2. 2
Table of contents
1
โข Introduction
2
โข The Single Phase AC Voltage Controller
3
โข The Single Phase AC Voltage Controller - Resistive
Load
4
โข The Single Phase AC Voltage Controller - RL Load
5
โข The Three Phase AC Voltage Controller โ Y
Connected Resistive Load
6
โข The Three Phase AC Voltage Controller โ ฮ
Connected Resistive Load
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
3. 3
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Introduction
An ac voltage controller is a converter that controls the
voltage, current, and average power delivered to an ac
load from an ac source.
The phase-controlled ac voltage controller has several
practical uses including light-dimmer circuits and speed
control of induction motors.
In a switching scheme called phase control, switching
takes place during every cycle of the source, in effect
removing some of the source waveform before it reaches
the load.
Integral-cycle control, the source is connected and
disconnected for several cycles at a time.
4. 4
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller
Basic Operation
For the single phase AC voltage controller
shown, electronic switches are shown as parallel
thyristors (SCRs). This SCR arrangement
makes it possible to have current in either
direction in the load. This SCR connection is
called antiparallel or inverse parallel because
the SCRs carry current in opposite directions. A
triac is equivalent to the antiparallel SCRs.
Other controlled switching devices can be used
instead of SCRs.
๏ Load current contains both positive and negative half-cycles. An analysis
identical to that done for the controlled half-wave rectifier can be done on a
half cycle for the voltage controller. Then, by symmetry, the result can be
extrapolated to describe the operation for the entire period.
๏ S1 conducts if a gate signal is applied during the positive half-cycle of the
source. S1 conducts until the current in it reaches zero.
๏ A gate signal is applied to S2 during the negative half-cycle of the source,
providing a path for negative load current.
vs
L
o
a
d
+ -vsw
S1
S2
+
-
+
-
io
vo
5. 5
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller
Basic Operation
Basic observations about this controller
The SCRs cannot conduct simultaneously.
The load voltage is the same as the source voltage when either SCR
is on. The load voltage is zero when both SCRs are OFF.
The switch voltage vsw is zero when either SCR is ON and is equal to
the source voltage when neither is ON.
The average current in the source and load is zero if the SCRs are
on for equal time intervals. The average current in each SCR is not
zero because of unidirectional SCR current.
The rms current in each SCR is 1/โ2 times the rms load current if
the SCRs are on for equal time intervals.
6. 6
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
vs
+ -vsw
S1
S2
+
-
+
-
io
voR
The Single Phase AC Voltage Controller - Resistive Load
๐ฃ๐ ๐๐ก = ๐๐ ๐ ๐๐๐๐ก
๐ฃ๐ ๐๐ก =
๐๐ ๐ ๐๐๐๐ก ๐ผ < ๐๐ก < ๐ ๐๐๐ ๐ + ๐ผ < ๐๐ก < 2๐
0 ๐๐กโ๐๐๐ค๐๐ ๐
Let the voltage source be
Output voltage is
The rms load voltage is
๐๐,๐๐๐ =
1
๐
(๐๐ ๐ ๐๐๐๐ก)2 ๐๐๐ก
๐
ฮฑ
=
๐๐
2
1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
7. 7
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - Resistive Load
The power factor of the load is
The rms current in the load and the source is
๐ผ ๐,๐๐๐ =
๐๐,๐๐๐
๐
=
๐๐
๐ 2
1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
๐๐ =
๐
๐
=
๐๐,๐๐๐
2
๐
๐๐ ,๐๐๐ ๐ผ๐ ,๐๐๐
=
๐๐,๐๐๐
2
๐
๐๐ ,๐๐๐ (๐๐,๐๐๐ ๐ )
=
๐๐,๐๐๐
๐๐ ,๐๐๐
=
๐๐
2
1 โ
๐ผ
๐ +
๐ ๐๐2๐ผ
2๐
๐๐ 2
๐๐ = 1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
The pf=1 for ฮฑ=0, which is the same as for an uncontrolled resistive load, and
the power factor for ฮฑ>0 is less than 1.
The average source current is zero because of half-wave symmetry.
๐ผ๐ ,๐ด๐ฃ๐ = ๐ผ ๐,๐ด๐ฃ๐ = 0
8. 8
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - Resistive Load
The average SCR current is
๐ผ๐๐ถ๐ ,๐ด๐ฃ๐ =
1
2๐
๐๐ ๐ ๐๐๐๐ก
๐
๐๐๐ก
๐
๐ผ
=
๐๐
2๐๐
(1 + ๐๐๐ ๐ผ)
๐ผ๐๐ถ๐ ,๐๐๐ =
1
2๐
(
๐๐ ๐ ๐๐๐๐ก
๐
)2 ๐๐๐ก
๐
ฮฑ
=
๐๐
2๐
1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
The rms SCR current is
๐ผ๐๐ถ๐ ,๐๐๐ =
๐๐
2 2๐
1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
=
๐ผ ๐,๐๐๐
2
ฯฮฑ 2ฯ 2ฯ+ฮฑ 3ฯ
ฯt
iS1
vs/R
9. 9
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Example: The single-phase ac voltage controller has a 120-V rms 60-Hz source.
The load resistance is 15 ฮฉ. Determine (a) the delay angle required to deliver
500 W to the load, (b) the rms source current, (c) the rms and average currents
in the SCRs, (d) the power factor.
๐๐,๐๐๐ =
๐๐
2
1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
=
2 ร 120
2
1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
๐ =
๐๐,๐๐๐
2
๐
โ ๐๐,๐๐๐
2
= ๐๐ = 500 ร 15 = 7500
๐๐,๐๐๐
2
= 1202
(1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
)
โด 7500 = 14400(1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
)
๐ผ
๐
โ
๐ ๐๐2๐ผ
2๐
= 0.479
2๐ผ โ ๐ ๐๐2๐ผ = 3.01
๐ผ = 1.54 rad = 88.1 ๐
(a)
The Single Phase AC Voltage Controller - Resistive Load
10. 10
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - Resistive Load
(b)
๐ผ ๐,๐๐๐ =
๐๐,๐๐๐
๐
=
86.6
15
= 5.77 A
๐๐,๐๐๐
2
= 7500 โ ๐๐,๐๐๐ = 86.6From (a)
๐ผ๐๐ถ๐ ,๐ด๐ฃ๐ =
๐๐
2๐๐
1 + ๐๐๐ ๐ผ =
2 ร 120
2๐15
1 + ๐๐๐ 88.1 = 1.86 A
๐ผ๐๐ถ๐ ,๐๐๐ =
๐ผ ๐,๐๐๐
2
=
5.77
2
= 4.08 A
(c)
๐๐ =
๐
๐
=
๐
๐๐ ,๐๐๐ ๐ผ๐ ,๐๐๐
= 1 โ
๐ผ
๐
+
๐ ๐๐2๐ผ
2๐
=
500
120 ร 5.77
= 0.722(d)
11. 11
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - RL Load
vs
+ -vsw
S1
S2
+
-
+
-
io
vo
R
L
When a gate signal is applied to S1 at ๐t=ฮฑ
in single phase AC voltage controller with
RL load, Kirchhoffโs voltage law for the
circuit is expressed as.
๐๐ ๐ ๐๐๐๐ก = ๐ ๐ ๐ ๐ก + ๐ฟ
๐๐ ๐ ๐ก
๐๐ก
The solution for current in this equation
(as obtained in the controlled half wave
rectifier section) is
๐ ๐ ๐๐ก =
๐๐
๐
sin ๐๐ก โ ๐ โ sin(๐ผ โ ๐)๐(๐ผโ๐๐ก) ๐๐
๐ผ โค ๐๐ก โค ๐ฝ
0 ๐๐กโ๐๐๐ค๐๐ ๐
where
๐ = ๐ 2 + (๐๐ฟ)2 ๐ = ๐ก๐๐โ1
(
๐๐ฟ
๐
)
The extinction angle ๐ฝ is the angle at which the current returns to zero, when
๐๐ก= ๐ฝ,
๐ ๐ ๐ฝ =
๐๐
๐
sin ๐ฝ โ ๐ โ sin(๐ผ โ ๐)๐(๐ผโ๐ฝ) ๐๐
(1)
(2)
12. 12
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - RL Load
A gate signal is applied to S2 at ๐t=ฯ+ฮฑ,
and the load current is negative but has a
form identical to that of the positive half-
cycle.
The above equation must be solved
numerically for ๐ฝ.
The angle (๐ฝ-ฮฑ) is called the conduction
angle ๐ถ.
๐ถ =๐ฝ-ฮฑ
In the interval between ฯ and ๐ฝ when the
source voltage is negative and the load
current is still positive, S2 cannot be
turned on because it is not forward biased.
The gate signal to S2 must be delayed at
least until the current in S1 reaches zero,
at ๐t= ๐ฝ. The delay angle is therefore at
least ๐ฝ- ฯ.
ฮฑโฅ๐ฝ- ฯ
13. 13
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - RL Load
When ฮฑ=ฮธ, equation (2) becomes
sin ๐ฝ โ ๐ = 0
which has a solution
๐ฝ โ ๐ = ฯ
Therefore
๐ถ = ๐ When ฮฑ=ฮธ
When ๐ถ=๐, one SCR is always conducting, and the voltage across the load is
the same as the voltage of the source. The load voltage and current are
sinusoids for this case, and the circuit is analyzed using phasor analysis for AC
circuits. The power delivered to the load is continuously controllable between
the two extremes corresponding to full source voltage and zero.
The expression of rms load current is
๐ผ ๐,๐๐๐ =
1
๐
๐ ๐
2
(๐๐ก) ๐๐๐ก
๐ฝ
ฮฑ
=
1
๐
๐ ๐
๐
sin ๐๐ก โ ๐ โ
๐ ๐
๐
sin(๐ผ โ ๐)๐(๐ผโ๐๐ก) ๐๐
2
๐๐๐ก
๐ฝ
ฮฑ
14. 14
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - RL Load
The average output voltage can be found as
An other way to find the expression of rms load current
is
๐ผ ๐,๐๐๐ =
1
๐ 2 + (๐๐ฟ)2
๐๐
2
1
๐
(๐ฝ โ ๐ผ โ
1
2
๐ ๐๐2๐ฝ +
1
2
๐ ๐๐2๐ผ)
Power absorbed by the load is determined from
๐ = ๐ผ ๐,๐๐๐
2
๐
The power factor of the load is
๐๐ =
๐
๐
=
๐๐,๐๐๐ ๐ผ ๐,๐๐๐
๐๐ ,๐๐๐ ๐ผ๐ ,๐๐๐
=
๐๐,๐๐๐
๐๐ ,๐๐๐
=
1
๐
(๐ฝ โ ๐ผ โ
1
2
๐ ๐๐2๐ฝ +
1
2
๐ ๐๐2๐ผ)
๐๐,๐๐๐ =
1
๐
(๐๐ ๐ ๐๐๐๐ก)2 ๐๐๐ก
๐ฝ
ฮฑ
=
๐๐
2
1
๐
(๐ฝ โ ๐ผ โ
1
2
๐ ๐๐2๐ฝ +
1
2
๐ ๐๐2๐ผ)
15. 15
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - RL Load
Each SCR carries one-half of the current waveform, making the average SCR
current
๐ผ๐๐ถ๐ ,๐ด๐ฃ๐ =
1
2๐
๐ ๐(๐๐ก) ๐๐๐ก
๐ฝ
ฮฑ
=
1
2๐
๐๐
๐
sin ๐๐ก โ ๐ โ sin(๐ผ โ ๐)๐(๐ผโ๐๐ก) ๐๐ ๐๐๐ก
๐ฝ
ฮฑ
The rms current in each SCR is
๐ผ๐๐ถ๐ ,๐๐๐ =
๐ผ ๐,๐๐๐
2
The average load current is zero,
๐ผ ๐,๐ด๐ฃ๐ = 0
16. 16
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
Example: For the single-phase voltage controller with RL load, the source is
120Vrms at 60 Hz, and the load is a series RL combination with R=20ฮฉ and
L=50mH. The delay angle ฮฑ is 90. Determine (a) an expression for load current
for the first half-period, (b) the rms load current, (c) the rms SCR current, (d)
the average SCR current, (e) the power delivered to the load, and (f) the power
factor.
(a)
The Single Phase AC Voltage Controller - RL Load
The extinction angle is determined from the numerical solution of i(ฮฒ)=0 in the
above equation.
17. 17
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Single Phase AC Voltage Controller - RL Load
(b)
(c)
(d)
(e)
(f)
๐ผ ๐,๐๐๐ =
1
27.5
ร 120 ร
1
๐
(3.83 โ 1.57 โ
1
2
๐ ๐๐440 + 0) = 3.27 A
๐ผ ๐,๐๐๐ =
1
๐ 2 + (๐๐ฟ)2
๐๐
2
1
๐
(๐ฝ โ ๐ผ โ
1
2
๐ ๐๐2๐ฝ โ
1
2
๐ ๐๐2๐ผ)
Or
18. 18
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
๏ The power delivered to the load in
three phase AC voltage controller
with Y-connected resistive load is
controlled by the delay angle ฮฑ on
each thyristor. The six thyristors
are turned on in the sequence 1-2-
3-4-5-6, at 60 intervals. Gate
signals are maintained
throughout the possible
conduction angle.
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
ab
c
R
RR
n
N
๏ The instantaneous voltage across each phase of the load is determined by
which thyristors are conducting. At any instant, three thyristors , two
thyristors , or no thyristors are ON.
๏ The instantaneous load voltages are either a line-to-neutral voltage (three
thyristors ON), one-half of a line-to-line voltage (two thyristors ON), or
zero (none on).
๏ Which thyristors are conducting depends on the delay angle ฮฑ and on the
source voltages at a particular instant. The ranges of ฮฑ that produce
particular types of load voltages are 0< ฮฑ<60o, 60o< ฮฑ<90o and 90o< ฮฑ<150o.
19. 19
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
๏ To study the output voltage Van, Vbn and Vcn, triggering angle ฮฑ must be
determined first.
๏ Suppose that the triggering angle ฮฑ equal to 30o.
๏ The output voltage Van will be studies when ฮฑ= 30o, and the same procedure
can be applied to get the output voltages Vbn and Vcn at any triggering angle
from 0 to 60o.
๐๐ด๐ = ๐๐sin๐t
๐๐ต๐ = ๐๐sin(๐t-2ฯ/3)
๐๐ถ๐ = ๐๐sin(๐t-4ฯ/3)
Let
๐๐ด๐ต = 3๐๐sin(๐t+ฯ/6)
๐๐ต๐ถ = 3๐๐sin(๐t-ฯ/2)
๐๐ถ๐ด = 3๐๐sin(๐t-7ฯ/6)
VAN VBN VCN
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
20. 20
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
1. Determine the triggering angle ฮฑ (for example ฮฑ= 30o).
2. Determine the conducting period for each thyristor.
โข As seen from the input phase voltages VAN, VBN and VCN, every 30o there is
a change that affect on the conduction of each thyristor.
VAN VBN VCN
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
VAN=VCN
VCN=0 VBN=0
VAN=VBN
VAN=0 VCN=0
VBN=VCN
VBN=0 VAN=0
VAN=VBNVAN=VCNVBN=VCN
21. 21
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
VAN VBN VCN
iG1
iG6
iG5
iG4
iG3
iG2
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
โข Because ฮฑ=30o, S1 will be
triggered at 30o, S3 will be
triggered at 150o (120o+ฮฑ), S5
will be triggered at 270o
(240o+ฮฑ).
โข S4 will be triggered after S1
by 180o, S6 will be triggered
after S3 by 180o S2 will be
triggered after S5 by 180o.
โข The six SCRs are turned on
in the sequence 1-2-3-4-5-6,
at 60o intervals.
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
ab
c
R
RR
n
N
22. 22
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
3. Study the conduction period for each thyristor.
โข Each thyristor will be studied at each angle that affect on the conduction of
each thyristor to determine if the thyristor will conduct or not.
โข The conduction period will be studied for S1.
โข At 30o, VAN=VCN, VAN and VCN are positive, while VBN is negative. So, the
current will flow from phase A and C to phase B. S1 will be on from 30o to
60o.
VAN VBN VCN
iG1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
+
+
-
23. 23
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
โข At 60o, VCN=0, VAN is positive, while VBN is negative. So, the current will
flow from phase Ato phase B. S1 will be ON from 60o to 90o.
VAN VBN VCN
iG1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
+
0
-
24. 24
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
โข At 90o, VBN=VCN, VAN is positive, while VBN and VCN are negative. So, the
current will flow from phase Ato phase B and phase C. S1 will be ON from
90o to 120o.
+ -
S4
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
+
-
-
VAN VBN VCN
iG1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
25. 25
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
โข At 120o, VBN=0, VAN is positive, while VCN is negative. So, the current will
flow from phase Ato phase C. S1 will be ON from 120o to 150o.
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
+
0
-
VAN VBN VCN
iG1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
26. 26
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
โข At 150o, VAN=VBN, VAN and VBN are positive, VCN is negative. So, the current
will flow from phase A and B to phase C. S1 will be ON from 150o to 180o.
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
+
+
-
VAN VBN VCN
iG1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
27. 27
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
โข At 180o, VAN=0, VBN is positive, VCN is negative. So, the current will flow
from phase B to phase C and the current will not flow in phase A. S1 will be
OFF from 180o to 210o.
โข At 210o, VAN= VCN, VBN is positive, VAN and VCN are negative. So, the
current will flow from phase B to phase A and C. S1 will be OFF from 210o
to 240o.
โข At 240o, VCN= 0, VBN is positive, VAN is negative. So, the current will flow
from phase B to phase A. S1 will be OFF from 240o to 270o.
โข At 270o, VBN=VCN, VBN and VCN are positive, VAN is negative. So, the current
will flow from phase B and C to phase A. S1 will be OFF from 270o to 300o.
โข At 300o, VBN=0, VCN is positive, VAN is negative. So, the current will flow
from phase C to phase A. S1 will be OFF from 300o to 330o.
โข At 330o, VAN=VBN, VCN is positive, VAN and VBN are negative. So, the current
will flow from phase C to phase A and B. S1 will be OFF from 330o to 360o.
28. 28
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
โข The same procedure can be
done for other thyristors to
determine the conduction
period for each thyristor.
4. Determine the thyristors
that will be conducted for
each period. For example,
when 0<ฯt<30o, S5 and S6
will be conducted, when
30o<ฯt<60o, S5, S6 and S1
will be conducted, ectโฆ
VAN VBN VCN
iG1
iG6
iG5
iG4
iG3
iG2
6,1,2 2,3,41,2,36,1 2,31,2 3,4 3,4,5 4,5 4,5,65,6 5,6,1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
29. 29
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
5. Determine the output voltages (Van,
Vbn and Vcn) at each period.
โข The output voltage Van can be
found by applying the thyristors
that will be conducted at each
period.
โข when 0<ฯt<30o, S5 and S6 will be
conducted which means that the
current will flow from phase C to
phase B, and there is no current
will flow in phase A. In this period
Van=0.
โข when 30o<ฯt<60o, S5, S6 and S1 will
be conducted which means that the
current will flow from phase A and
C to phase B. In this period
Van=VAN.
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
0
+
-
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
+
+
-
0<ฯt<30o
30o<ฯt<60o
30. 30
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
โข when 60o<ฯt<90o, S6 and S1 will be
conducted which means that the
current will flow from phase A to
phase B, and there is no current will
flow in phase C. In this period
Van=VAB/2.
โข After completing the output voltage
Van for the whole period, the
waveform of Van can be found from
the waveforms VAN, VAB/2, VAC/2 and
zero.
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
+ -
S4
S1
+ -
S6
S3
+ -
S2
S5
A B
C
a
b
c
R
RR
n
N
+
0
-
60o<ฯt<90o
VAN VBN VCN
iG1
iG6
iG5
iG4
iG3
iG2
6,1,2 2,3,41,2,36,1 2,31,2 3,4 3,4,5 4,5 4,5,65,6 5,6,1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
0 VAN VAB/2 VAN VAC/2 VAN 0 VAN VAB/2 VAN VAC/2 VANVan
31. 31
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o VAN VBN VCN
iG1
iG6
iG5
iG4
iG3
iG2
6,1,2 2,3,41,2,36,1 2,31,2 3,4 3,4,5 4,5 4,5,65,6 5,6,1
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
360o
0 VAN VAB/2 VAN VAC/2 VAN 0 VAN VAB/2 VAN VAC/2 VANVan
VAB/2
VAN
VAC/2
Van
๏ The figure below shows the
final shape for the output
voltage Van. The rms voltage
for this waveform will be
less than the rms voltage for
the input voltages VAN, VBN
and VCN.
30o
60o
90o
120o
150o
180o
210o
240o
270o
300o
330o
Van
360o
32. 32
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 0 โค ฮฑ<60o
๏ The other output waveforms (Vbn
and Vcn) can be found by the
same way, and the resulting
waveform of Vbn will be the same
as the waveform of Van shifted by
120o, and the waveform of Vbn
will be the same as the waveform
of Van shifted by 240o.
๏ At any instant, three thyristors
or two thyristors are ON. The
instantaneous load voltages are
either a line-to-neutral voltage
(three thyristors ON), one-half of
a line-to-line voltage (two
thyristors ON), or zero (none
ON)
๏ Because the load is resistive load,
the shape of the output current is
similar to the shape of the output
voltage.
33. 33
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 60o โค ฮฑ<90o
๏ Only two thyristors conduct at any one time when the delay angle is
between 60o and 90o.
๏ For ฮฑ=75o
, prior to 75o, S5 and S6 are conducting, and Van=0. When S1 is
turned on at 75o, S6 continues to conduct, but S5 must turn off because VCN
is negative. Voltage Van is then VAB/2. When S2 is turned on at 135 , S6 is
forced off, and Van= VAC/2. The next thyristor to turn on is S3, which forces
S1 off, and Van=0. One thyristor is always forced off when thyristor is
turned on for ฮฑ in this range. Load voltages are one-half line-to-line
voltages or zero.
34. 34
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
When 90o โค ฮฑ<150o
๏ Only two thyristors conduct
at any one time when the
delay angle is between 90o and
150o.
๏ For ฮฑ=120o
, prior to 120o, no
thyristors are on, and Van=0.
At ฮฑ=120o, S1 is turned on at
120o, S6 still has a gate signal
applied. Since VAB is positive,
both S1 and S6 are forward-
biased and begin to conduct,
and Van=VAB/2. Both S1 and S6
turn off when VAB becomes
negative. When a gate signal
is applied to S2, it turns on,
and S1 turns on again.
For ฮฑ>150o, there is no time interval when thyristor is forward-biased
while a gate signal is applied. Output voltage is zero for this condition.
36. 36
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
The rms output voltage for a Yโ connection loads are found to be:
๏ For 60oโค ฮฑ<90o
๐ฝ ๐,๐๐๐ =
๐
๐๐
๐ฝ ๐๐
๐
๐ ๐๐
๐๐
๐
๐ฝ ๐,๐๐๐ =
๐
๐
(
๐ฝ ๐จ๐ฉ
๐
) ๐ ๐ ๐๐
๐ ๐+๐ถ
๐ถ
+ (
๐ฝ ๐จ๐ช
๐
) ๐ ๐ ๐๐
๐๐ ๐+๐ถ
๐๐ ๐
๐ฝ ๐,๐๐๐ =
๐
๐
(
๐๐ฝ ๐sin(๐t+ฯ/6)
๐
) ๐ ๐ ๐๐
๐ ๐+๐ถ
๐ถ
+ (
๐๐ฝ ๐sin(๐tโฯ/6)
๐
) ๐ ๐ ๐๐
๐๐ ๐+๐ถ
๐๐ ๐
๐๐,๐๐๐ = 3๐๐
1
๐
๐
12
+
3๐ ๐๐2๐ผ
16
+
3๐๐๐ 2๐ผ
16
37. 37
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
The rms output voltage for a Yโ connection loads are found to be:
๏ For 90oโค ฮฑ<150o
๐ฝ ๐,๐๐๐ =
๐
๐๐
๐ฝ ๐๐
๐
๐ ๐๐
๐๐
๐
๐ฝ ๐,๐๐๐ =
๐
๐
(
๐ฝ ๐จ๐ฉ
๐
) ๐ ๐ ๐๐
๐๐ ๐
๐ถ
+ (
๐ฝ ๐จ๐ช
๐
) ๐ ๐ ๐๐
๐๐ ๐
๐ ๐+๐ถ
๐ฝ ๐,๐๐๐ =
๐
๐
(
๐๐ฝ ๐sin(๐t+ฯ/6)
๐
) ๐ ๐ ๐๐
๐๐ ๐
๐ถ
+ (
๐๐ฝ ๐sin(๐tโฯ/6)
๐
) ๐ ๐ ๐๐
๐๐ ๐
๐ ๐+๐ถ
๐ฝ ๐,๐๐๐ = ๐๐ฝ ๐
๐
๐
๐๐
๐๐
โ
๐ถ
๐
+
๐๐๐๐๐ถ
๐๐
โ
๐๐๐๐๐๐ถ
๐๐
38. 38
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ Y Connected Resistive Load
Example: a three phase bidirectional AC voltage controller Y-connected
connected to resistive load (R=10ฮฉ). The supply voltage VL-L=208V, f=60Hz. If
ฮฑ=ฯ/6, find the output voltage rms value and the input power factor.
๐๐,๐๐๐ = 3๐๐
1
๐
๐
6
โ
๐ผ
4
+
๐ ๐๐2๐ผ
8
= 208
1
๐
๐
6
โ
ฯ/6
4
+
๐ ๐๐2ฯ/6
8
= 83๐
๐ผ ๐,๐๐๐ =
๐๐,๐๐๐
๐
=
83
10
= 8.3๐ด
๐๐,๐๐ = 3๐ผ ๐,๐๐๐
2
๐ = 3 ร 8.32
ร 10 = 2066.7๐
๐ = 3๐ผ ๐,๐๐๐ ๐๐๐๐๐ข๐ก,๐๐๐ = 3 ร 8.3 ร 84.9 = 2114.4๐๐ด
๐๐๐๐๐ข๐ก,๐๐๐ =
208
2 3
= 84.9๐
๐๐ =
๐๐,๐๐
๐
=
2066.7
2114.4
= 0.977
39. 39
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ ฮ Connected Resistive Load
๏ The voltage across a load resistor is the corresponding line-to-line voltage
when a thyristor in the phase is on. The delay angle is referenced to the
zero crossing of the line-to-line voltage. thyristors are turned on in the
sequence 1-2-3-4-5-6.
The line current in each
phase is the sum of two of
the delta currents:
40. 40
Dr. Firas Obeidat Faculty of Engineering Philadelphia University
The Three Phase AC Voltage Controller โ ฮ Connected Resistive Load
The relationship between rms line
and delta currents depends on the
conduction angle of the thyristors.
For small conduction angles (large ฮฑ),
the delta currents do not overlap, and
the rms line currents are
Current waveforms for ฮฑ=130o
For large conduction angles (small ฮฑ),
the delta currents overlap, and the
rms line current is larger than โ2Iฮ.
In the limit when ฮณ (ฮฑ=0), the delta
currents and line currents are
sinusoids. The rms line current is
determined from ordinary three-
phase analysis.
Current waveforms for ฮฑ=90o
The range of rms line current is
therefore
depending on ฮฑ