XLPE
Australian standard power distribution cable

Construction:                                          Minimum Bending Radius :                                  Temperature Range :
Uncompacted Class 2 stranding, special                 10 x cable diameter                                       -40oC to +90oC
X-90 crosslinked Polyethylene (XLPE)
insulation, flame retardant & UV resistant             Nominal Voltage:
5V-90 PVC sheath.                                      600/1000V




                                                                        Nominal                                               Approx              Approx
                                                                      conductor                                               overall             weight
Part No.                                                               area mm2                 Stranding                      Ø mm                kg/km
3804590                                                                    1 x 16                     7 x 1.70                     9.4                205
3804591                                                                    1 x 25                    19 x 1.35                   11.4                 309
3804592                                                                    1 x 35                    19 x 1.53                   12.3                 412
3804593                                                                    1 x 50                    19 x 1.78                   13.7                 540
3804594                                                                    1 x 70                    19 x 2.14                   15.9                 760
3804595                                                                    1 x 95                    37 x 1.78                   17.6               1020
3804596                                                                  1 x 120                     37 x 2.03                   19.6               1270
3804597                                                                  1 x 150                     37 x 2.25                   21.7               1560
3804598                                                                  1 x 185                     37 x 2.52                   24.2               1930
3804599                                                                  1 x 240                     61 x 2.25                   27.2               2510
3804600                                                                  1 x 300                     61 x 2.52                   29.8               3120
3804601                                                                  1 x 400                     61 x 2.85                   33.4               3970
3804602                                                                  1 x 500                     61 x 3.20                   37.5               4980
3804603                                                                  1 x 630                127 x 2.52                         42               6400




Minimum size of copper earth conductors
AS/NZS 3000


Nominal area active            For copper active       Nominal area active            For copper active          Nominal area active     For copper active
conductors mm²                  conductors mm²         conductors mm²                  conductors mm²            conductors mm²           conductors mm²
1                                            *1.0      25                                                 6      185                                   70
1.5                                          *1.5      35                                               10       240                                   95
2.5                                           2.5      50                                               16       300                                  120
4                                             2.5      70                                               25       400                              ** ≥120
6                                             2.5      95                                               25       500                              ** ≥120
10                                              4      120                                              35       630                              ** ≥120
16                                              6      150                                              50


* Refer Wiring Rules, AS/NZS 3000 regarding 1.5 earthing conductors. 		
** A larger earthing conductor may be required to satisfy Clause 5.3.3.1.1




DKSH Australia Pty. Ltd.
14-17 Dansu Court, Hallam VIC 3803, Australia, Customer Service: 1800 010 113, Fax: (03) 9554 6677
www.dksh.com/australia

Xlpe pdf

  • 1.
    XLPE Australian standard powerdistribution cable Construction: Minimum Bending Radius : Temperature Range : Uncompacted Class 2 stranding, special 10 x cable diameter -40oC to +90oC X-90 crosslinked Polyethylene (XLPE) insulation, flame retardant & UV resistant Nominal Voltage: 5V-90 PVC sheath. 600/1000V Nominal Approx Approx conductor overall weight Part No. area mm2 Stranding Ø mm kg/km 3804590 1 x 16 7 x 1.70 9.4 205 3804591 1 x 25 19 x 1.35 11.4 309 3804592 1 x 35 19 x 1.53 12.3 412 3804593 1 x 50 19 x 1.78 13.7 540 3804594 1 x 70 19 x 2.14 15.9 760 3804595 1 x 95 37 x 1.78 17.6 1020 3804596 1 x 120 37 x 2.03 19.6 1270 3804597 1 x 150 37 x 2.25 21.7 1560 3804598 1 x 185 37 x 2.52 24.2 1930 3804599 1 x 240 61 x 2.25 27.2 2510 3804600 1 x 300 61 x 2.52 29.8 3120 3804601 1 x 400 61 x 2.85 33.4 3970 3804602 1 x 500 61 x 3.20 37.5 4980 3804603 1 x 630 127 x 2.52 42 6400 Minimum size of copper earth conductors AS/NZS 3000 Nominal area active For copper active Nominal area active For copper active Nominal area active For copper active conductors mm² conductors mm² conductors mm² conductors mm² conductors mm² conductors mm² 1 *1.0 25 6 185 70 1.5 *1.5 35 10 240 95 2.5 2.5 50 16 300 120 4 2.5 70 25 400 ** ≥120 6 2.5 95 25 500 ** ≥120 10 4 120 35 630 ** ≥120 16 6 150 50 * Refer Wiring Rules, AS/NZS 3000 regarding 1.5 earthing conductors. ** A larger earthing conductor may be required to satisfy Clause 5.3.3.1.1 DKSH Australia Pty. Ltd. 14-17 Dansu Court, Hallam VIC 3803, Australia, Customer Service: 1800 010 113, Fax: (03) 9554 6677 www.dksh.com/australia