Jyri Nieminen & Mikael Salonvaara
Hygrothermal performance of
light steel-framed walls
V T T R E S E A R C H N O T E S
TECHNICAL RESEARCH CENTRE OF FINLAND ESPOO 2000
VTT TIEDOTTEITA – MEDDELANDEN – RESEARCH NOTES 2070
TECHNICAL RESEARCH CENTRE OF FINLAND
ESPOO 2000
Hygrothermal performance of
light steel-framed walls
Jyri Nieminen, Mikael Salonvaara
VTT Building Technology
ISBN 951–38–5772–7 (soft back ed.)
ISSN 1235–0605 (soft back ed.)
ISBN 951–38–5773–5 (URL: http://www.inf.vtt.fi/pdf/)
ISSN 1455–0865 (URL: http://www.inf.vtt.fi/pdf/)
Copyright © Valtion teknillinen tutkimuskeskus (VTT) 2000
JULKAISIJA – UTGIVARE – PUBLISHER
Valtion teknillinen tutkimuskeskus (VTT), Vuorimiehentie 5, PL 2000, 02044 VTT
puh. vaihde (09) 4561, faksi (09) 456 4374
Statens tekniska forskningscentral (VTT), Bergsmansvägen 5, PB 2000, 02044 VTT
tel. växel (09) 4561, fax (09) 456 4374
Technical Research Centre of Finland (VTT), Vuorimiehentie 5, P.O.Box 2000, FIN–02044 VTT, Finland
phone internat. + 358 9 4561, fax + 358 9 456 4374
VTT Rakennustekniikka, Rakennusfysiikka, talo- ja palotekniikka,
Lämpömiehenkuja 3, PL 1804, 02044 VTT
puh. vaihde (09) 4561, faksi (09) 455 2408
VTT Byggnadsteknik, Byggnadsfysik, hus- och brandteknik,
Värmemansgränden 3, PB 1804, 02044 VTT
tel. växel (09) 4561, fax (09) 455 2408, (09) 456 4709
VTT Building Technology, Building Physics, Building Services and Fire Technology,
Lämpömiehenkuja 3, P.O.Box 1804, FIN–02044 VTT, Finland
phone internat. + 358 9 4561, fax + 358 9 455 2408, 358 9 456 4709
Technical editing Leena Ukskoski
Otamedia Oy, Espoo 2001
3
Nieminen, Jyri & Salonvaara, Mikael. Hygrothermal performance of light steel-framed walls. Espoo
2000. Technical Research Centre of Finland, VTT Tiedotteita – Meddelanden – Research Notes 2070.
26 p.
Keywords building envelope, steel structures, light-gauge steel, corrosion tests, weather resistance,
moisture, surface condensation, climatic conditions, heat transfer
Abstract
Hygrothermal performance of a new light-gauge steel framed building envelope system
has been analyzed using 3-D thermal simulations, 2-D combined heat, air and moisture
transfer simulations, laboratory testing in a calibrated and guarded hot box (ISO 8990),
weather resistance tests for full-sized structures, corrosion tests and field measurements
at experimental buildings in Ylöjärvi, Central Finland. The results show that a modern
steel wall structure based on perforated steel profiles performs satisfactorily in the cold
climate of Finland. The perforations reduce heat loss along the web of the profile
significantly. The field measurements show that no condensation has occurred in the
frame system. Temperature measurements and infrared surveys in demonstration
buildings show that surface temperatures are sufficiently high to prevent surface
condensation or even increased humidity on the surface. According to the calculations,
there are no severe corrosion risks in the steel frames in the Finnish climate. The
climate, however, has an important effect on the performance, and the structures should
be designed with regard to climatic conditions.
4
Preface
New building envelope systems based on light steel framing have been developed and
studied during the last 10–15 years in Finland. The focus of the research has been in the
high performance exterior wall systems. Good thermal insulation properties, durability
and minimised corrosion and moisture risks have been the key issues.
A number of research projects have been carried out during 1989–2000. This report
gives an overview of the most important results of these studies. The research work has
been funded by Rautaruukki Oyj, Outokumpu Polarit Oy, The Finnish Constructional
Steelwork Association, The National Technology Agency (Tekes), VTT Steel Research
Programme and The European Coal and Steel Community (ECSC).
5
Contents
Abstract............................................................................................................................. 3
Preface............................................................................................................................... 4
1. Introduction................................................................................................................. 7
2. Thermal performance of light steel structures............................................................. 8
2.1 Thermal bridges................................................................................................. 8
2.2 Comparision of thermal analysis tools............................................................. 12
2.3 Airtightness of steel buildings ......................................................................... 14
2.4 Temperature distribution in light gauge steel walls......................................... 14
3. Durability of light steel framing................................................................................ 17
3.1 Moisture variation in steel-framed walls ......................................................... 17
3.2 Corrosion risks caused by materials in contact with light gauge steel ............ 17
3.3 Hygrothermal simulations ............................................................................... 19
4. Summary ................................................................................................................... 23
References....................................................................................................................... 25
6
7
1. Introduction
New building enevlope systems based on light steel framing have been developed
during the last 10–15 years. The focus has been in commercial and public buildings, but
the use of steel structures in housing has also increased. Service life of buildings and
building components has become more and more important feature in marketing of
building products. When new building systems are introduced, the question of the
hygrothermal performance will be inevitably raised.
The purpose of the research has been to evaluate the hygrothermal performance and
durability of a light steel frame system used as an exterior wall structure in various
types of buildings. A number of research projects have been completed to show real,
tested and verified results on the questions related to performance:
• Development of light prefabricated steel framed facade units: Development and
hygrothermal testing of new light gauge steel frame systems /15/.
• Development 3-D heat transfer tools for steel structures: numerical 3-D tool for
calculation of temperature and heat flow distribution in steel structures /10/.
• Service life design of steel structures: field surveys of steel buildings, long-term
corrosion tests /6/.
• VTT Steel research programme’s /16/ project Performance of steel buildings:
development hygrothermal calculation tools, measuring devices and methods.
• ECSC (European Coal and Steel Coalition) Mega5-project Application of steel in
urban habitats: Low-energy steel house for a cold climate: development, testing and
demonstration of a new steel frame system, concept for energy-efficient residential
housing based on steel frame structures /7, 11/.
A new concept for steel construction based on perforated light gauge steel profiles was
developed and demonstrated in Ylöjärvi, Central Finland. The aim of the ECSC funded
Mega5 project /7/ were to ensure the performance and suitability of a light-gauge steel-
framed house for use in a cold climate. The project included comprehensive research on
the structural and hygrothermal performance of the structures as well as research on the
energy performance and environmental impacts of steel buildings.
The hygrothermal performance of a number of structures have been assessed using 3-
dimensional heat flow calculations and laboratory measurements with full-size
structures in a calibrated and guarded hot box according to ISO 8990 standard and
laboratory weather resistance tests. Also, the thermal performance of the structures was
investigated in the field monitoring (1996–2000) at the Ylöjärvi steel houses. The
monitoring project included temperature measurements from various locations in the
building envelopes, infrared surveys of the buildings, blower door tests to assess the air
tightness of the buildings and moisture monitoring from the frame structure.
In the VTT Steel research Programme’s /16/ research project ‘Performance of steel
buildings’ the accuracy of various measuring methods and computerized calculation
tools have been tested. The focus of the research has been on thermal measurements and
calculations.
8
2. Thermal performance of light steel structures
2.1 Thermal bridges
Just like all frame materials in an insulated structure, a steel member is a thermal bridge.
But, since thermal conductivity of steel is high, severe bridge effects are possible. The
effect of thermal bridges has been reduced by three methods:
• using double frame systems
• using exterior insulation systems
• using perforated (or slotted) the steel profiles.
Light-gauge steel-framed structures based on double frame system (horizontal and
vertical frame, Figure 1) have been used as external walls of office and public buildings.
The distance between the frames in both directions is typically 0.6 meters, and thermal
insulation is installed into the cavities between the frames. Double frame system
improves thermal quality of a wall by 20–25 % compared to single frame cavity
insulated wall, Table 1.
Exterior insulation systems reduce thermal bridging in a wall. The effect depends on the
thermal properties of the insulation system. Exterior insulation is very advantageous in
terms of moisture behavior, since the frame temperatures increase which in turn reduces
moisture risks in the frame.
Perforated webs in a light-gauge steel frame give two advantages for the structure. Due
to the perforations, the thermal properties of the structure are improved. This, in turn,
makes it feasible to use the structure as a single-frame wall system. A light-gauge steel
frame with perforated web is termed a thermoprofile, see Figures 2 and 3. U-shaped
thermoprofiles are used in prefabricated facade units for high-rise buildings. The load
bearing walls of detached and row houses are composed of vertical C-shaped
thermoprofiles. The material thickness of the profiles is typically 1.0–1.5 mm.
The effect of the perforations or slots in a thermoprofile can be taken into account by
introducing an equivalent thermal conductivity for the non-perforated material. Heat
transfer in the web can be assumed to be pure heat conduction. The equivalent thermal
conductivity can be defined by comparing conduction in the perforated case and in the
non-perforated case. The equivalent thermal conductivity depends on the perforation
system including the shape and dimensions of perforations, the dimensions of the steel
necks between the perforations and the thermal conductivity of the material in the
perforations, see Figure 4.
9
The reduced thermal bridging has a considerable effect on reducing the heat conduction
in the thermoprofile relative to solid steel (Figure 5). The perforations perform as
thermal breaks for the steel member reducing the heat conduction along the web by 70–
80%, Figure 6. According to studies carried out in Finland and Sweden /1, 8, 9/, the
equivalent thermal conductivity of a thermoprofile can be 5–10 W/m2
K.
Figure 1. Single and double framed wall structures used as exterior wall in Finland.
Table 1. Relative thermal resistance of insulated steel framed wall compared to one-
dimensional resistance of thermal insulation of corresponding thickness. All insulation
materials mineral wool, thermal conductivity 0.037 W/mK.
Wall structure Relative thermal resistance, %
Mineral wool insulation 175 mm 100
Single frame wall (figure 1)
- vertical frame C 175–50–1.2
45
Double frame wall
n vertical frame C 125–50–1.2
n horizontal frame Z 50–50–1.0
65
Single frame wall + exterior insulation 125+50 mm
- vertical frame C 125–50–1.2
75
Single frame wall, thermoprofiles
- vertical frame C 175–50–1.2
80
10
Figure 2. Thermoprofile alternatives. Profiles in the top row were used in Villa 2000
built for the Tuusula housing fair 2000 (left), and in Ylöjärvi steel houses built for the
Ylöjärvi housing fair 1996 (right). Other two exmples were manufactured for testing
purposes.
11
Equivalent thermal conductivity
5,5 – 7,5 W/m2
K
Equivalent thermal conductivity
5,5 – 7,5 W/m2
K
Equivalent thermal conductivity
5,0 – 7,0 W/m2
K
Figure 3. Perforation alternatives of a thermoprofile. Equivalent thermal conductivity
takes into account the perforations filled with insulation material. Equivalent thermal
conductivity depends on the properties of thermal insulation, the dimensions of the
perforations and the dimensions of the solid steel between the perforations.
0
5
10
15
20
25
30
35
0 1 2 3 4 5 6
THERMAL CONDUCTIVITY OF INSULATION [W/mK]
- +
HEAT
CONDUCTION
Figure 4. The effect of thermal insulation into the equivalent thermal conductivity of the
typical Finnish thermoprofile /12/.
0
10
20
30
40
50
60
THERMALCONDUCTIVITY[W/mK]
ZINC-COATEDSTEEL
STAINLESSSTEEL
THERMOPROFILE
CONCRETE
BRICK
WOOD
Figure 5. Thermal conductivity of various building materials used in load-bearing
structures. Equivalent thermal conductivity for the thermoprofile.
12
0,15
0,2
0,25
0,3
0,35
0,4
0,45
0,5
0,55
125 150 175 200 225 250 275
INSULATION THICKNESS [mm]
U-VALUE[W/m2K]
2,0 mm
1,5 mm
1,2 mm
2,0 mm
1,5 mm
1,2 mm
1,0 mm
45 mm
STEEL FRAME
C - 150…250 - 1,2…2,0
THERMO-PROFILE
C - 150…250 - 1,2…1,5
WOODEN FRAME
45 * 150…250
THERMO-PROFILE 1,2 mm:
MEASUREMENT: ISO8990
Figure 6. Calculated values of thermal transmittance for steel-framed and wood-framed
walls /9/. The thermal benefit of the perforations in a steel member of a single frame
structure is 40-50% depending on the insulation thickness of the wall.
2.2 Comparision of thermal analysis tools
Steel structures are typically 3-dimensional structures. Thermal analysis of these
structures is complicated, since numerical methods for 3-dimensional calculations are
usually required. However, single frame structures can be analysed using 2-dimensional
calculations even in the case where the web of a steel profile is perforataed, using
equivalent thermal conductivity as a material property for the steel member.
To facilitate the accuracy of calculational methods in comparision to measurements, a
series of laboratory tests in calibrated and guarded hot box apparatus (ISO 8990, /3/)
was carried out. Further more, the suitability of the heat flow method according to DIN
52611 standard /2/ for measurement of thermal transmittance was tested. The results
show that the agreement between calculated and measured (ISO 8990) results is rather
good, Table 2. Although only a few structures were tested, the heat flow method
according to DIN 52611 shows too high values compared to other analysis methods.
13
Table 2. Comparision of the thermal analysis tools for assessment of thermal
transmittance (U-value) of light steel framed walls. Measured values according to ISO
8990 and DIN 52611 standards and results from 2- and 3-dimensional simulations.
Wall type Structure layers from inside U-value [W/m2
K]
Gypsum board 13 mm
PE film vapor barrier
Steel frame a) TC 175–50–1,2 mm or
b) C 175–50–1,2 mm
+ mineral wool insulation
Gypsum board wind proofing 9 mm
a) ISO 8990: 0,263
3-D simulation: 0,257
2-D simulation: 0,257*)
b) 3-D simulation: 0,435
2-D simulation: 0,435
*)
equivalent thermal
conductivity 7,3 W/mK
Gypsum board 13 mm
PE film vapor barrier
Steel frame TC 175–50–1,2 mm
+ mineral wool insulation
Gypsum board wind proofing 9 mm
Wind proof rigid mineral wool 45 mm
ISO 8990: 0,188
3-D simulation: 0,190
2-D simulation: 0,190 *)
*)
equivalent thermal
conductivity 7,3 W/mK
Gypsum board 13 mm
PE film vapor barrier
Steel frame TU 150–50–1,0 mm
+ mineral wool insulation
Gypsum board wind proofing 9 mm
ISO 8990: 0,300
DIN 52611: 0,350
3-D simulation: 0,292
2-D simulation: 0,290*)
*)
equivalent thermal
conductivity 5,5 W/mK
Gypsum board 13 mm
PE film vapor barrier
Stailess steel frame U 150–50–1,0 mm
+ mineral wool insulation
Gypsum board wind proofing 9 mm
ISO 8990: -
DIN 52611: 0,375
3-D simulation: 0,340
2-D simulation: 0,340
Gypsum board 13 mm
PE film vapor barrier
Steel frame U 50–50–1,0 mm
+ mineral wool insulation
Steel frame U 125–50–1,0 mm
+ mineral wool insulation
a) air gap + over-clad steel façade
b) no façade
a)ISO 8990: 0,281
3-D simulation: 0,282
b) DIN 52611: 0,345*)
3-D simulation: 0,321*)
Gypsum board 13 mm
PE film vapor barrier
Steel frame U 150–50–2,0 mm
+ mineral wool insulation
Steel frame TU 100–50–1,0
+ mineral wool insulation
Gypsum board wind proofing 9 mm
ISO 8990:
DIN 52611: 0,225
3-D simulation: 0,214
3-D simulation: 0,210*)
*)
equivalent thermal
conductivity 16 W/mK
TC = C-shaped perforated steel profile (thermoprofile)
TU = U-shaped perforated steel profile, U = U–shaped steel profile
14
2.3 Airtightness of steel buildings
Air tightness of steel building has been tested only in 4 cases. Table 3 shows results
from measured cases and reference information from typical Finnish buildings.
Table 3. Airtightness of steel houses and typical Finnish buildings.
Building type Air leakage rate at 50 Pa,
air changes per hour
Prefabricated steel houses (row houses) 1,9–2,5
Site built steel house (row house) 3
Site built wooden detached houses 3–4
Prefabricated wooden detached houses 2–4
Prefabricated wooden row houses 3–5
Massive wooden houses (log houses) 7–15
Concrete buildings 1–4
Low-energy detached houses 0,8–2
The locations of air leaks in the steel houses were searched using an infrared camera.
Insufficient sealing of electrical and ventilation installations leading through the
air/vapor barrier of the envelope caused the most of the air leaks. These defects were
found systematically in all of the buildings.
2.4 Temperature distribution in light gauge steel walls
Temperature distributions in the single frame structures have been measured both in a
series of full-scale laboratory weather tests and in the structures of Ylöjärvi steel houses.
The temperatures on inner wall surface are sufficiently high to prevent ghosting, surface
condensation or even relative humidity high enough to increase the risk of mold growth
on the wall surface, Figures 7 and 8. Temperature on the inner surface of the wall on top
of the frame is 1–2 °C lower than the temperature between the frames.
The temperature of the outer flange of the steel frame depend on the thermal properties
of the wall outside the frame, Figure 9. The outer flange of the profile is considerably
warmer than outdoor air temperature due to heat conduction from the interior along the
web of the steel profile. Even though the perforations in a thermoprofile reduce heat
conduction along the frame, the residual conduction increases temperatures in the outer
parts of the frame, thus reducing the condensation risk and increasing the drying
potential in case of condensation. The use of exterior water vapor permeable insulation
as in the low-energy wall further improves the hygrothermal performance of the wall.
15
>24,9°C
<15,0°C
16,0
18,0
20,0
22,0
24,0
Figure 7. Infrared image of a steel wall.
-40
-30
-20
-10
0
10
20
30
0 2 4 6 8 10 12 14 16 18 20
Test time [days]
INDOORS
THERMO-PROFILE
STEEL PROFILE
OUTDOORS
Figure 8. Surface temperatures of a light steel-framed wall according to a laboratory
weather test.
16
-20
-15
-10
-5
0
5
10
0 0,5 1 1,5 2 2,5
THERMAL RESISTANCE OUTSIDE THE FRAME [m
2
k/W]
TEMPERATURE[
o
C]
GYPSUM BOARD 9 mm
WIND PROOF MINERAL WOOL 50 mm
WIND PROOF MINERAL WOOL 100 mm
OUT: -20 o
C
IN: +20o
C
Figure 9. The effect of thermal properties of wind proofing (see Figure 1) on the
temperature of outer parts of the frame /12/.
17
3. Durability of light steel framing
3.1 Moisture variation in steel-framed walls
The corrosion of a metal depend on the micro climate on the surface of a component.
Continuous corrosion is possible, if relative humidity on the metal surface exceeds 80%
at the same time as temperature is above 0°C (ISO 9223, /4/).
Figure 10 shows the monthly maximum values of relative humidity of eight measuring
points in the outer flange of the steel profiles measured in the Ylöjärvi steel houses. The
results show that relative humidity in wall 1 has exceeded 80%, but no condensation has
occurred. The humidity in wall 2 has not exceeded 90%.
40
50
60
70
80
90
100
MONTH 1996 - 1999
WALL1 1996 - 1997
WALL2 1996 - 1997
WALL1 MAXIMUM 1996 - 1999
WALL2 MAXIMUM 1996 - 1999
WALL1 WALL2
MEASUREMENTS
-
+
8 10 12 2 4 6 8
Figure 10. Monthly maximum of relative humidity in the external walls of the Ylöjärvi
steel buildings. Measurements on the outer flange of the steel members.
3.2 Corrosion risks caused by materials in contact with light
gauge steel
Corrosion risks caused by other building materials in contact with steel are studied in an
on-going long-term laboratory test. Insulated steel frames are placed in different
climates to see the effect of material and air humidity on corrosion. The materials being
studied are:
18
• cellulose fiber insulation
• glass wool insulation
• rock wool insulation
• impregnated wood.
The laboratory test has been going on for about 4 years (35000 hours of time of
wetness). Test conditions are given in Figure 11. The results show that the cellulose
insulation and impregnated wood promotes zinc corrosion in humid conditions, but no
corrosion products from steel were detected in any of the test pieces (Figure 12). There
are no signs of zinc corrosion in the test pieces insulated with mineral wool products. In
the case with continuous condensation, edge corrosion of steel was found in all the
specimens. The fire retardant chemicals (borax and boric acid) of the cellulose fiber
insulation were not stagnant. The chemicals re-crystallized on the steel surface, which
caused stronger edge corrosion in the test specimens insulated with cellulose fiber
insulation compared to other specimens.
Figure 11. Test climates in corrosion tests. Normal indoor conditions are being used as
reference (top). Corrosion tests are carried out in humid air (middle) and in conditions
where condensation occurs continuously (bottom).
19
a) Glass wool: no corrosion. b) Rock wool: no corrosion.
c) Cellulose fibre: zinc corrosion d) Impregnated wood: zinc and steel
corrosion.
Figure 12. Long-term corrosion test with steel members in contact with other materials.
Test conditions +23°C and 85% relative humidity. Test time 35 000 hours.
3.3 Hygrothermal simulations
The hours of wetness were also calculated for two wall types depicted in Figure 13
using the 2-D heat, air and moisture transfer simulation program LATENITE /5, 13/:
• Case A: the wall shown in Figure 6 on the left without exterior insulation and
• Case B: the wall shown in Figure 6 on the right, like case A except for an additional
layer of exterior insulation of 50 mm rigid wind proof mineral wool.
The hourly climates of Helsinki, Finland and St. Hubert, Belgium were used as a
starting point. The orientation of the walls was north which is considered to be the worst
orientation in terms of hygrothermal performance due to low solar radiation absorption.
Wind-driven rain was not taken into account in the simulations and the walls were
assumed to have a cladding with good cavity ventilation behind the cladding. The initial
conditions of the material layers were +20°C and 50% relative humidity. The indoor air
conditions were:
20
• temperature +22°C or outdoor air temperature if higher than +22°C
• indoor air moisture content xin was outdoor air moisture content xout + 3 g/kg, but
limited to 30% ≤ relative humidity ≤ 80%.
The simulations were carried out for a two-year period starting September 1.
The accumulated time of wetness for the two-year period in different parts of the wall
structures is shown in Figures 14 and 15 (wall with no exterior insulation) and in
Figures 16 and 17 (wall with exterior insulation). The results are valid on condition that
1) the vapor retarder in the warm side of the wall performs as intended, 2) there is no
high initial moisture content in the wall and 3) the wall system has been designed and
constructed to avoid moisture leaks into the wall (e.g., wind-driven rain).
Gypsum board 13 mm
PE-film 0,2 mm
Thermoprofile TC 175–50–1,2 mm
+ insulation 175 mm
Gypsum board wind proofing 9 mm
Ventilated air gap 22 mm
Wooden facade
Gypsum board 13 mm
PE-film 0,2 mm
Thermoprofile TC 175–50–1,2 mm
+ insulation 175 mm
Gypsum board wind proofing 9 mm
Wind proof rigid mineral wool 50 mm
Ventilated air gap 22 mm
Wooden facade
Figure 13. Illustration of the structure with perforated light gauge steel frame without
and with exterior insulation.
The results show, that the durability of the walls depends mainly on the outdoor climate
and the hygrothermal properties of the wind proofing attached on the outside of the
profiles. The hygroscopicity of the gypsum board is fairly low, but when moistened by
the outdoor air, it dries out rather slowly. This phenomenon increases the time of
wetness on the outer surface of the outer flange of a profile.
21
0.00 0.05 0.10 0.15 0.20 0.25
Distance from exterior surface, m
0.25
0.30
0.35
0.40
Width,m
1000
6000
IWET
6000
5000
4000
3000
2000
1000
Week # 104
Helsinki
Figure 14. Contour plot of the accumulated time of wetness in the layers of the steel
frame wall without exterior insulation. Exterior conditions: Helsinki weather data.
Length of the simulated period is 2 years (104 weeks). Arrow shows the location of the
highest contour value /14/.
0.00 0.05 0.10 0.15 0.20 0.25
Distance from exterior surface, m
0.25
0.30
0.35
0.40
Width,m
6000
1000
IWET
6000
5000
4000
3000
2000
1000
Week # 104
Saint-Hubert
Figure 15. Contour plot of the accumulated time of wetness in the layers of the steel
frame wall without exterior insulation. Exterior conditions: Saint Hubert weather data.
Length of the simulated period is 2 years (104 weeks) /14/.
22
0.00 0.05 0.10 0.15 0.20 0.25
Distance from exterior surface, m
0.25
0.30
0.35
0.40
Width,m
1000
5000
IWET
6000
5000
4000
3000
2000
1000
Week # 104
Helsinki
Figure 16. Contour plot of the accumulated time of wetness in the layers of the steel
frame wall with 50-mm exterior insulation. Exterior conditions: Helsinki weather data.
Length of the simulated period is 2 years (104 weeks) /14/.
0.00 0.05 0.10 0.15 0.20 0.25
Distance from exterior surface, m
0.25
0.30
0.35
0.40
Width,m
1000
6000
IWET
6000
5000
4000
3000
2000
1000
Week # 104
Saint-Hubert
Figure 17. Contour plot of the accumulated time of wetness in the layers of the steel
frame wall with 50 mm exterior insulation. Exterior conditions: Saint Hubert weather
data. Length of the simulated period is 2 years (104 weeks) /14/.
23
4. Summary
Irrespective of the materials from which frame structures are made, they form thermal
bridges to varying degrees across the thermal insulation layer. Thermal conductivity of
steel is high. A steel frame in a light-gauge construction extending uninterrupted across
the thermal insulation layer has a considerable effect on the thermal performance of the
structure. The development of thermal assessment tools has helped for the rapid
development of well insulated light-gauge single framed steel structures introducing
perforated webs of a steel member as thermal breaks in the structure. Due to the
perforations, the thermal properties of the structure are improved. The analysis carried
out shows that the new application of perforated light gauge steel frames fulfills the
requirements set for performance and durability in a cold climate of Finland.
If adequately designed and constructed, there are no major moisture or corrosion risks
involved with the structures. The long-term laboratory test and the field survey suggest,
that a steel frame insulated with mineral wool has a very good corrosion resistance and
thus a long service life.
The performance of an insulated structure depends on the performance of different
material layers together as a structure. Connection of gypsum board windproofing to
steel frame may reduce the corrosion resistance of the zinc layer by the slow humidity
variations due to hygrothermal properties of gypsum board with cardboard surfaces. In
moist conditions, cellulose fibre insulation and impregnated wood form alcalinous
environment, and thus increase the zinc corrosion rate. However, proper design and
installation may avoid the risks.
According to the calculation results and field measurements at Ylöjärvi steel houses, the
properties of the wind proofing material and the façade structure have an important
effect on the overall performance of the structure. By increasing the thermal resistance
of the wind proofing material the durability risk of corrosion due to exterior or interior
moisture loading can be totally neglected. Water vapor permeable and windproof
exterior insulation system increases the drying potential of a structure.
The service life of the structure can be estimated using the standard ISO 9223 Corrosion
of Metals. The corrosion is dependent on the time of wetness hours. With regard to all
the results from various research projects, the time of wetness hours in the most critical
point of the structure are between 0 and 2600 in the climate of Helsinki and 0–6100 in
the climate of St. Hubert depending on the composition of the structure. The corrosion
classification of the zinc layer is C1 or C2 (ISO 9223), where the service life of the zinc
layer is estimated to be from 40 years to more than 100 years. In the class C1, the linear
corrosion speed of zinc is less than 0,05 µm and, in the class C2, less than 0,5 µm a
24
year. If the thermal and hygrothermal effects of facade claddings are taken into account,
a reduced number of time of wetness hours can be expected, and thus a longer service
life for the zinc layers.
25
References
1. Blomberg, T. Heat conduction in two and three dimensionss. Computer modeling of
building physics applications. Lund 1996. Lund University. Report TVBH-1008.
2. DIN 52611. 1991. Teil 1. Wärmeschutztechnische Prüfungen; Bestimmung des
Wärmedurclasswiderstandes von Bauteilen. Prüfung im Laboratorium. Deutche
Institutt für Normierung.
3. ISO 8990. International standard 1994. Thermal insulation. Determination of
steady-state thermal transmission properties. Calibrated and guarded hot box.
International Organization for Standardization.
4. ISO 9223. International standard 1992. Corrosion of metals and alloys. Corrosivity
of atmospheres. Classification. International Organization for Standardization.
5. Karagioziz, A., Salonvaara, M. and Kumaran, K. 1994. LATENITE, Hygrothermal
material database, IEA Annex 24. International Energy Agency IEA Report TI-CA-
94/04.
6. Leino, T., Häkkä-Rönnholm, E., Nieminen, J., Koukkari, H., Hieta, J., Vesikari, E.
and Törnqvist, J. 1998. Teräsrakenteiden käyttöikäsuunnittelu. Service life design
of steel structures. VTT Research Notes 1937. 119 p. + app. 11 p. (In Finnish).
7. Low-energy steel house for a cold climate. ECSC project application of steel in
urban habitats. Project n:o 7210-SA/902 - 95 - F6.1. Final Report. Rautaruukki Oy
1998.
8. Mao, G. 1997. Thermal bridges. Efficient models for energy analysis in buildings.
Dissertation. Division of Building Technology, Department of Building Sciences,
Kungliga Tekniska Högskolan, Stockholm. Bulletin No 173. ISSN 0346-5918.
9. Nieminen, J. 1997. New well insulated light-gauge steel framed wall structure.
Proceedings of the 5th
International Conference Modern Building Materials,
Structures and Techniques. Vilnius, Lithuania, May 24–26, 1997. Vilnius Geminida
Technical University.
10. Nieminen, J., Kouhia I., Johanneson, G. and Mao, G. 1995. Design and thermal
performance of insulated sheet metal structures. Proceedings of the Nordic Steel
Construction Conference’95. Malmö, Sweden, June 19–21, 1995.
26
11. Nieminen, J., Saari, M., Salmi, P. and Tattari, K. 1997. Low energy steel house for
a cold climate. Proceedings of the International Conference Cold Climate
HVAC'97. Reykjavik, Iceland May 1–2, 1997. Iceland Heating, Ventilating and
Sanitary Association ICEVAC.
12. Nieminen, J. and Salonvaara, M. 1999. Long-term performance of light-gauge steel-
framed envelope structures. Proceedings of the Fourth International Conference on
Steel and Aluminium Structures ICSAS’99. Elsevier Science ltd. ISBN 0-08-
043014-7.
13. Salonvaara, M. and Karagiozis, A. 1994. Moisture transport in building envelopes
using an approximate factorization solution method. In: Proceedings of the Second
Annual Conference of the CFD Society of Canada Ed. by James J. Gottlieb and C.
Ross Ethier. Toronto, June 1–3, 1994.
14. Salonvaara, M. and Nieminen, J. 1998. Hygrothermal performance of a new light-
gauge steel-framed envelope system. Journal of Thermal Environment and Building
Science (22) 1998.
15. Teräsrunkoisen julkisivuelementin suunnitteluohje. 1993. Teräsrakenneyhdistys r.y.
TRY. ISBN 952-9683-04-9
16. VTT Steel Research Programme. VTT Building Technology. In print.
Published by
Vuorimiehentie 5, P.O.Box 2000, FIN–02044 VTT, Finland
Phone internat. +358 9 4561
Fax +358 9 456 4374
Series title, number and
report code of publication
VTT Research Notes 2070
VTT–TIED–2070
Author(s)
Nieminen, Jyri & Salonvaara, Mikael
Title
Hygrothermal performance of light steel-framed walls
Abstract
Hygrothermal performance of a new light-gauge steel framed building envelope system has been
analyzed using 3-D thermal simulations, 2-D combined heat, air and moisture transfer
simulations, laboratory testing in a calibrated and guarded hot box (ISO 8990), weather
resistance tests for full-sized structures, corrosion tests and field measurements at experimental
buildings in Ylöjärvi, Central Finland. The results show that a modern steel wall structure based
on perforated steel profiles performs satisfactorily in the cold climate of Finland. The
perforations reduce heat loss along the web of the profile significantly. The field measurements
show that no condensation has occurred in the frame system. Temperature measurements and
infrared surveys in demonstration buildings show that surface temperatures are sufficiently high
to prevent surface condensation or even increased humidity on the surface. According to the
calculations, there are no severe corrosion risks in the steel frames in the Finnish climate. The
climate, however, has an important effect on the performance, and the structures should be
designed with regard to climatic conditions.
Keywords
building envelope, steel structures, light-gauge steel, corrosion tests, weather resistance, moisture, surface
condensation, climatic conditions, heat transfer
Activity unit
VTT Building Technology, Building Physics, Building Services and Fire Technology,
Lämpömiehenkuja 3, P.O.Box 1804, FIN–02044 VTT, Finland
ISBN Project number
951–38–5772–7 (soft back edition)
951–38–5773–5 (URL: http://www.inf.vtt.fi/pdf/)
R8SU00655
Date Language Pages Price
December 2000 English 26 p. A
Name of project Commissioned by
VTT Steel Research Programme Rautaruukki Oyj, Outokumpu Polarit Oy,
The Finnish Constructional Steelwork Association,
The National Technology Agency (Tekes),
VTT Steel Research Programme,
The European Coal and Steel Community (ECSC)
Series title and ISSN Sold by
VTT Tiedotteita – Meddelanden – Research Notes
1235–0605 (soft back edition)
1455–0865 (URL: http://www.inf.vtt.fi/pdf/)
VTT Information Service
P.O.Box 2000, FIN–02044 VTT, Finland
Phone internat. +358 9 456 4404
Fax +358 9 456 4374
VTT TIEDOTTEITA – MEDDELANDEN – RESEARCH NOTES
VTT RAKENNUSTEKNIIKKA – VTT BYGGNADSTEKNIK –
VTT BUILDING TECHNOLOGY
1979 Nieminen, Jyri & Kouhia, Ilpo. Hyvin eristetyn loivan katon toimivuus ja vaatimukset. 1999. 38 s. + liitt. 3 s.
1981 Hakkarainen, Tuula (ed.) Smoke gas analysis by Fourier transform infrared spectroscopy. The SAFIR project.
1999. 81 p.
1988 Lahdenperä, Pertti. Ajatuksia ST-urakasta. Suomalaisen suunnittelu ja toteutus -menettelyn kehittäminen
amerikkalaisten oppien pohjalta. 1999. 40 s. + liitt. 2 s.
1990 Keski-Rahkonen, Olavi & Björkman, Jouni. Palotilastoja Suomesta ja ulkomailta toiminnallisten palosäädösten
perusteiksi. 1999. 56 s.
1991 Kokko, Erkki, Ojanen, Tuomo, Salonvaara, Mikael, Hukka, Antti & Viitanen, Hannu. Puurakenteiden
kosteustekninen toiminta. 1999. 160 s.
1994 Leppänen, Pekka, Pulakka, Sakari, Saari, Mikko & Viitanen, Hannu. Life-cycle-cost optimised wooden multi-
storey apartment building. Nordic Wood, Phase 2, Project P-2. Final report. 1999. 73 p.
1997 Jokinen, Petri, Lahtinen, Reima & Lehmus, Eila. Teräsrakenteiden suojaus kaariruiskutetulla sinkki-
pinnoitteella. 1999. 50 s. + liitt. 14 s.
2001 Haakana, Maarit & Soitinaho, Ulla. Kiinteistönhoitohenkilöstön motivointi energiansäästöön. Kokemukset
koulukohteista. 1999. 43 s. + liitt. 14 s.
2002 Andstén, Tauno, Juutilainen, Hemmo, Vaari, Jukka & Weckman, Henry. Test method for actuating and safety
devices of portable fire extinguishers. Nordtest Project No. 1435–99. 1999. 40 p. + app. 25 p.
2003 Vainio, Terttu, Riihimäki, Markku & Mäkelä, Pekka. Rakennuskustannusindeksi 2000. 1999. 70 s. + liitt. 2 s.
2005 Baroudi, Djebar, Kokkala, Matti & Weckman, Henry. Savuilmaisimien toiminta-aikojen laskentaohjelma
PALDET 2.1S. 1999. 37 s. + liitt. 1 s.
2013 Tillander, Kati & Keski-Rahkonen, Olavi. Palokunnan saatavuuden merkitys rakennuksen paloriski-
tarkastelussa. 2000. 213 s. + liitt. 55 s.
2025 Riihimäki, Markku & Lehtinen, Erkki. Talopaketit asuinrakentamisessa. Valmisosien yleisyys toimituksissa.
2000. 44 p.
2027 Hietaniemi, Jukka, Hostikka, Simo, Lindberg, Liisa & Kokkala, Matti. Vyöhykemalliohjelman CFAST-
kelpoisuuden arviointi. 2000. 51 s. + liitt. 14 s.
2028 Kokkala, Matti. Rakennusten paloturvallisuussuunnittelu. Toiminnallinen lähestymistapa. 2000. 63 s. + liitt.
15 s.
2029 Helenius, Antti. Shear strength of clinched connections in light gauge steel. 2000. 40 p. + app. 13 p.
2030 Rantamäki, Jouko, Kääriäinen, Hannu, Tulla, Kauko, Viitanen, Hannu, Kalliokoski, Pentti, Keskikuru, Timo,
Kokotti Helmi & Pasanen, Anna-Liisa. Rakennusten ja rakennusmateriaalien homeet. 2000. 40 s. + liitt. 6 s.
2041 Viirola, Heli & Raivio, Paula. Portlandsementin hydrataatio. 2000. 61 s.
2047 Leivo, Markku. Betonin pakkasenkestävyyden varmistaminen. Osa 2. Laadunvalvonta ja -varmistus. 2000.
13 s. + liitt. 25 s.
2048 Kuosa, Hannele. Älykkäät betonit ja betonirakenteet. 2000. 35 s. + liitt. 9 s.
2049 Lehtinen, Jari. Rakennushankkeen turvallisuusjohtaminen. Korkea rakennuskohde. 2000. 77 s. + liitt. 16 s.
2051 Karhu, Vesa & Loikkanen, Kaisu. Japanese and Chinese construction and facilities management software
markets. Preliminary study. 2000. 58 p. + app. 4 p.
2053 Luoma, Marianna & Pasanen, Pertti. Ilmanvaihtojärjestelmien puhdistus 15 toimistorakennuksessa.
Puhdistuksen ja säädön vaikutus toimistotilojen kanavien puhtauteen, ilmanvaihtuvuuteen, tuloilman laatuun ja
työntekijöiden työoloihin. 2000. 43 s. + liitt. 6 s.
2054 Riihimäki, Markku & Lehtinen, Erkki. Luonnonkiviteollisuuden markkinat. 2000. 57 s. + liitt. 19 s.
2056 Kuosa, Hannele & Vesikari Erkki. Betonin pakkasenkestävyyden varmistaminen. Osa 1. Perusteet ja
käyttöikämitoitus. 2000. 141 s.
2070 Nieminen, Jyri & Salonvaara, Mikael. Hygrothermal performance of light steel-framed walls. 2000. 26 p.
2072 Paiho, Satu, Leskinen, Mia & Mustakallio, Panu. Automaatiojärjestelmän hyödyntäminen energiatietoisen
käytön apuvälineenä. 2000. 63 s.

More Related Content

What's hot

Ultra super critical power plant materials
Ultra super critical power plant materialsUltra super critical power plant materials
Ultra super critical power plant materialsS S Ananthan Ananthan
 
Steel grounding-design-guide-and-application-notes
Steel grounding-design-guide-and-application-notesSteel grounding-design-guide-and-application-notes
Steel grounding-design-guide-and-application-notesNick Wang
 
Wire Arc Additive Manufacturing
Wire Arc Additive ManufacturingWire Arc Additive Manufacturing
Wire Arc Additive ManufacturingBatuhan Özçalık
 
Corrosion control
Corrosion controlCorrosion control
Corrosion controlDuy Vu
 
Vacuum Arc Remelting Furnaces in Midhani
Vacuum Arc Remelting Furnaces in MidhaniVacuum Arc Remelting Furnaces in Midhani
Vacuum Arc Remelting Furnaces in MidhaniAmitkumar Singalwar
 
Hot Hydroforging for Lightweighting Presentation IDE 2015
Hot Hydroforging for Lightweighting Presentation IDE 2015 Hot Hydroforging for Lightweighting Presentation IDE 2015
Hot Hydroforging for Lightweighting Presentation IDE 2015 Fluxtrol Inc.
 
Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...
Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...
Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...IRJET Journal
 
Iaetsd investigation of thermal
Iaetsd investigation of thermalIaetsd investigation of thermal
Iaetsd investigation of thermalIaetsd Iaetsd
 
Effect of thermal barrier coating for the improvement
Effect of thermal barrier coating for the improvementEffect of thermal barrier coating for the improvement
Effect of thermal barrier coating for the improvementeSAT Publishing House
 
THE USE OF 700 C FOR CARBON FREE
THE USE OF 700 C FOR CARBON FREETHE USE OF 700 C FOR CARBON FREE
THE USE OF 700 C FOR CARBON FREERAVI PRAJAPATI
 
Wire Arc Additive Manufacturing
Wire Arc Additive ManufacturingWire Arc Additive Manufacturing
Wire Arc Additive ManufacturingBatuhan Özçalık
 
A Review on Laser Surface Alloying
A Review on Laser Surface AlloyingA Review on Laser Surface Alloying
A Review on Laser Surface AlloyingIRJET Journal
 
Analysis Of Deterministic Arc Model
Analysis Of Deterministic Arc ModelAnalysis Of Deterministic Arc Model
Analysis Of Deterministic Arc Modeldgrabowski
 
Plasma Technology In Metallurgy & Metal Working Industry
Plasma Technology In Metallurgy & Metal Working IndustryPlasma Technology In Metallurgy & Metal Working Industry
Plasma Technology In Metallurgy & Metal Working IndustryRajesh Joshi
 
Presentation on Electric arc
Presentation on Electric arcPresentation on Electric arc
Presentation on Electric arcA. N. M. Jubaer
 
Heat Sink for Underground Pipe Line
Heat Sink for Underground Pipe LineHeat Sink for Underground Pipe Line
Heat Sink for Underground Pipe LineYogeshIJTSRD
 
mahfooz_pulsed electrodeposition technology
mahfooz_pulsed electrodeposition technologymahfooz_pulsed electrodeposition technology
mahfooz_pulsed electrodeposition technologyMahfooz Alam
 

What's hot (20)

Ultra super critical power plant materials
Ultra super critical power plant materialsUltra super critical power plant materials
Ultra super critical power plant materials
 
Subject assignment 2
Subject assignment 2Subject assignment 2
Subject assignment 2
 
SPPVersion9Final
SPPVersion9FinalSPPVersion9Final
SPPVersion9Final
 
Steel grounding-design-guide-and-application-notes
Steel grounding-design-guide-and-application-notesSteel grounding-design-guide-and-application-notes
Steel grounding-design-guide-and-application-notes
 
Wire Arc Additive Manufacturing
Wire Arc Additive ManufacturingWire Arc Additive Manufacturing
Wire Arc Additive Manufacturing
 
Corrosion control
Corrosion controlCorrosion control
Corrosion control
 
Vacuum Arc Remelting Furnaces in Midhani
Vacuum Arc Remelting Furnaces in MidhaniVacuum Arc Remelting Furnaces in Midhani
Vacuum Arc Remelting Furnaces in Midhani
 
Hot Hydroforging for Lightweighting Presentation IDE 2015
Hot Hydroforging for Lightweighting Presentation IDE 2015 Hot Hydroforging for Lightweighting Presentation IDE 2015
Hot Hydroforging for Lightweighting Presentation IDE 2015
 
Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...
Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...
Study and CFD Analysis on Different Test Plate Specimens with Different Nozzl...
 
Iaetsd investigation of thermal
Iaetsd investigation of thermalIaetsd investigation of thermal
Iaetsd investigation of thermal
 
Effect of thermal barrier coating for the improvement
Effect of thermal barrier coating for the improvementEffect of thermal barrier coating for the improvement
Effect of thermal barrier coating for the improvement
 
THE USE OF 700 C FOR CARBON FREE
THE USE OF 700 C FOR CARBON FREETHE USE OF 700 C FOR CARBON FREE
THE USE OF 700 C FOR CARBON FREE
 
Wire Arc Additive Manufacturing
Wire Arc Additive ManufacturingWire Arc Additive Manufacturing
Wire Arc Additive Manufacturing
 
A Review on Laser Surface Alloying
A Review on Laser Surface AlloyingA Review on Laser Surface Alloying
A Review on Laser Surface Alloying
 
Analysis Of Deterministic Arc Model
Analysis Of Deterministic Arc ModelAnalysis Of Deterministic Arc Model
Analysis Of Deterministic Arc Model
 
Plasma Technology In Metallurgy & Metal Working Industry
Plasma Technology In Metallurgy & Metal Working IndustryPlasma Technology In Metallurgy & Metal Working Industry
Plasma Technology In Metallurgy & Metal Working Industry
 
Presentation on Electric arc
Presentation on Electric arcPresentation on Electric arc
Presentation on Electric arc
 
04 main
04 main04 main
04 main
 
Heat Sink for Underground Pipe Line
Heat Sink for Underground Pipe LineHeat Sink for Underground Pipe Line
Heat Sink for Underground Pipe Line
 
mahfooz_pulsed electrodeposition technology
mahfooz_pulsed electrodeposition technologymahfooz_pulsed electrodeposition technology
mahfooz_pulsed electrodeposition technology
 

Similar to Thermoprofile hygrothermal performance tests

Study of effects of heat treatment on the hardness and microstructure of weld...
Study of effects of heat treatment on the hardness and microstructure of weld...Study of effects of heat treatment on the hardness and microstructure of weld...
Study of effects of heat treatment on the hardness and microstructure of weld...Alexander Decker
 
Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...
Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...
Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...IRJET Journal
 
IRJET- Study on Effect of Column Shape on Fire Resistance of CFST Column wi...
IRJET- 	 Study on Effect of Column Shape on Fire Resistance of CFST Column wi...IRJET- 	 Study on Effect of Column Shape on Fire Resistance of CFST Column wi...
IRJET- Study on Effect of Column Shape on Fire Resistance of CFST Column wi...IRJET Journal
 
Development of laboratory scale salt bath furnace
Development of laboratory scale salt bath furnaceDevelopment of laboratory scale salt bath furnace
Development of laboratory scale salt bath furnaceAlexander Decker
 
Design Study on Nuclear Transportation Cask
Design Study on Nuclear Transportation CaskDesign Study on Nuclear Transportation Cask
Design Study on Nuclear Transportation CaskZhi
 
IRJET- Study on the Behaviour of Cold Formed Steel Frames Hollow Section
IRJET-  	  Study on the Behaviour of Cold Formed Steel Frames Hollow SectionIRJET-  	  Study on the Behaviour of Cold Formed Steel Frames Hollow Section
IRJET- Study on the Behaviour of Cold Formed Steel Frames Hollow SectionIRJET Journal
 
MSB01_Architect_s_Guide_2010-08-05.pdf
MSB01_Architect_s_Guide_2010-08-05.pdfMSB01_Architect_s_Guide_2010-08-05.pdf
MSB01_Architect_s_Guide_2010-08-05.pdfSameerSawant61
 
Building Technology I : Project 2 : Construction Solutions
Building Technology I : Project 2 : Construction SolutionsBuilding Technology I : Project 2 : Construction Solutions
Building Technology I : Project 2 : Construction SolutionsJing Fan Koh
 
FIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINT
FIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINTFIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINT
FIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINTIRJET Journal
 
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...IRJET Journal
 
STEEL CONSTRUCTION.pptx
STEEL CONSTRUCTION.pptxSTEEL CONSTRUCTION.pptx
STEEL CONSTRUCTION.pptxINASel2
 
IRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat Slab
IRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat SlabIRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat Slab
IRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat SlabIRJET Journal
 
INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES
INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES  INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES
INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES Anupama Krishnan
 
High Tech Building Materials: ETFE
High Tech Building Materials: ETFEHigh Tech Building Materials: ETFE
High Tech Building Materials: ETFESneha Nagarajan
 
Review on Natural Draft Hyperbolic Cooling Towers
Review on Natural Draft Hyperbolic Cooling TowersReview on Natural Draft Hyperbolic Cooling Towers
Review on Natural Draft Hyperbolic Cooling TowersIRJET Journal
 
Thermal Energy Transfer of Steel Framing
Thermal Energy Transfer of Steel Framing Thermal Energy Transfer of Steel Framing
Thermal Energy Transfer of Steel Framing J. Patrick Lucas
 
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength...
IRJET-  	  Comparative Analysis of High Strength Concrete and Normal Strength...IRJET-  	  Comparative Analysis of High Strength Concrete and Normal Strength...
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength...IRJET Journal
 

Similar to Thermoprofile hygrothermal performance tests (20)

Study of effects of heat treatment on the hardness and microstructure of weld...
Study of effects of heat treatment on the hardness and microstructure of weld...Study of effects of heat treatment on the hardness and microstructure of weld...
Study of effects of heat treatment on the hardness and microstructure of weld...
 
Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...
Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...
Evaluation of Structural Behavior of Structural Steel Joints at Elevated Temp...
 
IRJET- Study on Effect of Column Shape on Fire Resistance of CFST Column wi...
IRJET- 	 Study on Effect of Column Shape on Fire Resistance of CFST Column wi...IRJET- 	 Study on Effect of Column Shape on Fire Resistance of CFST Column wi...
IRJET- Study on Effect of Column Shape on Fire Resistance of CFST Column wi...
 
Development of laboratory scale salt bath furnace
Development of laboratory scale salt bath furnaceDevelopment of laboratory scale salt bath furnace
Development of laboratory scale salt bath furnace
 
Final Document
Final DocumentFinal Document
Final Document
 
Design Study on Nuclear Transportation Cask
Design Study on Nuclear Transportation CaskDesign Study on Nuclear Transportation Cask
Design Study on Nuclear Transportation Cask
 
IRJET- Study on the Behaviour of Cold Formed Steel Frames Hollow Section
IRJET-  	  Study on the Behaviour of Cold Formed Steel Frames Hollow SectionIRJET-  	  Study on the Behaviour of Cold Formed Steel Frames Hollow Section
IRJET- Study on the Behaviour of Cold Formed Steel Frames Hollow Section
 
MSB01_Architect_s_Guide_2010-08-05.pdf
MSB01_Architect_s_Guide_2010-08-05.pdfMSB01_Architect_s_Guide_2010-08-05.pdf
MSB01_Architect_s_Guide_2010-08-05.pdf
 
Building Technology I : Project 2 : Construction Solutions
Building Technology I : Project 2 : Construction SolutionsBuilding Technology I : Project 2 : Construction Solutions
Building Technology I : Project 2 : Construction Solutions
 
FIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINT
FIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINTFIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINT
FIRE RESISTANT ANALYSIS OF RC BEAM COLUMN JOINT
 
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength Con...
 
PROJECT 2: CONSTRUCTION SOLUTIONS
PROJECT 2: CONSTRUCTION SOLUTIONSPROJECT 2: CONSTRUCTION SOLUTIONS
PROJECT 2: CONSTRUCTION SOLUTIONS
 
STEEL CONSTRUCTION.pptx
STEEL CONSTRUCTION.pptxSTEEL CONSTRUCTION.pptx
STEEL CONSTRUCTION.pptx
 
IRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat Slab
IRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat SlabIRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat Slab
IRJET- Effects of Thermal Loads on RCC Conventional Slab and Flat Slab
 
INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES
INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES  INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES
INSTRUCTION HANDBOOK TO ELABORATED CASE STUDIES
 
High Tech Building Materials: ETFE
High Tech Building Materials: ETFEHigh Tech Building Materials: ETFE
High Tech Building Materials: ETFE
 
Review on Natural Draft Hyperbolic Cooling Towers
Review on Natural Draft Hyperbolic Cooling TowersReview on Natural Draft Hyperbolic Cooling Towers
Review on Natural Draft Hyperbolic Cooling Towers
 
Thermal Energy Transfer of Steel Framing
Thermal Energy Transfer of Steel Framing Thermal Energy Transfer of Steel Framing
Thermal Energy Transfer of Steel Framing
 
Marth_Final Report
Marth_Final ReportMarth_Final Report
Marth_Final Report
 
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength...
IRJET-  	  Comparative Analysis of High Strength Concrete and Normal Strength...IRJET-  	  Comparative Analysis of High Strength Concrete and Normal Strength...
IRJET- Comparative Analysis of High Strength Concrete and Normal Strength...
 

More from Matis Velt

Viking passive.pdf
Viking passive.pdfViking passive.pdf
Viking passive.pdfMatis Velt
 
SeiCom catalogue 2023
SeiCom catalogue 2023SeiCom catalogue 2023
SeiCom catalogue 2023Matis Velt
 
The luxury property collections lookbook
The luxury property collections lookbookThe luxury property collections lookbook
The luxury property collections lookbookMatis Velt
 
Everhaus concept
Everhaus conceptEverhaus concept
Everhaus conceptMatis Velt
 
Everhaus modular
Everhaus modularEverhaus modular
Everhaus modularMatis Velt
 
Luxhus Pitch Deck
Luxhus Pitch DeckLuxhus Pitch Deck
Luxhus Pitch DeckMatis Velt
 
Desiree tiny house
Desiree tiny houseDesiree tiny house
Desiree tiny houseMatis Velt
 
Everhaus Tiny house
Everhaus Tiny houseEverhaus Tiny house
Everhaus Tiny houseMatis Velt
 
Thermoprofile presentation Everhaus
Thermoprofile presentation EverhausThermoprofile presentation Everhaus
Thermoprofile presentation EverhausMatis Velt
 
Thermoprofile presentation eng
Thermoprofile presentation engThermoprofile presentation eng
Thermoprofile presentation engMatis Velt
 
Everhaus product guide
Everhaus product guideEverhaus product guide
Everhaus product guideMatis Velt
 
Everhaus catalogue
Everhaus catalogueEverhaus catalogue
Everhaus catalogueMatis Velt
 
Everhaus brochure info
Everhaus brochure infoEverhaus brochure info
Everhaus brochure infoMatis Velt
 

More from Matis Velt (14)

Viking passive.pdf
Viking passive.pdfViking passive.pdf
Viking passive.pdf
 
SeiCom catalogue 2023
SeiCom catalogue 2023SeiCom catalogue 2023
SeiCom catalogue 2023
 
The luxury property collections lookbook
The luxury property collections lookbookThe luxury property collections lookbook
The luxury property collections lookbook
 
Luxhus pitch
Luxhus pitchLuxhus pitch
Luxhus pitch
 
Everhaus concept
Everhaus conceptEverhaus concept
Everhaus concept
 
Everhaus modular
Everhaus modularEverhaus modular
Everhaus modular
 
Luxhus Pitch Deck
Luxhus Pitch DeckLuxhus Pitch Deck
Luxhus Pitch Deck
 
Desiree tiny house
Desiree tiny houseDesiree tiny house
Desiree tiny house
 
Everhaus Tiny house
Everhaus Tiny houseEverhaus Tiny house
Everhaus Tiny house
 
Thermoprofile presentation Everhaus
Thermoprofile presentation EverhausThermoprofile presentation Everhaus
Thermoprofile presentation Everhaus
 
Thermoprofile presentation eng
Thermoprofile presentation engThermoprofile presentation eng
Thermoprofile presentation eng
 
Everhaus product guide
Everhaus product guideEverhaus product guide
Everhaus product guide
 
Everhaus catalogue
Everhaus catalogueEverhaus catalogue
Everhaus catalogue
 
Everhaus brochure info
Everhaus brochure infoEverhaus brochure info
Everhaus brochure info
 

Recently uploaded

9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhidelhimodel235
 
BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...
BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...
BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...ApartmentWala1
 
Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024VickyAulakh1
 
2k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 92055419142k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 9205541914Delhi Call girls
 
Eldeco Dwarka Project In Delhi-brochure.pdf.pdf
Eldeco Dwarka Project In Delhi-brochure.pdf.pdfEldeco Dwarka Project In Delhi-brochure.pdf.pdf
Eldeco Dwarka Project In Delhi-brochure.pdf.pdfkratirudram
 
Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)Delhi Call girls
 
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTurbo Tenant
 
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial VenturesM3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial Venturessheltercareglobal
 
ACE Terra Yamuna Expressway | 8929888700
ACE Terra Yamuna Expressway | 8929888700ACE Terra Yamuna Expressway | 8929888700
ACE Terra Yamuna Expressway | 8929888700Truhomes
 
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdfKohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdfManishSaxena95
 
Parksville 96 Surrey Floor Plans May 2024
Parksville 96 Surrey Floor Plans May 2024Parksville 96 Surrey Floor Plans May 2024
Parksville 96 Surrey Floor Plans May 2024VickyAulakh1
 
Majestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdfMajestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdfBabyrudram
 
Kolte Patil Kharadi Pune E Brochure.pdf
Kolte Patil Kharadi Pune E  Brochure.pdfKolte Patil Kharadi Pune E  Brochure.pdf
Kolte Patil Kharadi Pune E Brochure.pdfabbu831446
 
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort ServiceBDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort ServiceDelhi Call girls
 
David Litt Foreclosure Specialist - Your Partner in Real Estate Success
David Litt Foreclosure Specialist - Your Partner in Real Estate SuccessDavid Litt Foreclosure Specialist - Your Partner in Real Estate Success
David Litt Foreclosure Specialist - Your Partner in Real Estate SuccessDavid Litt
 
Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...
Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...
Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...asmaqueen5
 
Call Girls In Seelampur Delhi ↬8447779280}Seelampur Escorts Service In Delhi...
Call Girls In Seelampur  Delhi ↬8447779280}Seelampur Escorts Service In Delhi...Call Girls In Seelampur  Delhi ↬8447779280}Seelampur Escorts Service In Delhi...
Call Girls In Seelampur Delhi ↬8447779280}Seelampur Escorts Service In Delhi...asmaqueen5
 
BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...
BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...
BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...ApartmentWala1
 
Mahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdfMahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdfBabyrudram
 
Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)
Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)
Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)delhi24hrs1
 

Recently uploaded (20)

9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
9990771857 Call Girls in Dwarka Sector 3 Delhi (Call Girls) Delhi
 
BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...
BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...
BPTP THE AMAARIO For The Royals Of Tomorrow in Sector 37D Gurgaon Dwarka Expr...
 
Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024Greater Vancouver Realtors Statistics Package April 2024
Greater Vancouver Realtors Statistics Package April 2024
 
2k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 92055419142k Shot Call girls Karol Bagh Delhi 9205541914
2k Shot Call girls Karol Bagh Delhi 9205541914
 
Eldeco Dwarka Project In Delhi-brochure.pdf.pdf
Eldeco Dwarka Project In Delhi-brochure.pdf.pdfEldeco Dwarka Project In Delhi-brochure.pdf.pdf
Eldeco Dwarka Project In Delhi-brochure.pdf.pdf
 
Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)
Enjoy Night ≽ 8448380779 ≼ Call Girls In Iffco Chowk (Gurgaon)
 
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports WorkTENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
TENANT SCREENING REPORT SERVICES​ How Tenant Screening Reports Work
 
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial VenturesM3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
M3M The Line Brochure - Premium Investment Opportunity for Commercial Ventures
 
ACE Terra Yamuna Expressway | 8929888700
ACE Terra Yamuna Expressway | 8929888700ACE Terra Yamuna Expressway | 8929888700
ACE Terra Yamuna Expressway | 8929888700
 
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdfKohinoor Hinjewadi Phase 2 Pune  E-Brochure.pdf
Kohinoor Hinjewadi Phase 2 Pune E-Brochure.pdf
 
Parksville 96 Surrey Floor Plans May 2024
Parksville 96 Surrey Floor Plans May 2024Parksville 96 Surrey Floor Plans May 2024
Parksville 96 Surrey Floor Plans May 2024
 
Majestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdfMajestique Viman Nagar Pune Brochure.pdf
Majestique Viman Nagar Pune Brochure.pdf
 
Kolte Patil Kharadi Pune E Brochure.pdf
Kolte Patil Kharadi Pune E  Brochure.pdfKolte Patil Kharadi Pune E  Brochure.pdf
Kolte Patil Kharadi Pune E Brochure.pdf
 
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort ServiceBDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
BDSM⚡Call Girls in Sector 57 Noida Escorts >༒8448380779 Escort Service
 
David Litt Foreclosure Specialist - Your Partner in Real Estate Success
David Litt Foreclosure Specialist - Your Partner in Real Estate SuccessDavid Litt Foreclosure Specialist - Your Partner in Real Estate Success
David Litt Foreclosure Specialist - Your Partner in Real Estate Success
 
Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...
Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...
Call Girls In Krishna Nagar Delhi (Escort)↫8447779280↬@SHOT 1500- NIGHT 5500→...
 
Call Girls In Seelampur Delhi ↬8447779280}Seelampur Escorts Service In Delhi...
Call Girls In Seelampur  Delhi ↬8447779280}Seelampur Escorts Service In Delhi...Call Girls In Seelampur  Delhi ↬8447779280}Seelampur Escorts Service In Delhi...
Call Girls In Seelampur Delhi ↬8447779280}Seelampur Escorts Service In Delhi...
 
BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...
BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...
BPTP THE AMAARIO Luxury Project Invest Like Royalty in Sector 37D Gurgaon Dwa...
 
Mahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdfMahindra Happinest Tathawade Pune Brochure.pdf
Mahindra Happinest Tathawade Pune Brochure.pdf
 
Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)
Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)
Cheap Rate ✨➥9711108085▻✨Call Girls In Malviya Nagar(Delhi)
 

Thermoprofile hygrothermal performance tests

  • 1. VTTTIEDOTTEITA 2 0 7 0 Jyri Nieminen & Mikael Salonvaara Hygrothermal performance of light steel-framed walls V T T R E S E A R C H N O T E S TECHNICAL RESEARCH CENTRE OF FINLAND ESPOO 2000
  • 2. VTT TIEDOTTEITA – MEDDELANDEN – RESEARCH NOTES 2070 TECHNICAL RESEARCH CENTRE OF FINLAND ESPOO 2000 Hygrothermal performance of light steel-framed walls Jyri Nieminen, Mikael Salonvaara VTT Building Technology
  • 3. ISBN 951–38–5772–7 (soft back ed.) ISSN 1235–0605 (soft back ed.) ISBN 951–38–5773–5 (URL: http://www.inf.vtt.fi/pdf/) ISSN 1455–0865 (URL: http://www.inf.vtt.fi/pdf/) Copyright © Valtion teknillinen tutkimuskeskus (VTT) 2000 JULKAISIJA – UTGIVARE – PUBLISHER Valtion teknillinen tutkimuskeskus (VTT), Vuorimiehentie 5, PL 2000, 02044 VTT puh. vaihde (09) 4561, faksi (09) 456 4374 Statens tekniska forskningscentral (VTT), Bergsmansvägen 5, PB 2000, 02044 VTT tel. växel (09) 4561, fax (09) 456 4374 Technical Research Centre of Finland (VTT), Vuorimiehentie 5, P.O.Box 2000, FIN–02044 VTT, Finland phone internat. + 358 9 4561, fax + 358 9 456 4374 VTT Rakennustekniikka, Rakennusfysiikka, talo- ja palotekniikka, Lämpömiehenkuja 3, PL 1804, 02044 VTT puh. vaihde (09) 4561, faksi (09) 455 2408 VTT Byggnadsteknik, Byggnadsfysik, hus- och brandteknik, Värmemansgränden 3, PB 1804, 02044 VTT tel. växel (09) 4561, fax (09) 455 2408, (09) 456 4709 VTT Building Technology, Building Physics, Building Services and Fire Technology, Lämpömiehenkuja 3, P.O.Box 1804, FIN–02044 VTT, Finland phone internat. + 358 9 4561, fax + 358 9 455 2408, 358 9 456 4709 Technical editing Leena Ukskoski Otamedia Oy, Espoo 2001
  • 4. 3 Nieminen, Jyri & Salonvaara, Mikael. Hygrothermal performance of light steel-framed walls. Espoo 2000. Technical Research Centre of Finland, VTT Tiedotteita – Meddelanden – Research Notes 2070. 26 p. Keywords building envelope, steel structures, light-gauge steel, corrosion tests, weather resistance, moisture, surface condensation, climatic conditions, heat transfer Abstract Hygrothermal performance of a new light-gauge steel framed building envelope system has been analyzed using 3-D thermal simulations, 2-D combined heat, air and moisture transfer simulations, laboratory testing in a calibrated and guarded hot box (ISO 8990), weather resistance tests for full-sized structures, corrosion tests and field measurements at experimental buildings in Ylöjärvi, Central Finland. The results show that a modern steel wall structure based on perforated steel profiles performs satisfactorily in the cold climate of Finland. The perforations reduce heat loss along the web of the profile significantly. The field measurements show that no condensation has occurred in the frame system. Temperature measurements and infrared surveys in demonstration buildings show that surface temperatures are sufficiently high to prevent surface condensation or even increased humidity on the surface. According to the calculations, there are no severe corrosion risks in the steel frames in the Finnish climate. The climate, however, has an important effect on the performance, and the structures should be designed with regard to climatic conditions.
  • 5. 4 Preface New building envelope systems based on light steel framing have been developed and studied during the last 10–15 years in Finland. The focus of the research has been in the high performance exterior wall systems. Good thermal insulation properties, durability and minimised corrosion and moisture risks have been the key issues. A number of research projects have been carried out during 1989–2000. This report gives an overview of the most important results of these studies. The research work has been funded by Rautaruukki Oyj, Outokumpu Polarit Oy, The Finnish Constructional Steelwork Association, The National Technology Agency (Tekes), VTT Steel Research Programme and The European Coal and Steel Community (ECSC).
  • 6. 5 Contents Abstract............................................................................................................................. 3 Preface............................................................................................................................... 4 1. Introduction................................................................................................................. 7 2. Thermal performance of light steel structures............................................................. 8 2.1 Thermal bridges................................................................................................. 8 2.2 Comparision of thermal analysis tools............................................................. 12 2.3 Airtightness of steel buildings ......................................................................... 14 2.4 Temperature distribution in light gauge steel walls......................................... 14 3. Durability of light steel framing................................................................................ 17 3.1 Moisture variation in steel-framed walls ......................................................... 17 3.2 Corrosion risks caused by materials in contact with light gauge steel ............ 17 3.3 Hygrothermal simulations ............................................................................... 19 4. Summary ................................................................................................................... 23 References....................................................................................................................... 25
  • 7. 6
  • 8. 7 1. Introduction New building enevlope systems based on light steel framing have been developed during the last 10–15 years. The focus has been in commercial and public buildings, but the use of steel structures in housing has also increased. Service life of buildings and building components has become more and more important feature in marketing of building products. When new building systems are introduced, the question of the hygrothermal performance will be inevitably raised. The purpose of the research has been to evaluate the hygrothermal performance and durability of a light steel frame system used as an exterior wall structure in various types of buildings. A number of research projects have been completed to show real, tested and verified results on the questions related to performance: • Development of light prefabricated steel framed facade units: Development and hygrothermal testing of new light gauge steel frame systems /15/. • Development 3-D heat transfer tools for steel structures: numerical 3-D tool for calculation of temperature and heat flow distribution in steel structures /10/. • Service life design of steel structures: field surveys of steel buildings, long-term corrosion tests /6/. • VTT Steel research programme’s /16/ project Performance of steel buildings: development hygrothermal calculation tools, measuring devices and methods. • ECSC (European Coal and Steel Coalition) Mega5-project Application of steel in urban habitats: Low-energy steel house for a cold climate: development, testing and demonstration of a new steel frame system, concept for energy-efficient residential housing based on steel frame structures /7, 11/. A new concept for steel construction based on perforated light gauge steel profiles was developed and demonstrated in Ylöjärvi, Central Finland. The aim of the ECSC funded Mega5 project /7/ were to ensure the performance and suitability of a light-gauge steel- framed house for use in a cold climate. The project included comprehensive research on the structural and hygrothermal performance of the structures as well as research on the energy performance and environmental impacts of steel buildings. The hygrothermal performance of a number of structures have been assessed using 3- dimensional heat flow calculations and laboratory measurements with full-size structures in a calibrated and guarded hot box according to ISO 8990 standard and laboratory weather resistance tests. Also, the thermal performance of the structures was investigated in the field monitoring (1996–2000) at the Ylöjärvi steel houses. The monitoring project included temperature measurements from various locations in the building envelopes, infrared surveys of the buildings, blower door tests to assess the air tightness of the buildings and moisture monitoring from the frame structure. In the VTT Steel research Programme’s /16/ research project ‘Performance of steel buildings’ the accuracy of various measuring methods and computerized calculation tools have been tested. The focus of the research has been on thermal measurements and calculations.
  • 9. 8 2. Thermal performance of light steel structures 2.1 Thermal bridges Just like all frame materials in an insulated structure, a steel member is a thermal bridge. But, since thermal conductivity of steel is high, severe bridge effects are possible. The effect of thermal bridges has been reduced by three methods: • using double frame systems • using exterior insulation systems • using perforated (or slotted) the steel profiles. Light-gauge steel-framed structures based on double frame system (horizontal and vertical frame, Figure 1) have been used as external walls of office and public buildings. The distance between the frames in both directions is typically 0.6 meters, and thermal insulation is installed into the cavities between the frames. Double frame system improves thermal quality of a wall by 20–25 % compared to single frame cavity insulated wall, Table 1. Exterior insulation systems reduce thermal bridging in a wall. The effect depends on the thermal properties of the insulation system. Exterior insulation is very advantageous in terms of moisture behavior, since the frame temperatures increase which in turn reduces moisture risks in the frame. Perforated webs in a light-gauge steel frame give two advantages for the structure. Due to the perforations, the thermal properties of the structure are improved. This, in turn, makes it feasible to use the structure as a single-frame wall system. A light-gauge steel frame with perforated web is termed a thermoprofile, see Figures 2 and 3. U-shaped thermoprofiles are used in prefabricated facade units for high-rise buildings. The load bearing walls of detached and row houses are composed of vertical C-shaped thermoprofiles. The material thickness of the profiles is typically 1.0–1.5 mm. The effect of the perforations or slots in a thermoprofile can be taken into account by introducing an equivalent thermal conductivity for the non-perforated material. Heat transfer in the web can be assumed to be pure heat conduction. The equivalent thermal conductivity can be defined by comparing conduction in the perforated case and in the non-perforated case. The equivalent thermal conductivity depends on the perforation system including the shape and dimensions of perforations, the dimensions of the steel necks between the perforations and the thermal conductivity of the material in the perforations, see Figure 4.
  • 10. 9 The reduced thermal bridging has a considerable effect on reducing the heat conduction in the thermoprofile relative to solid steel (Figure 5). The perforations perform as thermal breaks for the steel member reducing the heat conduction along the web by 70– 80%, Figure 6. According to studies carried out in Finland and Sweden /1, 8, 9/, the equivalent thermal conductivity of a thermoprofile can be 5–10 W/m2 K. Figure 1. Single and double framed wall structures used as exterior wall in Finland. Table 1. Relative thermal resistance of insulated steel framed wall compared to one- dimensional resistance of thermal insulation of corresponding thickness. All insulation materials mineral wool, thermal conductivity 0.037 W/mK. Wall structure Relative thermal resistance, % Mineral wool insulation 175 mm 100 Single frame wall (figure 1) - vertical frame C 175–50–1.2 45 Double frame wall n vertical frame C 125–50–1.2 n horizontal frame Z 50–50–1.0 65 Single frame wall + exterior insulation 125+50 mm - vertical frame C 125–50–1.2 75 Single frame wall, thermoprofiles - vertical frame C 175–50–1.2 80
  • 11. 10 Figure 2. Thermoprofile alternatives. Profiles in the top row were used in Villa 2000 built for the Tuusula housing fair 2000 (left), and in Ylöjärvi steel houses built for the Ylöjärvi housing fair 1996 (right). Other two exmples were manufactured for testing purposes.
  • 12. 11 Equivalent thermal conductivity 5,5 – 7,5 W/m2 K Equivalent thermal conductivity 5,5 – 7,5 W/m2 K Equivalent thermal conductivity 5,0 – 7,0 W/m2 K Figure 3. Perforation alternatives of a thermoprofile. Equivalent thermal conductivity takes into account the perforations filled with insulation material. Equivalent thermal conductivity depends on the properties of thermal insulation, the dimensions of the perforations and the dimensions of the solid steel between the perforations. 0 5 10 15 20 25 30 35 0 1 2 3 4 5 6 THERMAL CONDUCTIVITY OF INSULATION [W/mK] - + HEAT CONDUCTION Figure 4. The effect of thermal insulation into the equivalent thermal conductivity of the typical Finnish thermoprofile /12/. 0 10 20 30 40 50 60 THERMALCONDUCTIVITY[W/mK] ZINC-COATEDSTEEL STAINLESSSTEEL THERMOPROFILE CONCRETE BRICK WOOD Figure 5. Thermal conductivity of various building materials used in load-bearing structures. Equivalent thermal conductivity for the thermoprofile.
  • 13. 12 0,15 0,2 0,25 0,3 0,35 0,4 0,45 0,5 0,55 125 150 175 200 225 250 275 INSULATION THICKNESS [mm] U-VALUE[W/m2K] 2,0 mm 1,5 mm 1,2 mm 2,0 mm 1,5 mm 1,2 mm 1,0 mm 45 mm STEEL FRAME C - 150…250 - 1,2…2,0 THERMO-PROFILE C - 150…250 - 1,2…1,5 WOODEN FRAME 45 * 150…250 THERMO-PROFILE 1,2 mm: MEASUREMENT: ISO8990 Figure 6. Calculated values of thermal transmittance for steel-framed and wood-framed walls /9/. The thermal benefit of the perforations in a steel member of a single frame structure is 40-50% depending on the insulation thickness of the wall. 2.2 Comparision of thermal analysis tools Steel structures are typically 3-dimensional structures. Thermal analysis of these structures is complicated, since numerical methods for 3-dimensional calculations are usually required. However, single frame structures can be analysed using 2-dimensional calculations even in the case where the web of a steel profile is perforataed, using equivalent thermal conductivity as a material property for the steel member. To facilitate the accuracy of calculational methods in comparision to measurements, a series of laboratory tests in calibrated and guarded hot box apparatus (ISO 8990, /3/) was carried out. Further more, the suitability of the heat flow method according to DIN 52611 standard /2/ for measurement of thermal transmittance was tested. The results show that the agreement between calculated and measured (ISO 8990) results is rather good, Table 2. Although only a few structures were tested, the heat flow method according to DIN 52611 shows too high values compared to other analysis methods.
  • 14. 13 Table 2. Comparision of the thermal analysis tools for assessment of thermal transmittance (U-value) of light steel framed walls. Measured values according to ISO 8990 and DIN 52611 standards and results from 2- and 3-dimensional simulations. Wall type Structure layers from inside U-value [W/m2 K] Gypsum board 13 mm PE film vapor barrier Steel frame a) TC 175–50–1,2 mm or b) C 175–50–1,2 mm + mineral wool insulation Gypsum board wind proofing 9 mm a) ISO 8990: 0,263 3-D simulation: 0,257 2-D simulation: 0,257*) b) 3-D simulation: 0,435 2-D simulation: 0,435 *) equivalent thermal conductivity 7,3 W/mK Gypsum board 13 mm PE film vapor barrier Steel frame TC 175–50–1,2 mm + mineral wool insulation Gypsum board wind proofing 9 mm Wind proof rigid mineral wool 45 mm ISO 8990: 0,188 3-D simulation: 0,190 2-D simulation: 0,190 *) *) equivalent thermal conductivity 7,3 W/mK Gypsum board 13 mm PE film vapor barrier Steel frame TU 150–50–1,0 mm + mineral wool insulation Gypsum board wind proofing 9 mm ISO 8990: 0,300 DIN 52611: 0,350 3-D simulation: 0,292 2-D simulation: 0,290*) *) equivalent thermal conductivity 5,5 W/mK Gypsum board 13 mm PE film vapor barrier Stailess steel frame U 150–50–1,0 mm + mineral wool insulation Gypsum board wind proofing 9 mm ISO 8990: - DIN 52611: 0,375 3-D simulation: 0,340 2-D simulation: 0,340 Gypsum board 13 mm PE film vapor barrier Steel frame U 50–50–1,0 mm + mineral wool insulation Steel frame U 125–50–1,0 mm + mineral wool insulation a) air gap + over-clad steel façade b) no façade a)ISO 8990: 0,281 3-D simulation: 0,282 b) DIN 52611: 0,345*) 3-D simulation: 0,321*) Gypsum board 13 mm PE film vapor barrier Steel frame U 150–50–2,0 mm + mineral wool insulation Steel frame TU 100–50–1,0 + mineral wool insulation Gypsum board wind proofing 9 mm ISO 8990: DIN 52611: 0,225 3-D simulation: 0,214 3-D simulation: 0,210*) *) equivalent thermal conductivity 16 W/mK TC = C-shaped perforated steel profile (thermoprofile) TU = U-shaped perforated steel profile, U = U–shaped steel profile
  • 15. 14 2.3 Airtightness of steel buildings Air tightness of steel building has been tested only in 4 cases. Table 3 shows results from measured cases and reference information from typical Finnish buildings. Table 3. Airtightness of steel houses and typical Finnish buildings. Building type Air leakage rate at 50 Pa, air changes per hour Prefabricated steel houses (row houses) 1,9–2,5 Site built steel house (row house) 3 Site built wooden detached houses 3–4 Prefabricated wooden detached houses 2–4 Prefabricated wooden row houses 3–5 Massive wooden houses (log houses) 7–15 Concrete buildings 1–4 Low-energy detached houses 0,8–2 The locations of air leaks in the steel houses were searched using an infrared camera. Insufficient sealing of electrical and ventilation installations leading through the air/vapor barrier of the envelope caused the most of the air leaks. These defects were found systematically in all of the buildings. 2.4 Temperature distribution in light gauge steel walls Temperature distributions in the single frame structures have been measured both in a series of full-scale laboratory weather tests and in the structures of Ylöjärvi steel houses. The temperatures on inner wall surface are sufficiently high to prevent ghosting, surface condensation or even relative humidity high enough to increase the risk of mold growth on the wall surface, Figures 7 and 8. Temperature on the inner surface of the wall on top of the frame is 1–2 °C lower than the temperature between the frames. The temperature of the outer flange of the steel frame depend on the thermal properties of the wall outside the frame, Figure 9. The outer flange of the profile is considerably warmer than outdoor air temperature due to heat conduction from the interior along the web of the steel profile. Even though the perforations in a thermoprofile reduce heat conduction along the frame, the residual conduction increases temperatures in the outer parts of the frame, thus reducing the condensation risk and increasing the drying potential in case of condensation. The use of exterior water vapor permeable insulation as in the low-energy wall further improves the hygrothermal performance of the wall.
  • 16. 15 >24,9°C <15,0°C 16,0 18,0 20,0 22,0 24,0 Figure 7. Infrared image of a steel wall. -40 -30 -20 -10 0 10 20 30 0 2 4 6 8 10 12 14 16 18 20 Test time [days] INDOORS THERMO-PROFILE STEEL PROFILE OUTDOORS Figure 8. Surface temperatures of a light steel-framed wall according to a laboratory weather test.
  • 17. 16 -20 -15 -10 -5 0 5 10 0 0,5 1 1,5 2 2,5 THERMAL RESISTANCE OUTSIDE THE FRAME [m 2 k/W] TEMPERATURE[ o C] GYPSUM BOARD 9 mm WIND PROOF MINERAL WOOL 50 mm WIND PROOF MINERAL WOOL 100 mm OUT: -20 o C IN: +20o C Figure 9. The effect of thermal properties of wind proofing (see Figure 1) on the temperature of outer parts of the frame /12/.
  • 18. 17 3. Durability of light steel framing 3.1 Moisture variation in steel-framed walls The corrosion of a metal depend on the micro climate on the surface of a component. Continuous corrosion is possible, if relative humidity on the metal surface exceeds 80% at the same time as temperature is above 0°C (ISO 9223, /4/). Figure 10 shows the monthly maximum values of relative humidity of eight measuring points in the outer flange of the steel profiles measured in the Ylöjärvi steel houses. The results show that relative humidity in wall 1 has exceeded 80%, but no condensation has occurred. The humidity in wall 2 has not exceeded 90%. 40 50 60 70 80 90 100 MONTH 1996 - 1999 WALL1 1996 - 1997 WALL2 1996 - 1997 WALL1 MAXIMUM 1996 - 1999 WALL2 MAXIMUM 1996 - 1999 WALL1 WALL2 MEASUREMENTS - + 8 10 12 2 4 6 8 Figure 10. Monthly maximum of relative humidity in the external walls of the Ylöjärvi steel buildings. Measurements on the outer flange of the steel members. 3.2 Corrosion risks caused by materials in contact with light gauge steel Corrosion risks caused by other building materials in contact with steel are studied in an on-going long-term laboratory test. Insulated steel frames are placed in different climates to see the effect of material and air humidity on corrosion. The materials being studied are:
  • 19. 18 • cellulose fiber insulation • glass wool insulation • rock wool insulation • impregnated wood. The laboratory test has been going on for about 4 years (35000 hours of time of wetness). Test conditions are given in Figure 11. The results show that the cellulose insulation and impregnated wood promotes zinc corrosion in humid conditions, but no corrosion products from steel were detected in any of the test pieces (Figure 12). There are no signs of zinc corrosion in the test pieces insulated with mineral wool products. In the case with continuous condensation, edge corrosion of steel was found in all the specimens. The fire retardant chemicals (borax and boric acid) of the cellulose fiber insulation were not stagnant. The chemicals re-crystallized on the steel surface, which caused stronger edge corrosion in the test specimens insulated with cellulose fiber insulation compared to other specimens. Figure 11. Test climates in corrosion tests. Normal indoor conditions are being used as reference (top). Corrosion tests are carried out in humid air (middle) and in conditions where condensation occurs continuously (bottom).
  • 20. 19 a) Glass wool: no corrosion. b) Rock wool: no corrosion. c) Cellulose fibre: zinc corrosion d) Impregnated wood: zinc and steel corrosion. Figure 12. Long-term corrosion test with steel members in contact with other materials. Test conditions +23°C and 85% relative humidity. Test time 35 000 hours. 3.3 Hygrothermal simulations The hours of wetness were also calculated for two wall types depicted in Figure 13 using the 2-D heat, air and moisture transfer simulation program LATENITE /5, 13/: • Case A: the wall shown in Figure 6 on the left without exterior insulation and • Case B: the wall shown in Figure 6 on the right, like case A except for an additional layer of exterior insulation of 50 mm rigid wind proof mineral wool. The hourly climates of Helsinki, Finland and St. Hubert, Belgium were used as a starting point. The orientation of the walls was north which is considered to be the worst orientation in terms of hygrothermal performance due to low solar radiation absorption. Wind-driven rain was not taken into account in the simulations and the walls were assumed to have a cladding with good cavity ventilation behind the cladding. The initial conditions of the material layers were +20°C and 50% relative humidity. The indoor air conditions were:
  • 21. 20 • temperature +22°C or outdoor air temperature if higher than +22°C • indoor air moisture content xin was outdoor air moisture content xout + 3 g/kg, but limited to 30% ≤ relative humidity ≤ 80%. The simulations were carried out for a two-year period starting September 1. The accumulated time of wetness for the two-year period in different parts of the wall structures is shown in Figures 14 and 15 (wall with no exterior insulation) and in Figures 16 and 17 (wall with exterior insulation). The results are valid on condition that 1) the vapor retarder in the warm side of the wall performs as intended, 2) there is no high initial moisture content in the wall and 3) the wall system has been designed and constructed to avoid moisture leaks into the wall (e.g., wind-driven rain). Gypsum board 13 mm PE-film 0,2 mm Thermoprofile TC 175–50–1,2 mm + insulation 175 mm Gypsum board wind proofing 9 mm Ventilated air gap 22 mm Wooden facade Gypsum board 13 mm PE-film 0,2 mm Thermoprofile TC 175–50–1,2 mm + insulation 175 mm Gypsum board wind proofing 9 mm Wind proof rigid mineral wool 50 mm Ventilated air gap 22 mm Wooden facade Figure 13. Illustration of the structure with perforated light gauge steel frame without and with exterior insulation. The results show, that the durability of the walls depends mainly on the outdoor climate and the hygrothermal properties of the wind proofing attached on the outside of the profiles. The hygroscopicity of the gypsum board is fairly low, but when moistened by the outdoor air, it dries out rather slowly. This phenomenon increases the time of wetness on the outer surface of the outer flange of a profile.
  • 22. 21 0.00 0.05 0.10 0.15 0.20 0.25 Distance from exterior surface, m 0.25 0.30 0.35 0.40 Width,m 1000 6000 IWET 6000 5000 4000 3000 2000 1000 Week # 104 Helsinki Figure 14. Contour plot of the accumulated time of wetness in the layers of the steel frame wall without exterior insulation. Exterior conditions: Helsinki weather data. Length of the simulated period is 2 years (104 weeks). Arrow shows the location of the highest contour value /14/. 0.00 0.05 0.10 0.15 0.20 0.25 Distance from exterior surface, m 0.25 0.30 0.35 0.40 Width,m 6000 1000 IWET 6000 5000 4000 3000 2000 1000 Week # 104 Saint-Hubert Figure 15. Contour plot of the accumulated time of wetness in the layers of the steel frame wall without exterior insulation. Exterior conditions: Saint Hubert weather data. Length of the simulated period is 2 years (104 weeks) /14/.
  • 23. 22 0.00 0.05 0.10 0.15 0.20 0.25 Distance from exterior surface, m 0.25 0.30 0.35 0.40 Width,m 1000 5000 IWET 6000 5000 4000 3000 2000 1000 Week # 104 Helsinki Figure 16. Contour plot of the accumulated time of wetness in the layers of the steel frame wall with 50-mm exterior insulation. Exterior conditions: Helsinki weather data. Length of the simulated period is 2 years (104 weeks) /14/. 0.00 0.05 0.10 0.15 0.20 0.25 Distance from exterior surface, m 0.25 0.30 0.35 0.40 Width,m 1000 6000 IWET 6000 5000 4000 3000 2000 1000 Week # 104 Saint-Hubert Figure 17. Contour plot of the accumulated time of wetness in the layers of the steel frame wall with 50 mm exterior insulation. Exterior conditions: Saint Hubert weather data. Length of the simulated period is 2 years (104 weeks) /14/.
  • 24. 23 4. Summary Irrespective of the materials from which frame structures are made, they form thermal bridges to varying degrees across the thermal insulation layer. Thermal conductivity of steel is high. A steel frame in a light-gauge construction extending uninterrupted across the thermal insulation layer has a considerable effect on the thermal performance of the structure. The development of thermal assessment tools has helped for the rapid development of well insulated light-gauge single framed steel structures introducing perforated webs of a steel member as thermal breaks in the structure. Due to the perforations, the thermal properties of the structure are improved. The analysis carried out shows that the new application of perforated light gauge steel frames fulfills the requirements set for performance and durability in a cold climate of Finland. If adequately designed and constructed, there are no major moisture or corrosion risks involved with the structures. The long-term laboratory test and the field survey suggest, that a steel frame insulated with mineral wool has a very good corrosion resistance and thus a long service life. The performance of an insulated structure depends on the performance of different material layers together as a structure. Connection of gypsum board windproofing to steel frame may reduce the corrosion resistance of the zinc layer by the slow humidity variations due to hygrothermal properties of gypsum board with cardboard surfaces. In moist conditions, cellulose fibre insulation and impregnated wood form alcalinous environment, and thus increase the zinc corrosion rate. However, proper design and installation may avoid the risks. According to the calculation results and field measurements at Ylöjärvi steel houses, the properties of the wind proofing material and the façade structure have an important effect on the overall performance of the structure. By increasing the thermal resistance of the wind proofing material the durability risk of corrosion due to exterior or interior moisture loading can be totally neglected. Water vapor permeable and windproof exterior insulation system increases the drying potential of a structure. The service life of the structure can be estimated using the standard ISO 9223 Corrosion of Metals. The corrosion is dependent on the time of wetness hours. With regard to all the results from various research projects, the time of wetness hours in the most critical point of the structure are between 0 and 2600 in the climate of Helsinki and 0–6100 in the climate of St. Hubert depending on the composition of the structure. The corrosion classification of the zinc layer is C1 or C2 (ISO 9223), where the service life of the zinc layer is estimated to be from 40 years to more than 100 years. In the class C1, the linear corrosion speed of zinc is less than 0,05 µm and, in the class C2, less than 0,5 µm a
  • 25. 24 year. If the thermal and hygrothermal effects of facade claddings are taken into account, a reduced number of time of wetness hours can be expected, and thus a longer service life for the zinc layers.
  • 26. 25 References 1. Blomberg, T. Heat conduction in two and three dimensionss. Computer modeling of building physics applications. Lund 1996. Lund University. Report TVBH-1008. 2. DIN 52611. 1991. Teil 1. Wärmeschutztechnische Prüfungen; Bestimmung des Wärmedurclasswiderstandes von Bauteilen. Prüfung im Laboratorium. Deutche Institutt für Normierung. 3. ISO 8990. International standard 1994. Thermal insulation. Determination of steady-state thermal transmission properties. Calibrated and guarded hot box. International Organization for Standardization. 4. ISO 9223. International standard 1992. Corrosion of metals and alloys. Corrosivity of atmospheres. Classification. International Organization for Standardization. 5. Karagioziz, A., Salonvaara, M. and Kumaran, K. 1994. LATENITE, Hygrothermal material database, IEA Annex 24. International Energy Agency IEA Report TI-CA- 94/04. 6. Leino, T., Häkkä-Rönnholm, E., Nieminen, J., Koukkari, H., Hieta, J., Vesikari, E. and Törnqvist, J. 1998. Teräsrakenteiden käyttöikäsuunnittelu. Service life design of steel structures. VTT Research Notes 1937. 119 p. + app. 11 p. (In Finnish). 7. Low-energy steel house for a cold climate. ECSC project application of steel in urban habitats. Project n:o 7210-SA/902 - 95 - F6.1. Final Report. Rautaruukki Oy 1998. 8. Mao, G. 1997. Thermal bridges. Efficient models for energy analysis in buildings. Dissertation. Division of Building Technology, Department of Building Sciences, Kungliga Tekniska Högskolan, Stockholm. Bulletin No 173. ISSN 0346-5918. 9. Nieminen, J. 1997. New well insulated light-gauge steel framed wall structure. Proceedings of the 5th International Conference Modern Building Materials, Structures and Techniques. Vilnius, Lithuania, May 24–26, 1997. Vilnius Geminida Technical University. 10. Nieminen, J., Kouhia I., Johanneson, G. and Mao, G. 1995. Design and thermal performance of insulated sheet metal structures. Proceedings of the Nordic Steel Construction Conference’95. Malmö, Sweden, June 19–21, 1995.
  • 27. 26 11. Nieminen, J., Saari, M., Salmi, P. and Tattari, K. 1997. Low energy steel house for a cold climate. Proceedings of the International Conference Cold Climate HVAC'97. Reykjavik, Iceland May 1–2, 1997. Iceland Heating, Ventilating and Sanitary Association ICEVAC. 12. Nieminen, J. and Salonvaara, M. 1999. Long-term performance of light-gauge steel- framed envelope structures. Proceedings of the Fourth International Conference on Steel and Aluminium Structures ICSAS’99. Elsevier Science ltd. ISBN 0-08- 043014-7. 13. Salonvaara, M. and Karagiozis, A. 1994. Moisture transport in building envelopes using an approximate factorization solution method. In: Proceedings of the Second Annual Conference of the CFD Society of Canada Ed. by James J. Gottlieb and C. Ross Ethier. Toronto, June 1–3, 1994. 14. Salonvaara, M. and Nieminen, J. 1998. Hygrothermal performance of a new light- gauge steel-framed envelope system. Journal of Thermal Environment and Building Science (22) 1998. 15. Teräsrunkoisen julkisivuelementin suunnitteluohje. 1993. Teräsrakenneyhdistys r.y. TRY. ISBN 952-9683-04-9 16. VTT Steel Research Programme. VTT Building Technology. In print.
  • 28. Published by Vuorimiehentie 5, P.O.Box 2000, FIN–02044 VTT, Finland Phone internat. +358 9 4561 Fax +358 9 456 4374 Series title, number and report code of publication VTT Research Notes 2070 VTT–TIED–2070 Author(s) Nieminen, Jyri & Salonvaara, Mikael Title Hygrothermal performance of light steel-framed walls Abstract Hygrothermal performance of a new light-gauge steel framed building envelope system has been analyzed using 3-D thermal simulations, 2-D combined heat, air and moisture transfer simulations, laboratory testing in a calibrated and guarded hot box (ISO 8990), weather resistance tests for full-sized structures, corrosion tests and field measurements at experimental buildings in Ylöjärvi, Central Finland. The results show that a modern steel wall structure based on perforated steel profiles performs satisfactorily in the cold climate of Finland. The perforations reduce heat loss along the web of the profile significantly. The field measurements show that no condensation has occurred in the frame system. Temperature measurements and infrared surveys in demonstration buildings show that surface temperatures are sufficiently high to prevent surface condensation or even increased humidity on the surface. According to the calculations, there are no severe corrosion risks in the steel frames in the Finnish climate. The climate, however, has an important effect on the performance, and the structures should be designed with regard to climatic conditions. Keywords building envelope, steel structures, light-gauge steel, corrosion tests, weather resistance, moisture, surface condensation, climatic conditions, heat transfer Activity unit VTT Building Technology, Building Physics, Building Services and Fire Technology, Lämpömiehenkuja 3, P.O.Box 1804, FIN–02044 VTT, Finland ISBN Project number 951–38–5772–7 (soft back edition) 951–38–5773–5 (URL: http://www.inf.vtt.fi/pdf/) R8SU00655 Date Language Pages Price December 2000 English 26 p. A Name of project Commissioned by VTT Steel Research Programme Rautaruukki Oyj, Outokumpu Polarit Oy, The Finnish Constructional Steelwork Association, The National Technology Agency (Tekes), VTT Steel Research Programme, The European Coal and Steel Community (ECSC) Series title and ISSN Sold by VTT Tiedotteita – Meddelanden – Research Notes 1235–0605 (soft back edition) 1455–0865 (URL: http://www.inf.vtt.fi/pdf/) VTT Information Service P.O.Box 2000, FIN–02044 VTT, Finland Phone internat. +358 9 456 4404 Fax +358 9 456 4374
  • 29. VTT TIEDOTTEITA – MEDDELANDEN – RESEARCH NOTES VTT RAKENNUSTEKNIIKKA – VTT BYGGNADSTEKNIK – VTT BUILDING TECHNOLOGY 1979 Nieminen, Jyri & Kouhia, Ilpo. Hyvin eristetyn loivan katon toimivuus ja vaatimukset. 1999. 38 s. + liitt. 3 s. 1981 Hakkarainen, Tuula (ed.) Smoke gas analysis by Fourier transform infrared spectroscopy. The SAFIR project. 1999. 81 p. 1988 Lahdenperä, Pertti. Ajatuksia ST-urakasta. Suomalaisen suunnittelu ja toteutus -menettelyn kehittäminen amerikkalaisten oppien pohjalta. 1999. 40 s. + liitt. 2 s. 1990 Keski-Rahkonen, Olavi & Björkman, Jouni. Palotilastoja Suomesta ja ulkomailta toiminnallisten palosäädösten perusteiksi. 1999. 56 s. 1991 Kokko, Erkki, Ojanen, Tuomo, Salonvaara, Mikael, Hukka, Antti & Viitanen, Hannu. Puurakenteiden kosteustekninen toiminta. 1999. 160 s. 1994 Leppänen, Pekka, Pulakka, Sakari, Saari, Mikko & Viitanen, Hannu. Life-cycle-cost optimised wooden multi- storey apartment building. Nordic Wood, Phase 2, Project P-2. Final report. 1999. 73 p. 1997 Jokinen, Petri, Lahtinen, Reima & Lehmus, Eila. Teräsrakenteiden suojaus kaariruiskutetulla sinkki- pinnoitteella. 1999. 50 s. + liitt. 14 s. 2001 Haakana, Maarit & Soitinaho, Ulla. Kiinteistönhoitohenkilöstön motivointi energiansäästöön. Kokemukset koulukohteista. 1999. 43 s. + liitt. 14 s. 2002 Andstén, Tauno, Juutilainen, Hemmo, Vaari, Jukka & Weckman, Henry. Test method for actuating and safety devices of portable fire extinguishers. Nordtest Project No. 1435–99. 1999. 40 p. + app. 25 p. 2003 Vainio, Terttu, Riihimäki, Markku & Mäkelä, Pekka. Rakennuskustannusindeksi 2000. 1999. 70 s. + liitt. 2 s. 2005 Baroudi, Djebar, Kokkala, Matti & Weckman, Henry. Savuilmaisimien toiminta-aikojen laskentaohjelma PALDET 2.1S. 1999. 37 s. + liitt. 1 s. 2013 Tillander, Kati & Keski-Rahkonen, Olavi. Palokunnan saatavuuden merkitys rakennuksen paloriski- tarkastelussa. 2000. 213 s. + liitt. 55 s. 2025 Riihimäki, Markku & Lehtinen, Erkki. Talopaketit asuinrakentamisessa. Valmisosien yleisyys toimituksissa. 2000. 44 p. 2027 Hietaniemi, Jukka, Hostikka, Simo, Lindberg, Liisa & Kokkala, Matti. Vyöhykemalliohjelman CFAST- kelpoisuuden arviointi. 2000. 51 s. + liitt. 14 s. 2028 Kokkala, Matti. Rakennusten paloturvallisuussuunnittelu. Toiminnallinen lähestymistapa. 2000. 63 s. + liitt. 15 s. 2029 Helenius, Antti. Shear strength of clinched connections in light gauge steel. 2000. 40 p. + app. 13 p. 2030 Rantamäki, Jouko, Kääriäinen, Hannu, Tulla, Kauko, Viitanen, Hannu, Kalliokoski, Pentti, Keskikuru, Timo, Kokotti Helmi & Pasanen, Anna-Liisa. Rakennusten ja rakennusmateriaalien homeet. 2000. 40 s. + liitt. 6 s. 2041 Viirola, Heli & Raivio, Paula. Portlandsementin hydrataatio. 2000. 61 s. 2047 Leivo, Markku. Betonin pakkasenkestävyyden varmistaminen. Osa 2. Laadunvalvonta ja -varmistus. 2000. 13 s. + liitt. 25 s. 2048 Kuosa, Hannele. Älykkäät betonit ja betonirakenteet. 2000. 35 s. + liitt. 9 s. 2049 Lehtinen, Jari. Rakennushankkeen turvallisuusjohtaminen. Korkea rakennuskohde. 2000. 77 s. + liitt. 16 s. 2051 Karhu, Vesa & Loikkanen, Kaisu. Japanese and Chinese construction and facilities management software markets. Preliminary study. 2000. 58 p. + app. 4 p. 2053 Luoma, Marianna & Pasanen, Pertti. Ilmanvaihtojärjestelmien puhdistus 15 toimistorakennuksessa. Puhdistuksen ja säädön vaikutus toimistotilojen kanavien puhtauteen, ilmanvaihtuvuuteen, tuloilman laatuun ja työntekijöiden työoloihin. 2000. 43 s. + liitt. 6 s. 2054 Riihimäki, Markku & Lehtinen, Erkki. Luonnonkiviteollisuuden markkinat. 2000. 57 s. + liitt. 19 s. 2056 Kuosa, Hannele & Vesikari Erkki. Betonin pakkasenkestävyyden varmistaminen. Osa 1. Perusteet ja käyttöikämitoitus. 2000. 141 s. 2070 Nieminen, Jyri & Salonvaara, Mikael. Hygrothermal performance of light steel-framed walls. 2000. 26 p. 2072 Paiho, Satu, Leskinen, Mia & Mustakallio, Panu. Automaatiojärjestelmän hyödyntäminen energiatietoisen käytön apuvälineenä. 2000. 63 s.