Mechanical Smoke Ventilation Calculations
For Basement Floor ( Store)
Mechanical Ventilation system for basement floor
#Assumptions:-
Fire Area = 3 x 3 = 9 sq.m
Smoke Plume High (.Y) = 2.5 M
Total height (H) = 3.5 M
Smoke layer thickness (db) = H - Y = 1 M
Floor Area = 1050 sq.m
#Determining the heat release
Q = q x A…………………………(1)
where q = 390 KW/sq.M
Refference :- BS7436 tables with aid of NFBA 204M tables.
From equation(1)
Qs = 3510 kw
#Determining smoke mass flow rate Ms
Ms = 0.188 PY 3/2…………………(2)
where P = Fire Perimeter = 12 M
Y = Clear height of smoke plume = 2.5 M
From equation(2)
Ms = 0.188 x12 x 2.53/2
Ms = 8.9 kg/s.
#Determining plume temperature rise:
dT = Qs…………(.3)
Ms x Cps
dT = 390 K
And
Ts = To + DT……………………(.4)
Where:
Ts = Smoke temp.
To =Ambient temp. = 303 K
Ts = 693 K
#Determining the required air flow rate:
V = Ms Ts………………(.5)
To ps
Where:-
V = Required air volumetric flow rate
ps = Smoke density = 1.2 Kg/m3
V = 17.0 M3/Sec.
=310,14CFM ~~= 37,000 CFM
#Determining duct size and fan static pressure:-
V = A X v…………………………(.8)
Where v = volumetric flow rate for one fan = 37,000 cfm
OR. v = volumetric flow rate for one fan = 17.0 M3/Sec.
A = duct cross sec. Area
V = desired air velocity in the duct = 6 M/Sec.
A = 2.83 M2
Static pressure ( in.wg) = 0.5 + duct friction loss
where duct friction loss = 0.5 in.wg
Total Static pressure ( in.wg) = 1 in.wg.
Conclusion:
System Description:
Exhaust Smoke Fans:
Nunmers: 2 Nos. Fans/Zone
Capacity: 18,500 cfm (each)
Type : Tubilar ducted
Location : Roof Top
Duct Size = 12.33 Sq.ft = 60" X 22"
Duct Size = 1.15 Sq.M = 152 X 56 CM
#Determining fresh air intake area:
No. of entrances and doors = 2 doors
Average door size (m) = 2.2 (width) , 2 (height)
=4.4m2
Total fresh air intake area = 8.8 m2
V = A X v…………………………(.8)
Where V = The required fresh air supply
=1CFM
=-M3/Sec.
Assuming average air velocity through doors to be 2m/s ( to allow door opening for
occupants evacuation)
A = - m2
The required area is less than doors and enterance areas
SO, Enterance area is sufficient as fresh air supply openings.
Fresh Air Fans:
Fresh Air Fans capacity shall be half of exhaust air capacity depending on the doors and
park ramp opening to deliver adequate fresh air amount for the other half of the floor area.
Fresh Air properties shall be:
Nunmers: 2 No. Fan
Capacity: 10,500 cfm
Type : Tubilar ducted
Location : Roof Top
Total Static pressure ( in.wg) = 1 in.wg.
GENERAL
-All fans used in smoke management and exhaust system ( exhaust and fresh air fans )
shall be capable to withstand 200 oC temp.for 30 min.
-All fans shall be interconnected with fire allarm panel for automatic operation also, shall be
provided with ON /OFF switch near enterances for manual operation by occupants.‫شرح‬
‫مروحة‬‫الدخان‬
Mechanical Smoke Ventilation Calculations
For Basement Floor ( Store)
Mechanical Ventilation system for basement floor
#Assumptions:-
Fire Area = 3 x 3 = 9 sq.m
Smoke Plume High (.Y) = 2.5 M
Total height (H) = 3.5 M
Smoke layer thickness (db) = H - Y = 1 M
Floor Area = 1050 sq.m
#Determining the heat release
Q = q x A…………………………(1)
where q = 390 KW/sq.M
Refference :- BS7436 tables with aid of NFBA 204M tables.
From equation(1)
Qs = 3510 kw
#Determining smoke mass flow rate Ms
Ms = 0.188 PY 3/2…………………(2)
where P = Fire Perimeter = 12 M
Y = Clear height of smoke plume = 2.5 M
From equation(2)
Ms = 0.188 x12 x 2.53/2
Ms = 8.9 kg/s.
#Determining plume temperature rise:
dT = Qs…………(.3)
Ms x Cps
dT = 390 K
And
Ts = To + DT……………………(.4)
Where:
Ts = Smoke temp.
To =Ambient temp. = 303 K
Ts = 693 K
#Determining the required air flow rate:
V = Ms Ts………………(.5)
To ps
Where:-
V = Required air volumetric flow rate
ps = Smoke density = 1.2 Kg/m3
V = 17.0 M3/Sec.
=310,14CFM ~~= 37,000 CFM
#Determining duct size and fan static pressure:-
V = A X v…………………………(.8)
Where v = volumetric flow rate for one fan = 37,000 cfm
OR. v = volumetric flow rate for one fan = 17.0 M3/Sec.
A = duct cross sec. Area
V = desired air velocity in the duct = 6 M/Sec.
A = 2.83 M2
Static pressure ( in.wg) = 0.5 + duct friction loss
where duct friction loss = 0.5 in.wg
Total Static pressure ( in.wg) = 1 in.wg.
Conclusion:
System Description:
Exhaust Smoke Fans:
Nunmers: 2 Nos. Fans/Zone
Capacity: 18,500 cfm (each)
Type : Tubilar ducted
Location : Roof Top
Duct Size = 12.33 Sq.ft = 60" X 22"
Duct Size = 1.15 Sq.M = 152 X 56 CM
#Determining fresh air intake area:
No. of entrances and doors = 2 doors
Average door size (m) = 2.2 (width) , 2 (height)
=4.4m2
Total fresh air intake area = 8.8 m2
V = A X v…………………………(.8)
Where V = The required fresh air supply
=1CFM
=-M3/Sec.
Assuming average air velocity through doors to be 2m/s ( to allow door opening for
occupants evacuation)
A = - m2
The required area is less than doors and enterance areas
SO, Enterance area is sufficient as fresh air supply openings.
Fresh Air Fans:
Fresh Air Fans capacity shall be half of exhaust air capacity depending on the doors and
park ramp opening to deliver adequate fresh air amount for the other half of the floor area.
Fresh Air properties shall be:
Nunmers: 2 No. Fan
Capacity: 10,500 cfm
Type : Tubilar ducted
Location : Roof Top
Total Static pressure ( in.wg) = 1 in.wg.
GENERAL
-All fans used in smoke management and exhaust system ( exhaust and fresh air fans )
shall be capable to withstand 200 oC temp.for 30 min.
-All fans shall be interconnected with fire allarm panel for automatic operation also, shall be
provided with ON /OFF switch near enterances for manual operation by occupants.

More Related Content

What's hot

Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learnQaimuddin SODHO
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load CalculationJitendra Jha
 
Cooling load calculations and principles
Cooling load calculations and principlesCooling load calculations and principles
Cooling load calculations and principlesDheiy Myth
 
Heating Ventilation & Air Conditioning (HVAC)
Heating Ventilation & Air Conditioning (HVAC)Heating Ventilation & Air Conditioning (HVAC)
Heating Ventilation & Air Conditioning (HVAC)Joshua Joel
 
Duct Design & Air distribution
Duct Design & Air distributionDuct Design & Air distribution
Duct Design & Air distributionDhrumit Patel
 
Load estimation in Air Conditioning
Load estimation in Air ConditioningLoad estimation in Air Conditioning
Load estimation in Air ConditioningParth Prajapati
 
HVAC Air distribution fundamentals
HVAC Air distribution fundamentalsHVAC Air distribution fundamentals
HVAC Air distribution fundamentalsAp Naseem
 
S3 Duct System Design Consideration
S3 Duct System Design ConsiderationS3 Duct System Design Consideration
S3 Duct System Design Considerationno suhaila
 
How to calculate cfm for commercial kitchen exhaust ventilation (1)
How to calculate cfm for commercial kitchen exhaust ventilation (1)How to calculate cfm for commercial kitchen exhaust ventilation (1)
How to calculate cfm for commercial kitchen exhaust ventilation (1)Ahmad Affan
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWRIDDHESH VARIK
 

What's hot (20)

RESNET: HVAC Presentation
RESNET: HVAC PresentationRESNET: HVAC Presentation
RESNET: HVAC Presentation
 
Hvac basics lunch & learn
Hvac basics lunch & learnHvac basics lunch & learn
Hvac basics lunch & learn
 
Heat Load Calculation
Heat Load CalculationHeat Load Calculation
Heat Load Calculation
 
Cooling load calculations and principles
Cooling load calculations and principlesCooling load calculations and principles
Cooling load calculations and principles
 
2. Hydrant System.pdf
2. Hydrant System.pdf2. Hydrant System.pdf
2. Hydrant System.pdf
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
Heating Ventilation & Air Conditioning (HVAC)
Heating Ventilation & Air Conditioning (HVAC)Heating Ventilation & Air Conditioning (HVAC)
Heating Ventilation & Air Conditioning (HVAC)
 
Duct Design & Air distribution
Duct Design & Air distributionDuct Design & Air distribution
Duct Design & Air distribution
 
Load estimation in Air Conditioning
Load estimation in Air ConditioningLoad estimation in Air Conditioning
Load estimation in Air Conditioning
 
AIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGINGAIR CONDITIONING SYSTEM DESINGING
AIR CONDITIONING SYSTEM DESINGING
 
HVAC Air distribution fundamentals
HVAC Air distribution fundamentalsHVAC Air distribution fundamentals
HVAC Air distribution fundamentals
 
Hvac formulas
Hvac formulasHvac formulas
Hvac formulas
 
S3 Duct System Design Consideration
S3 Duct System Design ConsiderationS3 Duct System Design Consideration
S3 Duct System Design Consideration
 
Ventilation System
Ventilation System Ventilation System
Ventilation System
 
How to calculate cfm for commercial kitchen exhaust ventilation (1)
How to calculate cfm for commercial kitchen exhaust ventilation (1)How to calculate cfm for commercial kitchen exhaust ventilation (1)
How to calculate cfm for commercial kitchen exhaust ventilation (1)
 
VARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOWVARIABLE REFRIGERATE FLOW
VARIABLE REFRIGERATE FLOW
 
Cooling load estimation
Cooling load estimationCooling load estimation
Cooling load estimation
 
Everything about Elite Fire.
Everything about Elite Fire. Everything about Elite Fire.
Everything about Elite Fire.
 
02 chilled-water-piping-pumps
02 chilled-water-piping-pumps02 chilled-water-piping-pumps
02 chilled-water-piping-pumps
 
Chiller ppt
Chiller pptChiller ppt
Chiller ppt
 

Similar to Smoke fan sizing

Gas dynamics and jet propulsion – presentationof problemsanswers
Gas dynamics and jet propulsion – presentationof problemsanswersGas dynamics and jet propulsion – presentationof problemsanswers
Gas dynamics and jet propulsion – presentationof problemsanswersVaidyanathan Ramakrishnan
 
Staircase fan roof
Staircase fan roofStaircase fan roof
Staircase fan roofAadii Soni
 
psychrometric chart & processes.pdf
psychrometric chart & processes.pdfpsychrometric chart & processes.pdf
psychrometric chart & processes.pdfAbhayThakur193489
 
Process Calculation - simple distillation
Process Calculation - simple distillationProcess Calculation - simple distillation
Process Calculation - simple distillationChandran Udumbasseri
 
The psychrometric chart theory and application
The psychrometric chart theory and applicationThe psychrometric chart theory and application
The psychrometric chart theory and applicationUsama Khan
 
2010 Sfpe Cpd On Explosion Venting
2010 Sfpe Cpd On Explosion Venting2010 Sfpe Cpd On Explosion Venting
2010 Sfpe Cpd On Explosion Ventingandrewwcwong
 
Project By Rcdohare& Miss Kakoli Shaw
Project By Rcdohare& Miss Kakoli ShawProject By Rcdohare& Miss Kakoli Shaw
Project By Rcdohare& Miss Kakoli ShawBHILAI STEEL PLANT
 
Sq 4.6 - fans and blowers (table format)
Sq   4.6 - fans and blowers (table format)Sq   4.6 - fans and blowers (table format)
Sq 4.6 - fans and blowers (table format)Murad Eltaher
 
Heat transfer(HT) lab manual
Heat transfer(HT) lab manualHeat transfer(HT) lab manual
Heat transfer(HT) lab manualnmahi96
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02ThamizhmaniT
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02ThamizhmaniT
 
report mini project print
report mini project print report mini project print
report mini project print Haziman Zakaria
 

Similar to Smoke fan sizing (20)

13 venting requirements
13 venting requirements13 venting requirements
13 venting requirements
 
Gas dynamics and jet propulsion – presentationof problemsanswers
Gas dynamics and jet propulsion – presentationof problemsanswersGas dynamics and jet propulsion – presentationof problemsanswers
Gas dynamics and jet propulsion – presentationof problemsanswers
 
Staircase fan roof
Staircase fan roofStaircase fan roof
Staircase fan roof
 
psychrometric chart & processes.pdf
psychrometric chart & processes.pdfpsychrometric chart & processes.pdf
psychrometric chart & processes.pdf
 
Process Calculation - simple distillation
Process Calculation - simple distillationProcess Calculation - simple distillation
Process Calculation - simple distillation
 
Psychrometry
PsychrometryPsychrometry
Psychrometry
 
The psychrometric chart theory and application
The psychrometric chart theory and applicationThe psychrometric chart theory and application
The psychrometric chart theory and application
 
JBruceHVAC
JBruceHVACJBruceHVAC
JBruceHVAC
 
2010 Sfpe Cpd On Explosion Venting
2010 Sfpe Cpd On Explosion Venting2010 Sfpe Cpd On Explosion Venting
2010 Sfpe Cpd On Explosion Venting
 
HVAC CAPSULEEMERSON EDUARDO RODRIGUES
HVAC CAPSULEEMERSON EDUARDO RODRIGUESHVAC CAPSULEEMERSON EDUARDO RODRIGUES
HVAC CAPSULEEMERSON EDUARDO RODRIGUES
 
HVAC CAPSULE EMERSON EDUARDO RODRIGUES
HVAC CAPSULE EMERSON EDUARDO RODRIGUESHVAC CAPSULE EMERSON EDUARDO RODRIGUES
HVAC CAPSULE EMERSON EDUARDO RODRIGUES
 
Project By Rcdohare& Miss Kakoli Shaw
Project By Rcdohare& Miss Kakoli ShawProject By Rcdohare& Miss Kakoli Shaw
Project By Rcdohare& Miss Kakoli Shaw
 
Sq 4.6 - fans and blowers (table format)
Sq   4.6 - fans and blowers (table format)Sq   4.6 - fans and blowers (table format)
Sq 4.6 - fans and blowers (table format)
 
Me2351 gas dynamics and jet propulsion-qb
Me2351 gas dynamics and jet propulsion-qbMe2351 gas dynamics and jet propulsion-qb
Me2351 gas dynamics and jet propulsion-qb
 
Heat transfer(HT) lab manual
Heat transfer(HT) lab manualHeat transfer(HT) lab manual
Heat transfer(HT) lab manual
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02
 
Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02Designofcondenser 130801223803-phpapp02
Designofcondenser 130801223803-phpapp02
 
report mini project print
report mini project print report mini project print
report mini project print
 
Design of condenser
Design of condenserDesign of condenser
Design of condenser
 
International standards in comparison
International standards in comparisonInternational standards in comparison
International standards in comparison
 

More from MUSTAFA AHMED ABDULJABBAR

Slide rule part2 carrier part load calculator supplement
Slide rule part2 carrier part load calculator supplementSlide rule part2 carrier part load calculator supplement
Slide rule part2 carrier part load calculator supplementMUSTAFA AHMED ABDULJABBAR
 
Slide rule part1 carrier part load calculator user manual and instructions
Slide rule part1 carrier part load calculator user manual and instructionsSlide rule part1 carrier part load calculator user manual and instructions
Slide rule part1 carrier part load calculator user manual and instructionsMUSTAFA AHMED ABDULJABBAR
 
Module 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTH
Module 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTHModule 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTH
Module 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTHMUSTAFA AHMED ABDULJABBAR
 
Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH
Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH
Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH MUSTAFA AHMED ABDULJABBAR
 
Wiring.module.3 GENERAL TRAINING ELECTRICITY
Wiring.module.3 GENERAL TRAINING ELECTRICITYWiring.module.3 GENERAL TRAINING ELECTRICITY
Wiring.module.3 GENERAL TRAINING ELECTRICITYMUSTAFA AHMED ABDULJABBAR
 

More from MUSTAFA AHMED ABDULJABBAR (20)

Slide rule part2 carrier part load calculator supplement
Slide rule part2 carrier part load calculator supplementSlide rule part2 carrier part load calculator supplement
Slide rule part2 carrier part load calculator supplement
 
Slide rule part1 carrier part load calculator user manual and instructions
Slide rule part1 carrier part load calculator user manual and instructionsSlide rule part1 carrier part load calculator user manual and instructions
Slide rule part1 carrier part load calculator user manual and instructions
 
CHECK LIST FOR ( HVAC ) WORK & SHOP DRAWING
CHECK LIST FOR ( HVAC ) WORK & SHOP DRAWINGCHECK LIST FOR ( HVAC ) WORK & SHOP DRAWING
CHECK LIST FOR ( HVAC ) WORK & SHOP DRAWING
 
Preventing compressor failure
Preventing compressor failurePreventing compressor failure
Preventing compressor failure
 
smacna cad standard
smacna cad standardsmacna cad standard
smacna cad standard
 
HVAC QUICK COMPRESSOR WINDING CHECK
HVAC QUICK COMPRESSOR WINDING CHECK  HVAC QUICK COMPRESSOR WINDING CHECK
HVAC QUICK COMPRESSOR WINDING CHECK
 
Stair case fan sizing
Stair case fan sizingStair case fan sizing
Stair case fan sizing
 
Auto cad shortcuts
Auto cad shortcutsAuto cad shortcuts
Auto cad shortcuts
 
Micro soft word arabic lang shortcut
Micro soft word arabic lang shortcutMicro soft word arabic lang shortcut
Micro soft word arabic lang shortcut
 
REFRIGERANT pipING module 3 GTAC
REFRIGERANT pipING module 3 GTACREFRIGERANT pipING module 3 GTAC
REFRIGERANT pipING module 3 GTAC
 
Module 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTH
Module 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTHModule 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTH
Module 9 GENERAL TRAINING ELECTRICITY ELECTRICAL TROUBLESHOOTING GTAC GTE GTH
 
Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH
Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH
Module 8 ELECTRONIC DEVICES AND CIRUITS GTAC GTE GTH
 
MODULE 4 Wiring diagram exercises
MODULE 4 Wiring diagram exercises MODULE 4 Wiring diagram exercises
MODULE 4 Wiring diagram exercises
 
30GT15-35 TON RECIPROCATING LIQUID CHILLERS
30GT15-35 TON  RECIPROCATING LIQUID CHILLERS30GT15-35 TON  RECIPROCATING LIQUID CHILLERS
30GT15-35 TON RECIPROCATING LIQUID CHILLERS
 
Wiring.module.3 GENERAL TRAINING ELECTRICITY
Wiring.module.3 GENERAL TRAINING ELECTRICITYWiring.module.3 GENERAL TRAINING ELECTRICITY
Wiring.module.3 GENERAL TRAINING ELECTRICITY
 
Understanding electronic.contrOL
Understanding electronic.contrOLUnderstanding electronic.contrOL
Understanding electronic.contrOL
 
Scroll compressors
Scroll compressorsScroll compressors
Scroll compressors
 
Refrigerant.service technique
Refrigerant.service techniqueRefrigerant.service technique
Refrigerant.service technique
 
Understanding electronic contrOL
Understanding electronic contrOLUnderstanding electronic contrOL
Understanding electronic contrOL
 
30GB packaged liquid chillers
30GB packaged liquid chillers30GB packaged liquid chillers
30GB packaged liquid chillers
 

Recently uploaded

Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionDr.Costas Sachpazis
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...Soham Mondal
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSKurinjimalarL3
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .Satyam Kumar
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxvipinkmenon1
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxKartikeyaDwivedi3
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024hassan khalil
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx959SahilShah
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxk795866
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort servicejennyeacort
 

Recently uploaded (20)

Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective IntroductionSachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
Sachpazis Costas: Geotechnical Engineering: A student's Perspective Introduction
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 
POWER SYSTEMS-1 Complete notes examples
POWER SYSTEMS-1 Complete notes  examplesPOWER SYSTEMS-1 Complete notes  examples
POWER SYSTEMS-1 Complete notes examples
 
Design and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdfDesign and analysis of solar grass cutter.pdf
Design and analysis of solar grass cutter.pdf
 
young call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Serviceyoung call girls in Green Park🔝 9953056974 🔝 escort Service
young call girls in Green Park🔝 9953056974 🔝 escort Service
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
OSVC_Meta-Data based Simulation Automation to overcome Verification Challenge...
 
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICSAPPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
APPLICATIONS-AC/DC DRIVES-OPERATING CHARACTERISTICS
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
Churning of Butter, Factors affecting .
Churning of Butter, Factors affecting  .Churning of Butter, Factors affecting  .
Churning of Butter, Factors affecting .
 
Introduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptxIntroduction to Microprocesso programming and interfacing.pptx
Introduction to Microprocesso programming and interfacing.pptx
 
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
9953056974 Call Girls In South Ex, Escorts (Delhi) NCR.pdf
 
Concrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptxConcrete Mix Design - IS 10262-2019 - .pptx
Concrete Mix Design - IS 10262-2019 - .pptx
 
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Serviceyoung call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
young call girls in Rajiv Chowk🔝 9953056974 🔝 Delhi escort Service
 
Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024Architect Hassan Khalil Portfolio for 2024
Architect Hassan Khalil Portfolio for 2024
 
Application of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptxApplication of Residue Theorem to evaluate real integrations.pptx
Application of Residue Theorem to evaluate real integrations.pptx
 
Introduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptxIntroduction-To-Agricultural-Surveillance-Rover.pptx
Introduction-To-Agricultural-Surveillance-Rover.pptx
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort serviceGurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
Gurgaon ✡️9711147426✨Call In girls Gurgaon Sector 51 escort service
 

Smoke fan sizing

  • 1. ‫شرح‬‫مروحة‬‫الدخان‬ Mechanical Smoke Ventilation Calculations For Basement Floor ( Store) Mechanical Ventilation system for basement floor #Assumptions:- Fire Area = 3 x 3 = 9 sq.m Smoke Plume High (.Y) = 2.5 M Total height (H) = 3.5 M Smoke layer thickness (db) = H - Y = 1 M Floor Area = 1050 sq.m #Determining the heat release Q = q x A…………………………(1) where q = 390 KW/sq.M Refference :- BS7436 tables with aid of NFBA 204M tables. From equation(1) Qs = 3510 kw #Determining smoke mass flow rate Ms Ms = 0.188 PY 3/2…………………(2) where P = Fire Perimeter = 12 M Y = Clear height of smoke plume = 2.5 M From equation(2) Ms = 0.188 x12 x 2.53/2 Ms = 8.9 kg/s. #Determining plume temperature rise: dT = Qs…………(.3) Ms x Cps dT = 390 K And Ts = To + DT……………………(.4) Where:
  • 2. Ts = Smoke temp. To =Ambient temp. = 303 K Ts = 693 K #Determining the required air flow rate: V = Ms Ts………………(.5) To ps Where:- V = Required air volumetric flow rate ps = Smoke density = 1.2 Kg/m3 V = 17.0 M3/Sec. =310,14CFM ~~= 37,000 CFM #Determining duct size and fan static pressure:- V = A X v…………………………(.8) Where v = volumetric flow rate for one fan = 37,000 cfm OR. v = volumetric flow rate for one fan = 17.0 M3/Sec. A = duct cross sec. Area V = desired air velocity in the duct = 6 M/Sec. A = 2.83 M2 Static pressure ( in.wg) = 0.5 + duct friction loss where duct friction loss = 0.5 in.wg Total Static pressure ( in.wg) = 1 in.wg. Conclusion: System Description: Exhaust Smoke Fans: Nunmers: 2 Nos. Fans/Zone Capacity: 18,500 cfm (each) Type : Tubilar ducted Location : Roof Top Duct Size = 12.33 Sq.ft = 60" X 22" Duct Size = 1.15 Sq.M = 152 X 56 CM #Determining fresh air intake area:
  • 3. No. of entrances and doors = 2 doors Average door size (m) = 2.2 (width) , 2 (height) =4.4m2 Total fresh air intake area = 8.8 m2 V = A X v…………………………(.8) Where V = The required fresh air supply =1CFM =-M3/Sec. Assuming average air velocity through doors to be 2m/s ( to allow door opening for occupants evacuation) A = - m2 The required area is less than doors and enterance areas SO, Enterance area is sufficient as fresh air supply openings. Fresh Air Fans: Fresh Air Fans capacity shall be half of exhaust air capacity depending on the doors and park ramp opening to deliver adequate fresh air amount for the other half of the floor area. Fresh Air properties shall be: Nunmers: 2 No. Fan Capacity: 10,500 cfm Type : Tubilar ducted Location : Roof Top Total Static pressure ( in.wg) = 1 in.wg. GENERAL -All fans used in smoke management and exhaust system ( exhaust and fresh air fans ) shall be capable to withstand 200 oC temp.for 30 min. -All fans shall be interconnected with fire allarm panel for automatic operation also, shall be provided with ON /OFF switch near enterances for manual operation by occupants.‫شرح‬ ‫مروحة‬‫الدخان‬ Mechanical Smoke Ventilation Calculations For Basement Floor ( Store)
  • 4. Mechanical Ventilation system for basement floor #Assumptions:- Fire Area = 3 x 3 = 9 sq.m Smoke Plume High (.Y) = 2.5 M Total height (H) = 3.5 M Smoke layer thickness (db) = H - Y = 1 M Floor Area = 1050 sq.m #Determining the heat release Q = q x A…………………………(1) where q = 390 KW/sq.M Refference :- BS7436 tables with aid of NFBA 204M tables. From equation(1) Qs = 3510 kw #Determining smoke mass flow rate Ms Ms = 0.188 PY 3/2…………………(2) where P = Fire Perimeter = 12 M Y = Clear height of smoke plume = 2.5 M From equation(2) Ms = 0.188 x12 x 2.53/2 Ms = 8.9 kg/s. #Determining plume temperature rise: dT = Qs…………(.3) Ms x Cps dT = 390 K And Ts = To + DT……………………(.4) Where: Ts = Smoke temp. To =Ambient temp. = 303 K Ts = 693 K #Determining the required air flow rate:
  • 5. V = Ms Ts………………(.5) To ps Where:- V = Required air volumetric flow rate ps = Smoke density = 1.2 Kg/m3 V = 17.0 M3/Sec. =310,14CFM ~~= 37,000 CFM #Determining duct size and fan static pressure:- V = A X v…………………………(.8) Where v = volumetric flow rate for one fan = 37,000 cfm OR. v = volumetric flow rate for one fan = 17.0 M3/Sec. A = duct cross sec. Area V = desired air velocity in the duct = 6 M/Sec. A = 2.83 M2 Static pressure ( in.wg) = 0.5 + duct friction loss where duct friction loss = 0.5 in.wg Total Static pressure ( in.wg) = 1 in.wg. Conclusion: System Description: Exhaust Smoke Fans: Nunmers: 2 Nos. Fans/Zone Capacity: 18,500 cfm (each) Type : Tubilar ducted Location : Roof Top Duct Size = 12.33 Sq.ft = 60" X 22" Duct Size = 1.15 Sq.M = 152 X 56 CM #Determining fresh air intake area: No. of entrances and doors = 2 doors Average door size (m) = 2.2 (width) , 2 (height) =4.4m2 Total fresh air intake area = 8.8 m2
  • 6. V = A X v…………………………(.8) Where V = The required fresh air supply =1CFM =-M3/Sec. Assuming average air velocity through doors to be 2m/s ( to allow door opening for occupants evacuation) A = - m2 The required area is less than doors and enterance areas SO, Enterance area is sufficient as fresh air supply openings. Fresh Air Fans: Fresh Air Fans capacity shall be half of exhaust air capacity depending on the doors and park ramp opening to deliver adequate fresh air amount for the other half of the floor area. Fresh Air properties shall be: Nunmers: 2 No. Fan Capacity: 10,500 cfm Type : Tubilar ducted Location : Roof Top Total Static pressure ( in.wg) = 1 in.wg. GENERAL -All fans used in smoke management and exhaust system ( exhaust and fresh air fans ) shall be capable to withstand 200 oC temp.for 30 min. -All fans shall be interconnected with fire allarm panel for automatic operation also, shall be provided with ON /OFF switch near enterances for manual operation by occupants.