B+G E-Tech User Manual for SDM630
SDM630
Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems
USER MANUAL
2013 V1.1
B+G E-Tech User Manual for SDM630
Important Safety Information is contained in the Maintenance section. Familiarize yourself with
this information before attempting installation or other procedures.
Symbols used in this document:
Risk of Danger: These instructions contain important safety information:
Read them before starting installation or servicing of the equipment
Caution: Risk of Electric Shock
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 1 -
1 Introduction
This document provides operating, maintenance and installation instructions . The unit measures
and displays the characteristics of single phase two wires(1p2w) , three phase three wires(3p3w,)
and three phase four wires(3p4w) supplies, including voltage, frequency, current, power ,active
and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh.
Maximum demand current can be measured over preset periods of up to 60minutes. In order to
measure energy,the unit requires voltage and current inputs in addition tot he supply required to
power the product.The requisite current input(s) are obtained via current transformers(CT).
This meter can be configured to work with a wide range of CTs,giving the unit a wide range of
operation.Built-in interfaces provides pulse and Rs485 Modbus RTU outputs.Configuration is
password protected.
This unit can be powered from a separate auxiliary(AC or DC)supply.Alternatively it can be
powered from the monitored supply,where appropriate.
1.1 Unit Characteristics
The Unit can measure and display:
 Line voltage and THD% (total harmonic distortion) of all phases
 Line Frequency
 Currents, Current demands and current THD% of all phases
 Power, maximum power demand and power factor
 Active energy imported and exported
 Reactive energy imported and exported
The unit has password-protected set-up screens for:
 Changing password
 Supply system selection 1p2w, 3p3w,3p4w
 Demand Interval time
 Reset for demand measurements
 Pulse output duration
Two pulse output indicates real-time energy measurement. An RS485 output allows remote
monitoring from another display or a computer.
1.2 Current Transformer Primary Current
The unit can be configured to operate with CT ratio between primary current and secondary
current.The secondary CT has two options: 1A/5A
1.3 RS485 Serial – Modbus RTU
This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely
monitoring and controlling the Unit
Set-up screens are provided for setting up the RS485 port. Refers to section 4.8
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 2 -
1.4 Pulse output
This provides two pulse outputs that clock up measured active and reactive energy. The constant
for reactive energy is 3200imp/kVArh. The pulse width for active energy can be set from the
set-up menu.
2. Start Up Screens
The first screen lights up all display segments
and can be used as a display check
The second screen indicates the firmware
installed in the unit and its build number.
The interface performs a self-test and
indicates the result if the test passes.
After a short delay, the screen will display active energy measurements.
3. Measurements
The buttons operate as follows:
Selects the Voltage and Current display screens
In Set-up Mode, this is the “Left” or “Back” button.
Select the Frequency and Power factor display screens
In Set-up Mode, this is the “Up” button
Select the Power display screens
In Set-up Mode, this is the “Down” button
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 3 -
Select the Energy display screens
In Set-up mode, this is the “Enter” or “Right” button
3.1 Voltage and Current
Each successive pressing of the button selects a new range:
Phase to neutral voltages
Current on each phase
Phase to neutral voltage THD%
Current THD% for each phase
3.2 Frequency and Power factor and Demand
Each successive pressing of the button selects a new range:
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 4 -
Frequency and Power Factor (total)
Power Factor of each phase
Maximum Power Demand
Maximum Current Demand
3.3 Power
Each successive pressing of the button select a new range:
Instantaneous Active Power in kW
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 5 -
Instantaneous Reactive Power in kVAr
Instantaneous Volt-amps in KVA
Total kW, kVArh, kVA
3.4 Energy Measurements
Each successive pressing of the button selects a new range:
Imported active energy in kWh
Exported active energy in kWh
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 6 -
Imported reactive energy in kVArh
Exported reactive energy in kVArh
Total active energy in kWh
Total reactive energy in kVAh
4. Setting Up
To enter set-up mode, pressing the button for 3 seconds, until the password screen
appears.
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 7 -
Setting up is password-protected so you must enter the correct password (default ‘1000’) before
processing. If an incorrect password is entered, the display will show: PASS Err
To exit setting-up mode, press repeatedly until the measurement screen is restored.
4.1 Set-up Entry Methods
Some menu items, such as password and CT, require a four-digit number entry while others, such
as supply system, require selection from a number of menu options.
4.1.1 Menu Option Selection
1. Use the and buttons to select the required item from the menu shown in
section 4.1. selection does not roll over between bottom and top of list
2. Press to confirm your selection
3. If an item flashes, then it can be adjusted by the and buttons. If not, there
maybe a further layer.
4. Having selected an option from the current layer, press to confirm your selection. The
SET indicator will appear.
5. Having completed a parameter setting, press to return to a higher menu level. The
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 8 -
SET indicator will be removed and you will be able to use the and buttons for
further menu selection.
6. On completion of all setting-up, press repeatedly until the measurement screen is
restored.
4.1.2 Number Entry Procedure
When Setting up the unit , some screens require the entering of a number. In particular, on entry
to the setting up section, a password must be entered. Digits are set individually, from left to
right. The procedure is as follows:
1. the current digit to be set flashes and is set using the and buttons
2. Press to confirm each digit setting. The SET indicator appears after the last digit
has been set.
3. After setting the last digit, press to exit the number setting routine. The SET
indicator will be removed.
4.2 Change password
1
Use the and to choose the change
password option
2
Press the to enter the change password
routine. The new password screen will appear with
the first digit flashing
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 9 -
3
Use and to set the first digit and
press to confirm your selection. The next
digit will flash.
4 Repeat the procedure for the remaining three digits
5 After setting the last digit, SET will show.
6
Press to exit the number setting routine and return to the Set-up menu. SET will be
removed
4.3 DIT Demand Integration Time
This sets the period in minutes over which the current and power readings are integrated for
maximum demand measurement. The options are: off, 5, 10,15 30,60 minutes
1
From the set-up menu, use and
buttons to select the DIT option. The screen will
show the currently selected integration time.
2
Press to enter the selection routine. The
current time interval will flash
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 10 -
3
Use and buttons to select the time
required.
4
Press to confirm the selection. SET
indicator will appear.
5
Press to exit the DIT selection routine and return to the menu.
4.4 Supply System
Use this section to set the type of power supply being monitored.
1
From the Set-up menu, use and
buttons to select the System option. The screen will
show the currently selected power supply .
2
Press to enter the selection routine. The
current selection will flash
3
Use and buttons to select the
required system option: 1P2(W),3P3(W) ,3P4(W)
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 11 -
4
Press to confirm the selection. SET
indicator will appear.
5
Press to exit the system selection routine and return to the menu. SET will
disappear and you will be returned to the main Set-up Menu
4.5 CT
The CT option sets the secondary current(CT2 1A or 5A) of the current transformer (CT) that
wires to the meter.
1
From the Set-up menu, use and
buttons to select the CT option.
2 Secondary CT setting
Press to enter the CT secondary current
selection routine.:5A/1A
3 Set CT Ratio value
Press to enter the CT Ratio setting screen.
The range is from 0001 to 9999.
4 For example,if set the ratio to be 100,it means the primary current equals secondary
currentx100
4.6 PT
The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that
wires to the meter.
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 12 -
1
From the Set-up menu, use and
buttons to select the PT option. The screen will
show the voltage PT secondary voltage value.
The default value is 230V
2 Secondary PT setting
Press to enter the PT secondary voltage
selection routine. The range is from 100 to 500V
3 Set PT ratios value
Press to enter the PT ratio screen.
The range is from 0001 to 9999
4 For example,if set the ratio to be 100,it means the primary voltage equals secondary
voltagex100
4.7Pulse output
This option allows you to configure the pulse output. The output can be set to provide a pulse for
a defined amount of energy active or reactive.
Use this section to set up the relay pulse output—Units: kWh , kVArh
1
From the Set-up menu, use and
buttons to select the Pulse output option.
2
Press to enter the selection routine. The
unit symbol will flash.
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 13 -
3
Use and buttons to choose kWh or
kVArh.
4
On Completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
4.7.1 Pulse rate
Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per
0.01kWh/0.1kWh/1kWh/10kWh/100kWh.
(It shows 1 impulse = 10kWh/kVArh)
1
From the Set-up menu, use and
buttons to select the Pulse Rate option.
2
Press to enter the selection routine. The
current setting will flash.
0.01/0.1/1/10/100kWh/kVarh per pulse
3
Use and buttons to choose pulse rate.On Completion of the entry
procedure, press to confirm the setting and press to return to the main set
up menu.
4.7.2 Pulse Duration
The energy monitored can be active or reactive and the pulse width can be selected as 200, 100
or 60ms.
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 14 -
(It shows pulse width of 200ms)
1
From the Set-up menu, use and
buttons to select the Pulse width option.
2
Press to enter the selection routine. The
current setting will flash.
3
Use and buttons to choose pulse width.On Completion of the entry
procedure, press to confirm the setting and press to return to the main set
up menu.
4.8 Communication
There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus
RTU, parameters are selected from Front panel.
4.8.1 RS485 Address
(The range is from 0 to 247)
4.8.2 Baud Rate
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 15 -
1
From the Set-up menu, use and
buttons to select the Baud Rate option.
2
Press to enter the selection routine. The
current setting will flash.
3
Use and buttons to choose Baud
rate 2.4k. 4.8k, 9.6k, 19.2k, 38.4k
4
On Completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
4.8.3 Parity
1
From the Set-up menu, use and
buttons to select the Parity option.
2
Press to enter the selection routine. The
current setting will flash.
3
Use and buttons to choose Parity
(EVEN / ODD / NONE)
4
On Completion of the entry procedure, press to confirm the setting and press
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 16 -
to return to the main set up menu.
4.8.4 Stop bits
1
From the Set-up menu, use and
buttons to select the Stop Bit option.
2
Press to enter the selection routine. The
current setting will flash.
3
Use and buttons to choose Stop Bit
(2 or 1)
4
On completion of the entry procedure, press to confirm the setting and press
to return to the main set up menu.
4.9 CLR
The meter provides a function to reset the maximum demand value of current and power.
1
From the Set-up menu, use and
buttons to select the reset option.
2
Press to enter the selection routine. The dIt
will flash.
3
Press to confirm the setting and press to return to the main set up menu.
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 17 -
5 Specifications
5.1 Measured Parameters
The unit can monitor and display the following parameters of a single phase two wire(1p2w),
three phase three wire(3p3w) or four phase four wire(3p4w) supply.
5.1.1 Voltage and Current
Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies)
Voltages between phases 173 to 500V a.c. (3p supplies only)
Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies)
Percentage voltage THD% between phases (three phase supplies only)
Current THD% for each phase
5.1.2 Power factor and Frequency and Max. Demand
Frequency in Hz
Instantaneous power:
Power 0 to 3600 MW
Reactive Power 0 to 3600 MVAr
Volt-amps 0 to 3600 MVA
Maximum demanded power since last Demand reset Power factor
Maximum neutral demand current, since the last Demand reset (for three phase supplies only)
5.1.3 Energy Measurements
Imported active energy 0 to 9999999.9 kWh
Exported active energy 0 to 9999999.9 kWh
Imported reactive energy 0 to 9999999.9 kVArh
Exported reactive energy 0 to 9999999.9 kVArh
Total active energy 0 to 9999999.9 kWh
Total reactive energy 0 to 9999999.9 kVArh
5.2 Measured Inputs
Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire capacity. single phase
two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) unbalanced. Line
frequency measured from L1 voltage or L3 voltage.
Three current inputs (six physical terminals) with 2.5mm² stranded wire capacity for connection
of external CTs. Nominal rated input current 5A or 1A a.c. Rms.
5.3 Accuracy
Voltage 0·5% of range maximum
Current 0·5% of nominal
Frequency 0·2% of mid-frequency
Power factor 1% of unity (0.01)
Active power (W) ±1% of range maximum
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 18 -
Reactive power (VAr) ±2% of range maximum
Apparent power (VA) ±1% of range maximum
Active energy (Wh) Class 1 IEC 62053-21
Reactive energy (VARh) ±2% of range maximum
Total harmonic distortion 1% up to 31st harmonic
Temperature co-efficient Voltage and current = 0.013%/°C typical
Active energy = 0·018%/°C, typical
Response time to step input 1s, typical, to >99% of final reading, at 50 Hz.
5.4 Auxiliary Supply
Two-way fixed connector with 2·5mm2 stranded wire capacity.
85 to 275V a.c. 50/60Hz ±10% or 120V to 380V d.c. ±20%. Consumption < 10W.
5.5 Interfaces for External Monitoring
Three interfaces are provided:
 an RS-485 communication channel that can be programmed for Modbus RTU protocol
 an relay output indicating real-time measured energy.(configurable)
 an pulse output 3200imp/kWh (not configurable)
The Modbus configuration (Baud rate etc.) and the pulse relay output assignments (kW/kVArh,
import/export etc.) are configured through the Set-up screens.
5.5.1 Pulse Relay Output
The pulse relay output can be set to generate pulses to represent kWh or kVArh.
Rate can be set to generate 1 pulse per:
0.01 = 10 Wh/VArh
0.1 = 100 Wh/VArh
1 = 1 kWh/kVArh
10 = 10 kWh/kVArh
100 = 100 kWh/kVArh
Pulse width 200/100/60 ms.
Relay Rating 240V ac 50mA
5.5.2 RS485 Output for Modbus RTU
For Modbus RTU, the following RS485 communication parameters can be configured from the
Set-up menu:
Baud rate 2400, 4800, ,9600, ,19200, 38400
Parity none/odd/even
Stop bits 1 or 2
RS485 network address nnn – 3-digit number, 1 to 247
Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot
be configured from the set-up menu.
5.6 Reference Conditions of Influence Quantities
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 19 -
Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is
verified under nominal value (within the specified tolerance) of these conditions.
Ambient temperature 23°C ±1°C
Input waveform 50 or 60Hz ±2%
Input waveform Sinusoidal (distortion factor < 0·005)
Auxiliary supply voltage Nominal ±1%
Auxiliary supply frequency Nominal ±1%
Auxiliary supply waveform (if AC) Sinusoidal (distortion factor < 0·05)
Magnetic field of external origin Terrestrial flux
5.7 Environment
Operating temperature -25°C to +55°C*
Storage temperature -40°C to +70°C*
Relative humidity 0 to 90%, non-condensing
Altitude Up to 2000m
Warm up time 1 minute
Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g
Shock 30g in 3 planes
*Maximum operating and storage temperatures are in the context of typical daily and seasonal
variation.
5.8 Mechanics
DIN rail dimensions 72 x 94.5 mm (WxH) per DIN 43880
Mounting DIN rail (DIN 43880)
Sealing IP20 (minimum)
Material Self-extinguishing UL 94 V-0
6 Dimensions
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 20 -
7. Installation
1)Single phase two wires
2) Three phase three wires
3)Three phase four wires
B+G E-Tech User Manual for SDM630
B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0
- 21 -

More Related Content

What's hot (10)

Hướng dẫn sử dụng tủ ex-3001 user
Hướng dẫn sử dụng tủ ex-3001 userHướng dẫn sử dụng tủ ex-3001 user
Hướng dẫn sử dụng tủ ex-3001 user
 
Hướng dẫn lắp đặt và lập trình tủ ex-3001 install - commissioning
Hướng dẫn lắp đặt và lập trình tủ ex-3001 install - commissioningHướng dẫn lắp đặt và lập trình tủ ex-3001 install - commissioning
Hướng dẫn lắp đặt và lập trình tủ ex-3001 install - commissioning
 
LED Lighting Product Attachment
LED Lighting Product AttachmentLED Lighting Product Attachment
LED Lighting Product Attachment
 
1394308953 impressora mp-4200-th_manual_01_manual_de_programacao
1394308953 impressora mp-4200-th_manual_01_manual_de_programacao1394308953 impressora mp-4200-th_manual_01_manual_de_programacao
1394308953 impressora mp-4200-th_manual_01_manual_de_programacao
 
Mh8 fc um
Mh8 fc umMh8 fc um
Mh8 fc um
 
Mini Socket Dimmer Z-Wave Everspring manual
Mini Socket Dimmer Z-Wave Everspring manualMini Socket Dimmer Z-Wave Everspring manual
Mini Socket Dimmer Z-Wave Everspring manual
 
ZME WALLC-S manual
ZME WALLC-S manualZME WALLC-S manual
ZME WALLC-S manual
 
PLC y Electroneumática: inversor de control vectorial
PLC y Electroneumática: inversor de control vectorialPLC y Electroneumática: inversor de control vectorial
PLC y Electroneumática: inversor de control vectorial
 
Fgs 212-en-a-v1.01
Fgs 212-en-a-v1.01Fgs 212-en-a-v1.01
Fgs 212-en-a-v1.01
 
BT X300 Professional Conferencing Unit User Guide
BT X300 Professional Conferencing Unit User GuideBT X300 Professional Conferencing Unit User Guide
BT X300 Professional Conferencing Unit User Guide
 

Viewers also liked

Gráfico diario del ibex 35 para el 16 03 2012
Gráfico diario del ibex 35 para el 16 03 2012Gráfico diario del ibex 35 para el 16 03 2012
Gráfico diario del ibex 35 para el 16 03 2012
Experiencia Trading
 

Viewers also liked (15)

1960sdecadesproject
1960sdecadesproject 1960sdecadesproject
1960sdecadesproject
 
Gráfico diario del ibex 35 para el 16 03 2012
Gráfico diario del ibex 35 para el 16 03 2012Gráfico diario del ibex 35 para el 16 03 2012
Gráfico diario del ibex 35 para el 16 03 2012
 
Jornada cooperacion Mendoza
Jornada cooperacion MendozaJornada cooperacion Mendoza
Jornada cooperacion Mendoza
 
Seraphim Energy Product Warranty.
Seraphim Energy Product Warranty. Seraphim Energy Product Warranty.
Seraphim Energy Product Warranty.
 
Figueroa Peru Arbitration Article (march 2017)
Figueroa Peru Arbitration Article (march 2017)Figueroa Peru Arbitration Article (march 2017)
Figueroa Peru Arbitration Article (march 2017)
 
PPH Updates 2011
PPH Updates 2011PPH Updates 2011
PPH Updates 2011
 
SMA Small
SMA Small SMA Small
SMA Small
 
Zeversolar brochure
Zeversolar brochureZeversolar brochure
Zeversolar brochure
 
Improving NGO Communication using Social Media
Improving NGO Communication using Social MediaImproving NGO Communication using Social Media
Improving NGO Communication using Social Media
 
Seraphim 255w Duraflex Datasheet
Seraphim 255w Duraflex Datasheet Seraphim 255w Duraflex Datasheet
Seraphim 255w Duraflex Datasheet
 
Pediatras unidos ante la situación de la pediatría en la región de Madrid
Pediatras unidos ante la situación de la pediatría en la región de MadridPediatras unidos ante la situación de la pediatría en la región de Madrid
Pediatras unidos ante la situación de la pediatría en la región de Madrid
 
Ancient mesopotamia
Ancient mesopotamiaAncient mesopotamia
Ancient mesopotamia
 
00 revolução russa – 9º ano sj
00 revolução russa – 9º ano sj00 revolução russa – 9º ano sj
00 revolução russa – 9º ano sj
 
внеклассное мероприятие
внеклассное мероприятиевнеклассное мероприятие
внеклассное мероприятие
 
The Most Eye-Popping Facts About Female Founders!
The Most Eye-Popping Facts About Female Founders!The Most Eye-Popping Facts About Female Founders!
The Most Eye-Popping Facts About Female Founders!
 

Similar to SDM 630MCT

Temperature sensor with binary sensor input start guide
Temperature sensor with binary sensor input start guideTemperature sensor with binary sensor input start guide
Temperature sensor with binary sensor input start guide
Domotica daVinci
 

Similar to SDM 630MCT (20)

PID Controllers from Precision Digital
PID Controllers from Precision DigitalPID Controllers from Precision Digital
PID Controllers from Precision Digital
 
Catalog mikro mikro din310-user-dienhathe.vn
Catalog mikro mikro din310-user-dienhathe.vnCatalog mikro mikro din310-user-dienhathe.vn
Catalog mikro mikro din310-user-dienhathe.vn
 
Catalog mikro mikro din310-user
Catalog mikro mikro din310-userCatalog mikro mikro din310-user
Catalog mikro mikro din310-user
 
Erbe icc-80-50-icc-service-manual
Erbe icc-80-50-icc-service-manualErbe icc-80-50-icc-service-manual
Erbe icc-80-50-icc-service-manual
 
MICOM P 632
MICOM P 632MICOM P 632
MICOM P 632
 
Temperature sensor with binary sensor input start guide
Temperature sensor with binary sensor input start guideTemperature sensor with binary sensor input start guide
Temperature sensor with binary sensor input start guide
 
Pf70 700 process_pi
Pf70 700 process_piPf70 700 process_pi
Pf70 700 process_pi
 
Diw manual
Diw manualDiw manual
Diw manual
 
Xmtg 8000
Xmtg 8000Xmtg 8000
Xmtg 8000
 
SPP-01 Super Parameter Programmer User Manual Ultisolar New Energy
SPP-01 Super Parameter Programmer User Manual Ultisolar New EnergySPP-01 Super Parameter Programmer User Manual Ultisolar New Energy
SPP-01 Super Parameter Programmer User Manual Ultisolar New Energy
 
Qubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_engQubino flush dimmer 0 10-v plus user manual_v1.0_eng
Qubino flush dimmer 0 10-v plus user manual_v1.0_eng
 
MICOM P 632
MICOM P 632MICOM P 632
MICOM P 632
 
Hm 5750 manual-0817
Hm 5750 manual-0817Hm 5750 manual-0817
Hm 5750 manual-0817
 
Pf700 energy savings_lab
Pf700 energy savings_labPf700 energy savings_lab
Pf700 energy savings_lab
 
Intelligent temperature transmitter module
Intelligent temperature transmitter moduleIntelligent temperature transmitter module
Intelligent temperature transmitter module
 
SkidWeigh Technology
SkidWeigh TechnologySkidWeigh Technology
SkidWeigh Technology
 
Hgm400 v1.1 en
Hgm400 v1.1 enHgm400 v1.1 en
Hgm400 v1.1 en
 
Installation Manual M1M 12.pdf
Installation Manual M1M 12.pdfInstallation Manual M1M 12.pdf
Installation Manual M1M 12.pdf
 
Maxvu tech support lvl presentation na
Maxvu tech support lvl presentation na Maxvu tech support lvl presentation na
Maxvu tech support lvl presentation na
 
Hioki 3334 AC/DC Power HiTester - Datasheet Mana
Hioki 3334 AC/DC Power HiTester - Datasheet ManaHioki 3334 AC/DC Power HiTester - Datasheet Mana
Hioki 3334 AC/DC Power HiTester - Datasheet Mana
 

More from Optimus Energy Philippines

More from Optimus Energy Philippines (20)

ABB Terra AC Wallbox EV Charger
ABB Terra AC Wallbox EV ChargerABB Terra AC Wallbox EV Charger
ABB Terra AC Wallbox EV Charger
 
Smart Energy Solutions
Smart Energy SolutionsSmart Energy Solutions
Smart Energy Solutions
 
Alpha ESS 10.1kWh Home Battery
Alpha ESS 10.1kWh Home Battery Alpha ESS 10.1kWh Home Battery
Alpha ESS 10.1kWh Home Battery
 
Alpha Smile 5 Hybrid Solar Inverter
Alpha Smile 5 Hybrid Solar InverterAlpha Smile 5 Hybrid Solar Inverter
Alpha Smile 5 Hybrid Solar Inverter
 
Chromagen Solar Hot Water Brochure
Chromagen Solar Hot Water BrochureChromagen Solar Hot Water Brochure
Chromagen Solar Hot Water Brochure
 
Midea 170L Heat Pump
Midea 170L Heat PumpMidea 170L Heat Pump
Midea 170L Heat Pump
 
Growatt 50000 80000
Growatt 50000 80000Growatt 50000 80000
Growatt 50000 80000
 
Growatt 30000 40000
Growatt 30000 40000Growatt 30000 40000
Growatt 30000 40000
 
Growatt 10000TL3-S
Growatt 10000TL3-SGrowatt 10000TL3-S
Growatt 10000TL3-S
 
Growatt 5000TL3-S
Growatt 5000TL3-SGrowatt 5000TL3-S
Growatt 5000TL3-S
 
Solis 30kw 3Phase
Solis 30kw 3PhaseSolis 30kw 3Phase
Solis 30kw 3Phase
 
Solis 20kw 3Phase
Solis 20kw 3PhaseSolis 20kw 3Phase
Solis 20kw 3Phase
 
solis 15kw 3Phase
solis 15kw 3Phasesolis 15kw 3Phase
solis 15kw 3Phase
 
Solis 10kw 3Phase
Solis 10kw 3PhaseSolis 10kw 3Phase
Solis 10kw 3Phase
 
Solis 6kw 3Phase
Solis 6kw 3PhaseSolis 6kw 3Phase
Solis 6kw 3Phase
 
Solis 5kw 3 phase
Solis 5kw 3 phaseSolis 5kw 3 phase
Solis 5kw 3 phase
 
Solis 4.0 Data Sheet
Solis 4.0 Data SheetSolis 4.0 Data Sheet
Solis 4.0 Data Sheet
 
Solis Inverter
Solis InverterSolis Inverter
Solis Inverter
 
Growatt 3000 s
Growatt 3000 sGrowatt 3000 s
Growatt 3000 s
 
JA 380w Mono Split
JA 380w Mono SplitJA 380w Mono Split
JA 380w Mono Split
 

Recently uploaded

Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...
Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...
Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...
drmarathore
 
Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Naicy mandal
 
怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证
怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证
怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证
ehyxf
 
怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证
怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证
怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证
tufbav
 
CHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICECHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)
amitlee9823
 
一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理
一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理
一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理
bbhul52a
 
怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证
怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证
怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证
tufbav
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝
Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝
Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
CHEAP Call Girls in Hauz Quazi (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Hauz Quazi  (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICECHEAP Call Girls in Hauz Quazi  (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Hauz Quazi (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...
Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...
Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...
amitlee9823
 

Recently uploaded (20)

Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...
Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...
Abort pregnancy in research centre+966_505195917 abortion pills in Kuwait cyt...
 
Top Rated Pune Call Girls Chakan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated  Pune Call Girls Chakan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...Top Rated  Pune Call Girls Chakan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated Pune Call Girls Chakan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
 
Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
Makarba ( Call Girls ) Ahmedabad ✔ 6297143586 ✔ Hot Model With Sexy Bhabi Rea...
 
怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证
怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证
怎样办理圣芭芭拉分校毕业证(UCSB毕业证书)成绩单留信认证
 
怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证
怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证
怎样办理斯威本科技大学毕业证(SUT毕业证书)成绩单留信认证
 
CHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICECHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Vinay Nagar (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
 
9892124323 Pooja Nehwal Call Girls Services Call Girls service in Santacruz A...
9892124323 Pooja Nehwal Call Girls Services Call Girls service in Santacruz A...9892124323 Pooja Nehwal Call Girls Services Call Girls service in Santacruz A...
9892124323 Pooja Nehwal Call Girls Services Call Girls service in Santacruz A...
 
Top Rated Pune Call Girls Katraj ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated  Pune Call Girls Katraj ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...Top Rated  Pune Call Girls Katraj ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated Pune Call Girls Katraj ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
 
9004554577, Get Adorable Call Girls service. Book call girls & escort service...
9004554577, Get Adorable Call Girls service. Book call girls & escort service...9004554577, Get Adorable Call Girls service. Book call girls & escort service...
9004554577, Get Adorable Call Girls service. Book call girls & escort service...
 
Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)
Escorts Service Sanjay Nagar ☎ 7737669865☎ Book Your One night Stand (Bangalore)
 
Get Premium Pimple Saudagar Call Girls (8005736733) 24x7 Rate 15999 with A/c ...
Get Premium Pimple Saudagar Call Girls (8005736733) 24x7 Rate 15999 with A/c ...Get Premium Pimple Saudagar Call Girls (8005736733) 24x7 Rate 15999 with A/c ...
Get Premium Pimple Saudagar Call Girls (8005736733) 24x7 Rate 15999 with A/c ...
 
一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理
一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理
一比一原版(nyu毕业证书)纽约大学毕业证学历认证靠谱办理
 
怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证
怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证
怎样办理维多利亚大学毕业证(UVic毕业证书)成绩单留信认证
 
Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝
Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝
Call Now ≽ 9953056974 ≼🔝 Call Girls In Yusuf Sarai ≼🔝 Delhi door step delevry≼🔝
 
CHEAP Call Girls in Hauz Quazi (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Hauz Quazi  (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICECHEAP Call Girls in Hauz Quazi  (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
CHEAP Call Girls in Hauz Quazi (-DELHI )🔝 9953056974🔝(=)/CALL GIRLS SERVICE
 
Call Girls Pimple Saudagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Pimple Saudagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Pimple Saudagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Pimple Saudagar Call Me 7737669865 Budget Friendly No Advance Booking
 
VVIP Pune Call Girls Balaji Nagar (7001035870) Pune Escorts Nearby with Compl...
VVIP Pune Call Girls Balaji Nagar (7001035870) Pune Escorts Nearby with Compl...VVIP Pune Call Girls Balaji Nagar (7001035870) Pune Escorts Nearby with Compl...
VVIP Pune Call Girls Balaji Nagar (7001035870) Pune Escorts Nearby with Compl...
 
Call Girls Chikhali Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Chikhali Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Chikhali Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Chikhali Call Me 7737669865 Budget Friendly No Advance Booking
 
Shikrapur Call Girls Most Awaited Fun 6297143586 High Profiles young Beautie...
Shikrapur Call Girls Most Awaited Fun  6297143586 High Profiles young Beautie...Shikrapur Call Girls Most Awaited Fun  6297143586 High Profiles young Beautie...
Shikrapur Call Girls Most Awaited Fun 6297143586 High Profiles young Beautie...
 
Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...
Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...
Vip Mumbai Call Girls Kalyan Call On 9920725232 With Body to body massage wit...
 

SDM 630MCT

  • 1. B+G E-Tech User Manual for SDM630 SDM630 Din Rail Smart Energy Meter for Single and Three Phase Electrical Systems USER MANUAL 2013 V1.1
  • 2. B+G E-Tech User Manual for SDM630 Important Safety Information is contained in the Maintenance section. Familiarize yourself with this information before attempting installation or other procedures. Symbols used in this document: Risk of Danger: These instructions contain important safety information: Read them before starting installation or servicing of the equipment Caution: Risk of Electric Shock
  • 3. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 1 - 1 Introduction This document provides operating, maintenance and installation instructions . The unit measures and displays the characteristics of single phase two wires(1p2w) , three phase three wires(3p3w,) and three phase four wires(3p4w) supplies, including voltage, frequency, current, power ,active and reactive energy, imported or exported. Energy is measured in terms of kWh, kVArh. Maximum demand current can be measured over preset periods of up to 60minutes. In order to measure energy,the unit requires voltage and current inputs in addition tot he supply required to power the product.The requisite current input(s) are obtained via current transformers(CT). This meter can be configured to work with a wide range of CTs,giving the unit a wide range of operation.Built-in interfaces provides pulse and Rs485 Modbus RTU outputs.Configuration is password protected. This unit can be powered from a separate auxiliary(AC or DC)supply.Alternatively it can be powered from the monitored supply,where appropriate. 1.1 Unit Characteristics The Unit can measure and display:  Line voltage and THD% (total harmonic distortion) of all phases  Line Frequency  Currents, Current demands and current THD% of all phases  Power, maximum power demand and power factor  Active energy imported and exported  Reactive energy imported and exported The unit has password-protected set-up screens for:  Changing password  Supply system selection 1p2w, 3p3w,3p4w  Demand Interval time  Reset for demand measurements  Pulse output duration Two pulse output indicates real-time energy measurement. An RS485 output allows remote monitoring from another display or a computer. 1.2 Current Transformer Primary Current The unit can be configured to operate with CT ratio between primary current and secondary current.The secondary CT has two options: 1A/5A 1.3 RS485 Serial – Modbus RTU This uses an RS485 serial port with Modbus RTU protocol to provide a means of remotely monitoring and controlling the Unit Set-up screens are provided for setting up the RS485 port. Refers to section 4.8
  • 4. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 2 - 1.4 Pulse output This provides two pulse outputs that clock up measured active and reactive energy. The constant for reactive energy is 3200imp/kVArh. The pulse width for active energy can be set from the set-up menu. 2. Start Up Screens The first screen lights up all display segments and can be used as a display check The second screen indicates the firmware installed in the unit and its build number. The interface performs a self-test and indicates the result if the test passes. After a short delay, the screen will display active energy measurements. 3. Measurements The buttons operate as follows: Selects the Voltage and Current display screens In Set-up Mode, this is the “Left” or “Back” button. Select the Frequency and Power factor display screens In Set-up Mode, this is the “Up” button Select the Power display screens In Set-up Mode, this is the “Down” button
  • 5. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 3 - Select the Energy display screens In Set-up mode, this is the “Enter” or “Right” button 3.1 Voltage and Current Each successive pressing of the button selects a new range: Phase to neutral voltages Current on each phase Phase to neutral voltage THD% Current THD% for each phase 3.2 Frequency and Power factor and Demand Each successive pressing of the button selects a new range:
  • 6. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 4 - Frequency and Power Factor (total) Power Factor of each phase Maximum Power Demand Maximum Current Demand 3.3 Power Each successive pressing of the button select a new range: Instantaneous Active Power in kW
  • 7. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 5 - Instantaneous Reactive Power in kVAr Instantaneous Volt-amps in KVA Total kW, kVArh, kVA 3.4 Energy Measurements Each successive pressing of the button selects a new range: Imported active energy in kWh Exported active energy in kWh
  • 8. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 6 - Imported reactive energy in kVArh Exported reactive energy in kVArh Total active energy in kWh Total reactive energy in kVAh 4. Setting Up To enter set-up mode, pressing the button for 3 seconds, until the password screen appears.
  • 9. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 7 - Setting up is password-protected so you must enter the correct password (default ‘1000’) before processing. If an incorrect password is entered, the display will show: PASS Err To exit setting-up mode, press repeatedly until the measurement screen is restored. 4.1 Set-up Entry Methods Some menu items, such as password and CT, require a four-digit number entry while others, such as supply system, require selection from a number of menu options. 4.1.1 Menu Option Selection 1. Use the and buttons to select the required item from the menu shown in section 4.1. selection does not roll over between bottom and top of list 2. Press to confirm your selection 3. If an item flashes, then it can be adjusted by the and buttons. If not, there maybe a further layer. 4. Having selected an option from the current layer, press to confirm your selection. The SET indicator will appear. 5. Having completed a parameter setting, press to return to a higher menu level. The
  • 10. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 8 - SET indicator will be removed and you will be able to use the and buttons for further menu selection. 6. On completion of all setting-up, press repeatedly until the measurement screen is restored. 4.1.2 Number Entry Procedure When Setting up the unit , some screens require the entering of a number. In particular, on entry to the setting up section, a password must be entered. Digits are set individually, from left to right. The procedure is as follows: 1. the current digit to be set flashes and is set using the and buttons 2. Press to confirm each digit setting. The SET indicator appears after the last digit has been set. 3. After setting the last digit, press to exit the number setting routine. The SET indicator will be removed. 4.2 Change password 1 Use the and to choose the change password option 2 Press the to enter the change password routine. The new password screen will appear with the first digit flashing
  • 11. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 9 - 3 Use and to set the first digit and press to confirm your selection. The next digit will flash. 4 Repeat the procedure for the remaining three digits 5 After setting the last digit, SET will show. 6 Press to exit the number setting routine and return to the Set-up menu. SET will be removed 4.3 DIT Demand Integration Time This sets the period in minutes over which the current and power readings are integrated for maximum demand measurement. The options are: off, 5, 10,15 30,60 minutes 1 From the set-up menu, use and buttons to select the DIT option. The screen will show the currently selected integration time. 2 Press to enter the selection routine. The current time interval will flash
  • 12. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 10 - 3 Use and buttons to select the time required. 4 Press to confirm the selection. SET indicator will appear. 5 Press to exit the DIT selection routine and return to the menu. 4.4 Supply System Use this section to set the type of power supply being monitored. 1 From the Set-up menu, use and buttons to select the System option. The screen will show the currently selected power supply . 2 Press to enter the selection routine. The current selection will flash 3 Use and buttons to select the required system option: 1P2(W),3P3(W) ,3P4(W)
  • 13. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 11 - 4 Press to confirm the selection. SET indicator will appear. 5 Press to exit the system selection routine and return to the menu. SET will disappear and you will be returned to the main Set-up Menu 4.5 CT The CT option sets the secondary current(CT2 1A or 5A) of the current transformer (CT) that wires to the meter. 1 From the Set-up menu, use and buttons to select the CT option. 2 Secondary CT setting Press to enter the CT secondary current selection routine.:5A/1A 3 Set CT Ratio value Press to enter the CT Ratio setting screen. The range is from 0001 to 9999. 4 For example,if set the ratio to be 100,it means the primary current equals secondary currentx100 4.6 PT The PT option sets the secondary voltage (PT2 100 to 500V) of the Voltage transformer (PT) that wires to the meter.
  • 14. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 12 - 1 From the Set-up menu, use and buttons to select the PT option. The screen will show the voltage PT secondary voltage value. The default value is 230V 2 Secondary PT setting Press to enter the PT secondary voltage selection routine. The range is from 100 to 500V 3 Set PT ratios value Press to enter the PT ratio screen. The range is from 0001 to 9999 4 For example,if set the ratio to be 100,it means the primary voltage equals secondary voltagex100 4.7Pulse output This option allows you to configure the pulse output. The output can be set to provide a pulse for a defined amount of energy active or reactive. Use this section to set up the relay pulse output—Units: kWh , kVArh 1 From the Set-up menu, use and buttons to select the Pulse output option. 2 Press to enter the selection routine. The unit symbol will flash.
  • 15. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 13 - 3 Use and buttons to choose kWh or kVArh. 4 On Completion of the entry procedure, press to confirm the setting and press to return to the main set up menu. 4.7.1 Pulse rate Use this to set the energy represented by each pulse. Rate can be set to 1 pulse per 0.01kWh/0.1kWh/1kWh/10kWh/100kWh. (It shows 1 impulse = 10kWh/kVArh) 1 From the Set-up menu, use and buttons to select the Pulse Rate option. 2 Press to enter the selection routine. The current setting will flash. 0.01/0.1/1/10/100kWh/kVarh per pulse 3 Use and buttons to choose pulse rate.On Completion of the entry procedure, press to confirm the setting and press to return to the main set up menu. 4.7.2 Pulse Duration The energy monitored can be active or reactive and the pulse width can be selected as 200, 100 or 60ms.
  • 16. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 14 - (It shows pulse width of 200ms) 1 From the Set-up menu, use and buttons to select the Pulse width option. 2 Press to enter the selection routine. The current setting will flash. 3 Use and buttons to choose pulse width.On Completion of the entry procedure, press to confirm the setting and press to return to the main set up menu. 4.8 Communication There is a RS485 port can be used for communication using Modbus RTU protocol. For Modbus RTU, parameters are selected from Front panel. 4.8.1 RS485 Address (The range is from 0 to 247) 4.8.2 Baud Rate
  • 17. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 15 - 1 From the Set-up menu, use and buttons to select the Baud Rate option. 2 Press to enter the selection routine. The current setting will flash. 3 Use and buttons to choose Baud rate 2.4k. 4.8k, 9.6k, 19.2k, 38.4k 4 On Completion of the entry procedure, press to confirm the setting and press to return to the main set up menu. 4.8.3 Parity 1 From the Set-up menu, use and buttons to select the Parity option. 2 Press to enter the selection routine. The current setting will flash. 3 Use and buttons to choose Parity (EVEN / ODD / NONE) 4 On Completion of the entry procedure, press to confirm the setting and press
  • 18. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 16 - to return to the main set up menu. 4.8.4 Stop bits 1 From the Set-up menu, use and buttons to select the Stop Bit option. 2 Press to enter the selection routine. The current setting will flash. 3 Use and buttons to choose Stop Bit (2 or 1) 4 On completion of the entry procedure, press to confirm the setting and press to return to the main set up menu. 4.9 CLR The meter provides a function to reset the maximum demand value of current and power. 1 From the Set-up menu, use and buttons to select the reset option. 2 Press to enter the selection routine. The dIt will flash. 3 Press to confirm the setting and press to return to the main set up menu.
  • 19. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 17 - 5 Specifications 5.1 Measured Parameters The unit can monitor and display the following parameters of a single phase two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) supply. 5.1.1 Voltage and Current Phase to neutral voltages 100 to 289V a.c. (not for 3p3w supplies) Voltages between phases 173 to 500V a.c. (3p supplies only) Percentage total voltage harmonic distortion (THD%) for each phase to N ( not for 3p3w supplies) Percentage voltage THD% between phases (three phase supplies only) Current THD% for each phase 5.1.2 Power factor and Frequency and Max. Demand Frequency in Hz Instantaneous power: Power 0 to 3600 MW Reactive Power 0 to 3600 MVAr Volt-amps 0 to 3600 MVA Maximum demanded power since last Demand reset Power factor Maximum neutral demand current, since the last Demand reset (for three phase supplies only) 5.1.3 Energy Measurements Imported active energy 0 to 9999999.9 kWh Exported active energy 0 to 9999999.9 kWh Imported reactive energy 0 to 9999999.9 kVArh Exported reactive energy 0 to 9999999.9 kVArh Total active energy 0 to 9999999.9 kWh Total reactive energy 0 to 9999999.9 kVArh 5.2 Measured Inputs Voltage inputs through 4-way fixed connector with 2.5mm² stranded wire capacity. single phase two wire(1p2w), three phase three wire(3p3w) or four phase four wire(3p4w) unbalanced. Line frequency measured from L1 voltage or L3 voltage. Three current inputs (six physical terminals) with 2.5mm² stranded wire capacity for connection of external CTs. Nominal rated input current 5A or 1A a.c. Rms. 5.3 Accuracy Voltage 0·5% of range maximum Current 0·5% of nominal Frequency 0·2% of mid-frequency Power factor 1% of unity (0.01) Active power (W) ±1% of range maximum
  • 20. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 18 - Reactive power (VAr) ±2% of range maximum Apparent power (VA) ±1% of range maximum Active energy (Wh) Class 1 IEC 62053-21 Reactive energy (VARh) ±2% of range maximum Total harmonic distortion 1% up to 31st harmonic Temperature co-efficient Voltage and current = 0.013%/°C typical Active energy = 0·018%/°C, typical Response time to step input 1s, typical, to >99% of final reading, at 50 Hz. 5.4 Auxiliary Supply Two-way fixed connector with 2·5mm2 stranded wire capacity. 85 to 275V a.c. 50/60Hz ±10% or 120V to 380V d.c. ±20%. Consumption < 10W. 5.5 Interfaces for External Monitoring Three interfaces are provided:  an RS-485 communication channel that can be programmed for Modbus RTU protocol  an relay output indicating real-time measured energy.(configurable)  an pulse output 3200imp/kWh (not configurable) The Modbus configuration (Baud rate etc.) and the pulse relay output assignments (kW/kVArh, import/export etc.) are configured through the Set-up screens. 5.5.1 Pulse Relay Output The pulse relay output can be set to generate pulses to represent kWh or kVArh. Rate can be set to generate 1 pulse per: 0.01 = 10 Wh/VArh 0.1 = 100 Wh/VArh 1 = 1 kWh/kVArh 10 = 10 kWh/kVArh 100 = 100 kWh/kVArh Pulse width 200/100/60 ms. Relay Rating 240V ac 50mA 5.5.2 RS485 Output for Modbus RTU For Modbus RTU, the following RS485 communication parameters can be configured from the Set-up menu: Baud rate 2400, 4800, ,9600, ,19200, 38400 Parity none/odd/even Stop bits 1 or 2 RS485 network address nnn – 3-digit number, 1 to 247 Modbus™ Word order Hi/Lo byte order is set automatically to normal or reverse. It cannot be configured from the set-up menu. 5.6 Reference Conditions of Influence Quantities
  • 21. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 19 - Influence Quantities are variables that affect measurement errors to a minor degree. Accuracy is verified under nominal value (within the specified tolerance) of these conditions. Ambient temperature 23°C ±1°C Input waveform 50 or 60Hz ±2% Input waveform Sinusoidal (distortion factor < 0·005) Auxiliary supply voltage Nominal ±1% Auxiliary supply frequency Nominal ±1% Auxiliary supply waveform (if AC) Sinusoidal (distortion factor < 0·05) Magnetic field of external origin Terrestrial flux 5.7 Environment Operating temperature -25°C to +55°C* Storage temperature -40°C to +70°C* Relative humidity 0 to 90%, non-condensing Altitude Up to 2000m Warm up time 1 minute Vibration 10Hz to 50Hz, IEC 60068-2-6, 2g Shock 30g in 3 planes *Maximum operating and storage temperatures are in the context of typical daily and seasonal variation. 5.8 Mechanics DIN rail dimensions 72 x 94.5 mm (WxH) per DIN 43880 Mounting DIN rail (DIN 43880) Sealing IP20 (minimum) Material Self-extinguishing UL 94 V-0 6 Dimensions
  • 22. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 20 - 7. Installation 1)Single phase two wires 2) Three phase three wires 3)Three phase four wires
  • 23. B+G E-Tech User Manual for SDM630 B+G E-Tech GmbH ° www.bg-etech.de ° info@bg-etech.de ° +49 (0) 3574 46755-0 - 21 -