2. Name Plate Data
Three phase Induction Motor
Main Motor Data
Power 22 KW
Voltage 400 V
Current 39.2 A
Frequency 60 Hz
Connection ∆ (Delta)
Insulation Class B
Weight 215 KG
3. Motor Measured Data
Motor Voltage Current PF KW KVAR KVA
No. (Volt) (Amp)
1 405.4 16 0.774 8.7 7.7 11.67
2 419 14.1 0.76 7.9 7.6 10.1
7 415.8 20.2 0.831 12.58 8.45 14.85
8 399.9 25.5 0.774 11.38 9.7 14.99
9 394.6 16.8 0.857 9.654 5.88 11.55
10 394.4 15.5 0.87 9.2 5.3 10.7
11 394.8 17.3 0.816 9.63 6.76 11.9
25 423 16.3 0.75 9 7.6 11.9
41 417.6 20.3 0.65 10.98 12.85 17.3
56 413.4 25.1 0.44 7.8 15.66 17.9
Note: Motor No. 41 & 56 are DOL (Direct On Line)
5. Graph between Load (%) and Efficiency (%)
Eff1= High Efficiency Motor Curve
Eff2= Standard Efficiency Motor Curve
Source: CEMEP (Committee of European Manufacturers of Electrical Machines and Power Electronics )
6. Graph
Eff1= High Efficiency Motor Curve
Eff2= Standard Efficiency Motor Curve
Source: CEMEP (Committee of European Manufacturers of Electrical Machines and Power
Electronics )
7. Rewinding
All motors in the industry were rewound.
Most of them were rewound twice and
some even thrice.
Rewinding once reduces the efficiency
from 2 to 3 percent.
The cost of rewinding is 65% of the initial
motor cost.
All the motors were more than 20 years old
which is more than their normal life span.
8. Calculations
KWsaved = L × KWRated × [( / Effold motor) – ( /Effnew motor)] × 00
KWhsavings = KWsaved × Annual Operating Hours
Operating Hours = (365× 24) – [10% of (365 × 24)] = 7884 hrs
Total Savings (Rupees) = KWhsavings × Unit Charges (Rupees/KWh)
L = Load Factor
Effold motor = Standard Motor Efficiency(Eff2)
Effnew motor= High Efficiency Motor Efficiency(Eff1)
The extra cost of an energy efficient motor is often quickly repaid in energy
savings.
9. Payback
Time required for the savings to equal the initial cost.
Simple Payback = Motor price
Annual Savings
Operational cost is about six times its initial purchase.
Purchase price of Energy Efficient motor is 15% to 30%
more than standard motor that can be recovered within 2
years.
11. Conclusion
Total KW in operation 96.824
No. of Motors 10
Total KW saved 12.643
Total Saving (Rupees) 996812
Total Investment (Rupees) 2870350
50% off Price 1435175
Payback Time 1year 6 months
Hence from these facts and figures,
replacement of all the motors is recommended