Peter, an electrician, used Agilent handheld meters and Bluetooth adapters as a wireless data logging system to troubleshoot a customer's high electricity bill. He monitored the farm's electrical loads over 1.5 hours and spotted an intermittent load that was running every 4 minutes. This led to discovering a broken water pipe causing the pump to run constantly, significantly increasing usage. The data logging system allowed Peter to non-invasively monitor and graph electrical usage over time to identify the source of the problem.
Agilent turn your agilent handheld meter into a data logger case study_5991-2084_en
1. Turn Your Agilent Handheld Meter
into A Data Logger
Case Study
Introduction
Peter Argyropoulos, owner and sole employee of Petros Electric, is a professional
electrician open to trying new tools to improve his service. Peter groups his work
Petros Electric into two categories: service calls and contracting jobs. Contracting jobs are typically
Uses Agilent installations that have a well-defined scope. In contrast, the majority of service
calls are from homeowners unable to resolve electrical issues on their own. These
Handheld Meters problems typically involve performing diagnostics and troubleshooting, and require
as Data Loggers test and measurements tools to identify the root cause. Recently Peter tried the
Agilent wireless remote connectivity solution, which allowed him to use his Agilent
handheld meters together as a data logger system.
Figure 1. Application configuration
2. Problem Solution
One of Petros Electric’s customers To initiate troubleshooting Peter needed After monitoring the main service
owns a small farm. This customer was to monitor the farm’s power loads feeders for about 1.5 hours, Peter was
concerned about his extremely high over a period of time. Without a data able to spot a large, intermittent load.
electricity bill, which covered a 30-day logger, this troubleshooting task would The graph (similar to the one shown in
billing period during the winter months. be difficult however he used Agilent’s Figure 2) showed that something was
Even though his usage habits had not newly-introduced wireless remote running approximately 1 minute and
changed over that duration, he was connectivity solution. The configuration 20 seconds every four minutes. It was
charged for significantly higher usage. used one Agilent U1272A handheld now possible to narrow the problem
Like many small farms, his was not an multimeter and two U1212A clamp down to the water pump, which lead to
energy intensive operation. Most of the meters, each equipped with Agilent the discovery of a broken underground
electricity was used in the main house U1177A Bluetooth® adapters. The water pipe in an outbuilding. Under
and a small bungalow for typical loads, solution also included an android tablet normal conditions, the pump would
like lighting, cooking, HVAC, and hot or phone loaded with a free Agilent only run when someone was using the
water. Without any idea why power con- Mobile Logger application. water. The constantly running water
sumption had changed so drastically, he pump had played the major role in the
called Petros to isolate the problem. Using the two clamp meters, he was farm owner’s high electricity bill along
able to monitor the current on the two with a number of other small loads
“hot” wires of the service as show in like a space heater used that winter
Figure 1. The Agilent U1272A multime- and a water bed heater, both of which
ter was used to measure the voltage showed up on graph as constant, low
between the two “hot” wires. level loads.
Figure 2. Voltage, current, and power trend logging with Agilent Mobile Logger app
2