GreenJet®
Transfer Fans
Model GJX
High Performance Axial Transfer Fan
2
GreenJet®
As cars park in an underground parking structure, carbon monoxide (CO) and other noxious fumes
are emitted into the atmosphere. There is a need for an efficient ventilation system to remove these
toxins, circulate fresh air into the car park, and assist firefighters with smoke control in the case of a fire
emergency. The GreenJet® model GJX includes a range of performances to accommodate your needs
for parking garage ventilation.
While ducted ventilation has been the standard for many years, innovation in
technology has shifted systems toward ductless designs. Ductless designs
use transfer fans to dilute and remove contaminants and control the smoke.
In addition, these systems provide greater control and operational savings.
Fresh air intended to replace contaminated exhaust
is removed along with contaminates through each
duct. The illustration below shows ducts closer to
the supply air remove much of the fresh air, leaving
mostly toxic air at the farthest duct, causing a
hazardous condition.
GreenJet transfer fans push fresh supply air through
the parking area towards the exhaust fan(s). This
removes a higher proportion of contaminated air and
replaces it with clean air.
Advantages:
•	 Simplified Design: Eliminates the need and expense of designing a duct system.
•	 Lower Construction Cost: GreenJet fans require less height against the ceiling than a ducted system. This
means the required height of each level is less, reducing excavation and lowering overall construction cost.
•	 Lower Installation Cost: A typical GreenJet system results in less installation time.
•	 Improved Operational Costs: Eliminating ductwork reduces the
system static pressure and allows for smaller supply and
exhaust fans to run using less power. The use of third-party
exhaust sensors allows for demand-based ventilation.
•	 Reduced Maintenance: GreenJet fans are more accessible
for maintenance than traditional systems, and eliminate
duct cleaning.
•	 Enhanced Safety: GreenJet fans are more efficient at
removing noxious fumes and clearing smoke, resulting in a
safer environment.
UL/cUL 705 Listed Power Ventilator
File No. E40001
UL/cUL Power Ventilator for Smoke Control Systems
File No. MH17511
AMCA licensed air performance may be found in
Greenheck’s Computer Aided Product Selection
program (CAPS).
Improved Exhaust Effectiveness with GreenJet
Carbon Monoxide (CO) Contaminate Concentration Level
Low HighMedium
Exhaust
Air
Exhaust
Air
Supply
Air
Supply
Air
Ducted System Ductless with GreenJet Transfer Fans
3
Construction and Installation
Ductless Garage Ventilation: Supply – Transfer – Exhaust
Typical installation and operation of ductless, enclosed parking garage HVAC systems consist of supply fans,
GJX GreenJet fans, and exhaust fans.
Under normal conditions, fresh air is introduced into the garage through entrance/exit ramps and through a
dedicated supply fan. The GreenJet model GJX fans are positioned to direct air from one end of the garage to
the other, supplying fresh air to the structure while also mixing and pushing contaminated air towards the point
of exhaust (typically on the end opposite the supply). An exhaust fan removes the contaminated air from the
garage. A timer, occupancy monitor, or demand-based control system can operate the entire system.
The GJX fans are available with Smoke Control certification for integration into a smoke exhaust control system.
GJX is intended to provide emergency responders a clear path for better and more effective access.
GJX GreenJet
Exhaust
Fan
Inlet and Outlet
Silencers
Inlet and Outlet
Guard
Casing
Flush Mounting
Brackets
GreenJet model GJX is a low profile, quiet fan suspended from the ceiling.
Construction features include:
•	 Durable steel casing with Permatector™ coating for corrosive environments
•	 Mounting brackets flush with the top of the silencers for no
additional height
•	 Airfoil propellers move large volumes of air with high efficiency in a
small diameter fan
•	 Sound absorbing inlet and outlet silencers with perforated inner liner
for maximum sound reduction
•	 Aerodynamic inlet design improving performance efficiency.
When installed ceiling hung,
GreenJet moves the air towards the
exhaust area by effectively creating
a continuous flow, avoiding the
creation of stagnant zones where
air may become trapped.
4
CFD velocity profile for a GJX-41 showing
200 fpm throw of 110 ft (33 m).
Car park layout with GJX velocity profiles
added giving initial placement locations.
Fan Placement and Velocity Profiles
Successful operation requires the correct fan quantities, placement, and direction of the transfer fans.
Discharge velocity profiles is a tool to provide a starting point for initial fan placement. GreenJet velocity
profiles are available for integration in an AutoCAD® layout. The images below show the use of Computational
Fluid Dynamics (CFD) to develop a 200 fpm velocity profile and integration into a design layout.
Design Layout
CFD Analysis
There are different CFD analyses often used in parking garages:
•	 Velocity analysis provides information on air movement but not the effect on contaminate removal.
•	 CO analysis provides the effectiveness in removing contaminants from the parking garage.
•	 Smoke removal analysis shows how quickly and effectively smoke is removed from the source point.
Natural airflow paths from supply to exhaust locations exist within a building structure. Integrating transfer fans
moves air outside of these pathways. An analysis on CO levels illustrates the impact of the GJX GreenJet fan
installation on a parking garage.
Without Jet Fans With Jet Fans
5
System Integration and Payback
Integration of GreenJet model GJX fans into Demand-Based Application
A demand-based system is controlled using sensors that measure parts per million (ppm) of contaminants and
sends information to the the facilities controller to increase or decrease speed based on actual conditions. The
image below shows how the GJX GreenJet is integrated into this application.
Energy Saving with Demand-Based Ventilation
There are two methods for controlling parking ventilation systems; an On / Off system where the ventilation
is on a timer or occupancy sensor, or demand-based with sensors changing the ventilation rate with
contaminate levels.
Simplified Example:
Five times the difference in prescribed
ventilation rates between systems
with and systems without air quality
monitoring and control.
Control Method Operation
Ventilation Rate*
(cfm per ft² of garage floor)
Operating Time
(hours)
Daily Operating Volume
(ft³ per ft² of garage floor)
On / Off Full 0.75 12 540
Demand-Based
Full 0.75 2 (average)
180
Reduced 0.15 10
*Full flow uses a 0.75 cfm/ft² (ASHRAE 62.1-2013) ventilation rate per square foot for garage area and reduced flow using
0.15 cfm/ft² (California Title 24).
A VFD can be used with
multiple GJX fans in a zone
for lower controller costs.
In this example, a demand-based method
results in a 66% reduction in the ventilation
requirement and related energy savings.
6
Performance and
Dimensional Data
GJX - 31 - L - 160 - 06 25 - M 20 - X
Fan Size (cm)
31, 36, 41
Fan RPM
M = 3500
Hub Size
Blade Pitch
Number of Blades Motor Horsepower
7 = ¾
10 = 1
15 = 1½
20 = 2
Casing
Certification
None
X - UL/cUL 705 Listed (Electrical)
HTUL - UL/cUL HT Listed
(Emergency Smoke Control)
30 = 3
Model Number Code
Silencer Silencer Junction Box
Fan
AIRFLOW DIRECTION
B BA
C I
Dia.
D
E
G
H
F
Size
(cm)
A B C D E F G H I
Weight*
lbs. (kg)
31
17.01
(432)
24.49
(622)
14.80
(376)
12.24
(311)
16.18
(411)
10.28
(261)
10.04
(255)
8.31
(211)
0.47
(12)
143
(65)
36
17.01
(432)
28.50
(724)
14.80
(376)
14.25
(362)
18.19
(462)
12.28
(312)
11.02
(280)
9.29
(236)
0.47
(12)
152
(69)
41
20.00
(508)
32.52
(826)
17.81
(452)
16.26
(413)
20.20
(513)
14.29
(363)
12.05
(306)
10.31
(262)
0.47
(12)
170
(77)
Dimensions shown in inches (millimeters).
*Weight includes largest motor for size.
Dimensional Data
Fan Size
Airflow
cfm (m³/hr)
Thrust
lbs (N)*
Throw
ft (m)**
Power
Bhp (kW)
Motor Size
HP (kW)
Motor Speed
dBA Inlet
@ 5 ft
GJX-31-160-0634
2,640
(4,485)
5.6
(24.9)
85
(25.9)
1.26
(0.94)
1.50
(1.1)
3500 71
GJX-31-160-0625
2,250
(3,823)
4.1
(18.2)
75
(22.9)
0.74
(.55)
0.75
(0.56)
3500 69
GJX-36-160-0627
4,070
(6,915)
9.9
(44.0)
100
(30.5)
1.94
(1.45)
2.00
(1.5)
3500 73
GJX-36-160-0622
3,620
(6,150)
7.8
(34.7)
90
(27.4)
1.48
(1.1)
1.50
(1.1)
3500 74
GJX-41-160-0623
6,010
(10,211)
16.6
(73.8)
115
(35.1)
2.94
(2.19)
3.00
(2.2)
3500 77
GJX-41-160-0616
5,050
(8,580)
11.7
(52.0)
105
(32.0)
1.95
(1.45)
2.00
(1.5)
3500 78
*Air density = 0.075 lb./ft3
**Throw distance for 200 ft/min
The performance shown is not AMCA licensed as it includes losses from appurtenances (accessories) in the airstream. Licensed data may be found in
Greenheck’s Computer Aided Product Selection program (CAPS).
7
Emergency High Temperature Smoke Removal
The GreenJet model GJX is UL Listed for Smoke Control. It is high temperature performance tested and rated for
design time used in emergency heat and smoke exhaust applications.
Emergency Temperature Options:
•	 150°C / 5 Hours (302°F / 5 Hours) - per British Standard 7346
(Components for smoke control systems)
•	 260°C / 4 Hours (500°F / 4 Hours) - per Industrial Risk Insurers
(North America)
UL/cUL Power Ventilator for Smoke Control Systems
File No. MH17511
Certifications & Additional
Products for Car Park Ventilation
Life Safety Dampers
Life safety dampers are intended to protect openings in walls, ceilings, floors and/or partitions to prevent the
spread of fire and/or smoke. These are necessary in multi-level car parks with common shafts to prevent the
spread of smoke from one floor to another.
Fire dampers are required by all building codes to maintain
the required fire resistance ratings of walls, partitions and
floors when penetrated by air ducts and transfer openings.
These products were tested and classified in accordance
with UL Standard 555.
Smoke Dampers have two applications:
1.	 These may be applied in a passive smoke control system
where they simply close and prevent the circulation of air
and smoke through a duct or a ventilation opening in a
smoke barrier.
2.	 These may be applied as part of an engineered smoke control system designed to control the spread of
smoke using walls and floors as barriers and using the building’s HVAC system and/or dedicated fans to
create pressure differences.
These products are tested and classified in accordance with UL Standard 555S.
Combination Fire Smoke Dampers perform the function of both a fire damper and a smoke damper. Building
layouts and designs often combine fire and smoke rated partitions and barriers requiring the installation of both
a fire damper and smoke damper at the same location. These products are tested and classified in accordance
with both UL 555 and UL 555S.
Supply and Exhaust Fans
Greenheck’s high performance fans are ideal for air ventilation in commercial, industrial or institutional buildings.
Design and construction are well suited for indoor or outdoor applications and can be easily installed in ducted
or non-ducted systems. Fans are designed to reduce operating costs with improved efficiency.
•	 AMCA Licensed Performance
•	 UL/cUL Listed for Electrical 705
•	 UL/cUL Listed for Power Ventilators
for Smoke Control Systems
•	 Spark resistant construction
As a result of our commitment to continuous improvement, Greenheck reserves the right to change
specifications without notice.
Specific Greenheck product warranties are located on greenheck.com within the product
area tabs and in the Library under Warranties.
P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com
Our Commitment
00.LAB.1020 R1 4-2018 RG
Copyright © 2018 Greenheck Fan Corp.
Enjoy Greenheck’s extraordinary service, before,
during and after the sale.
Greenheck offers added value to our wide selection of top performing, energy-efficient
products by providing several unique Greenheck service programs.
• Our Quick Delivery Program ensures shipment of our in-stock products within 24 hours
of placing your order. Our Quick Build made-to-order products can be produced in 1-3-
5-10-15- or 25 day production cycles, depending upon their complexity.
• Greenheck’s free Computer Aided Product Selection program (CAPS), rated by
many as the best in the industry, helps you conveniently and efficiently select the right
products for the challenge at hand.
• Greenheck has been Green for a long time! Our energy-saving products and ongoing
corporate commitment to sustainability can help you qualify for LEED credits.
• Our 3D service allows you to download at no charge, lightweight, easy-to-use
AutoDesk® Revit® 3D drawings for many of our ventilation products.
Find out more about these special Greenheck services at greenheck.com
Design and Selection Support
Prepared to Support
Green Building Efforts

More Related Content

What's hot

Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...
Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...
Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...
Simply Marcomms
 
MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...
MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...
MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...
Midwest Energy Efficiency Alliance
 
Isuzu ft4 engine line up
Isuzu ft4 engine line upIsuzu ft4 engine line up
Isuzu ft4 engine line up
NeilHawkins22
 
OPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDY
OPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDYOPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDY
OPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDY
vishal laddha
 
8 secondary ventilation
8 secondary ventilation8 secondary ventilation
8 secondary ventilation
Riswan Badu
 

What's hot (20)

Indirect Evaporative Cooling
Indirect Evaporative CoolingIndirect Evaporative Cooling
Indirect Evaporative Cooling
 
Enclosure climatecontrol
Enclosure climatecontrolEnclosure climatecontrol
Enclosure climatecontrol
 
Assessment regarding energy saving and decoupling for different ahu
Assessment regarding energy saving and decoupling for different ahuAssessment regarding energy saving and decoupling for different ahu
Assessment regarding energy saving and decoupling for different ahu
 
Module (s 101) شحن غاز التكييفrefrigerant recovering, vacuuming and gas char...
Module (s 101)  شحن غاز التكييفrefrigerant recovering, vacuuming and gas char...Module (s 101)  شحن غاز التكييفrefrigerant recovering, vacuuming and gas char...
Module (s 101) شحن غاز التكييفrefrigerant recovering, vacuuming and gas char...
 
Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...
Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...
Camfil Whitepaper - Energy Saving in Buildings Better AHU Pre Filters can bri...
 
Comparative Analysis of HVAC System Based on Life Cycle Cost Analysis
Comparative Analysis of HVAC System Based on Life Cycle Cost AnalysisComparative Analysis of HVAC System Based on Life Cycle Cost Analysis
Comparative Analysis of HVAC System Based on Life Cycle Cost Analysis
 
MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...
MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...
MEEA Industrial Webinar: Industrial Refrigeration – Opportunities for Energy ...
 
IRJET- Optimization and CFD Analysis on Profile Elements of Regenerative Rota...
IRJET- Optimization and CFD Analysis on Profile Elements of Regenerative Rota...IRJET- Optimization and CFD Analysis on Profile Elements of Regenerative Rota...
IRJET- Optimization and CFD Analysis on Profile Elements of Regenerative Rota...
 
Study & Review of Heat Recovery Systems for SO2 Gas Generation Process in Sug...
Study & Review of Heat Recovery Systems for SO2 Gas Generation Process in Sug...Study & Review of Heat Recovery Systems for SO2 Gas Generation Process in Sug...
Study & Review of Heat Recovery Systems for SO2 Gas Generation Process in Sug...
 
IRJET - Variable Refrigerant Volume:- Air Conditioning Part: A Review
IRJET - Variable Refrigerant Volume:- Air Conditioning Part: A ReviewIRJET - Variable Refrigerant Volume:- Air Conditioning Part: A Review
IRJET - Variable Refrigerant Volume:- Air Conditioning Part: A Review
 
Isuzu ft4 engine line up
Isuzu ft4 engine line upIsuzu ft4 engine line up
Isuzu ft4 engine line up
 
Handbook of mechanical engineering calculations
Handbook of mechanical engineering calculationsHandbook of mechanical engineering calculations
Handbook of mechanical engineering calculations
 
Levanter air systems
Levanter air systemsLevanter air systems
Levanter air systems
 
Development of a 300 kWe Integrated Axial Turbine and Generator for ORC Appli...
Development of a 300 kWe Integrated Axial Turbine and Generator for ORC Appli...Development of a 300 kWe Integrated Axial Turbine and Generator for ORC Appli...
Development of a 300 kWe Integrated Axial Turbine and Generator for ORC Appli...
 
Optimization in refrigeration systems
Optimization in refrigeration systemsOptimization in refrigeration systems
Optimization in refrigeration systems
 
OPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDY
OPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDYOPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDY
OPTIMIZATION OF COMPRESSED AIR IN THERMAL POWER PLANT-A NOVEL STUDY
 
HMX cooling solution boosts employee efficiency at TeraSpin
HMX cooling solution boosts employee efficiency at TeraSpinHMX cooling solution boosts employee efficiency at TeraSpin
HMX cooling solution boosts employee efficiency at TeraSpin
 
Ice Slurry TES for TIC
Ice Slurry TES for TICIce Slurry TES for TIC
Ice Slurry TES for TIC
 
Cpg 2010
Cpg 2010Cpg 2010
Cpg 2010
 
8 secondary ventilation
8 secondary ventilation8 secondary ventilation
8 secondary ventilation
 

Similar to Catalog gjx

Rosenberg's ECFanGrid Case Study by Axair Fans.
Rosenberg's ECFanGrid Case Study by Axair Fans.Rosenberg's ECFanGrid Case Study by Axair Fans.
Rosenberg's ECFanGrid Case Study by Axair Fans.
Rosenberg Canada
 
Zehnder ComfoAir Q Brochure Final
Zehnder ComfoAir Q Brochure FinalZehnder ComfoAir Q Brochure Final
Zehnder ComfoAir Q Brochure Final
Chris Kemp
 
Filter Selection w Window Filter Assembly
Filter Selection w Window Filter AssemblyFilter Selection w Window Filter Assembly
Filter Selection w Window Filter Assembly
Aaron Leftwick
 
Camfil farr facilities show presentation
Camfil farr facilities show presentationCamfil farr facilities show presentation
Camfil farr facilities show presentation
Simply Marcomms
 

Similar to Catalog gjx (20)

Underground car parking ventilation system
Underground car parking ventilation systemUnderground car parking ventilation system
Underground car parking ventilation system
 
Rosenberg's ECFanGrid Case Study by Axair Fans.
Rosenberg's ECFanGrid Case Study by Axair Fans.Rosenberg's ECFanGrid Case Study by Axair Fans.
Rosenberg's ECFanGrid Case Study by Axair Fans.
 
Industrial Air Compressor Distributor In NY - CS Industrial Services
Industrial Air Compressor Distributor In NY - CS Industrial ServicesIndustrial Air Compressor Distributor In NY - CS Industrial Services
Industrial Air Compressor Distributor In NY - CS Industrial Services
 
Screw air compressor usa
Screw air compressor usaScrew air compressor usa
Screw air compressor usa
 
All Energy Exhibition & Conference, Glasgow, May 2017
All Energy Exhibition & Conference, Glasgow, May 2017All Energy Exhibition & Conference, Glasgow, May 2017
All Energy Exhibition & Conference, Glasgow, May 2017
 
ELGI Airmate Air Accessories Total Compressed Air Solutions
ELGI Airmate Air Accessories Total Compressed Air SolutionsELGI Airmate Air Accessories Total Compressed Air Solutions
ELGI Airmate Air Accessories Total Compressed Air Solutions
 
Sb compact dx_ver.1.0_en
Sb compact dx_ver.1.0_enSb compact dx_ver.1.0_en
Sb compact dx_ver.1.0_en
 
CPD Presentation: Car Park Ventilation
CPD Presentation: Car Park VentilationCPD Presentation: Car Park Ventilation
CPD Presentation: Car Park Ventilation
 
Zehnder ComfoAir Q Brochure Final
Zehnder ComfoAir Q Brochure FinalZehnder ComfoAir Q Brochure Final
Zehnder ComfoAir Q Brochure Final
 
Filter Selection w Window Filter Assembly
Filter Selection w Window Filter AssemblyFilter Selection w Window Filter Assembly
Filter Selection w Window Filter Assembly
 
Design and Analysis of Air Intake Manifold for Formula Student Cars
Design and Analysis of Air Intake Manifold for Formula Student CarsDesign and Analysis of Air Intake Manifold for Formula Student Cars
Design and Analysis of Air Intake Manifold for Formula Student Cars
 
Air Flow Characteristics of an Air Cooled Condenser used in Thermal Power Plant
Air Flow Characteristics of an Air Cooled Condenser used in Thermal Power PlantAir Flow Characteristics of an Air Cooled Condenser used in Thermal Power Plant
Air Flow Characteristics of an Air Cooled Condenser used in Thermal Power Plant
 
Reducing running costs of a compressed air system
Reducing running costs of a compressed air system Reducing running costs of a compressed air system
Reducing running costs of a compressed air system
 
Car parking ventilation (mep intern.)
Car parking ventilation (mep intern.)Car parking ventilation (mep intern.)
Car parking ventilation (mep intern.)
 
Design and Optimization of Air Compressor Intake Valve Body Casing using ANSYS
Design and Optimization of Air Compressor Intake Valve Body Casing using ANSYSDesign and Optimization of Air Compressor Intake Valve Body Casing using ANSYS
Design and Optimization of Air Compressor Intake Valve Body Casing using ANSYS
 
Filtros Ingersoll Rand (F-Series Filters)
Filtros Ingersoll Rand (F-Series Filters)Filtros Ingersoll Rand (F-Series Filters)
Filtros Ingersoll Rand (F-Series Filters)
 
Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...Can car park ventilation schemes be more energy efficient? Yes – and they sho...
Can car park ventilation schemes be more energy efficient? Yes – and they sho...
 
Camfil farr facilities show presentation
Camfil farr facilities show presentationCamfil farr facilities show presentation
Camfil farr facilities show presentation
 
Camfil farr facilities show presentation
Camfil farr facilities show presentationCamfil farr facilities show presentation
Camfil farr facilities show presentation
 
Camfil farr facilities show presentation
Camfil farr facilities show presentationCamfil farr facilities show presentation
Camfil farr facilities show presentation
 

Recently uploaded

scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
HenryBriggs2
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
9953056974 Low Rate Call Girls In Saket, Delhi NCR
 

Recently uploaded (20)

Online food ordering system project report.pdf
Online food ordering system project report.pdfOnline food ordering system project report.pdf
Online food ordering system project report.pdf
 
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
scipt v1.pptxcxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxxx...
 
Thermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - VThermal Engineering-R & A / C - unit - V
Thermal Engineering-R & A / C - unit - V
 
Thermal Engineering Unit - I & II . ppt
Thermal Engineering  Unit - I & II . pptThermal Engineering  Unit - I & II . ppt
Thermal Engineering Unit - I & II . ppt
 
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
Bhubaneswar🌹Call Girls Bhubaneswar ❤Komal 9777949614 💟 Full Trusted CALL GIRL...
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKARHAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
HAND TOOLS USED AT ELECTRONICS WORK PRESENTED BY KOUSTAV SARKAR
 
Work-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptxWork-Permit-Receiver-in-Saudi-Aramco.pptx
Work-Permit-Receiver-in-Saudi-Aramco.pptx
 
Hostel management system project report..pdf
Hostel management system project report..pdfHostel management system project report..pdf
Hostel management system project report..pdf
 
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptxS1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
S1S2 B.Arch MGU - HOA1&2 Module 3 -Temple Architecture of Kerala.pptx
 
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
457503602-5-Gas-Well-Testing-and-Analysis-pptx.pptx
 
Employee leave management system project.
Employee leave management system project.Employee leave management system project.
Employee leave management system project.
 
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
💚Trustworthy Call Girls Pune Call Girls Service Just Call 🍑👄6378878445 🍑👄 Top...
 
A Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna MunicipalityA Study of Urban Area Plan for Pabna Municipality
A Study of Urban Area Plan for Pabna Municipality
 
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
Jaipur ❤CALL GIRL 0000000000❤CALL GIRLS IN Jaipur ESCORT SERVICE❤CALL GIRL IN...
 
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best ServiceTamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
Tamil Call Girls Bhayandar WhatsApp +91-9930687706, Best Service
 
Learn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic MarksLearn the concepts of Thermodynamics on Magic Marks
Learn the concepts of Thermodynamics on Magic Marks
 
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
NO1 Top No1 Amil Baba In Azad Kashmir, Kashmir Black Magic Specialist Expert ...
 
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
Call Girls in South Ex (delhi) call me [🔝9953056974🔝] escort service 24X7
 
Generative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPTGenerative AI or GenAI technology based PPT
Generative AI or GenAI technology based PPT
 

Catalog gjx

  • 1. April 2018 GreenJet® Transfer Fans Model GJX High Performance Axial Transfer Fan
  • 2. 2 GreenJet® As cars park in an underground parking structure, carbon monoxide (CO) and other noxious fumes are emitted into the atmosphere. There is a need for an efficient ventilation system to remove these toxins, circulate fresh air into the car park, and assist firefighters with smoke control in the case of a fire emergency. The GreenJet® model GJX includes a range of performances to accommodate your needs for parking garage ventilation. While ducted ventilation has been the standard for many years, innovation in technology has shifted systems toward ductless designs. Ductless designs use transfer fans to dilute and remove contaminants and control the smoke. In addition, these systems provide greater control and operational savings. Fresh air intended to replace contaminated exhaust is removed along with contaminates through each duct. The illustration below shows ducts closer to the supply air remove much of the fresh air, leaving mostly toxic air at the farthest duct, causing a hazardous condition. GreenJet transfer fans push fresh supply air through the parking area towards the exhaust fan(s). This removes a higher proportion of contaminated air and replaces it with clean air. Advantages: • Simplified Design: Eliminates the need and expense of designing a duct system. • Lower Construction Cost: GreenJet fans require less height against the ceiling than a ducted system. This means the required height of each level is less, reducing excavation and lowering overall construction cost. • Lower Installation Cost: A typical GreenJet system results in less installation time. • Improved Operational Costs: Eliminating ductwork reduces the system static pressure and allows for smaller supply and exhaust fans to run using less power. The use of third-party exhaust sensors allows for demand-based ventilation. • Reduced Maintenance: GreenJet fans are more accessible for maintenance than traditional systems, and eliminate duct cleaning. • Enhanced Safety: GreenJet fans are more efficient at removing noxious fumes and clearing smoke, resulting in a safer environment. UL/cUL 705 Listed Power Ventilator File No. E40001 UL/cUL Power Ventilator for Smoke Control Systems File No. MH17511 AMCA licensed air performance may be found in Greenheck’s Computer Aided Product Selection program (CAPS). Improved Exhaust Effectiveness with GreenJet Carbon Monoxide (CO) Contaminate Concentration Level Low HighMedium Exhaust Air Exhaust Air Supply Air Supply Air Ducted System Ductless with GreenJet Transfer Fans
  • 3. 3 Construction and Installation Ductless Garage Ventilation: Supply – Transfer – Exhaust Typical installation and operation of ductless, enclosed parking garage HVAC systems consist of supply fans, GJX GreenJet fans, and exhaust fans. Under normal conditions, fresh air is introduced into the garage through entrance/exit ramps and through a dedicated supply fan. The GreenJet model GJX fans are positioned to direct air from one end of the garage to the other, supplying fresh air to the structure while also mixing and pushing contaminated air towards the point of exhaust (typically on the end opposite the supply). An exhaust fan removes the contaminated air from the garage. A timer, occupancy monitor, or demand-based control system can operate the entire system. The GJX fans are available with Smoke Control certification for integration into a smoke exhaust control system. GJX is intended to provide emergency responders a clear path for better and more effective access. GJX GreenJet Exhaust Fan Inlet and Outlet Silencers Inlet and Outlet Guard Casing Flush Mounting Brackets GreenJet model GJX is a low profile, quiet fan suspended from the ceiling. Construction features include: • Durable steel casing with Permatector™ coating for corrosive environments • Mounting brackets flush with the top of the silencers for no additional height • Airfoil propellers move large volumes of air with high efficiency in a small diameter fan • Sound absorbing inlet and outlet silencers with perforated inner liner for maximum sound reduction • Aerodynamic inlet design improving performance efficiency. When installed ceiling hung, GreenJet moves the air towards the exhaust area by effectively creating a continuous flow, avoiding the creation of stagnant zones where air may become trapped.
  • 4. 4 CFD velocity profile for a GJX-41 showing 200 fpm throw of 110 ft (33 m). Car park layout with GJX velocity profiles added giving initial placement locations. Fan Placement and Velocity Profiles Successful operation requires the correct fan quantities, placement, and direction of the transfer fans. Discharge velocity profiles is a tool to provide a starting point for initial fan placement. GreenJet velocity profiles are available for integration in an AutoCAD® layout. The images below show the use of Computational Fluid Dynamics (CFD) to develop a 200 fpm velocity profile and integration into a design layout. Design Layout CFD Analysis There are different CFD analyses often used in parking garages: • Velocity analysis provides information on air movement but not the effect on contaminate removal. • CO analysis provides the effectiveness in removing contaminants from the parking garage. • Smoke removal analysis shows how quickly and effectively smoke is removed from the source point. Natural airflow paths from supply to exhaust locations exist within a building structure. Integrating transfer fans moves air outside of these pathways. An analysis on CO levels illustrates the impact of the GJX GreenJet fan installation on a parking garage. Without Jet Fans With Jet Fans
  • 5. 5 System Integration and Payback Integration of GreenJet model GJX fans into Demand-Based Application A demand-based system is controlled using sensors that measure parts per million (ppm) of contaminants and sends information to the the facilities controller to increase or decrease speed based on actual conditions. The image below shows how the GJX GreenJet is integrated into this application. Energy Saving with Demand-Based Ventilation There are two methods for controlling parking ventilation systems; an On / Off system where the ventilation is on a timer or occupancy sensor, or demand-based with sensors changing the ventilation rate with contaminate levels. Simplified Example: Five times the difference in prescribed ventilation rates between systems with and systems without air quality monitoring and control. Control Method Operation Ventilation Rate* (cfm per ft² of garage floor) Operating Time (hours) Daily Operating Volume (ft³ per ft² of garage floor) On / Off Full 0.75 12 540 Demand-Based Full 0.75 2 (average) 180 Reduced 0.15 10 *Full flow uses a 0.75 cfm/ft² (ASHRAE 62.1-2013) ventilation rate per square foot for garage area and reduced flow using 0.15 cfm/ft² (California Title 24). A VFD can be used with multiple GJX fans in a zone for lower controller costs. In this example, a demand-based method results in a 66% reduction in the ventilation requirement and related energy savings.
  • 6. 6 Performance and Dimensional Data GJX - 31 - L - 160 - 06 25 - M 20 - X Fan Size (cm) 31, 36, 41 Fan RPM M = 3500 Hub Size Blade Pitch Number of Blades Motor Horsepower 7 = ¾ 10 = 1 15 = 1½ 20 = 2 Casing Certification None X - UL/cUL 705 Listed (Electrical) HTUL - UL/cUL HT Listed (Emergency Smoke Control) 30 = 3 Model Number Code Silencer Silencer Junction Box Fan AIRFLOW DIRECTION B BA C I Dia. D E G H F Size (cm) A B C D E F G H I Weight* lbs. (kg) 31 17.01 (432) 24.49 (622) 14.80 (376) 12.24 (311) 16.18 (411) 10.28 (261) 10.04 (255) 8.31 (211) 0.47 (12) 143 (65) 36 17.01 (432) 28.50 (724) 14.80 (376) 14.25 (362) 18.19 (462) 12.28 (312) 11.02 (280) 9.29 (236) 0.47 (12) 152 (69) 41 20.00 (508) 32.52 (826) 17.81 (452) 16.26 (413) 20.20 (513) 14.29 (363) 12.05 (306) 10.31 (262) 0.47 (12) 170 (77) Dimensions shown in inches (millimeters). *Weight includes largest motor for size. Dimensional Data Fan Size Airflow cfm (m³/hr) Thrust lbs (N)* Throw ft (m)** Power Bhp (kW) Motor Size HP (kW) Motor Speed dBA Inlet @ 5 ft GJX-31-160-0634 2,640 (4,485) 5.6 (24.9) 85 (25.9) 1.26 (0.94) 1.50 (1.1) 3500 71 GJX-31-160-0625 2,250 (3,823) 4.1 (18.2) 75 (22.9) 0.74 (.55) 0.75 (0.56) 3500 69 GJX-36-160-0627 4,070 (6,915) 9.9 (44.0) 100 (30.5) 1.94 (1.45) 2.00 (1.5) 3500 73 GJX-36-160-0622 3,620 (6,150) 7.8 (34.7) 90 (27.4) 1.48 (1.1) 1.50 (1.1) 3500 74 GJX-41-160-0623 6,010 (10,211) 16.6 (73.8) 115 (35.1) 2.94 (2.19) 3.00 (2.2) 3500 77 GJX-41-160-0616 5,050 (8,580) 11.7 (52.0) 105 (32.0) 1.95 (1.45) 2.00 (1.5) 3500 78 *Air density = 0.075 lb./ft3 **Throw distance for 200 ft/min The performance shown is not AMCA licensed as it includes losses from appurtenances (accessories) in the airstream. Licensed data may be found in Greenheck’s Computer Aided Product Selection program (CAPS).
  • 7. 7 Emergency High Temperature Smoke Removal The GreenJet model GJX is UL Listed for Smoke Control. It is high temperature performance tested and rated for design time used in emergency heat and smoke exhaust applications. Emergency Temperature Options: • 150°C / 5 Hours (302°F / 5 Hours) - per British Standard 7346 (Components for smoke control systems) • 260°C / 4 Hours (500°F / 4 Hours) - per Industrial Risk Insurers (North America) UL/cUL Power Ventilator for Smoke Control Systems File No. MH17511 Certifications & Additional Products for Car Park Ventilation Life Safety Dampers Life safety dampers are intended to protect openings in walls, ceilings, floors and/or partitions to prevent the spread of fire and/or smoke. These are necessary in multi-level car parks with common shafts to prevent the spread of smoke from one floor to another. Fire dampers are required by all building codes to maintain the required fire resistance ratings of walls, partitions and floors when penetrated by air ducts and transfer openings. These products were tested and classified in accordance with UL Standard 555. Smoke Dampers have two applications: 1. These may be applied in a passive smoke control system where they simply close and prevent the circulation of air and smoke through a duct or a ventilation opening in a smoke barrier. 2. These may be applied as part of an engineered smoke control system designed to control the spread of smoke using walls and floors as barriers and using the building’s HVAC system and/or dedicated fans to create pressure differences. These products are tested and classified in accordance with UL Standard 555S. Combination Fire Smoke Dampers perform the function of both a fire damper and a smoke damper. Building layouts and designs often combine fire and smoke rated partitions and barriers requiring the installation of both a fire damper and smoke damper at the same location. These products are tested and classified in accordance with both UL 555 and UL 555S. Supply and Exhaust Fans Greenheck’s high performance fans are ideal for air ventilation in commercial, industrial or institutional buildings. Design and construction are well suited for indoor or outdoor applications and can be easily installed in ducted or non-ducted systems. Fans are designed to reduce operating costs with improved efficiency. • AMCA Licensed Performance • UL/cUL Listed for Electrical 705 • UL/cUL Listed for Power Ventilators for Smoke Control Systems • Spark resistant construction
  • 8. As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without notice. Specific Greenheck product warranties are located on greenheck.com within the product area tabs and in the Library under Warranties. P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com Our Commitment 00.LAB.1020 R1 4-2018 RG Copyright © 2018 Greenheck Fan Corp. Enjoy Greenheck’s extraordinary service, before, during and after the sale. Greenheck offers added value to our wide selection of top performing, energy-efficient products by providing several unique Greenheck service programs. • Our Quick Delivery Program ensures shipment of our in-stock products within 24 hours of placing your order. Our Quick Build made-to-order products can be produced in 1-3- 5-10-15- or 25 day production cycles, depending upon their complexity. • Greenheck’s free Computer Aided Product Selection program (CAPS), rated by many as the best in the industry, helps you conveniently and efficiently select the right products for the challenge at hand. • Greenheck has been Green for a long time! Our energy-saving products and ongoing corporate commitment to sustainability can help you qualify for LEED credits. • Our 3D service allows you to download at no charge, lightweight, easy-to-use AutoDesk® Revit® 3D drawings for many of our ventilation products. Find out more about these special Greenheck services at greenheck.com Design and Selection Support Prepared to Support Green Building Efforts