SlideShare a Scribd company logo
General Information
Before installing detectors, please thoroughly read these installation
instructions and Guide for Proper Use of System Smoke Detectors
(A05-1003-002), which provides detailed information on detector
spacing, placement, zoning, wiring, and special applications. Copies
of this manual are available from Honeywell.
NOTICE: This manual should be left with the owner/user of
this equipment.
IMPORTANT: This detector must be tested and maintained regularly
following NFPA 72 requirements.
General Description
The 5808W3 photoelectronic smoke/heat detector with built-in
wireless transmitter is intended for use with wireless alarm systems
that support 5800 series devices. Refer to control/communicator
installation instructions for compatibility. The 5808W3 smoke/
heat detector can be used with any 5800 series wireless receiver/
transceiver for residential installations. For commercial installations,
the 5881ENHC or the 5883H receiver is required. The transmitter can
send alarm, tamper, maintenance (when control panels are equipped
to process maintenance signals), and battery condition messages to
the system’s receiver. The maintenance signal fully complies with the
sensitivity test requirement specified in NFPA 72, 10.4.4.2.4 and is
approved by UL. Refer to the wireless system’s instructions for the
maximum number of transmitters that can be supported.
The 5808W3 incorporates a state-of-the-art optical sensing chamber
and an advanced microprocessor. The microprocessor allows the
detector to automatically maintain proper operation at factory
calibrated detection levels, even when sensitivity is altered due to the
presence of contaminants settling into the unit’s smoke chamber. In
order for this feature to work properly, the chamber must never be
opened while power is applied to the smoke detector. This includes
cleaning, maintenance or screen replacement. All models also feature
a restorable, built-in, fixed temperature (135°F) thermal detector and
is also capable of sensing a pre-freeze condition if the temperature is
below 41°F.
The 5808W3 contains a piezoelectric horn which generates the ANSI
S3.41 temporal pattern in an alarm condition. In alarm, a message
is also sent to the wireless control panel. The alarm message is
transmitted every 4 seconds until the smoke or heat condition has
cleared and the detector has reset. During an alarm condition,
pressing the detector’s test switch will silence the piezoelectric horn
for 5 minutes. Once the detector has reset, a RESTORE message is
transmitted to the control panel. The built-in Drift Compensation
algorithm automatically maintains the sensitivity of the detector.
Once the detector reaches its limit of compensation, it transmits a
maintenance signal to the panel. The mounting base installation is
simplified by the incorporation of features compatible with drywall
fasteners or other methods that provide a method for securing the
detector in place.
5808W3 Photoelectronic Smoke/Temperature
Detector with Built-in Wireless Transmitter
INSTALLATION AND SETUP GUIDE
I56-2768-005R
Two LEDs and a sounder on the detector provide local visual and
audible indication of the detector’s status:
Table 1: Detector LED Modes
Green LED Red LED
Piezoelectric
Horn
Power Up
Blinks every
5 sec
Blinks every
5 sec
Off
Normal (standby)
Blinks every
10 sec
Off Off
Out of Sensitivity Off
Blinks every
5 sec
Off
Freeze Trouble Off
Blinks every
10 sec
Off
Smoke Alarm Off
Blinks every
1 sec
Temporal Pattern
Thermal Alarm Off
Blinks every
4 sec
Temporal Pattern
Low Battery Off
Blinks every
45 sec
Chip every 45
sec after LED
blinks for 7 days
During initial power-up, the red and green LEDs will blink
synchronously once every 5 seconds. It will take approximately 20
seconds for the detector to finish the power-up cycle (see Table 1).
After power-up has completed and the detector is functioning normally
within its listed sensitivity range, the green LED blinks once every
10 seconds. If the detector is in need of maintenance because its
sensitivity has shifted outside the listed limits, the red LED blinks
once every 5 seconds. When alarm has been activated by smoke, the
red LED blinks every 1 second. During a thermal alarm condition
(>135°F) the red LED blinks once every 4 seconds. The LED indication
must not be used in place of the tests specified under Testing. In a
freeze trouble condition, the red LED will blink once every 10 seconds
(refer to Table 1). If the detector senses a low battery condition, the
red LED blinks once every 45 seconds.
To measure the detector’s sensitivity, the i3 Series Model SENS-RDR
Infrared Sensitivity Reader tool (see Figure 4) should be used. Refer to
instruction manual D100-98-00 for proper use of the SENS-RDR.
Low Battery Detection
The 5808W3 is powered by a single 3-volt CR123A or DL123A Lithium
battery (included). The detector checks for a low battery at least
every 65 minutes. If a low battery is detected, the transmitter sends
a low battery message to the control panel, which beeps and displays
the detector’s zone number. In addition, the red LED of the 5808W3
will blink every 45 seconds and the test switch will be disabled. This
condition will exist for a minimum of 7 days, and then the detector’s
horn will “chirp” about every 45 seconds. Pressing the test switch
during this time will silence the chirps for 12 hours. The battery
should be replaced BEFORE the chirps begin. Be sure to replace the
battery with a fresh one.
- 1 -
Battery Installation and Replacement
To replace the battery:
1.	Remove the detector from its mounting base by twisting the detector
counterclockwise. Remove the battery, and dispose properly.
2.	To ensure proper power-down sequence, wait a minimum of 20
seconds before installing new battery.
3.	Install a new 3-volt CR123A Lithium battery in the battery
compartment. Follow the polarity diagram inside the compartment.
4.	Reinstall the smoke detector onto the mounting base by turning
the detector clockwise.
5.	Test the detector as described in the TESTING SIGNAL
STRENGTH section of this manual. The green LED should blink
about once every 10 seconds to indicate normal operation. If the
battery is not installed correctly, the smoke detector will not
operate and the battery may be damaged. If the detector does not
appear to be sending a signal during any of the tests, check for
correct battery installation and for a fully charged battery.
TEST SWTICH
RED LED
GREEN LED
S0289-00
Figure 1. 5808W3 Wireless Smoke/Heat Detector
Programming
The smoke detector must be enrolled in the control panel before it can
operate in the system. The 5808W3 smoke/heat protection zone must
be enrolled as Loop 1 and “Input Type” 3 (supervised RF).
If programmed, this smoke detector is capable of monitoring the
additional conditions of Maintenance (transmitted as Loop 2), and
Low Temperature (transmitted as Loop 3). Tamper is transmitted
as Loop 4, but does not require programming. To take advantage of
the value added features of Maintenance and Low Temperature, you
must program each loop as a separate zone in the 5800 series wireless
compatible panel.
1.	 Enter the control’s Zone Programming mode.
2.	 Enter the zone number to be programmed.
3.	 Enter the applicable zone type when prompted. Program
	 • Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16),
	 • Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type
19), and
	 • Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone (type 8).
	NOTE: Loop 2 High/Low Maintenance is supported only on
commercial control panels such as the Vista-128FBP.
4.	When prompted, enter Input Type 03 (3 on some controls)
– Supervised RF Transmitter.
5.	When prompted for the serial number, transmit from the detector
by activating the tamper switch. To do this, hold the base of the
detector in one hand, and rotate the detector counter-clockwise
on the base until it snaps open. Then return to clockwise position
until the detector snaps into place.
6.	When the serial number is displayed, transmit from the detector
a second time by activating the tamper switch again as described
in Step 5. The current loop number (4) will begin to flash.
7.	Manually change the loop number to the desired loop number for
the zone (according to the application).
8.	When programming for this zone is complete, program other
zones for the transmitter as necessary (except for Tamper Loop
4, which does not require programming).
	WARNING: The fire protection zone enrolled must always be
Loop 1. Otherwise, fire annunciations will not be reported by the
control.
9.	Exit Programming mode when programming is complete, and
test the detector. Refer to the Testing Section.
See the control unit’s installation instructions for further details.
Mounting
First, determine the best location for the smoke detector, one that
provides a strong wireless transmission path and proper smoke
detection.AGOOD TRANSMISSION PATH MUST BE ESTABLISHED
FROM THE PROPOSED MOUNTING LOCATION BEFORE
PERMANENTLY INSTALLING THE DETECTOR. To check, perform
the test described in the TESTING SIGNAL STRENGTH section of
this manual. Prior to mounting the detector to the mounting base,
you must “enroll” the detector’s serial number into the system (see
the PROGRAMMING section). To mount the detector, perform the
following steps:
1.	Once a suitable location has been determined, install the
mounting base on the ceiling or on the wall (if local ordinances
permit). Use the two screws and anchors provided.
2.	Turn the detector in a clockwise direction in the mounting base
until it clicks into place.
3.	Test the detector immediately after completing the installation
(as described in the TESTING section of this manual) and refer
to the control system’s instructions for additional information
concerning the use of wireless smoke detectors.
DIRECT MOUNT HOLES
TAMPER RESISTANT TAB
(CUT OFF SMALL TAB TO ACTIVATE
TAMPER RESIST FEATURE)
TAMPER RELEASE TAB
S0290-00
Figure 2. Detector Mounting Base
S0162-01
Figure 3. Mount Detector Across Ceiling Panel Support
DO NOT attach the detector to removable ceiling
panels. Attach the detector across panel support as
shown in Figure 3.
- 2 -
Dust covers are an effective way to limit the entry of dust into the
smoke detector sensing chamber during construction. However, they
may not completely prevent airborne dust particles from entering the
detector. Therefore, it is recommended that the detectors be removed
before beginning construction or other dust producing activity. When
returning the system to service, be sure to remove the dust covers
from any detectors that were left in place during construction.
Smoke detectors are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.
Tamper Protection
This detector has a built-in tamper switch that will cause a CHECK
signal to be displayed at the console of the alarm system if it is
removed from its mounting base. The 5808W3 detector includes a
tamper-resistant feature that prevents removal from the mounting
base without the use of a tool. To engage the tamper-resistant feature,
cut the small plastic tab located on the mounting base (Figure 2), and
then install the detector. To remove the detector from the base once it
has been made tamper resistant, use a small screwdriver to depress
the square tamper release tab, located on the skirt of the mounting
base, and turn the detector counterclockwise.
Testing the Sensor
NOTE: Before testing, notify the central station that the smoke
detector system is undergoing maintenance, in order to prevent
unwanted alarms.
During initial power-up, do not use SENS-RDR or canned smoke to
test the detector. The SENS-RDR and canned aerosol can be used
after power-up sequence has completed. Detectors must be tested
after installation and following periodic maintenance. The 5808W3
may be tested as follows:
A. Test Switch
1.	A recessed test switch is located on the detector housing (see
Figure 4).
2.	Push and hold the recessed test switch for a minimum of 5
seconds. Use a small screwdriver or Allen key with maximum
diameter of 0.18 inch (the alarm panel will trigger and then the
smoke detector will go into alarm. If the tool is removed from the
recessed switch the sounder will shut off.)
	If the detector is within the listed sensitivity limits, the LED on
the detector should blink once per second and the horn should
sound within 3 seconds.
POSITION SENS-RDR AT AN ANGLE ON
THE OVAL AREA OR AT THE CHAMBER
OPENING BY THE WORD “PAINT”
RECESSED
TEST
SWITCH
LED
PUSH RECESSED
SWITCH WITH A
0.18˝ MAX.
DIAMETER TOOL
S0308-00
Figure 4. Recessed Test Switch Opening and SENS-RDR Position
B. Smoke Entry Test
A canned smoke agent may be used to test the detector. Refer to the
manufacturer’s instructions for proper use of the canned smoke. HSI
brand canned smoke has been tested and approved for use with this
type of smoke detector.
C. Direct Heat Method (Hair dryer of 1000-1500 watts)
Direct the heat toward either side thermistor. Be sure to hold the
heat source about 12 inches from the detector to avoid damage to the
plastic. The detector will reset only after it has time to cool.
Smoke detection testing is recommended for verifying system
protection capability.
A detector that fails to activate with any of these tests should first be
cleaned as outlined in this manual’s MAINTENANCE section. If the
detector still fails to activate, return for repair.
Testing Signal Strength
NOTE: Remove battery tab before installation.
This test should be performed in accordance with NFPA 72 inspection,
testing and maintenance requirements to determine a strong
communication path with the control panel.
1.	Activate the wireless system’s GO/NO GO TEST mode from
the keypad.
2.	Depress and hold the smoke detector’s TEST switch. If the
detector has not previously detected a low battery condition
and it is within proper sensitivity limits, the detector should
immediately transmit an alarm signal to the control panel.
The built-in horn will start to sound about 2.5 seconds after
depressing the button.
3.	The wireless system’s keypad should emit at least three audible
sounds when the alarm transmission is received and will display
the transmitting detector’s zone number.
4.	When the console has received the test signal, release the TEST
switch. The horn will immediately stop and a few seconds later
the detector’s zone number will clear from the console display.
5.	If the console does not respond as noted, check the polarity of the
battery and be sure it is fresh. If this is an initial installation,
try moving the detector to another location that provides proper
reception. Also be sure that the detector has been “enrolled” by
the control panel (see PROGRAMMING). Then, repeat the test.
6.	Turn off the system’s TEST mode from the keypad (security
code + OFF).
Testing Programmed Loops
This test should be performed before installation to ensure that all
loops intended to be used have been programmed and are operational
in the system.
1.	Activate the system’s TRANSMITTER ID SNIFFER mode from
the keypad (see the control panel’s instructions). All programmed
wireless zones will be displayed, one by one, on the system
keypad. Make sure all smoke detector zones are displayed in
the sequence. (If they are not, recheck that all zones have been
properly programmed.)
2.	With the detector mounted to the bracket, press the smoke
detector’s TEST switch. All zones associated with the smoke
detector should disappear from the keypad on the next display
cycle. This means that the system has received a transmission
from each loop you programmed.
3.	When testing is complete, enter the Installer code + the OFF key
to exit TEST mode.
When all system testing has been completed, notify the central station
that the system is back on line.
- 3 -
Maintenance
NOTE: Before performing maintenance on the detector, notify the
proper authorities and the central station that maintenance is being
performed and the system will be temporarily out of service. Disable
the zone or system undergoing maintenance to prevent any unwanted
alarms, and follow this procedure exactly, referring to Figure 5.
1.	Remove the detector housing from the base by twisting
counter-clockwise.
2.	 Remove the battery from the unit.
3.	Wait 20 seconds. (To ensure proper power-down sequence, the
battery must be removed from detector for a minimum of 20
seconds before continuing to the next step.)
4.	Remove the detector cover by turning counter-clockwise.
5.	Vacuum the cover or use canned air to remove any dust or debris.
6.	Remove the top half of the screen/sensing chamber by lifting
straight up (see Figure 5).
7.	Vacuum or use canned air to remove any dust or particles that
are present on all chamber sections.
8.	Replace the top half of the screen/sensing chamber by aligning
the arrow on the screen/sensing chamber with the arrow on the
housing. Press down firmly until the screen/sensing chamber is
fully seated.
9.	Replace the detector cover by placing it over the screen/sensing
chamber and turning it clockwise until it snaps into place.
Specifications	
Power Source:	One 3-volt CR123A Lithium Battery (included). (Replace with Duracell DL123A, Sanyo CR123A,
Panasonic CR123A or ADEMCO 466.)
Height:	 2.3 inches (58 mm)
Diameter:	 5.3 inches (135 mm) with mounting base
Weight:	 8.5 oz. (241 g) without battery
Operating Ambient Temperature Range:	 32° to 100°F (0° to 38°C)
Operating Humidity Range:	 0% to 95% Relative Humidity
Heat Sensor:	 135° F Fixed Temperature Electronic Thermistors
Freeze Warning Sensor:	 41°F (5°C)
Agency Listings:	 UL 268 – Commercial and Residential Installations
Please refer to insert for the Limitations of Fire Alarm Systems
FOR WARRANTY INFORMATION AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION INSTRUCTIONS FOR THE
RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED.
This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference,
and (2) This device must accept any interference received, including interference that may cause undesired operation.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User’s Manual.
D100-100-00 I56-2768-005R
10.	Reinstall the battery into the battery compartment noting proper
orientation. The red and green LEDs will flash once every 5
seconds for approximately 20 seconds until the power-up cycle is
complete.
11.	Reinstall the detector and test (see the Testing section).
12.	Notify the central station when the system is back in service.
	IMPORTANT: If this procedure is not followed exactly, the
detector may indicate a maintenance trouble after the power-up
sequence is complete. If this happens, remove the battery for 20
seconds and then reinstall.
REMOVABLE
DETECTOR
COVER
SCREEN/SENSING
CHAMBER
(TOP HALF)
DETECTOR HOUSING
S0111-00
Figure 5. Removing Screen/Sensing Chamber
2 Corporate Center Drive, Melville, NY 11747
Copyright © 2007 Honeywell International Inc.
www.honeywell.com/security

More Related Content

What's hot

Aeotec Multisensor 7 Manual
Aeotec Multisensor 7 ManualAeotec Multisensor 7 Manual
Aeotec Multisensor 7 Manual
Domotica daVinci
 
Manual Smoke Detector. Z-Wave Plus - Zipato
Manual Smoke Detector. Z-Wave Plus - ZipatoManual Smoke Detector. Z-Wave Plus - Zipato
Manual Smoke Detector. Z-Wave Plus - Zipato
Domotica daVinci
 
Manual pop 004308
Manual pop 004308Manual pop 004308
Manual pop 004308
Domotica daVinci
 
Instructions aeon labs door window sensor gen5
Instructions   aeon labs door window sensor gen5Instructions   aeon labs door window sensor gen5
Instructions aeon labs door window sensor gen5
Domotica daVinci
 
Mini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control PanelMini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control Panel
Vedard Security Alarm System Store
 
Orvibo all one_user_manual
Orvibo all one_user_manualOrvibo all one_user_manual
Orvibo all one_user_manual
Domotica daVinci
 
SIG SENS W
SIG SENS WSIG SENS W
SIG SENS W
Domotica daVinci
 
Manual Opening Detector with temeperature sensor Z-Wave Plus Version 2- Fibaro
Manual Opening Detector with temeperature sensor Z-Wave Plus Version 2- FibaroManual Opening Detector with temeperature sensor Z-Wave Plus Version 2- Fibaro
Manual Opening Detector with temeperature sensor Z-Wave Plus Version 2- Fibaro
Domotica daVinci
 
Manual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-PoppManual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-Popp
Domotica daVinci
 
Manual co detector-popp_en
Manual co detector-popp_enManual co detector-popp_en
Manual co detector-popp_en
Domotica daVinci
 
Eurotronic Spirit Radiator Thermostat Head Z-Wave Plus Manual
Eurotronic Spirit Radiator Thermostat Head Z-Wave Plus ManualEurotronic Spirit Radiator Thermostat Head Z-Wave Plus Manual
Eurotronic Spirit Radiator Thermostat Head Z-Wave Plus Manual
Domotica daVinci
 
SenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbookSenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbook
Hans Bronkhorst
 
Eur stellaz manual
Eur stellaz manualEur stellaz manual
Eur stellaz manual
Domotica daVinci
 
Water meter secure start guide
Water meter secure start guideWater meter secure start guide
Water meter secure start guide
Domotica daVinci
 
Smoke Detector Fibaro certified CE EN 14604
Smoke Detector Fibaro certified CE EN 14604Smoke Detector Fibaro certified CE EN 14604
Smoke Detector Fibaro certified CE EN 14604
Domotica daVinci
 
Sensative Door Window Sensor Strip Z-Wave Plus User Manual
Sensative Door Window Sensor Strip Z-Wave Plus User ManualSensative Door Window Sensor Strip Z-Wave Plus User Manual
Sensative Door Window Sensor Strip Z-Wave Plus User Manual
Domotica daVinci
 
Door sensor multisensor 4_ in_1 Zipato Z-Wave Plus
Door sensor  multisensor 4_ in_1 Zipato Z-Wave PlusDoor sensor  multisensor 4_ in_1 Zipato Z-Wave Plus
Door sensor multisensor 4_ in_1 Zipato Z-Wave Plus
Domotica daVinci
 
Smart Implant- Fibaro- Z-Wave
Smart Implant- Fibaro- Z-WaveSmart Implant- Fibaro- Z-Wave
Smart Implant- Fibaro- Z-Wave
Domotica daVinci
 
Fire alarm basics 1-6
Fire alarm basics 1-6Fire alarm basics 1-6
Fire alarm basics 1-6
grantlerc
 
S123 b30u
S123 b30uS123 b30u
S123 b30u
Domotica daVinci
 

What's hot (20)

Aeotec Multisensor 7 Manual
Aeotec Multisensor 7 ManualAeotec Multisensor 7 Manual
Aeotec Multisensor 7 Manual
 
Manual Smoke Detector. Z-Wave Plus - Zipato
Manual Smoke Detector. Z-Wave Plus - ZipatoManual Smoke Detector. Z-Wave Plus - Zipato
Manual Smoke Detector. Z-Wave Plus - Zipato
 
Manual pop 004308
Manual pop 004308Manual pop 004308
Manual pop 004308
 
Instructions aeon labs door window sensor gen5
Instructions   aeon labs door window sensor gen5Instructions   aeon labs door window sensor gen5
Instructions aeon labs door window sensor gen5
 
Mini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control PanelMini 2 zones Conventional Fire Alarm Control Panel
Mini 2 zones Conventional Fire Alarm Control Panel
 
Orvibo all one_user_manual
Orvibo all one_user_manualOrvibo all one_user_manual
Orvibo all one_user_manual
 
SIG SENS W
SIG SENS WSIG SENS W
SIG SENS W
 
Manual Opening Detector with temeperature sensor Z-Wave Plus Version 2- Fibaro
Manual Opening Detector with temeperature sensor Z-Wave Plus Version 2- FibaroManual Opening Detector with temeperature sensor Z-Wave Plus Version 2- Fibaro
Manual Opening Detector with temeperature sensor Z-Wave Plus Version 2- Fibaro
 
Manual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-PoppManual 10 year smoke detector Z-Wave Plus-Popp
Manual 10 year smoke detector Z-Wave Plus-Popp
 
Manual co detector-popp_en
Manual co detector-popp_enManual co detector-popp_en
Manual co detector-popp_en
 
Eurotronic Spirit Radiator Thermostat Head Z-Wave Plus Manual
Eurotronic Spirit Radiator Thermostat Head Z-Wave Plus ManualEurotronic Spirit Radiator Thermostat Head Z-Wave Plus Manual
Eurotronic Spirit Radiator Thermostat Head Z-Wave Plus Manual
 
SenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbookSenseTek Stratos Micra 25 installers handbook
SenseTek Stratos Micra 25 installers handbook
 
Eur stellaz manual
Eur stellaz manualEur stellaz manual
Eur stellaz manual
 
Water meter secure start guide
Water meter secure start guideWater meter secure start guide
Water meter secure start guide
 
Smoke Detector Fibaro certified CE EN 14604
Smoke Detector Fibaro certified CE EN 14604Smoke Detector Fibaro certified CE EN 14604
Smoke Detector Fibaro certified CE EN 14604
 
Sensative Door Window Sensor Strip Z-Wave Plus User Manual
Sensative Door Window Sensor Strip Z-Wave Plus User ManualSensative Door Window Sensor Strip Z-Wave Plus User Manual
Sensative Door Window Sensor Strip Z-Wave Plus User Manual
 
Door sensor multisensor 4_ in_1 Zipato Z-Wave Plus
Door sensor  multisensor 4_ in_1 Zipato Z-Wave PlusDoor sensor  multisensor 4_ in_1 Zipato Z-Wave Plus
Door sensor multisensor 4_ in_1 Zipato Z-Wave Plus
 
Smart Implant- Fibaro- Z-Wave
Smart Implant- Fibaro- Z-WaveSmart Implant- Fibaro- Z-Wave
Smart Implant- Fibaro- Z-Wave
 
Fire alarm basics 1-6
Fire alarm basics 1-6Fire alarm basics 1-6
Fire alarm basics 1-6
 
S123 b30u
S123 b30uS123 b30u
S123 b30u
 

Viewers also liked

Cardox Technology for the Steel Industry
Cardox Technology for the Steel IndustryCardox Technology for the Steel Industry
Cardox Technology for the Steel Industry
ATD-Pressure Gas System
 
Fabulatic
FabulaticFabulatic
Fabulatic
Francisco José
 
Aditivos quimicos
Aditivos quimicosAditivos quimicos
Aditivos quimicos
Ysaili Gil
 
Nuevo presentación de microsoft power point (2)
Nuevo presentación de microsoft power point (2)Nuevo presentación de microsoft power point (2)
Nuevo presentación de microsoft power point (2)
Gustavo Antonio González Jimenez
 
Cross inform-2016-21
Cross inform-2016-21Cross inform-2016-21
Cross inform-2016-21
EX ARTHUR MEXICO
 
Fiscoactualidades febrero núm_22
Fiscoactualidades febrero núm_22Fiscoactualidades febrero núm_22
Fiscoactualidades febrero núm_22
EX ARTHUR MEXICO
 
JBC 287
JBC 287JBC 287
JBC 287
Stephanie Sun
 
Internet y derechos fundamentales
Internet y derechos fundamentalesInternet y derechos fundamentales
Internet y derechos fundamentales
Liz Vargas Ortigozo
 
Phase3 cliqur
Phase3 cliqurPhase3 cliqur
Phase3 cliqur
Peter Zheng
 
104台東縣仁愛國小報告第八版-公告用
104台東縣仁愛國小報告第八版-公告用104台東縣仁愛國小報告第八版-公告用
104台東縣仁愛國小報告第八版-公告用
Jun-Yuan Huang
 
Relaciones bilaterales NAFTA
Relaciones bilaterales NAFTARelaciones bilaterales NAFTA
Relaciones bilaterales NAFTA
EmmaTaraH
 
Educomunicación 3
Educomunicación 3Educomunicación 3
Educomunicación 3
carolina Marcalla
 
Buscadores
BuscadoresBuscadores
Buscadores
stephanyl
 
2016 wendys wonderful kids conference
2016 wendys wonderful kids conference2016 wendys wonderful kids conference
2016 wendys wonderful kids conference
Lisa Dickson
 
Capitulo 7-terminado
Capitulo 7-terminadoCapitulo 7-terminado
Capitulo 7-terminado
Alexis Romero lopz
 
Telefonos inteligentes
Telefonos inteligentesTelefonos inteligentes
Telefonos inteligentes
Silvia Gomez
 
How to Spot a Fake Autograph
How to Spot a Fake AutographHow to Spot a Fake Autograph
How to Spot a Fake Autograph
Iconographs
 
Presentation4-2-1
Presentation4-2-1Presentation4-2-1
Presentation4-2-1
Charis Orr
 
Bryant 1
Bryant 1Bryant 1
Bryant 1
FELICIA Lakes
 
Ek4245 bab 4_perencanaan_keuangan
Ek4245 bab 4_perencanaan_keuanganEk4245 bab 4_perencanaan_keuangan
Ek4245 bab 4_perencanaan_keuangan
Thubby's Hubbyy
 

Viewers also liked (20)

Cardox Technology for the Steel Industry
Cardox Technology for the Steel IndustryCardox Technology for the Steel Industry
Cardox Technology for the Steel Industry
 
Fabulatic
FabulaticFabulatic
Fabulatic
 
Aditivos quimicos
Aditivos quimicosAditivos quimicos
Aditivos quimicos
 
Nuevo presentación de microsoft power point (2)
Nuevo presentación de microsoft power point (2)Nuevo presentación de microsoft power point (2)
Nuevo presentación de microsoft power point (2)
 
Cross inform-2016-21
Cross inform-2016-21Cross inform-2016-21
Cross inform-2016-21
 
Fiscoactualidades febrero núm_22
Fiscoactualidades febrero núm_22Fiscoactualidades febrero núm_22
Fiscoactualidades febrero núm_22
 
JBC 287
JBC 287JBC 287
JBC 287
 
Internet y derechos fundamentales
Internet y derechos fundamentalesInternet y derechos fundamentales
Internet y derechos fundamentales
 
Phase3 cliqur
Phase3 cliqurPhase3 cliqur
Phase3 cliqur
 
104台東縣仁愛國小報告第八版-公告用
104台東縣仁愛國小報告第八版-公告用104台東縣仁愛國小報告第八版-公告用
104台東縣仁愛國小報告第八版-公告用
 
Relaciones bilaterales NAFTA
Relaciones bilaterales NAFTARelaciones bilaterales NAFTA
Relaciones bilaterales NAFTA
 
Educomunicación 3
Educomunicación 3Educomunicación 3
Educomunicación 3
 
Buscadores
BuscadoresBuscadores
Buscadores
 
2016 wendys wonderful kids conference
2016 wendys wonderful kids conference2016 wendys wonderful kids conference
2016 wendys wonderful kids conference
 
Capitulo 7-terminado
Capitulo 7-terminadoCapitulo 7-terminado
Capitulo 7-terminado
 
Telefonos inteligentes
Telefonos inteligentesTelefonos inteligentes
Telefonos inteligentes
 
How to Spot a Fake Autograph
How to Spot a Fake AutographHow to Spot a Fake Autograph
How to Spot a Fake Autograph
 
Presentation4-2-1
Presentation4-2-1Presentation4-2-1
Presentation4-2-1
 
Bryant 1
Bryant 1Bryant 1
Bryant 1
 
Ek4245 bab 4_perencanaan_keuangan
Ek4245 bab 4_perencanaan_keuanganEk4245 bab 4_perencanaan_keuangan
Ek4245 bab 4_perencanaan_keuangan
 

Similar to Manual de instalacion detector honeywell

System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279
Henry Rosa
 
Evespring ST812 Z-Wave flood sendor manual in English
Evespring ST812 Z-Wave flood sendor manual in EnglishEvespring ST812 Z-Wave flood sendor manual in English
Evespring ST812 Z-Wave flood sendor manual in English
Domotica daVinci
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector Presentation
Mustafa Ali
 
Edwards Signaling E-HD Installation Manual
Edwards Signaling E-HD Installation ManualEdwards Signaling E-HD Installation Manual
Edwards Signaling E-HD Installation Manual
JMAC Supply
 
Honeywell 5809-data-sheet
Honeywell 5809-data-sheetHoneywell 5809-data-sheet
Honeywell 5809-data-sheet
Alarm Grid
 
Edwards Signaling E-PD Installation Manual
Edwards Signaling E-PD Installation ManualEdwards Signaling E-PD Installation Manual
Edwards Signaling E-PD Installation Manual
JMAC Supply
 
Honeywell 5808w3-install-guide
Honeywell 5808w3-install-guideHoneywell 5808w3-install-guide
Honeywell 5808w3-install-guide
Alarm Grid
 
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
Domotica daVinci
 
Fibaro FGSS-001 Smoke Sensor Manual (English)
Fibaro FGSS-001 Smoke Sensor Manual (English)Fibaro FGSS-001 Smoke Sensor Manual (English)
Fibaro FGSS-001 Smoke Sensor Manual (English)
Domotica daVinci
 
Honeywell is2560-spec-sheet
Honeywell is2560-spec-sheetHoneywell is2560-spec-sheet
Honeywell is2560-spec-sheet
Alarm Grid
 
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensorManual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Domotica daVinci
 
Alarm system wireless to wired adaptor
Alarm system wireless to wired adaptorAlarm system wireless to wired adaptor
Alarm system wireless to wired adaptor
Vedard Security Alarm System Store
 
500plus
500plus500plus
500plus
Andrew Tulley
 
Honeywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheetHoneywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheet
Alarm Grid
 
SenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbookSenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbook
Hans Bronkhorst
 
WirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible GasWirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible Gas
Miller Energy, Inc.
 
Honeywell 5821-install-guide
Honeywell 5821-install-guideHoneywell 5821-install-guide
Honeywell 5821-install-guide
Alarm Grid
 
Honeywell 5809-install-guide
Honeywell 5809-install-guideHoneywell 5809-install-guide
Honeywell 5809-install-guide
Alarm Grid
 
Webinar: Is your cheese at the correct temperature?
Webinar: Is your cheese at the correct temperature?Webinar: Is your cheese at the correct temperature?
Webinar: Is your cheese at the correct temperature?
Simple Hardware
 
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
Domotica daVinci
 

Similar to Manual de instalacion detector honeywell (20)

System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279System sensor 1400 manual i56-0279
System sensor 1400 manual i56-0279
 
Evespring ST812 Z-Wave flood sendor manual in English
Evespring ST812 Z-Wave flood sendor manual in EnglishEvespring ST812 Z-Wave flood sendor manual in English
Evespring ST812 Z-Wave flood sendor manual in English
 
Omni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector PresentationOmni Guard 660 Flame Detector Presentation
Omni Guard 660 Flame Detector Presentation
 
Edwards Signaling E-HD Installation Manual
Edwards Signaling E-HD Installation ManualEdwards Signaling E-HD Installation Manual
Edwards Signaling E-HD Installation Manual
 
Honeywell 5809-data-sheet
Honeywell 5809-data-sheetHoneywell 5809-data-sheet
Honeywell 5809-data-sheet
 
Edwards Signaling E-PD Installation Manual
Edwards Signaling E-PD Installation ManualEdwards Signaling E-PD Installation Manual
Edwards Signaling E-PD Installation Manual
 
Honeywell 5808w3-install-guide
Honeywell 5808w3-install-guideHoneywell 5808w3-install-guide
Honeywell 5808w3-install-guide
 
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
4 in 1 multi sensor Philio PSM02 (motion, door/window, temperature, lightness)
 
Fibaro FGSS-001 Smoke Sensor Manual (English)
Fibaro FGSS-001 Smoke Sensor Manual (English)Fibaro FGSS-001 Smoke Sensor Manual (English)
Fibaro FGSS-001 Smoke Sensor Manual (English)
 
Honeywell is2560-spec-sheet
Honeywell is2560-spec-sheetHoneywell is2560-spec-sheet
Honeywell is2560-spec-sheet
 
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensorManual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
Manual ES-12-ZIP-PD01Z PIR Z-Wave Plus motion sensor
 
Alarm system wireless to wired adaptor
Alarm system wireless to wired adaptorAlarm system wireless to wired adaptor
Alarm system wireless to wired adaptor
 
500plus
500plus500plus
500plus
 
Honeywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheetHoneywell is25100tc-spec-sheet
Honeywell is25100tc-spec-sheet
 
SenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbookSenseTek Stratos Micra 100 installers handbook
SenseTek Stratos Micra 100 installers handbook
 
WirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible GasWirelessHART Gas Detector for Toxic and Combustible Gas
WirelessHART Gas Detector for Toxic and Combustible Gas
 
Honeywell 5821-install-guide
Honeywell 5821-install-guideHoneywell 5821-install-guide
Honeywell 5821-install-guide
 
Honeywell 5809-install-guide
Honeywell 5809-install-guideHoneywell 5809-install-guide
Honeywell 5809-install-guide
 
Webinar: Is your cheese at the correct temperature?
Webinar: Is your cheese at the correct temperature?Webinar: Is your cheese at the correct temperature?
Webinar: Is your cheese at the correct temperature?
 
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
3 in 1 multisensor Philio PSP01 manual (motion, Temperature, lightness)
 

Recently uploaded

Technoblade The Legacy of a Minecraft Legend.
Technoblade The Legacy of a Minecraft Legend.Technoblade The Legacy of a Minecraft Legend.
Technoblade The Legacy of a Minecraft Legend.
Techno Merch
 
Top Interior Designers in Bangalore.pdf1
Top Interior Designers in Bangalore.pdf1Top Interior Designers in Bangalore.pdf1
Top Interior Designers in Bangalore.pdf1
Decomart Studio
 
Storytelling For The Web: Integrate Storytelling in your Design Process
Storytelling For The Web: Integrate Storytelling in your Design ProcessStorytelling For The Web: Integrate Storytelling in your Design Process
Storytelling For The Web: Integrate Storytelling in your Design Process
Chiara Aliotta
 
定制美国西雅图城市大学毕业证学历证书原版一模一样
定制美国西雅图城市大学毕业证学历证书原版一模一样定制美国西雅图城市大学毕业证学历证书原版一模一样
定制美国西雅图城市大学毕业证学历证书原版一模一样
qo1as76n
 
一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理
一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理
一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理
kecekev
 
NHR Engineers Portfolio 2023 2024 NISHANT RATHI
NHR Engineers Portfolio 2023 2024 NISHANT RATHINHR Engineers Portfolio 2023 2024 NISHANT RATHI
NHR Engineers Portfolio 2023 2024 NISHANT RATHI
NishantRathi18
 
Revolutionizing the Digital Landscape: Web Development Companies in India
Revolutionizing the Digital Landscape: Web Development Companies in IndiaRevolutionizing the Digital Landscape: Web Development Companies in India
Revolutionizing the Digital Landscape: Web Development Companies in India
amrsoftec1
 
Impact of Fonts: in Web and Apps Design
Impact of Fonts:  in Web and Apps DesignImpact of Fonts:  in Web and Apps Design
Impact of Fonts: in Web and Apps Design
contactproperweb2014
 
SECURING BUILDING PERMIT CITY OF CALOOCAN.pdf
SECURING BUILDING PERMIT CITY OF CALOOCAN.pdfSECURING BUILDING PERMIT CITY OF CALOOCAN.pdf
SECURING BUILDING PERMIT CITY OF CALOOCAN.pdf
eloprejohn333
 
AHMED TALAAT ARCHITECTURE PORTFOLIO .pdf
AHMED TALAAT ARCHITECTURE PORTFOLIO .pdfAHMED TALAAT ARCHITECTURE PORTFOLIO .pdf
AHMED TALAAT ARCHITECTURE PORTFOLIO .pdf
talaatahm
 
UNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptx
UNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptxUNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptx
UNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptx
GOWSIKRAJA PALANISAMY
 
Branding de la empresa de Bolt- 2024.pdf
Branding de la empresa de Bolt- 2024.pdfBranding de la empresa de Bolt- 2024.pdf
Branding de la empresa de Bolt- 2024.pdf
PabloMartelLpez
 
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
gpffo76j
 
Mohannad Abdullah portfolio _ V2 _22-24
Mohannad Abdullah  portfolio _ V2 _22-24Mohannad Abdullah  portfolio _ V2 _22-24
Mohannad Abdullah portfolio _ V2 _22-24
M. A. Architect
 
UNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptx
UNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptxUNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptx
UNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptx
GOWSIKRAJA PALANISAMY
 
一比一原版(BU毕业证)波士顿大学毕业证如何办理
一比一原版(BU毕业证)波士顿大学毕业证如何办理一比一原版(BU毕业证)波士顿大学毕业证如何办理
一比一原版(BU毕业证)波士顿大学毕业证如何办理
peuce
 
Timeless Principles of Good Design
Timeless Principles of Good DesignTimeless Principles of Good Design
Timeless Principles of Good Design
Carolina de Bartolo
 
ZAPATILLAS 2 X 110 ABRIL.pdf compra economico
ZAPATILLAS 2 X 110 ABRIL.pdf compra economicoZAPATILLAS 2 X 110 ABRIL.pdf compra economico
ZAPATILLAS 2 X 110 ABRIL.pdf compra economico
jhonguerrerobarturen
 
Practical eLearning Makeovers for Everyone
Practical eLearning Makeovers for EveryonePractical eLearning Makeovers for Everyone
Practical eLearning Makeovers for Everyone
Bianca Woods
 
哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样
哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样
哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样
qo1as76n
 

Recently uploaded (20)

Technoblade The Legacy of a Minecraft Legend.
Technoblade The Legacy of a Minecraft Legend.Technoblade The Legacy of a Minecraft Legend.
Technoblade The Legacy of a Minecraft Legend.
 
Top Interior Designers in Bangalore.pdf1
Top Interior Designers in Bangalore.pdf1Top Interior Designers in Bangalore.pdf1
Top Interior Designers in Bangalore.pdf1
 
Storytelling For The Web: Integrate Storytelling in your Design Process
Storytelling For The Web: Integrate Storytelling in your Design ProcessStorytelling For The Web: Integrate Storytelling in your Design Process
Storytelling For The Web: Integrate Storytelling in your Design Process
 
定制美国西雅图城市大学毕业证学历证书原版一模一样
定制美国西雅图城市大学毕业证学历证书原版一模一样定制美国西雅图城市大学毕业证学历证书原版一模一样
定制美国西雅图城市大学毕业证学历证书原版一模一样
 
一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理
一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理
一比一原版(UW毕业证)西雅图华盛顿大学毕业证如何办理
 
NHR Engineers Portfolio 2023 2024 NISHANT RATHI
NHR Engineers Portfolio 2023 2024 NISHANT RATHINHR Engineers Portfolio 2023 2024 NISHANT RATHI
NHR Engineers Portfolio 2023 2024 NISHANT RATHI
 
Revolutionizing the Digital Landscape: Web Development Companies in India
Revolutionizing the Digital Landscape: Web Development Companies in IndiaRevolutionizing the Digital Landscape: Web Development Companies in India
Revolutionizing the Digital Landscape: Web Development Companies in India
 
Impact of Fonts: in Web and Apps Design
Impact of Fonts:  in Web and Apps DesignImpact of Fonts:  in Web and Apps Design
Impact of Fonts: in Web and Apps Design
 
SECURING BUILDING PERMIT CITY OF CALOOCAN.pdf
SECURING BUILDING PERMIT CITY OF CALOOCAN.pdfSECURING BUILDING PERMIT CITY OF CALOOCAN.pdf
SECURING BUILDING PERMIT CITY OF CALOOCAN.pdf
 
AHMED TALAAT ARCHITECTURE PORTFOLIO .pdf
AHMED TALAAT ARCHITECTURE PORTFOLIO .pdfAHMED TALAAT ARCHITECTURE PORTFOLIO .pdf
AHMED TALAAT ARCHITECTURE PORTFOLIO .pdf
 
UNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptx
UNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptxUNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptx
UNIT IV-VISUAL STYLE AND MOBILE INTERFACES.pptx
 
Branding de la empresa de Bolt- 2024.pdf
Branding de la empresa de Bolt- 2024.pdfBranding de la empresa de Bolt- 2024.pdf
Branding de la empresa de Bolt- 2024.pdf
 
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
原版定做(penn毕业证书)美国宾夕法尼亚大学毕业证文凭学历证书原版一模一样
 
Mohannad Abdullah portfolio _ V2 _22-24
Mohannad Abdullah  portfolio _ V2 _22-24Mohannad Abdullah  portfolio _ V2 _22-24
Mohannad Abdullah portfolio _ V2 _22-24
 
UNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptx
UNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptxUNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptx
UNIT V ACTIONS AND COMMANDS, FORMS AND CONTROLS.pptx
 
一比一原版(BU毕业证)波士顿大学毕业证如何办理
一比一原版(BU毕业证)波士顿大学毕业证如何办理一比一原版(BU毕业证)波士顿大学毕业证如何办理
一比一原版(BU毕业证)波士顿大学毕业证如何办理
 
Timeless Principles of Good Design
Timeless Principles of Good DesignTimeless Principles of Good Design
Timeless Principles of Good Design
 
ZAPATILLAS 2 X 110 ABRIL.pdf compra economico
ZAPATILLAS 2 X 110 ABRIL.pdf compra economicoZAPATILLAS 2 X 110 ABRIL.pdf compra economico
ZAPATILLAS 2 X 110 ABRIL.pdf compra economico
 
Practical eLearning Makeovers for Everyone
Practical eLearning Makeovers for EveryonePractical eLearning Makeovers for Everyone
Practical eLearning Makeovers for Everyone
 
哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样
哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样
哪里办理美国中央华盛顿大学毕业证双学位证书原版一模一样
 

Manual de instalacion detector honeywell

  • 1. General Information Before installing detectors, please thoroughly read these installation instructions and Guide for Proper Use of System Smoke Detectors (A05-1003-002), which provides detailed information on detector spacing, placement, zoning, wiring, and special applications. Copies of this manual are available from Honeywell. NOTICE: This manual should be left with the owner/user of this equipment. IMPORTANT: This detector must be tested and maintained regularly following NFPA 72 requirements. General Description The 5808W3 photoelectronic smoke/heat detector with built-in wireless transmitter is intended for use with wireless alarm systems that support 5800 series devices. Refer to control/communicator installation instructions for compatibility. The 5808W3 smoke/ heat detector can be used with any 5800 series wireless receiver/ transceiver for residential installations. For commercial installations, the 5881ENHC or the 5883H receiver is required. The transmitter can send alarm, tamper, maintenance (when control panels are equipped to process maintenance signals), and battery condition messages to the system’s receiver. The maintenance signal fully complies with the sensitivity test requirement specified in NFPA 72, 10.4.4.2.4 and is approved by UL. Refer to the wireless system’s instructions for the maximum number of transmitters that can be supported. The 5808W3 incorporates a state-of-the-art optical sensing chamber and an advanced microprocessor. The microprocessor allows the detector to automatically maintain proper operation at factory calibrated detection levels, even when sensitivity is altered due to the presence of contaminants settling into the unit’s smoke chamber. In order for this feature to work properly, the chamber must never be opened while power is applied to the smoke detector. This includes cleaning, maintenance or screen replacement. All models also feature a restorable, built-in, fixed temperature (135°F) thermal detector and is also capable of sensing a pre-freeze condition if the temperature is below 41°F. The 5808W3 contains a piezoelectric horn which generates the ANSI S3.41 temporal pattern in an alarm condition. In alarm, a message is also sent to the wireless control panel. The alarm message is transmitted every 4 seconds until the smoke or heat condition has cleared and the detector has reset. During an alarm condition, pressing the detector’s test switch will silence the piezoelectric horn for 5 minutes. Once the detector has reset, a RESTORE message is transmitted to the control panel. The built-in Drift Compensation algorithm automatically maintains the sensitivity of the detector. Once the detector reaches its limit of compensation, it transmits a maintenance signal to the panel. The mounting base installation is simplified by the incorporation of features compatible with drywall fasteners or other methods that provide a method for securing the detector in place. 5808W3 Photoelectronic Smoke/Temperature Detector with Built-in Wireless Transmitter INSTALLATION AND SETUP GUIDE I56-2768-005R Two LEDs and a sounder on the detector provide local visual and audible indication of the detector’s status: Table 1: Detector LED Modes Green LED Red LED Piezoelectric Horn Power Up Blinks every 5 sec Blinks every 5 sec Off Normal (standby) Blinks every 10 sec Off Off Out of Sensitivity Off Blinks every 5 sec Off Freeze Trouble Off Blinks every 10 sec Off Smoke Alarm Off Blinks every 1 sec Temporal Pattern Thermal Alarm Off Blinks every 4 sec Temporal Pattern Low Battery Off Blinks every 45 sec Chip every 45 sec after LED blinks for 7 days During initial power-up, the red and green LEDs will blink synchronously once every 5 seconds. It will take approximately 20 seconds for the detector to finish the power-up cycle (see Table 1). After power-up has completed and the detector is functioning normally within its listed sensitivity range, the green LED blinks once every 10 seconds. If the detector is in need of maintenance because its sensitivity has shifted outside the listed limits, the red LED blinks once every 5 seconds. When alarm has been activated by smoke, the red LED blinks every 1 second. During a thermal alarm condition (>135°F) the red LED blinks once every 4 seconds. The LED indication must not be used in place of the tests specified under Testing. In a freeze trouble condition, the red LED will blink once every 10 seconds (refer to Table 1). If the detector senses a low battery condition, the red LED blinks once every 45 seconds. To measure the detector’s sensitivity, the i3 Series Model SENS-RDR Infrared Sensitivity Reader tool (see Figure 4) should be used. Refer to instruction manual D100-98-00 for proper use of the SENS-RDR. Low Battery Detection The 5808W3 is powered by a single 3-volt CR123A or DL123A Lithium battery (included). The detector checks for a low battery at least every 65 minutes. If a low battery is detected, the transmitter sends a low battery message to the control panel, which beeps and displays the detector’s zone number. In addition, the red LED of the 5808W3 will blink every 45 seconds and the test switch will be disabled. This condition will exist for a minimum of 7 days, and then the detector’s horn will “chirp” about every 45 seconds. Pressing the test switch during this time will silence the chirps for 12 hours. The battery should be replaced BEFORE the chirps begin. Be sure to replace the battery with a fresh one. - 1 -
  • 2. Battery Installation and Replacement To replace the battery: 1. Remove the detector from its mounting base by twisting the detector counterclockwise. Remove the battery, and dispose properly. 2. To ensure proper power-down sequence, wait a minimum of 20 seconds before installing new battery. 3. Install a new 3-volt CR123A Lithium battery in the battery compartment. Follow the polarity diagram inside the compartment. 4. Reinstall the smoke detector onto the mounting base by turning the detector clockwise. 5. Test the detector as described in the TESTING SIGNAL STRENGTH section of this manual. The green LED should blink about once every 10 seconds to indicate normal operation. If the battery is not installed correctly, the smoke detector will not operate and the battery may be damaged. If the detector does not appear to be sending a signal during any of the tests, check for correct battery installation and for a fully charged battery. TEST SWTICH RED LED GREEN LED S0289-00 Figure 1. 5808W3 Wireless Smoke/Heat Detector Programming The smoke detector must be enrolled in the control panel before it can operate in the system. The 5808W3 smoke/heat protection zone must be enrolled as Loop 1 and “Input Type” 3 (supervised RF). If programmed, this smoke detector is capable of monitoring the additional conditions of Maintenance (transmitted as Loop 2), and Low Temperature (transmitted as Loop 3). Tamper is transmitted as Loop 4, but does not require programming. To take advantage of the value added features of Maintenance and Low Temperature, you must program each loop as a separate zone in the 5800 series wireless compatible panel. 1. Enter the control’s Zone Programming mode. 2. Enter the zone number to be programmed. 3. Enter the applicable zone type when prompted. Program • Loop 1 (Heat/Smoke) as a Fire zone (type 9 or 16), • Loop 2 (High/Low Maintenance) as a 24-Hr. Trouble zone (type 19), and • Loop 3 (Freeze Warning Sensor) as a 24-Hr. Aux. zone (type 8). NOTE: Loop 2 High/Low Maintenance is supported only on commercial control panels such as the Vista-128FBP. 4. When prompted, enter Input Type 03 (3 on some controls) – Supervised RF Transmitter. 5. When prompted for the serial number, transmit from the detector by activating the tamper switch. To do this, hold the base of the detector in one hand, and rotate the detector counter-clockwise on the base until it snaps open. Then return to clockwise position until the detector snaps into place. 6. When the serial number is displayed, transmit from the detector a second time by activating the tamper switch again as described in Step 5. The current loop number (4) will begin to flash. 7. Manually change the loop number to the desired loop number for the zone (according to the application). 8. When programming for this zone is complete, program other zones for the transmitter as necessary (except for Tamper Loop 4, which does not require programming). WARNING: The fire protection zone enrolled must always be Loop 1. Otherwise, fire annunciations will not be reported by the control. 9. Exit Programming mode when programming is complete, and test the detector. Refer to the Testing Section. See the control unit’s installation instructions for further details. Mounting First, determine the best location for the smoke detector, one that provides a strong wireless transmission path and proper smoke detection.AGOOD TRANSMISSION PATH MUST BE ESTABLISHED FROM THE PROPOSED MOUNTING LOCATION BEFORE PERMANENTLY INSTALLING THE DETECTOR. To check, perform the test described in the TESTING SIGNAL STRENGTH section of this manual. Prior to mounting the detector to the mounting base, you must “enroll” the detector’s serial number into the system (see the PROGRAMMING section). To mount the detector, perform the following steps: 1. Once a suitable location has been determined, install the mounting base on the ceiling or on the wall (if local ordinances permit). Use the two screws and anchors provided. 2. Turn the detector in a clockwise direction in the mounting base until it clicks into place. 3. Test the detector immediately after completing the installation (as described in the TESTING section of this manual) and refer to the control system’s instructions for additional information concerning the use of wireless smoke detectors. DIRECT MOUNT HOLES TAMPER RESISTANT TAB (CUT OFF SMALL TAB TO ACTIVATE TAMPER RESIST FEATURE) TAMPER RELEASE TAB S0290-00 Figure 2. Detector Mounting Base S0162-01 Figure 3. Mount Detector Across Ceiling Panel Support DO NOT attach the detector to removable ceiling panels. Attach the detector across panel support as shown in Figure 3. - 2 -
  • 3. Dust covers are an effective way to limit the entry of dust into the smoke detector sensing chamber during construction. However, they may not completely prevent airborne dust particles from entering the detector. Therefore, it is recommended that the detectors be removed before beginning construction or other dust producing activity. When returning the system to service, be sure to remove the dust covers from any detectors that were left in place during construction. Smoke detectors are not to be used with detector guards unless the combination has been evaluated and found suitable for that purpose. Tamper Protection This detector has a built-in tamper switch that will cause a CHECK signal to be displayed at the console of the alarm system if it is removed from its mounting base. The 5808W3 detector includes a tamper-resistant feature that prevents removal from the mounting base without the use of a tool. To engage the tamper-resistant feature, cut the small plastic tab located on the mounting base (Figure 2), and then install the detector. To remove the detector from the base once it has been made tamper resistant, use a small screwdriver to depress the square tamper release tab, located on the skirt of the mounting base, and turn the detector counterclockwise. Testing the Sensor NOTE: Before testing, notify the central station that the smoke detector system is undergoing maintenance, in order to prevent unwanted alarms. During initial power-up, do not use SENS-RDR or canned smoke to test the detector. The SENS-RDR and canned aerosol can be used after power-up sequence has completed. Detectors must be tested after installation and following periodic maintenance. The 5808W3 may be tested as follows: A. Test Switch 1. A recessed test switch is located on the detector housing (see Figure 4). 2. Push and hold the recessed test switch for a minimum of 5 seconds. Use a small screwdriver or Allen key with maximum diameter of 0.18 inch (the alarm panel will trigger and then the smoke detector will go into alarm. If the tool is removed from the recessed switch the sounder will shut off.) If the detector is within the listed sensitivity limits, the LED on the detector should blink once per second and the horn should sound within 3 seconds. POSITION SENS-RDR AT AN ANGLE ON THE OVAL AREA OR AT THE CHAMBER OPENING BY THE WORD “PAINT” RECESSED TEST SWITCH LED PUSH RECESSED SWITCH WITH A 0.18˝ MAX. DIAMETER TOOL S0308-00 Figure 4. Recessed Test Switch Opening and SENS-RDR Position B. Smoke Entry Test A canned smoke agent may be used to test the detector. Refer to the manufacturer’s instructions for proper use of the canned smoke. HSI brand canned smoke has been tested and approved for use with this type of smoke detector. C. Direct Heat Method (Hair dryer of 1000-1500 watts) Direct the heat toward either side thermistor. Be sure to hold the heat source about 12 inches from the detector to avoid damage to the plastic. The detector will reset only after it has time to cool. Smoke detection testing is recommended for verifying system protection capability. A detector that fails to activate with any of these tests should first be cleaned as outlined in this manual’s MAINTENANCE section. If the detector still fails to activate, return for repair. Testing Signal Strength NOTE: Remove battery tab before installation. This test should be performed in accordance with NFPA 72 inspection, testing and maintenance requirements to determine a strong communication path with the control panel. 1. Activate the wireless system’s GO/NO GO TEST mode from the keypad. 2. Depress and hold the smoke detector’s TEST switch. If the detector has not previously detected a low battery condition and it is within proper sensitivity limits, the detector should immediately transmit an alarm signal to the control panel. The built-in horn will start to sound about 2.5 seconds after depressing the button. 3. The wireless system’s keypad should emit at least three audible sounds when the alarm transmission is received and will display the transmitting detector’s zone number. 4. When the console has received the test signal, release the TEST switch. The horn will immediately stop and a few seconds later the detector’s zone number will clear from the console display. 5. If the console does not respond as noted, check the polarity of the battery and be sure it is fresh. If this is an initial installation, try moving the detector to another location that provides proper reception. Also be sure that the detector has been “enrolled” by the control panel (see PROGRAMMING). Then, repeat the test. 6. Turn off the system’s TEST mode from the keypad (security code + OFF). Testing Programmed Loops This test should be performed before installation to ensure that all loops intended to be used have been programmed and are operational in the system. 1. Activate the system’s TRANSMITTER ID SNIFFER mode from the keypad (see the control panel’s instructions). All programmed wireless zones will be displayed, one by one, on the system keypad. Make sure all smoke detector zones are displayed in the sequence. (If they are not, recheck that all zones have been properly programmed.) 2. With the detector mounted to the bracket, press the smoke detector’s TEST switch. All zones associated with the smoke detector should disappear from the keypad on the next display cycle. This means that the system has received a transmission from each loop you programmed. 3. When testing is complete, enter the Installer code + the OFF key to exit TEST mode. When all system testing has been completed, notify the central station that the system is back on line. - 3 -
  • 4. Maintenance NOTE: Before performing maintenance on the detector, notify the proper authorities and the central station that maintenance is being performed and the system will be temporarily out of service. Disable the zone or system undergoing maintenance to prevent any unwanted alarms, and follow this procedure exactly, referring to Figure 5. 1. Remove the detector housing from the base by twisting counter-clockwise. 2. Remove the battery from the unit. 3. Wait 20 seconds. (To ensure proper power-down sequence, the battery must be removed from detector for a minimum of 20 seconds before continuing to the next step.) 4. Remove the detector cover by turning counter-clockwise. 5. Vacuum the cover or use canned air to remove any dust or debris. 6. Remove the top half of the screen/sensing chamber by lifting straight up (see Figure 5). 7. Vacuum or use canned air to remove any dust or particles that are present on all chamber sections. 8. Replace the top half of the screen/sensing chamber by aligning the arrow on the screen/sensing chamber with the arrow on the housing. Press down firmly until the screen/sensing chamber is fully seated. 9. Replace the detector cover by placing it over the screen/sensing chamber and turning it clockwise until it snaps into place. Specifications Power Source: One 3-volt CR123A Lithium Battery (included). (Replace with Duracell DL123A, Sanyo CR123A, Panasonic CR123A or ADEMCO 466.) Height: 2.3 inches (58 mm) Diameter: 5.3 inches (135 mm) with mounting base Weight: 8.5 oz. (241 g) without battery Operating Ambient Temperature Range: 32° to 100°F (0° to 38°C) Operating Humidity Range: 0% to 95% Relative Humidity Heat Sensor: 135° F Fixed Temperature Electronic Thermistors Freeze Warning Sensor: 41°F (5°C) Agency Listings: UL 268 – Commercial and Residential Installations Please refer to insert for the Limitations of Fire Alarm Systems FOR WARRANTY INFORMATION AND FOR DETAILS REGARDING THE LIMITATIONS OF THE ENTIRE ALARM SYSTEM, REFER TO THE INSTALLATION INSTRUCTIONS FOR THE RECEIVER/CONTROL WITH WHICH THIS DEVICE IS USED. This device complies with Part 15 of the FCC rules and RSS210 of Industry Canada. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) This device must accept any interference received, including interference that may cause undesired operation. The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User’s Manual. D100-100-00 I56-2768-005R 10. Reinstall the battery into the battery compartment noting proper orientation. The red and green LEDs will flash once every 5 seconds for approximately 20 seconds until the power-up cycle is complete. 11. Reinstall the detector and test (see the Testing section). 12. Notify the central station when the system is back in service. IMPORTANT: If this procedure is not followed exactly, the detector may indicate a maintenance trouble after the power-up sequence is complete. If this happens, remove the battery for 20 seconds and then reinstall. REMOVABLE DETECTOR COVER SCREEN/SENSING CHAMBER (TOP HALF) DETECTOR HOUSING S0111-00 Figure 5. Removing Screen/Sensing Chamber 2 Corporate Center Drive, Melville, NY 11747 Copyright © 2007 Honeywell International Inc. www.honeywell.com/security