Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
1 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
Retrofitting of Existing RCC Buildings by
Method of Jacketing
BHAVAR DADASAHEB O.
Assistant Professor,
Sandip Institute of Engineering & Managemnt,
At Post Mahiravani, Trimbak Road, Nashik.
Maharashtra (India)
DHAKE PRAVINCHANDRA D.
Assistant Professor,
Dept. of Civil Engineering
KKWIEER, Nashik
Maharashtra (India)
OGALE RAMESH A.
Assistant Professor,
Dept. of Civil Engineering
SSVPS’, BS Deore COE., Dhule
Maharashtra (India)
Abstract:
Many parts of the country have suffered earthquake in last three decades. In costal part of South
India faced Tsunami. In first three earthquakes it was found that many of damaged structures
were build in non-engineered masonry techniques. Unreinforced masonry structures are the
most vulnerable during an earthquake. Normally they are designed for vertical loads and since
masonry has adequate compressive strength, the structures behave well as long as the loads are
vertical. When such a masonry structure is subjected to lateral inertial loads during an
earthquake, the walls develop shear and flexural stresses. The strength of masonry under these
conditions often depends on the bond between brick and mortar (or stone and mortar), which is
quite poor. This bond is also often very poor when lime mortars or mud mortars are used. A
masonry wall can also undergo failure in-plane shear, if the inertial forces are in the plane of
the wall. Shear failure in the form of diagonal cracks is observed due to this. However,
catastrophic collapses take place when the wall experiences out-of-plane flexure. This can bring
down a roof and cause more damage. Masonry buildings with light roofs such as tiled roofs are
more vulnerable to out-of-plane vibrations since the top edge can undergo large deformations. It
is always useful to investigate the behavior of masonry buildings after an earthquake, so as to
identify any inadequacies in earthquake resistant design. Studying types of masonry
construction, their performance and failure patterns helps in improving the design and detailing
aspects.
In previous earthquakes many R.C.C buildings have also collapsed and are found unsafe due to
faulty workmanship. Many other causes are responsible for major collapse and damage to the
R.C.C structures.
The review of the codes shows that there were five zones of earth quakes of Indian subcontinents,
But its revision is now shoeing four zones of earth quake. Some part of Gujarat lies in zone V
which has largest severity of Earthquake. So as the districts that are located on the boundary of
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
2 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
Gujarat – Maharashtra like Nasik, Dhule, Nandoorbar lye in zone III of earthquake zone, zone
III is second largest zone of earth quake in India. Therefore it seems to be an compulsion to have
an review of the old RCC structures (Likely have completed their service period) in and around
Nashik for the structural behaviour to avoid future inconvenience.
This project is just a similar attempt. A health building in the heart of Nashik city is being
strengthened to overcome the future disorders. From the physical and experimental
investigations it was concluded that the building either should be demolished or at least should
be retrofitted with suitable technique to increase its service life.
It was then decided to implement RCC column jacketing technique due to its feasibility and ease
for execution.
All the columns on both the floors are now suitably jacketed, the loose pockets of concrete that
were investigated during the test are reconcreted, the faulty slabs are completely opened and the
rusted reinforcement is replaced with new reinforcement as per the design requirement. And the
slabs are recasted with M25 grade of ready mix concrete.
Keywords: RC jacketing, Rehabilitation, Retrofitting, Strengthening, Structural repair
1. Introduction
1.1 Seismic Strengthening (retrofitting)
Actions taken to upgrade the seismic resistance of an existing building so that it becomes safer
under future earthquakes. This can be in the form of providing seismic bands, eliminating
sources of weakness or concentrations of large mass and openings in walls, adding shear walls or
strong column points in walls, bracing roofs and floors to be able to act as horizontal
diaphragms, adequately connecting roofs to walls and columns and also connecting between
walls and foundations.
1.2 Concept of Retrofitting
Retrofitting is technical interventions in structural system of a building that improve the
resistance to earthquake by optimizing the strength, ductility and earthquake loads. Strength of
the building is generated from the structural dimensions, materials, shape, and number of
structural elements, etc. Ductility of the building is generated from good detailing, materials
used, degree of seismic resistant, etc. Earthquake load is generated from the site seismicity, mass
of the structures, important of buildings, degree of seismic resistant, etc.
Due to the variety of structural condition of building, it is hard to develop typical rules for
retrofitting. Each building has different approaches depending on the structural deficiencies.
Hence, engineers are needed to prepare and design the retrofitting approaches. In the design of
retrofitting approach, the engineer must comply with the building codes. The results generated
by the adopted retrofitting techniques must fulfill the minimum requirements on the buildings
codes, such as deformation, detailing, strength, etc.
1.3 Causes of failure
Damage to buildings were caused by a combination of affects:
 Old decaying buildings predating modern construction practices
 New Buildings not being designed to Indian earthquake codes
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
3 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
 Lack of knowledge, understanding or training in the use of these codes by local engineers
 Unawareness that Gujarat is a highly seismic region
 Buildings erected without owners seeking proper engineering advice
 Improper detailing of masonry and reinforced structures
 Poor materials, construction and workmanship used, particularly in commercial buildings
 Alterations and extensions being carried out without proper regard for effects on structure
during an earthquake
 Buildings having poor quality foundations or foundations built on poor soils
 Little or no regularity authority administering or policing the codes
Generally, commercial buildings were worst affected by the earthquake because of poor
workmanship, use of materials and inadequate attention to detailing.
1.4 Recent Retrofitting Methods
There are many relatively new technologies developed for seismic Retrofitting which are based
on “Response control”. These techniques includes providing additional damping using dampers
(Elasto-plastic dampers, friction dampers, tuned mass and tuned liquid dampers, visco-elastic
dampers, lead extrusion dampers etc.) and techniques such as base isolation which are introduced
to take care of seismic control.
1.4.1 Methods of Retrofitting
Increase the capacity/strength of the system (Seismic Resistance Based Design):
(i) Concrete Jacketing.
(ii) Steel Jacketing.
(iii) FRP Wrapping.
2. Retrofitting of health building at Nasik
2.1 General
In order to overcome the future disorders that may have occurred due to unwanted and no
predicted disasters it was decided to strengthen the existing Health building located in the central
part of Nashik city. This building was proposed in 1984 and accordingly was designed for B + G
+ 4 storeys. The building during its life span at the end in2008 found completely detoriated and
was not capable to sustain further loads. And was predicted that it may fail due to the following
reasons.
a) Higher ground water table in the locality.
b) Faulty workmanship during the stage of execution at initial stage.
c) The columns were not centered properly in their position.
d) Improper methods of compaction to the concrete.
e) Insufficient cover to the steel reinforcement.
In addition to this it may also have caused failure due to the non predicted disasters as was
caused too many buildings in the past which are listed in the next bit.
2.2 Causes of failure and damages to the building in past few earthquakes
Following were the main causes of failure and damages to the buildings in Gujarat &
Maharashtra; causes to buildings same in rest part India.
Damages to buildings were caused by a combination of affects:
1. Old decaying buildings predating modern construction practices
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
4 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
2. New Buildings not being designed to Indian earthquake codes
3. Lack of knowledge, understanding or training in the use of these codes by local engineers
4. Unawareness that Gujarat and some part of Maharashtra is a highly seismic region
5. Buildings erected without owners seeking proper engineering advice
6. Improper detailing of masonry and reinforced structures
7. Poor materials, construction and workmanship used, particularly in commercial buildings
8. Alterations and extensions being carried out without proper regard for effects on structure
during an earthquake.
9. Buildings having poor quality foundations or foundations built on poor soils.
10. Little or no regularity authority administering or policing the codes.
It’s necessary to every civil engineer to have knowledge of proper repairs and strengthening of
earthquake damaged buildings. Indian standards exist but are not used by local engineers or
builders in urban or rural areas, mainly due to lack of knowledge and training. As a result, many
of the owner-occupiers have unknowingly been carrying out bad repairs in Gujarat. Many
buildings have been severely weakened, and the experts are concerned to that there could be
another disaster in waiting from a future earthquake. Good repairs, using well-recognized
seismic standards may reduce this vulnerability.
This project aims in simple terms to explain to the engineers why earthquakes happen in India,
which regions are seismically active, how buildings respond in an earthquake; and how to safely
carry out good repair and strengthening techniques to damaged and low strength buildings.
Fig.1 Some damages those were occurred after earth quake at
Gujarat in non engineered R.C.C building construction
The inset shows large deformations were concentrated at column heads, which caused many soft
storey failures, as per picture. Buildings if designed with uniform deflections of insert would
have survived without collapse.”
2.2.1 Crushing of column head and bases
When masonry infill walls were ineffective because of large openings, column heads were
subjected to large vertical and lateral seismic forces. The heavy eccentric compressive stresses
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
5 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
crushed column heads and large shear deformations caused concrete to spall away from the main
bars because of links being too far apart. The extent of damage to the column heads often
depended on how well the infill wall panels were bonded to the columns.
Some common problems, which resulted in severe damage to the column heads or bases, were
from poor detailing as follows:
(a) Drain pipes and other services placed inside columns, caused severe weakening of the
columns making it less resistant to lateral loading;
(b) Shear link spacing was too large (typically 200-300mm), thus not providing adequate
confinement to the main bars, causing concrete to fall out;
(c) Links were not bent backwards into the columns so they easily separated, again letting
concrete out of the main bars;
(d) Very small links (6mm diameter) were used;
(e) Main bars were not bent back into the floor or ground beams so that reversal of shear loads
could not be resisted by the beam and column connections. Many failures occurred at
beam/column junctions.
2.2.2 Roof failures & Canopy structures
Damage to flat roofs was rare. However, pitched roofs often experienced non-structural damage
by tiles falling through open space between the timber battens as no tiles were nailed into the
timbers. Many tiles were manufactured with no holes to allow them to be nailed to the roof.
Several modern buildings had a single storey canopy with a flat roof supported by columns at
one end and beams running into the main structural frame at the other end. These suffered
varying degrees of damage depending on how slim the columns were.
2.3 Responsibility of building owners
The building owner is responsible for determining the need for the repair and its extent, whether
it is practical and safe to carry out the repair and whether it is within his budget. It is advised that
the building owner should in all cases seek professional advice from a qualified structural
engineer before carrying out any repairs. It is also equally important to retain the services of a
qualified builder when carrying out repairs.
2.4 Responsibility consulting engineers
Its responsibility of consulting engineers to provide safe structural design that can withstand the
earth quake load without any damage to the structures, regular sites visits and technical advice to
the site supervisors and workers is very essential to reduce the bad practices that would be
produce safe and economical shelters to the society.
2.5 Retrofitting of R.C.C Building by Method of Jacketing
As it’s shown in above part of chapter no five, that Nasik and some part of Maharashtra is along
the border part of Gujarat, Gujarat has suffered from severe earth quake in last two decades,
nobody knows which would be the next time of future earth quake & its intensity. Like Gujarat
many constructions in Maharashtra and at Nasik are found as non engineered unsafe & quality
compromised constructions, this would be future risk for coming days. So it is necessary to carry
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
6 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
out the non destructive tests of all construction in Nasik and rest part of India, to save valuable
lives and properties, now a days many advance retrofitting techniques are available in the world,
those can be used to repair & strengthen the unsafe and damaged buildings. Here the paper has
its focus on a Health building which is under execution (for re modification and strengthening of
existing structure).
2.5.1 History of Health Building
A group proposed to start a hospital in Nasik in 1984. And as per the decision the detail plan &
the structural details for the same were prepared. It was proposed to construct a Basement + G +
4 storey structure and the designs were prepared so. The site for the hospital was near Dwarka
circle. Nasik: 11.
Though it was planned to construct 6 storey in all, only 2 storey ( i. e. Basement + G) structure
was constructed in actual when structural details were for 6 storey. The built up area for
basement is 1236 sq.mt. and that of the ground floor is 1178 sq. mt.
This group had a smooth functioning upto 2004. Then in 2005 the administration of the hospital
was changed. New administrative body utilized the same infrastructure up to 2008.
Then in 2009 was decided to extend the building as per the initial plan and structural details. And
for the same had the structural audit in that respect. From the audit that all the defects were at the
execution stage. The faults that were concluded were as below.
a) The high ground water table in the region.
b) Eccentricity of all the columns was a serious problem observed.
c) Improper techniques that were followed during mixing, placing & compacting the concrete.
d) There were many loose pockets found in the concrete.
e) Sufficient concrete cover at different stages to the steel reinforcement was not maintained.
f) The terrace slabs are provided with unwanted thickness of IPS flooring at the top.
From the NDT test results it was suggested that the management should demolish the entire
existing structure instead of extending it and go for complete new structure. The management
refused to do so and asked to suggest such a measure so that the existing infrastructure at least
can withstand and be utilized for 5 – 7 years more. As the final conclusion and the requirement
of the management it was decided to go for ‘Retrofitting of the Structure’.
2.5.2 The steps that were suggested and are adopted are as below
(A) The entire flooring at the basement to be removed & to be provided again with a raft below
it. To overcome the uplift pressure that could be generated due to the higher ground water table it
was suggested to provide a raft below the basement floor.
(B) All the columns should be jacketed. In the existing structure it was found that the columns
were not centered properly in their position, due to which they were subjected to unwanted
eccentric loads. Also the concrete in columns, beams, slabs was not compacted properly which
created loose pockets & honey combs in the components. Suitable cover for the reinforcement
was not maintained.
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
7 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
To overcome the above difficulties it was decided to jacket all the columns such that the
eccentricity of loading will be reduced, the loose pockets of concrete will be capable to sustain
the load to which the column is subjected & all the steel get the required concrete covering.
(C) The loose pockets in the concrete in the beams are also removed and recasted in M25 grade.
(D) The unwanted heavy loading of water proofing (IPS flooring) damaged the slab to greater
extent.
Therefore, five slabs are entirely opened, strengthened with additional reinforcement and are
casted with 150 mm thick M25 grade concrete layer.
The estimated cost of retrofitting the existing structure is 4.5 crore. To meet the further
requirement of infrastructure the management now is constructing additional new building with
G + 2 storey, instead of razing the existing building.
1 2 3
Fig. 2 Photographs shows the step by step stages of retrofitting work for the considered
Health Building at Nashik
View 1. “Column jacketing at basement stage” 2. “beam column junction strengthening in
basement” 3. “finished Column after jacketing work”
Figures shows the work of column jacketing for existing columns for additional strengthening,
for its renovation work. These columns give the additional strength for its future use & make the
structure safe against seismic forces.
4 5 6
View 4. “Rusting condition of existing slabs reinforcement” 6. “Replaced slab reinforcement for
existing rusted steel reinforcement.” 7. “Application of chemical admixtures at the joint of new
and old concrete”
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
8 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
7 8
Fig. 3 Photographs shows the step by step stages of retrofitting work for the considered
Health Building at Nashik
View 7. “compaction of concrete by needle vibrator and placement of cover blocks” 8.“Finished
slab - ready to cure”
As discussed above all works those were carried out on strengthening of the Health building at
Nasik, will definitely increases the strength of existing building, this practice would be necessary
for many buildings at Nasik and rest of India, it will save the many lives, when any natural
disasters will occur.
3. Conclusion
Strengthening of building considered in the report is an attempt to increase the life and to sustain
the unwanted disturbances like, earthquakes floods etc. The building though was proposed to
have been constructed as six storied building and was designed as per requirements, but was
constructed only up to two storey, it should have worked or served for a period mre than the
designed life span, which is not so. And recommended the strengthening at early stage due to
minor effects of disaster, uplift pressure of ground water table, bad workmanships, hence had to
be retrofitted. Timely Repair of the structures can be concluded as, ‘A stitch in time, Saves
nine.’
3.1 Future scope for the work in Nasik area
Project work has focused on strengthening the RCC buildings. There is an large scope to create
an awareness in the occupants/ residents of the buildings those may have completed the service
period and or will probably be completing the service period in short future.
All such buildings in and around Nashik and all the metro cities in the state and country cn be
retrofitted with suitable technique to save the lives and property.
References
1. BS 1881 : Part 202 : 1986
2. Earthquake Engineering 10th
World Conference 1992.
3. IS 13311 – 1992 (Part I).
4. IS 13311 - 1992 – 2008 (Part II).
5. IS 13828 - 1993 (Part I).
6. Repair and Rehabilitation – Indian Concrete Journal, Sept. 1992.
7. Repair and Rehabilitation – Indian Concrete Journal, Nov. 1995.
Bhavar Dadasaheb O. et al. / International Journal of Research in
Modern Engineering and Emerging Technology
Vol. 1, Issue: 5, June: 2013
(IJRMEET) ISSN: 2320-6586
9 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com
RET Academy for International Journals of Multidisciplinary Research (RAIJMR)
8. Guidelines for Retrofitting of Concrete Structures - Draft published by JSCE, Sept. – 1999.
9. Seismic Retrofitting of Existing Building – The master builder, Vol. 3 Dr. H. S. Rao. Aug.-
Sept. 2001.
10. ISIS Educational Module 4, Feb. - 2004.
11. 13th
World Conference on Earthquake Engineering, AUG.- 2004.
12. STTP on Advancements in Concrete Technology, At – Bhimavaram (A.P.) Dec. – 2004
13. Alpha Sheth – Seismic Retrofitting by Conventional Method, Indian Concrete Journal, Vol.
76.
14. Project report on NDT by MERI, Nashik.
15. Structural Audit of Existing Buildings – I. H. Shah.
16. New and Emerging Technologies for Retrofitting and Repairs – Dr. Gopal Rai.
17. Manual for Retrofitting of Existing Vulnerable Buildings.
18. STTP on Earthquake Resistant Analysis, Design and Retrofitting of Structures, at Badnera
(Maharasthra) June 2008.

More Related Content

What's hot

Comparison of Mesh Type Seismic Retrofitting for Masonry Structures
Comparison of Mesh Type Seismic Retrofitting for Masonry StructuresComparison of Mesh Type Seismic Retrofitting for Masonry Structures
Comparison of Mesh Type Seismic Retrofitting for Masonry Structureschali090
 
Seismic retrofitting of buildings
Seismic retrofitting of buildingsSeismic retrofitting of buildings
Seismic retrofitting of buildingsSukanta Paul
 
C046401422
C046401422C046401422
C046401422IOSR-JEN
 
IRJET- A Review of Behaviour of Building under Earthquake with or without...
IRJET-  	  A Review of Behaviour of Building under Earthquake with or without...IRJET-  	  A Review of Behaviour of Building under Earthquake with or without...
IRJET- A Review of Behaviour of Building under Earthquake with or without...IRJET Journal
 
Seismic Retrofitting of a RC Building by Adding Steel Plate Shear Walls
Seismic Retrofitting of a RC Building by Adding Steel Plate Shear WallsSeismic Retrofitting of a RC Building by Adding Steel Plate Shear Walls
Seismic Retrofitting of a RC Building by Adding Steel Plate Shear WallsIOSR Journals
 
Seismic Retrofitting Techniques
Seismic Retrofitting TechniquesSeismic Retrofitting Techniques
Seismic Retrofitting TechniquesAritra Banerjee
 
Seismic vulnerability and building performance for structures and MEP Equipment
Seismic vulnerability and building performance for structures and MEP EquipmentSeismic vulnerability and building performance for structures and MEP Equipment
Seismic vulnerability and building performance for structures and MEP Equipmentmichaeljmack
 
SEISMIC RETROFITTING OF BUILDINGS
SEISMIC RETROFITTING OF BUILDINGSSEISMIC RETROFITTING OF BUILDINGS
SEISMIC RETROFITTING OF BUILDINGSSukanta Paul
 
IRJET- Seismic Analysis and Retrofitting of Reinforced Concrete Building ...
IRJET-  	  Seismic Analysis and Retrofitting of Reinforced Concrete Building ...IRJET-  	  Seismic Analysis and Retrofitting of Reinforced Concrete Building ...
IRJET- Seismic Analysis and Retrofitting of Reinforced Concrete Building ...IRJET Journal
 
Seismic retrofitting techniques
Seismic retrofitting techniquesSeismic retrofitting techniques
Seismic retrofitting techniquesghildiyal8811
 
Chapter 1 repair stratergies
Chapter 1 repair stratergiesChapter 1 repair stratergies
Chapter 1 repair stratergiesAnkit Patel
 
RETROFITTING OF CONCRETE STRUCTURE
RETROFITTING OFCONCRETE STRUCTURERETROFITTING OFCONCRETE STRUCTURE
RETROFITTING OF CONCRETE STRUCTUREshakti modi
 
IRJET- To Study and Analyze the Various Structures by the Structural Audit
IRJET- To Study and Analyze the Various Structures by the Structural AuditIRJET- To Study and Analyze the Various Structures by the Structural Audit
IRJET- To Study and Analyze the Various Structures by the Structural AuditIRJET Journal
 
Seismic retrofitting raj gajre
Seismic retrofitting raj gajreSeismic retrofitting raj gajre
Seismic retrofitting raj gajreRAJGajre1
 
SEISMIC RETROFITTING
SEISMIC RETROFITTINGSEISMIC RETROFITTING
SEISMIC RETROFITTINGRamesh M
 

What's hot (20)

N012318589
N012318589N012318589
N012318589
 
Comparison of Mesh Type Seismic Retrofitting for Masonry Structures
Comparison of Mesh Type Seismic Retrofitting for Masonry StructuresComparison of Mesh Type Seismic Retrofitting for Masonry Structures
Comparison of Mesh Type Seismic Retrofitting for Masonry Structures
 
Seismic retrofitting of buildings
Seismic retrofitting of buildingsSeismic retrofitting of buildings
Seismic retrofitting of buildings
 
Considerations for Seismic Retrofitting
Considerations for Seismic RetrofittingConsiderations for Seismic Retrofitting
Considerations for Seismic Retrofitting
 
C046401422
C046401422C046401422
C046401422
 
IRJET- A Review of Behaviour of Building under Earthquake with or without...
IRJET-  	  A Review of Behaviour of Building under Earthquake with or without...IRJET-  	  A Review of Behaviour of Building under Earthquake with or without...
IRJET- A Review of Behaviour of Building under Earthquake with or without...
 
Seismic Retrofitting of a RC Building by Adding Steel Plate Shear Walls
Seismic Retrofitting of a RC Building by Adding Steel Plate Shear WallsSeismic Retrofitting of a RC Building by Adding Steel Plate Shear Walls
Seismic Retrofitting of a RC Building by Adding Steel Plate Shear Walls
 
Lecture earthquake-4
Lecture earthquake-4Lecture earthquake-4
Lecture earthquake-4
 
Seismic Retrofitting Techniques
Seismic Retrofitting TechniquesSeismic Retrofitting Techniques
Seismic Retrofitting Techniques
 
Seismic vulnerability and building performance for structures and MEP Equipment
Seismic vulnerability and building performance for structures and MEP EquipmentSeismic vulnerability and building performance for structures and MEP Equipment
Seismic vulnerability and building performance for structures and MEP Equipment
 
SEISMIC RETROFITTING OF BUILDINGS
SEISMIC RETROFITTING OF BUILDINGSSEISMIC RETROFITTING OF BUILDINGS
SEISMIC RETROFITTING OF BUILDINGS
 
RETROFITTING
RETROFITTINGRETROFITTING
RETROFITTING
 
Sap 2000
Sap 2000Sap 2000
Sap 2000
 
IRJET- Seismic Analysis and Retrofitting of Reinforced Concrete Building ...
IRJET-  	  Seismic Analysis and Retrofitting of Reinforced Concrete Building ...IRJET-  	  Seismic Analysis and Retrofitting of Reinforced Concrete Building ...
IRJET- Seismic Analysis and Retrofitting of Reinforced Concrete Building ...
 
Seismic retrofitting techniques
Seismic retrofitting techniquesSeismic retrofitting techniques
Seismic retrofitting techniques
 
Chapter 1 repair stratergies
Chapter 1 repair stratergiesChapter 1 repair stratergies
Chapter 1 repair stratergies
 
RETROFITTING OF CONCRETE STRUCTURE
RETROFITTING OFCONCRETE STRUCTURERETROFITTING OFCONCRETE STRUCTURE
RETROFITTING OF CONCRETE STRUCTURE
 
IRJET- To Study and Analyze the Various Structures by the Structural Audit
IRJET- To Study and Analyze the Various Structures by the Structural AuditIRJET- To Study and Analyze the Various Structures by the Structural Audit
IRJET- To Study and Analyze the Various Structures by the Structural Audit
 
Seismic retrofitting raj gajre
Seismic retrofitting raj gajreSeismic retrofitting raj gajre
Seismic retrofitting raj gajre
 
SEISMIC RETROFITTING
SEISMIC RETROFITTINGSEISMIC RETROFITTING
SEISMIC RETROFITTING
 

Viewers also liked

Annotated lyrics - Mirphy
Annotated lyrics - MirphyAnnotated lyrics - Mirphy
Annotated lyrics - Mirphyrhsmediastudies
 
Les commandements du bon guide touristique
Les commandements du bon guide touristique Les commandements du bon guide touristique
Les commandements du bon guide touristique Marjorie Sanchez
 
My Dubai Experience Certificate
My Dubai Experience CertificateMy Dubai Experience Certificate
My Dubai Experience Certificateparthiban gowtham
 
すべての人に知っておいてほしい VoiceOverの基本原則
すべての人に知っておいてほしい VoiceOverの基本原則すべての人に知っておいてほしい VoiceOverの基本原則
すべての人に知っておいてほしい VoiceOverの基本原則知己 久保
 
Thedreamhome.org
Thedreamhome.orgThedreamhome.org
Thedreamhome.orgsalmansweet
 
Galicia gasta 10 millones más en comida rápida con la crisis - El Correo Gallego
Galicia gasta 10 millones más en comida rápida con la crisis - El Correo GallegoGalicia gasta 10 millones más en comida rápida con la crisis - El Correo Gallego
Galicia gasta 10 millones más en comida rápida con la crisis - El Correo GallegoEAE Business School
 
Plan de acción
Plan de acciónPlan de acción
Plan de acciónFC Porto
 

Viewers also liked (9)

Memorama
MemoramaMemorama
Memorama
 
Annotated lyrics - Mirphy
Annotated lyrics - MirphyAnnotated lyrics - Mirphy
Annotated lyrics - Mirphy
 
Les commandements du bon guide touristique
Les commandements du bon guide touristique Les commandements du bon guide touristique
Les commandements du bon guide touristique
 
My Dubai Experience Certificate
My Dubai Experience CertificateMy Dubai Experience Certificate
My Dubai Experience Certificate
 
すべての人に知っておいてほしい VoiceOverの基本原則
すべての人に知っておいてほしい VoiceOverの基本原則すべての人に知っておいてほしい VoiceOverの基本原則
すべての人に知っておいてほしい VoiceOverの基本原則
 
Thedreamhome.org
Thedreamhome.orgThedreamhome.org
Thedreamhome.org
 
Galicia gasta 10 millones más en comida rápida con la crisis - El Correo Gallego
Galicia gasta 10 millones más en comida rápida con la crisis - El Correo GallegoGalicia gasta 10 millones más en comida rápida con la crisis - El Correo Gallego
Galicia gasta 10 millones más en comida rápida con la crisis - El Correo Gallego
 
Plan de acción
Plan de acciónPlan de acción
Plan de acción
 
8 science
8 science8 science
8 science
 

Similar to 1 1 9-bhavar-dadasaheb-o.-et-al (2)

IRJET- A Review of Seismic Analysis of Shear Wall Optimization for Multi-...
IRJET-  	  A Review of Seismic Analysis of Shear Wall Optimization for Multi-...IRJET-  	  A Review of Seismic Analysis of Shear Wall Optimization for Multi-...
IRJET- A Review of Seismic Analysis of Shear Wall Optimization for Multi-...IRJET Journal
 
Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...
Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...
Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...IJERA Editor
 
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...IRJET Journal
 
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...IRJET Journal
 
Seismic Performance Study on RC Wall Structures
Seismic Performance Study on RC Wall StructuresSeismic Performance Study on RC Wall Structures
Seismic Performance Study on RC Wall StructuresIRJET Journal
 
seismicretrofitting of existing structure
seismicretrofitting of existing structureseismicretrofitting of existing structure
seismicretrofitting of existing structurearunarun505411
 
Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...
Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...
Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...IRJET Journal
 
Analysis And Retrofitting of RCC Building in Seismic Zone III
Analysis And Retrofitting of RCC Building in Seismic Zone IIIAnalysis And Retrofitting of RCC Building in Seismic Zone III
Analysis And Retrofitting of RCC Building in Seismic Zone IIIIRJET Journal
 
Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”ankialok
 
Seismic retrofitting techniques of rcc
Seismic retrofitting techniques of rccSeismic retrofitting techniques of rcc
Seismic retrofitting techniques of rccKorrapati Pratyusha
 
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSISDESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSISIjripublishers Ijri
 
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET Journal
 
Earthquake Resistance Architecture: A Study for the Architectural Design of B...
Earthquake Resistance Architecture: A Study for the Architectural Design of B...Earthquake Resistance Architecture: A Study for the Architectural Design of B...
Earthquake Resistance Architecture: A Study for the Architectural Design of B...ijtsrd
 
EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...
EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...
EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...Ijripublishers Ijri
 
COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...
COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...
COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...IRJET Journal
 
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...IRJET Journal
 

Similar to 1 1 9-bhavar-dadasaheb-o.-et-al (2) (20)

Iw3315041514
Iw3315041514Iw3315041514
Iw3315041514
 
IRJET- A Review of Seismic Analysis of Shear Wall Optimization for Multi-...
IRJET-  	  A Review of Seismic Analysis of Shear Wall Optimization for Multi-...IRJET-  	  A Review of Seismic Analysis of Shear Wall Optimization for Multi-...
IRJET- A Review of Seismic Analysis of Shear Wall Optimization for Multi-...
 
Dg33646652
Dg33646652Dg33646652
Dg33646652
 
Dg33646652
Dg33646652Dg33646652
Dg33646652
 
Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...
Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...
Comparison on Repair and Strengthening Techniques for Unreinforced Masonry St...
 
Indian standards on earthquake engineerin gkk
Indian standards on earthquake engineerin gkkIndian standards on earthquake engineerin gkk
Indian standards on earthquake engineerin gkk
 
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
IRJET- A Review Paper on Seismic Analysis of Old Masonry Buildings using Equi...
 
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
Influence of Openings and Local Soil Conditions on the Seismic Behavior of Tu...
 
Seismic Performance Study on RC Wall Structures
Seismic Performance Study on RC Wall StructuresSeismic Performance Study on RC Wall Structures
Seismic Performance Study on RC Wall Structures
 
seismicretrofitting of existing structure
seismicretrofitting of existing structureseismicretrofitting of existing structure
seismicretrofitting of existing structure
 
Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...
Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...
Condition Assessment and Evaluation of Concrete Structures by Advanced Non-de...
 
Analysis And Retrofitting of RCC Building in Seismic Zone III
Analysis And Retrofitting of RCC Building in Seismic Zone IIIAnalysis And Retrofitting of RCC Building in Seismic Zone III
Analysis And Retrofitting of RCC Building in Seismic Zone III
 
Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”Seismic analysis of multi storey reinforced concrete buildings frame”
Seismic analysis of multi storey reinforced concrete buildings frame”
 
Seismic retrofitting techniques of rcc
Seismic retrofitting techniques of rccSeismic retrofitting techniques of rcc
Seismic retrofitting techniques of rcc
 
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSISDESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
DESIGN AND ANALYSIS OF MULTI STORIED STRUCTURES USING STATIC NON LINEAR ANALYSIS
 
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube StructureIRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
IRJET- Comparative Study of Tube in Tube Structure and Frame Tube Structure
 
Earthquake Resistance Architecture: A Study for the Architectural Design of B...
Earthquake Resistance Architecture: A Study for the Architectural Design of B...Earthquake Resistance Architecture: A Study for the Architectural Design of B...
Earthquake Resistance Architecture: A Study for the Architectural Design of B...
 
EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...
EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...
EFFECT OF SHEAR WALL AREA ON SEISMIC BEHAVIOR OF MULTI STORIED BUILDINGS WITH...
 
COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...
COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...
COMPARATIVE STUDY ON G+10 STOREY RCC BULDING WITH AND WITHOUT SHEAR WALL USIN...
 
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
COMPARATIVE ANALYSIS OF MULTISTORY BUILDING WITH AND WITHOUT SHEAR WALL, X BR...
 

Recently uploaded

Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLDeelipZope
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoão Esperancinha
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerAnamika Sarkar
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZTE
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 

Recently uploaded (20)

Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
Current Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCLCurrent Transformer Drawing and GTP for MSETCL
Current Transformer Drawing and GTP for MSETCL
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube ExchangerStudy on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
Study on Air-Water & Water-Water Heat Exchange in a Finned Tube Exchanger
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
ZXCTN 5804 / ZTE PTN / ZTE POTN / ZTE 5804 PTN / ZTE POTN 5804 ( 100/200 GE Z...
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCRCall Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
Call Us -/9953056974- Call Girls In Vikaspuri-/- Delhi NCR
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 

1 1 9-bhavar-dadasaheb-o.-et-al (2)

  • 1. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 1 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) Retrofitting of Existing RCC Buildings by Method of Jacketing BHAVAR DADASAHEB O. Assistant Professor, Sandip Institute of Engineering & Managemnt, At Post Mahiravani, Trimbak Road, Nashik. Maharashtra (India) DHAKE PRAVINCHANDRA D. Assistant Professor, Dept. of Civil Engineering KKWIEER, Nashik Maharashtra (India) OGALE RAMESH A. Assistant Professor, Dept. of Civil Engineering SSVPS’, BS Deore COE., Dhule Maharashtra (India) Abstract: Many parts of the country have suffered earthquake in last three decades. In costal part of South India faced Tsunami. In first three earthquakes it was found that many of damaged structures were build in non-engineered masonry techniques. Unreinforced masonry structures are the most vulnerable during an earthquake. Normally they are designed for vertical loads and since masonry has adequate compressive strength, the structures behave well as long as the loads are vertical. When such a masonry structure is subjected to lateral inertial loads during an earthquake, the walls develop shear and flexural stresses. The strength of masonry under these conditions often depends on the bond between brick and mortar (or stone and mortar), which is quite poor. This bond is also often very poor when lime mortars or mud mortars are used. A masonry wall can also undergo failure in-plane shear, if the inertial forces are in the plane of the wall. Shear failure in the form of diagonal cracks is observed due to this. However, catastrophic collapses take place when the wall experiences out-of-plane flexure. This can bring down a roof and cause more damage. Masonry buildings with light roofs such as tiled roofs are more vulnerable to out-of-plane vibrations since the top edge can undergo large deformations. It is always useful to investigate the behavior of masonry buildings after an earthquake, so as to identify any inadequacies in earthquake resistant design. Studying types of masonry construction, their performance and failure patterns helps in improving the design and detailing aspects. In previous earthquakes many R.C.C buildings have also collapsed and are found unsafe due to faulty workmanship. Many other causes are responsible for major collapse and damage to the R.C.C structures. The review of the codes shows that there were five zones of earth quakes of Indian subcontinents, But its revision is now shoeing four zones of earth quake. Some part of Gujarat lies in zone V which has largest severity of Earthquake. So as the districts that are located on the boundary of
  • 2. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 2 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) Gujarat – Maharashtra like Nasik, Dhule, Nandoorbar lye in zone III of earthquake zone, zone III is second largest zone of earth quake in India. Therefore it seems to be an compulsion to have an review of the old RCC structures (Likely have completed their service period) in and around Nashik for the structural behaviour to avoid future inconvenience. This project is just a similar attempt. A health building in the heart of Nashik city is being strengthened to overcome the future disorders. From the physical and experimental investigations it was concluded that the building either should be demolished or at least should be retrofitted with suitable technique to increase its service life. It was then decided to implement RCC column jacketing technique due to its feasibility and ease for execution. All the columns on both the floors are now suitably jacketed, the loose pockets of concrete that were investigated during the test are reconcreted, the faulty slabs are completely opened and the rusted reinforcement is replaced with new reinforcement as per the design requirement. And the slabs are recasted with M25 grade of ready mix concrete. Keywords: RC jacketing, Rehabilitation, Retrofitting, Strengthening, Structural repair 1. Introduction 1.1 Seismic Strengthening (retrofitting) Actions taken to upgrade the seismic resistance of an existing building so that it becomes safer under future earthquakes. This can be in the form of providing seismic bands, eliminating sources of weakness or concentrations of large mass and openings in walls, adding shear walls or strong column points in walls, bracing roofs and floors to be able to act as horizontal diaphragms, adequately connecting roofs to walls and columns and also connecting between walls and foundations. 1.2 Concept of Retrofitting Retrofitting is technical interventions in structural system of a building that improve the resistance to earthquake by optimizing the strength, ductility and earthquake loads. Strength of the building is generated from the structural dimensions, materials, shape, and number of structural elements, etc. Ductility of the building is generated from good detailing, materials used, degree of seismic resistant, etc. Earthquake load is generated from the site seismicity, mass of the structures, important of buildings, degree of seismic resistant, etc. Due to the variety of structural condition of building, it is hard to develop typical rules for retrofitting. Each building has different approaches depending on the structural deficiencies. Hence, engineers are needed to prepare and design the retrofitting approaches. In the design of retrofitting approach, the engineer must comply with the building codes. The results generated by the adopted retrofitting techniques must fulfill the minimum requirements on the buildings codes, such as deformation, detailing, strength, etc. 1.3 Causes of failure Damage to buildings were caused by a combination of affects:  Old decaying buildings predating modern construction practices  New Buildings not being designed to Indian earthquake codes
  • 3. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 3 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR)  Lack of knowledge, understanding or training in the use of these codes by local engineers  Unawareness that Gujarat is a highly seismic region  Buildings erected without owners seeking proper engineering advice  Improper detailing of masonry and reinforced structures  Poor materials, construction and workmanship used, particularly in commercial buildings  Alterations and extensions being carried out without proper regard for effects on structure during an earthquake  Buildings having poor quality foundations or foundations built on poor soils  Little or no regularity authority administering or policing the codes Generally, commercial buildings were worst affected by the earthquake because of poor workmanship, use of materials and inadequate attention to detailing. 1.4 Recent Retrofitting Methods There are many relatively new technologies developed for seismic Retrofitting which are based on “Response control”. These techniques includes providing additional damping using dampers (Elasto-plastic dampers, friction dampers, tuned mass and tuned liquid dampers, visco-elastic dampers, lead extrusion dampers etc.) and techniques such as base isolation which are introduced to take care of seismic control. 1.4.1 Methods of Retrofitting Increase the capacity/strength of the system (Seismic Resistance Based Design): (i) Concrete Jacketing. (ii) Steel Jacketing. (iii) FRP Wrapping. 2. Retrofitting of health building at Nasik 2.1 General In order to overcome the future disorders that may have occurred due to unwanted and no predicted disasters it was decided to strengthen the existing Health building located in the central part of Nashik city. This building was proposed in 1984 and accordingly was designed for B + G + 4 storeys. The building during its life span at the end in2008 found completely detoriated and was not capable to sustain further loads. And was predicted that it may fail due to the following reasons. a) Higher ground water table in the locality. b) Faulty workmanship during the stage of execution at initial stage. c) The columns were not centered properly in their position. d) Improper methods of compaction to the concrete. e) Insufficient cover to the steel reinforcement. In addition to this it may also have caused failure due to the non predicted disasters as was caused too many buildings in the past which are listed in the next bit. 2.2 Causes of failure and damages to the building in past few earthquakes Following were the main causes of failure and damages to the buildings in Gujarat & Maharashtra; causes to buildings same in rest part India. Damages to buildings were caused by a combination of affects: 1. Old decaying buildings predating modern construction practices
  • 4. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 4 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) 2. New Buildings not being designed to Indian earthquake codes 3. Lack of knowledge, understanding or training in the use of these codes by local engineers 4. Unawareness that Gujarat and some part of Maharashtra is a highly seismic region 5. Buildings erected without owners seeking proper engineering advice 6. Improper detailing of masonry and reinforced structures 7. Poor materials, construction and workmanship used, particularly in commercial buildings 8. Alterations and extensions being carried out without proper regard for effects on structure during an earthquake. 9. Buildings having poor quality foundations or foundations built on poor soils. 10. Little or no regularity authority administering or policing the codes. It’s necessary to every civil engineer to have knowledge of proper repairs and strengthening of earthquake damaged buildings. Indian standards exist but are not used by local engineers or builders in urban or rural areas, mainly due to lack of knowledge and training. As a result, many of the owner-occupiers have unknowingly been carrying out bad repairs in Gujarat. Many buildings have been severely weakened, and the experts are concerned to that there could be another disaster in waiting from a future earthquake. Good repairs, using well-recognized seismic standards may reduce this vulnerability. This project aims in simple terms to explain to the engineers why earthquakes happen in India, which regions are seismically active, how buildings respond in an earthquake; and how to safely carry out good repair and strengthening techniques to damaged and low strength buildings. Fig.1 Some damages those were occurred after earth quake at Gujarat in non engineered R.C.C building construction The inset shows large deformations were concentrated at column heads, which caused many soft storey failures, as per picture. Buildings if designed with uniform deflections of insert would have survived without collapse.” 2.2.1 Crushing of column head and bases When masonry infill walls were ineffective because of large openings, column heads were subjected to large vertical and lateral seismic forces. The heavy eccentric compressive stresses
  • 5. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 5 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) crushed column heads and large shear deformations caused concrete to spall away from the main bars because of links being too far apart. The extent of damage to the column heads often depended on how well the infill wall panels were bonded to the columns. Some common problems, which resulted in severe damage to the column heads or bases, were from poor detailing as follows: (a) Drain pipes and other services placed inside columns, caused severe weakening of the columns making it less resistant to lateral loading; (b) Shear link spacing was too large (typically 200-300mm), thus not providing adequate confinement to the main bars, causing concrete to fall out; (c) Links were not bent backwards into the columns so they easily separated, again letting concrete out of the main bars; (d) Very small links (6mm diameter) were used; (e) Main bars were not bent back into the floor or ground beams so that reversal of shear loads could not be resisted by the beam and column connections. Many failures occurred at beam/column junctions. 2.2.2 Roof failures & Canopy structures Damage to flat roofs was rare. However, pitched roofs often experienced non-structural damage by tiles falling through open space between the timber battens as no tiles were nailed into the timbers. Many tiles were manufactured with no holes to allow them to be nailed to the roof. Several modern buildings had a single storey canopy with a flat roof supported by columns at one end and beams running into the main structural frame at the other end. These suffered varying degrees of damage depending on how slim the columns were. 2.3 Responsibility of building owners The building owner is responsible for determining the need for the repair and its extent, whether it is practical and safe to carry out the repair and whether it is within his budget. It is advised that the building owner should in all cases seek professional advice from a qualified structural engineer before carrying out any repairs. It is also equally important to retain the services of a qualified builder when carrying out repairs. 2.4 Responsibility consulting engineers Its responsibility of consulting engineers to provide safe structural design that can withstand the earth quake load without any damage to the structures, regular sites visits and technical advice to the site supervisors and workers is very essential to reduce the bad practices that would be produce safe and economical shelters to the society. 2.5 Retrofitting of R.C.C Building by Method of Jacketing As it’s shown in above part of chapter no five, that Nasik and some part of Maharashtra is along the border part of Gujarat, Gujarat has suffered from severe earth quake in last two decades, nobody knows which would be the next time of future earth quake & its intensity. Like Gujarat many constructions in Maharashtra and at Nasik are found as non engineered unsafe & quality compromised constructions, this would be future risk for coming days. So it is necessary to carry
  • 6. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 6 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) out the non destructive tests of all construction in Nasik and rest part of India, to save valuable lives and properties, now a days many advance retrofitting techniques are available in the world, those can be used to repair & strengthen the unsafe and damaged buildings. Here the paper has its focus on a Health building which is under execution (for re modification and strengthening of existing structure). 2.5.1 History of Health Building A group proposed to start a hospital in Nasik in 1984. And as per the decision the detail plan & the structural details for the same were prepared. It was proposed to construct a Basement + G + 4 storey structure and the designs were prepared so. The site for the hospital was near Dwarka circle. Nasik: 11. Though it was planned to construct 6 storey in all, only 2 storey ( i. e. Basement + G) structure was constructed in actual when structural details were for 6 storey. The built up area for basement is 1236 sq.mt. and that of the ground floor is 1178 sq. mt. This group had a smooth functioning upto 2004. Then in 2005 the administration of the hospital was changed. New administrative body utilized the same infrastructure up to 2008. Then in 2009 was decided to extend the building as per the initial plan and structural details. And for the same had the structural audit in that respect. From the audit that all the defects were at the execution stage. The faults that were concluded were as below. a) The high ground water table in the region. b) Eccentricity of all the columns was a serious problem observed. c) Improper techniques that were followed during mixing, placing & compacting the concrete. d) There were many loose pockets found in the concrete. e) Sufficient concrete cover at different stages to the steel reinforcement was not maintained. f) The terrace slabs are provided with unwanted thickness of IPS flooring at the top. From the NDT test results it was suggested that the management should demolish the entire existing structure instead of extending it and go for complete new structure. The management refused to do so and asked to suggest such a measure so that the existing infrastructure at least can withstand and be utilized for 5 – 7 years more. As the final conclusion and the requirement of the management it was decided to go for ‘Retrofitting of the Structure’. 2.5.2 The steps that were suggested and are adopted are as below (A) The entire flooring at the basement to be removed & to be provided again with a raft below it. To overcome the uplift pressure that could be generated due to the higher ground water table it was suggested to provide a raft below the basement floor. (B) All the columns should be jacketed. In the existing structure it was found that the columns were not centered properly in their position, due to which they were subjected to unwanted eccentric loads. Also the concrete in columns, beams, slabs was not compacted properly which created loose pockets & honey combs in the components. Suitable cover for the reinforcement was not maintained.
  • 7. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 7 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) To overcome the above difficulties it was decided to jacket all the columns such that the eccentricity of loading will be reduced, the loose pockets of concrete will be capable to sustain the load to which the column is subjected & all the steel get the required concrete covering. (C) The loose pockets in the concrete in the beams are also removed and recasted in M25 grade. (D) The unwanted heavy loading of water proofing (IPS flooring) damaged the slab to greater extent. Therefore, five slabs are entirely opened, strengthened with additional reinforcement and are casted with 150 mm thick M25 grade concrete layer. The estimated cost of retrofitting the existing structure is 4.5 crore. To meet the further requirement of infrastructure the management now is constructing additional new building with G + 2 storey, instead of razing the existing building. 1 2 3 Fig. 2 Photographs shows the step by step stages of retrofitting work for the considered Health Building at Nashik View 1. “Column jacketing at basement stage” 2. “beam column junction strengthening in basement” 3. “finished Column after jacketing work” Figures shows the work of column jacketing for existing columns for additional strengthening, for its renovation work. These columns give the additional strength for its future use & make the structure safe against seismic forces. 4 5 6 View 4. “Rusting condition of existing slabs reinforcement” 6. “Replaced slab reinforcement for existing rusted steel reinforcement.” 7. “Application of chemical admixtures at the joint of new and old concrete”
  • 8. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 8 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) 7 8 Fig. 3 Photographs shows the step by step stages of retrofitting work for the considered Health Building at Nashik View 7. “compaction of concrete by needle vibrator and placement of cover blocks” 8.“Finished slab - ready to cure” As discussed above all works those were carried out on strengthening of the Health building at Nasik, will definitely increases the strength of existing building, this practice would be necessary for many buildings at Nasik and rest of India, it will save the many lives, when any natural disasters will occur. 3. Conclusion Strengthening of building considered in the report is an attempt to increase the life and to sustain the unwanted disturbances like, earthquakes floods etc. The building though was proposed to have been constructed as six storied building and was designed as per requirements, but was constructed only up to two storey, it should have worked or served for a period mre than the designed life span, which is not so. And recommended the strengthening at early stage due to minor effects of disaster, uplift pressure of ground water table, bad workmanships, hence had to be retrofitted. Timely Repair of the structures can be concluded as, ‘A stitch in time, Saves nine.’ 3.1 Future scope for the work in Nasik area Project work has focused on strengthening the RCC buildings. There is an large scope to create an awareness in the occupants/ residents of the buildings those may have completed the service period and or will probably be completing the service period in short future. All such buildings in and around Nashik and all the metro cities in the state and country cn be retrofitted with suitable technique to save the lives and property. References 1. BS 1881 : Part 202 : 1986 2. Earthquake Engineering 10th World Conference 1992. 3. IS 13311 – 1992 (Part I). 4. IS 13311 - 1992 – 2008 (Part II). 5. IS 13828 - 1993 (Part I). 6. Repair and Rehabilitation – Indian Concrete Journal, Sept. 1992. 7. Repair and Rehabilitation – Indian Concrete Journal, Nov. 1995.
  • 9. Bhavar Dadasaheb O. et al. / International Journal of Research in Modern Engineering and Emerging Technology Vol. 1, Issue: 5, June: 2013 (IJRMEET) ISSN: 2320-6586 9 Online International, Reviewed & Indexed Monthly Journal www.raijmr.com RET Academy for International Journals of Multidisciplinary Research (RAIJMR) 8. Guidelines for Retrofitting of Concrete Structures - Draft published by JSCE, Sept. – 1999. 9. Seismic Retrofitting of Existing Building – The master builder, Vol. 3 Dr. H. S. Rao. Aug.- Sept. 2001. 10. ISIS Educational Module 4, Feb. - 2004. 11. 13th World Conference on Earthquake Engineering, AUG.- 2004. 12. STTP on Advancements in Concrete Technology, At – Bhimavaram (A.P.) Dec. – 2004 13. Alpha Sheth – Seismic Retrofitting by Conventional Method, Indian Concrete Journal, Vol. 76. 14. Project report on NDT by MERI, Nashik. 15. Structural Audit of Existing Buildings – I. H. Shah. 16. New and Emerging Technologies for Retrofitting and Repairs – Dr. Gopal Rai. 17. Manual for Retrofitting of Existing Vulnerable Buildings. 18. STTP on Earthquake Resistant Analysis, Design and Retrofitting of Structures, at Badnera (Maharasthra) June 2008.