UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 1.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
Fire Safety Technical
Guide
FIRE ALARMS SYSTEMS - UCL GENERAL
INSTALLATION DESIGN GUIDANCE &
EMPLOYERS REQUIREMENTS
(All Buildings Except Sleeping Accommodation)
Contents:
1.0 Introduction............................................................................................................................................................1
2.0. UCL Fire Alarm Device Standards.....................................................................................................................2
3.0. General Requirements & Design Standards ..................................................................................................2
4.0. Fire Alarm Panels & Electrical Supplies...........................................................................................................4
5.0. Manual Call Points................................................................................................................................................5
6.0. Sounders (Sound Pressure Requirements) .....................................................................................................5
7.0. Facilities For Hearing Impaired People...........................................................................................................7
8.0. Beam Detectors........................................................................................................................................................7
9.0. Fire Resistant Cabling ..........................................................................................................................................8
10.0. Marking And Indicating of Fire Alarm Devices ............................................................................................8
11.0. Ceilings, Ducts & Voids........................................................................................................................................8
12.0. Door Hold Open, Fire Dampers & Other Automatically Released Equipment.....................................9
13.0. Access Control Devices Connected to Fire Alarm Systems.....................................................................9
14.0. Provision of Audible & Visual Warning at Internal Building Boundaries.................................................9
15.0. Mechanical & Electrical, Air Handling & Smoke Control Equipment.....................................................9
16.0. Cause & Effect Matrix Fire Alarm System .....................................................................................................10
17.0. Fire Brigade Communications.........................................................................................................................10
18.0. General Commissioning Requirements........................................................................................................10
19.0. Quick Overview ..................................................................................................................................................12
The following information will be of assistance to Design Consultants, Project
Managers and Contractors employed by UCL or its agents.
~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
1.0. INTRODUCTION
1.1. The raising of the alarm and warning to occupants in case of fire is a legal
requirement. The addition of Automatic Fire Detection (AFD) is very often
desirable to assist in early detection, property protection and in some
instances an offset to extended Means of Escape (MoE) conditions.
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 2.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
1.2. UCL as the Client strives to improve its standards, only fire alarm system
designers, installers and maintenance companies that can demonstrate BAFE
SP203 or LPC1014 and with ISO9001 Quality Management System compliance
or equivalent. Therefore, the design, complexity and cost of a fire alarm
system including both capital and ‘whole life’ maintenance costs will need to
be considered carefully during project design.
1.3. This technical Note is to be regarded as a general statement of requirements
and is in addition to any British Standard recommendation or other instructions
received from the Local Fire or Building Control Authorities.
2.0. UCL FIRE ALARM DEVICE STANDARDS
2.1. All UCL fire alarm systems and devices are to use ‘OPEN APOLLO’ protocol only,
(unless the existing system is not compatible) with standard equipment to
ensure communality of systems, efficiency of maintenance and control of
software access. No other fire alarm panels or systems will be acceptable
unless written permission through the UCL Director Engineering Maintenance &
Infrastructure (EMI) / UCL Fire Safety Manager is sought first.
2.2. Loop Capacity - loops should be designed so that the numbers of devices on
the loop is limited so that there is some (approx.) 20% spare capacity e.g.
maximum loop capacity = 126 devices - then the actual loop device numbers
should be no more than 105 devices as a general rule.
3.0. GENERAL REQUIREMENTS & DESIGN STANDARDS
3.1. All fire alarm systems in UCL premises are to be designed to comply with the
latest edition of BS 5839-1 and BS5839 series, as necessary.
3.2. Unwanted alarms - the London Fire Brigade and other Fire Authorities require all
possible measures to be taken to reduce the instances of unwanted fire alarm
activations and calls to the fire authority. Designers of fire alarm systems must
to take considerable care to ensure that their fire alarm design reduces
unwanted fire alarms through thoughtful understanding of room/space
function where the detection is provided avoid unwanted activation as far a
reasonably practicable.
3.3. All new and refurbished fire alarm systems (except for sleeping risk - see TN055)
are to meet a minimum standard of BS 5839-1: Life Risk 4/3 (L4/L3) provision of
Automatic Fire Detection (AFD).
Note 1: Category L4/3 - the minimum standard of L4 provides AFD to all escape routes; this is to be
supplemented by risk assessing all rooms off escape stairs and corridors for the provision of additional
AFD to bring the system up to L3 standard. For example: all corridors and rooms off a staircase and high
risk rooms such as laboratories, plant rooms, storage may require detection, but office accommodation
(unless in single escape condition will probably not require additional detection). Risk analysis is to be
completed as part of the design of the system.
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 3.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
Note 2: each new system will need to be approved on a project-by-project basis to ensure that the
correct cover of fire detection has been provided. Where AFD is provided in existing refurbished areas
then generally, the devices should remain unless effected by wall or ceiling changes, which interfere with
the existing device positions.
3.4. Life Category L2 or L1 Standards - additional AFD to Life Category L2 or L1
standard, should be provided for specific areas such as ‘high risk’ or high value
(i.e. equipment or facilities in excess ÂŁ0.5 million insurance value) or, where
part of a ‘fire engineered’ solution. The UCL Fire Safety Manager should be
consulted in the first instance.
3.5. Optical Detectors - as a basic rule only ‘optical’ detectors should be used;
however, each project must be judged specifically on risk and guidance
provided in BS5839-1.
3.6. Other Detectors - in areas where there is an obvious risk of false alarms
including persistent dusty or dirty conditions then the following detector heads
should be considered:
(a). 1st Rate of Rise heat detectors;
(b). 2nd Fixed heat at 55°C, 75°C or 90°C to be used where there is likely to
be high ambient temperatures (boiler rooms or steam producing
apparatus);
3.7. Apollo Discovery Multi-Sensing - heads to be used in:
(a). all laboratories;
(b). kitchens and adjacent areas;
(c). other suitable locations;
(d). multi-sensing heads have five settings (guidance only check the latest
specification by Apollo for accuracy before instructing):
 Mode 1 - the most sensitive setting using both heat & smoke monitoring and
reacting at around less than 3% obscuration of the optical head;
 Mode 2 - optical sensing setting only, that reacts at less than 3% obscuration of the
optical head,
 Mode 3 - medium sensitivity setting, which uses both heat & smoke monitoring and
reacts at less than 3% obscuration of the optical head;
 Mode 4 - least sensitive setting using both heat & smoke monitoring and reacting at
around 5% obscuration of the optical head - use this setting in all laboratories and
peripheral kitchen areas;
 Mode 5 - heat sensing setting only;
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 4.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
4.0. FIRE ALARM PANELS & ELECTRICAL SUPPLIES
4.1. The fire detection system shall be designed, installed and commissioned in
accordance with the latest editions of BS5839-1, BSEN 54 Parts 1, 2 & 4 and
other relevant codes of practice.
4.2. The panel must be capable and compatible of using and switching between
all modes of Apollo Discovery detection heads, using alarm confirmation
facilities. In addition, have pier-to-pier networking and IP gateway facilities.
4.3. UCL Fire Alarm Panel Provision - only the manufactures of following fire alarm
panel are to be used:
 C-TEC - ZFP Range of 2 to 8 loop touchscreen controlled panel (depending
on size and complexity of premises) www.c-tec.co.uk);
 Morley IAS ZX series (see: www.morley-ias.co.uk);
 Advanced Electronic Ltd (see: www.advancedco.com);
 Kentec Ltd - small units and suppression alarms (see: www.kentec.co.uk);
Electrical Supplies & Batteries:
4.4. UCL requires standby batteries for fire alarm systems to last for 60 hours not for
the minimum specified by the British Standard of 24 hours.
4.5. Main Electrical Supply to Fire Alarm Panels - any new fire alarm system will
require a dedicated 240v ac supply in accordance with the latest editions of
BS7671 & BS 5839-1. This circuit is to be installed using fire resistant cable and
terminated into a double pole, isolating spur with key switch as defined in BS
5839-1.
4.6. Main Electrical Isolation to Fire Alarm Panels - means should be provided for
double pole isolation of the mains supply to all parts of the system; the isolation
facilities should be suitably sited, near the equipment served, for use by
maintenance technicians without the need for access to remote parts of the
building. It should be possible to lock the facilities in both the normal and
isolate positions to prevent unauthorised use. It should be possible to lock the
facilities in both the normal and isolate positions to prevent unauthorised use.
4.7. UCL requires a ‘Fire Safety Isolator Switch’ (available from www.firesafe.co.uk) to
be provided which is a secure method for safely isolating the mains voltage
supply to fire systems in accordance with BS 5839-1.
 The 'Fire Safety Isolation' switch can only be isolated by an authorised
person, by means of a keylock switch - the key is removable in both
ON/OFF positions;
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 5.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
 The fuse cannot be removed without taking the cover off & when in the off
position the FUSE is disconnected from the supply;
 A neon indicator is provided to indicate mains present at the switched
output;
 Technical Specification:
o Working Voltage : 250AV
o Switch Contact Rating : Double Pole - 250V AC 4Amp
o FUSE Rating : Max - 6A Fast (20mm) supplied
o Enclosure Material : RoHS Compliant FR ABS
o Weight : 175g
o Switch Surge Rating : 80Amp
o Key Number : 901
o Housing Size: Single Gang : W.86 x L.86 x H.56.5mm
5.0. Manual Call Points
5.1. The following Manual Call Points (MCPs) should be used for all systems:
 Apollo MCPs suitable for product range being installed
(see: www.apollo-fire.co.uk);
 KAC MCPs Alarm Company Ltd (see: www.kac.co.uk);
5.2. Anti-Tamper security covers - in student halls circulation spaces, common
rooms, bars of UCL Student’s Union occupancy and vulnerable places - Anti-
Tamper security covers are to be fitted to each call point supplied by:
 Apollo - transparent hinged Cover (Apollo Ref: 26729-152);
 KAC Ltd - as above under 'accessories' (KAC Ref: PS200 Plain Hinged
Cover);
6.0. SOUNDERS (SOUND PRESSURE REQUIREMENTS)
6.1. The following standard sounders may be used:
 Apollo - loop driven sounders with setting of 90+dB(A);
 Fulleon - further information can be found at: www.fulleon.co.uk;
 Bells - standard 8” or 10” ringing bells, where appropriate;
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 6.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
6.2. General Note on Sound Levels - experience has found that it is necessary to
have higher sounder levels to engage and motivate students and some staff
to evacuate the building. UCL requires a higher standard of audibility than BS
5839-1 for sounder coverage, therefore the average sounder level throughout
the building should meet or exceed 75 dB(A) in all areas. Often the BS
minimum sounder levels are not adequate for this task; furthermore, fire doors
can reduce sounder levels by up to 40 dB(A) when closed further reducing
overall sounder levels.
(a). Contingency Funds - consultants and contractors are to ensure that
contingency funds from the project are available at pre-contract, to
ensure that addition sounders can be installed at commissioning, should
the sound pressure coverage fall below acceptable levels any
particular area.
(b). Where sound levels fall below this standard, additional sounders MUST be
installed or other means used, to raise the sound levels.
(c). At the commissioning of the system (regardless of the size of installation),
a sound pressure check MUST be carried out with sound levels being
recorded on a log sheet. The log is to be submitted with the
‘Commissioning Certificate’ short fall are to be increased by the
addition of extra sounders to the area.
6.3. Voice Sounders (Preferred Option where Budgets Allow) - the following voice
sounders conforming to BS5839-8 can be used combination voice and tone
sounders should be used in all areas where the public or large numbers of
students' use the space, where phased evacuation or the need to
differentiate buildings is to be considered.
(a). Vimpex Ltd - 'Fire Cryer' (see: www.vimpex.co.uk) standard with the
following voice messages:
(1). Use Ref: (AK) “Fire emergency - please remain calm and
evacuate the building immediately” (Female Voice);
(2). Use Ref: (AC) “This is a fire alarm test - No action required - No
action required” (Female Voice).
(3). Use Ref: (AE) “Fire alarm test now complete” (Female Voice).
(b). Apollo system may also be considered;
6.4. Visual Alarms - meeting BSEN54-23 to be provided (visual flashing red strobe
lights or new LED Technology) in the following locations:
(a). In addition to audible sounders in noisy environments such as workshops
/ plant rooms / roof plant areas etc.;
(b). Environments where audible alarms are not acceptable (control rooms /
sound or anechoic booths etc.);
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 7.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
(c). Disabled Refuges & WC - where disabled or hearing impaired persons
may use facilities (such as WCs) and in Disabled Refuges to allow
communications with other by users;
(d). Find the Panel - to identify and locate the main fire alarm panel
particularly in property with identical frontage, or where the panel
location is not obvious or in the normal location of the main entrance
area;
6.5. Specialist Alarms - there may be projects that require more specialist
equipment (e.g. external) to be specified, in which case Klaxon units should be
considered. Further information can be found at www.klaxonsignals.com
7.0. FACILITIES FOR HEARING IMPAIRED PEOPLE
7.1. UCL has a specific policy and procedures for accommodating people with
disabilities - please discus with UCL Fire Safety Manager prior to design.
7.2. Deaf Messaging Service (DMS) - UCL uses a DMS system connected to the fire
alarm for hearing impaired persons through www.alarmscom.co.uk - further
details please see www.ucl.ac.uk/fire - UCL Fire Safety Technical Note TN007.
7.3. Visual Alarms - visual alarms are to be provided (visual flashing Red strobe
lights or new LED Technology) where disabled or hearing impaired persons
may use facilities (such as WCs or common rooms etc.). UCL will not accept
blanket coverage of a building with supplementary visual alarms (LED) as per
guidance in BS 5839-1.
8.0. BEAM DETECTORS
8.1. Where there is a requirement for covering large open spaces then Open Area
Smoke Imaging Detection (OSID) by Xtralis Ltd beam detectors should be
considered.
(a). These beam detectors use two wavelengths to distinguish between
particle size and solid intruding objects, thus helping to reduce
unwanted alarms. Moreover, one unit because of its design covers
much more area with multipoint viewing from a single beam detector
head, thus reducing the need for point detection. Further information
can be found at www.xtralis.com.
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 8.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
9.0. FIRE RESISTANT CABLING
9.1. Fire cables used in the installation of fire alarm systems meeting the latest
edition of BS 5839-1 / BS 6387 / BS 7629 / BS EN 50200 PH120 in design.
9.2. All cables shall be coloured Red, unless there is overriding aesthetic reasons for
White to be used. Special attention is to be paid to the terminating of cables
to ensure that earth faults are eliminated.
9.3. The following cables should be used in all instances:
(a). FP 200 Gold, equal or approved;
(b). MICC cabling is required where routes provide mission critical signals or
pass through a high risk or vulnerable areas (as per BS 5839-1);
9.4. Fixing - all fire alarm cabling is to be fixed to the structure of the building, fixed
in a cable tray or cable management system only using metal ties. No other
fixing is acceptable.
10.0. MARKING AND INDICATING OF FIRE ALARM DEVICES
10.1. Labelling - all fire alarm devices are to be permanently marked or using
suitable adhesive labels, to indicate the device Zone and Address number.
10.2. Identification - where remote or hidden detectors / devices are placed in
voids, ducts or above ceilings, a suitable LED repeater indicator is to be
provided in a logical and adjacent location. All LED indicators are to be
clearly marked specifying type of device, address number and remote device
location.
11.0. CEILINGS, DUCTS & VOIDS
11.1. Ceiling Voids - generally, where a void of 800 mm or greater than 10% of the
room height:
(a). Variation - considered as 'low risk' (e.g. simple light units only within it, or if
fire spread beyond the void / room of origin etc is unlikely) - then it is
reasonable not to provide AFD in these spaces. This should be recorded
as a variation on the relevant system certificate.
(b). Higher Risk - where there is an obvious risk such as significant electrical
equipment (other than light units) or air handling units / chillers / void
passes over other rooms or compartments, then the void should be
provided with appropriate automatic fire detection as any electrical /
equipment fire may not be detected at it initial stages. Clarification
may be sought for the UCL fire safety manger.
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 9.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
11.2. Detectors in Voids & Ducts - any void where detection is provided MUST be fully
accessible and not obstructed for maintenance purposes. This means that
ceiling tiles or access panels must be available directly below the detector to
allow maintenance and a testing pole to be used, which requires a clear
vertical path from below to be maintained.
11.3. Identification of Hidden Devices - see Para 10.2 above
12.0. DOOR HOLD OPEN, FIRE DAMPERS & OTHER AUTOMATICALLY
RELEASED EQUIPMENT
12.1. These items should adhere to the terms of latest edition of BS 5839-3. It should
be noted that 'door holders' are generally not acceptable on any fire door
that leads directly onto a ‘protected stair’ (to be discussed with the UCL Fire
Safety Manager).
12.2. Door Release Switches - electromagnetic door release switches are to be
positioned in a clear and accessible location, to prevent damage to fixings by
doors being pulled close against the magnetic holders.
13.0. ACCESS CONTROL DEVICES CONNECTED TO FIRE ALARM SYSTEMS
13.1. Where security Access Control Systems are to be installed in a building, it will
be necessary to interface with the fire alarm system to meet UCL, local fire and
District surveyor requirements. See UCL Fire Safety Technical Note TN001 &
TN005 for specific requirements.
14.0. PROVISION OF AUDIBLE & VISUAL WARNING AT INTERNAL BUILDING
BOUNDARIES CONNECTED TO THE FIRE ALARM SYSTEM
14.1. Where the Means of Escape (MoE) routes access and egress passes through a
building boundary, it is necessary to provide Visual and Audible Warning signs
connected to the fire alarm systems and it will be necessary to interface with
the fire alarm system to meet UCL, local fire and District Surveyor Authority
requirements. See UCL fire safety technical note TN058.
15.0. MECHANICAL & ELECTRICAL, AIR HANDLING & SMOKE CONTROL
EQUIPMENT
15.1. Where mechanical & electrical systems and smoke control measures are
provided and connected to the fire alarm system, please see UCL Fire Safety
Technical Notes TN 038 & TN039 for general requirements.
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 10.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
16.0. CAUSE & EFFECT MATRIX FIRE ALARM SYSTEM
16.1. Designers are to provide a cause and effect chart for all new systems - see UCL
Fire Safety Technical Note TN063.
17.0. FIRE BRIGADE COMMUNICATIONS
17.1. Generally, UCL fire alarm panels are to alert the fire brigade via the UCL
Security Control Room using the Gallagher Security System wherever possible,
by providing:
(a). a ‘Fire Signal’ generated at the fire panel;
(b). a Fault signal generated at the fire panel;
(c). a Pre-Alarm signal generated at the fire panel;
(d). The signal is to be sent back to the UCL Security Control Room using
connections via UCL Data system network.
17.2. Monitoring Centre - the signals are to terminate at the UCL Security Control
Room on the Main Campus, which acts as a 24-hour monitoring service for the
UCL estate.
(a). The UCL Security Control Room Manager can be contacted on 020 7679
3333 and should be consulted on all signals required to be monitored by
the Security Control Room, including security / lift / plant as well as fire
alarm signals.
(b). Data connections can be arranged through the UCL ISD Network
Group.
17.3. Alarm Receiving Company (ARC) - in some locations, a specialist ARC may be
required, which should be arranged through our fire alarm maintenance
provider and Southern Monitoring Services Ltd.
 A BT Redcare line and Digital Communications (Digicom) device will also
be required. Requirements and procedures will need to be discussed with
the UCL Fire Safety Manager at the outset of the project.
18.0. GENERAL COMMISSIONING REQUIREMENTS
Design, Installation Commissioning and UCL Acceptance Certificates
18.1. The provision of the appropriate design, installation and commissioning
certificates containing information based on the ‘Model Certificates’ provided
in BS 5839-1: Annex H, to be provided by the appropriate parties. Copies of
the certificates are to be issued as following:
(a). All original certificate(s) to be placed in the Operational & Maintenance
(O&M) Manuals;
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 11.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
(b). a copy of each certificate to be issued to the Fire Alarm Maintenance
Contract Manager (UCL EM&I);
(c). a copy of each certificate to be issued the UCL Fire Safety Manager for
building’s fire certificate and fire strategy documents;
(d). any additional copies required by an authorised person;
18.2. Design Certificate - is to be provided in all cases by the Design Consultant on
completion of the design stage of the fire alarm.
18.3. Installation Certificate - is to be provided in all cases by the Contractor
installing the fire alarm system, on completion of the installation stage.
18.4. Commissioning Certificate - is to be provided in all cases by Commissioning
Engineers (generally UCL Fire Alarm Maintenance provider) on completion of
the testing & commissioning stage of the fire alarm.
18.5. Acceptance Certificate (UCL) - this is to be completed and issued the by
Project / Design Consultant; and witnessed by a Nominated UCL Person on
behalf of the Director of UCL Estates.
18.6. Only on completion of the ‘Acceptance Certificate’ witnessed by a UCL
Nominated Person may:
(a). a new system, become the primary ‘Warning in Case of Fire’ for the
building;
(b). where the fire alarm system has been replaced / upgraded etc may the
old system be switched off and decommissioned. The new system may
then become the primary ‘Warning in Case of Fire’ for the building.
18.7. Addressing of Fire Device Locations - the programming of the device address
must be carefully considered to ensure that its location matches the local,
generic or room numbers to prevent confusion by staff, contractors or the Fire
Brigade in locating the device.
18.8. Drawing and Zone Chart - zone chart information is to be supplied as part of
the commissioning of the fire alarm system as follows:
(a). Clear fire alarm zone information in ‘A4 Word’ format, is to be provided
in a suitable ‘clip frame’ position adjacent to the fire alarm panel. This is
to provide quick reference to incident location.
(b). ‘As Installed’ Drawings are to be provided on hard copy A1 sheets and
in electronic AutoCAD 2007+ Version format scale of 1:50, 1:100 or 1:200
as appropriate.
UCL Fire Technical Note - TN054
__________________________________________________________________________________________________________
Date Last Amended: Jan 15 12.
Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does
not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities
19.0. QUICK OVERVIEW
19.1. General equipment overview required by UCL for new and existing fire alarm
systems on upgrading refurbishment etc (where practical):
Items / Devices Details Protocols & Remarks
Fire Panels C-Tec / Advance / Morley IAS ZX
Open Protocol / Apollo /
Addressable
Manual Call
Points
Apollo or KAC Type to Suite
Open Protocol / Apollo /
Addressable
Smoke Detectors Apollo Range - Type to Suite
Open Protocol / Apollo /
Addressable
Heat Detectors Apollo Range - Type to Suite
Open Protocol / Apollo /
Addressable
Multi-Sensing
Detectors
Apollo Discovery Range
Open Protocol / Apollo /
Addressable
Bells 8” / 10” To Suite Open Protocol / Addressable
Sounders
Apollo / Fulleon Range - Type to
Suite
Open Protocol / Addressable
Voice Sounders Vimpex ‘Firecryer’ Open Protocol / Addressable
Beam Detectors
Open Area Smoke Imaging
Detection (OSID) by xtralis
Open Protocol / Addressable
(www.xtralis.com)
Building Interface Philip Payne 2784 Range
‘Fire Alarm Activated Do not Enter’
illuminated signs
Cables
FP 200 Gold (or equivalent)
MIC (where required by BS5839-1)
Red unless aesthetic consideration
required
Special / Bespoke
Klaxon Ltd
(www.klaxonsignals.com)
One off external fittings etc
Flame Proof /
Explosive Proof
(EïŁ)
Apollo & CooperMEDC Ltd
(www.cooper-
safety.com/brands/medc)
BS EN 60079-10 - Explosion Proof (EïŁ)
& outside fittings
Visual Indicators
Do not blanket cover for DDA -
separate arrangements at UCL
Red LED indicators fitted to sounder
units
Deaf & Hearing
Impaired Warning
Systems
Deaf Message Service (DMS) or
similar texting system special )
Alarmscom Ltd
www.alarmscom.co.uk
Discuss with UCL Fire Safety Manager
End

More Related Content

Viewers also liked

understanding our past to improve our future
understanding our past to improve our futureunderstanding our past to improve our future
understanding our past to improve our futureGillian Smith
 
Fqh 1 siswa juni 14
Fqh 1 siswa  juni 14Fqh 1 siswa  juni 14
Fqh 1 siswa juni 14Jannatur Rohmah
 
KDK Events
KDK EventsKDK Events
KDK Eventspeffler
 
Ufone tum he tu ho!
Ufone tum he tu ho!Ufone tum he tu ho!
Ufone tum he tu ho!saadtipu sultan
 
Resource manager performance appraisal
Resource manager performance appraisalResource manager performance appraisal
Resource manager performance appraisaltimfaris792
 
My vacations
My vacationsMy vacations
My vacationsmaria867261
 
documents (18 files merged)
documents (18 files merged)documents (18 files merged)
documents (18 files merged)SAJID KN
 
Better burger
Better burgerBetter burger
Better burgerstephen fry
 

Viewers also liked (11)

Media Audiences
Media AudiencesMedia Audiences
Media Audiences
 
understanding our past to improve our future
understanding our past to improve our futureunderstanding our past to improve our future
understanding our past to improve our future
 
Fqh 1 siswa juni 14
Fqh 1 siswa  juni 14Fqh 1 siswa  juni 14
Fqh 1 siswa juni 14
 
KDK Events
KDK EventsKDK Events
KDK Events
 
Services Commerce Capabilities Newsletter, March 2015
Services Commerce Capabilities Newsletter, March 2015Services Commerce Capabilities Newsletter, March 2015
Services Commerce Capabilities Newsletter, March 2015
 
Ufone tum he tu ho!
Ufone tum he tu ho!Ufone tum he tu ho!
Ufone tum he tu ho!
 
Resource manager performance appraisal
Resource manager performance appraisalResource manager performance appraisal
Resource manager performance appraisal
 
My vacations
My vacationsMy vacations
My vacations
 
Make Awesome Lead Pages with Funnelkit
Make Awesome Lead Pages with FunnelkitMake Awesome Lead Pages with Funnelkit
Make Awesome Lead Pages with Funnelkit
 
documents (18 files merged)
documents (18 files merged)documents (18 files merged)
documents (18 files merged)
 
Better burger
Better burgerBetter burger
Better burger
 

Similar to UCL fire alarm installation guidance

Design of an intelligent nitrogen injection system for fire saftey of power t...
Design of an intelligent nitrogen injection system for fire saftey of power t...Design of an intelligent nitrogen injection system for fire saftey of power t...
Design of an intelligent nitrogen injection system for fire saftey of power t...eSAT Journals
 
Emergi lite emergency lighting design guide
Emergi lite emergency lighting design guideEmergi lite emergency lighting design guide
Emergi lite emergency lighting design guideEmergi-Lite
 
Fire protection facilities for petroleum
Fire protection facilities for petroleumFire protection facilities for petroleum
Fire protection facilities for petroleumVINOTHP24
 
Fire class
Fire classFire class
Fire classtantoputra
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationMustafa Ali
 
Manual tvoc 2
Manual tvoc 2Manual tvoc 2
Manual tvoc 2Olian M. G.
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Shubham .
 
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fire and Gas Detection System : Part 1_The Field Devices and Its PanelsFire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fire and Gas Detection System : Part 1_The Field Devices and Its PanelsGan Chun Chet
 
Crabtree Starbreaker 2016
Crabtree Starbreaker 2016Crabtree Starbreaker 2016
Crabtree Starbreaker 2016Darren Garbett
 
S.steele functional safety ppt
S.steele functional safety pptS.steele functional safety ppt
S.steele functional safety pptSimon Steele
 
Weeks 16 17 pe 3231 maintenance and fault finding
Weeks 16 17  pe 3231 maintenance and fault findingWeeks 16 17  pe 3231 maintenance and fault finding
Weeks 16 17 pe 3231 maintenance and fault findingCharlton Inao
 
Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Jed Concepcion
 
Control room ( Advance Services )
Control room ( Advance Services ) Control room ( Advance Services )
Control room ( Advance Services ) Divyanshu Prakash
 
E3 series system 9000 0574
E3 series system 9000 0574E3 series system 9000 0574
E3 series system 9000 0574Joan Loyola Riquero
 
Bserviceproject2
Bserviceproject2Bserviceproject2
Bserviceproject2Nge Chen
 
Building Services Report
Building Services ReportBuilding Services Report
Building Services ReportAmos Tan
 
Murco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetMurco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetThorne & Derrick UK
 
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using ArduinoBluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using ArduinoIRJET Journal
 

Similar to UCL fire alarm installation guidance (20)

Design of an intelligent nitrogen injection system for fire saftey of power t...
Design of an intelligent nitrogen injection system for fire saftey of power t...Design of an intelligent nitrogen injection system for fire saftey of power t...
Design of an intelligent nitrogen injection system for fire saftey of power t...
 
Emergi lite emergency lighting design guide
Emergi lite emergency lighting design guideEmergi lite emergency lighting design guide
Emergi lite emergency lighting design guide
 
Fire protection facilities for petroleum
Fire protection facilities for petroleumFire protection facilities for petroleum
Fire protection facilities for petroleum
 
Fire class
Fire classFire class
Fire class
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector Presentation
 
Manual tvoc 2
Manual tvoc 2Manual tvoc 2
Manual tvoc 2
 
Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?Why are fire detection & alarm system is required in buildings?
Why are fire detection & alarm system is required in buildings?
 
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fire and Gas Detection System : Part 1_The Field Devices and Its PanelsFire and Gas Detection System : Part 1_The Field Devices and Its Panels
Fire and Gas Detection System : Part 1_The Field Devices and Its Panels
 
Crabtree Starbreaker 2016
Crabtree Starbreaker 2016Crabtree Starbreaker 2016
Crabtree Starbreaker 2016
 
S.steele functional safety ppt
S.steele functional safety pptS.steele functional safety ppt
S.steele functional safety ppt
 
Weeks 16 17 pe 3231 maintenance and fault finding
Weeks 16 17  pe 3231 maintenance and fault findingWeeks 16 17  pe 3231 maintenance and fault finding
Weeks 16 17 pe 3231 maintenance and fault finding
 
ACA-02
ACA-02ACA-02
ACA-02
 
Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)Building Electronics (Fire Detection and Alarm System and CCTV)
Building Electronics (Fire Detection and Alarm System and CCTV)
 
Control room ( Advance Services )
Control room ( Advance Services ) Control room ( Advance Services )
Control room ( Advance Services )
 
E3 series system 9000 0574
E3 series system 9000 0574E3 series system 9000 0574
E3 series system 9000 0574
 
Bserviceproject2
Bserviceproject2Bserviceproject2
Bserviceproject2
 
Building Services Report
Building Services ReportBuilding Services Report
Building Services Report
 
Murco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data SheetMurco Fixed Gas Detectors - Data Sheet
Murco Fixed Gas Detectors - Data Sheet
 
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using ArduinoBluetooth Based Fire Detection and Robust Protection System By Using Arduino
Bluetooth Based Fire Detection and Robust Protection System By Using Arduino
 
Fire alarm systems
Fire alarm systemsFire alarm systems
Fire alarm systems
 

More from 1234marvin

Cc1608 fire systems design guide
Cc1608 fire systems design guideCc1608 fire systems design guide
Cc1608 fire systems design guide1234marvin
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline1234marvin
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline1234marvin
 
Ucl fire tn_054
Ucl fire tn_054Ucl fire tn_054
Ucl fire tn_0541234marvin
 
Induction machines
Induction machinesInduction machines
Induction machines1234marvin
 
Induction machines
Induction machinesInduction machines
Induction machines1234marvin
 

More from 1234marvin (6)

Cc1608 fire systems design guide
Cc1608 fire systems design guideCc1608 fire systems design guide
Cc1608 fire systems design guide
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline
 
2011 firealarmbookonline
2011 firealarmbookonline2011 firealarmbookonline
2011 firealarmbookonline
 
Ucl fire tn_054
Ucl fire tn_054Ucl fire tn_054
Ucl fire tn_054
 
Induction machines
Induction machinesInduction machines
Induction machines
 
Induction machines
Induction machinesInduction machines
Induction machines
 

Recently uploaded

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsCall Girls in Nagpur High Profile
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxDeepakSakkari2
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024Mark Billinghurst
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile servicerehmti665
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝soniya singh
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCall Girls in Nagpur High Profile
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...9953056974 Low Rate Call Girls In Saket, Delhi NCR
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxPoojaBan
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...srsj9000
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.eptoze12
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130Suhani Kapoor
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineeringmalavadedarshan25
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...VICTOR MAESTRE RAMIREZ
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2RajaP95
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfAsst.prof M.Gokilavani
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxJoĂŁo Esperancinha
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learningmisbanausheenparvam
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )Tsuyoshi Horigome
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxbritheesh05
 

Recently uploaded (20)

High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur EscortsHigh Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
High Profile Call Girls Nagpur Meera Call 7001035870 Meet With Nagpur Escorts
 
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
VICTOR MAESTRE RAMIREZ - Planetary Defender on NASA's Double Asteroid Redirec...
 
Biology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptxBiology for Computer Engineers Course Handout.pptx
Biology for Computer Engineers Course Handout.pptx
 
IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024IVE Industry Focused Event - Defence Sector 2024
IVE Industry Focused Event - Defence Sector 2024
 
Call Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile serviceCall Girls Delhi {Jodhpur} 9711199012 high profile service
Call Girls Delhi {Jodhpur} 9711199012 high profile service
 
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
Model Call Girl in Narela Delhi reach out to us at 🔝8264348440🔝
 
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service NashikCollege Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
College Call Girls Nashik Nehal 7001305949 Independent Escort Service Nashik
 
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
🔝9953056974🔝!!-YOUNG call girls in Rajendra Nagar Escort rvice Shot 2000 nigh...
 
Heart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptxHeart Disease Prediction using machine learning.pptx
Heart Disease Prediction using machine learning.pptx
 
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
Gfe Mayur Vihar Call Girls Service WhatsApp -> 9999965857 Available 24x7 ^ De...
 
Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.Oxy acetylene welding presentation note.
Oxy acetylene welding presentation note.
 
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
VIP Call Girls Service Hitech City Hyderabad Call +91-8250192130
 
Internship report on mechanical engineering
Internship report on mechanical engineeringInternship report on mechanical engineering
Internship report on mechanical engineering
 
Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...Software and Systems Engineering Standards: Verification and Validation of Sy...
Software and Systems Engineering Standards: Verification and Validation of Sy...
 
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2HARMONY IN THE HUMAN BEING - Unit-II UHV-2
HARMONY IN THE HUMAN BEING - Unit-II UHV-2
 
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdfCCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
CCS355 Neural Network & Deep Learning UNIT III notes and Question bank .pdf
 
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptxDecoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
Decoding Kotlin - Your guide to solving the mysterious in Kotlin.pptx
 
chaitra-1.pptx fake news detection using machine learning
chaitra-1.pptx  fake news detection using machine learningchaitra-1.pptx  fake news detection using machine learning
chaitra-1.pptx fake news detection using machine learning
 
SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )SPICE PARK APR2024 ( 6,793 SPICE Models )
SPICE PARK APR2024 ( 6,793 SPICE Models )
 
Artificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptxArtificial-Intelligence-in-Electronics (K).pptx
Artificial-Intelligence-in-Electronics (K).pptx
 

UCL fire alarm installation guidance

  • 1. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 1. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities Fire Safety Technical Guide FIRE ALARMS SYSTEMS - UCL GENERAL INSTALLATION DESIGN GUIDANCE & EMPLOYERS REQUIREMENTS (All Buildings Except Sleeping Accommodation) Contents: 1.0 Introduction............................................................................................................................................................1 2.0. UCL Fire Alarm Device Standards.....................................................................................................................2 3.0. General Requirements & Design Standards ..................................................................................................2 4.0. Fire Alarm Panels & Electrical Supplies...........................................................................................................4 5.0. Manual Call Points................................................................................................................................................5 6.0. Sounders (Sound Pressure Requirements) .....................................................................................................5 7.0. Facilities For Hearing Impaired People...........................................................................................................7 8.0. Beam Detectors........................................................................................................................................................7 9.0. Fire Resistant Cabling ..........................................................................................................................................8 10.0. Marking And Indicating of Fire Alarm Devices ............................................................................................8 11.0. Ceilings, Ducts & Voids........................................................................................................................................8 12.0. Door Hold Open, Fire Dampers & Other Automatically Released Equipment.....................................9 13.0. Access Control Devices Connected to Fire Alarm Systems.....................................................................9 14.0. Provision of Audible & Visual Warning at Internal Building Boundaries.................................................9 15.0. Mechanical & Electrical, Air Handling & Smoke Control Equipment.....................................................9 16.0. Cause & Effect Matrix Fire Alarm System .....................................................................................................10 17.0. Fire Brigade Communications.........................................................................................................................10 18.0. General Commissioning Requirements........................................................................................................10 19.0. Quick Overview ..................................................................................................................................................12 The following information will be of assistance to Design Consultants, Project Managers and Contractors employed by UCL or its agents. ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ 1.0. INTRODUCTION 1.1. The raising of the alarm and warning to occupants in case of fire is a legal requirement. The addition of Automatic Fire Detection (AFD) is very often desirable to assist in early detection, property protection and in some instances an offset to extended Means of Escape (MoE) conditions.
  • 2. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 2. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities 1.2. UCL as the Client strives to improve its standards, only fire alarm system designers, installers and maintenance companies that can demonstrate BAFE SP203 or LPC1014 and with ISO9001 Quality Management System compliance or equivalent. Therefore, the design, complexity and cost of a fire alarm system including both capital and ‘whole life’ maintenance costs will need to be considered carefully during project design. 1.3. This technical Note is to be regarded as a general statement of requirements and is in addition to any British Standard recommendation or other instructions received from the Local Fire or Building Control Authorities. 2.0. UCL FIRE ALARM DEVICE STANDARDS 2.1. All UCL fire alarm systems and devices are to use ‘OPEN APOLLO’ protocol only, (unless the existing system is not compatible) with standard equipment to ensure communality of systems, efficiency of maintenance and control of software access. No other fire alarm panels or systems will be acceptable unless written permission through the UCL Director Engineering Maintenance & Infrastructure (EMI) / UCL Fire Safety Manager is sought first. 2.2. Loop Capacity - loops should be designed so that the numbers of devices on the loop is limited so that there is some (approx.) 20% spare capacity e.g. maximum loop capacity = 126 devices - then the actual loop device numbers should be no more than 105 devices as a general rule. 3.0. GENERAL REQUIREMENTS & DESIGN STANDARDS 3.1. All fire alarm systems in UCL premises are to be designed to comply with the latest edition of BS 5839-1 and BS5839 series, as necessary. 3.2. Unwanted alarms - the London Fire Brigade and other Fire Authorities require all possible measures to be taken to reduce the instances of unwanted fire alarm activations and calls to the fire authority. Designers of fire alarm systems must to take considerable care to ensure that their fire alarm design reduces unwanted fire alarms through thoughtful understanding of room/space function where the detection is provided avoid unwanted activation as far a reasonably practicable. 3.3. All new and refurbished fire alarm systems (except for sleeping risk - see TN055) are to meet a minimum standard of BS 5839-1: Life Risk 4/3 (L4/L3) provision of Automatic Fire Detection (AFD). Note 1: Category L4/3 - the minimum standard of L4 provides AFD to all escape routes; this is to be supplemented by risk assessing all rooms off escape stairs and corridors for the provision of additional AFD to bring the system up to L3 standard. For example: all corridors and rooms off a staircase and high risk rooms such as laboratories, plant rooms, storage may require detection, but office accommodation (unless in single escape condition will probably not require additional detection). Risk analysis is to be completed as part of the design of the system.
  • 3. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 3. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities Note 2: each new system will need to be approved on a project-by-project basis to ensure that the correct cover of fire detection has been provided. Where AFD is provided in existing refurbished areas then generally, the devices should remain unless effected by wall or ceiling changes, which interfere with the existing device positions. 3.4. Life Category L2 or L1 Standards - additional AFD to Life Category L2 or L1 standard, should be provided for specific areas such as ‘high risk’ or high value (i.e. equipment or facilities in excess ÂŁ0.5 million insurance value) or, where part of a ‘fire engineered’ solution. The UCL Fire Safety Manager should be consulted in the first instance. 3.5. Optical Detectors - as a basic rule only ‘optical’ detectors should be used; however, each project must be judged specifically on risk and guidance provided in BS5839-1. 3.6. Other Detectors - in areas where there is an obvious risk of false alarms including persistent dusty or dirty conditions then the following detector heads should be considered: (a). 1st Rate of Rise heat detectors; (b). 2nd Fixed heat at 55°C, 75°C or 90°C to be used where there is likely to be high ambient temperatures (boiler rooms or steam producing apparatus); 3.7. Apollo Discovery Multi-Sensing - heads to be used in: (a). all laboratories; (b). kitchens and adjacent areas; (c). other suitable locations; (d). multi-sensing heads have five settings (guidance only check the latest specification by Apollo for accuracy before instructing):  Mode 1 - the most sensitive setting using both heat & smoke monitoring and reacting at around less than 3% obscuration of the optical head;  Mode 2 - optical sensing setting only, that reacts at less than 3% obscuration of the optical head,  Mode 3 - medium sensitivity setting, which uses both heat & smoke monitoring and reacts at less than 3% obscuration of the optical head;  Mode 4 - least sensitive setting using both heat & smoke monitoring and reacting at around 5% obscuration of the optical head - use this setting in all laboratories and peripheral kitchen areas;  Mode 5 - heat sensing setting only;
  • 4. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 4. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities 4.0. FIRE ALARM PANELS & ELECTRICAL SUPPLIES 4.1. The fire detection system shall be designed, installed and commissioned in accordance with the latest editions of BS5839-1, BSEN 54 Parts 1, 2 & 4 and other relevant codes of practice. 4.2. The panel must be capable and compatible of using and switching between all modes of Apollo Discovery detection heads, using alarm confirmation facilities. In addition, have pier-to-pier networking and IP gateway facilities. 4.3. UCL Fire Alarm Panel Provision - only the manufactures of following fire alarm panel are to be used:  C-TEC - ZFP Range of 2 to 8 loop touchscreen controlled panel (depending on size and complexity of premises) www.c-tec.co.uk);  Morley IAS ZX series (see: www.morley-ias.co.uk);  Advanced Electronic Ltd (see: www.advancedco.com);  Kentec Ltd - small units and suppression alarms (see: www.kentec.co.uk); Electrical Supplies & Batteries: 4.4. UCL requires standby batteries for fire alarm systems to last for 60 hours not for the minimum specified by the British Standard of 24 hours. 4.5. Main Electrical Supply to Fire Alarm Panels - any new fire alarm system will require a dedicated 240v ac supply in accordance with the latest editions of BS7671 & BS 5839-1. This circuit is to be installed using fire resistant cable and terminated into a double pole, isolating spur with key switch as defined in BS 5839-1. 4.6. Main Electrical Isolation to Fire Alarm Panels - means should be provided for double pole isolation of the mains supply to all parts of the system; the isolation facilities should be suitably sited, near the equipment served, for use by maintenance technicians without the need for access to remote parts of the building. It should be possible to lock the facilities in both the normal and isolate positions to prevent unauthorised use. It should be possible to lock the facilities in both the normal and isolate positions to prevent unauthorised use. 4.7. UCL requires a ‘Fire Safety Isolator Switch’ (available from www.firesafe.co.uk) to be provided which is a secure method for safely isolating the mains voltage supply to fire systems in accordance with BS 5839-1.  The 'Fire Safety Isolation' switch can only be isolated by an authorised person, by means of a keylock switch - the key is removable in both ON/OFF positions;
  • 5. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 5. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities  The fuse cannot be removed without taking the cover off & when in the off position the FUSE is disconnected from the supply;  A neon indicator is provided to indicate mains present at the switched output;  Technical Specification: o Working Voltage : 250AV o Switch Contact Rating : Double Pole - 250V AC 4Amp o FUSE Rating : Max - 6A Fast (20mm) supplied o Enclosure Material : RoHS Compliant FR ABS o Weight : 175g o Switch Surge Rating : 80Amp o Key Number : 901 o Housing Size: Single Gang : W.86 x L.86 x H.56.5mm 5.0. Manual Call Points 5.1. The following Manual Call Points (MCPs) should be used for all systems:  Apollo MCPs suitable for product range being installed (see: www.apollo-fire.co.uk);  KAC MCPs Alarm Company Ltd (see: www.kac.co.uk); 5.2. Anti-Tamper security covers - in student halls circulation spaces, common rooms, bars of UCL Student’s Union occupancy and vulnerable places - Anti- Tamper security covers are to be fitted to each call point supplied by:  Apollo - transparent hinged Cover (Apollo Ref: 26729-152);  KAC Ltd - as above under 'accessories' (KAC Ref: PS200 Plain Hinged Cover); 6.0. SOUNDERS (SOUND PRESSURE REQUIREMENTS) 6.1. The following standard sounders may be used:  Apollo - loop driven sounders with setting of 90+dB(A);  Fulleon - further information can be found at: www.fulleon.co.uk;  Bells - standard 8” or 10” ringing bells, where appropriate;
  • 6. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 6. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities 6.2. General Note on Sound Levels - experience has found that it is necessary to have higher sounder levels to engage and motivate students and some staff to evacuate the building. UCL requires a higher standard of audibility than BS 5839-1 for sounder coverage, therefore the average sounder level throughout the building should meet or exceed 75 dB(A) in all areas. Often the BS minimum sounder levels are not adequate for this task; furthermore, fire doors can reduce sounder levels by up to 40 dB(A) when closed further reducing overall sounder levels. (a). Contingency Funds - consultants and contractors are to ensure that contingency funds from the project are available at pre-contract, to ensure that addition sounders can be installed at commissioning, should the sound pressure coverage fall below acceptable levels any particular area. (b). Where sound levels fall below this standard, additional sounders MUST be installed or other means used, to raise the sound levels. (c). At the commissioning of the system (regardless of the size of installation), a sound pressure check MUST be carried out with sound levels being recorded on a log sheet. The log is to be submitted with the ‘Commissioning Certificate’ short fall are to be increased by the addition of extra sounders to the area. 6.3. Voice Sounders (Preferred Option where Budgets Allow) - the following voice sounders conforming to BS5839-8 can be used combination voice and tone sounders should be used in all areas where the public or large numbers of students' use the space, where phased evacuation or the need to differentiate buildings is to be considered. (a). Vimpex Ltd - 'Fire Cryer' (see: www.vimpex.co.uk) standard with the following voice messages: (1). Use Ref: (AK) “Fire emergency - please remain calm and evacuate the building immediately” (Female Voice); (2). Use Ref: (AC) “This is a fire alarm test - No action required - No action required” (Female Voice). (3). Use Ref: (AE) “Fire alarm test now complete” (Female Voice). (b). Apollo system may also be considered; 6.4. Visual Alarms - meeting BSEN54-23 to be provided (visual flashing red strobe lights or new LED Technology) in the following locations: (a). In addition to audible sounders in noisy environments such as workshops / plant rooms / roof plant areas etc.; (b). Environments where audible alarms are not acceptable (control rooms / sound or anechoic booths etc.);
  • 7. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 7. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities (c). Disabled Refuges & WC - where disabled or hearing impaired persons may use facilities (such as WCs) and in Disabled Refuges to allow communications with other by users; (d). Find the Panel - to identify and locate the main fire alarm panel particularly in property with identical frontage, or where the panel location is not obvious or in the normal location of the main entrance area; 6.5. Specialist Alarms - there may be projects that require more specialist equipment (e.g. external) to be specified, in which case Klaxon units should be considered. Further information can be found at www.klaxonsignals.com 7.0. FACILITIES FOR HEARING IMPAIRED PEOPLE 7.1. UCL has a specific policy and procedures for accommodating people with disabilities - please discus with UCL Fire Safety Manager prior to design. 7.2. Deaf Messaging Service (DMS) - UCL uses a DMS system connected to the fire alarm for hearing impaired persons through www.alarmscom.co.uk - further details please see www.ucl.ac.uk/fire - UCL Fire Safety Technical Note TN007. 7.3. Visual Alarms - visual alarms are to be provided (visual flashing Red strobe lights or new LED Technology) where disabled or hearing impaired persons may use facilities (such as WCs or common rooms etc.). UCL will not accept blanket coverage of a building with supplementary visual alarms (LED) as per guidance in BS 5839-1. 8.0. BEAM DETECTORS 8.1. Where there is a requirement for covering large open spaces then Open Area Smoke Imaging Detection (OSID) by Xtralis Ltd beam detectors should be considered. (a). These beam detectors use two wavelengths to distinguish between particle size and solid intruding objects, thus helping to reduce unwanted alarms. Moreover, one unit because of its design covers much more area with multipoint viewing from a single beam detector head, thus reducing the need for point detection. Further information can be found at www.xtralis.com.
  • 8. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 8. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities 9.0. FIRE RESISTANT CABLING 9.1. Fire cables used in the installation of fire alarm systems meeting the latest edition of BS 5839-1 / BS 6387 / BS 7629 / BS EN 50200 PH120 in design. 9.2. All cables shall be coloured Red, unless there is overriding aesthetic reasons for White to be used. Special attention is to be paid to the terminating of cables to ensure that earth faults are eliminated. 9.3. The following cables should be used in all instances: (a). FP 200 Gold, equal or approved; (b). MICC cabling is required where routes provide mission critical signals or pass through a high risk or vulnerable areas (as per BS 5839-1); 9.4. Fixing - all fire alarm cabling is to be fixed to the structure of the building, fixed in a cable tray or cable management system only using metal ties. No other fixing is acceptable. 10.0. MARKING AND INDICATING OF FIRE ALARM DEVICES 10.1. Labelling - all fire alarm devices are to be permanently marked or using suitable adhesive labels, to indicate the device Zone and Address number. 10.2. Identification - where remote or hidden detectors / devices are placed in voids, ducts or above ceilings, a suitable LED repeater indicator is to be provided in a logical and adjacent location. All LED indicators are to be clearly marked specifying type of device, address number and remote device location. 11.0. CEILINGS, DUCTS & VOIDS 11.1. Ceiling Voids - generally, where a void of 800 mm or greater than 10% of the room height: (a). Variation - considered as 'low risk' (e.g. simple light units only within it, or if fire spread beyond the void / room of origin etc is unlikely) - then it is reasonable not to provide AFD in these spaces. This should be recorded as a variation on the relevant system certificate. (b). Higher Risk - where there is an obvious risk such as significant electrical equipment (other than light units) or air handling units / chillers / void passes over other rooms or compartments, then the void should be provided with appropriate automatic fire detection as any electrical / equipment fire may not be detected at it initial stages. Clarification may be sought for the UCL fire safety manger.
  • 9. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 9. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities 11.2. Detectors in Voids & Ducts - any void where detection is provided MUST be fully accessible and not obstructed for maintenance purposes. This means that ceiling tiles or access panels must be available directly below the detector to allow maintenance and a testing pole to be used, which requires a clear vertical path from below to be maintained. 11.3. Identification of Hidden Devices - see Para 10.2 above 12.0. DOOR HOLD OPEN, FIRE DAMPERS & OTHER AUTOMATICALLY RELEASED EQUIPMENT 12.1. These items should adhere to the terms of latest edition of BS 5839-3. It should be noted that 'door holders' are generally not acceptable on any fire door that leads directly onto a ‘protected stair’ (to be discussed with the UCL Fire Safety Manager). 12.2. Door Release Switches - electromagnetic door release switches are to be positioned in a clear and accessible location, to prevent damage to fixings by doors being pulled close against the magnetic holders. 13.0. ACCESS CONTROL DEVICES CONNECTED TO FIRE ALARM SYSTEMS 13.1. Where security Access Control Systems are to be installed in a building, it will be necessary to interface with the fire alarm system to meet UCL, local fire and District surveyor requirements. See UCL Fire Safety Technical Note TN001 & TN005 for specific requirements. 14.0. PROVISION OF AUDIBLE & VISUAL WARNING AT INTERNAL BUILDING BOUNDARIES CONNECTED TO THE FIRE ALARM SYSTEM 14.1. Where the Means of Escape (MoE) routes access and egress passes through a building boundary, it is necessary to provide Visual and Audible Warning signs connected to the fire alarm systems and it will be necessary to interface with the fire alarm system to meet UCL, local fire and District Surveyor Authority requirements. See UCL fire safety technical note TN058. 15.0. MECHANICAL & ELECTRICAL, AIR HANDLING & SMOKE CONTROL EQUIPMENT 15.1. Where mechanical & electrical systems and smoke control measures are provided and connected to the fire alarm system, please see UCL Fire Safety Technical Notes TN 038 & TN039 for general requirements.
  • 10. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 10. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities 16.0. CAUSE & EFFECT MATRIX FIRE ALARM SYSTEM 16.1. Designers are to provide a cause and effect chart for all new systems - see UCL Fire Safety Technical Note TN063. 17.0. FIRE BRIGADE COMMUNICATIONS 17.1. Generally, UCL fire alarm panels are to alert the fire brigade via the UCL Security Control Room using the Gallagher Security System wherever possible, by providing: (a). a ‘Fire Signal’ generated at the fire panel; (b). a Fault signal generated at the fire panel; (c). a Pre-Alarm signal generated at the fire panel; (d). The signal is to be sent back to the UCL Security Control Room using connections via UCL Data system network. 17.2. Monitoring Centre - the signals are to terminate at the UCL Security Control Room on the Main Campus, which acts as a 24-hour monitoring service for the UCL estate. (a). The UCL Security Control Room Manager can be contacted on 020 7679 3333 and should be consulted on all signals required to be monitored by the Security Control Room, including security / lift / plant as well as fire alarm signals. (b). Data connections can be arranged through the UCL ISD Network Group. 17.3. Alarm Receiving Company (ARC) - in some locations, a specialist ARC may be required, which should be arranged through our fire alarm maintenance provider and Southern Monitoring Services Ltd.  A BT Redcare line and Digital Communications (Digicom) device will also be required. Requirements and procedures will need to be discussed with the UCL Fire Safety Manager at the outset of the project. 18.0. GENERAL COMMISSIONING REQUIREMENTS Design, Installation Commissioning and UCL Acceptance Certificates 18.1. The provision of the appropriate design, installation and commissioning certificates containing information based on the ‘Model Certificates’ provided in BS 5839-1: Annex H, to be provided by the appropriate parties. Copies of the certificates are to be issued as following: (a). All original certificate(s) to be placed in the Operational & Maintenance (O&M) Manuals;
  • 11. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 11. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities (b). a copy of each certificate to be issued to the Fire Alarm Maintenance Contract Manager (UCL EM&I); (c). a copy of each certificate to be issued the UCL Fire Safety Manager for building’s fire certificate and fire strategy documents; (d). any additional copies required by an authorised person; 18.2. Design Certificate - is to be provided in all cases by the Design Consultant on completion of the design stage of the fire alarm. 18.3. Installation Certificate - is to be provided in all cases by the Contractor installing the fire alarm system, on completion of the installation stage. 18.4. Commissioning Certificate - is to be provided in all cases by Commissioning Engineers (generally UCL Fire Alarm Maintenance provider) on completion of the testing & commissioning stage of the fire alarm. 18.5. Acceptance Certificate (UCL) - this is to be completed and issued the by Project / Design Consultant; and witnessed by a Nominated UCL Person on behalf of the Director of UCL Estates. 18.6. Only on completion of the ‘Acceptance Certificate’ witnessed by a UCL Nominated Person may: (a). a new system, become the primary ‘Warning in Case of Fire’ for the building; (b). where the fire alarm system has been replaced / upgraded etc may the old system be switched off and decommissioned. The new system may then become the primary ‘Warning in Case of Fire’ for the building. 18.7. Addressing of Fire Device Locations - the programming of the device address must be carefully considered to ensure that its location matches the local, generic or room numbers to prevent confusion by staff, contractors or the Fire Brigade in locating the device. 18.8. Drawing and Zone Chart - zone chart information is to be supplied as part of the commissioning of the fire alarm system as follows: (a). Clear fire alarm zone information in ‘A4 Word’ format, is to be provided in a suitable ‘clip frame’ position adjacent to the fire alarm panel. This is to provide quick reference to incident location. (b). ‘As Installed’ Drawings are to be provided on hard copy A1 sheets and in electronic AutoCAD 2007+ Version format scale of 1:50, 1:100 or 1:200 as appropriate.
  • 12. UCL Fire Technical Note - TN054 __________________________________________________________________________________________________________ Date Last Amended: Jan 15 12. Issued by the - Fire Safety Manager, UCL Safety Services, Gower Street, London, WC1E 6BT - This guide is to be regarded as a general statement of requirements, but does not replace the relevant British Standards or any other instructions received from the Local Fire or Building Control Authorities 19.0. QUICK OVERVIEW 19.1. General equipment overview required by UCL for new and existing fire alarm systems on upgrading refurbishment etc (where practical): Items / Devices Details Protocols & Remarks Fire Panels C-Tec / Advance / Morley IAS ZX Open Protocol / Apollo / Addressable Manual Call Points Apollo or KAC Type to Suite Open Protocol / Apollo / Addressable Smoke Detectors Apollo Range - Type to Suite Open Protocol / Apollo / Addressable Heat Detectors Apollo Range - Type to Suite Open Protocol / Apollo / Addressable Multi-Sensing Detectors Apollo Discovery Range Open Protocol / Apollo / Addressable Bells 8” / 10” To Suite Open Protocol / Addressable Sounders Apollo / Fulleon Range - Type to Suite Open Protocol / Addressable Voice Sounders Vimpex ‘Firecryer’ Open Protocol / Addressable Beam Detectors Open Area Smoke Imaging Detection (OSID) by xtralis Open Protocol / Addressable (www.xtralis.com) Building Interface Philip Payne 2784 Range ‘Fire Alarm Activated Do not Enter’ illuminated signs Cables FP 200 Gold (or equivalent) MIC (where required by BS5839-1) Red unless aesthetic consideration required Special / Bespoke Klaxon Ltd (www.klaxonsignals.com) One off external fittings etc Flame Proof / Explosive Proof (EïŁ) Apollo & CooperMEDC Ltd (www.cooper- safety.com/brands/medc) BS EN 60079-10 - Explosion Proof (EïŁ) & outside fittings Visual Indicators Do not blanket cover for DDA - separate arrangements at UCL Red LED indicators fitted to sounder units Deaf & Hearing Impaired Warning Systems Deaf Message Service (DMS) or similar texting system special ) Alarmscom Ltd www.alarmscom.co.uk Discuss with UCL Fire Safety Manager End