SlideShare a Scribd company logo
1 of 92
Download to read offline
JUBAIL BULK PLANT
SUBSTATION 204
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 12.02.2015
Operator: Mustang HDP
JUBAIL BULK PLANT
12.02.2015
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
BATTERY ROOM (103) / Summary
Height of Room: 6.500 m, Mounting Height: 5.000 m, Light loss factor: 0.60 Values in Lux, Scale 1:93
Surface [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 510 434 563 0.852
Floor 49 474 385 526 0.812
Ceiling 86 297 249 348 0.836
Walls (4) 86 379 246 568 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.749, Ceiling / Working Plane: 0.583.
Luminaire Parts List
Specific connected load: 8.78 W/m² = 1.72 W/m²/100 lx (Ground area: 60.48 m²)
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 9
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 46098 Total: 46098 531.0
Page 3
JUBAIL BULK PLANT
12.02.2015
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
MECHANICAL ROOM (102) / Summary
Height of Room: 6.500 m, Mounting Height: 6.500 m, Light loss factor: 0.60 Values in Lux, Scale 1:88
Surface [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 488 423 533 0.866
Floor 49 455 380 512 0.837
Ceiling 86 358 317 682 0.886
Walls (4) 86 423 285 741 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.887, Ceiling / Working Plane: 0.733.
Luminaire Parts List
Specific connected load: 9.30 W/m² = 1.90 W/m²/100 lx (Ground area: 57.12 m²)
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 9
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 46098 Total: 46098 531.0
Page 3
JUBAIL BULK PLANT
12.02.2015
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
SWITCHGEAR ROOM (101) / Summary
Height of Room: 6.500 m, Mounting Height: 5.000 m, Light loss factor: 0.60 Values in Lux, Scale 1:183
Surface [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 441 346 484 0.783
Floor 49 425 316 473 0.744
Ceiling 86 242 199 290 0.821
Walls (6) 86 306 201 422 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.694, Ceiling / Working Plane: 0.549.
Luminaire Parts List
Specific connected load: 5.99 W/m² = 1.36 W/m²/100 lx (Ground area: 285.55 m²)
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 29
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 148538 Total: 148538 1711.0
Page 3
JUBAIL BULK PLANT
12.02.2015
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TELECOM ROOM (104) / Summary
Height of Room: 6.500 m, Mounting Height: 6.500 m, Light loss factor: 0.60 Values in Lux, Scale 1:27
Surface [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 580 524 609 0.904
Floor 49 489 446 527 0.911
Ceiling 86 999 809 1312 0.810
Walls (4) 86 784 313 1857 /
Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.441, Ceiling / Working Plane: 1.723.
Luminaire Parts List
Specific connected load: 30.10 W/m² = 5.19 W/m²/100 lx (Ground area: 5.88 m²)
No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W]
1 3
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 15366 Total: 15366 177.0
Page 3
JUBAIL BULK PLANT
FOAM SKID SHELTER
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 10.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
10.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
FOAM SKID SHELTER / Summary
450
480 480
480
480
510
510
510 510
510
510
510
510
510
510
510
540
540
540 540
540
540
540
540
540
540
540
11.00 m
0.00 1.38 4.13 6.88 9.63
13.70 m
0.00
1.37
4.11
6.85
9.59
12.33
Height of Room: 5.100 m, Mounting Height: 5.100 m, Light loss factor: 0.55 Values in Lux, Scale 1:176
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 507 426 557 0.840
Floor 49 483 393 540 0.814
Ceiling 86 305 271 507 0.888
Walls (4) 86 392 313 525 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 21 21
Lower Wall 21 21
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.787, Ceiling / Working Plane: 0.602.
Luminaire Parts List
Specific connected load: 7.83 W/m² = 1.54 W/m²/100 lx (Ground area: 150.70 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 20
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 102440 Total: 102440 1180.0
Page 3
JUBAIL BULK PLANT
SECURITY SUPPORT BUILDING
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 10.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
10.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
BATTERY ROOM (110) / Summary
680
680
720
720
720
720
720
720
720
720
760
760
760 760
760
760
760
760
760
800
4.80 m
0.00 1.20 3.60
6.60 m
0.00
1.10
3.30
5.50
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:85
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 741 646 802 0.871
Floor 49 668 544 729 0.815
Ceiling 86 447 403 762 0.900
Walls (4) 86 561 428 741 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.780, Ceiling / Working Plane: 0.604.
Luminaire Parts List
Specific connected load: 11.17 W/m² = 1.51 W/m²/100 lx (Ground area: 31.68 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 6
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 30732 Total: 30732 354.0
Page 3
JUBAIL BULK PLANT
10.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
ELECTRICAL ROOM (109) / Summary
360
360
390
390
390
390
390
390
390
420
420
420
420
420
420
420
420
420
420
450
450 450
450
450
450
450
450
450
450
450
4.00 m
0.00 2.00
4.50 m
0.00
1.13
3.38
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:58
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 407 341 465 0.838
Floor 49 353 288 396 0.816
Ceiling 86 243 203 518 0.836
Walls (4) 86 298 215 452 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.751, Ceiling / Working Plane: 0.598.
Luminaire Parts List
Specific connected load: 6.56 W/m² = 1.61 W/m²/100 lx (Ground area: 18.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 10244 Total: 10244 118.0
Page 3
JUBAIL BULK PLANT
10.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TELECOM ROOM (108) / Summary
660
660
690
690
690
690
690
690
690
720
720
720 720
720
720
720
720
720
720
720
4.00 m
0.00 1.00 3.00
2.00 m
0.00
1.00
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:29
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 701 618 755 0.881
Floor 49 585 502 645 0.857
Ceiling 86 525 439 759 0.837
Walls (4) 86 589 378 942 /
Workplane:
Height: 0.760 m
Grid: 32 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.899, Ceiling / Working Plane: 0.748.
Luminaire Parts List
Specific connected load: 14.75 W/m² = 2.10 W/m²/100 lx (Ground area: 8.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 10244 Total: 10244 118.0
Page 3
JUBAIL BULK PLANT
10.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
SECURITY ROOM (107) / Summary
560
600
600
600
600
640
640
640
640
640
640
640
640
640
640
680
680
680
680
680
680
680
680
680
3.40 m
0.00 1.70
5.00 m
0.00
0.83
2.50
4.17
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:65
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 634 546 705 0.860
Floor 49 550 445 622 0.808
Ceiling 86 396 323 711 0.816
Walls (4) 86 482 350 765 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.785, Ceiling / Working Plane: 0.624.
Luminaire Parts List
Specific connected load: 10.41 W/m² = 1.64 W/m²/100 lx (Ground area: 17.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 3
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 15366 Total: 15366 177.0
Page 3
JUBAIL BULK PLANT
11.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
PRAYER ROOM (102) / Summary
520
520
560
560
560
560
560
560
560
600
600
600
600
600
600
600
640
640 640
640
640
640
640
640
640
640
680
680
680
680
680
680
680
680
680
680
2.80 m
0.00 1.40
2.80 m
0.00
0.70
2.10
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:36
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 604 508 692 0.842
Floor 49 498 416 554 0.836
Ceiling 86 374 325 479 0.869
Walls (4) 86 457 329 834 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.804, Ceiling / Working Plane: 0.620.
Luminaire Parts List
Specific connected load: 8.93 W/m² = 1.48 W/m²/100 lx (Ground area: 7.84 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 6930 Total: 6930 70.0
Page 3
JUBAIL BULK PLANT
11.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
BREAK ROOM (103) / Summary
600
600
640
640
640
640
640
640
680
680
680
680
680
680
680
680
680
680
680
4.20 m
0.00 1.05 3.15
3.80 m
0.00
0.95
2.85
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:49
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 667 564 720 0.845
Floor 49 582 469 637 0.805
Ceiling 86 394 359 492 0.912
Walls (4) 86 505 386 654 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 18 18
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.794, Ceiling / Working Plane: 0.590.
Luminaire Parts List
Specific connected load: 8.77 W/m² = 1.32 W/m²/100 lx (Ground area: 15.96 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
11.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
WATER HEATER ROOM (105) / Summary
640
640
660
660
660
660
660
680
680
680
680
680
680
680
680
700
700 700
700
700
700
2.25 m
0.00 1.13
1.30 m
0.00
0.10
0.65
1.20
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:17
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 668 611 708 0.915
Floor 49 508 453 539 0.891
Ceiling 86 651 575 868 0.883
Walls (4) 86 632 329 1166 /
Workplane:
Height: 0.760 m
Grid: 16 x 8 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 1.043, Ceiling / Working Plane: 0.975.
Luminaire Parts List
Specific connected load: 20.17 W/m² = 3.02 W/m²/100 lx (Ground area: 2.93 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 1
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 5122 Total: 5122 59.0
Page 3
JUBAIL BULK PLANT
11.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TOILET (102) / Summary
540
540
540
540
540
630
630
630
630
630
630
630
630
630
630
630
630
630
630
630
720
720
720
720
720
810
810
810
810
810
810
810
2.25 m
0.00 0.56 1.69
4.60 m
0.00
1.15
3.45
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:60
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 657 444 852 0.676
Floor 49 572 419 644 0.733
Ceiling 86 307 254 380 0.828
Walls (4) 86 371 256 616 /
Workplane:
Height: 0.760 m
Grid: 128 x 64 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.560, Ceiling / Working Plane: 0.468.
Luminaire Parts List
Specific connected load: 17.00 W/m² = 2.59 W/m²/100 lx (Ground area: 10.35 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 8552 Total: 8552 176.0
Page 3
JUBAIL BULK PLANT
FSF SUPPORT BUILDING
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 22.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
09.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
OFFICE - FSF SUPPORT BUILDING / Summary
660 660
690
690
690
690
720
720
720
720
720 720
720
720
720
720
720
750
750
750
750
750 750 750
750
750
750
750
3.70 m
0.00 0.93 2.78
3.90 m
0.00
0.20
0.97
2.92
3.70
Height of Room: 2.650 m, Mounting Height: 2.750 m, Light loss factor: 0.60 Values in Lux, Scale 1:51
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 712 633 759 0.889
Floor 49 611 489 671 0.801
Ceiling 86 430 389 568 0.904
Walls (4) 86 544 385 707 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 16 17
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.805, Ceiling / Working Plane: 0.604.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 9.70 W/m² = 1.36 W/m²/100 lx (Ground area: 14.43 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
10.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
BREAK ROOM (102) - FSF SUPPORT BUILDING / Summary
340
340
340
360
360
360
360
360
360
360
360
360
360
360
380
380
380 380
380
380
380
380
380
380
400
400
400 400
400
400
400
400
400
400
2.50 m
0.00 1.25
2.50 m
0.00
0.20
1.25
2.30
Height of Room: 2.650 m, Mounting Height: 2.650 m, Light loss factor: 0.60 Values in Lux, Scale 1:33
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 366 316 415 0.864
Floor 49 288 243 319 0.842
Ceiling 86 217 168 239 0.773
Walls (4) 86 266 181 354 /
Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.770, Ceiling / Working Plane: 0.594.
Proportion of points with less than 400 lx (for IEQ-7): 85.94%.
Luminaire Parts List
Specific connected load: 5.60 W/m² = 1.53 W/m²/100 lx (Ground area: 6.25 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 1
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 3465 Total: 3465 35.0
Page 3
JUBAIL BULK PLANT
10.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TOILET (103) - FSF SUPPORT BUILDING / Summary
600
650
650
700
700
700
700
700
700
750
750
750
750
750
750
750
800
800 800 800 800
800
800
800
800
800
800
2.80 m
0.00 0.70 2.10
1.30 m
0.00
0.10
0.65
1.20
Height of Room: 2.650 m, Mounting Height: 2.750 m, Light loss factor: 0.60 Values in Lux, Scale 1:21
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 720 571 820 0.793
Floor 49 571 435 655 0.762
Ceiling 86 362 293 394 0.811
Walls (4) 86 441 305 597 /
Workplane:
Height: 0.760 m
Grid: 64 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.634, Ceiling / Working Plane: 0.502.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 24.18 W/m² = 3.36 W/m²/100 lx (Ground area: 3.64 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 4276 Total: 4276 88.0
Page 3
JUBAIL BULK PLANT
OPERATOR SHELTER
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 09.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
09.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
OPERATOR SHELTER / Summary
630
630
660 660
660
660
690
690
690 690
690
690
690
690
690
690
690
720
720
720
720
720
720
720
720
3.80 m
0.00 0.95 2.85
3.70 m
0.00
0.20
0.93
2.78
3.50
Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:48
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 678 614 726 0.906
Floor 49 582 477 639 0.819
Ceiling 86 432 387 564 0.895
Walls (4) 86 535 379 732 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.839, Ceiling / Working Plane: 0.638.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 9.96 W/m² = 1.47 W/m²/100 lx (Ground area: 14.06 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
09.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TOILET (102) - OPERATOR SHELTER / Summary
700
700
750 750
750
750
800
800 800 800 800
800
800
800
800
800
800
850
850 850 850
850
850
850
850
850
850
850
3.70 m
0.00 0.20 0.93 2.78 3.50
2.00 m
0.00
0.20
0.50
1.50
1.80
Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:27
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 789 645 869 0.817
Floor 49 661 507 769 0.768
Ceiling 86 394 323 503 0.820
Walls (4) 86 476 327 775 /
Workplane:
Height: 0.760 m
Grid: 64 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.620, Ceiling / Working Plane: 0.499.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 23.78 W/m² = 3.01 W/m²/100 lx (Ground area: 7.40 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 8552 Total: 8552 176.0
Page 3
JUBAIL BULK PLANT
BILL OF LADING/PRINTER AREA
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 26.11.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
26.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
BILL OF LADING/PRINTER AREA / Summary
650
650
650
650
650
650
650
650
700 700
700
700
750
750
750 750
750
750
750
750
750
750
750
800
800 800 800
800
800
800
800
800
800
800
4.60 m
0.00 1.15 3.45
3.50 m
0.00
0.88
2.63
Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor: 0.50 Values in Lux, Scale 1:45
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 766 609 837 0.795
Floor 49 679 561 743 0.826
Ceiling 86 474 416 613 0.876
Walls (4) 86 587 454 756 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.801, Ceiling / Working Plane: 0.619.
Luminaire Parts List
Specific connected load: 14.66 W/m² = 1.91 W/m²/100 lx (Ground area: 16.10 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 20488 Total: 20488 236.0
Page 3
JUBAIL BULK PLANT
SEC RMU ROOM
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 14.01.2015
Operator: Mustang HDP
JUBAIL BULK PLANT
14.01.2015
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
SEC RMU ROOM / Summary
680 680
720
720
720
720
720
720 720
720
720 720
720
760
760
760
760
760
760 760
760
760
760
760
800
800
800
800
800
800 800
800
800
800
800
6.50 m
0.00 1.08 3.25 5.42
8.50 m
0.00
1.06
3.19
5.32
7.45
Height of Room: 5.400 m, Mounting Height: 5.400 m, Light loss factor: 0.60 Values in Lux, Scale 1:110
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 748 631 816 0.844
Floor 49 694 586 756 0.845
Ceiling 86 510 467 861 0.915
Walls (4) 86 621 465 874 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.852, Ceiling / Working Plane: 0.682.
Luminaire Parts List
Specific connected load: 12.81 W/m² = 1.71 W/m²/100 lx (Ground area: 55.25 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 12
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 61464 Total: 61464 708.0
Page 3
JUBAIL BULK PLANT
SECURITY GUARDHOUSE & GATE SUNSHADE
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 22.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
08.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
SECURITY GUARDHOUSE / Summary
400
400
400
400
450
450
450
450
450
450
450
450 450
450
450
450
500
500
500
500
500
500
500
500
500
500
500
550
550
550
550
550
550
550
550
7.00 m
0.00 1.17 3.50 5.83
5.00 m
0.00
1.25
3.75
Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:65
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 496 356 559 0.719
Floor 49 455 346 501 0.761
Ceiling 86 280 243 346 0.867
Walls (4) 86 368 250 466 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.760, Ceiling / Working Plane: 0.566.
Proportion of points with less than 400 lx (for IEQ-7): 1.37%.
Luminaire Parts List
Specific connected load: 6.00 W/m² = 1.21 W/m²/100 lx (Ground area: 35.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 6
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 20790 Total: 20790 210.0
Page 3
JUBAIL BULK PLANT
08.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
GATE HOUSE SUNSHADE / Summary
320 320
320
320 320
320
320
320 320 320
320 320 320
320
320 320
320 320 320
400
400
400 400 400
400 400 400
400 400 400
400 400 400
400 400
400
400
22.00 m
0.00 8.25 13.75
38.00 m
0.00
3.17
9.50
15.83
22.16
28.49
34.82
Height of Room: 6.130 m, Mounting Height: 5.130 m, Light loss factor: 0.50 Values in Lux, Scale 1:488
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 367 131 516 0.357
Floor 20 357 176 460 0.494
Ceiling 80 64 41 73 0.652
Walls (4) 50 101 43 231 /
Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.000 m
UGR Lengthways- Across to luminaire axis
Left Wall 22 22
Lower Wall 22 22
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.249, Ceiling / Working Plane: 0.173.
Proportion of points with less than 400 lx (for IEQ-7): 79.13%.
Luminaire Parts List
Specific connected load: 7.67 W/m² = 2.09 W/m²/100 lx (Ground area: 836.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 24
PHILIPS BY461P 1xLED240S/740 WB GC
(1.000)
24000 24000 267.0
Total: 576000 Total: 576000 6408.0
Page 7
1952K - JUBAIL BULK PLANT
LOADING RACKS
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 29.06.2014
Operator: Mustang HDP
1952K - JUBAIL BULK PLANT
29.06.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
COOPER CROUSE-HINDS DMV 150 HPS DMVS2A150GP-RD739 / Luminaire Data
Sheet
Luminous emittance 1:
80
120
160
200
cd/klm η = 67%
C0 - C180 C90 - C270
0° 15° 30°
45°
60°
75°
90°
105°
105°
90°
75°
60°
45°
30° 15° 0°
Luminaire classification according to CIE: 98
CIE flux code: 31 60 91 98 67
DMV Class 1 Div 2 Hazardous Location luminaire
Luminous emittance 1:
Components:
•2 x
Glare Evaluation According to UGR
ρ Ceiling 70 70 50 50 30 70 70 50 50 30
ρ Walls 50 30 50 30 30 50 30 50 30 30
ρ Floor 20 20 20 20 20 20 20 20 20 20
Room Size
X Y
Viewing direction at right angles
to lamp axis
Viewing direction parallel
to lamp axis
2H 2H 29.0 30.5 29.3 30.8 31.1 29.0 30.5 29.3 30.8 31.1
3H 32.1 33.5 32.5 33.9 34.2 32.1 33.5 32.5 33.9 34.2
4H 33.7 35.1 34.1 35.4 35.8 33.7 35.1 34.1 35.4 35.8
6H 34.8 36.1 35.2 36.4 36.8 34.8 36.1 35.2 36.4 36.8
8H 35.1 36.3 35.5 36.7 37.1 35.1 36.3 35.5 36.7 37.1
12H 35.2 36.4 35.6 36.7 37.1 35.2 36.4 35.6 36.7 37.1
4H 2H 30.2 31.5 30.5 31.8 32.2 30.2 31.5 30.5 31.8 32.2
3H 33.4 34.6 33.8 35.0 35.4 33.4 34.6 33.8 35.0 35.4
4H 35.2 36.2 35.6 36.6 37.0 35.2 36.2 35.6 36.6 37.0
6H 36.3 37.2 36.8 37.7 38.1 36.3 37.2 36.8 37.7 38.1
8H 36.6 37.5 37.1 37.9 38.4 36.6 37.5 37.1 37.9 38.4
12H 36.8 37.6 37.3 38.0 38.5 36.8 37.6 37.3 38.0 38.5
8H 4H 35.8 36.6 36.3 37.1 37.5 35.8 36.6 36.3 37.1 37.5
6H 37.1 37.8 37.6 38.3 38.8 37.1 37.8 37.6 38.3 38.8
8H 37.5 38.1 38.0 38.6 39.1 37.5 38.1 38.0 38.6 39.1
12H 37.7 38.2 38.2 38.7 39.3 37.7 38.2 38.2 38.7 39.3
12H 4H 35.9 36.6 36.3 37.1 37.6 35.9 36.6 36.3 37.1 37.6
6H 37.2 37.8 37.7 38.3 38.8 37.2 37.8 37.7 38.3 38.8
8H 37.6 38.2 38.2 38.7 39.2 37.6 38.2 38.2 38.7 39.2
Variation of the observer position for the luminaire distances S
S = 1.0H +0.1 / -0.0 +0.1 / -0.0
S = 1.5H +0.1 / -0.1 +0.1 / -0.1
S = 2.0H +0.3 / -0.3 +0.3 / -0.3
Standard table BK10 BK10
Correction
Summand
19.8 19.8
Corrected Glare Indices referring to 16000lm Total Luminous Flux
Page 2
1952K - JUBAIL BULK PLANT
29.06.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
LOADING RACKS / Summary
200
240
240
240
240
240
280
280
280 280
280
280
280
280
280
280
280
320 320
320
320
320
320
320
320
320
320
320
30.00 m
0.00 2.50 7.50 12.50 17.50 22.50 27.50
20.00 m
0.00
2.00
6.00
10.00
14.00
18.00
Height of Room: 8.600 m, Mounting Height: 7.600 m, Light loss factor: 0.71 Values in Lux, Scale 1:257
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 275 180 334 0.655
Floor 20 263 182 315 0.693
Ceiling 80 83 65 91 0.781
Walls (4) 50 211 73 406 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
UGR Lengthways- Across to luminaire axis
Left Wall >30 >30
Lower Wall >30 >30
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.778, Ceiling / Working Plane: 0.301.
Proportion of points with less than 400 lx (for IEQ-7): 100.00%.
Luminaire Parts List
Specific connected load: 9.45 W/m² = 3.44 W/m²/100 lx (Ground area: 600.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 30
COOPER CROUSE-HINDS DMV 150 HPS
DMVS2A150GP-RD739 (1.000)
10687 16000 189.0
Total: 320619 Total: 480000 5670.0
Page 3
JUBAIL BULK PLANT
SALES AND INSPECTION BUILDING
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 16.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
16.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TRANSACTION COUNTER (103) / Summary
1000
1000
1040 1040
1040
1040
1080
1080
1080 1080
1080
1080
1080
1080
1080
1080
1080
1120
1120
1120 1120
1120
1120
1120
1120
1120
1120
1120
1160
1160
1160
1160
1160
1160
1160
3.00 m
0.00 0.75 2.25
2.80 m
0.00
0.70
2.10
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:36
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 1083 970 1170 0.896
Floor 49 905 758 988 0.837
Ceiling 86 715 674 840 0.942
Walls (4) 86 862 606 1268 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.858, Ceiling / Working Plane: 0.660.
Luminaire Parts List
Specific connected load: 16.67 W/m² = 1.54 W/m²/100 lx (Ground area: 8.40 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
ELECTRICAL ROOM (109) / Summary
720
720
720
760
760
760
760
760
760
760
760
760 760
760
800
800
800
800
800
800
800
800 800 800
800
5.10 m
0.00 1.27 3.82
3.60 m
0.00
0.20
0.90
2.70
3.40
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:47
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 772 679 833 0.880
Floor 49 675 557 740 0.826
Ceiling 86 489 415 633 0.850
Walls (4) 86 597 439 817 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.808, Ceiling / Working Plane: 0.634.
Luminaire Parts List
Specific connected load: 12.85 W/m² = 1.67 W/m²/100 lx (Ground area: 18.36 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 20488 Total: 20488 236.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
DRIVER'S WAITING ROOM (104) / Summary
480
480
480
480
510
510
510 510
510
510
510
510
510 510
510
510
510
510
510
510
510
540
540
540
540
540 540
540
540
540
540
540
540
540
540
540
540
540
540
540 540
540
540
540
540
540
540
540
540
540
540
570
570
570
10.50 m
0.00 1.31 3.94 6.57 9.20
9.60 m
0.00
1.20
3.60
6.00
8.40
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:124
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 515 432 579 0.838
Floor 49 483 363 533 0.752
Ceiling 86 279 254 372 0.913
Walls (4) 86 376 275 492 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 21 21
Lower Wall 21 21
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.739, Ceiling / Working Plane: 0.541.
Luminaire Parts List
Specific connected load: 5.56 W/m² = 1.08 W/m²/100 lx (Ground area: 100.80 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 16
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 55440 Total: 55440 560.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
PRAYER ROOM (105) / Summary
800
840
840
880
880
880 880
880
880
880
880
880
880
920
920
920
920
920
920
920
920
920
960
960
960
4.80 m
0.00 0.80 2.40 4.00
6.00 m
0.00
1.00
3.00
5.00
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 889 784 968 0.882
Floor 49 796 620 880 0.779
Ceiling 86 510 457 661 0.896
Walls (4) 86 668 506 882 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.783, Ceiling / Working Plane: 0.574.
Luminaire Parts List
Specific connected load: 10.94 W/m² = 1.23 W/m²/100 lx (Ground area: 28.80 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 9
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 31185 Total: 31185 315.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
VESTIBULE (101) / Summary
360
360
390
390 390
390
390
390
390
420
420
420
420
420
420
420
420
450
450
450
450
450
480
480
480
480
480
480
480
480
480
3.20 m
0.00 1.60
3.80 m
0.00
0.95
2.85
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:49
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 418 342 488 0.818
Floor 49 356 288 401 0.809
Ceiling 86 245 213 301 0.868
Walls (4) 86 308 217 490 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 16 17
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.770, Ceiling / Working Plane: 0.586.
Luminaire Parts List
Specific connected load: 5.76 W/m² = 1.38 W/m²/100 lx (Ground area: 12.16 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 6930 Total: 6930 70.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
FOYER (105) / Summary
570
570
570
600
600
600
600
600
600
630
630 630 630 630
630
630
630
630
630
630
630
3.60 m
0.00 0.90 2.70
2.00 m
0.00
0.10
1.00
1.90
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:26
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 606 532 653 0.878
Floor 49 496 410 545 0.826
Ceiling 86 398 347 474 0.872
Walls (4) 86 476 330 667 /
Workplane:
Height: 0.760 m
Grid: 32 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.849, Ceiling / Working Plane: 0.657.
Luminaire Parts List
Specific connected load: 9.72 W/m² = 1.60 W/m²/100 lx (Ground area: 7.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 6930 Total: 6930 70.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TELECOM ROOM (110) / Summary
570
570
600
600
600
600
600
600
600
630
630
630
630
630
630
630
630
630
630
660
660
660
660
660
3.00 m
0.00 1.50
3.50 m
0.00
0.20
0.88
2.63
3.30
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:45
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 610 535 666 0.878
Floor 49 513 436 562 0.850
Ceiling 86 404 344 562 0.852
Walls (4) 86 477 341 740 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.823, Ceiling / Working Plane: 0.663.
Luminaire Parts List
Specific connected load: 11.24 W/m² = 1.84 W/m²/100 lx (Ground area: 10.50 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 10244 Total: 10244 118.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
PRAYER ROOM (201) / Summary
760
760
800
800
800
800
800
800
800
840
840 840 840
840
840
840
840
840
840
840
840
7.10 m
0.00 0.89 2.66 4.43 6.20
3.90 m
0.00
0.20
0.97
2.92
3.70
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 813 709 878 0.872
Floor 49 722 562 832 0.779
Ceiling 86 468 431 610 0.922
Walls (4) 86 611 450 764 /
Workplane:
Height: 0.760 m
Grid: 32 x 16 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.783, Ceiling / Working Plane: 0.576.
Luminaire Parts List
Specific connected load: 10.11 W/m² = 1.24 W/m²/100 lx (Ground area: 27.69 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 8
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 27720 Total: 27720 280.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
CLERK OFFICE (203-204) / Summary
920
920
920
960
960
960
960
960
960
960
960
960
1000
1000
1000
1000
1000
1000
1000
2.50 m
0.00 0.63 1.88
3.90 m
0.00
0.97
2.92
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 965 846 1043 0.877
Floor 49 814 673 888 0.827
Ceiling 86 629 576 801 0.917
Walls (4) 86 765 524 1309 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 16 17
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.851, Ceiling / Working Plane: 0.652.
Luminaire Parts List
Specific connected load: 14.36 W/m² = 1.49 W/m²/100 lx (Ground area: 9.75 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TRUCK INSPECTOR OFFICE (206-207) / Summary
760
760
800
800
800 800
800
800
800
800
800
800
800
840
840
840
840
840
840
840
840
840
840
3.10 m
0.00 0.78 2.33
3.90 m
0.00
0.97
2.92
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 814 707 875 0.869
Floor 49 698 577 766 0.826
Ceiling 86 506 471 590 0.932
Walls (4) 86 632 444 896 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 16 17
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.825, Ceiling / Working Plane: 0.622.
Luminaire Parts List
Specific connected load: 11.58 W/m² = 1.42 W/m²/100 lx (Ground area: 12.09 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
PRODUCT SALES REP OFFICE (208-210) / Summary
760
760
800
800
800
800
840
840 840
840
840
840
840
840
840
880
880 880
880
880
880
880
880
880
880
880
3.00 m
0.00 0.75 2.25
3.90 m
0.00
0.97
2.92
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 837 728 901 0.870
Floor 49 716 591 784 0.825
Ceiling 86 524 485 617 0.926
Walls (4) 86 653 452 953 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 16 17
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.829, Ceiling / Working Plane: 0.626.
Luminaire Parts List
Specific connected load: 11.97 W/m² = 1.43 W/m²/100 lx (Ground area: 11.70 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
ELECTRICAL ROOM (211) / Summary
390
390
390
390
390
390
390 390
390
390
390
390
390
390
390
390
390
420
420
420 420
420
420
420
420
420
420
420
450
450
450 450
450
450
450
450
450
450
450
3.30 m
0.00 1.65
2.10 m
0.00
0.10
1.05
2.00
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:27
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 409 355 456 0.868
Floor 49 336 280 367 0.834
Ceiling 86 291 229 505 0.789
Walls (4) 86 330 222 540 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.862, Ceiling / Working Plane: 0.712.
Luminaire Parts List
Specific connected load: 8.51 W/m² = 2.08 W/m²/100 lx (Ground area: 6.93 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 1
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 5122 Total: 5122 59.0
Page 3
JUBAIL BULK PLANT
17.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
COMM. ROOM (213) / Summary
920
960
960
960
960
960
1000
1000 1000 1000
1000
1000
1000
1000
1000
1000
1000
1000
1040
1040 1040
1040
1040
1040
1040
1040
1040
2.80 m
0.00 0.70 2.10
1.70 m
0.00
0.10
0.85
1.60
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:22
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 984 891 1045 0.906
Floor 49 789 684 844 0.867
Ceiling 86 841 683 941 0.812
Walls (4) 86 880 516 1496 /
Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.974, Ceiling / Working Plane: 0.855.
Luminaire Parts List
Specific connected load: 24.79 W/m² = 2.52 W/m²/100 lx (Ground area: 4.76 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 10244 Total: 10244 118.0
Page 3
JUBAIL BULK PLANT
O & M BUILDING
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 21.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
ELECTRICAL AND UPS ROOM / Summary
360
390
390
390
390
390
390
420
420 420
420
420
420
420
420
420
420
420
420
420
420
420
420
420
420
420
420
450
450 450
450
450
450
450
450
450
450
450
9.00 m
0.00 1.50 4.50 7.50
7.00 m
0.00
1.75
5.25
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:90
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 416 341 468 0.820
Floor 49 384 299 424 0.780
Ceiling 86 236 201 517 0.851
Walls (4) 86 301 224 389 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 22 22
Lower Wall 21 21
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.733, Ceiling / Working Plane: 0.567.
Luminaire Parts List
Specific connected load: 5.62 W/m² = 1.35 W/m²/100 lx (Ground area: 63.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 6
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 30732 Total: 30732 354.0
Page 3
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TER UPS ROOM / Summary
360
400
400
400
400
400
400
440
440
440
440
440
440
440
440
480
480
480
480
480
480
480
480
4.50 m
0.00 2.25
6.00 m
0.00
1.00
3.00
5.00
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 438 350 520 0.799
Floor 49 388 308 442 0.795
Ceiling 86 253 213 576 0.840
Walls (4) 86 314 225 515 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.729, Ceiling / Working Plane: 0.578.
Luminaire Parts List
Specific connected load: 6.56 W/m² = 1.50 W/m²/100 lx (Ground area: 27.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 3
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 15366 Total: 15366 177.0
Page 3
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
RACK/SERVER ROOM / Summary
560
560
560
600
600
600
600
600
600
600
600
600
600
600
640
640
640
640
640
640
640
640
640
640
9.00 m
0.00 1.13 3.38 5.63 7.88
7.00 m
0.00
1.17
3.50
5.83
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:90
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 600 507 669 0.846
Floor 49 553 403 615 0.729
Ceiling 86 326 280 425 0.859
Walls (4) 86 437 328 526 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.745, Ceiling / Working Plane: 0.544.
Luminaire Parts List
Specific connected load: 6.67 W/m² = 1.11 W/m²/100 lx (Ground area: 63.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 12
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 41580 Total: 41580 420.0
Page 3
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
BATTERY ROOM / Summary
440
440
480
480
480
480
480
480
480
480
480
480
480
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
520
560
560
560
560
560
5.60 m
0.00 1.40 4.20
6.00 m
0.00
1.50
4.50
Height of Room: 3.300 m, Mounting Height: 2.800 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 497 403 567 0.811
Floor 49 445 342 487 0.767
Ceiling 86 265 224 304 0.844
Walls (4) 86 336 221 424 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 22 22
Lower Wall 22 22
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.676, Ceiling / Working Plane: 0.534.
Luminaire Parts List
Specific connected load: 7.02 W/m² = 1.41 W/m²/100 lx (Ground area: 33.60 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 20488 Total: 20488 236.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TER BATTERY ROOM / Summary
560
560 560
560
600
600
600
600
600
600
600
600
600
640
640 640
640
640
640
640
640
640
640
640 640
640
640
640
640
640
640
640
680
680
680
680
680
680
7.00 m
0.00 1.17 3.50 5.83
6.00 m
0.00
1.50
4.50
Height of Room: 3.300 m, Mounting Height: 2.800 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 613 509 694 0.830
Floor 49 556 423 615 0.760
Ceiling 86 331 269 382 0.814
Walls (4) 86 420 279 553 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 22 22
Lower Wall 22 22
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.685, Ceiling / Working Plane: 0.540.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 8.43 W/m² = 1.38 W/m²/100 lx (Ground area: 42.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 6
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 30732 Total: 30732 354.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
PRODUCT TESTING / Summary
570
600
600
600
600
600
600
600 600 630
630
630
630
630
630
630
630
630
660
660
660
660
660
660
660
4.70 m
0.00 1.18 3.53
6.00 m
0.00
1.00
3.00
5.00
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 621 537 678 0.865
Floor 49 553 425 609 0.769
Ceiling 86 349 309 422 0.886
Walls (4) 86 458 338 582 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.763, Ceiling / Working Plane: 0.562.
Luminaire Parts List
Specific connected load: 7.45 W/m² = 1.20 W/m²/100 lx (Ground area: 28.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 6
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 20790 Total: 20790 210.0
Page 3
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TELECOM ROOM / Summary
720
760
760
760
800
800
800 800
800
800
800
800
800
840
840 840
840
840
840
840
840
4.80 m
0.00 1.20 3.60
6.00 m
0.00
1.00
3.00
5.00
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 804 699 875 0.869
Floor 49 722 589 790 0.816
Ceiling 86 490 441 697 0.901
Walls (4) 86 612 475 881 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.785, Ceiling / Working Plane: 0.609.
Luminaire Parts List
Specific connected load: 12.29 W/m² = 1.53 W/m²/100 lx (Ground area: 28.80 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 6
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 30732 Total: 30732 354.0
Page 3
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
STORE ROOM FOR OPERATION / Summary
540
540
570
570
570
570
570
570
570
570
570
570 600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
600
4.80 m
0.00 1.20 3.60
4.00 m
0.00
0.20
1.00
3.00
3.80
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 577 501 625 0.869
Floor 49 502 397 547 0.791
Ceiling 86 329 294 406 0.892
Walls (4) 86 426 311 556 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 18 18
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.767, Ceiling / Working Plane: 0.571.
Luminaire Parts List
Specific connected load: 7.29 W/m² = 1.26 W/m²/100 lx (Ground area: 19.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TEA ROOM / Summary
350
350
350
350
350
350
350
350
350
350 420
420
420
420
420
420
420
420
420
420
420
490
490
490
490
490
490
490
560
560
2.30 m
0.00 1.15
4.00 m
0.00
1.00
3.00
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 387 229 577 0.590
Floor 49 329 240 411 0.728
Ceiling 86 161 133 186 0.828
Walls (4) 86 196 129 260 /
Workplane:
Height: 0.760 m
Grid: 64 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.480, Ceiling / Working Plane: 0.416.
Luminaire Parts List
Specific connected load: 9.57 W/m² = 2.47 W/m²/100 lx (Ground area: 9.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 4276 Total: 4276 88.0
Page 3
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
DRIVER'S TRAINING ROOM / Summary
680
720
720
720
720
720
760
760
760 760
760
760
760
760
760
760
760
800
800
800
800
800
800
800
800
800
800
800
8.20 m
0.00 1.02 3.07 5.12 7.17
6.00 m
0.00
1.00
3.00
5.00
Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 755 649 833 0.860
Floor 49 690 515 766 0.746
Ceiling 86 411 350 491 0.852
Walls (4) 86 546 378 677 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.740, Ceiling / Working Plane: 0.545.
Luminaire Parts List
Specific connected load: 8.54 W/m² = 1.13 W/m²/100 lx (Ground area: 49.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 12
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 41580 Total: 41580 420.0
Page 3
JUBAIL BULK PLANT
21.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
STORE ROOM FOR MAINTENANCE / Summary
600
600
600
630
630
630
630
630
630
630
630
630
630
660
660
660
660
660
660
660
660
660
660
660
660
660
660
660
660
660
4.30 m
0.00 1.08 3.23
4.00 m
0.00
0.20
1.00
3.00
3.80
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 634 556 677 0.877
Floor 49 549 437 603 0.796
Ceiling 86 366 327 460 0.892
Walls (4) 86 472 350 593 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 18 18
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.777, Ceiling / Working Plane: 0.578.
Luminaire Parts List
Specific connected load: 8.14 W/m² = 1.28 W/m²/100 lx (Ground area: 17.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
19.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
STORE ROOM / Summary
420
420
420
420
480
480
480
480
480
480
480
480
480
480
480
510
510
510
510
510
510
510
510
510
510
510 510 510
510
510
510
4.80 m
0.00 1.20 3.60
4.80 m
0.00
1.20
3.60
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:62
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 489 394 543 0.806
Floor 49 435 338 474 0.776
Ceiling 86 277 247 335 0.893
Walls (4) 86 361 256 446 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.761, Ceiling / Working Plane: 0.566.
Luminaire Parts List
Specific connected load: 6.08 W/m² = 1.24 W/m²/100 lx (Ground area: 23.04 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
19.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
ENTRANCE / Summary
480
480
480
560
560
560
560
560
560
560
640
640
640 640
640
640
640
640
640
640
640
720
720
720 720
720
720
720
720
720
720
2.40 m
0.00 0.60 1.80
2.20 m
0.00
1.10
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:29
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 610 426 792 0.700
Floor 49 503 362 598 0.720
Ceiling 86 269 216 309 0.801
Walls (4) 86 331 212 489 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.533, Ceiling / Working Plane: 0.441.
Luminaire Parts List
Specific connected load: 16.67 W/m² = 2.73 W/m²/100 lx (Ground area: 5.28 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 2
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 4276 Total: 4276 88.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
HALLWAY-1 & 2 / Summary
360
400
440 440
440
440
440 440
440
440
440
440
440
440
480
480
480
480
480
480
480
480
480
480
480
480
480
480
520
14.80 m
0.00 1.48 4.44 7.40 10.36 13.32
1.80 m
0.00
0.90
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:106
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 453 332 528 0.733
Floor 49 393 299 461 0.761
Ceiling 86 282 226 389 0.800
Walls (4) 86 352 238 557 /
Workplane:
Height: 0.760 m
Grid: 128 x 16 Points
Boundary Zone: 0.000 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.827, Ceiling / Working Plane: 0.624.
Luminaire Parts List
Specific connected load: 6.57 W/m² = 1.45 W/m²/100 lx (Ground area: 26.64 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 5
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 17325 Total: 17325 175.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
PRAYER ROOM / Summary
600
600
640
640
640
640
640
640
640
640
640
640
680
680
680
680
680
680
680
680
680
680
680
680
680
680
680
680
680
680
680
680
720
7.20 m
0.00 1.20 3.60 6.00
5.80 m
0.00
0.97
2.90
4.83
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:75
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 654 559 725 0.856
Floor 49 594 448 661 0.755
Ceiling 86 362 311 456 0.860
Walls (4) 86 481 349 610 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.756, Ceiling / Working Plane: 0.553.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 7.54 W/m² = 1.15 W/m²/100 lx (Ground area: 41.76 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 9
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 31185 Total: 31185 315.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
OPERATION PERSONNEL / Summary
720
760
760
760
760
760
760
800
800
800
800
800
800
800
840
840
840
840
840
3.50 m
0.00 0.88 2.63
6.00 m
0.00
1.00
3.00
5.00
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:78
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 790 686 859 0.868
Floor 49 691 555 762 0.802
Ceiling 86 459 416 579 0.906
Walls (4) 86 594 448 773 /
Workplane:
Height: 0.760 m
Grid: 64 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 17 17
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.788, Ceiling / Working Plane: 0.581.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 10.00 W/m² = 1.27 W/m²/100 lx (Ground area: 21.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 6
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 20790 Total: 20790 210.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
OPERATION ENGINEER / Summary
780
780
810
810
810
810
810
810
810
840
840
840
840
840
840
840
840
870
870
870
870
870
870
870
870
870
870
870
3.10 m
0.00 0.78 2.33
4.00 m
0.00
0.20
1.00
3.00
3.80
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 825 734 883 0.890
Floor 49 699 574 766 0.821
Ceiling 86 497 461 572 0.928
Walls (4) 86 626 456 890 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 16 17
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.805, Ceiling / Working Plane: 0.602.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 11.29 W/m² = 1.37 W/m²/100 lx (Ground area: 12.40 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
SECRETARY / Summary
950
1000 1000
1000
1000
1050
1050
1050 1050
1050
1050
1050
1050
1050
1050
1050
1100
1100
1100 1100
1100
1100
1100
1100
1100
1100
1100
3.10 m
0.00 0.78 2.33
2.90 m
0.00
0.72
2.17
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:38
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 1050 929 1133 0.885
Floor 49 882 738 966 0.837
Ceiling 86 672 631 786 0.940
Walls (4) 86 822 549 1125 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 16 17
Lower Wall 16 17
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.841, Ceiling / Working Plane: 0.639.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 15.57 W/m² = 1.48 W/m²/100 lx (Ground area: 8.99 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
FOREMAN OFFICE / Summary
600 600
630
630
630
630
630
630 630
630
630
630
630
660
660
660
660
660
660 660
660
660
660
4.20 m
0.00 1.05 3.15
4.00 m
0.00
0.20
1.00
3.00
3.80
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 646 568 690 0.879
Floor 49 558 451 612 0.808
Ceiling 86 374 337 473 0.901
Walls (4) 86 481 373 602 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 18 18
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.779, Ceiling / Working Plane: 0.579.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 8.33 W/m² = 1.29 W/m²/100 lx (Ground area: 16.80 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
OPERATION SUPERVISOR / Summary
760
760
800
800
800
800
800
800
800
800
800
800 800
840
840
840
840
840
840
840
840
840
840
880
880
880
880
880
880
880
880
880
880
880
880
880
880
880
880
880
880
880
880
4.20 m
0.00 1.05 3.15
2.90 m
0.00
0.72
2.17
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:38
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 823 710 892 0.863
Floor 49 705 577 770 0.818
Ceiling 86 504 462 607 0.915
Walls (4) 86 632 438 947 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 18 18
Lower Wall 16 17
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.815, Ceiling / Working Plane: 0.613.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 11.49 W/m² = 1.40 W/m²/100 lx (Ground area: 12.18 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
DOCUMENT ROOM / Summary
840
840
880
880
880
880
880
920
920
920 920
920
920
920
920
920
920
920
960
960 960 960
960
960
960
960
960
960
960
3.60 m
0.00 0.90 2.70
3.00 m
0.00
0.75
2.25
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:39
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 922 806 989 0.874
Floor 49 785 656 860 0.836
Ceiling 86 577 542 686 0.940
Walls (4) 86 719 522 1036 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 18 18
Lower Wall 16 17
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.832, Ceiling / Working Plane: 0.626.
Luminaire Parts List
Specific connected load: 12.96 W/m² = 1.41 W/m²/100 lx (Ground area: 10.80 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TELECOM ROOM (FIRST FLOOR) / Summary
800
800
840
840
840
840
880
880
880 880
880
880
880
880
880
880
880
920
920
920 920 920
920
920
920
920
920
920
5.10 m
0.00 1.27 3.82
3.00 m
0.00
0.75
2.25
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:39
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 875 757 955 0.865
Floor 49 766 645 836 0.842
Ceiling 86 585 524 790 0.896
Walls (4) 86 699 491 1050 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.838, Ceiling / Working Plane: 0.668.
Luminaire Parts List
Specific connected load: 15.42 W/m² = 1.76 W/m²/100 lx (Ground area: 15.30 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 20488 Total: 20488 236.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
ELECTRICAL ROOM (FIRST FLOOR) / Summary
330
360
360
360
360
390
390
390
390
390
420
420
420
420
420
420
420
420
420
1.80 m
0.00 0.90
4.00 m
0.00
2.00
Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 383 316 443 0.825
Floor 49 313 259 352 0.827
Ceiling 86 274 209 430 0.764
Walls (4) 86 307 196 595 /
Workplane:
Height: 0.760 m
Grid: 32 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.855, Ceiling / Working Plane: 0.716.
Luminaire Parts List
Specific connected load: 8.19 W/m² = 2.14 W/m²/100 lx (Ground area: 7.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 1
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 5122 Total: 5122 59.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
CONFERENCE ROOM / Summary
680
720
720 720
720
720
720
760
760 760
760
760
760
760
760
760
760
760
800
800
800
800
800
800 800
800
800
800
800
800
800
7.80 m
0.00 0.97 2.92 4.87 6.82
4.00 m
0.00
0.20
1.00
3.00
3.80
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:56
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 748 647 814 0.865
Floor 49 667 520 733 0.780
Ceiling 86 425 393 547 0.925
Walls (4) 86 558 417 685 /
Workplane:
Height: 0.760 m
Grid: 64 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.775, Ceiling / Working Plane: 0.568.
Luminaire Parts List
Specific connected load: 8.97 W/m² = 1.20 W/m²/100 lx (Ground area: 31.20 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 8
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 27720 Total: 27720 280.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
MAINTENANCE SUPERVISOR / Summary
600 600
630
630
630
630
630
630 630
630
630
630
630
660
660
660
660
660
660 660
660
660
660
4.20 m
0.00 1.05 3.15
4.00 m
0.00
0.20
1.00
3.00
3.80
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 646 568 690 0.879
Floor 49 558 451 612 0.808
Ceiling 86 374 337 473 0.901
Walls (4) 86 481 373 602 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 18 18
Lower Wall 18 18
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.779, Ceiling / Working Plane: 0.579.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 8.33 W/m² = 1.29 W/m²/100 lx (Ground area: 16.80 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
MAINTENANCE ENGINEER / Summary
760
760
800
800
800
840
840 840
840
840
840
840
840
840
840
840
880
880
880
880
880
880
880
880
880
880
880
4.20 m
0.00 1.05 3.15
2.80 m
0.00
0.70
2.10
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:36
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 845 731 916 0.865
Floor 49 721 595 788 0.825
Ceiling 86 521 475 622 0.913
Walls (4) 86 650 472 987 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.818, Ceiling / Working Plane: 0.616.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 11.90 W/m² = 1.41 W/m²/100 lx (Ground area: 11.76 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
20.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
MAINTENANCE PERSONNEL / Summary
850
850
900
900
900
900
900
950
950
950
950
950
950
950
3.10 m
0.00 0.78 2.33
7.70 m
0.00
0.96
2.89
4.82
6.75
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:99
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 909 776 984 0.854
Floor 49 805 630 880 0.782
Ceiling 86 537 496 634 0.923
Walls (4) 86 693 497 933 /
Workplane:
Height: 0.760 m
Grid: 32 x 64 Points
Boundary Zone: 0.100 m
UGR Lengthways- Across to luminaire axis
Left Wall 17 17
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.803, Ceiling / Working Plane: 0.591.
Luminaire Parts List
Specific connected load: 11.73 W/m² = 1.29 W/m²/100 lx (Ground area: 23.87 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 8
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 27720 Total: 27720 280.0
Page 3
JUBAIL BULK PLANT
20.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
MESS HALL / Summary
680
680
680
680
680
680
720
720 720
720
720
720
720
720
720
720
760
760
760
760
760
760
760
760
760
760
760
760
5.50 m
0.00 0.92 2.75 4.58
6.80 m
0.00
1.13
3.40
5.67
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:88
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 723 624 797 0.864
Floor 49 654 494 727 0.756
Ceiling 86 404 357 498 0.882
Walls (4) 86 536 402 685 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.766, Ceiling / Working Plane: 0.559.
Luminaire Parts List
Specific connected load: 8.42 W/m² = 1.17 W/m²/100 lx (Ground area: 37.40 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 9
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 31185 Total: 31185 315.0
Page 3
JUBAIL BULK PLANT
22.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
MAINTENANCE WORKSHOP / Summary
560
600
600
600
640
640
640
640
640
640
640
640
640
640
640
680
680
680
680
680
680
680
680
680
680
680
12.00 m
0.00 1.20 3.60 6.00 8.40
12.00 m
0.00
1.20
3.60
6.00
8.40
10.80
Height of Room: 6.200 m, Mounting Height: 4.700 m, Light loss factor: 0.55 Values in Lux, Scale 1:155
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 649 524 715 0.807
Floor 49 618 478 690 0.774
Ceiling 86 361 298 424 0.825
Walls (4) 86 459 307 627 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.200 m
UGR Lengthways- Across to luminaire axis
Left Wall 21 21
Lower Wall 21 21
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.709, Ceiling / Working Plane: 0.556.
Luminaire Parts List
Specific connected load: 10.24 W/m² = 1.58 W/m²/100 lx (Ground area: 144.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 25
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 128050 Total: 128050 1475.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
LOCKER ROOM / Summary
480
480
480
480
540
540 540 540 540
540
540
540
540
540
540
540 540
540
540
540
540
540
540
540
600 600
600
600
600
600 600
600
600
600
600
600
600
660
660
660
660
3.40 m
0.00 0.85 2.55
4.00 m
0.00
0.20
1.00
3.00
3.80
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 544 408 679 0.749
Floor 49 473 333 574 0.703
Ceiling 86 242 199 292 0.822
Walls (4) 86 290 191 456 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.519, Ceiling / Working Plane: 0.444.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 12.94 W/m² = 2.38 W/m²/100 lx (Ground area: 13.60 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 8552 Total: 8552 176.0
Page 3
JUBAIL BULK PLANT
13.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TEA ROOM / Summary
640
640
640
640
640
640
640 720 720
720
720
720
720
720
720
720
720
720
720
720
720
720
720
720
800
800
800
800
800
880
880
880
880
2.40 m
0.00 0.60 1.80
4.00 m
0.00
1.00
3.00
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 707 513 895 0.725
Floor 49 615 444 732 0.722
Ceiling 86 327 262 368 0.802
Walls (4) 86 397 265 559 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.558, Ceiling / Working Plane: 0.462.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 18.33 W/m² = 2.59 W/m²/100 lx (Ground area: 9.60 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 8552 Total: 8552 176.0
Page 3
JUBAIL BULK PLANT
19.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
MULTI-PURPOSE ROOM / Summary
770
770
770
840
840
840
840
840
840
840
840
840
840
840
840
840
840
840
840 910
910
910
910
910
910
910
910
910
910
910 910
910 910
910
910
910
910
910
910
910
910
910
910 910
6.80 m
0.00 2.04 3.40 4.76
12.20 m
0.00
0.87
2.61
4.35
6.09
7.83
9.57
11.31
Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:157
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 872 667 987 0.765
Floor 49 826 528 942 0.639
Ceiling 86 424 334 516 0.786
Walls (4) 86 486 333 768 /
Workplane:
Height: 0.760 m
Grid: 128 x 128 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.550, Ceiling / Working Plane: 0.487.
Luminaire Parts List
Specific connected load: 18.56 W/m² = 2.13 W/m²/100 lx (Ground area: 82.96 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 35
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 74830 Total: 74830 1540.0
Page 3
JUBAIL BULK PLANT
TRUCK IDENTIFICATION SHELTER
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 26.11.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
26.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TRUCK IDENTIFICATION SHELTER / Summary
650
650
650
650
700
700
700
750
750
750
750
750
750
750
750
750
750
800
800
800
800
800
800
850
3.50 m
0.00 0.88 2.63
4.50 m
0.00
1.13
3.38
Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor: 0.50 Values in Lux, Scale 1:58
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 780 620 853 0.795
Floor 49 691 573 756 0.829
Ceiling 86 484 426 626 0.879
Walls (4) 86 599 465 769 /
Workplane:
Height: 0.760 m
Grid: 64 x 64 Points
Boundary Zone: 0.000 m
UGR Lengthways- Across to luminaire axis
Left Wall 19 19
Lower Wall 20 20
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.803, Ceiling / Working Plane: 0.621.
Luminaire Parts List
Specific connected load: 14.98 W/m² = 1.92 W/m²/100 lx (Ground area: 15.75 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 20488 Total: 20488 236.0
Page 3
JUBAIL BULK PLANT
TRUCK INSPECTION ROOM
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 14.09.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
14.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TRUCK INSPECTION ROOM (101) / Summary
690
690 690
720
720
720
720
720
720
720
720
720
720
720
750
750
750
750
750
750
750
750
750 750
750
750
3.60 m
0.00 0.90 2.70
3.60 m
0.00
0.20
0.90
2.70
3.40
Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:47
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 722 659 772 0.912
Floor 49 617 517 675 0.838
Ceiling 86 467 429 613 0.919
Walls (4) 86 574 410 811 /
Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.200 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.846, Ceiling / Working Plane: 0.647.
Luminaire Parts List
Specific connected load: 10.80 W/m² = 1.50 W/m²/100 lx (Ground area: 12.96 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 13860 Total: 13860 140.0
Page 3
JUBAIL BULK PLANT
14.09.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
TOILET (102) / Summary
770
770
770
770
840
840
840
840
840
840
840
910
910
910
910
910
910
910
910
910
910
910
980
980
980
980
980
3.40 m
0.00 0.85 2.55
1.90 m
0.00
0.10
0.47
1.42
1.80
Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:25
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 863 688 990 0.798
Floor 49 731 572 808 0.782
Ceiling 86 443 359 507 0.812
Walls (4) 86 535 354 803 /
Workplane:
Height: 0.760 m
Grid: 64 x 32 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.641, Ceiling / Working Plane: 0.513.
Luminaire Parts List
Specific connected load: 27.24 W/m² = 3.16 W/m²/100 lx (Ground area: 6.46 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 4
COOPER LIGHTING - PORTFOLIO LD4A28DL3
ERM4A28940 4LM111H PORTFOLIO 4 INCH 50
DEGREE CUTOFF RECESSED SINGLE WALL
WASH LUMINAIRE SEMI-SPECULAR CLEAR
TRIM AND SPECULAR CLEAR KICKER (Type 1)
* (1.000)
2138 2138 44.0
*Modified Technical Specifications Total: 8552 Total: 8552 176.0
Page 3
JUBAIL BULK PLANT
CHEMICAL STORAGE SHED
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 01.11.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
01.11.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
CHEMICAL STORAGE SHED / Summary
360
420
420
420
480
480
480 480
480
480
480
480
480
480
480
540
540
540 540
540
540
540
540
540
540
540
600
600
600 600
600
600
600
600
600
600
600
10.00 m
0.00 0.83 2.50 4.17 5.84 7.51 9.18
8.00 m
0.00
1.00
3.00
5.00
7.00
Height of Room: 4.960 m, Mounting Height: 4.960 m, Light loss factor: 0.50 Values in Lux, Scale 1:103
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 500 339 616 0.678
Floor 20 453 329 546 0.727
Ceiling 80 157 127 397 0.811
Walls (4) 50 333 207 553 /
Workplane:
Height: 0.760 m
Grid: 32 x 32 Points
Boundary Zone: 0.000 m
UGR Lengthways- Across to luminaire axis
Left Wall 20 20
Lower Wall 19 19
(CIE, SHR = 0.25.)
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.696, Ceiling / Working Plane: 0.314.
Proportion of points with less than 400 lx (for IEQ-7): 9.18%.
Luminaire Parts List
Specific connected load: 17.70 W/m² = 3.54 W/m²/100 lx (Ground area: 80.00 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 24
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 122928 Total: 122928 1416.0
Page 3
JUBAIL BULK PLANT
SEAL RACK
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 16.10.2014
Operator: Mustang HDP
JUBAIL BULK PLANT
16.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
SEAL RACK / Summary
440
440
440
460
460
460
460
460
460
460
460
480
480
480 480
480
480
480
480
480
480
480
480
500
500
500 500
500
500
500
500
500
500
500
2.20 m
0.00 1.10
1.90 m
0.00
0.10
0.95
1.80
Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:25
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 470 419 514 0.892
Floor 49 366 297 396 0.810
Ceiling 86 327 269 379 0.822
Walls (4) 86 375 243 565 /
Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.875, Ceiling / Working Plane: 0.696.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 8.37 W/m² = 1.78 W/m²/100 lx (Ground area: 4.18 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 1
COOPER LIGHTING - METALUX 22EN-LD1-34-
UNV-L840-CD1-U METALUX 2X2 ENCOUNTER
FIXTURE (Type 1)* (1.000)
3465 3465 35.0
*Modified Technical Specifications Total: 3465 Total: 3465 35.0
Page 3
JUBAIL BULK PLANT
16.10.2014
Mustang HDP
Prince Turki Road, Al-Khobar, Saudi Arabia
Operator Mustang HDP
Telephone +966 (3) 869-7100
Fax 966 (3) 869-7200
e-Mail
STORE / Summary
640
680
680
680
680
680
680
720
720
720
720
720
720
720
720
720
720
720
760
760
760 760
760
760
760
760
760
760
760
760
2.20 m
0.00 1.10
1.90 m
0.00
0.10
0.95
1.80
Height of Room: 2.600 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:25
Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0
Workplane / 710 626 785 0.882
Floor 49 553 447 600 0.809
Ceiling 86 479 372 578 0.777
Walls (4) 86 547 366 936 /
Workplane:
Height: 0.760 m
Grid: 16 x 16 Points
Boundary Zone: 0.100 m
Illuminance Quotient (according to LG7): Walls / Working Plane: 0.837, Ceiling / Working Plane: 0.675.
Proportion of points with less than 400 lx (for IEQ-7): 0.00%.
Luminaire Parts List
Specific connected load: 14.11 W/m² = 1.99 W/m²/100 lx (Ground area: 4.18 m²)
No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W]
1 1
PHILIPS DAY-BRITE - PHILIPS CFI
DWAE51L840-4 PHILIPS DW VAPORLUME LED
Molded plastic and formed steel housing, clear
patterned plastic enclosure (Type 1)* (1.000)
5122 5122 59.0
*Modified Technical Specifications Total: 5122 Total: 5122 59.0
Page 3
JUBAIL BULK PLANT
FIRE WATER PUMPS STATION
Partner for Contact: SAUDI ARABIAN OIL COMPANY
Order No.: 1
Company: SAUDI ARAMCO
Customer No.: 1
Date: 15.01.2015
Operator: Mustang HDP
Attachment

More Related Content

Similar to Attachment

District Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar RailDistrict Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar Rail
Jaygopal Kottilil
 
SARNATH-PROFILE-CAE
SARNATH-PROFILE-CAESARNATH-PROFILE-CAE
SARNATH-PROFILE-CAE
Sarnath R
 
Architect Sample
Architect SampleArchitect Sample
Architect Sample
Hai Nguyen
 
Builder Sample
Builder SampleBuilder Sample
Builder Sample
Hai Nguyen
 

Similar to Attachment (20)

Design of security room
Design of security roomDesign of security room
Design of security room
 
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODECOMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
COMPARISON BETWEEN VARIOUS STEEL SECTION BY USING IS CODE AND EURO CODE
 
Cat 5e u utp data lan cables - upcom
Cat 5e u utp data lan cables - upcomCat 5e u utp data lan cables - upcom
Cat 5e u utp data lan cables - upcom
 
Baf Shaheen College (B+12) ETABS Dynamic Analysis.pptx
Baf Shaheen College (B+12) ETABS Dynamic Analysis.pptxBaf Shaheen College (B+12) ETABS Dynamic Analysis.pptx
Baf Shaheen College (B+12) ETABS Dynamic Analysis.pptx
 
Computer Aided Analysis and Design of Multi-Storeyed Building using Staad Pro
Computer Aided Analysis and Design of Multi-Storeyed Building using Staad ProComputer Aided Analysis and Design of Multi-Storeyed Building using Staad Pro
Computer Aided Analysis and Design of Multi-Storeyed Building using Staad Pro
 
STRUCTURAL CALCULATION - CURTAIN WALL (SAMPLE DESIGN)
STRUCTURAL CALCULATION - CURTAIN WALL (SAMPLE DESIGN)STRUCTURAL CALCULATION - CURTAIN WALL (SAMPLE DESIGN)
STRUCTURAL CALCULATION - CURTAIN WALL (SAMPLE DESIGN)
 
Modul 7 a157841
Modul 7  a157841Modul 7  a157841
Modul 7 a157841
 
District Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar RailDistrict Cooling Service - Presentation to Qatar Rail
District Cooling Service - Presentation to Qatar Rail
 
AC895_7.24.15.pdf
AC895_7.24.15.pdfAC895_7.24.15.pdf
AC895_7.24.15.pdf
 
Goniophotometer for-automotive-and-signal-lamps
Goniophotometer for-automotive-and-signal-lampsGoniophotometer for-automotive-and-signal-lamps
Goniophotometer for-automotive-and-signal-lamps
 
Goniophotometer for-automotive-and-signal-lamps
Goniophotometer for-automotive-and-signal-lampsGoniophotometer for-automotive-and-signal-lamps
Goniophotometer for-automotive-and-signal-lamps
 
IRJET - Design and Analysis of Residential Institute Building
IRJET - Design and Analysis of Residential Institute BuildingIRJET - Design and Analysis of Residential Institute Building
IRJET - Design and Analysis of Residential Institute Building
 
SARNATH-PROFILE-CAE
SARNATH-PROFILE-CAESARNATH-PROFILE-CAE
SARNATH-PROFILE-CAE
 
Building economics presentation 3 2
Building economics presentation 3 2Building economics presentation 3 2
Building economics presentation 3 2
 
High Precision Goniophotometer for Automotive and Traffic Signal Lamps
High Precision Goniophotometer for Automotive and Traffic Signal LampsHigh Precision Goniophotometer for Automotive and Traffic Signal Lamps
High Precision Goniophotometer for Automotive and Traffic Signal Lamps
 
Architect Sample
Architect SampleArchitect Sample
Architect Sample
 
Stahl TEF 2430 Green Perimeter Light - ATEX Zone 1 Zone 2 Hazardous Area
Stahl TEF 2430 Green Perimeter Light - ATEX Zone 1 Zone 2 Hazardous AreaStahl TEF 2430 Green Perimeter Light - ATEX Zone 1 Zone 2 Hazardous Area
Stahl TEF 2430 Green Perimeter Light - ATEX Zone 1 Zone 2 Hazardous Area
 
Stahl TEF 2430 Green Perimeter Helideck Light - ATEX Zone 1 Zone 2 Hazardous ...
Stahl TEF 2430 Green Perimeter Helideck Light - ATEX Zone 1 Zone 2 Hazardous ...Stahl TEF 2430 Green Perimeter Helideck Light - ATEX Zone 1 Zone 2 Hazardous ...
Stahl TEF 2430 Green Perimeter Helideck Light - ATEX Zone 1 Zone 2 Hazardous ...
 
Cat6 u utp data lan cable - upcom
Cat6 u utp data lan cable - upcomCat6 u utp data lan cable - upcom
Cat6 u utp data lan cable - upcom
 
Builder Sample
Builder SampleBuilder Sample
Builder Sample
 

Recently uploaded

XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
ssuser89054b
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Christo Ananth
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
dharasingh5698
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
dollysharma2066
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Christo Ananth
 

Recently uploaded (20)

data_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdfdata_management_and _data_science_cheat_sheet.pdf
data_management_and _data_science_cheat_sheet.pdf
 
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
XXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXXX
 
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
Call for Papers - Educational Administration: Theory and Practice, E-ISSN: 21...
 
Double Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torqueDouble Revolving field theory-how the rotor develops torque
Double Revolving field theory-how the rotor develops torque
 
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete RecordCCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
CCS335 _ Neural Networks and Deep Learning Laboratory_Lab Complete Record
 
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 BookingVIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
VIP Call Girls Palanpur 7001035870 Whatsapp Number, 24/07 Booking
 
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
VIP Model Call Girls Kothrud ( Pune ) Call ON 8005736733 Starting From 5K to ...
 
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdfONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
ONLINE FOOD ORDER SYSTEM PROJECT REPORT.pdf
 
Unit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdfUnit 1 - Soil Classification and Compaction.pdf
Unit 1 - Soil Classification and Compaction.pdf
 
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
Call Girls Pimpri Chinchwad Call Me 7737669865 Budget Friendly No Advance Boo...
 
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Mahipalpur Delhi Contact Us 8377877756
 
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptxBSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
BSides Seattle 2024 - Stopping Ethan Hunt From Taking Your Data.pptx
 
Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...Call for Papers - International Journal of Intelligent Systems and Applicatio...
Call for Papers - International Journal of Intelligent Systems and Applicatio...
 
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...Top Rated  Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
Top Rated Pune Call Girls Budhwar Peth ⟟ 6297143586 ⟟ Call Me For Genuine Se...
 
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
Call for Papers - African Journal of Biological Sciences, E-ISSN: 2663-2187, ...
 
Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01Double rodded leveling 1 pdf activity 01
Double rodded leveling 1 pdf activity 01
 
Roadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and RoutesRoadmap to Membership of RICS - Pathways and Routes
Roadmap to Membership of RICS - Pathways and Routes
 
Unleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leapUnleashing the Power of the SORA AI lastest leap
Unleashing the Power of the SORA AI lastest leap
 
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance BookingCall Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
Call Girls Walvekar Nagar Call Me 7737669865 Budget Friendly No Advance Booking
 
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...Booking open Available Pune Call Girls Pargaon  6297143586 Call Hot Indian Gi...
Booking open Available Pune Call Girls Pargaon 6297143586 Call Hot Indian Gi...
 

Attachment

  • 1. JUBAIL BULK PLANT SUBSTATION 204 Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 12.02.2015 Operator: Mustang HDP
  • 2. JUBAIL BULK PLANT 12.02.2015 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail BATTERY ROOM (103) / Summary Height of Room: 6.500 m, Mounting Height: 5.000 m, Light loss factor: 0.60 Values in Lux, Scale 1:93 Surface [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 510 434 563 0.852 Floor 49 474 385 526 0.812 Ceiling 86 297 249 348 0.836 Walls (4) 86 379 246 568 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.749, Ceiling / Working Plane: 0.583. Luminaire Parts List Specific connected load: 8.78 W/m² = 1.72 W/m²/100 lx (Ground area: 60.48 m²) No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W] 1 9 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 46098 Total: 46098 531.0 Page 3
  • 3. JUBAIL BULK PLANT 12.02.2015 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail MECHANICAL ROOM (102) / Summary Height of Room: 6.500 m, Mounting Height: 6.500 m, Light loss factor: 0.60 Values in Lux, Scale 1:88 Surface [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 488 423 533 0.866 Floor 49 455 380 512 0.837 Ceiling 86 358 317 682 0.886 Walls (4) 86 423 285 741 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.887, Ceiling / Working Plane: 0.733. Luminaire Parts List Specific connected load: 9.30 W/m² = 1.90 W/m²/100 lx (Ground area: 57.12 m²) No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W] 1 9 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 46098 Total: 46098 531.0 Page 3
  • 4. JUBAIL BULK PLANT 12.02.2015 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail SWITCHGEAR ROOM (101) / Summary Height of Room: 6.500 m, Mounting Height: 5.000 m, Light loss factor: 0.60 Values in Lux, Scale 1:183 Surface [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 441 346 484 0.783 Floor 49 425 316 473 0.744 Ceiling 86 242 199 290 0.821 Walls (6) 86 306 201 422 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.694, Ceiling / Working Plane: 0.549. Luminaire Parts List Specific connected load: 5.99 W/m² = 1.36 W/m²/100 lx (Ground area: 285.55 m²) No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W] 1 29 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 148538 Total: 148538 1711.0 Page 3
  • 5. JUBAIL BULK PLANT 12.02.2015 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TELECOM ROOM (104) / Summary Height of Room: 6.500 m, Mounting Height: 6.500 m, Light loss factor: 0.60 Values in Lux, Scale 1:27 Surface [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 580 524 609 0.904 Floor 49 489 446 527 0.911 Ceiling 86 999 809 1312 0.810 Walls (4) 86 784 313 1857 / Workplane: Height: 0.760 m Grid: 16 x 16 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 1.441, Ceiling / Working Plane: 1.723. Luminaire Parts List Specific connected load: 30.10 W/m² = 5.19 W/m²/100 lx (Ground area: 5.88 m²) No. Pieces Designation (Correction Factor) (Luminaire) [lm] (Lamps) [lm] P [W] 1 3 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 15366 Total: 15366 177.0 Page 3
  • 6. JUBAIL BULK PLANT FOAM SKID SHELTER Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 10.09.2014 Operator: Mustang HDP
  • 7. JUBAIL BULK PLANT 10.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail FOAM SKID SHELTER / Summary 450 480 480 480 480 510 510 510 510 510 510 510 510 510 510 510 540 540 540 540 540 540 540 540 540 540 540 11.00 m 0.00 1.38 4.13 6.88 9.63 13.70 m 0.00 1.37 4.11 6.85 9.59 12.33 Height of Room: 5.100 m, Mounting Height: 5.100 m, Light loss factor: 0.55 Values in Lux, Scale 1:176 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 507 426 557 0.840 Floor 49 483 393 540 0.814 Ceiling 86 305 271 507 0.888 Walls (4) 86 392 313 525 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 21 21 Lower Wall 21 21 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.787, Ceiling / Working Plane: 0.602. Luminaire Parts List Specific connected load: 7.83 W/m² = 1.54 W/m²/100 lx (Ground area: 150.70 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 20 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 102440 Total: 102440 1180.0 Page 3
  • 8. JUBAIL BULK PLANT SECURITY SUPPORT BUILDING Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 10.09.2014 Operator: Mustang HDP
  • 9. JUBAIL BULK PLANT 10.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail BATTERY ROOM (110) / Summary 680 680 720 720 720 720 720 720 720 720 760 760 760 760 760 760 760 760 760 800 4.80 m 0.00 1.20 3.60 6.60 m 0.00 1.10 3.30 5.50 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:85 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 741 646 802 0.871 Floor 49 668 544 729 0.815 Ceiling 86 447 403 762 0.900 Walls (4) 86 561 428 741 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.780, Ceiling / Working Plane: 0.604. Luminaire Parts List Specific connected load: 11.17 W/m² = 1.51 W/m²/100 lx (Ground area: 31.68 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 6 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 30732 Total: 30732 354.0 Page 3
  • 10. JUBAIL BULK PLANT 10.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail ELECTRICAL ROOM (109) / Summary 360 360 390 390 390 390 390 390 390 420 420 420 420 420 420 420 420 420 420 450 450 450 450 450 450 450 450 450 450 450 4.00 m 0.00 2.00 4.50 m 0.00 1.13 3.38 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:58 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 407 341 465 0.838 Floor 49 353 288 396 0.816 Ceiling 86 243 203 518 0.836 Walls (4) 86 298 215 452 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.751, Ceiling / Working Plane: 0.598. Luminaire Parts List Specific connected load: 6.56 W/m² = 1.61 W/m²/100 lx (Ground area: 18.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 10244 Total: 10244 118.0 Page 3
  • 11. JUBAIL BULK PLANT 10.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TELECOM ROOM (108) / Summary 660 660 690 690 690 690 690 690 690 720 720 720 720 720 720 720 720 720 720 720 4.00 m 0.00 1.00 3.00 2.00 m 0.00 1.00 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:29 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 701 618 755 0.881 Floor 49 585 502 645 0.857 Ceiling 86 525 439 759 0.837 Walls (4) 86 589 378 942 / Workplane: Height: 0.760 m Grid: 32 x 16 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.899, Ceiling / Working Plane: 0.748. Luminaire Parts List Specific connected load: 14.75 W/m² = 2.10 W/m²/100 lx (Ground area: 8.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 10244 Total: 10244 118.0 Page 3
  • 12. JUBAIL BULK PLANT 10.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail SECURITY ROOM (107) / Summary 560 600 600 600 600 640 640 640 640 640 640 640 640 640 640 680 680 680 680 680 680 680 680 680 3.40 m 0.00 1.70 5.00 m 0.00 0.83 2.50 4.17 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:65 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 634 546 705 0.860 Floor 49 550 445 622 0.808 Ceiling 86 396 323 711 0.816 Walls (4) 86 482 350 765 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.785, Ceiling / Working Plane: 0.624. Luminaire Parts List Specific connected load: 10.41 W/m² = 1.64 W/m²/100 lx (Ground area: 17.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 3 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 15366 Total: 15366 177.0 Page 3
  • 13. JUBAIL BULK PLANT 11.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail PRAYER ROOM (102) / Summary 520 520 560 560 560 560 560 560 560 600 600 600 600 600 600 600 640 640 640 640 640 640 640 640 640 640 680 680 680 680 680 680 680 680 680 680 2.80 m 0.00 1.40 2.80 m 0.00 0.70 2.10 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:36 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 604 508 692 0.842 Floor 49 498 416 554 0.836 Ceiling 86 374 325 479 0.869 Walls (4) 86 457 329 834 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.804, Ceiling / Working Plane: 0.620. Luminaire Parts List Specific connected load: 8.93 W/m² = 1.48 W/m²/100 lx (Ground area: 7.84 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 6930 Total: 6930 70.0 Page 3
  • 14. JUBAIL BULK PLANT 11.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail BREAK ROOM (103) / Summary 600 600 640 640 640 640 640 640 680 680 680 680 680 680 680 680 680 680 680 4.20 m 0.00 1.05 3.15 3.80 m 0.00 0.95 2.85 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:49 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 667 564 720 0.845 Floor 49 582 469 637 0.805 Ceiling 86 394 359 492 0.912 Walls (4) 86 505 386 654 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 18 18 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.794, Ceiling / Working Plane: 0.590. Luminaire Parts List Specific connected load: 8.77 W/m² = 1.32 W/m²/100 lx (Ground area: 15.96 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 15. JUBAIL BULK PLANT 11.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail WATER HEATER ROOM (105) / Summary 640 640 660 660 660 660 660 680 680 680 680 680 680 680 680 700 700 700 700 700 700 2.25 m 0.00 1.13 1.30 m 0.00 0.10 0.65 1.20 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:17 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 668 611 708 0.915 Floor 49 508 453 539 0.891 Ceiling 86 651 575 868 0.883 Walls (4) 86 632 329 1166 / Workplane: Height: 0.760 m Grid: 16 x 8 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 1.043, Ceiling / Working Plane: 0.975. Luminaire Parts List Specific connected load: 20.17 W/m² = 3.02 W/m²/100 lx (Ground area: 2.93 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 1 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 5122 Total: 5122 59.0 Page 3
  • 16. JUBAIL BULK PLANT 11.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TOILET (102) / Summary 540 540 540 540 540 630 630 630 630 630 630 630 630 630 630 630 630 630 630 630 720 720 720 720 720 810 810 810 810 810 810 810 2.25 m 0.00 0.56 1.69 4.60 m 0.00 1.15 3.45 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:60 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 657 444 852 0.676 Floor 49 572 419 644 0.733 Ceiling 86 307 254 380 0.828 Walls (4) 86 371 256 616 / Workplane: Height: 0.760 m Grid: 128 x 64 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.560, Ceiling / Working Plane: 0.468. Luminaire Parts List Specific connected load: 17.00 W/m² = 2.59 W/m²/100 lx (Ground area: 10.35 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 8552 Total: 8552 176.0 Page 3
  • 17. JUBAIL BULK PLANT FSF SUPPORT BUILDING Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 22.09.2014 Operator: Mustang HDP
  • 18. JUBAIL BULK PLANT 09.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail OFFICE - FSF SUPPORT BUILDING / Summary 660 660 690 690 690 690 720 720 720 720 720 720 720 720 720 720 720 750 750 750 750 750 750 750 750 750 750 750 3.70 m 0.00 0.93 2.78 3.90 m 0.00 0.20 0.97 2.92 3.70 Height of Room: 2.650 m, Mounting Height: 2.750 m, Light loss factor: 0.60 Values in Lux, Scale 1:51 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 712 633 759 0.889 Floor 49 611 489 671 0.801 Ceiling 86 430 389 568 0.904 Walls (4) 86 544 385 707 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 16 17 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.805, Ceiling / Working Plane: 0.604. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 9.70 W/m² = 1.36 W/m²/100 lx (Ground area: 14.43 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 19. JUBAIL BULK PLANT 10.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail BREAK ROOM (102) - FSF SUPPORT BUILDING / Summary 340 340 340 360 360 360 360 360 360 360 360 360 360 360 380 380 380 380 380 380 380 380 380 380 400 400 400 400 400 400 400 400 400 400 2.50 m 0.00 1.25 2.50 m 0.00 0.20 1.25 2.30 Height of Room: 2.650 m, Mounting Height: 2.650 m, Light loss factor: 0.60 Values in Lux, Scale 1:33 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 366 316 415 0.864 Floor 49 288 243 319 0.842 Ceiling 86 217 168 239 0.773 Walls (4) 86 266 181 354 / Workplane: Height: 0.760 m Grid: 16 x 16 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.770, Ceiling / Working Plane: 0.594. Proportion of points with less than 400 lx (for IEQ-7): 85.94%. Luminaire Parts List Specific connected load: 5.60 W/m² = 1.53 W/m²/100 lx (Ground area: 6.25 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 1 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 3465 Total: 3465 35.0 Page 3
  • 20. JUBAIL BULK PLANT 10.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TOILET (103) - FSF SUPPORT BUILDING / Summary 600 650 650 700 700 700 700 700 700 750 750 750 750 750 750 750 800 800 800 800 800 800 800 800 800 800 800 2.80 m 0.00 0.70 2.10 1.30 m 0.00 0.10 0.65 1.20 Height of Room: 2.650 m, Mounting Height: 2.750 m, Light loss factor: 0.60 Values in Lux, Scale 1:21 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 720 571 820 0.793 Floor 49 571 435 655 0.762 Ceiling 86 362 293 394 0.811 Walls (4) 86 441 305 597 / Workplane: Height: 0.760 m Grid: 64 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.634, Ceiling / Working Plane: 0.502. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 24.18 W/m² = 3.36 W/m²/100 lx (Ground area: 3.64 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 4276 Total: 4276 88.0 Page 3
  • 21. JUBAIL BULK PLANT OPERATOR SHELTER Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 09.09.2014 Operator: Mustang HDP
  • 22. JUBAIL BULK PLANT 09.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail OPERATOR SHELTER / Summary 630 630 660 660 660 660 690 690 690 690 690 690 690 690 690 690 690 720 720 720 720 720 720 720 720 3.80 m 0.00 0.95 2.85 3.70 m 0.00 0.20 0.93 2.78 3.50 Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:48 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 678 614 726 0.906 Floor 49 582 477 639 0.819 Ceiling 86 432 387 564 0.895 Walls (4) 86 535 379 732 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.839, Ceiling / Working Plane: 0.638. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 9.96 W/m² = 1.47 W/m²/100 lx (Ground area: 14.06 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 23. JUBAIL BULK PLANT 09.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TOILET (102) - OPERATOR SHELTER / Summary 700 700 750 750 750 750 800 800 800 800 800 800 800 800 800 800 800 850 850 850 850 850 850 850 850 850 850 850 3.70 m 0.00 0.20 0.93 2.78 3.50 2.00 m 0.00 0.20 0.50 1.50 1.80 Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:27 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 789 645 869 0.817 Floor 49 661 507 769 0.768 Ceiling 86 394 323 503 0.820 Walls (4) 86 476 327 775 / Workplane: Height: 0.760 m Grid: 64 x 32 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.620, Ceiling / Working Plane: 0.499. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 23.78 W/m² = 3.01 W/m²/100 lx (Ground area: 7.40 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 8552 Total: 8552 176.0 Page 3
  • 24. JUBAIL BULK PLANT BILL OF LADING/PRINTER AREA Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 26.11.2014 Operator: Mustang HDP
  • 25. JUBAIL BULK PLANT 26.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail BILL OF LADING/PRINTER AREA / Summary 650 650 650 650 650 650 650 650 700 700 700 700 750 750 750 750 750 750 750 750 750 750 750 800 800 800 800 800 800 800 800 800 800 800 4.60 m 0.00 1.15 3.45 3.50 m 0.00 0.88 2.63 Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor: 0.50 Values in Lux, Scale 1:45 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 766 609 837 0.795 Floor 49 679 561 743 0.826 Ceiling 86 474 416 613 0.876 Walls (4) 86 587 454 756 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.000 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.801, Ceiling / Working Plane: 0.619. Luminaire Parts List Specific connected load: 14.66 W/m² = 1.91 W/m²/100 lx (Ground area: 16.10 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 20488 Total: 20488 236.0 Page 3
  • 26. JUBAIL BULK PLANT SEC RMU ROOM Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 14.01.2015 Operator: Mustang HDP
  • 27. JUBAIL BULK PLANT 14.01.2015 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail SEC RMU ROOM / Summary 680 680 720 720 720 720 720 720 720 720 720 720 720 760 760 760 760 760 760 760 760 760 760 760 800 800 800 800 800 800 800 800 800 800 800 6.50 m 0.00 1.08 3.25 5.42 8.50 m 0.00 1.06 3.19 5.32 7.45 Height of Room: 5.400 m, Mounting Height: 5.400 m, Light loss factor: 0.60 Values in Lux, Scale 1:110 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 748 631 816 0.844 Floor 49 694 586 756 0.845 Ceiling 86 510 467 861 0.915 Walls (4) 86 621 465 874 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.852, Ceiling / Working Plane: 0.682. Luminaire Parts List Specific connected load: 12.81 W/m² = 1.71 W/m²/100 lx (Ground area: 55.25 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 12 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 61464 Total: 61464 708.0 Page 3
  • 28. JUBAIL BULK PLANT SECURITY GUARDHOUSE & GATE SUNSHADE Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 22.09.2014 Operator: Mustang HDP
  • 29. JUBAIL BULK PLANT 08.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail SECURITY GUARDHOUSE / Summary 400 400 400 400 450 450 450 450 450 450 450 450 450 450 450 450 500 500 500 500 500 500 500 500 500 500 500 550 550 550 550 550 550 550 550 7.00 m 0.00 1.17 3.50 5.83 5.00 m 0.00 1.25 3.75 Height of Room: 2.700 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:65 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 496 356 559 0.719 Floor 49 455 346 501 0.761 Ceiling 86 280 243 346 0.867 Walls (4) 86 368 250 466 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.000 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.760, Ceiling / Working Plane: 0.566. Proportion of points with less than 400 lx (for IEQ-7): 1.37%. Luminaire Parts List Specific connected load: 6.00 W/m² = 1.21 W/m²/100 lx (Ground area: 35.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 6 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 20790 Total: 20790 210.0 Page 3
  • 30. JUBAIL BULK PLANT 08.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail GATE HOUSE SUNSHADE / Summary 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 320 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 400 22.00 m 0.00 8.25 13.75 38.00 m 0.00 3.17 9.50 15.83 22.16 28.49 34.82 Height of Room: 6.130 m, Mounting Height: 5.130 m, Light loss factor: 0.50 Values in Lux, Scale 1:488 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 367 131 516 0.357 Floor 20 357 176 460 0.494 Ceiling 80 64 41 73 0.652 Walls (4) 50 101 43 231 / Workplane: Height: 0.760 m Grid: 128 x 128 Points Boundary Zone: 0.000 m UGR Lengthways- Across to luminaire axis Left Wall 22 22 Lower Wall 22 22 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.249, Ceiling / Working Plane: 0.173. Proportion of points with less than 400 lx (for IEQ-7): 79.13%. Luminaire Parts List Specific connected load: 7.67 W/m² = 2.09 W/m²/100 lx (Ground area: 836.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 24 PHILIPS BY461P 1xLED240S/740 WB GC (1.000) 24000 24000 267.0 Total: 576000 Total: 576000 6408.0 Page 7
  • 31. 1952K - JUBAIL BULK PLANT LOADING RACKS Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 29.06.2014 Operator: Mustang HDP
  • 32. 1952K - JUBAIL BULK PLANT 29.06.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail COOPER CROUSE-HINDS DMV 150 HPS DMVS2A150GP-RD739 / Luminaire Data Sheet Luminous emittance 1: 80 120 160 200 cd/klm η = 67% C0 - C180 C90 - C270 0° 15° 30° 45° 60° 75° 90° 105° 105° 90° 75° 60° 45° 30° 15° 0° Luminaire classification according to CIE: 98 CIE flux code: 31 60 91 98 67 DMV Class 1 Div 2 Hazardous Location luminaire Luminous emittance 1: Components: •2 x Glare Evaluation According to UGR ρ Ceiling 70 70 50 50 30 70 70 50 50 30 ρ Walls 50 30 50 30 30 50 30 50 30 30 ρ Floor 20 20 20 20 20 20 20 20 20 20 Room Size X Y Viewing direction at right angles to lamp axis Viewing direction parallel to lamp axis 2H 2H 29.0 30.5 29.3 30.8 31.1 29.0 30.5 29.3 30.8 31.1 3H 32.1 33.5 32.5 33.9 34.2 32.1 33.5 32.5 33.9 34.2 4H 33.7 35.1 34.1 35.4 35.8 33.7 35.1 34.1 35.4 35.8 6H 34.8 36.1 35.2 36.4 36.8 34.8 36.1 35.2 36.4 36.8 8H 35.1 36.3 35.5 36.7 37.1 35.1 36.3 35.5 36.7 37.1 12H 35.2 36.4 35.6 36.7 37.1 35.2 36.4 35.6 36.7 37.1 4H 2H 30.2 31.5 30.5 31.8 32.2 30.2 31.5 30.5 31.8 32.2 3H 33.4 34.6 33.8 35.0 35.4 33.4 34.6 33.8 35.0 35.4 4H 35.2 36.2 35.6 36.6 37.0 35.2 36.2 35.6 36.6 37.0 6H 36.3 37.2 36.8 37.7 38.1 36.3 37.2 36.8 37.7 38.1 8H 36.6 37.5 37.1 37.9 38.4 36.6 37.5 37.1 37.9 38.4 12H 36.8 37.6 37.3 38.0 38.5 36.8 37.6 37.3 38.0 38.5 8H 4H 35.8 36.6 36.3 37.1 37.5 35.8 36.6 36.3 37.1 37.5 6H 37.1 37.8 37.6 38.3 38.8 37.1 37.8 37.6 38.3 38.8 8H 37.5 38.1 38.0 38.6 39.1 37.5 38.1 38.0 38.6 39.1 12H 37.7 38.2 38.2 38.7 39.3 37.7 38.2 38.2 38.7 39.3 12H 4H 35.9 36.6 36.3 37.1 37.6 35.9 36.6 36.3 37.1 37.6 6H 37.2 37.8 37.7 38.3 38.8 37.2 37.8 37.7 38.3 38.8 8H 37.6 38.2 38.2 38.7 39.2 37.6 38.2 38.2 38.7 39.2 Variation of the observer position for the luminaire distances S S = 1.0H +0.1 / -0.0 +0.1 / -0.0 S = 1.5H +0.1 / -0.1 +0.1 / -0.1 S = 2.0H +0.3 / -0.3 +0.3 / -0.3 Standard table BK10 BK10 Correction Summand 19.8 19.8 Corrected Glare Indices referring to 16000lm Total Luminous Flux Page 2
  • 33. 1952K - JUBAIL BULK PLANT 29.06.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail LOADING RACKS / Summary 200 240 240 240 240 240 280 280 280 280 280 280 280 280 280 280 280 320 320 320 320 320 320 320 320 320 320 320 30.00 m 0.00 2.50 7.50 12.50 17.50 22.50 27.50 20.00 m 0.00 2.00 6.00 10.00 14.00 18.00 Height of Room: 8.600 m, Mounting Height: 7.600 m, Light loss factor: 0.71 Values in Lux, Scale 1:257 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 275 180 334 0.655 Floor 20 263 182 315 0.693 Ceiling 80 83 65 91 0.781 Walls (4) 50 211 73 406 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.000 m UGR Lengthways- Across to luminaire axis Left Wall >30 >30 Lower Wall >30 >30 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.778, Ceiling / Working Plane: 0.301. Proportion of points with less than 400 lx (for IEQ-7): 100.00%. Luminaire Parts List Specific connected load: 9.45 W/m² = 3.44 W/m²/100 lx (Ground area: 600.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 30 COOPER CROUSE-HINDS DMV 150 HPS DMVS2A150GP-RD739 (1.000) 10687 16000 189.0 Total: 320619 Total: 480000 5670.0 Page 3
  • 34. JUBAIL BULK PLANT SALES AND INSPECTION BUILDING Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 16.09.2014 Operator: Mustang HDP
  • 35. JUBAIL BULK PLANT 16.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TRANSACTION COUNTER (103) / Summary 1000 1000 1040 1040 1040 1040 1080 1080 1080 1080 1080 1080 1080 1080 1080 1080 1080 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120 1160 1160 1160 1160 1160 1160 1160 3.00 m 0.00 0.75 2.25 2.80 m 0.00 0.70 2.10 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:36 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 1083 970 1170 0.896 Floor 49 905 758 988 0.837 Ceiling 86 715 674 840 0.942 Walls (4) 86 862 606 1268 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.858, Ceiling / Working Plane: 0.660. Luminaire Parts List Specific connected load: 16.67 W/m² = 1.54 W/m²/100 lx (Ground area: 8.40 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 36. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail ELECTRICAL ROOM (109) / Summary 720 720 720 760 760 760 760 760 760 760 760 760 760 760 800 800 800 800 800 800 800 800 800 800 800 5.10 m 0.00 1.27 3.82 3.60 m 0.00 0.20 0.90 2.70 3.40 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:47 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 772 679 833 0.880 Floor 49 675 557 740 0.826 Ceiling 86 489 415 633 0.850 Walls (4) 86 597 439 817 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.808, Ceiling / Working Plane: 0.634. Luminaire Parts List Specific connected load: 12.85 W/m² = 1.67 W/m²/100 lx (Ground area: 18.36 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 20488 Total: 20488 236.0 Page 3
  • 37. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail DRIVER'S WAITING ROOM (104) / Summary 480 480 480 480 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 570 570 570 10.50 m 0.00 1.31 3.94 6.57 9.20 9.60 m 0.00 1.20 3.60 6.00 8.40 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:124 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 515 432 579 0.838 Floor 49 483 363 533 0.752 Ceiling 86 279 254 372 0.913 Walls (4) 86 376 275 492 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 21 21 Lower Wall 21 21 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.739, Ceiling / Working Plane: 0.541. Luminaire Parts List Specific connected load: 5.56 W/m² = 1.08 W/m²/100 lx (Ground area: 100.80 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 16 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 55440 Total: 55440 560.0 Page 3
  • 38. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail PRAYER ROOM (105) / Summary 800 840 840 880 880 880 880 880 880 880 880 880 880 920 920 920 920 920 920 920 920 920 960 960 960 4.80 m 0.00 0.80 2.40 4.00 6.00 m 0.00 1.00 3.00 5.00 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 889 784 968 0.882 Floor 49 796 620 880 0.779 Ceiling 86 510 457 661 0.896 Walls (4) 86 668 506 882 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.783, Ceiling / Working Plane: 0.574. Luminaire Parts List Specific connected load: 10.94 W/m² = 1.23 W/m²/100 lx (Ground area: 28.80 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 9 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 31185 Total: 31185 315.0 Page 3
  • 39. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail VESTIBULE (101) / Summary 360 360 390 390 390 390 390 390 390 420 420 420 420 420 420 420 420 450 450 450 450 450 480 480 480 480 480 480 480 480 480 3.20 m 0.00 1.60 3.80 m 0.00 0.95 2.85 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:49 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 418 342 488 0.818 Floor 49 356 288 401 0.809 Ceiling 86 245 213 301 0.868 Walls (4) 86 308 217 490 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 16 17 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.770, Ceiling / Working Plane: 0.586. Luminaire Parts List Specific connected load: 5.76 W/m² = 1.38 W/m²/100 lx (Ground area: 12.16 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 6930 Total: 6930 70.0 Page 3
  • 40. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail FOYER (105) / Summary 570 570 570 600 600 600 600 600 600 630 630 630 630 630 630 630 630 630 630 630 630 3.60 m 0.00 0.90 2.70 2.00 m 0.00 0.10 1.00 1.90 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:26 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 606 532 653 0.878 Floor 49 496 410 545 0.826 Ceiling 86 398 347 474 0.872 Walls (4) 86 476 330 667 / Workplane: Height: 0.760 m Grid: 32 x 16 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.849, Ceiling / Working Plane: 0.657. Luminaire Parts List Specific connected load: 9.72 W/m² = 1.60 W/m²/100 lx (Ground area: 7.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 6930 Total: 6930 70.0 Page 3
  • 41. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TELECOM ROOM (110) / Summary 570 570 600 600 600 600 600 600 600 630 630 630 630 630 630 630 630 630 630 660 660 660 660 660 3.00 m 0.00 1.50 3.50 m 0.00 0.20 0.88 2.63 3.30 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:45 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 610 535 666 0.878 Floor 49 513 436 562 0.850 Ceiling 86 404 344 562 0.852 Walls (4) 86 477 341 740 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.823, Ceiling / Working Plane: 0.663. Luminaire Parts List Specific connected load: 11.24 W/m² = 1.84 W/m²/100 lx (Ground area: 10.50 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 10244 Total: 10244 118.0 Page 3
  • 42. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail PRAYER ROOM (201) / Summary 760 760 800 800 800 800 800 800 800 840 840 840 840 840 840 840 840 840 840 840 840 7.10 m 0.00 0.89 2.66 4.43 6.20 3.90 m 0.00 0.20 0.97 2.92 3.70 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 813 709 878 0.872 Floor 49 722 562 832 0.779 Ceiling 86 468 431 610 0.922 Walls (4) 86 611 450 764 / Workplane: Height: 0.760 m Grid: 32 x 16 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.783, Ceiling / Working Plane: 0.576. Luminaire Parts List Specific connected load: 10.11 W/m² = 1.24 W/m²/100 lx (Ground area: 27.69 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 8 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 27720 Total: 27720 280.0 Page 3
  • 43. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail CLERK OFFICE (203-204) / Summary 920 920 920 960 960 960 960 960 960 960 960 960 1000 1000 1000 1000 1000 1000 1000 2.50 m 0.00 0.63 1.88 3.90 m 0.00 0.97 2.92 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 965 846 1043 0.877 Floor 49 814 673 888 0.827 Ceiling 86 629 576 801 0.917 Walls (4) 86 765 524 1309 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 16 17 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.851, Ceiling / Working Plane: 0.652. Luminaire Parts List Specific connected load: 14.36 W/m² = 1.49 W/m²/100 lx (Ground area: 9.75 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 44. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TRUCK INSPECTOR OFFICE (206-207) / Summary 760 760 800 800 800 800 800 800 800 800 800 800 800 840 840 840 840 840 840 840 840 840 840 3.10 m 0.00 0.78 2.33 3.90 m 0.00 0.97 2.92 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 814 707 875 0.869 Floor 49 698 577 766 0.826 Ceiling 86 506 471 590 0.932 Walls (4) 86 632 444 896 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 16 17 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.825, Ceiling / Working Plane: 0.622. Luminaire Parts List Specific connected load: 11.58 W/m² = 1.42 W/m²/100 lx (Ground area: 12.09 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 45. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail PRODUCT SALES REP OFFICE (208-210) / Summary 760 760 800 800 800 800 840 840 840 840 840 840 840 840 840 880 880 880 880 880 880 880 880 880 880 880 3.00 m 0.00 0.75 2.25 3.90 m 0.00 0.97 2.92 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:51 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 837 728 901 0.870 Floor 49 716 591 784 0.825 Ceiling 86 524 485 617 0.926 Walls (4) 86 653 452 953 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 16 17 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.829, Ceiling / Working Plane: 0.626. Luminaire Parts List Specific connected load: 11.97 W/m² = 1.43 W/m²/100 lx (Ground area: 11.70 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 46. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail ELECTRICAL ROOM (211) / Summary 390 390 390 390 390 390 390 390 390 390 390 390 390 390 390 390 390 420 420 420 420 420 420 420 420 420 420 420 450 450 450 450 450 450 450 450 450 450 450 3.30 m 0.00 1.65 2.10 m 0.00 0.10 1.05 2.00 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:27 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 409 355 456 0.868 Floor 49 336 280 367 0.834 Ceiling 86 291 229 505 0.789 Walls (4) 86 330 222 540 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.862, Ceiling / Working Plane: 0.712. Luminaire Parts List Specific connected load: 8.51 W/m² = 2.08 W/m²/100 lx (Ground area: 6.93 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 1 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 5122 Total: 5122 59.0 Page 3
  • 47. JUBAIL BULK PLANT 17.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail COMM. ROOM (213) / Summary 920 960 960 960 960 960 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1040 1040 1040 1040 1040 1040 1040 1040 1040 2.80 m 0.00 0.70 2.10 1.70 m 0.00 0.10 0.85 1.60 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:22 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 984 891 1045 0.906 Floor 49 789 684 844 0.867 Ceiling 86 841 683 941 0.812 Walls (4) 86 880 516 1496 / Workplane: Height: 0.760 m Grid: 16 x 16 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.974, Ceiling / Working Plane: 0.855. Luminaire Parts List Specific connected load: 24.79 W/m² = 2.52 W/m²/100 lx (Ground area: 4.76 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 10244 Total: 10244 118.0 Page 3
  • 48. JUBAIL BULK PLANT O & M BUILDING Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 21.09.2014 Operator: Mustang HDP
  • 49. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail ELECTRICAL AND UPS ROOM / Summary 360 390 390 390 390 390 390 420 420 420 420 420 420 420 420 420 420 420 420 420 420 420 420 420 420 420 420 450 450 450 450 450 450 450 450 450 450 450 9.00 m 0.00 1.50 4.50 7.50 7.00 m 0.00 1.75 5.25 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:90 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 416 341 468 0.820 Floor 49 384 299 424 0.780 Ceiling 86 236 201 517 0.851 Walls (4) 86 301 224 389 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 22 22 Lower Wall 21 21 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.733, Ceiling / Working Plane: 0.567. Luminaire Parts List Specific connected load: 5.62 W/m² = 1.35 W/m²/100 lx (Ground area: 63.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 6 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 30732 Total: 30732 354.0 Page 3
  • 50. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TER UPS ROOM / Summary 360 400 400 400 400 400 400 440 440 440 440 440 440 440 440 480 480 480 480 480 480 480 480 4.50 m 0.00 2.25 6.00 m 0.00 1.00 3.00 5.00 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 438 350 520 0.799 Floor 49 388 308 442 0.795 Ceiling 86 253 213 576 0.840 Walls (4) 86 314 225 515 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.729, Ceiling / Working Plane: 0.578. Luminaire Parts List Specific connected load: 6.56 W/m² = 1.50 W/m²/100 lx (Ground area: 27.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 3 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 15366 Total: 15366 177.0 Page 3
  • 51. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail RACK/SERVER ROOM / Summary 560 560 560 600 600 600 600 600 600 600 600 600 600 600 640 640 640 640 640 640 640 640 640 640 9.00 m 0.00 1.13 3.38 5.63 7.88 7.00 m 0.00 1.17 3.50 5.83 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:90 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 600 507 669 0.846 Floor 49 553 403 615 0.729 Ceiling 86 326 280 425 0.859 Walls (4) 86 437 328 526 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.745, Ceiling / Working Plane: 0.544. Luminaire Parts List Specific connected load: 6.67 W/m² = 1.11 W/m²/100 lx (Ground area: 63.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 12 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 41580 Total: 41580 420.0 Page 3
  • 52. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail BATTERY ROOM / Summary 440 440 480 480 480 480 480 480 480 480 480 480 480 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 520 560 560 560 560 560 5.60 m 0.00 1.40 4.20 6.00 m 0.00 1.50 4.50 Height of Room: 3.300 m, Mounting Height: 2.800 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 497 403 567 0.811 Floor 49 445 342 487 0.767 Ceiling 86 265 224 304 0.844 Walls (4) 86 336 221 424 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 22 22 Lower Wall 22 22 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.676, Ceiling / Working Plane: 0.534. Luminaire Parts List Specific connected load: 7.02 W/m² = 1.41 W/m²/100 lx (Ground area: 33.60 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 20488 Total: 20488 236.0 Page 3
  • 53. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TER BATTERY ROOM / Summary 560 560 560 560 600 600 600 600 600 600 600 600 600 640 640 640 640 640 640 640 640 640 640 640 640 640 640 640 640 640 640 640 680 680 680 680 680 680 7.00 m 0.00 1.17 3.50 5.83 6.00 m 0.00 1.50 4.50 Height of Room: 3.300 m, Mounting Height: 2.800 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 613 509 694 0.830 Floor 49 556 423 615 0.760 Ceiling 86 331 269 382 0.814 Walls (4) 86 420 279 553 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 22 22 Lower Wall 22 22 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.685, Ceiling / Working Plane: 0.540. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 8.43 W/m² = 1.38 W/m²/100 lx (Ground area: 42.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 6 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 30732 Total: 30732 354.0 Page 3
  • 54. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail PRODUCT TESTING / Summary 570 600 600 600 600 600 600 600 600 630 630 630 630 630 630 630 630 630 660 660 660 660 660 660 660 4.70 m 0.00 1.18 3.53 6.00 m 0.00 1.00 3.00 5.00 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 621 537 678 0.865 Floor 49 553 425 609 0.769 Ceiling 86 349 309 422 0.886 Walls (4) 86 458 338 582 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.763, Ceiling / Working Plane: 0.562. Luminaire Parts List Specific connected load: 7.45 W/m² = 1.20 W/m²/100 lx (Ground area: 28.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 6 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 20790 Total: 20790 210.0 Page 3
  • 55. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TELECOM ROOM / Summary 720 760 760 760 800 800 800 800 800 800 800 800 800 840 840 840 840 840 840 840 840 4.80 m 0.00 1.20 3.60 6.00 m 0.00 1.00 3.00 5.00 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 804 699 875 0.869 Floor 49 722 589 790 0.816 Ceiling 86 490 441 697 0.901 Walls (4) 86 612 475 881 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.785, Ceiling / Working Plane: 0.609. Luminaire Parts List Specific connected load: 12.29 W/m² = 1.53 W/m²/100 lx (Ground area: 28.80 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 6 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 30732 Total: 30732 354.0 Page 3
  • 56. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail STORE ROOM FOR OPERATION / Summary 540 540 570 570 570 570 570 570 570 570 570 570 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 600 4.80 m 0.00 1.20 3.60 4.00 m 0.00 0.20 1.00 3.00 3.80 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 577 501 625 0.869 Floor 49 502 397 547 0.791 Ceiling 86 329 294 406 0.892 Walls (4) 86 426 311 556 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 18 18 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.767, Ceiling / Working Plane: 0.571. Luminaire Parts List Specific connected load: 7.29 W/m² = 1.26 W/m²/100 lx (Ground area: 19.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 57. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TEA ROOM / Summary 350 350 350 350 350 350 350 350 350 350 420 420 420 420 420 420 420 420 420 420 420 490 490 490 490 490 490 490 560 560 2.30 m 0.00 1.15 4.00 m 0.00 1.00 3.00 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 387 229 577 0.590 Floor 49 329 240 411 0.728 Ceiling 86 161 133 186 0.828 Walls (4) 86 196 129 260 / Workplane: Height: 0.760 m Grid: 64 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.480, Ceiling / Working Plane: 0.416. Luminaire Parts List Specific connected load: 9.57 W/m² = 2.47 W/m²/100 lx (Ground area: 9.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 4276 Total: 4276 88.0 Page 3
  • 58. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail DRIVER'S TRAINING ROOM / Summary 680 720 720 720 720 720 760 760 760 760 760 760 760 760 760 760 760 800 800 800 800 800 800 800 800 800 800 800 8.20 m 0.00 1.02 3.07 5.12 7.17 6.00 m 0.00 1.00 3.00 5.00 Height of Room: 2.500 m, Mounting Height: 2.500 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 755 649 833 0.860 Floor 49 690 515 766 0.746 Ceiling 86 411 350 491 0.852 Walls (4) 86 546 378 677 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.740, Ceiling / Working Plane: 0.545. Luminaire Parts List Specific connected load: 8.54 W/m² = 1.13 W/m²/100 lx (Ground area: 49.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 12 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 41580 Total: 41580 420.0 Page 3
  • 59. JUBAIL BULK PLANT 21.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail STORE ROOM FOR MAINTENANCE / Summary 600 600 600 630 630 630 630 630 630 630 630 630 630 660 660 660 660 660 660 660 660 660 660 660 660 660 660 660 660 660 4.30 m 0.00 1.08 3.23 4.00 m 0.00 0.20 1.00 3.00 3.80 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 634 556 677 0.877 Floor 49 549 437 603 0.796 Ceiling 86 366 327 460 0.892 Walls (4) 86 472 350 593 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 18 18 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.777, Ceiling / Working Plane: 0.578. Luminaire Parts List Specific connected load: 8.14 W/m² = 1.28 W/m²/100 lx (Ground area: 17.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 60. JUBAIL BULK PLANT 19.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail STORE ROOM / Summary 420 420 420 420 480 480 480 480 480 480 480 480 480 480 480 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 510 4.80 m 0.00 1.20 3.60 4.80 m 0.00 1.20 3.60 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:62 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 489 394 543 0.806 Floor 49 435 338 474 0.776 Ceiling 86 277 247 335 0.893 Walls (4) 86 361 256 446 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.761, Ceiling / Working Plane: 0.566. Luminaire Parts List Specific connected load: 6.08 W/m² = 1.24 W/m²/100 lx (Ground area: 23.04 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 61. JUBAIL BULK PLANT 19.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail ENTRANCE / Summary 480 480 480 560 560 560 560 560 560 560 640 640 640 640 640 640 640 640 640 640 640 720 720 720 720 720 720 720 720 720 720 2.40 m 0.00 0.60 1.80 2.20 m 0.00 1.10 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:29 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 610 426 792 0.700 Floor 49 503 362 598 0.720 Ceiling 86 269 216 309 0.801 Walls (4) 86 331 212 489 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.533, Ceiling / Working Plane: 0.441. Luminaire Parts List Specific connected load: 16.67 W/m² = 2.73 W/m²/100 lx (Ground area: 5.28 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 2 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 4276 Total: 4276 88.0 Page 3
  • 62. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail HALLWAY-1 & 2 / Summary 360 400 440 440 440 440 440 440 440 440 440 440 440 440 480 480 480 480 480 480 480 480 480 480 480 480 480 480 520 14.80 m 0.00 1.48 4.44 7.40 10.36 13.32 1.80 m 0.00 0.90 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:106 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 453 332 528 0.733 Floor 49 393 299 461 0.761 Ceiling 86 282 226 389 0.800 Walls (4) 86 352 238 557 / Workplane: Height: 0.760 m Grid: 128 x 16 Points Boundary Zone: 0.000 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.827, Ceiling / Working Plane: 0.624. Luminaire Parts List Specific connected load: 6.57 W/m² = 1.45 W/m²/100 lx (Ground area: 26.64 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 5 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 17325 Total: 17325 175.0 Page 3
  • 63. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail PRAYER ROOM / Summary 600 600 640 640 640 640 640 640 640 640 640 640 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 680 720 7.20 m 0.00 1.20 3.60 6.00 5.80 m 0.00 0.97 2.90 4.83 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:75 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 654 559 725 0.856 Floor 49 594 448 661 0.755 Ceiling 86 362 311 456 0.860 Walls (4) 86 481 349 610 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.756, Ceiling / Working Plane: 0.553. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 7.54 W/m² = 1.15 W/m²/100 lx (Ground area: 41.76 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 9 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 31185 Total: 31185 315.0 Page 3
  • 64. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail OPERATION PERSONNEL / Summary 720 760 760 760 760 760 760 800 800 800 800 800 800 800 840 840 840 840 840 3.50 m 0.00 0.88 2.63 6.00 m 0.00 1.00 3.00 5.00 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:78 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 790 686 859 0.868 Floor 49 691 555 762 0.802 Ceiling 86 459 416 579 0.906 Walls (4) 86 594 448 773 / Workplane: Height: 0.760 m Grid: 64 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 17 17 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.788, Ceiling / Working Plane: 0.581. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 10.00 W/m² = 1.27 W/m²/100 lx (Ground area: 21.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 6 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 20790 Total: 20790 210.0 Page 3
  • 65. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail OPERATION ENGINEER / Summary 780 780 810 810 810 810 810 810 810 840 840 840 840 840 840 840 840 870 870 870 870 870 870 870 870 870 870 870 3.10 m 0.00 0.78 2.33 4.00 m 0.00 0.20 1.00 3.00 3.80 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 825 734 883 0.890 Floor 49 699 574 766 0.821 Ceiling 86 497 461 572 0.928 Walls (4) 86 626 456 890 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 16 17 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.805, Ceiling / Working Plane: 0.602. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 11.29 W/m² = 1.37 W/m²/100 lx (Ground area: 12.40 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 66. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail SECRETARY / Summary 950 1000 1000 1000 1000 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1050 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 1100 3.10 m 0.00 0.78 2.33 2.90 m 0.00 0.72 2.17 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:38 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 1050 929 1133 0.885 Floor 49 882 738 966 0.837 Ceiling 86 672 631 786 0.940 Walls (4) 86 822 549 1125 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 16 17 Lower Wall 16 17 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.841, Ceiling / Working Plane: 0.639. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 15.57 W/m² = 1.48 W/m²/100 lx (Ground area: 8.99 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 67. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail FOREMAN OFFICE / Summary 600 600 630 630 630 630 630 630 630 630 630 630 630 660 660 660 660 660 660 660 660 660 660 4.20 m 0.00 1.05 3.15 4.00 m 0.00 0.20 1.00 3.00 3.80 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 646 568 690 0.879 Floor 49 558 451 612 0.808 Ceiling 86 374 337 473 0.901 Walls (4) 86 481 373 602 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 18 18 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.779, Ceiling / Working Plane: 0.579. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 8.33 W/m² = 1.29 W/m²/100 lx (Ground area: 16.80 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 68. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail OPERATION SUPERVISOR / Summary 760 760 800 800 800 800 800 800 800 800 800 800 800 840 840 840 840 840 840 840 840 840 840 880 880 880 880 880 880 880 880 880 880 880 880 880 880 880 880 880 880 880 880 4.20 m 0.00 1.05 3.15 2.90 m 0.00 0.72 2.17 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:38 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 823 710 892 0.863 Floor 49 705 577 770 0.818 Ceiling 86 504 462 607 0.915 Walls (4) 86 632 438 947 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 18 18 Lower Wall 16 17 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.815, Ceiling / Working Plane: 0.613. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 11.49 W/m² = 1.40 W/m²/100 lx (Ground area: 12.18 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 69. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail DOCUMENT ROOM / Summary 840 840 880 880 880 880 880 920 920 920 920 920 920 920 920 920 920 920 960 960 960 960 960 960 960 960 960 960 960 3.60 m 0.00 0.90 2.70 3.00 m 0.00 0.75 2.25 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:39 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 922 806 989 0.874 Floor 49 785 656 860 0.836 Ceiling 86 577 542 686 0.940 Walls (4) 86 719 522 1036 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 18 18 Lower Wall 16 17 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.832, Ceiling / Working Plane: 0.626. Luminaire Parts List Specific connected load: 12.96 W/m² = 1.41 W/m²/100 lx (Ground area: 10.80 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 70. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TELECOM ROOM (FIRST FLOOR) / Summary 800 800 840 840 840 840 880 880 880 880 880 880 880 880 880 880 880 920 920 920 920 920 920 920 920 920 920 920 5.10 m 0.00 1.27 3.82 3.00 m 0.00 0.75 2.25 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:39 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 875 757 955 0.865 Floor 49 766 645 836 0.842 Ceiling 86 585 524 790 0.896 Walls (4) 86 699 491 1050 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.838, Ceiling / Working Plane: 0.668. Luminaire Parts List Specific connected load: 15.42 W/m² = 1.76 W/m²/100 lx (Ground area: 15.30 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 20488 Total: 20488 236.0 Page 3
  • 71. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail ELECTRICAL ROOM (FIRST FLOOR) / Summary 330 360 360 360 360 390 390 390 390 390 420 420 420 420 420 420 420 420 420 1.80 m 0.00 0.90 4.00 m 0.00 2.00 Height of Room: 3.300 m, Mounting Height: 3.300 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 383 316 443 0.825 Floor 49 313 259 352 0.827 Ceiling 86 274 209 430 0.764 Walls (4) 86 307 196 595 / Workplane: Height: 0.760 m Grid: 32 x 16 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.855, Ceiling / Working Plane: 0.716. Luminaire Parts List Specific connected load: 8.19 W/m² = 2.14 W/m²/100 lx (Ground area: 7.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 1 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 5122 Total: 5122 59.0 Page 3
  • 72. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail CONFERENCE ROOM / Summary 680 720 720 720 720 720 720 760 760 760 760 760 760 760 760 760 760 760 800 800 800 800 800 800 800 800 800 800 800 800 800 7.80 m 0.00 0.97 2.92 4.87 6.82 4.00 m 0.00 0.20 1.00 3.00 3.80 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:56 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 748 647 814 0.865 Floor 49 667 520 733 0.780 Ceiling 86 425 393 547 0.925 Walls (4) 86 558 417 685 / Workplane: Height: 0.760 m Grid: 64 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.775, Ceiling / Working Plane: 0.568. Luminaire Parts List Specific connected load: 8.97 W/m² = 1.20 W/m²/100 lx (Ground area: 31.20 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 8 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 27720 Total: 27720 280.0 Page 3
  • 73. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail MAINTENANCE SUPERVISOR / Summary 600 600 630 630 630 630 630 630 630 630 630 630 630 660 660 660 660 660 660 660 660 660 660 4.20 m 0.00 1.05 3.15 4.00 m 0.00 0.20 1.00 3.00 3.80 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 646 568 690 0.879 Floor 49 558 451 612 0.808 Ceiling 86 374 337 473 0.901 Walls (4) 86 481 373 602 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 18 18 Lower Wall 18 18 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.779, Ceiling / Working Plane: 0.579. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 8.33 W/m² = 1.29 W/m²/100 lx (Ground area: 16.80 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 74. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail MAINTENANCE ENGINEER / Summary 760 760 800 800 800 840 840 840 840 840 840 840 840 840 840 840 880 880 880 880 880 880 880 880 880 880 880 4.20 m 0.00 1.05 3.15 2.80 m 0.00 0.70 2.10 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:36 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 845 731 916 0.865 Floor 49 721 595 788 0.825 Ceiling 86 521 475 622 0.913 Walls (4) 86 650 472 987 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.818, Ceiling / Working Plane: 0.616. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 11.90 W/m² = 1.41 W/m²/100 lx (Ground area: 11.76 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 75. JUBAIL BULK PLANT 20.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail MAINTENANCE PERSONNEL / Summary 850 850 900 900 900 900 900 950 950 950 950 950 950 950 3.10 m 0.00 0.78 2.33 7.70 m 0.00 0.96 2.89 4.82 6.75 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:99 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 909 776 984 0.854 Floor 49 805 630 880 0.782 Ceiling 86 537 496 634 0.923 Walls (4) 86 693 497 933 / Workplane: Height: 0.760 m Grid: 32 x 64 Points Boundary Zone: 0.100 m UGR Lengthways- Across to luminaire axis Left Wall 17 17 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.803, Ceiling / Working Plane: 0.591. Luminaire Parts List Specific connected load: 11.73 W/m² = 1.29 W/m²/100 lx (Ground area: 23.87 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 8 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 27720 Total: 27720 280.0 Page 3
  • 76. JUBAIL BULK PLANT 20.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail MESS HALL / Summary 680 680 680 680 680 680 720 720 720 720 720 720 720 720 720 720 760 760 760 760 760 760 760 760 760 760 760 760 5.50 m 0.00 0.92 2.75 4.58 6.80 m 0.00 1.13 3.40 5.67 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:88 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 723 624 797 0.864 Floor 49 654 494 727 0.756 Ceiling 86 404 357 498 0.882 Walls (4) 86 536 402 685 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.766, Ceiling / Working Plane: 0.559. Luminaire Parts List Specific connected load: 8.42 W/m² = 1.17 W/m²/100 lx (Ground area: 37.40 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 9 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 31185 Total: 31185 315.0 Page 3
  • 77. JUBAIL BULK PLANT 22.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail MAINTENANCE WORKSHOP / Summary 560 600 600 600 640 640 640 640 640 640 640 640 640 640 640 680 680 680 680 680 680 680 680 680 680 680 12.00 m 0.00 1.20 3.60 6.00 8.40 12.00 m 0.00 1.20 3.60 6.00 8.40 10.80 Height of Room: 6.200 m, Mounting Height: 4.700 m, Light loss factor: 0.55 Values in Lux, Scale 1:155 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 649 524 715 0.807 Floor 49 618 478 690 0.774 Ceiling 86 361 298 424 0.825 Walls (4) 86 459 307 627 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.200 m UGR Lengthways- Across to luminaire axis Left Wall 21 21 Lower Wall 21 21 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.709, Ceiling / Working Plane: 0.556. Luminaire Parts List Specific connected load: 10.24 W/m² = 1.58 W/m²/100 lx (Ground area: 144.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 25 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 128050 Total: 128050 1475.0 Page 3
  • 78. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail LOCKER ROOM / Summary 480 480 480 480 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 540 600 600 600 600 600 600 600 600 600 600 600 600 600 660 660 660 660 3.40 m 0.00 0.85 2.55 4.00 m 0.00 0.20 1.00 3.00 3.80 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 544 408 679 0.749 Floor 49 473 333 574 0.703 Ceiling 86 242 199 292 0.822 Walls (4) 86 290 191 456 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.519, Ceiling / Working Plane: 0.444. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 12.94 W/m² = 2.38 W/m²/100 lx (Ground area: 13.60 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 8552 Total: 8552 176.0 Page 3
  • 79. JUBAIL BULK PLANT 13.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TEA ROOM / Summary 640 640 640 640 640 640 640 720 720 720 720 720 720 720 720 720 720 720 720 720 720 720 720 720 800 800 800 800 800 880 880 880 880 2.40 m 0.00 0.60 1.80 4.00 m 0.00 1.00 3.00 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:52 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 707 513 895 0.725 Floor 49 615 444 732 0.722 Ceiling 86 327 262 368 0.802 Walls (4) 86 397 265 559 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.558, Ceiling / Working Plane: 0.462. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 18.33 W/m² = 2.59 W/m²/100 lx (Ground area: 9.60 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 8552 Total: 8552 176.0 Page 3
  • 80. JUBAIL BULK PLANT 19.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail MULTI-PURPOSE ROOM / Summary 770 770 770 840 840 840 840 840 840 840 840 840 840 840 840 840 840 840 840 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 910 6.80 m 0.00 2.04 3.40 4.76 12.20 m 0.00 0.87 2.61 4.35 6.09 7.83 9.57 11.31 Height of Room: 2.500 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:157 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 872 667 987 0.765 Floor 49 826 528 942 0.639 Ceiling 86 424 334 516 0.786 Walls (4) 86 486 333 768 / Workplane: Height: 0.760 m Grid: 128 x 128 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.550, Ceiling / Working Plane: 0.487. Luminaire Parts List Specific connected load: 18.56 W/m² = 2.13 W/m²/100 lx (Ground area: 82.96 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 35 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 74830 Total: 74830 1540.0 Page 3
  • 81. JUBAIL BULK PLANT TRUCK IDENTIFICATION SHELTER Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 26.11.2014 Operator: Mustang HDP
  • 82. JUBAIL BULK PLANT 26.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TRUCK IDENTIFICATION SHELTER / Summary 650 650 650 650 700 700 700 750 750 750 750 750 750 750 750 750 750 800 800 800 800 800 800 850 3.50 m 0.00 0.88 2.63 4.50 m 0.00 1.13 3.38 Height of Room: 2.800 m, Mounting Height: 2.800 m, Light loss factor: 0.50 Values in Lux, Scale 1:58 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 780 620 853 0.795 Floor 49 691 573 756 0.829 Ceiling 86 484 426 626 0.879 Walls (4) 86 599 465 769 / Workplane: Height: 0.760 m Grid: 64 x 64 Points Boundary Zone: 0.000 m UGR Lengthways- Across to luminaire axis Left Wall 19 19 Lower Wall 20 20 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.803, Ceiling / Working Plane: 0.621. Luminaire Parts List Specific connected load: 14.98 W/m² = 1.92 W/m²/100 lx (Ground area: 15.75 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 20488 Total: 20488 236.0 Page 3
  • 83. JUBAIL BULK PLANT TRUCK INSPECTION ROOM Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 14.09.2014 Operator: Mustang HDP
  • 84. JUBAIL BULK PLANT 14.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TRUCK INSPECTION ROOM (101) / Summary 690 690 690 720 720 720 720 720 720 720 720 720 720 720 750 750 750 750 750 750 750 750 750 750 750 750 3.60 m 0.00 0.90 2.70 3.60 m 0.00 0.20 0.90 2.70 3.40 Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:47 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 722 659 772 0.912 Floor 49 617 517 675 0.838 Ceiling 86 467 429 613 0.919 Walls (4) 86 574 410 811 / Workplane: Height: 0.760 m Grid: 16 x 16 Points Boundary Zone: 0.200 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.846, Ceiling / Working Plane: 0.647. Luminaire Parts List Specific connected load: 10.80 W/m² = 1.50 W/m²/100 lx (Ground area: 12.96 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 13860 Total: 13860 140.0 Page 3
  • 85. JUBAIL BULK PLANT 14.09.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail TOILET (102) / Summary 770 770 770 770 840 840 840 840 840 840 840 910 910 910 910 910 910 910 910 910 910 910 980 980 980 980 980 3.40 m 0.00 0.85 2.55 1.90 m 0.00 0.10 0.47 1.42 1.80 Height of Room: 3.000 m, Mounting Height: 3.100 m, Light loss factor: 0.60 Values in Lux, Scale 1:25 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 863 688 990 0.798 Floor 49 731 572 808 0.782 Ceiling 86 443 359 507 0.812 Walls (4) 86 535 354 803 / Workplane: Height: 0.760 m Grid: 64 x 32 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.641, Ceiling / Working Plane: 0.513. Luminaire Parts List Specific connected load: 27.24 W/m² = 3.16 W/m²/100 lx (Ground area: 6.46 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 4 COOPER LIGHTING - PORTFOLIO LD4A28DL3 ERM4A28940 4LM111H PORTFOLIO 4 INCH 50 DEGREE CUTOFF RECESSED SINGLE WALL WASH LUMINAIRE SEMI-SPECULAR CLEAR TRIM AND SPECULAR CLEAR KICKER (Type 1) * (1.000) 2138 2138 44.0 *Modified Technical Specifications Total: 8552 Total: 8552 176.0 Page 3
  • 86. JUBAIL BULK PLANT CHEMICAL STORAGE SHED Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 01.11.2014 Operator: Mustang HDP
  • 87. JUBAIL BULK PLANT 01.11.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail CHEMICAL STORAGE SHED / Summary 360 420 420 420 480 480 480 480 480 480 480 480 480 480 480 540 540 540 540 540 540 540 540 540 540 540 600 600 600 600 600 600 600 600 600 600 600 10.00 m 0.00 0.83 2.50 4.17 5.84 7.51 9.18 8.00 m 0.00 1.00 3.00 5.00 7.00 Height of Room: 4.960 m, Mounting Height: 4.960 m, Light loss factor: 0.50 Values in Lux, Scale 1:103 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 500 339 616 0.678 Floor 20 453 329 546 0.727 Ceiling 80 157 127 397 0.811 Walls (4) 50 333 207 553 / Workplane: Height: 0.760 m Grid: 32 x 32 Points Boundary Zone: 0.000 m UGR Lengthways- Across to luminaire axis Left Wall 20 20 Lower Wall 19 19 (CIE, SHR = 0.25.) Illuminance Quotient (according to LG7): Walls / Working Plane: 0.696, Ceiling / Working Plane: 0.314. Proportion of points with less than 400 lx (for IEQ-7): 9.18%. Luminaire Parts List Specific connected load: 17.70 W/m² = 3.54 W/m²/100 lx (Ground area: 80.00 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 24 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 122928 Total: 122928 1416.0 Page 3
  • 88. JUBAIL BULK PLANT SEAL RACK Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 16.10.2014 Operator: Mustang HDP
  • 89. JUBAIL BULK PLANT 16.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail SEAL RACK / Summary 440 440 440 460 460 460 460 460 460 460 460 480 480 480 480 480 480 480 480 480 480 480 480 500 500 500 500 500 500 500 500 500 500 500 2.20 m 0.00 1.10 1.90 m 0.00 0.10 0.95 1.80 Height of Room: 2.600 m, Mounting Height: 2.700 m, Light loss factor: 0.60 Values in Lux, Scale 1:25 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 470 419 514 0.892 Floor 49 366 297 396 0.810 Ceiling 86 327 269 379 0.822 Walls (4) 86 375 243 565 / Workplane: Height: 0.760 m Grid: 16 x 16 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.875, Ceiling / Working Plane: 0.696. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 8.37 W/m² = 1.78 W/m²/100 lx (Ground area: 4.18 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 1 COOPER LIGHTING - METALUX 22EN-LD1-34- UNV-L840-CD1-U METALUX 2X2 ENCOUNTER FIXTURE (Type 1)* (1.000) 3465 3465 35.0 *Modified Technical Specifications Total: 3465 Total: 3465 35.0 Page 3
  • 90. JUBAIL BULK PLANT 16.10.2014 Mustang HDP Prince Turki Road, Al-Khobar, Saudi Arabia Operator Mustang HDP Telephone +966 (3) 869-7100 Fax 966 (3) 869-7200 e-Mail STORE / Summary 640 680 680 680 680 680 680 720 720 720 720 720 720 720 720 720 720 720 760 760 760 760 760 760 760 760 760 760 760 760 2.20 m 0.00 1.10 1.90 m 0.00 0.10 0.95 1.80 Height of Room: 2.600 m, Mounting Height: 2.600 m, Light loss factor: 0.60 Values in Lux, Scale 1:25 Surface ρ [%] Eav [lx] Emin [lx] Emax [lx] u0 Workplane / 710 626 785 0.882 Floor 49 553 447 600 0.809 Ceiling 86 479 372 578 0.777 Walls (4) 86 547 366 936 / Workplane: Height: 0.760 m Grid: 16 x 16 Points Boundary Zone: 0.100 m Illuminance Quotient (according to LG7): Walls / Working Plane: 0.837, Ceiling / Working Plane: 0.675. Proportion of points with less than 400 lx (for IEQ-7): 0.00%. Luminaire Parts List Specific connected load: 14.11 W/m² = 1.99 W/m²/100 lx (Ground area: 4.18 m²) No. Pieces Designation (Correction Factor) Φ (Luminaire) [lm] Φ (Lamps) [lm] P [W] 1 1 PHILIPS DAY-BRITE - PHILIPS CFI DWAE51L840-4 PHILIPS DW VAPORLUME LED Molded plastic and formed steel housing, clear patterned plastic enclosure (Type 1)* (1.000) 5122 5122 59.0 *Modified Technical Specifications Total: 5122 Total: 5122 59.0 Page 3
  • 91. JUBAIL BULK PLANT FIRE WATER PUMPS STATION Partner for Contact: SAUDI ARABIAN OIL COMPANY Order No.: 1 Company: SAUDI ARAMCO Customer No.: 1 Date: 15.01.2015 Operator: Mustang HDP