Retrofit for gas-insulated high voltage
switchgear (GIS) - 8D1 and 8D2
Page 2 of 23
Table of Contents
1 Introduction .............................................................................................................. 4
2 Description of retrofit circuit-breaker 8DN8 ................................................................ 5
3 Technical data for retrofit circuit-breaker 8DN8 .......................................................... 6
4 Adapter - retrofitting circuit-breaker 8DN8 - existing switchgear ................................. 7
5 Retrofitting steps ..................................................................................................... 12
6 Circuit-breaker maintenance comparison old vs. new ............................................... 19
7 Time schedule for retrofit solution............................................................................ 21
8 Scope of delivery ..................................................................................................... 21
9 Life time expectation of existing GIS without new circuit-breaker.............................. 21
10 Type tests ................................................................................................................ 21
11 Options ................................................................................................................... 22
Page 3 of 23
List of Figures
Fig. 1: Existing substation with 8D2 double-pressure circuit-breaker............................................... 4
Fig. 2: Main dimensions of retrofit circuit-breaker 8DN8................................................................. 5
Fig. 3: 8D2 bay with old blast piston circuit-breaker........................................................................ 7
Fig. 4: 8D2 bay with 8DN8 circuit-breaker ...................................................................................... 8
Fig. 5: 8DN8-circuit-breaker with two adapters equipped with gas-tight bushings towards the GIS
section ............................................................................................................................... 9
Fig. 6: Side view of the 8DN8 circuit-breaker with two adapters...................................................... 9
Fig. 7: Top view of 8DN8-circuit-breaker with two adapters.......................................................... 10
Fig. 8: Top view of contact arrangement ...................................................................................... 11
Fig. 9: Side view of an 8D switchgear with doublel-pressure circuit-breaker .................................. 12
Fig. 10: Electrical view ................................................................................................................. 12
Fig. 11: SF6 pressure view............................................................................................................ 13
Fig. 12: Third retrofitting step (a)................................................................................................. 14
Fig. 13: Third retrofitting step (b)................................................................................................. 14
Fig. 14: Fourth retrofitting step (a)............................................................................................... 15
Fig. 15: Fourth retrofitting step (b) .............................................................................................. 15
Fig. 16: Fifth retrofitting step (a).................................................................................................. 16
Fig. 17: Fifth retrofitting step (b).................................................................................................. 17
Fig. 18: Sixth retrofitting step: Bay after retrofitting ..................................................................... 18
Fig. 19: Standardized maintenance costs ..................................................................................... 20
List of Tables
Tab. 1: Technical data for circuit-breaker 8DN8 .............................................................................. 6
Tab. 2: Technical data of the adapter ............................................................................................. 7
Tab. 3: Comparison SF6 content old/new........................................................................................ 8
Tab. 4: Comparison of the maintenance intervals of the different circuit-breakers......................... 19
Page 4 of 23
1 Introduction
The first SF6-gas insulated switchgear of type 8D1 and 8D2 delivered by Siemens are now 40 years
and older. These substations have proved outstanding in operation. They are rugged, reliable, and
virtually leak-free (SF6 or oil) and still fulfill their function perfectly.
Today, stricter and more economically focused standards apply with respect to the maintenance of
gas-insulated switchgear. Especially the SF6 – double -pressure circuit-breakers used since GIS
systems were first introduced on the market are highly maintenance-intensive. However, since the
other GIS components (excluding the original circuit-breaker) require very little maintenance and
have an expected life span of over 50 years provided the Siemens maintenance recommendations
described in the operating manual are followed, Siemens offers a retrofit solution. This is in the
form of a state-of-the-art SF6-circuit-breaker with spring mechanism based on more than 40 years
of accumulated experience and intensive research.
Fig. 1: Existing substation with 8D2 double-pressure circuit-breaker
Page 5 of 23
2 Description of retrofit circuit-breaker 8DN8
The circuit-breaker employed in this retrofit solution is used in the current GIS and HIS substations
8DN8 up to 145 kV and also in 123 kV and 145 kV outdoor circuit-breakers. This type-tested breaker
has proven itself in service over the years in thousands of applications. The most important
advantages of this self-compression circuit-breaker of the latest generation are:
 Significantly lower maintenance costs (see chapter 6)
 Type-tested to the latest IEC standard (at the time of the development)
 State-of–the-art spring mechanism with extremely low maintenance
Fig. 2: Main dimensions of retrofit circuit-breaker 8DN8
Page 6 of 23
3 Technical data for retrofit circuit-breaker 8DN8
Standard
IEC, latest edition (at the time of the
development)
Rated voltage 123 – 145 kV
Rated frequency 50/60 Hz
Rated short-time power-frequency withstand
voltage
230 – 275 kV
Rated lightning impulse withstand voltage 550 – 650 kV
Rated normal current 3150 A
Rated short-circuit-breaking current 40 kA
Rated short-time withstand current 40 kA
Rated duration of short-circuit </= 3 s
Rated peak withstand current 100 kA
First-pole-to-clear-factor 1.5
SF6 filling pressure at 20 °C 0.56 MPa
Loss of SF6 0.52 MPa
General lockout SF6 0.50 MPa
Volume of SF6 gas: 35kg
Break time 60 ms
Opening time 32 +/- 3 ms
Arcing time (50 Hz) 24 ms
Closing time 55 +/- 6 ms
Operating sequence (IEC) CO-15s-CO or O-0.3s-CO-3min-CO
Motor spring operating mechanism
220 V DC / 3.0 A / 10 A
230 V AC / 8.0 A / 20 A
Auto reclosing 3-pole
Closing coil 225 W at 220 V DC
Tripping coil 225 W at 220 V DC
Auxiliary switch 8 NO/8 NC/1 WI; 250 V / 2.5 A
Weight of circuit-breaker without SF6 gas: 900 kg
Tab. 1: Technical data for circuit-breaker 8DN8
Replaces: Circuit- breaker for 8D1 and 8D2 up to 145 kV, double-pressure type and blast piston
type
Page 7 of 23
4 Adapter – retrofitting circuit-breaker 8DN8 – existing
switchgear
The adapter, two of which are needed for connecting the new circuit-breaker to the existing
switchgear, is type-tested with 650 kV rated lightning impulse withstand voltage and connects the
three-phase encapsulated circuit-breaker with the single-phase encapsulated switchgear.
The adapter forms a single SF6-gas compartment with joint gas monitoring together with the
circuit-breaker. It is connected to the existing GIS switchgear through gas-tight bushings.
Rated lightning impulse withstand voltage: 650 kV
Weight of an adapter: approx. 200 kg
SF6 filling pressure at 20°C: 0.56 MPa
Volume of SF6 gas/adapter: 18.75 kg
Tab. 2: Technical data of the adapter
Fig. 3: 8D2 bay with old blast piston circuit-breaker
Page 8 of 23
Retrofit 8DN8 self-
compression circuit-
breaker 123 kV
8D1/2 double pressure
circuit-breaker
123 kV
8D2 blast piston circuit-
breaker 123/145 kV
Circuit-breaker 35 kg
Adapter 2 x 18.75 kg
Total volume SF6 gas 72.5 kg 105 kg 87 kg
Tab. 3: Comparison SF6 content old/new
Fig. 4: 8D2 bay with 8DN8 circuit-breaker
Page 9 of 23
Fig. 5: 8DN8-circuit-breaker with two adapters equipped with gas-tight bushings towards the GIS section
Fig. 6: Side view of the 8DN8 circuit-breaker with two adapters
Page 10 of 23
Fig. 3 shows the original system with 8D2 blast piston circuit-breaker. In Fig. 4, the circuit-breaker is
replaced by an 8DN8 circuit-breaker. The connection between the 3-phase encapsulated 8DN8
circuit-breaker and the remaining single-phase 8D2 encapsulated GIS section is implemented via
two adapters as shown in perspective in Fig. 5. Fig. 6 shows a side view from left to right:
 Upper and lower adapter - transition from single-phase encapsulation to 3-phase
encapsulation
 3-phase encapsulated 8DN8 circuit-breaker
Fig. 7: Top view of 8DN8-circuit-breaker with two adapters
Fig. 7 shows the top view of the three-pole encapsulated 8DN8 circuit-breaker with indicated
contact arrangement connected to the single-pole encapsulated adapters.
Page 11 of 23
Fig. 8: Top view of contact arrangement
Fig. 8 shows the contact arrangement of the adapter.
Page 12 of 23
5 Retrofitting steps
Fig. 9: Side view of an 8D switchgear with doublel-pressure circuit-breaker
Fig. 9 shows the typical design of a 8D bay with doublel-pressure circuit-breaker
Fig. 10: Electrical view
Legend: red= voltage, green: no voltage
Page 13 of 23
Fig. 11: SF6 pressure view
Legend: blue= air at atmospheric pressure; yellow= SF6 at rated pressure
Views 10 and 11 show the second step of the retrofit
1) Switch off circuit -breaker -Q0
2) Switch off disconnectors -Q1, -Q2 and -Q8
3) Switch on and secure earthing switches -Q51 and -Q52
4) Switch off and earth the cable from the remote end
5) Switch off the auxiliary and tripping circuits
6) Perform gas work in accordance with diagram
7) Disassemble old circuit-breaker -Q0 with accessories
8) Check the existing 8D2 bushings and contacts
9) Install the new circuit-breaker with preassembled adapters
10) Install the new circuit-breaker module
11) Evacuate the new circuit-breaker module
12) Modify or replace the VOS (local control cubicle)
13) Top up SF6 to rated pressure
14) Commission the new circuit-breaker
15) Switch on the auxiliary and tripping circuits
16) Switch off the earthing switches -Q51, -Q52 and -Q8 and the earthing switch at the remote
end of the cable.
17) Switch on disconnectors -Q1, -Q2 and -Q8
18) Switch on circuit-breaker -Q0
19) Bay is energized
Figs. 12-18 show the individual steps of the retrofit graphically
Page 14 of 23
Fig. 12: Third retrofitting step (a)
Fig. 13: Third retrofitting step (b)
Page 15 of 23
1,5 to
-Q8
-T5
-Q52
-Q51
-Q9
-Q2 -Q1
BB II BB I
-Z1
-Q0
SF6-Gas Scheme
Fig. 14: Fourth retrofitting step (a)
Fig. 15: Fourth retrofitting step (b)
Page 16 of 23
Fig. 16: Fifth retrofitting step (a)
Page 17 of 23
Fig. 17: Fifth retrofitting step (b)
Page 18 of 23
1792 1115 1245 940
4000 1,5
to
1335
5335
4050
-Q8
-T5
-Q52
-Q51
-Q9
-Q2 -Q1
BB II BB I
-Z1
-Q0
3000
Fig. 18: Sixth retrofitting step: Bay after retrofitting
Page 19 of 23
6 Circuit-breaker maintenance comparison old vs. new
8D1/2
Double -pressure circuit-
breaker
8D2
Blast piston circuit-breaker
8DN8
Self compression circuit-breaker
Minor
inspection (or
enhanced
visual
inspection)
1000 x CO in rated nominal
current range or after 5 years
3000 x CO in rated nominal
current range or after 10 years
3000 x CO in rated nominal current
range or after 17 years
Taking out of service
necessary
Taking out of service
necessary
Taking out of service not necessary
Replacement of blast valve
Major
Inspection
(or standard
inspection)
5000 x CO in rated nominal
current range or after 10
years
6000 x CO in rated nominal
current range or after 20 years
6000 x CO in rated nominal current
range or after 25 years
Taking out of service
necessary
Taking out of service
necessary
Taking out of service necessary
Replacement of blast valve
Tab. 4 Comparison of the maintenance intervals of the different circuit-breakers
Table 4 compares the maintenance intervals of the individual circuit-breaker types over a period of
25 years. It can be plainly seen that the maintenance expenditure as well as the short maintenance
intervals for double-pressure circuit-breaker are no longer economical compared with the new
8DN8-circuit-breaker and no longer in keeping with today’s needs.
Fig. 19 shows the standardized maintenance costs (at today’s costs) of the different circuit-breaker
types over a 25-year operating period which naturally does not represent the whole life span of the
new 8DN8 circuit-breaker. Compared to the new 8DN8-circuit-breaker the maintenance costs for
the 8D1 double-pressure circuit-breaker are about 15 times higher, and the costs for the 8D2- blast
piston circuit-breaker still 3 times as high.
Page 20 of 23
Fig. 19: Standardized maintenance costs
- blue: Double-pressure circuit-breaker 8D1/8D2
- red: Blast piston circuit-breaker 8D2
- yellow: Self compression circuit-breaker 8DN8
Page 21 of 23
7 Time schedule for retrofit solution
The total duration from the receipt of the order to the provisional acceptance test is approximately
9 months referred to 1 bay. The actual retrofit, for example the dismantling of the existing circuit-
breaker, installation of the new circuit-breaker, start-up and high voltage testing takes
approximately 4 weeks.
8 Scope of delivery
The scope of delivery comprises:
 Circuit-breaker 8DN8, 3-phase encapsulated, including supporting structure
 SF6 gas (2 x 40 kg bottles to ensure problem-free conversion); SF6 gas from the old 8D1/2
breaker is reused)
 2 adapters – from 3-phase encapsulated circuit-breaker to single-phase switchgear
 Small parts such as sealing material, filter material, etc.
 Control cubicle adaptation components or complete new control cubicle
9 Life time expectation of existing GIS without new
circuit-breaker
A life expectancy > 50 years is predicted for the remaining GIS components, provided that the
Siemens maintenance recommendations have been followed as described in the operating manual.
Tests on the gastight insulators of an over 40-year old 8D2 GIS did not show any discrepancies. The
insulators did not produce any partial discharges. Naturally, if desired, a retrofit can be carried out
on the existing disconnector and earthing switches. These devices can then be equipped with the
latest motor drives.
10 Type tests
Type tests are available for the retrofit 8DN8-circuit-breaker.
Page 22 of 23
11 Options
 Local control cubicle, including control cable
 Service measures on the bays in conjunction with the planned retrofit
 Retrofitting of the disconnector / earthing switch drives with the latest generation of drives
 Overhaul of the dismantled 8D1/8D2 circuit-breaker
 Decentralized SF6 gas monitoring
 Replacement of old cast-resin voltage transformer with SF6-insulated transformer
 UHF antennas
Page 23 of 23
Published by and copyright © 2011:
Siemens AG
Energy Sector
Freyeslebenstrasse 1
91058 Erlangen, Germany
Siemens AG
Energy Sector
Power Distribution Division
Transmission and Distribution Services
Humboldtstrasse 59
90459 Nuremberg, Germany
For more information, please contact
our Customer Support Center.
Phone: +49 180/524 70 00
Fax: +49 180/524 24 71
(Charges depending on provider)
E-mail: support.energy@siemens.com
Power Distribution Division
Transmission and Distribution Services
Order No. SE_AS_1010e_W3233-8D1D2Retrofit
Printed in Germany
Printed on elementary chlorine-free bleached paper.
All rights reserved.
Trademarks mentioned in this document
are the property of Siemens AG, its affiliates,
or their respective owners.
Subject to change without prior notice.
The information in this document contains
general descriptions of the technical options
available, which may not apply in all cases.
The required technical options should therefore
be specified in the contract.

More Related Content

What's hot

IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)
IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)
IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)AHMED MOHAMED HEGAB
 
2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revbVan Phuong Pham
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introductionH. Kheir
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protectionsrini09
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersSARAVANAN A
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a SubstationMd. Atiqur Rahman
 
Copper Cable Lugs and Terminals Catalogue
Copper Cable Lugs and Terminals CatalogueCopper Cable Lugs and Terminals Catalogue
Copper Cable Lugs and Terminals CatalogueGrey Hawk Electricals
 
350328726-2017-Celdas-Mt.pptx
350328726-2017-Celdas-Mt.pptx350328726-2017-Celdas-Mt.pptx
350328726-2017-Celdas-Mt.pptxlgv2
 
Interlocking on switchgear principles
Interlocking on switchgear principlesInterlocking on switchgear principles
Interlocking on switchgear principlesBryan Johnson
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substationhimanshu kumar
 
Electrical Grid Substation
Electrical Grid SubstationElectrical Grid Substation
Electrical Grid SubstationAng Sovann
 
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxNGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxMUHAMMAD TAHIR
 
7SD61 Cable Differential Protection Relay
7SD61 Cable Differential Protection Relay7SD61 Cable Differential Protection Relay
7SD61 Cable Differential Protection Relayashwini reliserv
 
A2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorialA2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorialJack Duff
 

What's hot (20)

GUIDE TO OVERALL OVERHEAD LINE DESIGN
GUIDE TO OVERALL OVERHEAD LINE  DESIGNGUIDE TO OVERALL OVERHEAD LINE  DESIGN
GUIDE TO OVERALL OVERHEAD LINE DESIGN
 
IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)
IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)
IEEE Guide for Field Testing of Shielded Power Cable (IEEE 400.2 2013)
 
2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb2. station transformer 100 mva 230kv-datasheet revb
2. station transformer 100 mva 230kv-datasheet revb
 
Transformers protection, an introduction
Transformers protection, an introductionTransformers protection, an introduction
Transformers protection, an introduction
 
Bus Bar protection
Bus Bar protectionBus Bar protection
Bus Bar protection
 
Practical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineersPractical handbook-for-relay-protection-engineers
Practical handbook-for-relay-protection-engineers
 
Switchgear Equipment in a Substation
Switchgear Equipment in a SubstationSwitchgear Equipment in a Substation
Switchgear Equipment in a Substation
 
GIS-NESCL-6
GIS-NESCL-6GIS-NESCL-6
GIS-NESCL-6
 
Copper Cable Lugs and Terminals Catalogue
Copper Cable Lugs and Terminals CatalogueCopper Cable Lugs and Terminals Catalogue
Copper Cable Lugs and Terminals Catalogue
 
350328726-2017-Celdas-Mt.pptx
350328726-2017-Celdas-Mt.pptx350328726-2017-Celdas-Mt.pptx
350328726-2017-Celdas-Mt.pptx
 
Interlocking on switchgear principles
Interlocking on switchgear principlesInterlocking on switchgear principles
Interlocking on switchgear principles
 
Gas insulated substation
Gas insulated substationGas insulated substation
Gas insulated substation
 
IEEE substation design
IEEE substation designIEEE substation design
IEEE substation design
 
Electrical Grid Substation
Electrical Grid SubstationElectrical Grid Substation
Electrical Grid Substation
 
Transformer
TransformerTransformer
Transformer
 
132 kv
132 kv132 kv
132 kv
 
NGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptxNGR & Zig-Zag Transformer.pptx
NGR & Zig-Zag Transformer.pptx
 
7SD61 Cable Differential Protection Relay
7SD61 Cable Differential Protection Relay7SD61 Cable Differential Protection Relay
7SD61 Cable Differential Protection Relay
 
A2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorialA2.34+transformer+maintenance+tutorial
A2.34+transformer+maintenance+tutorial
 
Substation overview
Substation overviewSubstation overview
Substation overview
 

Similar to Gis basics

Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...
Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...
Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...AUTHELECTRONIC
 
Dual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion Systems
Dual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion SystemsDual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion Systems
Dual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion SystemsIRJET Journal
 
A Three Phase AC-AC ZCS Resonant Converter for Induction Heating
A Three Phase AC-AC ZCS Resonant Converter for Induction HeatingA Three Phase AC-AC ZCS Resonant Converter for Induction Heating
A Three Phase AC-AC ZCS Resonant Converter for Induction HeatingIJMTST Journal
 
Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...
Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...
Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...IRJET Journal
 
3.7 GHz Microwave Amplifier Design
3.7 GHz Microwave Amplifier Design3.7 GHz Microwave Amplifier Design
3.7 GHz Microwave Amplifier DesignRashad Alsaffar
 
PowerElectronics_FinalDesign
PowerElectronics_FinalDesignPowerElectronics_FinalDesign
PowerElectronics_FinalDesignSpencer Minder
 
Original MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 NewOriginal MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 NewAUTHELECTRONIC
 
Original IGBT IGW25N120 G25H1203 25A 1200V TO-3P New
Original IGBT IGW25N120 G25H1203 25A 1200V TO-3P NewOriginal IGBT IGW25N120 G25H1203 25A 1200V TO-3P New
Original IGBT IGW25N120 G25H1203 25A 1200V TO-3P Newauthelectroniccom
 
Dienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecapDienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecapDien Ha The
 
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationIRJET Journal
 
Implementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 V
Implementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 VImplementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 V
Implementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 VIJECEIAES
 
Product: UPS: UniStar VP
Product: UPS: UniStar VPProduct: UPS: UniStar VP
Product: UPS: UniStar VPStaco Energy
 
Lot 04 - AL SAAD Brackish water and reverse osmosis plant
Lot 04 - AL SAAD Brackish water and reverse osmosis plantLot 04 - AL SAAD Brackish water and reverse osmosis plant
Lot 04 - AL SAAD Brackish water and reverse osmosis plantMohammed Abdelkawy
 
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...IJNLC Int.Jour on Natural Lang computing
 
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V NewOriginal MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V NewAUTHELECTRONIC
 
Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...
Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...
Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...IRJET Journal
 

Similar to Gis basics (20)

Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...
Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...
Original N-CHANNEL MOSFET GP8NC60KD 8NC60KD 8NC60 15A 600V TO-220 New STMicro...
 
Cd00003612
Cd00003612Cd00003612
Cd00003612
 
Bq24195l
Bq24195lBq24195l
Bq24195l
 
Dual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion Systems
Dual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion SystemsDual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion Systems
Dual Bridge Rectifier for PMSG Variable Speed Wind Energy Conversion Systems
 
A Three Phase AC-AC ZCS Resonant Converter for Induction Heating
A Three Phase AC-AC ZCS Resonant Converter for Induction HeatingA Three Phase AC-AC ZCS Resonant Converter for Induction Heating
A Three Phase AC-AC ZCS Resonant Converter for Induction Heating
 
Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...
Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...
Series Voltage Compensator Modeling and Design for Reduction of Grid-Tie Sola...
 
3.7 GHz Microwave Amplifier Design
3.7 GHz Microwave Amplifier Design3.7 GHz Microwave Amplifier Design
3.7 GHz Microwave Amplifier Design
 
PowerElectronics_FinalDesign
PowerElectronics_FinalDesignPowerElectronics_FinalDesign
PowerElectronics_FinalDesign
 
Original MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 NewOriginal MOSFET P20NM60 20NM60 20N60C3 20N60 New
Original MOSFET P20NM60 20NM60 20N60C3 20N60 New
 
Mcb c60 h dc
Mcb c60 h dcMcb c60 h dc
Mcb c60 h dc
 
Original IGBT IGW25N120 G25H1203 25A 1200V TO-3P New
Original IGBT IGW25N120 G25H1203 25A 1200V TO-3P NewOriginal IGBT IGW25N120 G25H1203 25A 1200V TO-3P New
Original IGBT IGW25N120 G25H1203 25A 1200V TO-3P New
 
Dienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecapDienhathe.com catalogue epcos-capacitor_phasecap
Dienhathe.com catalogue epcos-capacitor_phasecap
 
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated SubstationModeling and Analysis of a 3-Phase 132kv GasInsulated Substation
Modeling and Analysis of a 3-Phase 132kv GasInsulated Substation
 
Implementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 V
Implementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 VImplementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 V
Implementation of Buck-Boost Converter as Low Voltage Stabilizer at 15 V
 
Product: UPS: UniStar VP
Product: UPS: UniStar VPProduct: UPS: UniStar VP
Product: UPS: UniStar VP
 
Lot 04 - AL SAAD Brackish water and reverse osmosis plant
Lot 04 - AL SAAD Brackish water and reverse osmosis plantLot 04 - AL SAAD Brackish water and reverse osmosis plant
Lot 04 - AL SAAD Brackish water and reverse osmosis plant
 
DFIG_report
DFIG_reportDFIG_report
DFIG_report
 
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
A High Step Up Hybrid Switch Converter Connected With PV Array For High Volta...
 
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V NewOriginal MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
Original MOSFET N-Channel STGF10NC60KD GF10NC60KD 10NC60 10N60 10A 600V New
 
Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...
Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...
Closed Loop Control of Hybrid Boosting Converter for Renewable Energy Applica...
 

Recently uploaded

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Dr.Costas Sachpazis
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and usesDevarapalliHaritha
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AIabhishek36461
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxwendy cai
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girlsssuser7cb4ff
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidNikhilNagaraju
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 

Recently uploaded (20)

Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
Sheet Pile Wall Design and Construction: A Practical Guide for Civil Engineer...
 
power system scada applications and uses
power system scada applications and usespower system scada applications and uses
power system scada applications and uses
 
Past, Present and Future of Generative AI
Past, Present and Future of Generative AIPast, Present and Future of Generative AI
Past, Present and Future of Generative AI
 
What are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptxWhat are the advantages and disadvantages of membrane structures.pptx
What are the advantages and disadvantages of membrane structures.pptx
 
Call Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call GirlsCall Girls Narol 7397865700 Independent Call Girls
Call Girls Narol 7397865700 Independent Call Girls
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
main PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfidmain PPT.pptx of girls hostel security using rfid
main PPT.pptx of girls hostel security using rfid
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptxExploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
Exploring_Network_Security_with_JA3_by_Rakesh Seal.pptx
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 

Gis basics

  • 1. Retrofit for gas-insulated high voltage switchgear (GIS) - 8D1 and 8D2
  • 2. Page 2 of 23 Table of Contents 1 Introduction .............................................................................................................. 4 2 Description of retrofit circuit-breaker 8DN8 ................................................................ 5 3 Technical data for retrofit circuit-breaker 8DN8 .......................................................... 6 4 Adapter - retrofitting circuit-breaker 8DN8 - existing switchgear ................................. 7 5 Retrofitting steps ..................................................................................................... 12 6 Circuit-breaker maintenance comparison old vs. new ............................................... 19 7 Time schedule for retrofit solution............................................................................ 21 8 Scope of delivery ..................................................................................................... 21 9 Life time expectation of existing GIS without new circuit-breaker.............................. 21 10 Type tests ................................................................................................................ 21 11 Options ................................................................................................................... 22
  • 3. Page 3 of 23 List of Figures Fig. 1: Existing substation with 8D2 double-pressure circuit-breaker............................................... 4 Fig. 2: Main dimensions of retrofit circuit-breaker 8DN8................................................................. 5 Fig. 3: 8D2 bay with old blast piston circuit-breaker........................................................................ 7 Fig. 4: 8D2 bay with 8DN8 circuit-breaker ...................................................................................... 8 Fig. 5: 8DN8-circuit-breaker with two adapters equipped with gas-tight bushings towards the GIS section ............................................................................................................................... 9 Fig. 6: Side view of the 8DN8 circuit-breaker with two adapters...................................................... 9 Fig. 7: Top view of 8DN8-circuit-breaker with two adapters.......................................................... 10 Fig. 8: Top view of contact arrangement ...................................................................................... 11 Fig. 9: Side view of an 8D switchgear with doublel-pressure circuit-breaker .................................. 12 Fig. 10: Electrical view ................................................................................................................. 12 Fig. 11: SF6 pressure view............................................................................................................ 13 Fig. 12: Third retrofitting step (a)................................................................................................. 14 Fig. 13: Third retrofitting step (b)................................................................................................. 14 Fig. 14: Fourth retrofitting step (a)............................................................................................... 15 Fig. 15: Fourth retrofitting step (b) .............................................................................................. 15 Fig. 16: Fifth retrofitting step (a).................................................................................................. 16 Fig. 17: Fifth retrofitting step (b).................................................................................................. 17 Fig. 18: Sixth retrofitting step: Bay after retrofitting ..................................................................... 18 Fig. 19: Standardized maintenance costs ..................................................................................... 20 List of Tables Tab. 1: Technical data for circuit-breaker 8DN8 .............................................................................. 6 Tab. 2: Technical data of the adapter ............................................................................................. 7 Tab. 3: Comparison SF6 content old/new........................................................................................ 8 Tab. 4: Comparison of the maintenance intervals of the different circuit-breakers......................... 19
  • 4. Page 4 of 23 1 Introduction The first SF6-gas insulated switchgear of type 8D1 and 8D2 delivered by Siemens are now 40 years and older. These substations have proved outstanding in operation. They are rugged, reliable, and virtually leak-free (SF6 or oil) and still fulfill their function perfectly. Today, stricter and more economically focused standards apply with respect to the maintenance of gas-insulated switchgear. Especially the SF6 – double -pressure circuit-breakers used since GIS systems were first introduced on the market are highly maintenance-intensive. However, since the other GIS components (excluding the original circuit-breaker) require very little maintenance and have an expected life span of over 50 years provided the Siemens maintenance recommendations described in the operating manual are followed, Siemens offers a retrofit solution. This is in the form of a state-of-the-art SF6-circuit-breaker with spring mechanism based on more than 40 years of accumulated experience and intensive research. Fig. 1: Existing substation with 8D2 double-pressure circuit-breaker
  • 5. Page 5 of 23 2 Description of retrofit circuit-breaker 8DN8 The circuit-breaker employed in this retrofit solution is used in the current GIS and HIS substations 8DN8 up to 145 kV and also in 123 kV and 145 kV outdoor circuit-breakers. This type-tested breaker has proven itself in service over the years in thousands of applications. The most important advantages of this self-compression circuit-breaker of the latest generation are:  Significantly lower maintenance costs (see chapter 6)  Type-tested to the latest IEC standard (at the time of the development)  State-of–the-art spring mechanism with extremely low maintenance Fig. 2: Main dimensions of retrofit circuit-breaker 8DN8
  • 6. Page 6 of 23 3 Technical data for retrofit circuit-breaker 8DN8 Standard IEC, latest edition (at the time of the development) Rated voltage 123 – 145 kV Rated frequency 50/60 Hz Rated short-time power-frequency withstand voltage 230 – 275 kV Rated lightning impulse withstand voltage 550 – 650 kV Rated normal current 3150 A Rated short-circuit-breaking current 40 kA Rated short-time withstand current 40 kA Rated duration of short-circuit </= 3 s Rated peak withstand current 100 kA First-pole-to-clear-factor 1.5 SF6 filling pressure at 20 °C 0.56 MPa Loss of SF6 0.52 MPa General lockout SF6 0.50 MPa Volume of SF6 gas: 35kg Break time 60 ms Opening time 32 +/- 3 ms Arcing time (50 Hz) 24 ms Closing time 55 +/- 6 ms Operating sequence (IEC) CO-15s-CO or O-0.3s-CO-3min-CO Motor spring operating mechanism 220 V DC / 3.0 A / 10 A 230 V AC / 8.0 A / 20 A Auto reclosing 3-pole Closing coil 225 W at 220 V DC Tripping coil 225 W at 220 V DC Auxiliary switch 8 NO/8 NC/1 WI; 250 V / 2.5 A Weight of circuit-breaker without SF6 gas: 900 kg Tab. 1: Technical data for circuit-breaker 8DN8 Replaces: Circuit- breaker for 8D1 and 8D2 up to 145 kV, double-pressure type and blast piston type
  • 7. Page 7 of 23 4 Adapter – retrofitting circuit-breaker 8DN8 – existing switchgear The adapter, two of which are needed for connecting the new circuit-breaker to the existing switchgear, is type-tested with 650 kV rated lightning impulse withstand voltage and connects the three-phase encapsulated circuit-breaker with the single-phase encapsulated switchgear. The adapter forms a single SF6-gas compartment with joint gas monitoring together with the circuit-breaker. It is connected to the existing GIS switchgear through gas-tight bushings. Rated lightning impulse withstand voltage: 650 kV Weight of an adapter: approx. 200 kg SF6 filling pressure at 20°C: 0.56 MPa Volume of SF6 gas/adapter: 18.75 kg Tab. 2: Technical data of the adapter Fig. 3: 8D2 bay with old blast piston circuit-breaker
  • 8. Page 8 of 23 Retrofit 8DN8 self- compression circuit- breaker 123 kV 8D1/2 double pressure circuit-breaker 123 kV 8D2 blast piston circuit- breaker 123/145 kV Circuit-breaker 35 kg Adapter 2 x 18.75 kg Total volume SF6 gas 72.5 kg 105 kg 87 kg Tab. 3: Comparison SF6 content old/new Fig. 4: 8D2 bay with 8DN8 circuit-breaker
  • 9. Page 9 of 23 Fig. 5: 8DN8-circuit-breaker with two adapters equipped with gas-tight bushings towards the GIS section Fig. 6: Side view of the 8DN8 circuit-breaker with two adapters
  • 10. Page 10 of 23 Fig. 3 shows the original system with 8D2 blast piston circuit-breaker. In Fig. 4, the circuit-breaker is replaced by an 8DN8 circuit-breaker. The connection between the 3-phase encapsulated 8DN8 circuit-breaker and the remaining single-phase 8D2 encapsulated GIS section is implemented via two adapters as shown in perspective in Fig. 5. Fig. 6 shows a side view from left to right:  Upper and lower adapter - transition from single-phase encapsulation to 3-phase encapsulation  3-phase encapsulated 8DN8 circuit-breaker Fig. 7: Top view of 8DN8-circuit-breaker with two adapters Fig. 7 shows the top view of the three-pole encapsulated 8DN8 circuit-breaker with indicated contact arrangement connected to the single-pole encapsulated adapters.
  • 11. Page 11 of 23 Fig. 8: Top view of contact arrangement Fig. 8 shows the contact arrangement of the adapter.
  • 12. Page 12 of 23 5 Retrofitting steps Fig. 9: Side view of an 8D switchgear with doublel-pressure circuit-breaker Fig. 9 shows the typical design of a 8D bay with doublel-pressure circuit-breaker Fig. 10: Electrical view Legend: red= voltage, green: no voltage
  • 13. Page 13 of 23 Fig. 11: SF6 pressure view Legend: blue= air at atmospheric pressure; yellow= SF6 at rated pressure Views 10 and 11 show the second step of the retrofit 1) Switch off circuit -breaker -Q0 2) Switch off disconnectors -Q1, -Q2 and -Q8 3) Switch on and secure earthing switches -Q51 and -Q52 4) Switch off and earth the cable from the remote end 5) Switch off the auxiliary and tripping circuits 6) Perform gas work in accordance with diagram 7) Disassemble old circuit-breaker -Q0 with accessories 8) Check the existing 8D2 bushings and contacts 9) Install the new circuit-breaker with preassembled adapters 10) Install the new circuit-breaker module 11) Evacuate the new circuit-breaker module 12) Modify or replace the VOS (local control cubicle) 13) Top up SF6 to rated pressure 14) Commission the new circuit-breaker 15) Switch on the auxiliary and tripping circuits 16) Switch off the earthing switches -Q51, -Q52 and -Q8 and the earthing switch at the remote end of the cable. 17) Switch on disconnectors -Q1, -Q2 and -Q8 18) Switch on circuit-breaker -Q0 19) Bay is energized Figs. 12-18 show the individual steps of the retrofit graphically
  • 14. Page 14 of 23 Fig. 12: Third retrofitting step (a) Fig. 13: Third retrofitting step (b)
  • 15. Page 15 of 23 1,5 to -Q8 -T5 -Q52 -Q51 -Q9 -Q2 -Q1 BB II BB I -Z1 -Q0 SF6-Gas Scheme Fig. 14: Fourth retrofitting step (a) Fig. 15: Fourth retrofitting step (b)
  • 16. Page 16 of 23 Fig. 16: Fifth retrofitting step (a)
  • 17. Page 17 of 23 Fig. 17: Fifth retrofitting step (b)
  • 18. Page 18 of 23 1792 1115 1245 940 4000 1,5 to 1335 5335 4050 -Q8 -T5 -Q52 -Q51 -Q9 -Q2 -Q1 BB II BB I -Z1 -Q0 3000 Fig. 18: Sixth retrofitting step: Bay after retrofitting
  • 19. Page 19 of 23 6 Circuit-breaker maintenance comparison old vs. new 8D1/2 Double -pressure circuit- breaker 8D2 Blast piston circuit-breaker 8DN8 Self compression circuit-breaker Minor inspection (or enhanced visual inspection) 1000 x CO in rated nominal current range or after 5 years 3000 x CO in rated nominal current range or after 10 years 3000 x CO in rated nominal current range or after 17 years Taking out of service necessary Taking out of service necessary Taking out of service not necessary Replacement of blast valve Major Inspection (or standard inspection) 5000 x CO in rated nominal current range or after 10 years 6000 x CO in rated nominal current range or after 20 years 6000 x CO in rated nominal current range or after 25 years Taking out of service necessary Taking out of service necessary Taking out of service necessary Replacement of blast valve Tab. 4 Comparison of the maintenance intervals of the different circuit-breakers Table 4 compares the maintenance intervals of the individual circuit-breaker types over a period of 25 years. It can be plainly seen that the maintenance expenditure as well as the short maintenance intervals for double-pressure circuit-breaker are no longer economical compared with the new 8DN8-circuit-breaker and no longer in keeping with today’s needs. Fig. 19 shows the standardized maintenance costs (at today’s costs) of the different circuit-breaker types over a 25-year operating period which naturally does not represent the whole life span of the new 8DN8 circuit-breaker. Compared to the new 8DN8-circuit-breaker the maintenance costs for the 8D1 double-pressure circuit-breaker are about 15 times higher, and the costs for the 8D2- blast piston circuit-breaker still 3 times as high.
  • 20. Page 20 of 23 Fig. 19: Standardized maintenance costs - blue: Double-pressure circuit-breaker 8D1/8D2 - red: Blast piston circuit-breaker 8D2 - yellow: Self compression circuit-breaker 8DN8
  • 21. Page 21 of 23 7 Time schedule for retrofit solution The total duration from the receipt of the order to the provisional acceptance test is approximately 9 months referred to 1 bay. The actual retrofit, for example the dismantling of the existing circuit- breaker, installation of the new circuit-breaker, start-up and high voltage testing takes approximately 4 weeks. 8 Scope of delivery The scope of delivery comprises:  Circuit-breaker 8DN8, 3-phase encapsulated, including supporting structure  SF6 gas (2 x 40 kg bottles to ensure problem-free conversion); SF6 gas from the old 8D1/2 breaker is reused)  2 adapters – from 3-phase encapsulated circuit-breaker to single-phase switchgear  Small parts such as sealing material, filter material, etc.  Control cubicle adaptation components or complete new control cubicle 9 Life time expectation of existing GIS without new circuit-breaker A life expectancy > 50 years is predicted for the remaining GIS components, provided that the Siemens maintenance recommendations have been followed as described in the operating manual. Tests on the gastight insulators of an over 40-year old 8D2 GIS did not show any discrepancies. The insulators did not produce any partial discharges. Naturally, if desired, a retrofit can be carried out on the existing disconnector and earthing switches. These devices can then be equipped with the latest motor drives. 10 Type tests Type tests are available for the retrofit 8DN8-circuit-breaker.
  • 22. Page 22 of 23 11 Options  Local control cubicle, including control cable  Service measures on the bays in conjunction with the planned retrofit  Retrofitting of the disconnector / earthing switch drives with the latest generation of drives  Overhaul of the dismantled 8D1/8D2 circuit-breaker  Decentralized SF6 gas monitoring  Replacement of old cast-resin voltage transformer with SF6-insulated transformer  UHF antennas
  • 23. Page 23 of 23 Published by and copyright © 2011: Siemens AG Energy Sector Freyeslebenstrasse 1 91058 Erlangen, Germany Siemens AG Energy Sector Power Distribution Division Transmission and Distribution Services Humboldtstrasse 59 90459 Nuremberg, Germany For more information, please contact our Customer Support Center. Phone: +49 180/524 70 00 Fax: +49 180/524 24 71 (Charges depending on provider) E-mail: support.energy@siemens.com Power Distribution Division Transmission and Distribution Services Order No. SE_AS_1010e_W3233-8D1D2Retrofit Printed in Germany Printed on elementary chlorine-free bleached paper. All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract.