure 6 shows the storey drift for blast and
earthquake loading. From the figure 6 it is observed
that for the earthquake load, the storey drift comes
out to be within permissible limit specified by
code. Whereas, in the case of blast load the storey
drift exceeds than the permissible limit specially on
the storeys where blast is applied.
2.4 Quantity of Material
Table 4 shows the size of the optimum sections
which are designed for blast resistant and
earthquake resistant building. From the table 4 it is
observed that the blast resisting building is having
mostly same size of beams but size of columns is
much more up to the plinth and at the level where
blast load applied. Table 5 represent the difference
of quantity of concrete between blast resistant and
earthquake resistant. From the table 5 it is observed
that the quantity of concrete for the blast resistant
building is 40 percentage higher than the
earthquake resistant building as higher section are
required for blast case.
2.4 Safe Charge explosive and Safe Stand-Off
Distance Calculations
Safe charge explosive and safe stand-off distance
for earthquake resistant RCC building is obtained
by trial and error method. The safe charge
explosive and safe stand-off distance are obtained
as 0.03 tonne TNT and 31.5 meter respectively.
Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com
ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66
www.ijera.com 66 | P a g e
III. CONCLUSIONS
Behaviour of structures subjected to blast load as
compared to earthquake load is significantly
different as the blast pressure is of very high
intensity which is applied in milliseconds in form
of impact load. Based on the numerical study
carried out herein the following major conclusions
are drawn.
 In blast, the storey displacement is higher than
the same for earthquake and at 1st
and 2nd
storey, displacements are higher in comparison
to other storey level. But in case of earthquake
load, the displacement is proportionally
increasing.
 As far as the structural as well as non structural
safety of building in terms of functional aspect
is concerned, the storey drift is a critical
parameter. For earthquake load, the storey drift
comes out to be within permissible limit
specified by code. Whereas in the case of blast
load, the storey drift exceeds than the
permissible limit specially on the storeys
where blast is applied.
 Quantity of concrete for blast resistant building
is around 40 % higher than the earthquake
resistant building.
 Safe charge explosive of 0.03 Tonne TNT is
obtained for the RCC structure with the
sections of structural elements same as per the
requirement for earthquake resistance.
 For the earthquake resistant RCC building, the
safe stand-off distance is 31.5 m for the charge
weight of 0.1 Tonne TNT.
REFFERENCES
[1] Kashif, Q., and Verma, M. B.,(2014),
“Effect of Blast on G+4 RCC Frame
Structure”, International Journal of
Emerging Technology and Advanced
Engineering, 4(11),pp-145-149.
[2] Marjanishvili, S., and Agnew E.,(2006),
“Comparison of various procedures for
progressive collapse analysis”, Journal of
performance of constructed facilities,
20(4),pp-365-374.
[3] Rose, T.A., Smith, P.D. and Mays, G.C.
The effectiveness of walls designed for the
protection of structures against airblast
from high explosives. Proceedings of the
Institution of Civil EngineersStructures
and Buildings. 1995; 110(1):78-85
[4] Shallan, O., Eraky, A., Sakr, T. and Emad,
S.,(2014), “Response of Building
Structures to Blast Effects”, International
Journal of Engineering Innovative
Technology, 4(2), pp-167-175.
[5] Singla, S., Singla, P., and Singla,
A.,(2015), “Computation of blast loading
for a multi storeyed framed building”,
International Journal of Research in
Engineering and Technology,4(2),pp-759-
766.
[6] Zhao, C.F., Chen, J.Y., Wang, y., Lu,
S.J.,(2012),” Damage mechanism and
response of reinforced concrete
containment structure under internal blast
loading”, Journal Theoretical and Applied
Fracture Mechanics,61,pp-12-20
[7] IS Code IS: 4991-1968 ―Criteria for blast
resistant design of structures for explosion
above ground‖, Bureau of Indian
Standards (1968)
[8] Web: www.wbdg.com , Hinman
E,(2011),”Blast safety of the building
envelope”, whole building design guide.

More Related Content

What's hot

Earthquake Resistance Design-Impact On Cost Of Reinforced Concrete Builidings
Earthquake Resistance Design-Impact On Cost Of Reinforced  Concrete BuilidingsEarthquake Resistance Design-Impact On Cost Of Reinforced  Concrete Builidings
Earthquake Resistance Design-Impact On Cost Of Reinforced Concrete BuilidingsIJMER
 
Analysis and connection designs of precast load bearing wall
Analysis and connection designs of precast load bearing wallAnalysis and connection designs of precast load bearing wall
Analysis and connection designs of precast load bearing walleSAT Publishing House
 
IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...
IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...
IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...IRJET Journal
 
Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...
Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...
Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...IOSR Journals
 
IRJET-Effect of Blast Loading on Framed Structure: A Review
IRJET-Effect of Blast Loading on Framed Structure: A ReviewIRJET-Effect of Blast Loading on Framed Structure: A Review
IRJET-Effect of Blast Loading on Framed Structure: A ReviewIRJET Journal
 
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisPerformance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisIJMER
 
IRJET- Analysis of Irregular RCC Framed Structure for Fundamental Natural...
IRJET-  	  Analysis of Irregular RCC Framed Structure for Fundamental Natural...IRJET-  	  Analysis of Irregular RCC Framed Structure for Fundamental Natural...
IRJET- Analysis of Irregular RCC Framed Structure for Fundamental Natural...IRJET Journal
 
IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...
IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...
IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...IRJET Journal
 
Seismic evaluation & retrofit assessment of jlnm hospital, rainawari srinaga
Seismic evaluation & retrofit assessment of jlnm  hospital, rainawari srinagaSeismic evaluation & retrofit assessment of jlnm  hospital, rainawari srinaga
Seismic evaluation & retrofit assessment of jlnm hospital, rainawari srinagaIAEME Publication
 
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...IAEME Publication
 
IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...
IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...
IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...IRJET Journal
 
EXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETE
EXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETEEXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETE
EXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETEIAEME Publication
 
Effect of Impulsive Loads on G+3 RCC Building
Effect of Impulsive Loads on G+3 RCC BuildingEffect of Impulsive Loads on G+3 RCC Building
Effect of Impulsive Loads on G+3 RCC BuildingIJMERJOURNAL
 
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...ijtsrd
 
Earthquake Analysis of Multi Storied Residential Building - A Case Study
Earthquake Analysis of Multi Storied Residential Building - A Case StudyEarthquake Analysis of Multi Storied Residential Building - A Case Study
Earthquake Analysis of Multi Storied Residential Building - A Case StudyIJERA Editor
 
Effects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildingsEffects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildingseSAT Journals
 
Earth quake response of different shapes of mivan wall tall buildings
Earth quake response of different shapes of mivan wall tall buildingsEarth quake response of different shapes of mivan wall tall buildings
Earth quake response of different shapes of mivan wall tall buildingseSAT Journals
 

What's hot (19)

Earthquake Resistance Design-Impact On Cost Of Reinforced Concrete Builidings
Earthquake Resistance Design-Impact On Cost Of Reinforced  Concrete BuilidingsEarthquake Resistance Design-Impact On Cost Of Reinforced  Concrete Builidings
Earthquake Resistance Design-Impact On Cost Of Reinforced Concrete Builidings
 
Analysis and connection designs of precast load bearing wall
Analysis and connection designs of precast load bearing wallAnalysis and connection designs of precast load bearing wall
Analysis and connection designs of precast load bearing wall
 
IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...
IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...
IRJET-The Study of Effect of Blast Load on Multi-Storey Building by using Tim...
 
Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...
Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...
Evaluation of Structural Implication of Incorporating Base Isolator as Earthq...
 
IRJET-Effect of Blast Loading on Framed Structure: A Review
IRJET-Effect of Blast Loading on Framed Structure: A ReviewIRJET-Effect of Blast Loading on Framed Structure: A Review
IRJET-Effect of Blast Loading on Framed Structure: A Review
 
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover AnalysisPerformance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
Performance Based Evaluation of Shear Walled RCC Building by Pushover Analysis
 
IRJET- Analysis of Irregular RCC Framed Structure for Fundamental Natural...
IRJET-  	  Analysis of Irregular RCC Framed Structure for Fundamental Natural...IRJET-  	  Analysis of Irregular RCC Framed Structure for Fundamental Natural...
IRJET- Analysis of Irregular RCC Framed Structure for Fundamental Natural...
 
IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...
IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...
IRJET- Effect of Different Soil Conditions on Seismic Response of Multi-Store...
 
Seismic evaluation & retrofit assessment of jlnm hospital, rainawari srinaga
Seismic evaluation & retrofit assessment of jlnm  hospital, rainawari srinagaSeismic evaluation & retrofit assessment of jlnm  hospital, rainawari srinaga
Seismic evaluation & retrofit assessment of jlnm hospital, rainawari srinaga
 
13.80 89
13.80 8913.80 89
13.80 89
 
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
EFFECT OF SEISMIC LOAD ON REINFORCED CONCRETE MULTISTORY BUILDING FROM ECONOM...
 
presentation]
presentation]presentation]
presentation]
 
IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...
IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...
IRJET- Analytical Study of Steel Buildings with Different Geometric Configura...
 
EXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETE
EXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETEEXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETE
EXPERIMENTAL STUDY ON BEHAVIOUR OF FLYASH BASED GEOPOLYMER CONCRETE
 
Effect of Impulsive Loads on G+3 RCC Building
Effect of Impulsive Loads on G+3 RCC BuildingEffect of Impulsive Loads on G+3 RCC Building
Effect of Impulsive Loads on G+3 RCC Building
 
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...Seismic Performance of Reinforced Cement Concrete Structures with and Without...
Seismic Performance of Reinforced Cement Concrete Structures with and Without...
 
Earthquake Analysis of Multi Storied Residential Building - A Case Study
Earthquake Analysis of Multi Storied Residential Building - A Case StudyEarthquake Analysis of Multi Storied Residential Building - A Case Study
Earthquake Analysis of Multi Storied Residential Building - A Case Study
 
Effects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildingsEffects of shape on the wind instigate response of high rise buildings
Effects of shape on the wind instigate response of high rise buildings
 
Earth quake response of different shapes of mivan wall tall buildings
Earth quake response of different shapes of mivan wall tall buildingsEarth quake response of different shapes of mivan wall tall buildings
Earth quake response of different shapes of mivan wall tall buildings
 

Similar to Comparative Study of Response of Structures Subjected To Blast and Earthquake Loading

IRJET- Response of a Rectangular Reinforced Concrete Structure with and w...
IRJET-  	  Response of a Rectangular Reinforced Concrete Structure with and w...IRJET-  	  Response of a Rectangular Reinforced Concrete Structure with and w...
IRJET- Response of a Rectangular Reinforced Concrete Structure with and w...IRJET Journal
 
“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...
“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...
“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...IRJET Journal
 
Behaviour of Reinforced Concrete Beams under Different Kinds of Blast Loading
Behaviour of Reinforced Concrete Beams under Different Kinds of Blast LoadingBehaviour of Reinforced Concrete Beams under Different Kinds of Blast Loading
Behaviour of Reinforced Concrete Beams under Different Kinds of Blast LoadingMD ASIF AKBARI
 
Presentation blast load
Presentation blast loadPresentation blast load
Presentation blast load9893100459
 
REVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDING
REVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDINGREVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDING
REVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDINGIRJET Journal
 
Progressive collapse analysis in rc structure due to 150513181706
Progressive collapse analysis in rc structure due to 150513181706Progressive collapse analysis in rc structure due to 150513181706
Progressive collapse analysis in rc structure due to 150513181706pradip patel
 
Blast resistant structure
Blast resistant structureBlast resistant structure
Blast resistant structureLoga Raja
 
ANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECT
ANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECTANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECT
ANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECTIRJET Journal
 
Comparative Study of Irregular Shape Buildings
Comparative Study of Irregular Shape BuildingsComparative Study of Irregular Shape Buildings
Comparative Study of Irregular Shape BuildingsIRJET Journal
 
A Review On Behavior Of Tall Structure Under Blast Loading
A Review On Behavior Of Tall Structure Under Blast LoadingA Review On Behavior Of Tall Structure Under Blast Loading
A Review On Behavior Of Tall Structure Under Blast LoadingIRJET Journal
 
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABSStudy of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABSIRJET Journal
 
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...IRJET Journal
 
Structures to Resist the Effects of the Accidental Explosions
Structures to Resist the Effects of the Accidental ExplosionsStructures to Resist the Effects of the Accidental Explosions
Structures to Resist the Effects of the Accidental Explosionsijtsrd
 
A Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC FramesA Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC FramesIRJET Journal
 
Behavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A ReviewBehavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A ReviewIJERA Editor
 
Behavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A Review Behavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A Review IJERA Editor
 
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...IRJET Journal
 
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”IRJET Journal
 

Similar to Comparative Study of Response of Structures Subjected To Blast and Earthquake Loading (20)

IRJET- Response of a Rectangular Reinforced Concrete Structure with and w...
IRJET-  	  Response of a Rectangular Reinforced Concrete Structure with and w...IRJET-  	  Response of a Rectangular Reinforced Concrete Structure with and w...
IRJET- Response of a Rectangular Reinforced Concrete Structure with and w...
 
“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...
“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...
“Comparative Analysis of Blast Load on Multi Storey R.C.C. Building at Differ...
 
Behaviour of Reinforced Concrete Beams under Different Kinds of Blast Loading
Behaviour of Reinforced Concrete Beams under Different Kinds of Blast LoadingBehaviour of Reinforced Concrete Beams under Different Kinds of Blast Loading
Behaviour of Reinforced Concrete Beams under Different Kinds of Blast Loading
 
Presentation blast load
Presentation blast loadPresentation blast load
Presentation blast load
 
Tallbuildings_2013.pdf
Tallbuildings_2013.pdfTallbuildings_2013.pdf
Tallbuildings_2013.pdf
 
REVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDING
REVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDINGREVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDING
REVIEW STUDY ON IMPACT OF BLAST LOAD ON R.C.C. BUILDING
 
Progressive collapse analysis in rc structure due to 150513181706
Progressive collapse analysis in rc structure due to 150513181706Progressive collapse analysis in rc structure due to 150513181706
Progressive collapse analysis in rc structure due to 150513181706
 
Blast resistant structure
Blast resistant structureBlast resistant structure
Blast resistant structure
 
ANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECT
ANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECTANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECT
ANALYSIS OF G+6 STORY STEEL STRUCTURE UNDER BLASTING EFFECT
 
Comparative Study of Irregular Shape Buildings
Comparative Study of Irregular Shape BuildingsComparative Study of Irregular Shape Buildings
Comparative Study of Irregular Shape Buildings
 
A Review On Behavior Of Tall Structure Under Blast Loading
A Review On Behavior Of Tall Structure Under Blast LoadingA Review On Behavior Of Tall Structure Under Blast Loading
A Review On Behavior Of Tall Structure Under Blast Loading
 
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABSStudy of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
Study of Seismic and Wind Effect on Multi-Storey R.C.C. Building using ETABS
 
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
Study of Self Compacting Concrete by using Marginal Materials-Partial Replace...
 
G012454144
G012454144G012454144
G012454144
 
Structures to Resist the Effects of the Accidental Explosions
Structures to Resist the Effects of the Accidental ExplosionsStructures to Resist the Effects of the Accidental Explosions
Structures to Resist the Effects of the Accidental Explosions
 
A Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC FramesA Study on the Impact of Seismic Performance on RCC Frames
A Study on the Impact of Seismic Performance on RCC Frames
 
Behavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A ReviewBehavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A Review
 
Behavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A Review Behavior of RCC Structural Members for Blast Analysis: A Review
Behavior of RCC Structural Members for Blast Analysis: A Review
 
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...
IRJET-Analysis of G+25 RCC Bare Framed Structure with Shear Wall Under the Ef...
 
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
 

Recently uploaded

Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxpurnimasatapathy1234
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escortsranjana rawat
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfAsst.prof M.Gokilavani
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacingjaychoudhary37
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 

Recently uploaded (20)

Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Microscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptxMicroscopic Analysis of Ceramic Materials.pptx
Microscopic Analysis of Ceramic Materials.pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
(MEERA) Dapodi Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Escorts
 
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdfCCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
CCS355 Neural Network & Deep Learning Unit II Notes with Question bank .pdf
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
microprocessor 8085 and its interfacing
microprocessor 8085  and its interfacingmicroprocessor 8085  and its interfacing
microprocessor 8085 and its interfacing
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 

Comparative Study of Response of Structures Subjected To Blast and Earthquake Loading

  • 1. Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66 www.ijera.com 62 | P a g e Comparative Study of Response of Structures Subjected To Blast and Earthquake Loading Aditya C. Bhatt1 , Snehal V. Mevada2 , Sumant B. Patel3 1 P.G. Student, 2 Assistant Professor, 3 Associate Professor, Structural Engineering Department, Birla Vishvakarma Mahavidyalaya [Engineering College], Vallabh Vidyanagar, Gujarat, India. ABSTRACT The increase in the number of terrorist attacks especially in the last few years has shown that the effect of blast load on building is a serious challenge that should be taken in to consideration for designing of structures. This type of loading damages the structures, externally as well as internally. Hence the blast load should be considered with same importance as earthquake load. The present study includes the comparative performance of G+3 storey building subjected to blast and earthquake loading using ETABS. For four storey building using different input parameters like charge explosive, stand-off distance and layout of building the blast pressure are conducted and linear time history analysis is carried out. Comparative study for blast and earthquake loading is carried out for different parameters like maximum storey displacement, storey drift and quantity of materials. Safe charge explosive and safe stand-off distance are obtained for the RCC structure with the sections of structural elements same as per the requirement for earthquake resistance. Displacement is higher for the blast loading as compared to earthquake loading and very high for the storey at which blast load is applied. Quantity of concrete is 40 percentages higher for blast resistant building than the earthquake resistant building. Keywords: blast, earthquake, explosion, charge weight, safe stand-off distance I. INTRODUCTION Protecting civilian buildings from the threat of terrorist activities is one of the most essential challenges for structural engineers. Events of the past decades have greatly increased the attentiveness of structural designers about the threat of terrorist attacks using explosive devices. Extensive research into structural analysis considering blast effects and techniques to protect buildings has been initiated in many countries to build up methods for protecting critical infrastructure and the built environment. There are a number of means available to prevent a booming terrorist attack on a building [3] . Structures analysed for blast loads are subjected to entirely different types of load than that considered in conventional design. Here structures are subjected to quickly moving shock wave which may exert pressures many times greater than those experienced under the greatest of hurricanes. However, in blast phenomenon, the peak intensity lasts for a very small duration only [1] . The blast can generally categorize as external and internal blast. External blast can further recognized as surface burst or air burst. An explosion which is located at a distance from and above the structure is known as air burst explosion, while surface blast will occur when detonation is situated close to or on the ground. An internal or confined explosion will produce shock loads or, gas pressure loads from the confinement of the products of the explosion. This pressure has a long duration in comparison to that of the shock pressure, due to external explosion. Due to highly uncertainty in predicting blast loads, it is difficult to construct blast proof building. But various structural and non-structural precautions can be taken to minimize structural damage and physical injuries [5] . Shallan et al. [3] showed that the effect of blast load decrease with increasing the standoff distance from the building and with variation of the aspect ratios of the buildings there is no variation in the displacement of the column in the face of the blast load but with increasing the aspect ratio the effect of blast load decrease in other element in the building. Kashif and Varma (2015) [1] analysed a five storey RCC symmetric building for blast load for 100 kg and 500 kg of Tri-Nitro-Toluene placed at 30 m distance from point of explosion. It was concluded that building was not behaving as a RESEARCH ARTICLE OPEN ACCESS
  • 2. Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66 www.ijera.com 63 | P a g e cantilever structure under blast load, which is different from the earthquake and wind. Results of the performance level of building, maximum displacement , plastic hinges locations were defined and compared for both 100 kg and 500 kg TNT explosives. Based on the literature review carried out, it is observed that some researchers have investigated the effect of blast load on structures. However there is a need for detail parametric investigation in this area. Following are the main objective of the present study. i ) To obtain the response of multi storied structures under blast and earthquake loading. ii) To obtain the safe standoff distance for multi storied building which is safe in earthquake. 1.1 Blast Load And Earthquake Load Similarities and differences between seismic and blast loading are noticeable. Both of these loads are dynamic loads and they produce dynamic structural response. The structural behavior in response to these loads is inelastic as well. The focus of structural design against these loads is on life safety as opposed to preventing structural damage. Differences between blast and seismic loading are presented in Figure 1. [7] II. NUMERICAL STUDY In the numerical study carried out herein, the G + 3 storied RCC building is considered.. Figure 2 shows the plan and 3D view of the building considered. Table 1 represents the physical properties and input parameters of the considered building. The analysis and design is carried out in ETABS software. For G+3 storied RCC building, both blast and earthquake loading are applied. Comparative study has been carried out for the same for different criteria like storey displacement, storey drift and quantity of concrete. For the earthquake resistant building, calculation of both safe charge-explosive and safe stand-off distance have been carried out 2.1 Methodology First of all consider the buildings subjected to a blast equivalent in yield to some tonne of TNT at a certain standoff distance. For the dynamic analysis of structures, the blast effects are most conveniently represented by a loading-time history which is applied to the structural members as transient loading. The magnitude and the pressure- time history of the blast load is calculated as per IS 4991-1968. Then pressure calculated is applied as UDL on column. Linear time history analysis is carried out and the response of structure is obtained subjected to blast loading. 2.2 Blast Load Calculation as per the IS 4991:1968. For the study carried out herein explosive of 0.1 tonne TNT equivalent is considered. Building is situated 21 m from the ground zero. Analysis of the same building is carried out for Blast load combinations. Table 2 shows the blast parameters for 0.1 Tonne TNT and 21 m stand-off distance. Table 3 reprents the load combination considered in the present study. 2.2.1 Characteristics of the blast load Scaled distance = 21/ (0.1) (1/3) = 45.243 m Assuming pa = 1 kg/cm² ( From IS 4991:1968, Table: 1) Sr. No. Parameter Value 1 Height of the story 3.5 m 2 Span of each bay 5 m 3 Plan dimension of building 15 m x 15 m 4 Number of storey G+3 5 Grade of concrete M25 6 Height of plinth 1.5 m 7 Zone V 8 Importance factor 1 9 Soil type Medium Figure 1: BLAST AND SEISMIC WAVES Table 1: PROPERTIES OF BUILDING
  • 3. Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66 www.ijera.com 64 | P a g e q0 = 0.142 kg/cm2 t0 =31.25 * (0.1) 0.33 = 14.505 milliseconds td =21.6 * (0.1) 0.33 = 10.026 milliseconds M = 1.25 a = 344 m/s U = 0.43 m/milliseconds 2.2.2 Blast Pressure on the building S is lesser of H or B/2 = 7 m tc = 3S/U = 10.026 milliseconds tt = l/U = 34.884 milliseconds tr = 4S/U = 65.116 milliseconds As tr>td there is no pressure on back face For roof & sides (from IS 4991:1968 Table 2) For front face Cd = 1 For roof and side face Cd = -0.4 ps0 + Cdq0 = 59.15 kN/m² EARTHQUAKE BLAST 1.5*DL+1.5*LL 1.5*DL+1.5*LL 1.2*DL+1.2*LL±1.2*EQX±1 .2*EQY 1.2*DL+1.2*LL+ 1*BL 1.5*DL+±1.5*EQX±1.5*EQ Y 1.5*DL+1*BL 0.9*DL+±1.5*EQX±1.5*EQ Y 0.9*DL+1*BL Figure 3 shows the isometric view of the building in which blast load is applied as udl to the column. Figure 4 shows the pressure-time diagram for the front and side faces for the considered blast loading. For the earthquake loading linear static analysis is considered. 2.3 Comparative Study of G+3 Storied Building For Blast And Earthquake Loading 2.3.1 Displacement Comparison Figure 5 shows the storey displacement for blast and earthquake loading. Total four cases are discussed here. „BLAST-EQ SECTION‟ means, the blast load is applied in the building which is designed for Earthquake resistance. „BLAST- REVISED SECTION‟ means the section provided are revised based on the representation of blast resistance, In this case, 0.1 Tonne TNT is considered. The third case of „EQ-section‟, the Table 3 : LOAD COMBINATIONS FOR EARTHQUAKE AND BLAST LOAD Figure 3: BLAST LOAD APLLIED AS UDL AT FRONT FACE Table 2 : BLAST PARAMETERS FOR 0.1 TONNE TNT AND 21 M STAND-OFF DISTANCE
  • 4. Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66 www.ijera.com 65 | P a g e sections are designed only for earthquake loading. In the last case of „EQ SECTION SAFE IN BLAT‟, the maximum charge weight is obtained to make the earthquake resistant building safe during blast. The charge weight for each case in mentioned in the bracket From the figure 5, it is observed that the storey displacement for blast loading is higher than the same for earthquake and at level 1st and 2nd storey displacements are higher in comparison to other storey level. But in case of Earthquake load the displacement is proportionally increasing. 2.3.2 Storey Drift Comparison As far as the structural as well as non structural safety of building in terms of functional aspect is concerned the storey drift is a critical parameter. Figure 6 shows the storey drift for blast and earthquake loading. From the figure 6 it is observed that for the earthquake load, the storey drift comes out to be within permissible limit specified by code. Whereas, in the case of blast load the storey drift exceeds than the permissible limit specially on the storeys where blast is applied. 2.4 Quantity of Material Table 4 shows the size of the optimum sections which are designed for blast resistant and earthquake resistant building. From the table 4 it is observed that the blast resisting building is having mostly same size of beams but size of columns is much more up to the plinth and at the level where blast load applied. Table 5 represent the difference of quantity of concrete between blast resistant and earthquake resistant. From the table 5 it is observed that the quantity of concrete for the blast resistant building is 40 percentage higher than the earthquake resistant building as higher section are required for blast case. 2.4 Safe Charge explosive and Safe Stand-Off Distance Calculations Safe charge explosive and safe stand-off distance for earthquake resistant RCC building is obtained by trial and error method. The safe charge explosive and safe stand-off distance are obtained as 0.03 tonne TNT and 31.5 meter respectively.
  • 5. Aditya C. Bhatt.et al. Int. Journal of Engineering Research and Applications www.ijera.com ISSN: 2248-9622, Vol. 6, Issue 5, (Part - 2) May 2016, pp.62-66 www.ijera.com 66 | P a g e III. CONCLUSIONS Behaviour of structures subjected to blast load as compared to earthquake load is significantly different as the blast pressure is of very high intensity which is applied in milliseconds in form of impact load. Based on the numerical study carried out herein the following major conclusions are drawn.  In blast, the storey displacement is higher than the same for earthquake and at 1st and 2nd storey, displacements are higher in comparison to other storey level. But in case of earthquake load, the displacement is proportionally increasing.  As far as the structural as well as non structural safety of building in terms of functional aspect is concerned, the storey drift is a critical parameter. For earthquake load, the storey drift comes out to be within permissible limit specified by code. Whereas in the case of blast load, the storey drift exceeds than the permissible limit specially on the storeys where blast is applied.  Quantity of concrete for blast resistant building is around 40 % higher than the earthquake resistant building.  Safe charge explosive of 0.03 Tonne TNT is obtained for the RCC structure with the sections of structural elements same as per the requirement for earthquake resistance.  For the earthquake resistant RCC building, the safe stand-off distance is 31.5 m for the charge weight of 0.1 Tonne TNT. REFFERENCES [1] Kashif, Q., and Verma, M. B.,(2014), “Effect of Blast on G+4 RCC Frame Structure”, International Journal of Emerging Technology and Advanced Engineering, 4(11),pp-145-149. [2] Marjanishvili, S., and Agnew E.,(2006), “Comparison of various procedures for progressive collapse analysis”, Journal of performance of constructed facilities, 20(4),pp-365-374. [3] Rose, T.A., Smith, P.D. and Mays, G.C. The effectiveness of walls designed for the protection of structures against airblast from high explosives. Proceedings of the Institution of Civil EngineersStructures and Buildings. 1995; 110(1):78-85 [4] Shallan, O., Eraky, A., Sakr, T. and Emad, S.,(2014), “Response of Building Structures to Blast Effects”, International Journal of Engineering Innovative Technology, 4(2), pp-167-175. [5] Singla, S., Singla, P., and Singla, A.,(2015), “Computation of blast loading for a multi storeyed framed building”, International Journal of Research in Engineering and Technology,4(2),pp-759- 766. [6] Zhao, C.F., Chen, J.Y., Wang, y., Lu, S.J.,(2012),” Damage mechanism and response of reinforced concrete containment structure under internal blast loading”, Journal Theoretical and Applied Fracture Mechanics,61,pp-12-20 [7] IS Code IS: 4991-1968 ―Criteria for blast resistant design of structures for explosion above ground‖, Bureau of Indian Standards (1968) [8] Web: www.wbdg.com , Hinman E,(2011),”Blast safety of the building envelope”, whole building design guide.