Design of Reinforced Concrete Structure
Prepared by:
Ghanashyam Prajapati (13cv88)
LIMIT STATE METHOD
INTRODUCTION
Designer has to ensure the structures, he designs are:
 Fit for their purpose
 Safe
 Economical and durable
2
INTRODUCTION
Following Uncertainties affect the safety of a structure
 about loading
 about material strength and
 about structural dimensions
 about behaviour under load
3
LIMIT STATE DESIGN
Limit State: State at which one of the conditions pertaining
to the structure has reached a limiting value
Limit States
Limit States of Strength Limit States of Serviceability
Strength as governed by material Deflection
Buckling strength Vibration
Stability against overturning, swayFatigue cracks (reparable
damage)
Fatigue Fracture Corrosion
Brittle Fracture Fire resistance 4
RANDOM VARIATIONS
5
Resistance, S
Load effect, Q
f(S)
f(Q)
Qm
Frequency
Probability density functions for strength and load effect
Sm
LIMIT STATES DESIGN
 Basis of Limit States Design
2
Q
2
s
m
m Q
S






6
Fig. 1 Probability distribution of the safety margin R-Q
R-Q
R-Q<0 R-Q>0
(R-Q)m
f(R-Q)
 (R-Q)
PROBABILITY OF FAILURE
 





















 



2
Q
2
R
m
m
Q
R
m
f
Q
R
Q
R
P





7
SAFETY INDEX
 2.32 3.09 3.72 4.27 4.75 5.2 5.61
Pf =  (-) 10-2 10-3 10-4 10-5 10-6 10-7 10-8
2
Q
2
S
m
m Q
S






8
Pf = [- ]
PARTIAL SAFETY FACTOR
)
V
1
(
S
)
V
1
(
Q 2
s
sq
m
2
q
qs
m 


 


9
m
u
k
fk S
Q 
 /


ALLOWABLE STRESS DESIGN (ASD)
 Stresses caused by the characteristic loads must be less than an
“allowable stress”, which is a fraction of the yield strength
 Allowable stress may be defined in terms of a “factor of safety"
which represents a margin for overload and other unknown factors
which could be tolerated by the structure
10
Characteristic
Load Effects
Characteristic Strength
Factor of Safety

Allowable stress = (Yield stress) / (Factor of safety)
Limitations
 Material non-linearity
 Non-linear behaviour in the postbuckled state and the
property of steel to tolerate high stresses by yielding locally
and redistributing the loads not accounted for.
 No allowance for redistribution of loads in statically
indeterminate members
11
ALLOWABLE SRESS DESIGN (ASD)
LIMIT STATES DESIGN
 “Limit States" are various conditions in which a structure would be
considered to have failed to fulfil the purpose for which it was built.
 “Ultimate Limit States” are those catastrophic states,which require a
larger reliability in order to reduce the probability of its occurrence
to a very low level.
 “Serviceability Limit State" refers to the limits on acceptable
performance of the structure during service.
12
GENERAL PRINCIPLES OF
LIMIT STATES DESIGN
 Structure to be designed for the Limit States at which they would
become unfit for their intended purpose by choosing,
appropriate partial safety factors, based on probabilistic
methods.
 Two partial safety factors, one applied to loading (f) and another
to the material strength (m) shall be employed.
13
 f allows for;
 Possible deviation of the actual behaviour of the structure from the
analysis model
 Deviation of loads from specified values and
 Reduced probability that the various loads acting together will
simultaneously reach the characteristic value.
14
LIMIT STATES DESIGN
15
(Load * Load Factor)

(Resistance ) (Resistance
Factor)
• m takes account;
– Possible deviation of the material in the structure from that
assumed in design
– Possible reduction in the strength of the material from its
characteristic value
– Manufacturing tolerances.
– Mode of failure (ductile or brittle)
IS800 SECTION 5 LIMIT STATE DESIGN
 5.1 Basis for Design
 5.2 Limit State Design
 5.3 Actions
 5.4 Strength
 5.5 Factors Governing the Ultimate Strength
 5.5.1 Stability
 5.5.2 Fatigue
 5.5.3 Plastic Collapse
 5.6 Limit State of Serviceability
 5.6.1 Deflection
 5.6.2 Vibration
 5.6.3 Durability
 5.6.4 Fire Resistance
16
5.1 BASIS FOR DESIGN
 the structure shall be designed to withstand safely all loads likely to act
on it throughout its life.
 It shall also satisfy the serviceability requirements, such as limitations of
deflection and vibration.
 It shall not suffer total collapse under accidental loads such as from
explosions or impact or due to consequences of human error to an
extent beyond the local damages.
 The objective of design is to achieve a structure that will remain fit for
use during its life with an acceptable target reliability.
17
5.1.3
The potential for catastrophic damage shall be limited or avoided by
appropriate choice of one or more of the following:
 i) avoiding, eliminating or reducing exposure to hazards, which the
structure is likely to sustain.
 ii) choosing structural forms, layouts and details and designing such
that
 the structure has low sensitivity to hazardous conditions.
 the structure survives with only local damage even after serious
damage to any one individual element by the hazard.
18
CONDITIONS TO BE SATISFIED TO AVOID
A DISPROPORTIONATE COLLAPSE
 building should be effectively tied together at each principal floor
level and each column should be effectively held in position by
means of continuous ties (beams) nearly orthogonal
 each storey of the building should be checked to ensure
disproportionate collapse would not precipitate by the notional
removal, one at a time, of each column.
 check should be made at each storey by removing one lateral
support system at a time to ensure disproportionate collapse would
not occur.
19
ACTIONS
 5.3.1 Classification of Actions 
 by their variation with time as given below:
 a) Permanent Actions (Qp): Actions due to self-weight of structural and
non-structural components, fittings, ancillaries, and fixed equipment etc.
 b) Variable Actions (Qv): Actions due to construction and service stage
loads such as imposed (live) loads (crane loads, snow loads etc.), wind
loads, and earthquake loads etc.
 c) Accidental Actions (Qa): Actions due to explosions, impact of vehicles,
and fires etc.
20
PARTIAL SAFETY FACTORS (ACTIONS)
2
1
Combina
tion
Limit State of Strength Limit state of Serviceability
DL
LL WL
/
EL
AL DL
LL
WL
/EL
Lead
ing
Accompa
Nying
Leadi
ng
Accompan
ying
DL+LL+CL 1.5 1.5 1.05   1.0 1.0 1.0 
DL+LL+CL
+
WL/EL
1.2
1.2
1.2
1.2
1.05
0.53
0.6
1.2
 1.0 0.8 0.8 0.8
DL+WL/EL
1.5
(0.9)
*
  1.5  1.0   1.0
DL+ER
1.2
(0.9)
1.2       
DL+LL+AL 1.0 0.35 0.35  1.0    
PARTIAL SAFETY FACTORS (STRENGTH)
Sl.
No
Definition Partial Safety Factor
1 Resistance, governed by
yielding mo
1.1
2 Resistance of member to
buckling mo
1.1
3 Resistance, governed by
ultimate stress m1
1.25
4 Resistance of connection m1
Bolts-Friction Type
Bolts-Bearing Type
Rivets
Welds
Shop
Fabrication
s
Field
Fabricatio
ns
1.25
1.25
1.25
1.25
1.25
1.25
1.25
1.50 2
2
5.5 FACTORS GOVERNING THE ULTIMATE
STRENGTH
 frame stability against overturning and sway
 Fatigue design shall be as per Section 13 of this code. When designing
for fatigue, the load factor for action, f, equal to unity shall be used for
the load causing stress fluctuation and stress range.
 Plastic Collapse  Plastic analysis and design may be used if the
requirement specified under the plastic method of analysis (Section 4.5)
are satisfied.
23
5.6 LIMIT STATE OF SERVICEABILITY
 Deflections are to be checked for the most adverse but realistic
combination of service loads and their arrangement, by elastic analysis,
using a load factor of 1.0
 Suitable provisions in the design shall be made for the dynamic effects
of live loads, impact loads and vibration/fatigue due to machinery
operating loads.
 The durability of steel structures shall be ensured by following
recommendations of Section 15.
 Design provisions to resist fire are briefly discussed in Section 16.
2
4
LIMITING DEFLECTIONS UNDER LL ONLY
2
5
Type of
building
Deflectio
n
Design Load Member Supporting
Maximum
Deflection
Indus
trial
building
Vertical
Live
load/Wind
load
Purlins and
Girts
Purlins and
Girts
Elastic cladding
Brittle cladding
Span / 150
Span / 180
Live load Simple span Elastic cladding Span / 240
Live load Simple span Brittle cladding Span / 300
Live load Cantilever span Elastic cladding Span / 120
Live load Cantilever span Brittle cladding Span / 150
Live load or
Wind load
Rafter
supporting
Profiled Metal
Sheeting
Span / 180
Plastered Sheeting Span / 240
Crane load
(Manual
operation)
Gantry Crane Span / 500
Crane load
(Electric
operation
over 50 t)
Gantry Crane Span / 1000
DEFLECTION LIMITS UNDER LL ONLY
Deflection
Design Load Member Supporting
Maximum
Deflection
Lateral
Crane+
wind
No cranes Column
Elastic
cladding
Height / 150
No cranes Column
Masonry/brittle
cladding
Height / 240
Crane
Gantry
(lateral)
Crane Span / 400
Vertical
Live load Floors & roofs
Not
susceptible
to cracking
Span / 300
Live load Floor & Roof
Susceptible to
cracking
Span / 360
Lateral Wind Building --- Height / 500
Wind
Inter storey
drift
---
Storey height
/ 300
2
6
27

More Related Content

Similar to state-method.ppt

3 - Structural Integrity Evaluation of Offshore Wind Turbines - Giuliani
3 - Structural Integrity Evaluation of Offshore Wind Turbines - Giuliani3 - Structural Integrity Evaluation of Offshore Wind Turbines - Giuliani
3 - Structural Integrity Evaluation of Offshore Wind Turbines - GiulianiStroNGER2012
 
Structural Integrity Evaluation of Offshore Wind Turbines
Structural Integrity Evaluation of Offshore Wind TurbinesStructural Integrity Evaluation of Offshore Wind Turbines
Structural Integrity Evaluation of Offshore Wind TurbinesFranco Bontempi
 
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...IRJET Journal
 
Masonry Code Of Practice Amp
Masonry Code Of Practice   AmpMasonry Code Of Practice   Amp
Masonry Code Of Practice AmpTeja Ande
 
Planning, Analysis, Design and Detailing of degree college building by adapti...
Planning, Analysis, Design and Detailing of degree college building by adapti...Planning, Analysis, Design and Detailing of degree college building by adapti...
Planning, Analysis, Design and Detailing of degree college building by adapti...IRJET Journal
 
Ceng 5503 chapter i
Ceng 5503   chapter iCeng 5503   chapter i
Ceng 5503 chapter iseyfen
 
SEISMIC RESISTANT DESING IN STRUCTURAL E
SEISMIC RESISTANT DESING IN STRUCTURAL ESEISMIC RESISTANT DESING IN STRUCTURAL E
SEISMIC RESISTANT DESING IN STRUCTURAL E23se04
 
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”IRJET Journal
 
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDINGSEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDINGIRJET Journal
 
Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...
Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...
Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...P. Pravin Kumar Venkat Rao
 
IRJET- Disproportionate Collapse in Building Structure
IRJET- Disproportionate Collapse in Building StructureIRJET- Disproportionate Collapse in Building Structure
IRJET- Disproportionate Collapse in Building StructureIRJET Journal
 
2 marks Question with Answer for Design of Reinforced Cement Concrete Elements
2 marks Question with Answer for Design of Reinforced Cement Concrete Elements 2 marks Question with Answer for Design of Reinforced Cement Concrete Elements
2 marks Question with Answer for Design of Reinforced Cement Concrete Elements shielaBalanta2
 
A Review on Stressed Skin Behaviour of Steel Façade Frame
A Review on Stressed Skin Behaviour of Steel Façade FrameA Review on Stressed Skin Behaviour of Steel Façade Frame
A Review on Stressed Skin Behaviour of Steel Façade FrameIRJET Journal
 
RCC Unit 003 (1).pdf
RCC  Unit 003 (1).pdfRCC  Unit 003 (1).pdf
RCC Unit 003 (1).pdfamit38457
 
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGSSEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGSIRJET Journal
 
Structure analysis of multistoried building for different plan configuration
Structure analysis of multistoried building for different plan configurationStructure analysis of multistoried building for different plan configuration
Structure analysis of multistoried building for different plan configurationIRJET Journal
 
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...IRJET Journal
 
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabsIRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabsIRJET Journal
 
A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...
A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...
A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...IRJET Journal
 

Similar to state-method.ppt (20)

3 - Structural Integrity Evaluation of Offshore Wind Turbines - Giuliani
3 - Structural Integrity Evaluation of Offshore Wind Turbines - Giuliani3 - Structural Integrity Evaluation of Offshore Wind Turbines - Giuliani
3 - Structural Integrity Evaluation of Offshore Wind Turbines - Giuliani
 
Structural Integrity Evaluation of Offshore Wind Turbines
Structural Integrity Evaluation of Offshore Wind TurbinesStructural Integrity Evaluation of Offshore Wind Turbines
Structural Integrity Evaluation of Offshore Wind Turbines
 
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...
IRJET- Effect of Viscous Dampers on Response Reduction Factor for RCC Frame u...
 
Masonry Code Of Practice Amp
Masonry Code Of Practice   AmpMasonry Code Of Practice   Amp
Masonry Code Of Practice Amp
 
Planning, Analysis, Design and Detailing of degree college building by adapti...
Planning, Analysis, Design and Detailing of degree college building by adapti...Planning, Analysis, Design and Detailing of degree college building by adapti...
Planning, Analysis, Design and Detailing of degree college building by adapti...
 
Ceng 5503 chapter i
Ceng 5503   chapter iCeng 5503   chapter i
Ceng 5503 chapter i
 
SEISMIC RESISTANT DESING IN STRUCTURAL E
SEISMIC RESISTANT DESING IN STRUCTURAL ESEISMIC RESISTANT DESING IN STRUCTURAL E
SEISMIC RESISTANT DESING IN STRUCTURAL E
 
Bdp 1
Bdp 1Bdp 1
Bdp 1
 
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
“A REVIEW STUDY ON STEEL STRUCTURE SUBJECTED TO BLAST LOADING”
 
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDINGSEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
SEISMIC ANALYSIS OF HYBRID STRUCTURAL CONTROL SYSTEM IN RC BUILDING
 
Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...
Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...
Effect of Seismic Zone and Story Height on Response Reduction Factor for SMRF...
 
IRJET- Disproportionate Collapse in Building Structure
IRJET- Disproportionate Collapse in Building StructureIRJET- Disproportionate Collapse in Building Structure
IRJET- Disproportionate Collapse in Building Structure
 
2 marks Question with Answer for Design of Reinforced Cement Concrete Elements
2 marks Question with Answer for Design of Reinforced Cement Concrete Elements 2 marks Question with Answer for Design of Reinforced Cement Concrete Elements
2 marks Question with Answer for Design of Reinforced Cement Concrete Elements
 
A Review on Stressed Skin Behaviour of Steel Façade Frame
A Review on Stressed Skin Behaviour of Steel Façade FrameA Review on Stressed Skin Behaviour of Steel Façade Frame
A Review on Stressed Skin Behaviour of Steel Façade Frame
 
RCC Unit 003 (1).pdf
RCC  Unit 003 (1).pdfRCC  Unit 003 (1).pdf
RCC Unit 003 (1).pdf
 
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGSSEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
SEISMIC EVALUATION OF RETROFITING TO REINFORCED CONCRETE BUILDINGS
 
Structure analysis of multistoried building for different plan configuration
Structure analysis of multistoried building for different plan configurationStructure analysis of multistoried building for different plan configuration
Structure analysis of multistoried building for different plan configuration
 
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
IRJET- Study of Behavior Parameters of the Building with Variations in Story ...
 
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabsIRJET-  	  Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
IRJET- Effect of Bracing and Unbracing in Steel Stuctures by using ETabs
 
A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...
A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...
A RESEARCH ON ANALYSIS OF PROGRESSIVE COLLPSE OF RCC BUILDING WITH BLAST LOAD...
 

Recently uploaded

Presentation on Workplace Politics.ppt..
Presentation on Workplace Politics.ppt..Presentation on Workplace Politics.ppt..
Presentation on Workplace Politics.ppt..Masuk Ahmed
 
0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf
0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf
0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdfssuserded2d4
 
Resumes, Cover Letters, and Applying Online
Resumes, Cover Letters, and Applying OnlineResumes, Cover Letters, and Applying Online
Resumes, Cover Letters, and Applying OnlineBruce Bennett
 
Hot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night StandHot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night Standkumarajju5765
 
Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...
Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...
Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...ranjana rawat
 
TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...
TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...
TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...rightmanforbloodline
 
Top Rated Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated  Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...Top Rated  Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...Call Girls in Nagpur High Profile
 
Dark Dubai Call Girls O525547819 Skin Call Girls Dubai
Dark Dubai Call Girls O525547819 Skin Call Girls DubaiDark Dubai Call Girls O525547819 Skin Call Girls Dubai
Dark Dubai Call Girls O525547819 Skin Call Girls Dubaikojalkojal131
 
Brand Analysis for reggaeton artist Jahzel.
Brand Analysis for reggaeton artist Jahzel.Brand Analysis for reggaeton artist Jahzel.
Brand Analysis for reggaeton artist Jahzel.GabrielaMiletti
 
Call Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangaloreamitlee9823
 
Delhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip CallDelhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Callshivangimorya083
 
Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...
Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...
Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...Pooja Nehwal
 
Bur Dubai Call Girl Service #$# O56521286O Call Girls In Bur Dubai
Bur Dubai Call Girl Service #$# O56521286O Call Girls In Bur DubaiBur Dubai Call Girl Service #$# O56521286O Call Girls In Bur Dubai
Bur Dubai Call Girl Service #$# O56521286O Call Girls In Bur Dubaiparisharma5056
 
CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service 🧳
CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service  🧳CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service  🧳
CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service 🧳anilsa9823
 
Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...
Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...
Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...amitlee9823
 
Internship Report].pdf iiwmoosmsosmshkssmk
Internship Report].pdf iiwmoosmsosmshkssmkInternship Report].pdf iiwmoosmsosmshkssmk
Internship Report].pdf iiwmoosmsosmshkssmkSujalTamhane
 
Get To Know About "Lauren Prophet-Bryant''
Get To Know About "Lauren Prophet-Bryant''Get To Know About "Lauren Prophet-Bryant''
Get To Know About "Lauren Prophet-Bryant''Lauren Prophet-Bryant
 
Dubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big Boody
Dubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big BoodyDubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big Boody
Dubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big Boodykojalkojal131
 
Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...
Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...
Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...amitlee9823
 

Recently uploaded (20)

Presentation on Workplace Politics.ppt..
Presentation on Workplace Politics.ppt..Presentation on Workplace Politics.ppt..
Presentation on Workplace Politics.ppt..
 
0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf
0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf
0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf0425-GDSC-TMU.pdf
 
Resumes, Cover Letters, and Applying Online
Resumes, Cover Letters, and Applying OnlineResumes, Cover Letters, and Applying Online
Resumes, Cover Letters, and Applying Online
 
Sensual Moments: +91 9999965857 Independent Call Girls Paharganj Delhi {{ Mon...
Sensual Moments: +91 9999965857 Independent Call Girls Paharganj Delhi {{ Mon...Sensual Moments: +91 9999965857 Independent Call Girls Paharganj Delhi {{ Mon...
Sensual Moments: +91 9999965857 Independent Call Girls Paharganj Delhi {{ Mon...
 
Hot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night StandHot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night Stand
Hot Call Girls |Delhi |Janakpuri ☎ 9711199171 Book Your One night Stand
 
Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...
Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...
Book Paid Saswad Call Girls Pune 8250192130Low Budget Full Independent High P...
 
TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...
TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...
TEST BANK For An Introduction to Brain and Behavior, 7th Edition by Bryan Kol...
 
Top Rated Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated  Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...Top Rated  Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
Top Rated Pune Call Girls Deccan ⟟ 6297143586 ⟟ Call Me For Genuine Sex Serv...
 
Dark Dubai Call Girls O525547819 Skin Call Girls Dubai
Dark Dubai Call Girls O525547819 Skin Call Girls DubaiDark Dubai Call Girls O525547819 Skin Call Girls Dubai
Dark Dubai Call Girls O525547819 Skin Call Girls Dubai
 
Brand Analysis for reggaeton artist Jahzel.
Brand Analysis for reggaeton artist Jahzel.Brand Analysis for reggaeton artist Jahzel.
Brand Analysis for reggaeton artist Jahzel.
 
Call Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service BangaloreCall Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
Call Girls Bidadi Just Call 👗 7737669865 👗 Top Class Call Girl Service Bangalore
 
Delhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip CallDelhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
Delhi Call Girls South Delhi 9711199171 ☎✔👌✔ Whatsapp Hard And Sexy Vip Call
 
Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...
Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...
Dombivli Call Girls, 9892124323, Kharghar Call Girls, chembur Call Girls, Vas...
 
Bur Dubai Call Girl Service #$# O56521286O Call Girls In Bur Dubai
Bur Dubai Call Girl Service #$# O56521286O Call Girls In Bur DubaiBur Dubai Call Girl Service #$# O56521286O Call Girls In Bur Dubai
Bur Dubai Call Girl Service #$# O56521286O Call Girls In Bur Dubai
 
CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service 🧳
CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service  🧳CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service  🧳
CALL ON ➥8923113531 🔝Call Girls Husainganj Lucknow best Female service 🧳
 
Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...
Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...
Call Girls Devanahalli Just Call 👗 7737669865 👗 Top Class Call Girl Service B...
 
Internship Report].pdf iiwmoosmsosmshkssmk
Internship Report].pdf iiwmoosmsosmshkssmkInternship Report].pdf iiwmoosmsosmshkssmk
Internship Report].pdf iiwmoosmsosmshkssmk
 
Get To Know About "Lauren Prophet-Bryant''
Get To Know About "Lauren Prophet-Bryant''Get To Know About "Lauren Prophet-Bryant''
Get To Know About "Lauren Prophet-Bryant''
 
Dubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big Boody
Dubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big BoodyDubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big Boody
Dubai Call Girls Demons O525547819 Call Girls IN DUbai Natural Big Boody
 
Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...
Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...
Call Girls Jayanagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Ban...
 

state-method.ppt

  • 1. 1 Design of Reinforced Concrete Structure Prepared by: Ghanashyam Prajapati (13cv88) LIMIT STATE METHOD
  • 2. INTRODUCTION Designer has to ensure the structures, he designs are:  Fit for their purpose  Safe  Economical and durable 2
  • 3. INTRODUCTION Following Uncertainties affect the safety of a structure  about loading  about material strength and  about structural dimensions  about behaviour under load 3
  • 4. LIMIT STATE DESIGN Limit State: State at which one of the conditions pertaining to the structure has reached a limiting value Limit States Limit States of Strength Limit States of Serviceability Strength as governed by material Deflection Buckling strength Vibration Stability against overturning, swayFatigue cracks (reparable damage) Fatigue Fracture Corrosion Brittle Fracture Fire resistance 4
  • 5. RANDOM VARIATIONS 5 Resistance, S Load effect, Q f(S) f(Q) Qm Frequency Probability density functions for strength and load effect Sm
  • 6. LIMIT STATES DESIGN  Basis of Limit States Design 2 Q 2 s m m Q S       6 Fig. 1 Probability distribution of the safety margin R-Q R-Q R-Q<0 R-Q>0 (R-Q)m f(R-Q)  (R-Q)
  • 7. PROBABILITY OF FAILURE                             2 Q 2 R m m Q R m f Q R Q R P      7
  • 8. SAFETY INDEX  2.32 3.09 3.72 4.27 4.75 5.2 5.61 Pf =  (-) 10-2 10-3 10-4 10-5 10-6 10-7 10-8 2 Q 2 S m m Q S       8 Pf = [- ]
  • 9. PARTIAL SAFETY FACTOR ) V 1 ( S ) V 1 ( Q 2 s sq m 2 q qs m        9 m u k fk S Q   /  
  • 10. ALLOWABLE STRESS DESIGN (ASD)  Stresses caused by the characteristic loads must be less than an “allowable stress”, which is a fraction of the yield strength  Allowable stress may be defined in terms of a “factor of safety" which represents a margin for overload and other unknown factors which could be tolerated by the structure 10 Characteristic Load Effects Characteristic Strength Factor of Safety 
  • 11. Allowable stress = (Yield stress) / (Factor of safety) Limitations  Material non-linearity  Non-linear behaviour in the postbuckled state and the property of steel to tolerate high stresses by yielding locally and redistributing the loads not accounted for.  No allowance for redistribution of loads in statically indeterminate members 11 ALLOWABLE SRESS DESIGN (ASD)
  • 12. LIMIT STATES DESIGN  “Limit States" are various conditions in which a structure would be considered to have failed to fulfil the purpose for which it was built.  “Ultimate Limit States” are those catastrophic states,which require a larger reliability in order to reduce the probability of its occurrence to a very low level.  “Serviceability Limit State" refers to the limits on acceptable performance of the structure during service. 12
  • 13. GENERAL PRINCIPLES OF LIMIT STATES DESIGN  Structure to be designed for the Limit States at which they would become unfit for their intended purpose by choosing, appropriate partial safety factors, based on probabilistic methods.  Two partial safety factors, one applied to loading (f) and another to the material strength (m) shall be employed. 13
  • 14.  f allows for;  Possible deviation of the actual behaviour of the structure from the analysis model  Deviation of loads from specified values and  Reduced probability that the various loads acting together will simultaneously reach the characteristic value. 14
  • 15. LIMIT STATES DESIGN 15 (Load * Load Factor)  (Resistance ) (Resistance Factor) • m takes account; – Possible deviation of the material in the structure from that assumed in design – Possible reduction in the strength of the material from its characteristic value – Manufacturing tolerances. – Mode of failure (ductile or brittle)
  • 16. IS800 SECTION 5 LIMIT STATE DESIGN  5.1 Basis for Design  5.2 Limit State Design  5.3 Actions  5.4 Strength  5.5 Factors Governing the Ultimate Strength  5.5.1 Stability  5.5.2 Fatigue  5.5.3 Plastic Collapse  5.6 Limit State of Serviceability  5.6.1 Deflection  5.6.2 Vibration  5.6.3 Durability  5.6.4 Fire Resistance 16
  • 17. 5.1 BASIS FOR DESIGN  the structure shall be designed to withstand safely all loads likely to act on it throughout its life.  It shall also satisfy the serviceability requirements, such as limitations of deflection and vibration.  It shall not suffer total collapse under accidental loads such as from explosions or impact or due to consequences of human error to an extent beyond the local damages.  The objective of design is to achieve a structure that will remain fit for use during its life with an acceptable target reliability. 17
  • 18. 5.1.3 The potential for catastrophic damage shall be limited or avoided by appropriate choice of one or more of the following:  i) avoiding, eliminating or reducing exposure to hazards, which the structure is likely to sustain.  ii) choosing structural forms, layouts and details and designing such that  the structure has low sensitivity to hazardous conditions.  the structure survives with only local damage even after serious damage to any one individual element by the hazard. 18
  • 19. CONDITIONS TO BE SATISFIED TO AVOID A DISPROPORTIONATE COLLAPSE  building should be effectively tied together at each principal floor level and each column should be effectively held in position by means of continuous ties (beams) nearly orthogonal  each storey of the building should be checked to ensure disproportionate collapse would not precipitate by the notional removal, one at a time, of each column.  check should be made at each storey by removing one lateral support system at a time to ensure disproportionate collapse would not occur. 19
  • 20. ACTIONS  5.3.1 Classification of Actions   by their variation with time as given below:  a) Permanent Actions (Qp): Actions due to self-weight of structural and non-structural components, fittings, ancillaries, and fixed equipment etc.  b) Variable Actions (Qv): Actions due to construction and service stage loads such as imposed (live) loads (crane loads, snow loads etc.), wind loads, and earthquake loads etc.  c) Accidental Actions (Qa): Actions due to explosions, impact of vehicles, and fires etc. 20
  • 21. PARTIAL SAFETY FACTORS (ACTIONS) 2 1 Combina tion Limit State of Strength Limit state of Serviceability DL LL WL / EL AL DL LL WL /EL Lead ing Accompa Nying Leadi ng Accompan ying DL+LL+CL 1.5 1.5 1.05   1.0 1.0 1.0  DL+LL+CL + WL/EL 1.2 1.2 1.2 1.2 1.05 0.53 0.6 1.2  1.0 0.8 0.8 0.8 DL+WL/EL 1.5 (0.9) *   1.5  1.0   1.0 DL+ER 1.2 (0.9) 1.2        DL+LL+AL 1.0 0.35 0.35  1.0    
  • 22. PARTIAL SAFETY FACTORS (STRENGTH) Sl. No Definition Partial Safety Factor 1 Resistance, governed by yielding mo 1.1 2 Resistance of member to buckling mo 1.1 3 Resistance, governed by ultimate stress m1 1.25 4 Resistance of connection m1 Bolts-Friction Type Bolts-Bearing Type Rivets Welds Shop Fabrication s Field Fabricatio ns 1.25 1.25 1.25 1.25 1.25 1.25 1.25 1.50 2 2
  • 23. 5.5 FACTORS GOVERNING THE ULTIMATE STRENGTH  frame stability against overturning and sway  Fatigue design shall be as per Section 13 of this code. When designing for fatigue, the load factor for action, f, equal to unity shall be used for the load causing stress fluctuation and stress range.  Plastic Collapse  Plastic analysis and design may be used if the requirement specified under the plastic method of analysis (Section 4.5) are satisfied. 23
  • 24. 5.6 LIMIT STATE OF SERVICEABILITY  Deflections are to be checked for the most adverse but realistic combination of service loads and their arrangement, by elastic analysis, using a load factor of 1.0  Suitable provisions in the design shall be made for the dynamic effects of live loads, impact loads and vibration/fatigue due to machinery operating loads.  The durability of steel structures shall be ensured by following recommendations of Section 15.  Design provisions to resist fire are briefly discussed in Section 16. 2 4
  • 25. LIMITING DEFLECTIONS UNDER LL ONLY 2 5 Type of building Deflectio n Design Load Member Supporting Maximum Deflection Indus trial building Vertical Live load/Wind load Purlins and Girts Purlins and Girts Elastic cladding Brittle cladding Span / 150 Span / 180 Live load Simple span Elastic cladding Span / 240 Live load Simple span Brittle cladding Span / 300 Live load Cantilever span Elastic cladding Span / 120 Live load Cantilever span Brittle cladding Span / 150 Live load or Wind load Rafter supporting Profiled Metal Sheeting Span / 180 Plastered Sheeting Span / 240 Crane load (Manual operation) Gantry Crane Span / 500 Crane load (Electric operation over 50 t) Gantry Crane Span / 1000
  • 26. DEFLECTION LIMITS UNDER LL ONLY Deflection Design Load Member Supporting Maximum Deflection Lateral Crane+ wind No cranes Column Elastic cladding Height / 150 No cranes Column Masonry/brittle cladding Height / 240 Crane Gantry (lateral) Crane Span / 400 Vertical Live load Floors & roofs Not susceptible to cracking Span / 300 Live load Floor & Roof Susceptible to cracking Span / 360 Lateral Wind Building --- Height / 500 Wind Inter storey drift --- Storey height / 300 2 6
  • 27. 27