Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 1
The benefits of analyzing thermal performance using computational fluid dynamic (CFD) models at the
board and server level are well understood. This practice, established for decades, has proven to be more
cost effective with respect to product design while yielding faster times to market than earlier non-
simulation methods. In addition, thermal margins have been drastically reduced without compromising
performance and reliability. For the same reasons, data center designers also rely on CFD to ensure the
most cost effective room layout without compromising server inlet air flow and temperature.
An extensive amount of data is required to accurately simulate a data center. This includes thermal
models of the installed IT equipment. Typically server manufacturers do not provide sufficient thermal
information about their products for data center simulation. Currently only the outer dimensions, name
plate power and maximum operating temperature are readily available, but for meaningful data center
results, information regarding flow rates, vent geometry, and typical power consumption is also essential.
Until recently, migrating this information across the simulation supply chain was difficult. However, with
6SigmaDC’s suite of thermal modeling tools, the process has become seamless. Now, detailed, validated
thermal models at the server level can be used in data center models to provide solid, reliable predictions
of facility operations. Using 6SigmaET, the thermal details of the server can be characterized, and a
simplified version, using a control volume (or black box) approach can be used by the rest of the 6SigmaDC
software to predict airflows and heat dissipations at the rack and room levels.
This paper will explore the creation and use of a simplified server model (SSM) using the full suite of
6SigmaDC software. A detailed server model of the Facebook Open Compute Windmill Server will be
created in 6SigmaET. This detailed model will be simplified and the SSM will be used to verify the design
of the Open Compute Rack and an example data center. The paper will discuss the benefits and limitations
of thermal simulation at the server, rack and data center level. The process followed can be seen in figure
1 overleaf. Finally, a comparison will be made between using a SSM in a data center simulation and using
basic server data readily available today, this will be conducted in a failure scenario. Air flows and
temperatures will re-assessed and a discussion presented.
Thinking Outside the Box –
Server Design for Data Center
Optimization
Marie Ross, Senior Applications Engineer
Tom Gregory, Consultant Engineer
October 2013
Ju
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 2
Detailed Server
Modeling the server in detail allows IT equipment designers to optimize and verify the design before
manufacture. It provides an understanding of the airflow requirements, optimum component placement,
and flow patterns. It is also critical for heat sink selection and flow guides. For the Windmill server, this
level of analysis provides insights on the perfect baffling structure to ensure air flow through both the CPU
heatsinks as well as the memory cards.
The server model, based on Intel’s Windmill server,
can be found on the Open Compute website
(www.opencompute.com). The CAD drawings were
downloaded, and Open Compute specifications were
imposed (Figure 2) in a 6SigmaET model.
Total power dissipation is 236 W - 7.1 W per memory
card, 50 W per CPU, 6.2 W from the Drive, 0.5 W from
the power interface, with the remainder being evenly
distributed on the motherboard. The model was
simulated in an open test chamber environment with
a supply temperature of 26.5°C. This supply
temperature was chosen as it is just below the
ASHRAE specified maximum inlet temperature of 27°C.
Server
Simulation
Simplify Server
Rack Simulation
Data Center
Simulation
Detailed simulation of the motherboard and server.
A simplified server model is created from the detailed server simulation.
Simulation of the Open Rack with simplified server models. The
rack will be simulated in a rack test environment.
Simulation of a typical modern data center.
Figure 1 – Methodology
Figure 2: Detailed Server Model
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 3
Simplified Server
It is not possible within a reasonable timescale to model thousands of duplicated detailed thermal server
models in a rack or data center simulation. However, this is not an issue as the internal layout of the server
has been verified and validated through simulation and test. In this case, after the detailed model was
finalized in 6SigmaET, a SSM was created. The SSM are shown in Figure 3.
Figure 3 – Simplified server model. Front and rear view. Vents highlighted in red.
A SSM treats all internal components as a black box. It is calculated by using the detailed server model
and creates a simplified chassis, which includes the vent geometry, flow rate and heat dissipation. This
SSM includes sufficient information so that the airflow through the data center can be accurately
predicted.
In reality when the cold aisle in the data center is contained there is potential it will become pressurized.
In this situation more air will be forced through the server than if the server was placed in open space.
To account for this, both 6SigmaRack and 6SigmaRoom have an input called the Coefficient of Excess Flow,
the value for which is calculated within the detailed server model.
The coefficient is obtained by running the detailed model in 6SigmaET at various inlet velocities to assess
its impedance. This impedance curve is then validated within 6SigmaRack to ensure that pressure drop
meets that provided with the rack. Figure 4 shows the impedance curve comparison between the rack
and server level models for this case study.
Figure 4: Comparison between detailed and simplified servers
0
10
20
30
40
50
60
70
0 20 40 60 80 100
FlowRate(CFM)
Pressure (Pa)
Detailed Simplified
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 4
Rack
Many thermal issues in the data center are caused by rack issues as opposed to the data center
environment Rack level thermal analysis gives designers and room operators insights related to the rack
thermal design. Is it properly designed? Are face plates necessary? What is the effect of cabling? It
provides useful knowledge related to air flow such as issues with recirculation within the rack, or
insufficient air flow from the floor grille. It also enables the data center designer or operator to determine
the maximum IT load that can be installed in the rack.
In this study, a 6SigmaRack model of the Open Compute rack was also created
from a CAD model. Thermally insignificant features were removed. Three
Windmill servers were installed in to each shelf (Figure 5). Fifteen shelves of
Windmill servers and three power supplies were installed in to the rack. The SSM
was used to represent the servers. The rack was then installed in a 6SigmaRack
Test Chamber environment (Figure 6). The model represents a contained cold
aisle with sufficient airflow through the floor grille to meet the equipment airflow
requirements. The supply temperature was set to 26.5°C, which is the
same as the server simulation.
Figure 6: Open Compute rack simulation
Figure 5: Windmill server configuration
within rack tray
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 5
Data Center
Data Center, or Room, scale models provide the necessary information to design the facility’s cooling
system. For example the airflow produced from the ACUs can be designed to match the airflow
requirements of the installed IT equipment. These simulations can be used to validate the data center
conceptual design before it becomes operational, and racks that are able to meet the equipment’s cooling
requirements can be chosen. Modeling can also determine proper placement of new IT equipment to
the room.
For this study, a model of a typical modern data center was created, as shown in Figure 7. It was designed
with 12 rows and 150 racks housing 45 server each, which gives a total of 6750 servers. The total load of
the data center is 1716 kW. The data center has 14 air cooling units (ACUs), which provides N+1
redundancy. The racks were modeled in 6SigmaRack and imported into 6SigmaRoom where the data
center simulations were performed.
6SigmaRoom has extensive thermal model libraries of equipment found in a data center. The six Power
Distribution Units (PDU) as well as the 14 ACU objects were obtained from these libraries. The
obstructions from both the network and power cabling were also modeled.
Figure 7: Data Center Simulation
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 6
Failure Scenario
To show the difference between using SSMs and current design practices, the above methodology was
redone using server data that is typically available: outer dimensions, name plate power and maximum
operating temperature. The inflow and outflow were assumed to be the same dimensions as the front
and back of the server, and a fixed flow rate was set as a ratio to the server input power – 120cfm/kW
which is typical engineering assumption
Both scenarios operated within design specifications for a fully functional data center. However, both
have N+1 redundancy to ensure that if an ACU unit were to fail, the servers would continue to function
and receive adequate airflow at the proper temperature. The next study was set to analyze what would
happen if one of the cooling units were to fail. The ACU that has been red-crossed in Figure 8 was turned
off and a simulation with both models was run.
Figure 8: Data Center Failure Scenario
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 7
Results
The Windmill server simulation results were analyzed and no
thermal design issues were found. All components were
operating below their maximum operating temperature
(Figure 9). The air guides ensure that the airflow passes over the
CPU heatsinks and memory cards.
The rack level simulation of the Open Compute Rack were also analysed and, as can
be seen in figure 10, no thermal issues were found. The rack is well designed and
there are few paths for recircualtion. All equipment receives sufficent aiflow below
27°C, which is the ASHRAE specfication. The equipment at the top of the rack receives
slightly warmer air due to some recirculated air coming over the top of the
equipment. The recirculation does not cause any thermal issues.
Figure 10: Mean inlet temperature of servers
The data center simulation was performed in 6SigmaRoom and the results of the simulation were
analyzed. There are no overheating servers in the data center. Figure 11 shows the ASHRAE temperature
plot for the data center. The cooling was configured using the data center model and SSM to match the
cooling requirements of IT. This design is an idealized one with no thermal issues. Its purpose is to
illustrate the methodology of data center design using SSMs.
Figure 11: ASHRAE Temperature plot and Floor Grille temperature plot
Figure 9: Server Surface Temperature plot
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 8
Figure 12 shows a comparison between using SSM versus using design assumptions in the data center
simulation. This is done is a failure scenario, as specified above, the red cross indicates the failed ACU. The
plots below show the number of cabinets which contain overheating equipment.
If the data center model was created using server models based on basic assumptions the data
center operator would come to the conclusion that the cooling in the data center is insufficent
and increase the cooling capacity. This would be incorrect and would reduce the efficency of the
data center. Though it is beyond the scope of this paper, after the building costs, operationsal
costs are the highest. Over specificying the cooling equipment can cost operators million per year
in unnessessary energy bills.
Data Center model, using server models
created from the detailed server simulation
Data Center model, using server models
based on basic assumptions
Figure 12
Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 9
Conclusion
Like for IT equipment simulation, using CFD for data centers is a useful tool for design validation and
troubleshooting. It allows for a detailed assessment of the heat and air flow patterns that will emanate
from the selected IT equipment as these are intricately linked. Without validated and accurate
information about the server, a data center simulation will never be correct, and the design will reflect
that – even in idealized conceptual designs.
To save on solving time, simplified IT equipment models, SSM, can be used to exchange relevant data
between electronic simulation and data center simulation tools. Careful consideration must be taken,
however, to ensure that specific data is not lost both at the rack and room level as well as within the
server. The server model must be a finalized, detailed design before it can be characterized flow and heat
dissipation patterns. These are then used as boundary conditions to define a black box without
compromising accuracy. This can be done in 6SigmaET, and seamlessly integrated into either 6SigmaRack
or 6SigmaRoom.
Incorporating the SSM in the rack and data center analysis enables a far better design than those currently
done. This innovative approach can save the data center operator millions in energy costs per year. With
6SigmaDC, the entire electronics supply chain can be optimized for functionality, reliably and operational
costs.
UK Corporate Headquarters
Future Facilities Limited.
1 Salamanca Street
London SE1 7HX
Tel: +44 (0) 20 7840 9540
Fax: +44 (0) 20 7091 7171
Email: info@futurefacilities.com
North America
Future Facilities Inc.
2055 Gateway Place, Suite 110
San Jose
CA 95110
Tel: +1 408 436 7701
Fax: +1 408 436 7705
Email: info@futurefacilities.com
Japan
Future Facilities KK
S2 bldg. 5F
2-15-22 Shinjuku
Shinjuku-Ku, Tokyo 160-0022
Tel: +81 (0) 3 5312 8070
Fax: +81 (0) 3 5312 8071
Email: jp-info@futurefacilities.com

More Related Content

Viewers also liked

Schneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference DesignsSchneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference DesignsSchneider Electric
 
Data Center Simulation Modeling must do
Data Center Simulation Modeling must doData Center Simulation Modeling must do
Data Center Simulation Modeling must doRobert Schmidt
 
Datacenter Modeling must do - minimum inputs for ensuring accuracy
Datacenter Modeling must do - minimum inputs for ensuring accuracyDatacenter Modeling must do - minimum inputs for ensuring accuracy
Datacenter Modeling must do - minimum inputs for ensuring accuracyRobert Schmidt
 
CFD Introduction using Ansys Fluent
CFD Introduction using Ansys FluentCFD Introduction using Ansys Fluent
CFD Introduction using Ansys Fluentsavani4611
 
個人簡歷與作品介紹-01
個人簡歷與作品介紹-01個人簡歷與作品介紹-01
個人簡歷與作品介紹-01Kang-Hua Liu
 
2D CFD Code Based on MATLAB- As Good As FLUENT!
2D CFD Code Based on MATLAB- As Good As FLUENT!2D CFD Code Based on MATLAB- As Good As FLUENT!
2D CFD Code Based on MATLAB- As Good As FLUENT!Jiannan Tan
 
ANSYS Fluent - CFD Final year thesis
ANSYS Fluent - CFD Final year thesisANSYS Fluent - CFD Final year thesis
ANSYS Fluent - CFD Final year thesisDibyajyoti Laha
 

Viewers also liked (10)

CFD & ANSYS FLUENT
CFD & ANSYS FLUENTCFD & ANSYS FLUENT
CFD & ANSYS FLUENT
 
Schneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference DesignsSchneider Electric Data Center Reference Designs
Schneider Electric Data Center Reference Designs
 
Data Center Simulation Modeling must do
Data Center Simulation Modeling must doData Center Simulation Modeling must do
Data Center Simulation Modeling must do
 
Datacenter Modeling must do - minimum inputs for ensuring accuracy
Datacenter Modeling must do - minimum inputs for ensuring accuracyDatacenter Modeling must do - minimum inputs for ensuring accuracy
Datacenter Modeling must do - minimum inputs for ensuring accuracy
 
CFD Introduction using Ansys Fluent
CFD Introduction using Ansys FluentCFD Introduction using Ansys Fluent
CFD Introduction using Ansys Fluent
 
個人簡歷與作品介紹-01
個人簡歷與作品介紹-01個人簡歷與作品介紹-01
個人簡歷與作品介紹-01
 
Modular Data Center Design
Modular Data Center DesignModular Data Center Design
Modular Data Center Design
 
2D CFD Code Based on MATLAB- As Good As FLUENT!
2D CFD Code Based on MATLAB- As Good As FLUENT!2D CFD Code Based on MATLAB- As Good As FLUENT!
2D CFD Code Based on MATLAB- As Good As FLUENT!
 
ANSYS Fluent - CFD Final year thesis
ANSYS Fluent - CFD Final year thesisANSYS Fluent - CFD Final year thesis
ANSYS Fluent - CFD Final year thesis
 
CFD analysis of an Airfoil
CFD analysis of an AirfoilCFD analysis of an Airfoil
CFD analysis of an Airfoil
 

Similar to Data Center Optimization with Server Design Simulation

CoolSim Overview
CoolSim OverviewCoolSim Overview
CoolSim Overviewpaulbemis
 
Server room cooling report
Server room cooling reportServer room cooling report
Server room cooling reportommuruga ps
 
Data center cooling ahmed abdel-salam (2019)
Data center cooling   ahmed abdel-salam (2019)Data center cooling   ahmed abdel-salam (2019)
Data center cooling ahmed abdel-salam (2019)Ahmed Abdel-Salam
 
HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...
HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...
HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...IRJET Journal
 
Whitepaper: Exadata Consolidation Success Story
Whitepaper: Exadata Consolidation Success StoryWhitepaper: Exadata Consolidation Success Story
Whitepaper: Exadata Consolidation Success StoryKristofferson A
 
IRJET- Cloud Cost Analyzer and Optimizer
IRJET- Cloud Cost Analyzer and OptimizerIRJET- Cloud Cost Analyzer and Optimizer
IRJET- Cloud Cost Analyzer and OptimizerIRJET Journal
 
Windows server power_efficiency___robben_and_worthington__final
Windows server power_efficiency___robben_and_worthington__finalWindows server power_efficiency___robben_and_worthington__final
Windows server power_efficiency___robben_and_worthington__finalBruce Worthington
 
Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...
Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...
Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...Principled Technologies
 
Applying Cloud Techniques to Address Complexity in HPC System Integrations
Applying Cloud Techniques to Address Complexity in HPC System IntegrationsApplying Cloud Techniques to Address Complexity in HPC System Integrations
Applying Cloud Techniques to Address Complexity in HPC System Integrationsinside-BigData.com
 
Secure power grid simulation on cloud
Secure power grid simulation on cloudSecure power grid simulation on cloud
Secure power grid simulation on cloudieeepondy
 
white_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdfwhite_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdfwberring
 
Fast & Easy Electronics Thermal Management
Fast & Easy Electronics Thermal ManagementFast & Easy Electronics Thermal Management
Fast & Easy Electronics Thermal ManagementSimScale
 
Optimizing The Data Centre Environment
Optimizing The Data Centre EnvironmentOptimizing The Data Centre Environment
Optimizing The Data Centre Environmentmixalisg
 
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationRobert Schmidt
 
Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...
Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...
Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...Tarik Reza Toha
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...SimScale
 
Electro Thermal IC Simulation With Saber
Electro Thermal  IC Simulation  With  SaberElectro Thermal  IC Simulation  With  Saber
Electro Thermal IC Simulation With Saberdomnitei
 
AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...
AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...
AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...Principled Technologies
 
Performance and Energy evaluation
Performance and Energy evaluationPerformance and Energy evaluation
Performance and Energy evaluationGIORGOS STAMELOS
 

Similar to Data Center Optimization with Server Design Simulation (20)

CoolSim Overview
CoolSim OverviewCoolSim Overview
CoolSim Overview
 
Server room cooling report
Server room cooling reportServer room cooling report
Server room cooling report
 
Data center cooling ahmed abdel-salam (2019)
Data center cooling   ahmed abdel-salam (2019)Data center cooling   ahmed abdel-salam (2019)
Data center cooling ahmed abdel-salam (2019)
 
Build Energy Saving into Your Datacenter
Build Energy Saving into Your DatacenterBuild Energy Saving into Your Datacenter
Build Energy Saving into Your Datacenter
 
HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...
HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...
HEAT TRANSFER ANALYSIS ON LAPTOP COOLING SYSTEM BEFORE AND AFTER INTRODUCING ...
 
Whitepaper: Exadata Consolidation Success Story
Whitepaper: Exadata Consolidation Success StoryWhitepaper: Exadata Consolidation Success Story
Whitepaper: Exadata Consolidation Success Story
 
IRJET- Cloud Cost Analyzer and Optimizer
IRJET- Cloud Cost Analyzer and OptimizerIRJET- Cloud Cost Analyzer and Optimizer
IRJET- Cloud Cost Analyzer and Optimizer
 
Windows server power_efficiency___robben_and_worthington__final
Windows server power_efficiency___robben_and_worthington__finalWindows server power_efficiency___robben_and_worthington__final
Windows server power_efficiency___robben_and_worthington__final
 
Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...
Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...
Handle a higher rate of Microsoft SQL Server transactions with Google Cloud C...
 
Applying Cloud Techniques to Address Complexity in HPC System Integrations
Applying Cloud Techniques to Address Complexity in HPC System IntegrationsApplying Cloud Techniques to Address Complexity in HPC System Integrations
Applying Cloud Techniques to Address Complexity in HPC System Integrations
 
Secure power grid simulation on cloud
Secure power grid simulation on cloudSecure power grid simulation on cloud
Secure power grid simulation on cloud
 
white_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdfwhite_paper_Liquid-Cooling-Solutions.pdf
white_paper_Liquid-Cooling-Solutions.pdf
 
Fast & Easy Electronics Thermal Management
Fast & Easy Electronics Thermal ManagementFast & Easy Electronics Thermal Management
Fast & Easy Electronics Thermal Management
 
Optimizing The Data Centre Environment
Optimizing The Data Centre EnvironmentOptimizing The Data Centre Environment
Optimizing The Data Centre Environment
 
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center OperationASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
ASHRAE Prediction Is Better Than Cure – CFD Simulation For Data Center Operation
 
Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...
Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...
Exploiting a Synergy between Greedy Approach and NSGA for Scheduling in Compu...
 
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
Data Center Cooling System Design: Reducing Cooling Costs and Power Consumpti...
 
Electro Thermal IC Simulation With Saber
Electro Thermal  IC Simulation  With  SaberElectro Thermal  IC Simulation  With  Saber
Electro Thermal IC Simulation With Saber
 
AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...
AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...
AMD EPYC 7763 processor-based servers can offer a better value for MySQL work...
 
Performance and Energy evaluation
Performance and Energy evaluationPerformance and Energy evaluation
Performance and Energy evaluation
 

Recently uploaded

BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASEBATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASEOrtus Solutions, Corp
 
Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)OPEN KNOWLEDGE GmbH
 
CRM Contender Series: HubSpot vs. Salesforce
CRM Contender Series: HubSpot vs. SalesforceCRM Contender Series: HubSpot vs. Salesforce
CRM Contender Series: HubSpot vs. SalesforceBrainSell Technologies
 
Cloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEECloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEEVICTOR MAESTRE RAMIREZ
 
Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...
Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...
Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...Matt Ray
 
Building Real-Time Data Pipelines: Stream & Batch Processing workshop Slide
Building Real-Time Data Pipelines: Stream & Batch Processing workshop SlideBuilding Real-Time Data Pipelines: Stream & Batch Processing workshop Slide
Building Real-Time Data Pipelines: Stream & Batch Processing workshop SlideChristina Lin
 
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed DataAlluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed DataAlluxio, Inc.
 
办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样
办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样
办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样umasea
 
Software Project Health Check: Best Practices and Techniques for Your Product...
Software Project Health Check: Best Practices and Techniques for Your Product...Software Project Health Check: Best Practices and Techniques for Your Product...
Software Project Health Check: Best Practices and Techniques for Your Product...Velvetech LLC
 
Xen Safety Embedded OSS Summit April 2024 v4.pdf
Xen Safety Embedded OSS Summit April 2024 v4.pdfXen Safety Embedded OSS Summit April 2024 v4.pdf
Xen Safety Embedded OSS Summit April 2024 v4.pdfStefano Stabellini
 
GOING AOT WITH GRAALVM – DEVOXX GREECE.pdf
GOING AOT WITH GRAALVM – DEVOXX GREECE.pdfGOING AOT WITH GRAALVM – DEVOXX GREECE.pdf
GOING AOT WITH GRAALVM – DEVOXX GREECE.pdfAlina Yurenko
 
Folding Cheat Sheet #4 - fourth in a series
Folding Cheat Sheet #4 - fourth in a seriesFolding Cheat Sheet #4 - fourth in a series
Folding Cheat Sheet #4 - fourth in a seriesPhilip Schwarz
 
How to Track Employee Performance A Comprehensive Guide.pdf
How to Track Employee Performance A Comprehensive Guide.pdfHow to Track Employee Performance A Comprehensive Guide.pdf
How to Track Employee Performance A Comprehensive Guide.pdfLivetecs LLC
 
SuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte Germany
SuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte GermanySuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte Germany
SuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte GermanyChristoph Pohl
 
What is Advanced Excel and what are some best practices for designing and cre...
What is Advanced Excel and what are some best practices for designing and cre...What is Advanced Excel and what are some best practices for designing and cre...
What is Advanced Excel and what are some best practices for designing and cre...Technogeeks
 
React Server Component in Next.js by Hanief Utama
React Server Component in Next.js by Hanief UtamaReact Server Component in Next.js by Hanief Utama
React Server Component in Next.js by Hanief UtamaHanief Utama
 
Buds n Tech IT Solutions: Top-Notch Web Services in Noida
Buds n Tech IT Solutions: Top-Notch Web Services in NoidaBuds n Tech IT Solutions: Top-Notch Web Services in Noida
Buds n Tech IT Solutions: Top-Notch Web Services in Noidabntitsolutionsrishis
 
SpotFlow: Tracking Method Calls and States at Runtime
SpotFlow: Tracking Method Calls and States at RuntimeSpotFlow: Tracking Method Calls and States at Runtime
SpotFlow: Tracking Method Calls and States at Runtimeandrehoraa
 
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...stazi3110
 

Recently uploaded (20)

BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASEBATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
BATTLEFIELD ORM: TIPS, TACTICS AND STRATEGIES FOR CONQUERING YOUR DATABASE
 
Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)Der Spagat zwischen BIAS und FAIRNESS (2024)
Der Spagat zwischen BIAS und FAIRNESS (2024)
 
CRM Contender Series: HubSpot vs. Salesforce
CRM Contender Series: HubSpot vs. SalesforceCRM Contender Series: HubSpot vs. Salesforce
CRM Contender Series: HubSpot vs. Salesforce
 
Cloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEECloud Data Center Network Construction - IEEE
Cloud Data Center Network Construction - IEEE
 
Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...
Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...
Open Source Summit NA 2024: Open Source Cloud Costs - OpenCost's Impact on En...
 
Building Real-Time Data Pipelines: Stream & Batch Processing workshop Slide
Building Real-Time Data Pipelines: Stream & Batch Processing workshop SlideBuilding Real-Time Data Pipelines: Stream & Batch Processing workshop Slide
Building Real-Time Data Pipelines: Stream & Batch Processing workshop Slide
 
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed DataAlluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
Alluxio Monthly Webinar | Cloud-Native Model Training on Distributed Data
 
办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样
办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样
办理学位证(UQ文凭证书)昆士兰大学毕业证成绩单原版一模一样
 
2.pdf Ejercicios de programación competitiva
2.pdf Ejercicios de programación competitiva2.pdf Ejercicios de programación competitiva
2.pdf Ejercicios de programación competitiva
 
Software Project Health Check: Best Practices and Techniques for Your Product...
Software Project Health Check: Best Practices and Techniques for Your Product...Software Project Health Check: Best Practices and Techniques for Your Product...
Software Project Health Check: Best Practices and Techniques for Your Product...
 
Xen Safety Embedded OSS Summit April 2024 v4.pdf
Xen Safety Embedded OSS Summit April 2024 v4.pdfXen Safety Embedded OSS Summit April 2024 v4.pdf
Xen Safety Embedded OSS Summit April 2024 v4.pdf
 
GOING AOT WITH GRAALVM – DEVOXX GREECE.pdf
GOING AOT WITH GRAALVM – DEVOXX GREECE.pdfGOING AOT WITH GRAALVM – DEVOXX GREECE.pdf
GOING AOT WITH GRAALVM – DEVOXX GREECE.pdf
 
Folding Cheat Sheet #4 - fourth in a series
Folding Cheat Sheet #4 - fourth in a seriesFolding Cheat Sheet #4 - fourth in a series
Folding Cheat Sheet #4 - fourth in a series
 
How to Track Employee Performance A Comprehensive Guide.pdf
How to Track Employee Performance A Comprehensive Guide.pdfHow to Track Employee Performance A Comprehensive Guide.pdf
How to Track Employee Performance A Comprehensive Guide.pdf
 
SuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte Germany
SuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte GermanySuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte Germany
SuccessFactors 1H 2024 Release - Sneak-Peek by Deloitte Germany
 
What is Advanced Excel and what are some best practices for designing and cre...
What is Advanced Excel and what are some best practices for designing and cre...What is Advanced Excel and what are some best practices for designing and cre...
What is Advanced Excel and what are some best practices for designing and cre...
 
React Server Component in Next.js by Hanief Utama
React Server Component in Next.js by Hanief UtamaReact Server Component in Next.js by Hanief Utama
React Server Component in Next.js by Hanief Utama
 
Buds n Tech IT Solutions: Top-Notch Web Services in Noida
Buds n Tech IT Solutions: Top-Notch Web Services in NoidaBuds n Tech IT Solutions: Top-Notch Web Services in Noida
Buds n Tech IT Solutions: Top-Notch Web Services in Noida
 
SpotFlow: Tracking Method Calls and States at Runtime
SpotFlow: Tracking Method Calls and States at RuntimeSpotFlow: Tracking Method Calls and States at Runtime
SpotFlow: Tracking Method Calls and States at Runtime
 
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
Building a General PDE Solving Framework with Symbolic-Numeric Scientific Mac...
 

Data Center Optimization with Server Design Simulation

  • 1. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 1 The benefits of analyzing thermal performance using computational fluid dynamic (CFD) models at the board and server level are well understood. This practice, established for decades, has proven to be more cost effective with respect to product design while yielding faster times to market than earlier non- simulation methods. In addition, thermal margins have been drastically reduced without compromising performance and reliability. For the same reasons, data center designers also rely on CFD to ensure the most cost effective room layout without compromising server inlet air flow and temperature. An extensive amount of data is required to accurately simulate a data center. This includes thermal models of the installed IT equipment. Typically server manufacturers do not provide sufficient thermal information about their products for data center simulation. Currently only the outer dimensions, name plate power and maximum operating temperature are readily available, but for meaningful data center results, information regarding flow rates, vent geometry, and typical power consumption is also essential. Until recently, migrating this information across the simulation supply chain was difficult. However, with 6SigmaDC’s suite of thermal modeling tools, the process has become seamless. Now, detailed, validated thermal models at the server level can be used in data center models to provide solid, reliable predictions of facility operations. Using 6SigmaET, the thermal details of the server can be characterized, and a simplified version, using a control volume (or black box) approach can be used by the rest of the 6SigmaDC software to predict airflows and heat dissipations at the rack and room levels. This paper will explore the creation and use of a simplified server model (SSM) using the full suite of 6SigmaDC software. A detailed server model of the Facebook Open Compute Windmill Server will be created in 6SigmaET. This detailed model will be simplified and the SSM will be used to verify the design of the Open Compute Rack and an example data center. The paper will discuss the benefits and limitations of thermal simulation at the server, rack and data center level. The process followed can be seen in figure 1 overleaf. Finally, a comparison will be made between using a SSM in a data center simulation and using basic server data readily available today, this will be conducted in a failure scenario. Air flows and temperatures will re-assessed and a discussion presented. Thinking Outside the Box – Server Design for Data Center Optimization Marie Ross, Senior Applications Engineer Tom Gregory, Consultant Engineer October 2013 Ju
  • 2. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 2 Detailed Server Modeling the server in detail allows IT equipment designers to optimize and verify the design before manufacture. It provides an understanding of the airflow requirements, optimum component placement, and flow patterns. It is also critical for heat sink selection and flow guides. For the Windmill server, this level of analysis provides insights on the perfect baffling structure to ensure air flow through both the CPU heatsinks as well as the memory cards. The server model, based on Intel’s Windmill server, can be found on the Open Compute website (www.opencompute.com). The CAD drawings were downloaded, and Open Compute specifications were imposed (Figure 2) in a 6SigmaET model. Total power dissipation is 236 W - 7.1 W per memory card, 50 W per CPU, 6.2 W from the Drive, 0.5 W from the power interface, with the remainder being evenly distributed on the motherboard. The model was simulated in an open test chamber environment with a supply temperature of 26.5°C. This supply temperature was chosen as it is just below the ASHRAE specified maximum inlet temperature of 27°C. Server Simulation Simplify Server Rack Simulation Data Center Simulation Detailed simulation of the motherboard and server. A simplified server model is created from the detailed server simulation. Simulation of the Open Rack with simplified server models. The rack will be simulated in a rack test environment. Simulation of a typical modern data center. Figure 1 – Methodology Figure 2: Detailed Server Model
  • 3. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 3 Simplified Server It is not possible within a reasonable timescale to model thousands of duplicated detailed thermal server models in a rack or data center simulation. However, this is not an issue as the internal layout of the server has been verified and validated through simulation and test. In this case, after the detailed model was finalized in 6SigmaET, a SSM was created. The SSM are shown in Figure 3. Figure 3 – Simplified server model. Front and rear view. Vents highlighted in red. A SSM treats all internal components as a black box. It is calculated by using the detailed server model and creates a simplified chassis, which includes the vent geometry, flow rate and heat dissipation. This SSM includes sufficient information so that the airflow through the data center can be accurately predicted. In reality when the cold aisle in the data center is contained there is potential it will become pressurized. In this situation more air will be forced through the server than if the server was placed in open space. To account for this, both 6SigmaRack and 6SigmaRoom have an input called the Coefficient of Excess Flow, the value for which is calculated within the detailed server model. The coefficient is obtained by running the detailed model in 6SigmaET at various inlet velocities to assess its impedance. This impedance curve is then validated within 6SigmaRack to ensure that pressure drop meets that provided with the rack. Figure 4 shows the impedance curve comparison between the rack and server level models for this case study. Figure 4: Comparison between detailed and simplified servers 0 10 20 30 40 50 60 70 0 20 40 60 80 100 FlowRate(CFM) Pressure (Pa) Detailed Simplified
  • 4. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 4 Rack Many thermal issues in the data center are caused by rack issues as opposed to the data center environment Rack level thermal analysis gives designers and room operators insights related to the rack thermal design. Is it properly designed? Are face plates necessary? What is the effect of cabling? It provides useful knowledge related to air flow such as issues with recirculation within the rack, or insufficient air flow from the floor grille. It also enables the data center designer or operator to determine the maximum IT load that can be installed in the rack. In this study, a 6SigmaRack model of the Open Compute rack was also created from a CAD model. Thermally insignificant features were removed. Three Windmill servers were installed in to each shelf (Figure 5). Fifteen shelves of Windmill servers and three power supplies were installed in to the rack. The SSM was used to represent the servers. The rack was then installed in a 6SigmaRack Test Chamber environment (Figure 6). The model represents a contained cold aisle with sufficient airflow through the floor grille to meet the equipment airflow requirements. The supply temperature was set to 26.5°C, which is the same as the server simulation. Figure 6: Open Compute rack simulation Figure 5: Windmill server configuration within rack tray
  • 5. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 5 Data Center Data Center, or Room, scale models provide the necessary information to design the facility’s cooling system. For example the airflow produced from the ACUs can be designed to match the airflow requirements of the installed IT equipment. These simulations can be used to validate the data center conceptual design before it becomes operational, and racks that are able to meet the equipment’s cooling requirements can be chosen. Modeling can also determine proper placement of new IT equipment to the room. For this study, a model of a typical modern data center was created, as shown in Figure 7. It was designed with 12 rows and 150 racks housing 45 server each, which gives a total of 6750 servers. The total load of the data center is 1716 kW. The data center has 14 air cooling units (ACUs), which provides N+1 redundancy. The racks were modeled in 6SigmaRack and imported into 6SigmaRoom where the data center simulations were performed. 6SigmaRoom has extensive thermal model libraries of equipment found in a data center. The six Power Distribution Units (PDU) as well as the 14 ACU objects were obtained from these libraries. The obstructions from both the network and power cabling were also modeled. Figure 7: Data Center Simulation
  • 6. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 6 Failure Scenario To show the difference between using SSMs and current design practices, the above methodology was redone using server data that is typically available: outer dimensions, name plate power and maximum operating temperature. The inflow and outflow were assumed to be the same dimensions as the front and back of the server, and a fixed flow rate was set as a ratio to the server input power – 120cfm/kW which is typical engineering assumption Both scenarios operated within design specifications for a fully functional data center. However, both have N+1 redundancy to ensure that if an ACU unit were to fail, the servers would continue to function and receive adequate airflow at the proper temperature. The next study was set to analyze what would happen if one of the cooling units were to fail. The ACU that has been red-crossed in Figure 8 was turned off and a simulation with both models was run. Figure 8: Data Center Failure Scenario
  • 7. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 7 Results The Windmill server simulation results were analyzed and no thermal design issues were found. All components were operating below their maximum operating temperature (Figure 9). The air guides ensure that the airflow passes over the CPU heatsinks and memory cards. The rack level simulation of the Open Compute Rack were also analysed and, as can be seen in figure 10, no thermal issues were found. The rack is well designed and there are few paths for recircualtion. All equipment receives sufficent aiflow below 27°C, which is the ASHRAE specfication. The equipment at the top of the rack receives slightly warmer air due to some recirculated air coming over the top of the equipment. The recirculation does not cause any thermal issues. Figure 10: Mean inlet temperature of servers The data center simulation was performed in 6SigmaRoom and the results of the simulation were analyzed. There are no overheating servers in the data center. Figure 11 shows the ASHRAE temperature plot for the data center. The cooling was configured using the data center model and SSM to match the cooling requirements of IT. This design is an idealized one with no thermal issues. Its purpose is to illustrate the methodology of data center design using SSMs. Figure 11: ASHRAE Temperature plot and Floor Grille temperature plot Figure 9: Server Surface Temperature plot
  • 8. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 8 Figure 12 shows a comparison between using SSM versus using design assumptions in the data center simulation. This is done is a failure scenario, as specified above, the red cross indicates the failed ACU. The plots below show the number of cabinets which contain overheating equipment. If the data center model was created using server models based on basic assumptions the data center operator would come to the conclusion that the cooling in the data center is insufficent and increase the cooling capacity. This would be incorrect and would reduce the efficency of the data center. Though it is beyond the scope of this paper, after the building costs, operationsal costs are the highest. Over specificying the cooling equipment can cost operators million per year in unnessessary energy bills. Data Center model, using server models created from the detailed server simulation Data Center model, using server models based on basic assumptions Figure 12
  • 9. Future Facilities| 6SigmaET – Thinking Outside the Box – Server Design for Data Center Optimization 9 Conclusion Like for IT equipment simulation, using CFD for data centers is a useful tool for design validation and troubleshooting. It allows for a detailed assessment of the heat and air flow patterns that will emanate from the selected IT equipment as these are intricately linked. Without validated and accurate information about the server, a data center simulation will never be correct, and the design will reflect that – even in idealized conceptual designs. To save on solving time, simplified IT equipment models, SSM, can be used to exchange relevant data between electronic simulation and data center simulation tools. Careful consideration must be taken, however, to ensure that specific data is not lost both at the rack and room level as well as within the server. The server model must be a finalized, detailed design before it can be characterized flow and heat dissipation patterns. These are then used as boundary conditions to define a black box without compromising accuracy. This can be done in 6SigmaET, and seamlessly integrated into either 6SigmaRack or 6SigmaRoom. Incorporating the SSM in the rack and data center analysis enables a far better design than those currently done. This innovative approach can save the data center operator millions in energy costs per year. With 6SigmaDC, the entire electronics supply chain can be optimized for functionality, reliably and operational costs. UK Corporate Headquarters Future Facilities Limited. 1 Salamanca Street London SE1 7HX Tel: +44 (0) 20 7840 9540 Fax: +44 (0) 20 7091 7171 Email: info@futurefacilities.com North America Future Facilities Inc. 2055 Gateway Place, Suite 110 San Jose CA 95110 Tel: +1 408 436 7701 Fax: +1 408 436 7705 Email: info@futurefacilities.com Japan Future Facilities KK S2 bldg. 5F 2-15-22 Shinjuku Shinjuku-Ku, Tokyo 160-0022 Tel: +81 (0) 3 5312 8070 Fax: +81 (0) 3 5312 8071 Email: jp-info@futurefacilities.com