Pulverized Coal Fired
Boiler Startup Procedure
By
Ashvani Shukla
C&I
Reliance
Index
• Startup Procedure of Boiler andAuxiliaries
1. Induced Draft Fan
2. Forced Draft Fan
3. PrimaryAir Fan
4. Mills
5. Coal Feeders
6. Air Pre Heaters
7. Burners
ID Fan
• START PERMISSIVES
• ID FAN REGULATING DAMPER MIN POSITION (< 10%)
• ID FAN SCOOP MIN POSITION (< 10%)
• ID FAN OUTLET GATE - FULL CLOSED
• ID FAN INLET GATE - FULL CLOSED
• LUBE OIL PRESSURE ADEQUATE (> 0.8 KG/CM2) [TAG - HNC11CP201]
• ID FAN BEARING TEMP NOT HI (< 850 C)
• MOTOR BEARING TEMP NOT HI (< 950 C)
• MOTOR WINDING TEMP NOT HI (< 1050C, ALL 6)
• ANY FLUE GAS PATH (A OR B) AVAILABLE
• APH - A ELECTRIC OR AIR MOTOR ON
•
•
•
•
•
•
•
•
APH - A FLUE GAS INLET DAMPER & OUT LET GATE OPEN
ESP - A PASS OUT LET GATE OPEN
OR
APH - B ELECTRIC OR AIR MOTOR ON
APH - B FLUE GAS INLET DAMPER & OUT LET GATE OPEN
ESP - B PASS OUT LET GATE OPEN
PATH - A AVAILABLE
PATH - B AVAILABLE
HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS)
15 SEC TIMER SHOULD ELAPSE AFTER THE PREVIOUS START OF ANY HT MOTOR (BFP
, ID,
CWP)
• INTERLOCKS
STAND BY LOP STARTS
• IF FAN IS RUNNING AND LUB OIL HEADER PRESURE < 0.6 KSC (60 SEC
TIME DELAY) OR
• IF FAN IS RUNNING AND RUNNING LOP TRIPS >1 SEC AND OTHER LOP IN
STANDBY
.
ID FAN INLET AND OUTLET GATE WILL OPEN ON AUTO, IF
• ID FAN IS RUNNING (60SEC DELAY) [IF OTHER FAN IS NOT RUNNING GATE
WILL OPEN IMMEDIATELY] OR
• ID FAN A & B ARE NOT RUNNING.
ID FAN INLET /OUTLET GATE CLOSE PERMISSIVE WILL BE AVAILABLE ONLY
WHEN FAN NOT RUNNING.
ID FAN INLET/OUTLET GATE CLOSE ON AUTO IF ID FAN TRIPS AND OTHER ID
FAN IS RUNNING & ONE FD FAN IN SERVICE.
AFTER START COMMAND
• OUTLET & INLET GATE CLOSE, IGV & SCOOP GO FOR MINIMUM FOR
SELECTED FAN
• SELECTED FAN MOTOR STARTS
• OUTLET & INLET GATE CLOSE, IGV & SCOOP GO FOR MINIMUM FOR
STAND BY FAN IF IT IS NOT IN SERVICE
•OUTLET GATE OPENS & THEN INLET GATE OPENS FOR THE STARTED FAN.
RUNBACK ON ONE ID FAN TRIPPING IS 90MW.
PROTECTIONS
S.N. DESCRIPTION VALUES TIMER
(SEC)
ALARM TRIP
1. 1 ID FAN BRG TEMP (DE & NDE) 0C 60 75 85 5
1. 2 ID FAN MOTOR BRG TEMP (DE &
NDE) 0C
60 85 95 5
1. 3 ID FAN BRG VIBRATION
(MM/SEC)
0.5 4.5 - -
1. 4 MOTOR BRG VIBRATION
(MM/SEC)
0.5 4.5 -
1. 4 LUBE OIL PRESSURE (KG/CM2)
[HNC11CP205]
1.0 0.4 0.2 10
1. 6 H/C COOLER OIL I/L TEMP (0C)
[HNC12CT201]
95 100 110 -
1. 7 H/C COOLER OIL O/L TEMP (0C)
[HNC12CT202]
70 80 90 -
1. 8 ID FAN MTR WDG TEMP (0C) [2 /
6]
80 105 120 5
1. 9 H/C LUBE OIL PRESSURE
(KG/CM2)
[HNC22/11CP201-4]
1.0 0.8 0.6 15
DURING
STARTIN
G
1. 10 H/C LUBE OIL FILTER DP
(KG/CM2)
< 0.4 0.65 - HIGH
0.7 - V HIGH
- -
1. 11 POST PURGE FAN TRIP FROM
BMS *
- 10 + 75 -175 /
+150
-
ID Fan
• ID & FD FANS WILLTRIPON POST PURGE IF
FURNACE PRESSURE EXCEEDS > +150 OR < -175
MMWCAFTER PURGE COMPLETEAND BEFORE HFO
TRIPV
ALVE OPENS.
• POST PURGE TRIP:AFTER 5 MINUTES OF PURGING,
BOILERAIR FLOW > 40%,ALLFEEDERS & MILLS
OFF,ALLOILV
ALVES CLOSED, NO FLAME
DETECTED,ALLGAS V
ALVES CLOSED, THEN BOTH
ID FANSAND FD FANS WILLTRIPIF FURNACE
PRESSURE VERYHIGH OR VERYLOW OCCURS
• CONSCUTIVE STARTTIMER WILLRESETTO ZERO
WHENALL6 WINDING TEMPERA
TURE < 500C &
BREAKER STOP> 2 HOURS.
FD FAN
• START PERMISSIVES
• LUB OIL PRESSURE > 0.8 KSC
• CONTROL OIL PRESSURE > 8.0 KSC
• BLADE PITCH AT MINIMUM POSITION (<10%)
• OUT LET DAMPER CLOSED
• FAN BEARING TEMPERATURE NOT HIGH (<850C)
• MOTOR BEARING TEMPERATURE (DE/NDE) NOT HIGH (<850C)
• MOTOR WINDING TEMPERATURE (<1050C)
• ANY ID FAN IS RUNNING & OTHER FD FAN IS OFF
• (SECOND FD FAN WILL START ONLY IF BOTH ID FANS ARE
RUNNING)
• HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS)
PROTECTION
Sr.N. DESCRIPTION VALUE TIMER
(SEC)
ALARM TRIP
1. 1 MOTOR WINDING TEMPERATURE
(0C) [2 / 6]
80 105 120 5
1. 2 FD FAN & MOTOR BRG TEMP (DE
& NDE) 0C
60 85 95 5
1. 3 FAN BRG VIBRATION (MM/SEC) 0.5 4.5 - -
1. 4 MOTOR BRG VIBRATION
(MM/SEC)
0.5 4.5 -
1. 5 POST PURGE FAN TRIP FROM BMS - 10 + 75 -175
/
+150
-
1. 6 BOTH ID FANS OFF / TRIP FROM FSSS
PA FAN
• PERMISSIVE
• PA FAN LUBE OIL PRESSURE ADEQUATE (> 0.8 KSC) [HFE11CP201]
• H/C SCOOP MIN. POSITION (< 5%)
• FAN INLET REGULATING DAMPER MIN. POSITION (< 5%)
• FAN OUTLET DAMPER FULL CLOSE
• MOTOR BEARING TEMP
. (DE & NDE) NOT HIGH (< 85OC)
• FAN BEARING TEMP
. (DE & NDE) NOT HIGH (< 75OC)
• ALL MOTOR WINDING TEMP
. NOT HIGH (< 105OC)
• PURGE COMPLETED
• ANY FD FAN IS RUNNING.
• HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS)
• WINDING TEMP NOT HIGH AND BOTH APH PATH ARE I/S
• APH-A ON
• APH-A PA I/L & O/L DAMPER FULL OPEN AND APH-B ON
• APH-B PA I/L & O/L DAMPER FULL OPEN
OR [ANY APH ON AND OTHER PA FAN NOT I/S]
INTERLOCKS
AFTER GIVING START COMMAND TO PA FAN
• FAN MOTOR STARTS.
• OUT LET DAMPER OF STARTED FAN OPENS AFTER 60 SECONDS (IF
DAMPER IN AUTO)
STAND BY LOP OF PA FAN STARTS
• IF FAN IS RUNNING AND LUB OIL PRESURE < 0.6 KSC (60 SEC TIME DELAY)
OR
• IF FAN IS RUNNING AND RUNNING LOP TRIPS.
SECOND SEAL AIR FAN WILL START AUTOMATICALLY
• IF ANY PA FAN IS RUNNING AND SEAL AIR TO COLD PA DP IS LOW (< 100
MMWC) FOR 10 SEC. AND SEAL AIR FAN NOT RED TAGGED AND OUT OF
SERVICE IS NOT ALARM NOT PERSISTING OR
• FIRST SEAL AIR FAN FAILED TO START AFTER A START COMMAND
SEAL AIR FAN (S) WILL STOP ON ANY OF FOLLOWING CONDITIONS
• BOTH PA FANS NOT RUNNING FOR 15 SEC.
• BOTH SEAL AIR FANS RUNNING AND SEAL AIR TO COLD PA DP NOT LOW
AND COMMAND GIVEN FOR STOPPING.
PROTECTION
Sr.N. DESCRIPTION VALUES TIMER
(SEC)
ALARM TRIP
1. 1 LUB OIL PRESSURE (KSC)
[HFE11CP205]
>1.0 0.4 0.2 2 SEC
1. 2 MOTOR BEARING TEMP. (DE & NDE)
(OC)
50-60 85 95 5
1. 3 FAN BEARING TEMP. (DE & NDE) OC 40-50 65 75 5
1. 4 FAN BEARING VIBRATION (MM/SEC) 1.0 4.5 - -
1. 5 MOTOR BEARING VIBRATION
(MM/SEC)
1.0 4.5 -
1. 6 MOTOR WINDING TEMP (OC) [2 / 6] 80 105 120 5 SEC
1. 7 H/C WORKING OIL COOLER I/L TEMP.
(OC) [HFE12CT201-3]
<95 100 110 2 SEC
1. 8 H/C WORKING OIL COOLER O/L TEMP
(OC) [HFE12CT202-3]
<70 80 90 2 SEC
1. 9 H/C LUB OIL PRESSURE (KSC)
[HFE12CP201-4]
>1.0 <0.8 0.6 15
DURING
STARTI
NG
1. 10 H/C LUBE OIL FILTER DP (KG/CM2) < 0.4 0.4 - HIGH
0.6 - V
HIGH
- -
1. 11 BOILER TRIP FROM FSSS - - TRIP -
BOWL MILL
• PERMISSIVES
BOTH PA FANS RUNNING OR ONE PA FAN RUNNING AND NO MILL IN SERVICE.
IGNITION ENERGY AVAILABLE
• AT LEAST 3 OIL GUNS IN SERVICE AT THE ADJACENT OIL ELEVATION OR
• ADJACENT COAL FEEDER SPEED > 50% & FEEDER RUN FOR 50 SEC AND BOILER LOAD > 30 %
• BOILER LOAD > 30% AND MORE THAN 2 X1 ELEVATION BURNERS IN SERVICE (ONLY FOR
MILL-A)
LUBE OIL OK
• LUBE OIL PRESSURE ADEQUATE (> 2.4 KSC) FOR 5 MIN CONTINUOUSLY
• OIL FILTER CLEAN (DP < 1.0 KSC)
• LUBE OIL LEVEL ADEQUATE
• SUMP OIL TEMPERATURE ADEQUATE (>22 0C)
PULVERIZER OUT LET TEMPERATURE < 940 C WITH GOOD QUALITY SIGNAL
MILL INERTING STEAM VALVE CLOSED AND BREAKER NOT IN TEST.
ALL MILL DISCHARGE VALVE & BURNER MANUAL ISOLATION VALVE OPEN (FORCED)
TRAMP IRON HOPPER VALVE OPEN (FORCED).
PULVERIZER BREAKER & GRAVIMETRIC FEEDER IN REMOTE.
COLD AIR GATE OPEN (FORCED).
FURNACE FIRING PERMISSIVE SATISFIED.
•SCANNER FAN AC OR DC RUNNING
• ALL BURNER TILT AT HORIZONTAL OR ANY OIL ELEVATION IN SERVICE
• PURGE COMPLETE
• BOTH MFT RELAY RESET
• NO FURNACE FIRING INHIBIT SIGNAL
•NO COAL/OIL/GAS/IGNITOR ELEVATION BURNERS TRIPPED PERSISTING.
HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS)
MILL TRIP RESET.
SLAVE QUALITY O.K
ACFS ELEVATION A / B / C NOT SELECTED
ACFS MDV / MMV / PAV / CIV STATUS O.K (FORCED)
PULVERIZER NOT RED TAGGED
SEAL AIR VALVE OPEN
PULVERIZER TO SEAL AIR DP > 200mmwc
MOTOR FEEDER NOT FAULTY
START PULV SEQUENCE COMMAND GIVEN
INTERLOCKS
• IF ANY PA FAN TRIPS TOP ELEVATION MILL WILL TRIP DIRECTLY
• LUB OIL PUMP WILL START ONLY IF SUMP LEVEL IS ADEQUATE &
OIL TEMPERATURE IS >15 0C
• HOT AIR DAMPER WILL OPEN BY 10% ON HOT AIR GATE OPENING.
• WHEN MILL IS STOPPED, COLD AIR DAMPER WILL GO FOR 5%
OUTTRACK OPEN & IF MILL SEAL AIR VALVE IS CLOSED COLD AIR
DAMPER WILL CLOSE COMPLETELY
.
• MILL AIR FLOW DEPENDS ON FEEDER SPEED:
• FOR FEED RATE 0-33% AIR FLOW WILL BE 27.6 TPH & FOR FEED
RATE 33%-100% AIR FLOW WILL BE 27.6TPH TO 36 TPH LINEAR
• IF DUST IS IN SERVICE, 40% OF DUST FEEDRATE WILL BE ADDED
WITH FEEDER FEED RATE AND AIR FLOW WILL BE AS GIVEN ABOVE
SLNO DESCRIPTION
VALUES TIMER
(SEC)
ALARM TRIP
1. 1 LUB OIL PRESSURE LOW > 2.4 1.2 0.75 10
1. 2 LUB OIL FILTER DP HIGH < 0.5 0.6 - 2
1. 3 LUB OIL TEMPERATURE HIGH (0C)
45
65 - 2
1. 4 LUB OIL TEMPERATURE LOW (0C) 20 - 2
1. 5 LUB OIL SUMP TEMPERATURE HIGH (0C) 40 - 52 2
1. 6 LUB OIL SUMP LEVEL LOW - - TRIP 10
1. 7 LUB OIL PUMP NOT RUNNING - - TRIP 2
1. 8 FEEDER I/S AND LOSS OF PA FLOW (T/HR) > 28 - 10 NO TD
1. 9
IGNITION ENERGY NOT AVAILABLE
(REFER INTERLOCK)
- - TRIP 5
1. 10 MFT ACTED - - TRIP -
1. 11 MILL DISCHARGE GATES CLOSE (BYPASSED) - - TRIP 2
1. 12 SEAL AIR TO MILL DP LOW (MMWC) 300 - 125 60
1. 13 LOSS OF PA FAN / PRESSURE TRIP
850 675
BOTH PA FANS STOPPED
AND ANY ONE MILL
RUNNING
500 -
625 5
TRIP -
1. 14
PA HEADER PRESSURE LOW TRIP
(PA HDR PR < 675 mmwc AND ALL MILL I/S)
MILL-C
TRIP
5 SEC
1. 15 BURNER MANUAL ISOLATION VALVE CLOSED (BYPASSED) - - TRIP -
1. 16
FD OR BFP TRIPPING RUNBACK:
ALL MILLS RUNNING AND (ONE FD FAN RUNNING OR
ATLEAST TWO BFP’s NOT RUNNING)
- - MILL-C
1. 17 EMERGENCY PB OPERATED TRIP
1. 18 LOSS OF PA FAN RUNBACK TRIP
IF 3 MILLS I/S
MILL-C -
MILL-B 2 SEC
IF MILLS-AB/AC/BC I/S TOP MILL -
1. 19
LOSS OF PULVERIZER TRIP
(FEEDER RUNNING AND PULV STOPPED/ RUNNING FB LOST)
TRIP 1 SEC
TOP MILL TRIPPING ON GEN BKR OPEN SIGNAL:
TOP MILL WILL TRIP IF (GEN ACTIVE POWER > 3
MW AND GEN BREAKER OPEN (10 SEC PULSE))
AND ANY OF THE FOLLOWING CONDITION EXISTS
• ANY TWO MILLS RUNNING AND 2 ELEVATIONS
IN SERVICE
• 3 MILLS IN SERVICE AND NO COREX IN SERVICE
• 3 MILLS IN SERVICE AND COREX X1 ELEVATION
IN SERVICE
LOS PANEL LOGICS
LUB OIL PUMP WILL START IF ALL THE FOLLOWING CONDITIONS ARE SATISFIED:
• LUB OIL LEVEL ADEQUATE (TD 10SEC)
• SUMP OIL TEMP ADEQUATE 15OC
• LOP START (LOCAL SWITCH OR LOP START PB FROM BMS)-BYPASSED
LUB OIL PUMP WILL STOP IF PULVERISER IS OFF FOR MORE THAN 5 MINUTES AND
NO CONTACT OF CRL34 EXISTS AND ANY OF THE FOLLOWING CONDITIONS ARE
SATISFIED:
• LUB OIL LEVEL VERY LOW (TD 10 SEC)
• SUMP OIL TEMP NOT ADEQUATE
• LOP ON AND LUB OIL PRESSURE VERY LOW (TD 10 SEC)
LUB OIL SYSTEM HEALTHY IF LOP IS ON AND ALL THE FOLLOWING CONDITIONS
EXISTS:
• LUB OIL PRESSURE NOT VERY LOW 1.2 KSC (TD 60 SEC)
• SUMP OIL TEMP ADEQUATE 15OC
• LUB OIL LEVEL ADEQUATE (TD 10 SEC)
• LUB OIL DISCHARGE FILTER CLEAR 0.6 KSC
LUB OIL SYSTEM FAILED IF ANY OF THE FOLLOWING CONDITIONS EXISTS:
• IF PULVERISER IS ON AND
• LOP NOT ON FOR 2 SEC OR SUMP OIL TEMP NOT ADEQUATE (TD 1 HOUR)
• LOSS OF A.C POWER AT PLOS PANEL FOR > 2 SEC
• LUB OIL LEVEL VERY LOW (TD 10 SEC)
• LOP ON AND LUB OIL PRESSURE VERY LOW (TD 10 SEC)
RAW COAL FEEDER
• PERMISSIVES
• MILL RUNNING (30 SEC TIME DELAY)
• FEEDER SPEED DEMAND AT MINIMUM AND FEEDER NOT RT
• FEEDER IN REMOTE
• COAL FIRING PERMISSIVE SATISFIED
• PA FLOW ABOVE MINIMUM >10 T/Hr
• BUNKER OUTLET GATE OPEN
• FEEDER INLET GATE OPEN
• FEEDER TRIP RESET
• MILL MOTOR NOT OVER LOADED
• MILL GROUP READY AND GROUP SEQUENCE STARTED
• IF MILL GROUP SEQUENCE IN AUTO AND FEEDER IN AUTO AND HOT AIR
GATE OPEN
• NO BOILER TRIP
PROTECTION
• LOSS OF COAL ON BELT (TIME DELAY 5 SEC.)
• SHEAR PIN FAIL
• MFT ACTED
• MILL MAIN MOTOR OFF
6.0 - AIR PRE HEATER
PERMISSIVE (ELE / AIR MOTOR)
• APH GUIDE BEARING TEMP NOT HIGH (<700C)
• APH SUPPORT BEARING TEMP NOT HIGH (<700C)
INTERLOCKS
• AIR MOTOR STARTS (SOLENOID VALVE DE-ENERGISES) WHEN ELE.
MOTOR TRIPS.
• AIR MOTOR STOPS (SOLENOID VALVE ENERGISES) WHEN ELECTRICAL
MOTOR STARTS.
• SUPPORT / GUIDE BRG LOP STARTS WHEN APH ELEC MOTOR / AIR MOTOR
ON AND APH GUIDE / SUPPORT BRG TEMP > 400C
• SUPPORT / GUIDE BRG LOP STOPS WHEN APH BRG TEMP < 400C
• STAND BY LOP WILL START WHEN AUTO START COMMAND IS PERSISTING
FOR MAIN LOP FOR 2 SEC. AND THE MAIN LOP IS NOT ON OR IF THE
RUNNING LOP TRIPS
AIR PRE-HEATER DAMPERS
FLUEGAS, SA & PA INLET/OUTLET DAMPER
• AUTO OPEN
• APH ELECTRIC / AIR MOTOR NOT ON AND
OTHER APH ELECTRIC / AIR MOTOR NOT ON
• AUTO CLOSE
• APH ELECTRIC / AIR MOTOR NOT ON AND
OTHER APH ELECTRIC / AIR MOTOR ON
• OPERATION OF INLET & OUTLET DAMPERS OF APH
(FOR AIR & FLUE GAS PATH)
• FAN SIDE DAMPER SHOULD BE OPEN, FOR OPENING
THE BOILER SIDE DAMPER
• BOILER SIDE DAMPER SHOULD BE CLOSED FOR
CLOSING FAN SIDE DAMPER
BURNER MANAGEMENT SYSTEM
PURGE PERMISSIVES
• ALL NOZZLE VALVES, IGNITOR VALVES CLOSED.
• LOTV, HOTV, COREX GAS TV & IGTV CLOSED.
• ALL SCANNER SENSE NO FLAME (ALL ELEVATION ¾ SCANNERS SHOWS NO
FLAME)
• BC 2/4SCANNER FLAME NOT ON
• AB 2/4SCANNER FLAME NOT ON
• AX1 2/4SCANNER FLAME NOT ON
• X1 2/4SCANNER FLAME NOT ON
• X3 2/4SCANNER FLAME NOT ON
• NO IGNITION FROM AX1 AND BC CORNERS
• NO DISCRIMINTING SCANNER FLAME ON
• ALL FEEDERS OFF
• BOTH PA FANS OFF
• MILLS A, B & C HOT AIR GATES CLOSED AND ACFS HOT AIR GATE CLOSED
• IGNITOR GAS & COREX GAS VENT VALVES OPEN
• ALL AUXLIARY DAMPERS MODULATING
• ELEVATION A, B, C AND XX OUT OF FOUR ELEVATION >/=TWO ELEVATIONS
SHOULD BE MODULATING
• CC, BC, AB, AX1, X1, X2, X3 OUT SEVEN ELEVATIONS >/= FIVE ELEVATIONS SHOULD BE
MODULATING
• OR
• ELEVATIONS A, B, C AND XX OUT OF FOUR ELEVATION >/=TWO ELEVATIONS CONTROL STATION
OUT PUT COMMAND SHOULD BE >8%
• CC, BC, AB, AX1, X1, X2, X3 OUT SEVEN ELEVATIONS >/= FIVE ELEVATIONS CONTROL STATION
OUT PUT COMMAND SHOULD BE >8%
UNIT AIR FLOW GREATER THAN 40%(190 TPH)
• NO BOILER TRIP
• DRUM LEVEL VERY LOW FOR MORE THAN 5 SECONDS
• DRUM LEVEL VERY HIGH FOR MORE THAN 10 SECONDS
• FURNACE PRESSURE VERY LOW (2/3 LOGIC)
• FURNACE PRESSURE VERY HIGH (2/3 LOGIC)
• TOTAL AIR FLOW LESS THAN 40%
• BOTH ID FANS OFF
• BOTH FD FANS OFF
• LOSS OF REHEATER PROTECTION
• UNIT FLAME FAILURE TRIP
• LOSS OF ALL FUEL TRIP
• LOSS OF 220V DC MFT POWER, FOR MORE THAN 2 SEC.
• CRITICAL I/O MODULE FAIL
• EMERGENCY TRIP SWITCH ACTIVATED
• SPARE MFT TRIP
• 11.ANY ID FAN AND FD FAN RUNNING
• 12.CRITICAL IN PUT /OUT PUT MODULES FOR OIL GAS AND COAL ARE IN GOOD QUALITY
FUEL OIL VALVES
• PERMISSIVES
• LOTV OPENS ONLY IF ALL THE FOLLOWING CONDITION PERSISTS
• NO MFT ACTIVE
• LFO SUPPLY PRESSURE ADEQUATE (HJF60CP101)>6 Ksc
• ELEVATION AX1 ALL LFO VALVES CLOSED
• LOTV TRIP CONDITIONS DOES NOT EXIST
• LFO TRIP VALVES NOT RED TAGGED
• LFO TRIP VALVE CLOSE FEED BACK EXIST
• LFO BOTH HEADER PT’S NOT IN BADQUALITY
• ATOMIZING AIR PT NOT IN BADQUALITY (HJN10CP101)
• MODULE STATUS OK
• HOTV OPENS ONLY IF ALL THE FOLLOWING CONDITION PERSISTS
• NO MFT ACTIVE
• HOTV CLOSED
• ATOMIZING STEAM HEADER PT NOT BADQULITY
• HFO HEADER PT’S NOT BAD QULITY
• SLAVE MADULE STATUS OK
• HO SUPPLY PRESSURE ADEQUATE >=8 Ksc (HJF40CP102)
• ALL HO NOZZLE VALVES CLOSED
• HO SUPPLY TEMPERATURE ADEQUATE >=100 DEG C (HJF30CT101)
•HO RETURN TRIP VALVE OPEN
• HO TRIP VALVE CLOSE COMMAND NOT EXISTS
• HOTV NOT RED TAGGED
HORV OPENS ONLY IF ALL FOLLOWING CONDITION PERSIST
HO RETURN TRIP VALVE OPEN PUSHBUTTON PRESSED
• ALL HO NOZZLE VALVES CLOSED
IGNITOR TRIP VALVE OPENS ONLY IF THE FALLOWING CONDITIONS PERSISTNO MFT
ACTIVE
• IGTV IN CLOSE CONDTION
• ALL IGNITOR VALVES OF AX1 AND BC CLOSED
• IGNITOR GAS SUPPLY PRESSURE ADEQUATE>=0.75 KSC (SFA20CP101)
• IGNITOR TRIP VALVE TRIP CONDITION NOT EXISTS
• IGTV NOT RED TAGGED AND CLOSED
• BOTH PRESSURE TRANSMITTERS ARE GOOD QUALITY
•SLAVE MODULE GOOD QUALITY
IGNITOR FIRING PERMISSIVE
• AL TRIP CLEAR AND 1 MINUTE TIMED OUT
• MFT RELAY RESET
• IGTV OPEN
• IGNITOR SUPPLY PRESSURE >MIN
• IGNITOR SUPPLY PRESSURE <MAX
• EITHER IGNITOR FAN RUNNING OR IGNITOR TO FURNACE DP NORMAL (>MIN
80MMWC)
• PROTECTIONS
HOTV CLOSES IF ANY OF THE FOLLOWING CONDITION PERSISTS.
• TEMPERATURE OF HFO IS VERY LOW (HJF40CT102)<=90 0C AND ALL HONV’S NOT CLOSED AND HO RTV
NOT OPENED
• PRESSURE OF HFO IS VERY LOW (2.5 KSC)(HJF40CP102/3/4) AND ALL HONV NOT CLOSED INITIAL TIME
DELAY 32 SEC NORMAL TIME DELAY IS 2 SEC
• ANY HONV NOT CLOSED ON NO FLAME DETECTED AFTER IGNITION PROVEN (TIME DELAY IS 20SEC) AND
ANY BURNER VALVE FAIL TO CLOSE
• ATOMISING STEAM PRESSURE VERY LOW (3.0 KSC (HJF60CP101/2/3) & 5 SEC TIME DELAY) AND
ALLHONV NOT CLOSED AND NO HO ELEVATION IN START/STOP>90 SEC AND HORTV NOT OPEN,
• MFT ACTS AND HFO RETURN TRIP VALVE NOT OPEN
• VALVE FAILED TO OPEN WITH IN 10 SEC
• VALVE FAILED TO CLOSE WITH IN 10 SEC
• NO FAULT IN HOTV FACE PLATE
• VALVE LIMIT SWITCH MISS MATCH
• HO PRESSURE BAD QUALITY
• ATOMIZING STEAM PT BAD QUALITY
• LOSS OF UNIT LOGIC POWER SUPPLY
LOTV CLOSES IF ANY OF THE FOLLOWING CONDITION PERSISTS
• LFO HEADER PRESSURE LOW (2.0 KSC) AFTER OPENING OF LOTV 32 SEC TIME DELAY
• ATOMISING AIR PRESSURE VERY LOW TRIP (2.5 KSC & 5 SEC TIME DELAY), PROVIDED ANY OF LONV IS
OPEN AND ATOMIZING AIR PRESSURE LOW AND NO LFO ELEVATION IN START /STOP FOR >70 SEC
• VALVE FAILED TO CLOSE WITH IN 10 SEC AFTER GIVING CLOSE COMMAND (LOTV TRIPPED)
• VALVE FAILED TO OPEN WITH IN 10 SEC AFTER GIVING OPEN COMMAND (LOTV TRIPPED)
• NO FAULT LOTV FACE PLATE
• ANY LONV NOT CLOSED ON NO FLAME DETECTED AFTER IGNITION PROVEN
(TIME DELAY IS 20SEC AND ANY BURNER VALVE FAIL TO CLOSE)
• BOTH LFO HEADER PT’S BADQUALITY
• BOTH ATOMINZING AIR PT BAD QUALITY
• IGNITOR BURNER VALVE FAILED TO CLOSE MORE THAN 20 SEC AFTER FLAME
FAILURE
• LOSS OF UNIT LOGIC POWER SUPPLY
• MFT ACTIVE
IGNITOR TRIP VALVE LOGIC
IGNITOR TRIP VALVE CLOSES IF ANY OF THE FOLLOWING CONDITION EXISTS
• BOILER TRIP (MFT)
• IGNITOR GAS PRESSURE VERY LOW (0.2 KSC)(SFA20CP102) / HIGH (40 KSC)
(SFA20CP101) PROVIDED ANY OF IGNITOR BURNER VALVES NOT CLOSED FOR
MORE THAN 2 SEC.
• IGNITOR BURNER VALVE AX1/BC FAILED TO CLOSE MORE THAN 20 SEC. AFTER
SENSING NO FLAME AND ANY BURNER VALVE FAIL TO CLOSE
• VALVE FAILED TO OPEN WITH IN 10 SEC
• VALVE FAILED TO CLOSE WITH IN 10 SEC
• IGNITOR GAS PRESSURE TRANSMITTER BAD QUALITY
• LOSS OF UNIT LOGIC POWER SUPPLY
NO TIME DELAY IS THERE FOR IGNITOR HEADER VENT VALVE CLOSING AFTER TRIP
VALVE OPENING
FOR ALL OIL BURNERS, WHILE SCAVENGING IGNITOR VALVE OPEN TIME IS 45 SEC
OIL BURNER SEQUENCE.
ON START COMMAND FOR ANY PAIR
• IGNITOR CORNER VALVE OPENS PROVIDED IGNITOR NO FLAME PERSIST AND
IGNITOR FIRING PERMISSIVE SATISFIED AND START COMMAND GIVEN.
• PAIR START WILL INITIATE ELECTRIC SPARK FOR 10 SEC WITH IN 10 SEC IGNITOR
HAS TO BE PROVEN (IONIC FLAME MONITOR DETECTS THE FLAME AND IGNITOR
FLOW IS ADEQUATE)
• IF IGNITOR PROVEN, ATOMISING AIR / STEAM VALVE OPENS (2-3 SEC). THEN OIL
VALVE OPENS (2-3 SEC).
• IF SCANNER SENSES FLAME BEFORE 70 SEC, GUN STABLISES.
• IGNITOR STAYS FOR 70 SEC FROM INSTANT OF START COMMAND.
• IGNITOR CORNER VAVLE STOP/CLOSE WILL BE INITIATED AFTER CORNER OIL
NOZZLE VALVE OPEN (BURNER START TRIAL COMPLETION) WITH 15 SEC TIME
DELAY
• IGNITOR IS ALSO BROUGHT DURING SCAVENGING OR THE ASSOCIATED
ELEVATION BURNERS HAVE PLANNED SHUT DOWN OR STOP COMMAND
ATOMIZING AIR/STEAM VALVE OPEN
• LFO/HFO SELECTED
• ASSOCIATED CORNER IGNITOR TRIAL TIME COMPLETED
• OIL GUN ENGAGE
• SCAVENGING VALVE SHOULD BE CLOSED CONDITION
• START MEMORY PERSISTING
BURNER IN SERVICE WILL COME
• LFO/HFO SELECTED
• OIL START MEMORY
.
• ONCE OIL VALVE FULL OPENS AND 15 SEC ELAPSED AND WITH IN THIS
PERIOD OIL FLAME DETECTED FROM MAIN FLAME SCANNE
UNIT FLAME FAILURE
• THE PROTECTION GETS ARMED WHEN ANY OF THE FOLLOWING
CONDITION PERSISTS FOR > 2 SEC.
• ANY COAL FEEDER PROVEN
• AX1 OR BC OIL ELEVATION ¾ NOZZLE VALVES OPEN WITH HFO & HFO
PRESSURE > 4 KSC
• COREX X1 (2/4) / X2 (3/4) / X3 (3/4) GAS BURNERS IN SERVICE AND
COREX GAS PRESSURE > 30% (100 MMWC)
• WHEN ALL THE ELEVATIONS VOTED TOGETHER FOR NO FLAME FAILURE
TRIP OCCURS
ELEVATION VOTING
• ELEVATION C VOTES WHEN ANY OF THE FOLLOWING CONDITION
PERSISTS
• FEEDER C NOT PROVEN FOR > 2SEC OR SIGNAL BADQUALITY
. AND BC
ELEVATION (3/4 NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR
SIGNAL BADQUALITY
• BC ELEVATION 2/4 SCANNER SHOWS NO FLAME AND BC ELEVATION (3/4
NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQULITY
.
ELEVATION B VOTES WHEN ANY OF THE FOLLOWING CONDITION PERSISTS
• FEEDER B NOT PROVEN FOR > 2 SEC OR SIGNAL BADQULITY
. AND BC ELEVATION
(¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQULITY
• AB ELEVATION 2/4 SCANNER SHOWS NO FLAME AND ELEVATION BC 2/4
SCANNER SHOWS NO FLAME AND BC ELEVATION (¾ NOZZLE VALVE NOT OPEN)
OIL NOT IN SERVICE OR SIGNAL BADQUALITY
ELEVATION A VOTES WHEN ANY OF THE FOLLOWING CONDITION PERSISTS
• FEEDER A NOT PROVEN FOR >2 SEC OR SIGNAL BADQULITY
. AND AX1 ELEVATION
(¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE AND AX1 HFO SELECTED.
• AB ELEVATION 2/4 SCANNER SHOWS NO FLAME AND ELEVATION AX1 2/4
SCANNERS SENSE NO FLAME AND AX1 ELEVATION (¾ NOZZLE VALVE NOT OPEN)
OIL NOT IN SERVICE.
ELEVATION X1 VOTES WHEN ANY OF THE FOLLOWING CONDITION PERSISTS
• ELEVATION X1 NOT IN SERVICE 2/4 AND AX1 ELEVATION (¾ NOZZLE VALVE NOT
OPEN) OIL NOT IN SERVICE OR SIGNAL BADQUALITY
.
• ELEVATION AX1 2/4 SCANNER SHOWS NO FLAME AND AX1 ELEVATION (¾ NOZZLE
VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQUALITY AND X1 2/4
SCANNER SHOWS NO FLAME.
ELEVATION X2 VOTE WHEN ANY OF THE FOLLOWING CONDITION PERSISTS
• X2 ELEVATION NOT IN SERVICE OR X1 ELEVATION 2/4 SCANNER SHOWS NO
FLAME AND ELEVATION X3 2/4 SCANNER SHOWS NO FLAME.
ELEVATION X3 VOTE WHEN ANY OF THE FOLLOWING CONDITION PERSISTS
• WHEN X3 2/4 SCANNER SHOWS NO FLAME OR X3 ELEVATION NOT IN SERVICE.
•
LOSS OF ALL FUEL.
• THE PROTECTION GETS ARMED WHEN ANY IGNITOR AT ANY ELEVATION GETS PROVEN.
• BOILER WILL TRIP ON LOSS OF ALL FUEL WHEN ALL THE FOLLOWING CONDITION PERSISTS
• ALL COREX NOZZELS VALVE CLOSED/TRIPPED
• AX1 AND BC ELEVATION ALL HONV CLOSED/TRIPPED
• ALL FEEDERS OFF/TRIPPED
• AX1 ELEVATION ALL LONV CLOSED/TRIPPED
• ALL IGNITOR VALVE CLOSED/TRIPPED OR IGTV NOT OPEN/TRIPPED
REHEATER PROTECTION
THIS PROTECTION GETS ARMED, WHEN ANY OF THE FOLLOWING CONDITION EXISTS
• ANY FEEDER PROVEN.
• ANY COREX BURNER PROVEN
• AX1>/=3/4 WITH HFO
• AX1 4/4 WITH LFO +BC>/=1/4
• BC >/= 3/4 WITH HFO
• AX1= 2 WITH LFO +BC=/>1
• AX1=/>1 WITH LFO+BC=/>2
• AX1=/>1 WITH HFO+BC=/>2
BOILER WILL TRIP ON THIS PROTECTION WHEN ANY OF THE FOLLOWING CONDITION PERSISTS FOR 10 SEC.
• GCB OPENS AND HPBP CV < 2% OPEN.
• BOTH LPBP CVS < 2% OPEN.
• BOTH LPBP STOP VALVES CLOSED.
• BOTH MAIN STEAM VALVES (BOILER) ARE CLOSED.
LESS THAN FIRE BALL & LOSS OF A.C. (NOT INCLUDED AT PRESENT)
• BOILER WILL TRIP ON THIS PROTECTION WHEN ALL THE FOLLOWING
CONDITION PERSISTS
• ANY ELEVATION (AX1, BC, A, B, C, X1, X2, X3) STARTED & LOSS OF AC
POWER FOR 2 SEC
• ALL FEEDERS OFF
• AX1 OR BC ELEVATION NOT IN SERVICE {ELEVATION IN SERVICE
MEANS ¾ HFO NOZZLE VALVES OPEN AND HFO PRESSURE > 30%}
IGNITOR AIR FAN
• START PERMISSIVE
• FAN NOT OUT OF SERVICE
• FAN NOT RED TAGGED
• IGNITOR TO FURNACE <75 MMWC
• OTHER FAN FAIL TO START
• OTHER FAN FAIL TO STOP
•
•
•
STOP PERMISSIVE
IGNITOR TO FURNACE DP >75 MMWC AND OPERATOR STOP
COMMAND
• EMERGENCY STOP FROM LOCAL
SCANNER AIR FAN
• START PERMISSIVE
• FAN NOT OUT OF SERVICE
• SCANNER TO FURNACE DP<150MMWC
• OTHER FAN FAIL TO START
•
•
•
•
STOP PERMISSIVE
STOP FROM DCS AND F SCANNER TO FURNACE DP>150 MMWC
SCANNER FAN DISCHARGE PR LOW 230MMWC AND SCANNER TO
FURNACE DP LOW 220MMWC
• SCANNER AIR FAN EMERGENCY DAMPER
• OPEN PERMISSIVE
• BOTH FD FANS OFF
• CLOSE PERMISSIVE
• ANY FD FAN RUNNING
•
ADDITIONAL COAL FIRING SYSTEM
(ACFS)
ACFS PAV’S PERMISSIVES.
• ALL MDV’S CLOSED.
• ALL BIV’S OPENED.
• ADJACENT IGNITION ENERGY PROVEN.
• ELEVATION SELECTED FOR ACFS.
• FURNACE FIRING PERMISSIVE SATISFIED.
• FD FAN RELEASE.
• UNSELECTED ELEVATION PAV’S NOT OPEN.
• ACFS COLD AIR GATE OPEN.
ACFS HOT AIR GATE PERMISSIVES:
• ANY ONE-ELEVATION PAV’S FULL OPEN.
• HOT AIR GATE CLOSED.
• HOT AIR GATE NOT RED TAGGED.
ACFS CIV’S PERMISSIVES:
• ALL PAV’S OPENED.
• UNSELECTED ELEVATION CIV’S FULL CLOSED.
• ACFS PA FLOW ADEQUATE.
• ACFS PA HEADER TEMP NOT HIGH.
ACFS COMPRESSOR PERMISSIVES:
•
• DIV-1 OPEN TO GROUP A/C.
• CONVEYING GROUP TRIP RESET.
• COMPRESSOR TROUBLE RESET.
• DIV-A & B OPEN TO SELECTED ELEVATION.
• ALL CIV’S OF SELECTED ELEVATION OPEN.
• ANY ONE ELEVATION SELECTED FOR ACFS.
• MFT RELAYS RESET.
•
ACFS PS PUMP PERMISSIVES:
•
• COMPRESSOR RUNNING.
• COMPRESSOR DISCHARGE PRESSURE ADEQUATE.
• CONVEYING GROUP TRIP RESET.
• PS PUMP DISCHARGE PRESSURE NOT VERY HIGH.
•
ACFS RAL PERMISSIVES:
•
• PS PUMP RUNNING.
• COMPRESSOR DISCHARGE PRESSURE ADEQUATE.
• PS PUMP DISCHARGE PRESSURE NOT VERY HIGH.
• CONVEYING GROUP TRIP RESET.
•
ACFS BAG HOUSE FAN PERMISSIVES:
ON STARTING OF ANY PS PUMP
, BAG HOUSE BLOWER WILL START IN
AUTO AND CORRESPONDING KGV WILL OPEN AFTER 15 SEC OF
BLOWER RUNNING.
BAG HOUSE BLOWER WILL STOP IN AUTO AFTER BOTH RAL STOPPING
AND KGVS WILL CLOSE AFTER BLOWER STOP
.
ACFS CONVEYING GROUP EMERGENCY TRIPS:
• LOSS OF COMPRESSOR TRIP
.
• LOSS OF ACFS PA FLOW TRIP
.
• ACFS SELECTED ELEVATION MDV OPEN TRIP
.
• ACFS SELECTED ELEVATION MMV OPEN TRIP [BYPASSED]
• ACFS LOSS OF IGNITION ENERGY TRIP
.
• ACFS SELECTED ELEVATION DIV CLOSE TRIP
.
• ACFS LOSS OF PA FAN / PRESSURE TRIP
.
• BOILER TRIP – ACFS.
• ACFS SLAVE BAD QUALITY TRIP
.
SECONDARY AIR DAMPER CONTROL
• WIND BOX DP (MMWC) CONTROL SET POINT
WILL BE GENERATED AS PER REQIREMENT
DAMPER OPERATION:
XX ELEVATION:
• MODULATE TO MAITAIN WIND BOX TO
FURNACE DP AS PER ABOVE CURVE (TABLE)
• CLOSE WHEN BOILER LOAD >30%AND X3 NO
BURNERS IN SERVICE
• OPEN FULL WHEN WB TO FURNACE DP GOES
>THAN 240MMWC AND RESET AT 175MMWC
• OPEN FULL ON MFT (BOILER TRIP OR BOTH FD
OFF OR BOTH ID OFF)
AB ELEVATION:
• MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• CLOSE WHEN BOILER LOAD >30%AND MILL-A/ACFS PAV’S NOT OPEN FOR MILL-A AND
MILL-B/ACFS PAV’S NOT OPEN NOT OPEN FOR MILL-B
• OPEN FULL WHEN WB TO FURNACE DP GOES >THAN 175MMWC AND RESET AT
125MMWC
•OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF) CC
ELEVATION:
• MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• CLOSE WHEN BOILER LOAD >30%AND MILL- C NOT IN SERVICE /ACFS PAV’S NOT OPEN
FOR MILL-C
• OPEN FULL WHEN WB TO FURNACE DP GOES >THAN 175MMWC AND RESET AT
125MMWC
• OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF)
X1 ELEVATION:
• MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• CLOSE WHEN BOILER LOAD >30% AND AX1, X1 AND X2 NO BURNERS IN SERVICE
• OPENING PROPORTINAL TO COREX C-HEADER PRESSURE (180MMWC TO 600MMWC
SADC WILL OPERATE 30% TO 100%)WHEN X1 IN SERVICE
•OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF) X2
ELEVATION:
• MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• CLOSE WHEN BOILER LOAD >30% AND AX1, X1AND X3 NO BURNERS IN SERVICE
• OPENING PROPORTINAL TO COREX C-HEADER PRESSURE (180MMWC TO 600MMWC
SADC WILL OPERATE 30% TO 100%)WHEN X2 IN SERVICE
• OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF)
X3 ELEVATION:
• MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• CLOSE WHEN BOILER LOAD >30% AND X2 AND X3 NO BURNERS IN SERVICE
• OPENING PROPORTINAL TO COREX C-HEADER PRESSURE (180MMWC TO 600MMWC SADC WILL
OPERATE 30% TO 100%)WHEN X3 IN SERVICE
• OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF)
•
A ELEVATION:
• MODULATE TO MAINTAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• OPENING PRAPORTIONAL TO ELEVATION FEED RATE FROM 20 TO 70%
• CLOSE WHEN THE BOILER LOAD >30% AND AX1 AND A NOT IN SERVICE
• OPENS FULL ON MFT
•
B ELEVATION:
• MODULATE TO MAINTAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• OPENING PRAPORTIONAL TO ELEVATION FEED RATE FROM 20 TO 70%
• CLOSE WHEN THE BOILER LOAD >30% AND BC OR B NOT IN SERVICE
• OPENS FULL ON MFT
•
C ELEVATION:
• MODULATE TO MAINTAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE)
• OPENING PRAPORTIONAL TO ELEVATION FEED RATE FROM 20 TO 70%
• CLOSE WHEN THE BOILER LOAD >30% AND BC OR C NOT IN SERVICE
• OPENS FULL ON MFT
•
• AFTER 40 SEC OF MFT ALL THE DAMPERS TO AUTOMATICALLY MODULATE TO MAINTAIN 40
MMWC WIND BOX PRESSURE
Thank you

More Related Content

Similar to Pulverized Coal Fired Boiler Startup Procedure

Regulator-and-Control-Valve-Sizing (2).pdf
Regulator-and-Control-Valve-Sizing (2).pdfRegulator-and-Control-Valve-Sizing (2).pdf
Regulator-and-Control-Valve-Sizing (2).pdfscehmha83
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)Billa ParameswaraRao
 
Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownNitin Mahalle
 
Pre commissioning steam turbines load trial
Pre commissioning steam turbines load trialPre commissioning steam turbines load trial
Pre commissioning steam turbines load trialNagesh H
 
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfKomatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfpaidongzhong6790
 
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfKomatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdffragmentkqdpry
 
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfKomatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfjiangshou26
 
INTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGINTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGSURAJ KUMAR
 
Reciprocating Compressors.pdf
Reciprocating Compressors.pdfReciprocating Compressors.pdf
Reciprocating Compressors.pdfDWNLDUSRML
 
Electrical_Submersible_Pump (final).ppt
Electrical_Submersible_Pump (final).pptElectrical_Submersible_Pump (final).ppt
Electrical_Submersible_Pump (final).pptAnkit732751
 
Summer Internship final reports
Summer Internship final reportsSummer Internship final reports
Summer Internship final reportsvivek srivastava
 
Power Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the TurbogeneratorPower Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the TurbogeneratorManohar Tatwawadi
 
Fc744 Fuel
Fc744 FuelFc744 Fuel
Fc744 Fueltheoryce
 
Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)
Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)
Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)fjjkekfksemmm
 
432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdf
432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdf432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdf
432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdfJeferson872537
 

Similar to Pulverized Coal Fired Boiler Startup Procedure (20)

Regulator-and-Control-Valve-Sizing (2).pdf
Regulator-and-Control-Valve-Sizing (2).pdfRegulator-and-Control-Valve-Sizing (2).pdf
Regulator-and-Control-Valve-Sizing (2).pdf
 
steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)steam turbine turbine interlocks for (KWU turbine)
steam turbine turbine interlocks for (KWU turbine)
 
PUMPS.ppt
PUMPS.pptPUMPS.ppt
PUMPS.ppt
 
Unit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdownUnit lightup synchronisation & shutdown
Unit lightup synchronisation & shutdown
 
Pre commissioning steam turbines load trial
Pre commissioning steam turbines load trialPre commissioning steam turbines load trial
Pre commissioning steam turbines load trial
 
CARGO OIL PUMPING SYSTEM.pdf
CARGO OIL PUMPING SYSTEM.pdfCARGO OIL PUMPING SYSTEM.pdf
CARGO OIL PUMPING SYSTEM.pdf
 
CARGO OIL PUMPING SYSTEM.pdf
CARGO OIL PUMPING SYSTEM.pdfCARGO OIL PUMPING SYSTEM.pdf
CARGO OIL PUMPING SYSTEM.pdf
 
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfKomatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
 
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfKomatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
 
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdfKomatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
Komatsu WA150PZ-5 Wheel Loader Service Repair Manual (SN H50051 and up).pdf
 
INTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNINGINTRODUCTION TO GOVERNING
INTRODUCTION TO GOVERNING
 
Reciprocating Compressors.pdf
Reciprocating Compressors.pdfReciprocating Compressors.pdf
Reciprocating Compressors.pdf
 
Electrical_Submersible_Pump (final).ppt
Electrical_Submersible_Pump (final).pptElectrical_Submersible_Pump (final).ppt
Electrical_Submersible_Pump (final).ppt
 
Summer Internship final reports
Summer Internship final reportsSummer Internship final reports
Summer Internship final reports
 
Power Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the TurbogeneratorPower Plant Simulator, Unloading and shutting the Turbogenerator
Power Plant Simulator, Unloading and shutting the Turbogenerator
 
Fc744 Fuel
Fc744 FuelFc744 Fuel
Fc744 Fuel
 
Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)
Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)
Komatsu wa150 pz 5 wheel loader service repair manual (sn h50051 and up)
 
960649.pdf
960649.pdf960649.pdf
960649.pdf
 
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
FURNACE SAFEGUARD SUPERVISORY SYSTEM (FSSS)
 
432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdf
432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdf432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdf
432112393-Manual-Injecao-Mercedes-Bens-Detroit.pdf
 

Recently uploaded

the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxhumanexperienceaaa
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...Call Girls in Nagpur High Profile
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingrakeshbaidya232001
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...ranjana rawat
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSRajkumarAkumalla
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxpranjaldaimarysona
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130Suhani Kapoor
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxupamatechverse
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...RajaP95
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingrknatarajan
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Call Girls in Nagpur High Profile
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Dr.Costas Sachpazis
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...ranjana rawat
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSISrknatarajan
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escortsranjana rawat
 

Recently uploaded (20)

the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptxthe ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
the ladakh protest in leh ladakh 2024 sonam wangchuk.pptx
 
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...Booking open Available Pune Call Girls Koregaon Park  6297143586 Call Hot Ind...
Booking open Available Pune Call Girls Koregaon Park 6297143586 Call Hot Ind...
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
Porous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writingPorous Ceramics seminar and technical writing
Porous Ceramics seminar and technical writing
 
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
(ANVI) Koregaon Park Call Girls Just Call 7001035870 [ Cash on Delivery ] Pun...
 
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICSHARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
HARDNESS, FRACTURE TOUGHNESS AND STRENGTH OF CERAMICS
 
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINEDJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
DJARUM4D - SLOT GACOR ONLINE | SLOT DEMO ONLINE
 
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur EscortsCall Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
Call Girls Service Nagpur Tanvi Call 7001035870 Meet With Nagpur Escorts
 
Processing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptxProcessing & Properties of Floor and Wall Tiles.pptx
Processing & Properties of Floor and Wall Tiles.pptx
 
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
VIP Call Girls Service Kondapur Hyderabad Call +91-8250192130
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Introduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptxIntroduction to IEEE STANDARDS and its different types.pptx
Introduction to IEEE STANDARDS and its different types.pptx
 
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
IMPLICATIONS OF THE ABOVE HOLISTIC UNDERSTANDING OF HARMONY ON PROFESSIONAL E...
 
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and workingUNIT-V FMM.HYDRAULIC TURBINE - Construction and working
UNIT-V FMM.HYDRAULIC TURBINE - Construction and working
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
Structural Analysis and Design of Foundations: A Comprehensive Handbook for S...
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
(SHREYA) Chakan Call Girls Just Call 7001035870 [ Cash on Delivery ] Pune Esc...
 
UNIT-III FMM. DIMENSIONAL ANALYSIS
UNIT-III FMM.        DIMENSIONAL ANALYSISUNIT-III FMM.        DIMENSIONAL ANALYSIS
UNIT-III FMM. DIMENSIONAL ANALYSIS
 
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Isha Call 7001035870 Meet With Nagpur Escorts
 

Pulverized Coal Fired Boiler Startup Procedure

  • 1. Pulverized Coal Fired Boiler Startup Procedure By Ashvani Shukla C&I Reliance
  • 2. Index • Startup Procedure of Boiler andAuxiliaries 1. Induced Draft Fan 2. Forced Draft Fan 3. PrimaryAir Fan 4. Mills 5. Coal Feeders 6. Air Pre Heaters 7. Burners
  • 3. ID Fan • START PERMISSIVES • ID FAN REGULATING DAMPER MIN POSITION (< 10%) • ID FAN SCOOP MIN POSITION (< 10%) • ID FAN OUTLET GATE - FULL CLOSED • ID FAN INLET GATE - FULL CLOSED • LUBE OIL PRESSURE ADEQUATE (> 0.8 KG/CM2) [TAG - HNC11CP201] • ID FAN BEARING TEMP NOT HI (< 850 C) • MOTOR BEARING TEMP NOT HI (< 950 C) • MOTOR WINDING TEMP NOT HI (< 1050C, ALL 6) • ANY FLUE GAS PATH (A OR B) AVAILABLE • APH - A ELECTRIC OR AIR MOTOR ON • • • • • • • • APH - A FLUE GAS INLET DAMPER & OUT LET GATE OPEN ESP - A PASS OUT LET GATE OPEN OR APH - B ELECTRIC OR AIR MOTOR ON APH - B FLUE GAS INLET DAMPER & OUT LET GATE OPEN ESP - B PASS OUT LET GATE OPEN PATH - A AVAILABLE PATH - B AVAILABLE HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS) 15 SEC TIMER SHOULD ELAPSE AFTER THE PREVIOUS START OF ANY HT MOTOR (BFP , ID, CWP)
  • 4. • INTERLOCKS STAND BY LOP STARTS • IF FAN IS RUNNING AND LUB OIL HEADER PRESURE < 0.6 KSC (60 SEC TIME DELAY) OR • IF FAN IS RUNNING AND RUNNING LOP TRIPS >1 SEC AND OTHER LOP IN STANDBY . ID FAN INLET AND OUTLET GATE WILL OPEN ON AUTO, IF • ID FAN IS RUNNING (60SEC DELAY) [IF OTHER FAN IS NOT RUNNING GATE WILL OPEN IMMEDIATELY] OR • ID FAN A & B ARE NOT RUNNING. ID FAN INLET /OUTLET GATE CLOSE PERMISSIVE WILL BE AVAILABLE ONLY WHEN FAN NOT RUNNING. ID FAN INLET/OUTLET GATE CLOSE ON AUTO IF ID FAN TRIPS AND OTHER ID FAN IS RUNNING & ONE FD FAN IN SERVICE. AFTER START COMMAND • OUTLET & INLET GATE CLOSE, IGV & SCOOP GO FOR MINIMUM FOR SELECTED FAN • SELECTED FAN MOTOR STARTS • OUTLET & INLET GATE CLOSE, IGV & SCOOP GO FOR MINIMUM FOR STAND BY FAN IF IT IS NOT IN SERVICE •OUTLET GATE OPENS & THEN INLET GATE OPENS FOR THE STARTED FAN. RUNBACK ON ONE ID FAN TRIPPING IS 90MW.
  • 5. PROTECTIONS S.N. DESCRIPTION VALUES TIMER (SEC) ALARM TRIP 1. 1 ID FAN BRG TEMP (DE & NDE) 0C 60 75 85 5 1. 2 ID FAN MOTOR BRG TEMP (DE & NDE) 0C 60 85 95 5 1. 3 ID FAN BRG VIBRATION (MM/SEC) 0.5 4.5 - - 1. 4 MOTOR BRG VIBRATION (MM/SEC) 0.5 4.5 - 1. 4 LUBE OIL PRESSURE (KG/CM2) [HNC11CP205] 1.0 0.4 0.2 10 1. 6 H/C COOLER OIL I/L TEMP (0C) [HNC12CT201] 95 100 110 - 1. 7 H/C COOLER OIL O/L TEMP (0C) [HNC12CT202] 70 80 90 - 1. 8 ID FAN MTR WDG TEMP (0C) [2 / 6] 80 105 120 5 1. 9 H/C LUBE OIL PRESSURE (KG/CM2) [HNC22/11CP201-4] 1.0 0.8 0.6 15 DURING STARTIN G 1. 10 H/C LUBE OIL FILTER DP (KG/CM2) < 0.4 0.65 - HIGH 0.7 - V HIGH - - 1. 11 POST PURGE FAN TRIP FROM BMS * - 10 + 75 -175 / +150 -
  • 6. ID Fan • ID & FD FANS WILLTRIPON POST PURGE IF FURNACE PRESSURE EXCEEDS > +150 OR < -175 MMWCAFTER PURGE COMPLETEAND BEFORE HFO TRIPV ALVE OPENS. • POST PURGE TRIP:AFTER 5 MINUTES OF PURGING, BOILERAIR FLOW > 40%,ALLFEEDERS & MILLS OFF,ALLOILV ALVES CLOSED, NO FLAME DETECTED,ALLGAS V ALVES CLOSED, THEN BOTH ID FANSAND FD FANS WILLTRIPIF FURNACE PRESSURE VERYHIGH OR VERYLOW OCCURS • CONSCUTIVE STARTTIMER WILLRESETTO ZERO WHENALL6 WINDING TEMPERA TURE < 500C & BREAKER STOP> 2 HOURS.
  • 7. FD FAN • START PERMISSIVES • LUB OIL PRESSURE > 0.8 KSC • CONTROL OIL PRESSURE > 8.0 KSC • BLADE PITCH AT MINIMUM POSITION (<10%) • OUT LET DAMPER CLOSED • FAN BEARING TEMPERATURE NOT HIGH (<850C) • MOTOR BEARING TEMPERATURE (DE/NDE) NOT HIGH (<850C) • MOTOR WINDING TEMPERATURE (<1050C) • ANY ID FAN IS RUNNING & OTHER FD FAN IS OFF • (SECOND FD FAN WILL START ONLY IF BOTH ID FANS ARE RUNNING) • HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS)
  • 8. PROTECTION Sr.N. DESCRIPTION VALUE TIMER (SEC) ALARM TRIP 1. 1 MOTOR WINDING TEMPERATURE (0C) [2 / 6] 80 105 120 5 1. 2 FD FAN & MOTOR BRG TEMP (DE & NDE) 0C 60 85 95 5 1. 3 FAN BRG VIBRATION (MM/SEC) 0.5 4.5 - - 1. 4 MOTOR BRG VIBRATION (MM/SEC) 0.5 4.5 - 1. 5 POST PURGE FAN TRIP FROM BMS - 10 + 75 -175 / +150 - 1. 6 BOTH ID FANS OFF / TRIP FROM FSSS
  • 9. PA FAN • PERMISSIVE • PA FAN LUBE OIL PRESSURE ADEQUATE (> 0.8 KSC) [HFE11CP201] • H/C SCOOP MIN. POSITION (< 5%) • FAN INLET REGULATING DAMPER MIN. POSITION (< 5%) • FAN OUTLET DAMPER FULL CLOSE • MOTOR BEARING TEMP . (DE & NDE) NOT HIGH (< 85OC) • FAN BEARING TEMP . (DE & NDE) NOT HIGH (< 75OC) • ALL MOTOR WINDING TEMP . NOT HIGH (< 105OC) • PURGE COMPLETED • ANY FD FAN IS RUNNING. • HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS) • WINDING TEMP NOT HIGH AND BOTH APH PATH ARE I/S • APH-A ON • APH-A PA I/L & O/L DAMPER FULL OPEN AND APH-B ON • APH-B PA I/L & O/L DAMPER FULL OPEN OR [ANY APH ON AND OTHER PA FAN NOT I/S]
  • 10. INTERLOCKS AFTER GIVING START COMMAND TO PA FAN • FAN MOTOR STARTS. • OUT LET DAMPER OF STARTED FAN OPENS AFTER 60 SECONDS (IF DAMPER IN AUTO) STAND BY LOP OF PA FAN STARTS • IF FAN IS RUNNING AND LUB OIL PRESURE < 0.6 KSC (60 SEC TIME DELAY) OR • IF FAN IS RUNNING AND RUNNING LOP TRIPS. SECOND SEAL AIR FAN WILL START AUTOMATICALLY • IF ANY PA FAN IS RUNNING AND SEAL AIR TO COLD PA DP IS LOW (< 100 MMWC) FOR 10 SEC. AND SEAL AIR FAN NOT RED TAGGED AND OUT OF SERVICE IS NOT ALARM NOT PERSISTING OR • FIRST SEAL AIR FAN FAILED TO START AFTER A START COMMAND SEAL AIR FAN (S) WILL STOP ON ANY OF FOLLOWING CONDITIONS • BOTH PA FANS NOT RUNNING FOR 15 SEC. • BOTH SEAL AIR FANS RUNNING AND SEAL AIR TO COLD PA DP NOT LOW AND COMMAND GIVEN FOR STOPPING.
  • 11. PROTECTION Sr.N. DESCRIPTION VALUES TIMER (SEC) ALARM TRIP 1. 1 LUB OIL PRESSURE (KSC) [HFE11CP205] >1.0 0.4 0.2 2 SEC 1. 2 MOTOR BEARING TEMP. (DE & NDE) (OC) 50-60 85 95 5 1. 3 FAN BEARING TEMP. (DE & NDE) OC 40-50 65 75 5 1. 4 FAN BEARING VIBRATION (MM/SEC) 1.0 4.5 - - 1. 5 MOTOR BEARING VIBRATION (MM/SEC) 1.0 4.5 - 1. 6 MOTOR WINDING TEMP (OC) [2 / 6] 80 105 120 5 SEC 1. 7 H/C WORKING OIL COOLER I/L TEMP. (OC) [HFE12CT201-3] <95 100 110 2 SEC 1. 8 H/C WORKING OIL COOLER O/L TEMP (OC) [HFE12CT202-3] <70 80 90 2 SEC 1. 9 H/C LUB OIL PRESSURE (KSC) [HFE12CP201-4] >1.0 <0.8 0.6 15 DURING STARTI NG 1. 10 H/C LUBE OIL FILTER DP (KG/CM2) < 0.4 0.4 - HIGH 0.6 - V HIGH - - 1. 11 BOILER TRIP FROM FSSS - - TRIP -
  • 12. BOWL MILL • PERMISSIVES BOTH PA FANS RUNNING OR ONE PA FAN RUNNING AND NO MILL IN SERVICE. IGNITION ENERGY AVAILABLE • AT LEAST 3 OIL GUNS IN SERVICE AT THE ADJACENT OIL ELEVATION OR • ADJACENT COAL FEEDER SPEED > 50% & FEEDER RUN FOR 50 SEC AND BOILER LOAD > 30 % • BOILER LOAD > 30% AND MORE THAN 2 X1 ELEVATION BURNERS IN SERVICE (ONLY FOR MILL-A) LUBE OIL OK • LUBE OIL PRESSURE ADEQUATE (> 2.4 KSC) FOR 5 MIN CONTINUOUSLY • OIL FILTER CLEAN (DP < 1.0 KSC) • LUBE OIL LEVEL ADEQUATE • SUMP OIL TEMPERATURE ADEQUATE (>22 0C) PULVERIZER OUT LET TEMPERATURE < 940 C WITH GOOD QUALITY SIGNAL MILL INERTING STEAM VALVE CLOSED AND BREAKER NOT IN TEST. ALL MILL DISCHARGE VALVE & BURNER MANUAL ISOLATION VALVE OPEN (FORCED) TRAMP IRON HOPPER VALVE OPEN (FORCED). PULVERIZER BREAKER & GRAVIMETRIC FEEDER IN REMOTE. COLD AIR GATE OPEN (FORCED).
  • 13. FURNACE FIRING PERMISSIVE SATISFIED. •SCANNER FAN AC OR DC RUNNING • ALL BURNER TILT AT HORIZONTAL OR ANY OIL ELEVATION IN SERVICE • PURGE COMPLETE • BOTH MFT RELAY RESET • NO FURNACE FIRING INHIBIT SIGNAL •NO COAL/OIL/GAS/IGNITOR ELEVATION BURNERS TRIPPED PERSISTING. HT MOTOR START PERMISSIVES SATISFIED (REFER HT MOTORS) MILL TRIP RESET. SLAVE QUALITY O.K ACFS ELEVATION A / B / C NOT SELECTED ACFS MDV / MMV / PAV / CIV STATUS O.K (FORCED) PULVERIZER NOT RED TAGGED SEAL AIR VALVE OPEN PULVERIZER TO SEAL AIR DP > 200mmwc MOTOR FEEDER NOT FAULTY START PULV SEQUENCE COMMAND GIVEN
  • 14. INTERLOCKS • IF ANY PA FAN TRIPS TOP ELEVATION MILL WILL TRIP DIRECTLY • LUB OIL PUMP WILL START ONLY IF SUMP LEVEL IS ADEQUATE & OIL TEMPERATURE IS >15 0C • HOT AIR DAMPER WILL OPEN BY 10% ON HOT AIR GATE OPENING. • WHEN MILL IS STOPPED, COLD AIR DAMPER WILL GO FOR 5% OUTTRACK OPEN & IF MILL SEAL AIR VALVE IS CLOSED COLD AIR DAMPER WILL CLOSE COMPLETELY . • MILL AIR FLOW DEPENDS ON FEEDER SPEED: • FOR FEED RATE 0-33% AIR FLOW WILL BE 27.6 TPH & FOR FEED RATE 33%-100% AIR FLOW WILL BE 27.6TPH TO 36 TPH LINEAR • IF DUST IS IN SERVICE, 40% OF DUST FEEDRATE WILL BE ADDED WITH FEEDER FEED RATE AND AIR FLOW WILL BE AS GIVEN ABOVE
  • 15. SLNO DESCRIPTION VALUES TIMER (SEC) ALARM TRIP 1. 1 LUB OIL PRESSURE LOW > 2.4 1.2 0.75 10 1. 2 LUB OIL FILTER DP HIGH < 0.5 0.6 - 2 1. 3 LUB OIL TEMPERATURE HIGH (0C) 45 65 - 2 1. 4 LUB OIL TEMPERATURE LOW (0C) 20 - 2 1. 5 LUB OIL SUMP TEMPERATURE HIGH (0C) 40 - 52 2 1. 6 LUB OIL SUMP LEVEL LOW - - TRIP 10 1. 7 LUB OIL PUMP NOT RUNNING - - TRIP 2 1. 8 FEEDER I/S AND LOSS OF PA FLOW (T/HR) > 28 - 10 NO TD 1. 9 IGNITION ENERGY NOT AVAILABLE (REFER INTERLOCK) - - TRIP 5 1. 10 MFT ACTED - - TRIP - 1. 11 MILL DISCHARGE GATES CLOSE (BYPASSED) - - TRIP 2 1. 12 SEAL AIR TO MILL DP LOW (MMWC) 300 - 125 60 1. 13 LOSS OF PA FAN / PRESSURE TRIP 850 675 BOTH PA FANS STOPPED AND ANY ONE MILL RUNNING 500 - 625 5 TRIP - 1. 14 PA HEADER PRESSURE LOW TRIP (PA HDR PR < 675 mmwc AND ALL MILL I/S) MILL-C TRIP 5 SEC 1. 15 BURNER MANUAL ISOLATION VALVE CLOSED (BYPASSED) - - TRIP - 1. 16 FD OR BFP TRIPPING RUNBACK: ALL MILLS RUNNING AND (ONE FD FAN RUNNING OR ATLEAST TWO BFP’s NOT RUNNING) - - MILL-C 1. 17 EMERGENCY PB OPERATED TRIP 1. 18 LOSS OF PA FAN RUNBACK TRIP IF 3 MILLS I/S MILL-C - MILL-B 2 SEC IF MILLS-AB/AC/BC I/S TOP MILL - 1. 19 LOSS OF PULVERIZER TRIP (FEEDER RUNNING AND PULV STOPPED/ RUNNING FB LOST) TRIP 1 SEC
  • 16. TOP MILL TRIPPING ON GEN BKR OPEN SIGNAL: TOP MILL WILL TRIP IF (GEN ACTIVE POWER > 3 MW AND GEN BREAKER OPEN (10 SEC PULSE)) AND ANY OF THE FOLLOWING CONDITION EXISTS • ANY TWO MILLS RUNNING AND 2 ELEVATIONS IN SERVICE • 3 MILLS IN SERVICE AND NO COREX IN SERVICE • 3 MILLS IN SERVICE AND COREX X1 ELEVATION IN SERVICE
  • 17. LOS PANEL LOGICS LUB OIL PUMP WILL START IF ALL THE FOLLOWING CONDITIONS ARE SATISFIED: • LUB OIL LEVEL ADEQUATE (TD 10SEC) • SUMP OIL TEMP ADEQUATE 15OC • LOP START (LOCAL SWITCH OR LOP START PB FROM BMS)-BYPASSED LUB OIL PUMP WILL STOP IF PULVERISER IS OFF FOR MORE THAN 5 MINUTES AND NO CONTACT OF CRL34 EXISTS AND ANY OF THE FOLLOWING CONDITIONS ARE SATISFIED: • LUB OIL LEVEL VERY LOW (TD 10 SEC) • SUMP OIL TEMP NOT ADEQUATE • LOP ON AND LUB OIL PRESSURE VERY LOW (TD 10 SEC) LUB OIL SYSTEM HEALTHY IF LOP IS ON AND ALL THE FOLLOWING CONDITIONS EXISTS: • LUB OIL PRESSURE NOT VERY LOW 1.2 KSC (TD 60 SEC) • SUMP OIL TEMP ADEQUATE 15OC • LUB OIL LEVEL ADEQUATE (TD 10 SEC) • LUB OIL DISCHARGE FILTER CLEAR 0.6 KSC LUB OIL SYSTEM FAILED IF ANY OF THE FOLLOWING CONDITIONS EXISTS: • IF PULVERISER IS ON AND • LOP NOT ON FOR 2 SEC OR SUMP OIL TEMP NOT ADEQUATE (TD 1 HOUR) • LOSS OF A.C POWER AT PLOS PANEL FOR > 2 SEC • LUB OIL LEVEL VERY LOW (TD 10 SEC) • LOP ON AND LUB OIL PRESSURE VERY LOW (TD 10 SEC)
  • 18. RAW COAL FEEDER • PERMISSIVES • MILL RUNNING (30 SEC TIME DELAY) • FEEDER SPEED DEMAND AT MINIMUM AND FEEDER NOT RT • FEEDER IN REMOTE • COAL FIRING PERMISSIVE SATISFIED • PA FLOW ABOVE MINIMUM >10 T/Hr • BUNKER OUTLET GATE OPEN • FEEDER INLET GATE OPEN • FEEDER TRIP RESET • MILL MOTOR NOT OVER LOADED • MILL GROUP READY AND GROUP SEQUENCE STARTED • IF MILL GROUP SEQUENCE IN AUTO AND FEEDER IN AUTO AND HOT AIR GATE OPEN • NO BOILER TRIP
  • 19. PROTECTION • LOSS OF COAL ON BELT (TIME DELAY 5 SEC.) • SHEAR PIN FAIL • MFT ACTED • MILL MAIN MOTOR OFF 6.0 - AIR PRE HEATER PERMISSIVE (ELE / AIR MOTOR) • APH GUIDE BEARING TEMP NOT HIGH (<700C) • APH SUPPORT BEARING TEMP NOT HIGH (<700C) INTERLOCKS • AIR MOTOR STARTS (SOLENOID VALVE DE-ENERGISES) WHEN ELE. MOTOR TRIPS. • AIR MOTOR STOPS (SOLENOID VALVE ENERGISES) WHEN ELECTRICAL MOTOR STARTS. • SUPPORT / GUIDE BRG LOP STARTS WHEN APH ELEC MOTOR / AIR MOTOR ON AND APH GUIDE / SUPPORT BRG TEMP > 400C • SUPPORT / GUIDE BRG LOP STOPS WHEN APH BRG TEMP < 400C • STAND BY LOP WILL START WHEN AUTO START COMMAND IS PERSISTING FOR MAIN LOP FOR 2 SEC. AND THE MAIN LOP IS NOT ON OR IF THE RUNNING LOP TRIPS
  • 20. AIR PRE-HEATER DAMPERS FLUEGAS, SA & PA INLET/OUTLET DAMPER • AUTO OPEN • APH ELECTRIC / AIR MOTOR NOT ON AND OTHER APH ELECTRIC / AIR MOTOR NOT ON • AUTO CLOSE • APH ELECTRIC / AIR MOTOR NOT ON AND OTHER APH ELECTRIC / AIR MOTOR ON • OPERATION OF INLET & OUTLET DAMPERS OF APH (FOR AIR & FLUE GAS PATH) • FAN SIDE DAMPER SHOULD BE OPEN, FOR OPENING THE BOILER SIDE DAMPER • BOILER SIDE DAMPER SHOULD BE CLOSED FOR CLOSING FAN SIDE DAMPER
  • 21. BURNER MANAGEMENT SYSTEM PURGE PERMISSIVES • ALL NOZZLE VALVES, IGNITOR VALVES CLOSED. • LOTV, HOTV, COREX GAS TV & IGTV CLOSED. • ALL SCANNER SENSE NO FLAME (ALL ELEVATION ¾ SCANNERS SHOWS NO FLAME) • BC 2/4SCANNER FLAME NOT ON • AB 2/4SCANNER FLAME NOT ON • AX1 2/4SCANNER FLAME NOT ON • X1 2/4SCANNER FLAME NOT ON • X3 2/4SCANNER FLAME NOT ON • NO IGNITION FROM AX1 AND BC CORNERS • NO DISCRIMINTING SCANNER FLAME ON • ALL FEEDERS OFF • BOTH PA FANS OFF • MILLS A, B & C HOT AIR GATES CLOSED AND ACFS HOT AIR GATE CLOSED • IGNITOR GAS & COREX GAS VENT VALVES OPEN • ALL AUXLIARY DAMPERS MODULATING • ELEVATION A, B, C AND XX OUT OF FOUR ELEVATION >/=TWO ELEVATIONS SHOULD BE MODULATING
  • 22. • CC, BC, AB, AX1, X1, X2, X3 OUT SEVEN ELEVATIONS >/= FIVE ELEVATIONS SHOULD BE MODULATING • OR • ELEVATIONS A, B, C AND XX OUT OF FOUR ELEVATION >/=TWO ELEVATIONS CONTROL STATION OUT PUT COMMAND SHOULD BE >8% • CC, BC, AB, AX1, X1, X2, X3 OUT SEVEN ELEVATIONS >/= FIVE ELEVATIONS CONTROL STATION OUT PUT COMMAND SHOULD BE >8% UNIT AIR FLOW GREATER THAN 40%(190 TPH) • NO BOILER TRIP • DRUM LEVEL VERY LOW FOR MORE THAN 5 SECONDS • DRUM LEVEL VERY HIGH FOR MORE THAN 10 SECONDS • FURNACE PRESSURE VERY LOW (2/3 LOGIC) • FURNACE PRESSURE VERY HIGH (2/3 LOGIC) • TOTAL AIR FLOW LESS THAN 40% • BOTH ID FANS OFF • BOTH FD FANS OFF • LOSS OF REHEATER PROTECTION • UNIT FLAME FAILURE TRIP • LOSS OF ALL FUEL TRIP • LOSS OF 220V DC MFT POWER, FOR MORE THAN 2 SEC. • CRITICAL I/O MODULE FAIL • EMERGENCY TRIP SWITCH ACTIVATED • SPARE MFT TRIP • 11.ANY ID FAN AND FD FAN RUNNING • 12.CRITICAL IN PUT /OUT PUT MODULES FOR OIL GAS AND COAL ARE IN GOOD QUALITY
  • 23. FUEL OIL VALVES • PERMISSIVES • LOTV OPENS ONLY IF ALL THE FOLLOWING CONDITION PERSISTS • NO MFT ACTIVE • LFO SUPPLY PRESSURE ADEQUATE (HJF60CP101)>6 Ksc • ELEVATION AX1 ALL LFO VALVES CLOSED • LOTV TRIP CONDITIONS DOES NOT EXIST • LFO TRIP VALVES NOT RED TAGGED • LFO TRIP VALVE CLOSE FEED BACK EXIST • LFO BOTH HEADER PT’S NOT IN BADQUALITY • ATOMIZING AIR PT NOT IN BADQUALITY (HJN10CP101) • MODULE STATUS OK • HOTV OPENS ONLY IF ALL THE FOLLOWING CONDITION PERSISTS • NO MFT ACTIVE • HOTV CLOSED • ATOMIZING STEAM HEADER PT NOT BADQULITY • HFO HEADER PT’S NOT BAD QULITY • SLAVE MADULE STATUS OK • HO SUPPLY PRESSURE ADEQUATE >=8 Ksc (HJF40CP102) • ALL HO NOZZLE VALVES CLOSED • HO SUPPLY TEMPERATURE ADEQUATE >=100 DEG C (HJF30CT101)
  • 24. •HO RETURN TRIP VALVE OPEN • HO TRIP VALVE CLOSE COMMAND NOT EXISTS • HOTV NOT RED TAGGED HORV OPENS ONLY IF ALL FOLLOWING CONDITION PERSIST HO RETURN TRIP VALVE OPEN PUSHBUTTON PRESSED • ALL HO NOZZLE VALVES CLOSED IGNITOR TRIP VALVE OPENS ONLY IF THE FALLOWING CONDITIONS PERSISTNO MFT ACTIVE • IGTV IN CLOSE CONDTION • ALL IGNITOR VALVES OF AX1 AND BC CLOSED • IGNITOR GAS SUPPLY PRESSURE ADEQUATE>=0.75 KSC (SFA20CP101) • IGNITOR TRIP VALVE TRIP CONDITION NOT EXISTS • IGTV NOT RED TAGGED AND CLOSED • BOTH PRESSURE TRANSMITTERS ARE GOOD QUALITY •SLAVE MODULE GOOD QUALITY IGNITOR FIRING PERMISSIVE • AL TRIP CLEAR AND 1 MINUTE TIMED OUT • MFT RELAY RESET • IGTV OPEN • IGNITOR SUPPLY PRESSURE >MIN • IGNITOR SUPPLY PRESSURE <MAX • EITHER IGNITOR FAN RUNNING OR IGNITOR TO FURNACE DP NORMAL (>MIN 80MMWC)
  • 25. • PROTECTIONS HOTV CLOSES IF ANY OF THE FOLLOWING CONDITION PERSISTS. • TEMPERATURE OF HFO IS VERY LOW (HJF40CT102)<=90 0C AND ALL HONV’S NOT CLOSED AND HO RTV NOT OPENED • PRESSURE OF HFO IS VERY LOW (2.5 KSC)(HJF40CP102/3/4) AND ALL HONV NOT CLOSED INITIAL TIME DELAY 32 SEC NORMAL TIME DELAY IS 2 SEC • ANY HONV NOT CLOSED ON NO FLAME DETECTED AFTER IGNITION PROVEN (TIME DELAY IS 20SEC) AND ANY BURNER VALVE FAIL TO CLOSE • ATOMISING STEAM PRESSURE VERY LOW (3.0 KSC (HJF60CP101/2/3) & 5 SEC TIME DELAY) AND ALLHONV NOT CLOSED AND NO HO ELEVATION IN START/STOP>90 SEC AND HORTV NOT OPEN, • MFT ACTS AND HFO RETURN TRIP VALVE NOT OPEN • VALVE FAILED TO OPEN WITH IN 10 SEC • VALVE FAILED TO CLOSE WITH IN 10 SEC • NO FAULT IN HOTV FACE PLATE • VALVE LIMIT SWITCH MISS MATCH • HO PRESSURE BAD QUALITY • ATOMIZING STEAM PT BAD QUALITY • LOSS OF UNIT LOGIC POWER SUPPLY LOTV CLOSES IF ANY OF THE FOLLOWING CONDITION PERSISTS • LFO HEADER PRESSURE LOW (2.0 KSC) AFTER OPENING OF LOTV 32 SEC TIME DELAY • ATOMISING AIR PRESSURE VERY LOW TRIP (2.5 KSC & 5 SEC TIME DELAY), PROVIDED ANY OF LONV IS OPEN AND ATOMIZING AIR PRESSURE LOW AND NO LFO ELEVATION IN START /STOP FOR >70 SEC • VALVE FAILED TO CLOSE WITH IN 10 SEC AFTER GIVING CLOSE COMMAND (LOTV TRIPPED) • VALVE FAILED TO OPEN WITH IN 10 SEC AFTER GIVING OPEN COMMAND (LOTV TRIPPED) • NO FAULT LOTV FACE PLATE
  • 26. • ANY LONV NOT CLOSED ON NO FLAME DETECTED AFTER IGNITION PROVEN (TIME DELAY IS 20SEC AND ANY BURNER VALVE FAIL TO CLOSE) • BOTH LFO HEADER PT’S BADQUALITY • BOTH ATOMINZING AIR PT BAD QUALITY • IGNITOR BURNER VALVE FAILED TO CLOSE MORE THAN 20 SEC AFTER FLAME FAILURE • LOSS OF UNIT LOGIC POWER SUPPLY • MFT ACTIVE IGNITOR TRIP VALVE LOGIC IGNITOR TRIP VALVE CLOSES IF ANY OF THE FOLLOWING CONDITION EXISTS • BOILER TRIP (MFT) • IGNITOR GAS PRESSURE VERY LOW (0.2 KSC)(SFA20CP102) / HIGH (40 KSC) (SFA20CP101) PROVIDED ANY OF IGNITOR BURNER VALVES NOT CLOSED FOR MORE THAN 2 SEC. • IGNITOR BURNER VALVE AX1/BC FAILED TO CLOSE MORE THAN 20 SEC. AFTER SENSING NO FLAME AND ANY BURNER VALVE FAIL TO CLOSE • VALVE FAILED TO OPEN WITH IN 10 SEC • VALVE FAILED TO CLOSE WITH IN 10 SEC • IGNITOR GAS PRESSURE TRANSMITTER BAD QUALITY • LOSS OF UNIT LOGIC POWER SUPPLY NO TIME DELAY IS THERE FOR IGNITOR HEADER VENT VALVE CLOSING AFTER TRIP VALVE OPENING FOR ALL OIL BURNERS, WHILE SCAVENGING IGNITOR VALVE OPEN TIME IS 45 SEC
  • 27. OIL BURNER SEQUENCE. ON START COMMAND FOR ANY PAIR • IGNITOR CORNER VALVE OPENS PROVIDED IGNITOR NO FLAME PERSIST AND IGNITOR FIRING PERMISSIVE SATISFIED AND START COMMAND GIVEN. • PAIR START WILL INITIATE ELECTRIC SPARK FOR 10 SEC WITH IN 10 SEC IGNITOR HAS TO BE PROVEN (IONIC FLAME MONITOR DETECTS THE FLAME AND IGNITOR FLOW IS ADEQUATE) • IF IGNITOR PROVEN, ATOMISING AIR / STEAM VALVE OPENS (2-3 SEC). THEN OIL VALVE OPENS (2-3 SEC). • IF SCANNER SENSES FLAME BEFORE 70 SEC, GUN STABLISES. • IGNITOR STAYS FOR 70 SEC FROM INSTANT OF START COMMAND. • IGNITOR CORNER VAVLE STOP/CLOSE WILL BE INITIATED AFTER CORNER OIL NOZZLE VALVE OPEN (BURNER START TRIAL COMPLETION) WITH 15 SEC TIME DELAY • IGNITOR IS ALSO BROUGHT DURING SCAVENGING OR THE ASSOCIATED ELEVATION BURNERS HAVE PLANNED SHUT DOWN OR STOP COMMAND ATOMIZING AIR/STEAM VALVE OPEN • LFO/HFO SELECTED • ASSOCIATED CORNER IGNITOR TRIAL TIME COMPLETED • OIL GUN ENGAGE • SCAVENGING VALVE SHOULD BE CLOSED CONDITION • START MEMORY PERSISTING
  • 28. BURNER IN SERVICE WILL COME • LFO/HFO SELECTED • OIL START MEMORY . • ONCE OIL VALVE FULL OPENS AND 15 SEC ELAPSED AND WITH IN THIS PERIOD OIL FLAME DETECTED FROM MAIN FLAME SCANNE UNIT FLAME FAILURE • THE PROTECTION GETS ARMED WHEN ANY OF THE FOLLOWING CONDITION PERSISTS FOR > 2 SEC. • ANY COAL FEEDER PROVEN • AX1 OR BC OIL ELEVATION ¾ NOZZLE VALVES OPEN WITH HFO & HFO PRESSURE > 4 KSC • COREX X1 (2/4) / X2 (3/4) / X3 (3/4) GAS BURNERS IN SERVICE AND COREX GAS PRESSURE > 30% (100 MMWC) • WHEN ALL THE ELEVATIONS VOTED TOGETHER FOR NO FLAME FAILURE TRIP OCCURS ELEVATION VOTING • ELEVATION C VOTES WHEN ANY OF THE FOLLOWING CONDITION PERSISTS • FEEDER C NOT PROVEN FOR > 2SEC OR SIGNAL BADQUALITY . AND BC ELEVATION (3/4 NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQUALITY • BC ELEVATION 2/4 SCANNER SHOWS NO FLAME AND BC ELEVATION (3/4 NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQULITY .
  • 29. ELEVATION B VOTES WHEN ANY OF THE FOLLOWING CONDITION PERSISTS • FEEDER B NOT PROVEN FOR > 2 SEC OR SIGNAL BADQULITY . AND BC ELEVATION (¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQULITY • AB ELEVATION 2/4 SCANNER SHOWS NO FLAME AND ELEVATION BC 2/4 SCANNER SHOWS NO FLAME AND BC ELEVATION (¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQUALITY ELEVATION A VOTES WHEN ANY OF THE FOLLOWING CONDITION PERSISTS • FEEDER A NOT PROVEN FOR >2 SEC OR SIGNAL BADQULITY . AND AX1 ELEVATION (¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE AND AX1 HFO SELECTED. • AB ELEVATION 2/4 SCANNER SHOWS NO FLAME AND ELEVATION AX1 2/4 SCANNERS SENSE NO FLAME AND AX1 ELEVATION (¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE. ELEVATION X1 VOTES WHEN ANY OF THE FOLLOWING CONDITION PERSISTS • ELEVATION X1 NOT IN SERVICE 2/4 AND AX1 ELEVATION (¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQUALITY . • ELEVATION AX1 2/4 SCANNER SHOWS NO FLAME AND AX1 ELEVATION (¾ NOZZLE VALVE NOT OPEN) OIL NOT IN SERVICE OR SIGNAL BADQUALITY AND X1 2/4 SCANNER SHOWS NO FLAME. ELEVATION X2 VOTE WHEN ANY OF THE FOLLOWING CONDITION PERSISTS • X2 ELEVATION NOT IN SERVICE OR X1 ELEVATION 2/4 SCANNER SHOWS NO FLAME AND ELEVATION X3 2/4 SCANNER SHOWS NO FLAME. ELEVATION X3 VOTE WHEN ANY OF THE FOLLOWING CONDITION PERSISTS • WHEN X3 2/4 SCANNER SHOWS NO FLAME OR X3 ELEVATION NOT IN SERVICE. •
  • 30. LOSS OF ALL FUEL. • THE PROTECTION GETS ARMED WHEN ANY IGNITOR AT ANY ELEVATION GETS PROVEN. • BOILER WILL TRIP ON LOSS OF ALL FUEL WHEN ALL THE FOLLOWING CONDITION PERSISTS • ALL COREX NOZZELS VALVE CLOSED/TRIPPED • AX1 AND BC ELEVATION ALL HONV CLOSED/TRIPPED • ALL FEEDERS OFF/TRIPPED • AX1 ELEVATION ALL LONV CLOSED/TRIPPED • ALL IGNITOR VALVE CLOSED/TRIPPED OR IGTV NOT OPEN/TRIPPED REHEATER PROTECTION THIS PROTECTION GETS ARMED, WHEN ANY OF THE FOLLOWING CONDITION EXISTS • ANY FEEDER PROVEN. • ANY COREX BURNER PROVEN • AX1>/=3/4 WITH HFO • AX1 4/4 WITH LFO +BC>/=1/4 • BC >/= 3/4 WITH HFO • AX1= 2 WITH LFO +BC=/>1 • AX1=/>1 WITH LFO+BC=/>2 • AX1=/>1 WITH HFO+BC=/>2 BOILER WILL TRIP ON THIS PROTECTION WHEN ANY OF THE FOLLOWING CONDITION PERSISTS FOR 10 SEC. • GCB OPENS AND HPBP CV < 2% OPEN. • BOTH LPBP CVS < 2% OPEN. • BOTH LPBP STOP VALVES CLOSED. • BOTH MAIN STEAM VALVES (BOILER) ARE CLOSED.
  • 31. LESS THAN FIRE BALL & LOSS OF A.C. (NOT INCLUDED AT PRESENT) • BOILER WILL TRIP ON THIS PROTECTION WHEN ALL THE FOLLOWING CONDITION PERSISTS • ANY ELEVATION (AX1, BC, A, B, C, X1, X2, X3) STARTED & LOSS OF AC POWER FOR 2 SEC • ALL FEEDERS OFF • AX1 OR BC ELEVATION NOT IN SERVICE {ELEVATION IN SERVICE MEANS ¾ HFO NOZZLE VALVES OPEN AND HFO PRESSURE > 30%} IGNITOR AIR FAN • START PERMISSIVE • FAN NOT OUT OF SERVICE • FAN NOT RED TAGGED • IGNITOR TO FURNACE <75 MMWC • OTHER FAN FAIL TO START • OTHER FAN FAIL TO STOP • • • STOP PERMISSIVE IGNITOR TO FURNACE DP >75 MMWC AND OPERATOR STOP COMMAND • EMERGENCY STOP FROM LOCAL
  • 32. SCANNER AIR FAN • START PERMISSIVE • FAN NOT OUT OF SERVICE • SCANNER TO FURNACE DP<150MMWC • OTHER FAN FAIL TO START • • • • STOP PERMISSIVE STOP FROM DCS AND F SCANNER TO FURNACE DP>150 MMWC SCANNER FAN DISCHARGE PR LOW 230MMWC AND SCANNER TO FURNACE DP LOW 220MMWC • SCANNER AIR FAN EMERGENCY DAMPER • OPEN PERMISSIVE • BOTH FD FANS OFF • CLOSE PERMISSIVE • ANY FD FAN RUNNING •
  • 33. ADDITIONAL COAL FIRING SYSTEM (ACFS) ACFS PAV’S PERMISSIVES. • ALL MDV’S CLOSED. • ALL BIV’S OPENED. • ADJACENT IGNITION ENERGY PROVEN. • ELEVATION SELECTED FOR ACFS. • FURNACE FIRING PERMISSIVE SATISFIED. • FD FAN RELEASE. • UNSELECTED ELEVATION PAV’S NOT OPEN. • ACFS COLD AIR GATE OPEN. ACFS HOT AIR GATE PERMISSIVES: • ANY ONE-ELEVATION PAV’S FULL OPEN. • HOT AIR GATE CLOSED. • HOT AIR GATE NOT RED TAGGED. ACFS CIV’S PERMISSIVES: • ALL PAV’S OPENED.
  • 34. • UNSELECTED ELEVATION CIV’S FULL CLOSED. • ACFS PA FLOW ADEQUATE. • ACFS PA HEADER TEMP NOT HIGH. ACFS COMPRESSOR PERMISSIVES: • • DIV-1 OPEN TO GROUP A/C. • CONVEYING GROUP TRIP RESET. • COMPRESSOR TROUBLE RESET. • DIV-A & B OPEN TO SELECTED ELEVATION. • ALL CIV’S OF SELECTED ELEVATION OPEN. • ANY ONE ELEVATION SELECTED FOR ACFS. • MFT RELAYS RESET. • ACFS PS PUMP PERMISSIVES: • • COMPRESSOR RUNNING. • COMPRESSOR DISCHARGE PRESSURE ADEQUATE. • CONVEYING GROUP TRIP RESET. • PS PUMP DISCHARGE PRESSURE NOT VERY HIGH. • ACFS RAL PERMISSIVES: • • PS PUMP RUNNING. • COMPRESSOR DISCHARGE PRESSURE ADEQUATE. • PS PUMP DISCHARGE PRESSURE NOT VERY HIGH. • CONVEYING GROUP TRIP RESET. •
  • 35. ACFS BAG HOUSE FAN PERMISSIVES: ON STARTING OF ANY PS PUMP , BAG HOUSE BLOWER WILL START IN AUTO AND CORRESPONDING KGV WILL OPEN AFTER 15 SEC OF BLOWER RUNNING. BAG HOUSE BLOWER WILL STOP IN AUTO AFTER BOTH RAL STOPPING AND KGVS WILL CLOSE AFTER BLOWER STOP . ACFS CONVEYING GROUP EMERGENCY TRIPS: • LOSS OF COMPRESSOR TRIP . • LOSS OF ACFS PA FLOW TRIP . • ACFS SELECTED ELEVATION MDV OPEN TRIP . • ACFS SELECTED ELEVATION MMV OPEN TRIP [BYPASSED] • ACFS LOSS OF IGNITION ENERGY TRIP . • ACFS SELECTED ELEVATION DIV CLOSE TRIP . • ACFS LOSS OF PA FAN / PRESSURE TRIP . • BOILER TRIP – ACFS. • ACFS SLAVE BAD QUALITY TRIP .
  • 36. SECONDARY AIR DAMPER CONTROL • WIND BOX DP (MMWC) CONTROL SET POINT WILL BE GENERATED AS PER REQIREMENT DAMPER OPERATION: XX ELEVATION: • MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • CLOSE WHEN BOILER LOAD >30%AND X3 NO BURNERS IN SERVICE • OPEN FULL WHEN WB TO FURNACE DP GOES >THAN 240MMWC AND RESET AT 175MMWC • OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF)
  • 37. AB ELEVATION: • MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • CLOSE WHEN BOILER LOAD >30%AND MILL-A/ACFS PAV’S NOT OPEN FOR MILL-A AND MILL-B/ACFS PAV’S NOT OPEN NOT OPEN FOR MILL-B • OPEN FULL WHEN WB TO FURNACE DP GOES >THAN 175MMWC AND RESET AT 125MMWC •OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF) CC ELEVATION: • MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • CLOSE WHEN BOILER LOAD >30%AND MILL- C NOT IN SERVICE /ACFS PAV’S NOT OPEN FOR MILL-C • OPEN FULL WHEN WB TO FURNACE DP GOES >THAN 175MMWC AND RESET AT 125MMWC • OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF) X1 ELEVATION: • MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • CLOSE WHEN BOILER LOAD >30% AND AX1, X1 AND X2 NO BURNERS IN SERVICE • OPENING PROPORTINAL TO COREX C-HEADER PRESSURE (180MMWC TO 600MMWC SADC WILL OPERATE 30% TO 100%)WHEN X1 IN SERVICE •OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF) X2 ELEVATION: • MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • CLOSE WHEN BOILER LOAD >30% AND AX1, X1AND X3 NO BURNERS IN SERVICE • OPENING PROPORTINAL TO COREX C-HEADER PRESSURE (180MMWC TO 600MMWC SADC WILL OPERATE 30% TO 100%)WHEN X2 IN SERVICE • OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF)
  • 38. X3 ELEVATION: • MODULATE TO MAITAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • CLOSE WHEN BOILER LOAD >30% AND X2 AND X3 NO BURNERS IN SERVICE • OPENING PROPORTINAL TO COREX C-HEADER PRESSURE (180MMWC TO 600MMWC SADC WILL OPERATE 30% TO 100%)WHEN X3 IN SERVICE • OPEN FULL ON MFT (BOILER TRIP OR BOTH FD OFF OR BOTH ID OFF) • A ELEVATION: • MODULATE TO MAINTAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • OPENING PRAPORTIONAL TO ELEVATION FEED RATE FROM 20 TO 70% • CLOSE WHEN THE BOILER LOAD >30% AND AX1 AND A NOT IN SERVICE • OPENS FULL ON MFT • B ELEVATION: • MODULATE TO MAINTAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • OPENING PRAPORTIONAL TO ELEVATION FEED RATE FROM 20 TO 70% • CLOSE WHEN THE BOILER LOAD >30% AND BC OR B NOT IN SERVICE • OPENS FULL ON MFT • C ELEVATION: • MODULATE TO MAINTAIN WIND BOX TO FURNACE DP AS PER ABOVE CURVE (TABLE) • OPENING PRAPORTIONAL TO ELEVATION FEED RATE FROM 20 TO 70% • CLOSE WHEN THE BOILER LOAD >30% AND BC OR C NOT IN SERVICE • OPENS FULL ON MFT • • AFTER 40 SEC OF MFT ALL THE DAMPERS TO AUTOMATICALLY MODULATE TO MAINTAIN 40 MMWC WIND BOX PRESSURE