SlideShare a Scribd company logo
1 of 82
Three-Phase UPS Solutions

                                              Contact: Douglas Stansfield
                                              Douglas.Stansfield@gmail.com




           © 2008 Eaton Corporation. All rights reserved.
Powerware Series Three-Phase Product Lineup

Covering 10-1100 kVA with single systems and
providing paralleled capacity up to 8.8 MVA




                                               2   2
The Value of Eaton

Eaton Three-Phase UPSs provide the
greatest combination of benefits, delivering
tangible benefits for specifying engineers,
consultants and end users

» Lowest Total Cost of Ownership industry-wide
» Superior Performance and efficiency
» Real-time Information and Control
» World-class Support and Service




                                                     Eaton 9390
                                                 3                3
Low TCO


    Low TCO
      Improving the bottom line


Eaton UPSs deliver low TCO from advances in several
product facets
»   400V Site Design
»   High Power Density – small system footprints
»   Reduced weight and transportation costs
»   Low installation and Leading Efficiency – Quantifiable Benefits
»   Maintenance
»   Scalability
                                                            4         4
Low TCO – Leading Efficiency

Two complementary Eaton-proprietary technologies,
maximizing UPS efficiency under any condition!

Variable Module Management System (VMMS)
» Maximized efficiency in double conversion mode
» Both in single- and multi-UPS systems applications

Energy Saver Systems (ESS)
» The ultimate savings: 99% efficiency
» Automatic fast transfer to double conversion
  mode when needed (in less than 2 ms)


Energy Advantage Architecture
 Higher System Efficiency
 No Compromise On Reliability




                                                       5   5
Low TCO – Leading Efficiency

Energy costs are overwhelming
equipment costs in data centers.
  » UPS electrical losses account for 5-10%
   of the overall electrical expenditure.*


Eaton’s Energy Saver System drives
these losses down to nearly zero.


The energy savings recovers the cost
of the UPS in less than 5 years.

* Underlying figures from The Invisible Crisis in the Data Center:
The Economic Meltdown of Moore’s Law, Uptime Institute, 2007




                                                                     6   6
Low TCO – Leading Efficiency




ESS Efficiency 99% – across the complete operating range

                                               7           7
Low TCO – Leading Efficiency




The energy savings from ESS typically recovers
100% of the UPS cost over a 3-5 year period
» At 250kW of critical load, the savings is equivalent
  to $4000 per year per point of efficiency gain.

Backing up your 250kW load with an ESS UPS
is equivalent to pulling 29 cars off the road.


                                                         8   8
Low TCO – Leading Efficiency

How to maximize efficiency with lighter loads in double
conversion mode, especially in multi-UPS and redundant
system configurations?

Solution #1: Concentrate load on certain UPS’s to maximize
UPS load level and overall system efficiency
» Some energy savings
  • Limited to multiple-UPS systems (with several UPS in parallel)
  • Still not optimal


Solution #2: Eaton 9395 and its Variable
Module Management System
» Automatically optimize efficiency at UPM level
  • Concentrate the load on certain UPM’s to maximize
    overall system efficiency

» Only possible thanks to modularity of Eaton 9395 UPS
  • Not limited to multiple-UPS systems
  • Achieve even higher optimization thanks to UPM’s modularity



                                                                     9   9
Low TCO – Leading Efficiency

Example with same load applied to different
multi-UPS configurations




                                              10   10
5 0 5 0 5 0
                                                                                                    82 88 93 99 104 110
    Low TCO – Leading Efficiency




                                                                                                          0
                                                                                                        77
                                                                                                          5
                                                                                                        71
                                                                                                          0
                                                                                                        66
                         9395 UPS Efficiency




                                                                                                          5
                                                                                                        60
                                                                                                          0
                                                                                                        55
                                                                                        Eaton 9395 1100kVA UPS




                                                                                                          5
                                                                                                        49
                                                                          Eaton 9395 825kVA UPS




                                                                                                                          Load kVA
                                                                                                          0
                                                                                                        44
                                                               9395 1100kVA with VMMS and N+0 configuration*
                                                                9395 550kVA
                                                               Eaton 9395 550kVA UPS
                                                               9395 825kVA with VMMS and N+0 configuration*




                                                                                                          5
                                                                                                        38
                                                            Eaton 9395 275kVA UPS




                                                                                                      0
                                                                                                    33
VMMS allows to shift




                                                                                                          5
                                                                                                        27
to higher efficiency
curves (according to
         (according to                                    Typical Operations Range




                                                                                                          0
                                                                                                        22
system’s redundancy
system’s redundancy
requirements)
requirements)




                                                                                                          5
                                                                                                        16
up to N+0 VMMS
efficiency curve




                                                                                                          0
                                                                                                        11
                                       9395 275kVA
                                                                  Notes:
                                       9395 550kVA




                                                                                                      .5 55
                                                                  - Scaled drawing
                                       9395 825kVA




                                                                                                    27
                                                                  - VMMS and N+0 curves using VMMS default max
                                                     92


                                                             90




                                                                            86




                                                                                       82


                                                                                             80
                                           96


                                                94




                                                                     88




                                                                                  84




                                                                                                   78
                                       9395 1100kVA
                                                                    UPM % load level @ 80% (*)
                                                                   Efficiency %
                                       9395 VMMS N+0
                                                                                              11                                     11
Low TCO – 400V Site Design

480V AC
» Losses through the UPS, isolation transformer/PDU, and server equipment
» End-to-end efficiency of approximately 76%




                                                       12               12
Low TCO – 400V Site Design

600V AC
»   Used primarily in Canada
»   Can provide small savings in equipment costs, and utilizes lower currents
»   Requires multiple isolation transformer-based PDUs
»   End-to-end efficiency of approximately 76%




                                                            13                  13
Low TCO – 400V Site Design

400V AC
» Commonly used throughout the world
» PDU isolation transformers eliminated
» End-to-end efficiency of approximately 80%




                                               14   14
Low TCO – 400V Site Design




                             $592k        $689k     $97k


                             $7,027k      $7,284k   $257k


                             $7,619k      $7,973k   $354k


                             $6,072k      $7,284k   $1,212k


                             $6,664k      $7,973k   $1,309k




                                     15                       15
Low TCO – High Power Density

Eaton three-phase UPSs offer                                    9390 IT
 the highest power density.
The small footprint designs allows
existing facilities to increase
capacity without expensive building
modifications, and allows new         Competitor A
                                      Footprint
construction to maximize revenue
generating floor space vs.
support space.


                                                          Competitor B
                                                          Footprint




                                                     16                   16
Low TCO – Reduced Weight
and Transportation Costs

The Eaton 9395 UPS
» Lighter weight results in about
  20% carbon reduction due
  to transportation
» 15 tons of CO2 emissions are
  saved every 100 MVA worth of data
  center UPS is shipped 500 miles,
  compared to legacy equipment
» Lowest energy required for
  production (50%-80% reduction
  compared to legacy equipment)
» Up to 50% reduction in required
  floor space
» Reduction of hazardous materials

                                      17   17
Low TCO – Reduced Weight
and Transportation Costs
                                                                                    CROSS
                       DENSITY                 FOOTPRINT      DIMENSIONS           COUNTRY
MANUFACTURER     kVA   (kW per ft )
                                 2    WEIGHT      (ft )
                                                     2
                                                              (W x D x H, in.)   FREIGHT COST
Eaton 9395       550      29.6         2977      16.7      73.6 x 32.7 x 73.7        $893
COMPETITOR A     500      24.1         6900      18.7       69.0 x 39.0 x 82.0      $2,070
COMPETITOR B     500      24.0         5226      18.8       80.7 x 33.5 x 76.7      $1,568
COMPETITOR C     500      23.9         5512      20.9       94.0 x 32.0 x 71.0      $1,654
COMPETITOR D     500      23.1         5795      19.5       72.0 x 39.0 x 78.0      $1,739
COMPETITOR E     600      20.6         6373      29.1       99.8 x 42.0 x 80.0      $1,912
COMPETITOR F     500      15.1         6930      29.9      114.2 x 37.7 x 79.7      $2,079



» Freight Savings: Half the freight cost
» Fits through all doors, freight elevators, no dismantling,
  no need for crane rental
» Easier handling, eliminates most floor loading concerns




                                                                            18                  18
Low TCO – Reduced Installation
and Maintenance Costs

Traditional multi-module installations involve 3 times the
connections for inter-unit power and communications cabling

                                               SBM
           225 kVA +         225 kVA +          or
                                                Tie




The 9395 is a completely integrated
large system. Everything is pre-wired
and fully front-accessible with top or
bottom cable entry standard.


     SIGNIFICANT SAVINGS IN CABLING AND INSTALLATION TIME

                                                      19      19
Low TCO – Scalability

“Inside the Box” – Single Module Upgradeability

“Outside the Box” – Multi-Module Systems
» Parallel for redundancy or capacity
» Individual battery support removes a
  single-point-of-failure possibility

Powerware® Hot Sync Paralleling Technology
»   Eliminates a single point of failure opportunity
»   Peer-to-peer paralleling without wires
»   Eliminates BUNDLES of inter-cabling
»   Easy to parallel units
»   Firmware setting changes
»   Hot Sync CAN bridge Card

                                                       20   20
Superior Performance



  Superior performance
          is crucial to your business



Eaton uses advanced systems and redundancy to ensure
maximum uptime even when parts fail and systems malfunction
» Redundancy
» Superior battery management
» Hot Sync paralleling


                                             21           21
Consistent Reliability – Redundancy

Data center efficiency                   ISBM     UPM 1   UPM 2     REDUNDANT
                                                                    UPMs
surveys reveal that UPSs
are often under loaded at
50% or lower.

End users purchasing
a 9395 with more than INTEGRATED
one UPM can choose          SBM (ISBM)
the inherent redundancy
option. Anytime the load is
below 50% capacity, it is
automatically redundant.

» No other UPS manufacturer can offer this additional value to
  customers without adding a costly second UPS system.
» It may be the single most important feature that saves the customer
  from dropping their load.

                                                          22              22
Consistent Reliability –
Superior Battery Management

Conventional knowledge says
that batteries must be subjected
to continual float charging to maintain
backup time and health of the batteries.
Eaton engineers questioned this concept because:
» Data shows that most VRLA batteries designed
  with a 10-year useful life are replaced every
  4-5 years.
» Float charging a battery accelerates positive grid
  corrosion of the lead plates reducing service life.
» Float charging causes extra heat within the battery
  system, as compared to a cyclical charging
  system. And everyone knows that heat is a major
  factor in battery life.



                                                        23   23
Consistent Reliability –
Superior Battery Management


 ABM consists of three
 operating modes:
 » Charge Mode
 » Rest Mode
 » Test Mode


The UPS enters Charge mode under any         What if the battery is called upon to
of the following conditions:                 support a load when the UPS is near the
                                             end of its rest mode?
» Whenever the UPS is commanded to turn on
                                             Using a 15 minute battery as an example, the
» After any Utility power outage lasting
                                             battery would provide all but 30 seconds of its
  longer than 15 seconds
                                             15 minute backup time. This is proportionally
» Whenever the battery is replaced (or the   true for other battery sizes.
  battery breaker is opened and re-closed)

                                                                      24                       24
Consistent Reliability –
Superior Battery Management




                              25   25
Consistent Reliability – Hot Sync

No “single-point” failure
» Units synchronize to Utility or load bus
  independently
» Units load share within 5% independently
» Units “selective trip” instantaneously
» All without depending on inter module wiring!


Accomplished without
              “Master/Slave”
              configuration
» No Master “sync” or “load control signal”
  needed
» Enhanced Reliability and Simpler installation
» Easier and Quicker to troubleshoot
» Tie cabinet (ISBM) is simple/reliable in
  concept and in implementation


                                                  26   26
Real-time Information and Control




 Real-time
   Information and Control
Keeping data centers and facilities online requires
real-time information and control capabilities.
Eaton UPSs offer flexible options to interface with multiple
systems and give customers the best control.

                                                               27   27
Real-time Information and Control

Eaton Three-phase UPSs offer a variety of connectivity cards to
provide custom information and control options to end-users
» Web/SNMP
» Modbus
» AS400 relays
» Serial port
» Industrial Relay Card
» Environmental monitoring
  probe
» Hot Sync CAN
  Bridge Card




                                                28                28
Real-time Information and Control –
PowerXpert




                                      29   29
Real-time Information and Control –
ConnectUPS

ConnectUPS Web Interface




                                      30   30
Real-time Information and Control – IPM/IPP

Intelligent Power Manager software
for monitoring
 » Monitor and manage multiple power devices across
   the network from any PC with an Internet browser
 » Compatible with VMware’s vCenter™ Server
    • View your power and network devices from the same
      vCenter dashboard
    • During a power event, the software triggers vMotion™ to
      transparently move virtual machines to an available server on
      the network for zero downtime



Intelligent Power Protector software for shutdown
 » Gracefully shuts down computers and virtual machines/servers
   (powered by an Eaton UPS) during a power outage that lasts
   longer than the available battery runtime

Download from the Power Quality website: www.eaton.com/intelligentpower


                                                                      31   31
Real-time Information and Control – eNotify
     MONITORED UPS                                              CUSTOMER
                                   CONNECTIVITY                 MONITORING                SERVICE DELIVERY
     AND BATTERY
                                                                CENTER




 Equipment                    Connectivity                 Back Office (CMC)               Service Delivery
• Eaton 3-phase UPS          • Web/SNMP card via          • Monitors more than 1,500      • National coverage —
  (9395, 9390, 9315, 9315      customer-supplied            UPS systems                     240 field technicians in
  SBM, 9355, 9330,             e-mail server connection   • Collects, stores & trends       US and Canada
  BladeUPS)                  • Daily outbound-only          data                          • 24x7 coverage with
• Eaton 1-phase UPS            heartbeat e-mail from      • Uses anomaly detection          4-hour response in top
  (9140, 9155, 9120, 9125,     UPS to CRC for secure        system to proactively           50 markets
  9130, 9135, 9170+)           connectivity                 identify & act on potential   • Remote repair/
• 48 alarm events,           • No remote control            load-loss events                diagnostics expedites
  11 critical alarms           capability                 • Customers can receive           delivery
                                                            monthly reports, real-time
                                                            notification, & call CMC
                                                            7x24 with questions

                                                                                          32                           32
Support and Service




 Support and
 Service

Eaton UPSs are a long-term investment, with the ability
to have a service life of 20 years or more!
That’s why we have a dedicated support and service team to assist customers
with routine maintenance and questions to keep your investment running
smoothly.
                                                        33               33
Why Customers Buy Eaton Service

» Service technician’s expert knowledge of
  Eaton products
» Deal direct with the factory
» Quick response by having 240+ field technicians
» 24x7x365 emergency access for service contract
  customers to technical support and on-site technician
» Safety – our technicians are trained and equipped
  to work within the latest OSHA and NFPA
  safety guidelines
» Access to field parts inventory maintained
  by technician
» Increased reliability – experienced technician with factory
  training, technical support resources, focused on a
  specific manufacturer’s product


 Source: Hahn Consulting UPS VOC Needs Assessments, 2002-2006, based on Eaton UPS 3P customer phone and personal interviews



                                                                                                       34                     34
Eaton Service Numbers

» Average number of emergencies successfully
  responded to annually >5,000
» Average speed of answering phone calls = 16 seconds
» FirstTime Fix = 75% (2010)
» Average tenure of Eaton field technician employees =
  10.2 years
» Number of Preventive Maintenance visits completed
  annually = >30,000
» Number of factory training hours in 2009 for Eaton
  field technicians = 12,480 hours
» Training time for a new Eaton field technician =
  minimum of 16 weeks classroom/lab training, and up
  to one year of mentoring in the field
» Overall Customer Satisfaction = 99% (2009)


 Source: Hahn Consulting UPS VOC Needs Assessments, 2002-2006, based on Eaton UPS 3P customer phone and personal interviews



                                                                                                       35                     35
Field Technician Coverage – US & Canada




                                 36       36
Field Technician Coverage – Global Reach




                                 37        37
Sections




           9x55   9390   9395        Success
                                     Stories


                                38         38
9X55 – Overview

Product Snapshot

Power Rating: 8-30 kVA
Topology: Double-Conversion On-line
Input Power Factor: >0.99 at full load
Output Power Factor: 0.9 pf
Input/Output Voltage: 208/208 or 220/220 input
120/208/240 Split Phase (9155) 480/208 or
600/208 w/ xfmr
Frequency: 50/60 Hz selectable, auto-configuring
Configuration: Tower




                                                   39   39
9X55 – Low Total Cost of Ownership



15 kVa Comparison                20 kVa Comparison
Battery Runtime = 5 Minutes      Battery Runtime = 18 Minutes
Footprint = 408 Square Inches    Footprint = 680 Square Inches


Competitor C 15 kVA              Competitor C 20 kVA
Battery Runtime = 5 Minutes      Battery Runtime = 5 Minutes
Footprint = 1320 Square Inches   Footprint = 1320 Square Inches


At 15 kVA, the 9355 occupies     At 20 kVA, the 9355 occupies
70 percent less footprint        48 percent less footprint and
                                 delivers over three times the
                                 battery runtime




                                                                  40   40
9X55 – Low Total Cost of Ownership
10 & 15 kVA          Dimensions                    Runtime       (min)
                                       Footprint
Configurations       (inches)          (square     10 kVA    15 kVA
       Product       W    D       H    inches)
                                                                         75%
      9355           12   34      32   408         9         5           smaller
                                                                         footprint!
      Competitor A   21   33      59   693         9         5
      Competitor B   24   36      82   864         9         5
      Competitor C   33   40      63   1320        9         5
      Competitor D   36   20      35   720         9         5           13%
      Competitor E   24   33      64   792         9         5           more
                                                                         capacity!
20 & 30 kVA          Dimensions                    Dimensions
                                       Footprint
Configurations       (inches)                      (inches)
                                       (square
       Product       W    D       H    inches)     20 kVA    30 kVA
                                                                         Up to 350%
      9355           20   34      66   680         18        11          more
      Competitor A   21   33      59   693         5         5           runtime!
      Competitor B   24   36      82   864         5         5
      Competitor C   33   40      63   1320        5         5
      Competitor D   36   20      35   720         5         5
      Competitor E   24   33      64   792         5         5


                                                                         41           41
9X55 – Unique Product Features

Integrated Power Distribution
Modules provide customized
distribution and connectivity




                                 42   42
9X55 – Power Distribution

» Factory Installed on-board Power Distribution Modules
» PDM is equipped with circuit breakers, terminal block,
  and configurable output plugs
» Maximum of 4 panels per PDM
» The combined quantities of single
  locking receptacle panels (shown
  with an *) must not exceed 4 per PDM
» PDM is ordered using 4 dedicated digits in the UPS
  CTO number.
» PDM ships attached to the UPS
PDM Panels:
 (2) 5-15R     (2) 5-20R UL   (2) 5-20R CSA   (2) 6-15R     (2) 6-20R

 (2) L5-15R    (1) L5-20R*    (1) L5-30R*     (2) L6-15R    (1) L6-20R*

 (1) L6-30R*   (1) L14-20R*   (1) L14-30R*    (1) L21-20R   (1) L21-30R


IEC 320 C13 and C19 panels available (120V)

                                                                          43   43
9X55 – Power Distribution

The 9355’s on-board power distribution module is compatible with
Eaton’s optional rack power modules (RPM) and enclosure power
distribution units (ePDU™), providing maximum flexibility in
distributing power throughout the facility or data center.

Easier, Less Complex, and More
Cost-Effective End-of-Row Solution
for Price Sensitive Customer!

Enabling Plug-and-Play Power Distribution

                                          Eaton RPMs and ePDUs simplify
                                          power distribution by reducing the
                                          number of cables to manage and
                                          distribution points to monitor


                                                                       Back To
                                                                       Main

                                                           44                  44
9390 – Overview

Product Snapshot

Power Rating: 20-160 kVA
Topology: Double-Conversion On-line
Input Power Factor: >0.99 at full load
Output Power Factor: 0.9 pf
Input/Output Voltage: 208/208,
400/400, 480/480, 480/208, 600/600,
600/208
Frequency: 50/60 Hz selectable,
auto-configuring
Battery Types: VRLA, AGM, Gel, Wet
Configuration: Tower

                                         40 kVA 9390IT   20-80 kVA   100-160 kVA




                                                               45                  45
9390 – Low Total Cost of Ownership

Energy Saver System




                                 46   46
9390IT – Low Total Cost of Ownership
               Dimensions        Footprint
               (inches)          (square
                                 inches)
Product        W    D       H
                                             61%
9390IT         28   31      74   865         smaller
Competitor A   59   38      79   2238
                                             footprint!
Competitor B   60   36      72   2136        13%
                                             more
                                             capacity!




                                              47          47
9390 – Unique Product Features

» Optional Integrated Batteries
  (9390IT)
» Full compliment of Line & Match
  distribution cabinets (Pisano’s Grand
  Statement Here)
» Serviceable design




                                          48   48
9390 – Unique Product Features

Line and Match system accessory cabinets
» Use the most economical option (space and cost) to meet your
  site requirements. No other manufacturer offers the flexiblity of
  the Eaton 9390 line of accessory cabinets.


              IBC                         IAC                  IDC




                                                          49          49
IAC

9390 IAC cabinet is available in three configurations
» Maintenance Bypass
» Parallel Tie
» 42 Pole Distribution




      Maintenance Bypass      Tie            Distribution



                                                    50      50
IDC

      Integrated Distribution Cabinet
      Incorporates any or all of three functionalities
      within a single cabinet
       » Maintenance Bypass
       » Step Down Transformer
       » Power Distribution
         • With (2) 42 pole load centers
         • With (1 to 6) distribution breakers
         • With (1) 42 pole panel and
         • (1-3) 225A SFBs




                                                 51      51
9390 IBC

Variable battery bus
configurations
»   384VDC – 480VDC
»   (192 – 240 cells)
»   Virtually limitless runtime possibilities
»   Size batteries based on runtime, or
»   Size batteries based on lowest cost

0.8 and 0.9pf runtime
Charts for sizing
kVA upgrade support
IBC-S
» Up to 16 minutes @ 40kVA
» Up to 7 minutes @ 80kVA

IBC-L
» 10 minutes to several hours…                      IBC-S                IBC-L
                                                570mm/22.5” WIDE   1085mm/42.7” WIDE




                                                                    52                 52
Serviceability

100% Front Access
» Fast, easy access
» Unit can be backed up against wall or
  into a corner
» No clearance needed at rear
  or sides


Fast repair and return
to service
Mean time to repair (MTTR) less
than 30 minutes
» Power modules are field-replaceable
   units
» Fan tray is a field-replaceable unit
» Slide in/out design


9390 provides the best
serviceability


                                          53   53
Serviceable Design (40/80kVA)
                          Top cable
                          entry area
X-Slot
communication
bays

                          Replaceable
                          converter/inverter
System Control            modules
and interface boards
                          Redundant
                          power supplies




                          Slide out fan tray


                          Input/Output
                          connections
                          DC connections
Modular static
switch assembly
                          Bottom                    Back To
                          cable
                          entry area                Main

                                               54        54
9395 – Overview

Product Snapshot

Power Rating: 225-1100 kVA
Topology: Double-Conversion On-line
Input Power Factor: >0.99 at full load
Output Power Factor: 0.9 pf
Input/Output Voltage: 400/400,
480/480, 480/208
Frequency: 50/60 Hz selectable,
auto-configuring
Battery Types: VRLA, AGM, Gel, Wet
Configuration: Tower




                                         55   55
9395 – Low Total Cost of Ownership

Energy Saver System




                                 56   56
9395 – Footprint
                                                                                  CROSS
                     DENSITY                 FOOTPRINT      DIMENSIONS           COUNTRY
MANUFACTURER   kVA   (kW per ft )
                               2    WEIGHT      (ft )
                                                   2
                                                            (W x D x H, in.)   FREIGHT COST
Eaton 9395     550      29.6         2977      16.7      73.6 x 32.7 x 73.7        $893
COMPETITOR A   500      24.1         6900      18.7       69.0 x 39.0 x 82.0      $2,070
COMPETITOR B   500      24.0         5226      18.8       80.7 x 33.5 x 76.7      $1,568
COMPETITOR C   500      23.9         5512      20.9       94.0 x 32.0 x 71.0      $1,654
COMPETITOR D   500      23.1         5795      19.5       72.0 x 39.0 x 78.0      $1,739
COMPETITOR E   600      20.6         6373      29.1       99.8 x 42.0 x 80.0      $1,912
COMPETITOR F   500      15.1         6930      29.9      114.2 x 37.7 x 79.7      $2,079




                                                                          57                  57
9395 – Unique Product Features

» VMMS
» SMaRT Certification
» Inherent Redundancy
» Easy Capacity Test
» Concurrent Maintenance
» Flexible/Scalable/Upgradeable




                                  58   58
VMMS Principle

Example With Same Load Applied To
Different Multi-UPS Configurations




                                     59   59
VMMS Applications

VMMS can be used in all multi-module
(multiple-UPM) 9395 systems
» Single 9395 units from 550kVA to 1100kVA
» Distributed parallel systems SBM Systems


Typical Applications Where VMMS
Particularly Efficient
»   Redundant N+1 and 2N systems UPS’s
     • Lightly loaded: typically operate at loads < 45% load level
       where efficiency is not optimal
» Data Centers, especially when UPS system
  feeds dual corded servers
» Any applications when load is not constant




                                                                     60   60
SMaRT Certification

The SMaRT Gold certified 9395 can
contribute to points in two LEED Credit
Categories for buildings and projects
seeking certification.




                                          61   61
Inherent Redundancy Option

 Next Generation Reliability
 Data center efficiency surveys reveal that
 UPSs are often under loaded at 50% or lower.


 End users purchasing a Eaton 9395 with
 more than one UPM can use the inherent
 redundancy capability. Anytime the load is
 below 50% capacity, it is automatically
 redundant.



» No other UPS manufacturer can offer this additional value to
  customers without adding a costly second UPS system
» It may be the single most important feature that saves
  the customer from dropping their load


                                                           62    62
Easy Capacity Load Testing

The Eaton 9395 leverages an enhanced startup and
commissioning offering exclusive to Eaton field
technicians. It can take the place of some
traditional load bank tests to save customers time
and money during startup and commissioning.

This load test ensures validation of performance of
an installed UPS and can simulate various
operations and power transfers.


» No load banks to rent
» No load connections needed
» No wasted energy




         LOAD TEST CAPABILITY SAVES CUSTOMERS TIME AND MONEY


                                                       63      63
Easy Capacity Load Testing

       An Eaton field technician applies full load, tests & calibrates:
       Rectifier                          RIB
       Inverter                           Static bypass switch
       Battery – with option to perform   Fuses                   No Output
       full battery discharge test        Contactors             Connection &
       BIB                                Conductors
                                                                  Load Bank
                                                                   Needed




ADDITIONAL THERMAL IMAGING TESTS ARE POSSIBLE ON UPS, INPUT CABLES AND SWITCHGEAR


                                                                 64             64
Easy Capacity Load Testing

Easy Redundancy Test:
» Eaton field technician can disable one
  UPM to demonstrate redundancy
» Alternately loads each UPM to
  capacity in redundant systems




                                                               X
  EASY SERVICE DISCONNECT FEATURE MAKES IT SIMPLE TO ISOLATE UPMS


                                                       65           65
Flexible, Scalable, Upgradeable




   On-site                                  On-site
   upgrade     275 kVA Redundant!           upgrade   550 kVA Redundant!


Add another 275 kVA in the field for redundancy, or for capacity
» Simply choose an ISBM sized for future growth
» Leave space on the left side
Enables flexibility for future changes in load demands, and
new requirements for higher reliability

                                                          66               66
Concurrent Maintenance

     With the N+1 redundant designs of Powerware Hot
     Sync Technology (including units with the
     inherent redundancy option), you can completely
     isolate and service a redundant module, while the
     other module carries the load…no need to go to
     bypass for service

               “…high-availability cannot be achieved
               without considering the concurrent
               maintainability and the fault-tolerance
               of the underlying infrastructure”
                                  The Uptime Institute


                                                              Back To
CONCURRENT MAINTENANCE = HIGHER AVAILABILITY                  Main

                                                         67        67
Success Stories




 Success Stories
      our strongest advocates…customers




                                68        68
Our Customers: Collier County

Eaton 9355 and 9390
UPS, eNotify and
Service
“They’re on the spot 24x7 if I
need them. Whether I need
to change a phone number
in their system or have a
question on a unit, they are
very responsive.”

David Holmes,
Senior Facilities
Management Department




                                 69   69
Our Customers: Miami Dolphins

Eaton 9390 UPS
“Just last week we
lost power for about
20 seconds at the
training facility. If
you were standing
inside the data center,
you'd never have known.”

Joe Curbelo,
Director of
Infrastructure Services




                                70   70
Our Customers:
Indianapolis Motor Speedway Productions

Eaton 9355 UPS
“We have the peace
of mind that we won't
lose data and that our
data won't get corrupted...
It allows all of our servers
to keep on humming
without interruption.”

Scott Burgett,
Maintenance Engineer




                                 71       71
Our Customers: CoSentry

9395 UPS with
Energy Saver System
“Competitive offerings
with a track record didn’t
exist—at least not for a
modular UPS of this size.
This application afforded the
purchase of one UPS, so we
were obviously delighted to
find that we could purchase
redundancy—effectively two
for the price of one!”

Kevin Dorhmann,
Chief Technology Officer




                                72   72
Our Customers: BMW Sauber

Eaton 9395 UPS
Hinwil, Switzerland
With the 9395, BMW Sauber saves
roughly one-fourth of the energy
used by comparable systems.




                                   73   73
Our Customers: Southwest Airlines

Eaton 9355, 9315
and Powerware Plus
750 UPS; PowerTrust
Service Plans
“Gary Rose and Jason
Renshaw know me and I
know them. I don’t have
to worry when they come
on-site. They know my
building. They know my
loads. And they know how
critical it is.”

Steve Hurst,
Project Leader




                                    74   74
Our Customers: NetRiver

Eaton 9395 UPS with
Energy Saver System
“That’s huge, because
traditional UPSs are terrible
in terms of efficiency. It’s like
going to those places in the
mall where you put your
change in and get only part
of it back. With this Eaton
UPS, it’s like putting 100
pennies in and you get 99
cents back. Because we use
billions of pennies, so to
speak, it really adds up.”

Adam Vierra,
Sales and Marketing
Manager


                                    75   75
Our Customers: American Kennel Club

Eaton 9390 UPS
“We wanted to know that we
could buy something appropriate
for our current needs but not
have to throw it out and replace
it if our power needs changed in
the future.”

Charles Kneifel,
Chief Information Officer




                                   76   76
Our Customers: NextEnergy

9395 UPS
“The nice thing about the 9395 is that
a lot of the features that we needed
developed were already there in
some format.”

Max Dorflinger,
Director of Program Delivery




                                         77   77
Our Customers:
U.S. Navy Tactical Training Group Pacific

9395 UPS
“The Navy doesn’t want to put in
something that’s not energy efficient.
Everyone is trying to save money these
days, and energy efficiency is an
important part of that. Without a reliable
   UPS, if we had a power outage, training
would go down for the entire west coast—
or beyond.”

Tom Hurst,
Facilities Manager




                                             78   78
Our Customers:
Washington Department of Ecology

9395 UPS
“We are fully confident that the
unit will handle everything we’re
asking of it. The technician put
it through extensive testing at
the startup,” noting that
assessments ranged from
automatic transfer scenarios to
load bank tests. “We know it’s
going to hold the load.”

Steve Strope,
Facility Manager




                                    79   79
Our Customers: UNC Pembroke

PowerTrust Service Plan
with 9355 UPS
Field Tech: David Horrell
“In David, we have a technician
who is as reliable as our Eaton
UPS,” Barry Graves says.
“The performance of our systems
is critical, so we can’t settle for
anything less.”




                                      80   80
Our Customers:
Royal Caribbean Oasis of the Seas

20 UPS from 1 to 350 kVA
9395, 9390, 9355 and
9155 Marine UPS
“We have worked with Eaton for over
10 years in all of our most demanding
cruise ship construction projects,”
says System Coordinator Ville Talsi of
shipbuilding group STX Europe,
Turku, Finland. “Their high quality
products and field services around the
world have guaranteed an enjoyable
cruise experience for passengers and
uninterrupted working for the
sophisticated technology on board
our ships.”
                                              Back To
                                              Main

                                         81        81
82   82

More Related Content

What's hot

Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Harshit Srivastava
 
Electric power transmission full explanation and presentation
Electric power transmission full explanation and presentationElectric power transmission full explanation and presentation
Electric power transmission full explanation and presentationRakesh Gurjar
 
Over Head Line Insulators : Presentation Topic in Electrical Engineering Seminar
Over Head Line Insulators : Presentation Topic in Electrical Engineering SeminarOver Head Line Insulators : Presentation Topic in Electrical Engineering Seminar
Over Head Line Insulators : Presentation Topic in Electrical Engineering SeminarSandip Kumar Sahoo
 
over head insulators
over head insulatorsover head insulators
over head insulatorsFahad Rasheed
 
Simple Capacitive Voltage Transformer (CVT) Testing for Switchyard Equipment
Simple Capacitive Voltage Transformer (CVT) Testing for Switchyard EquipmentSimple Capacitive Voltage Transformer (CVT) Testing for Switchyard Equipment
Simple Capacitive Voltage Transformer (CVT) Testing for Switchyard EquipmentSARAVANAN A
 
Feasibility study of setting of solar plant in Philippines
Feasibility study of setting of solar plant in Philippines Feasibility study of setting of solar plant in Philippines
Feasibility study of setting of solar plant in Philippines Siddharth Kundu
 
Power Transmission & Distribution in India
Power Transmission & Distribution in IndiaPower Transmission & Distribution in India
Power Transmission & Distribution in IndiaIndian Energy Sector
 
Partial Discharge Test - Switchgear
Partial Discharge Test - Switchgear Partial Discharge Test - Switchgear
Partial Discharge Test - Switchgear RajuGupta88
 
Transmisiion line design concept
Transmisiion line design conceptTransmisiion line design concept
Transmisiion line design conceptKumar VEL
 
Self assembly in photovoltaic devices
Self assembly in photovoltaic devicesSelf assembly in photovoltaic devices
Self assembly in photovoltaic devicesZaahir Salam
 
Final Report Biomass
Final Report BiomassFinal Report Biomass
Final Report BiomassNeel Patel
 
Cable sizing to withstand short circuit current
Cable sizing to withstand short circuit currentCable sizing to withstand short circuit current
Cable sizing to withstand short circuit currentLeonardo ENERGY
 
Clearance required for setting up thermal power plant
Clearance required for setting up thermal power plantClearance required for setting up thermal power plant
Clearance required for setting up thermal power plantSushant Kumar Sinha
 
Energy Efficiency of Telecom Networks
Energy Efficiency of Telecom NetworksEnergy Efficiency of Telecom Networks
Energy Efficiency of Telecom NetworksPavel Loskot
 
Optimal Cable Sizing in PV Systems: Case Study
Optimal Cable Sizing in PV Systems: Case StudyOptimal Cable Sizing in PV Systems: Case Study
Optimal Cable Sizing in PV Systems: Case StudyLeonardo ENERGY
 
molten carbonate fuel cell
molten carbonate fuel cellmolten carbonate fuel cell
molten carbonate fuel cellAfrin Nirfa
 
Captive Power Plants.pdf
Captive Power Plants.pdfCaptive Power Plants.pdf
Captive Power Plants.pdfSourav Bhunia
 

What's hot (20)

Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"Areva "Manufacturing of transformer, uses & it’s accessories"
Areva "Manufacturing of transformer, uses & it’s accessories"
 
Paper battery
Paper batteryPaper battery
Paper battery
 
Electric power transmission full explanation and presentation
Electric power transmission full explanation and presentationElectric power transmission full explanation and presentation
Electric power transmission full explanation and presentation
 
Over Head Line Insulators : Presentation Topic in Electrical Engineering Seminar
Over Head Line Insulators : Presentation Topic in Electrical Engineering SeminarOver Head Line Insulators : Presentation Topic in Electrical Engineering Seminar
Over Head Line Insulators : Presentation Topic in Electrical Engineering Seminar
 
over head insulators
over head insulatorsover head insulators
over head insulators
 
Simple Capacitive Voltage Transformer (CVT) Testing for Switchyard Equipment
Simple Capacitive Voltage Transformer (CVT) Testing for Switchyard EquipmentSimple Capacitive Voltage Transformer (CVT) Testing for Switchyard Equipment
Simple Capacitive Voltage Transformer (CVT) Testing for Switchyard Equipment
 
Feasibility study of setting of solar plant in Philippines
Feasibility study of setting of solar plant in Philippines Feasibility study of setting of solar plant in Philippines
Feasibility study of setting of solar plant in Philippines
 
Power Transmission & Distribution in India
Power Transmission & Distribution in IndiaPower Transmission & Distribution in India
Power Transmission & Distribution in India
 
Partial Discharge Test - Switchgear
Partial Discharge Test - Switchgear Partial Discharge Test - Switchgear
Partial Discharge Test - Switchgear
 
Transmisiion line design concept
Transmisiion line design conceptTransmisiion line design concept
Transmisiion line design concept
 
Self assembly in photovoltaic devices
Self assembly in photovoltaic devicesSelf assembly in photovoltaic devices
Self assembly in photovoltaic devices
 
Final Report Biomass
Final Report BiomassFinal Report Biomass
Final Report Biomass
 
Cable sizing to withstand short circuit current
Cable sizing to withstand short circuit currentCable sizing to withstand short circuit current
Cable sizing to withstand short circuit current
 
Clearance required for setting up thermal power plant
Clearance required for setting up thermal power plantClearance required for setting up thermal power plant
Clearance required for setting up thermal power plant
 
Cable Sizing Calculations
Cable Sizing CalculationsCable Sizing Calculations
Cable Sizing Calculations
 
CUF vs PR
CUF vs PRCUF vs PR
CUF vs PR
 
Energy Efficiency of Telecom Networks
Energy Efficiency of Telecom NetworksEnergy Efficiency of Telecom Networks
Energy Efficiency of Telecom Networks
 
Optimal Cable Sizing in PV Systems: Case Study
Optimal Cable Sizing in PV Systems: Case StudyOptimal Cable Sizing in PV Systems: Case Study
Optimal Cable Sizing in PV Systems: Case Study
 
molten carbonate fuel cell
molten carbonate fuel cellmolten carbonate fuel cell
molten carbonate fuel cell
 
Captive Power Plants.pdf
Captive Power Plants.pdfCaptive Power Plants.pdf
Captive Power Plants.pdf
 

Similar to Eaton UPS Three phase family-gq_r8_lite

Eaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptxEaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptxmancangkul1
 
Eaton ups energoefektivitate
Eaton ups energoefektivitateEaton ups energoefektivitate
Eaton ups energoefektivitateElektrumlv
 
Limit data center costs without limiting growth
Limit data center costs without limiting growthLimit data center costs without limiting growth
Limit data center costs without limiting growthSwitchOn to Eaton
 
9395-UPS-Brochure
9395-UPS-Brochure9395-UPS-Brochure
9395-UPS-BrochureEhab Saleh
 
Eaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_CEaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_CEhab Saleh
 
Steam turbines solutions
Steam turbines solutions Steam turbines solutions
Steam turbines solutions Farid Nazri
 
An overview of Eaton's Utility segment solutions
An overview of Eaton's Utility segment solutionsAn overview of Eaton's Utility segment solutions
An overview of Eaton's Utility segment solutionsEaton Electrical
 
Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design ConsiderationsSchneider Electric
 
 Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energy Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energyjerianasmith
 
Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power
 
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmElektrumlv
 
Ls catalog thiet bi tu dong i p5a_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i p5a_e_1105_dienhathe.vnLs catalog thiet bi tu dong i p5a_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i p5a_e_1105_dienhathe.vnDien Ha The
 
Ls catalog thiet bi tu dong i p5a_e_1105
Ls catalog thiet bi tu dong i p5a_e_1105Ls catalog thiet bi tu dong i p5a_e_1105
Ls catalog thiet bi tu dong i p5a_e_1105Dien Ha The
 
Voltage stabilisation and optimisation by Captech - The facts
Voltage stabilisation and optimisation by Captech - The factsVoltage stabilisation and optimisation by Captech - The facts
Voltage stabilisation and optimisation by Captech - The factsEddie Hoade
 
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)GE코리아
 
6dec2011 - Power Back-up_1
6dec2011 - Power Back-up_16dec2011 - Power Back-up_1
6dec2011 - Power Back-up_1Agora Group
 

Similar to Eaton UPS Three phase family-gq_r8_lite (20)

Eaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptxEaton 93PM 30-50kW UPS.pptx
Eaton 93PM 30-50kW UPS.pptx
 
Eaton ups energoefektivitate
Eaton ups energoefektivitateEaton ups energoefektivitate
Eaton ups energoefektivitate
 
10027042_USV_Argument_gb
10027042_USV_Argument_gb10027042_USV_Argument_gb
10027042_USV_Argument_gb
 
Limit data center costs without limiting growth
Limit data center costs without limiting growthLimit data center costs without limiting growth
Limit data center costs without limiting growth
 
9395-UPS-Brochure
9395-UPS-Brochure9395-UPS-Brochure
9395-UPS-Brochure
 
Eaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_CEaton_9155_9355_15kVA_datasheet_rev_C
Eaton_9155_9355_15kVA_datasheet_rev_C
 
Steam turbines solutions
Steam turbines solutions Steam turbines solutions
Steam turbines solutions
 
An overview of Eaton's Utility segment solutions
An overview of Eaton's Utility segment solutionsAn overview of Eaton's Utility segment solutions
An overview of Eaton's Utility segment solutions
 
9096 Enphase Introduction
9096 Enphase Introduction9096 Enphase Introduction
9096 Enphase Introduction
 
Secure Power Design Considerations
Secure Power Design ConsiderationsSecure Power Design Considerations
Secure Power Design Considerations
 
 Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energy Running UPS in Economy Mode To Save Energy
 Running UPS in Economy Mode To Save Energy
 
Flyer 4 page
Flyer 4 pageFlyer 4 page
Flyer 4 page
 
Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...Magellan Power - High Reliability Australian Technology Innovative, Customise...
Magellan Power - High Reliability Australian Technology Innovative, Customise...
 
The ErP Directive and its impact on switchgear
The ErP Directive and its impact on switchgearThe ErP Directive and its impact on switchgear
The ErP Directive and its impact on switchgear
 
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībāmPC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
PC 3-fāžu UPS izvēles iespējas ražošanas uzņēmumu vajadzībām
 
Ls catalog thiet bi tu dong i p5a_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i p5a_e_1105_dienhathe.vnLs catalog thiet bi tu dong i p5a_e_1105_dienhathe.vn
Ls catalog thiet bi tu dong i p5a_e_1105_dienhathe.vn
 
Ls catalog thiet bi tu dong i p5a_e_1105
Ls catalog thiet bi tu dong i p5a_e_1105Ls catalog thiet bi tu dong i p5a_e_1105
Ls catalog thiet bi tu dong i p5a_e_1105
 
Voltage stabilisation and optimisation by Captech - The facts
Voltage stabilisation and optimisation by Captech - The factsVoltage stabilisation and optimisation by Captech - The facts
Voltage stabilisation and optimisation by Captech - The facts
 
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
GE LV5 1500V 태양광 인버터(LV5 1500V Solar Inverter)
 
6dec2011 - Power Back-up_1
6dec2011 - Power Back-up_16dec2011 - Power Back-up_1
6dec2011 - Power Back-up_1
 

Recently uploaded

Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...amitlee9823
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Roland Driesen
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...Aggregage
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfPaul Menig
 
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxpriyanshujha201
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsP&CO
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear RegressionRavindra Nath Shukla
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdfRenandantas16
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxWorkforce Group
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Servicediscovermytutordmt
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Delhi Call girls
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMRavindra Nath Shukla
 
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756dollysharma2066
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒anilsa9823
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...rajveerescorts2022
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfAmzadHosen3
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...lizamodels9
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityEric T. Tung
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...Paul Menig
 

Recently uploaded (20)

Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
Call Girls Jp Nagar Just Call 👗 7737669865 👗 Top Class Call Girl Service Bang...
 
Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...Boost the utilization of your HCL environment by reevaluating use cases and f...
Boost the utilization of your HCL environment by reevaluating use cases and f...
 
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
The Path to Product Excellence: Avoiding Common Pitfalls and Enhancing Commun...
 
Grateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdfGrateful 7 speech thanking everyone that has helped.pdf
Grateful 7 speech thanking everyone that has helped.pdf
 
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptxB.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
B.COM Unit – 4 ( CORPORATE SOCIAL RESPONSIBILITY ( CSR ).pptx
 
Value Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and painsValue Proposition canvas- Customer needs and pains
Value Proposition canvas- Customer needs and pains
 
Regression analysis: Simple Linear Regression Multiple Linear Regression
Regression analysis:  Simple Linear Regression Multiple Linear RegressionRegression analysis:  Simple Linear Regression Multiple Linear Regression
Regression analysis: Simple Linear Regression Multiple Linear Regression
 
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf0183760ssssssssssssssssssssssssssss00101011 (27).pdf
0183760ssssssssssssssssssssssssssss00101011 (27).pdf
 
Cracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptxCracking the Cultural Competence Code.pptx
Cracking the Cultural Competence Code.pptx
 
Call Girls in Gomti Nagar - 7388211116 - With room Service
Call Girls in Gomti Nagar - 7388211116  - With room ServiceCall Girls in Gomti Nagar - 7388211116  - With room Service
Call Girls in Gomti Nagar - 7388211116 - With room Service
 
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
Best VIP Call Girls Noida Sector 40 Call Me: 8448380779
 
Monte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSMMonte Carlo simulation : Simulation using MCSM
Monte Carlo simulation : Simulation using MCSM
 
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
FULL ENJOY Call Girls In Majnu Ka Tilla, Delhi Contact Us 8377877756
 
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒VIP Call Girls In Saharaganj ( Lucknow  ) 🔝 8923113531 🔝  Cash Payment (COD) 👒
VIP Call Girls In Saharaganj ( Lucknow ) 🔝 8923113531 🔝 Cash Payment (COD) 👒
 
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
👉Chandigarh Call Girls 👉9878799926👉Just Call👉Chandigarh Call Girl In Chandiga...
 
John Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdfJohn Halpern sued for sexual assault.pdf
John Halpern sued for sexual assault.pdf
 
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
VVVIP Call Girls In Greater Kailash ➡️ Delhi ➡️ 9999965857 🚀 No Advance 24HRS...
 
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
Call Girls In DLf Gurgaon ➥99902@11544 ( Best price)100% Genuine Escort In 24...
 
How to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League CityHow to Get Started in Social Media for Art League City
How to Get Started in Social Media for Art League City
 
7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...7.pdf This presentation captures many uses and the significance of the number...
7.pdf This presentation captures many uses and the significance of the number...
 

Eaton UPS Three phase family-gq_r8_lite

  • 1. Three-Phase UPS Solutions Contact: Douglas Stansfield Douglas.Stansfield@gmail.com © 2008 Eaton Corporation. All rights reserved.
  • 2. Powerware Series Three-Phase Product Lineup Covering 10-1100 kVA with single systems and providing paralleled capacity up to 8.8 MVA 2 2
  • 3. The Value of Eaton Eaton Three-Phase UPSs provide the greatest combination of benefits, delivering tangible benefits for specifying engineers, consultants and end users » Lowest Total Cost of Ownership industry-wide » Superior Performance and efficiency » Real-time Information and Control » World-class Support and Service Eaton 9390 3 3
  • 4. Low TCO Low TCO Improving the bottom line Eaton UPSs deliver low TCO from advances in several product facets » 400V Site Design » High Power Density – small system footprints » Reduced weight and transportation costs » Low installation and Leading Efficiency – Quantifiable Benefits » Maintenance » Scalability 4 4
  • 5. Low TCO – Leading Efficiency Two complementary Eaton-proprietary technologies, maximizing UPS efficiency under any condition! Variable Module Management System (VMMS) » Maximized efficiency in double conversion mode » Both in single- and multi-UPS systems applications Energy Saver Systems (ESS) » The ultimate savings: 99% efficiency » Automatic fast transfer to double conversion mode when needed (in less than 2 ms) Energy Advantage Architecture  Higher System Efficiency  No Compromise On Reliability 5 5
  • 6. Low TCO – Leading Efficiency Energy costs are overwhelming equipment costs in data centers. » UPS electrical losses account for 5-10% of the overall electrical expenditure.* Eaton’s Energy Saver System drives these losses down to nearly zero. The energy savings recovers the cost of the UPS in less than 5 years. * Underlying figures from The Invisible Crisis in the Data Center: The Economic Meltdown of Moore’s Law, Uptime Institute, 2007 6 6
  • 7. Low TCO – Leading Efficiency ESS Efficiency 99% – across the complete operating range 7 7
  • 8. Low TCO – Leading Efficiency The energy savings from ESS typically recovers 100% of the UPS cost over a 3-5 year period » At 250kW of critical load, the savings is equivalent to $4000 per year per point of efficiency gain. Backing up your 250kW load with an ESS UPS is equivalent to pulling 29 cars off the road. 8 8
  • 9. Low TCO – Leading Efficiency How to maximize efficiency with lighter loads in double conversion mode, especially in multi-UPS and redundant system configurations? Solution #1: Concentrate load on certain UPS’s to maximize UPS load level and overall system efficiency » Some energy savings • Limited to multiple-UPS systems (with several UPS in parallel) • Still not optimal Solution #2: Eaton 9395 and its Variable Module Management System » Automatically optimize efficiency at UPM level • Concentrate the load on certain UPM’s to maximize overall system efficiency » Only possible thanks to modularity of Eaton 9395 UPS • Not limited to multiple-UPS systems • Achieve even higher optimization thanks to UPM’s modularity 9 9
  • 10. Low TCO – Leading Efficiency Example with same load applied to different multi-UPS configurations 10 10
  • 11. 5 0 5 0 5 0 82 88 93 99 104 110 Low TCO – Leading Efficiency 0 77 5 71 0 66 9395 UPS Efficiency 5 60 0 55 Eaton 9395 1100kVA UPS 5 49 Eaton 9395 825kVA UPS Load kVA 0 44 9395 1100kVA with VMMS and N+0 configuration* 9395 550kVA Eaton 9395 550kVA UPS 9395 825kVA with VMMS and N+0 configuration* 5 38 Eaton 9395 275kVA UPS 0 33 VMMS allows to shift 5 27 to higher efficiency curves (according to (according to Typical Operations Range 0 22 system’s redundancy system’s redundancy requirements) requirements) 5 16 up to N+0 VMMS efficiency curve 0 11 9395 275kVA Notes: 9395 550kVA .5 55 - Scaled drawing 9395 825kVA 27 - VMMS and N+0 curves using VMMS default max 92 90 86 82 80 96 94 88 84 78 9395 1100kVA UPM % load level @ 80% (*) Efficiency % 9395 VMMS N+0 11 11
  • 12. Low TCO – 400V Site Design 480V AC » Losses through the UPS, isolation transformer/PDU, and server equipment » End-to-end efficiency of approximately 76% 12 12
  • 13. Low TCO – 400V Site Design 600V AC » Used primarily in Canada » Can provide small savings in equipment costs, and utilizes lower currents » Requires multiple isolation transformer-based PDUs » End-to-end efficiency of approximately 76% 13 13
  • 14. Low TCO – 400V Site Design 400V AC » Commonly used throughout the world » PDU isolation transformers eliminated » End-to-end efficiency of approximately 80% 14 14
  • 15. Low TCO – 400V Site Design $592k $689k $97k $7,027k $7,284k $257k $7,619k $7,973k $354k $6,072k $7,284k $1,212k $6,664k $7,973k $1,309k 15 15
  • 16. Low TCO – High Power Density Eaton three-phase UPSs offer 9390 IT the highest power density. The small footprint designs allows existing facilities to increase capacity without expensive building modifications, and allows new Competitor A Footprint construction to maximize revenue generating floor space vs. support space. Competitor B Footprint 16 16
  • 17. Low TCO – Reduced Weight and Transportation Costs The Eaton 9395 UPS » Lighter weight results in about 20% carbon reduction due to transportation » 15 tons of CO2 emissions are saved every 100 MVA worth of data center UPS is shipped 500 miles, compared to legacy equipment » Lowest energy required for production (50%-80% reduction compared to legacy equipment) » Up to 50% reduction in required floor space » Reduction of hazardous materials 17 17
  • 18. Low TCO – Reduced Weight and Transportation Costs CROSS DENSITY FOOTPRINT DIMENSIONS COUNTRY MANUFACTURER kVA (kW per ft ) 2 WEIGHT (ft ) 2 (W x D x H, in.) FREIGHT COST Eaton 9395 550 29.6 2977 16.7 73.6 x 32.7 x 73.7 $893 COMPETITOR A 500 24.1 6900 18.7 69.0 x 39.0 x 82.0 $2,070 COMPETITOR B 500 24.0 5226 18.8 80.7 x 33.5 x 76.7 $1,568 COMPETITOR C 500 23.9 5512 20.9 94.0 x 32.0 x 71.0 $1,654 COMPETITOR D 500 23.1 5795 19.5 72.0 x 39.0 x 78.0 $1,739 COMPETITOR E 600 20.6 6373 29.1 99.8 x 42.0 x 80.0 $1,912 COMPETITOR F 500 15.1 6930 29.9 114.2 x 37.7 x 79.7 $2,079 » Freight Savings: Half the freight cost » Fits through all doors, freight elevators, no dismantling, no need for crane rental » Easier handling, eliminates most floor loading concerns 18 18
  • 19. Low TCO – Reduced Installation and Maintenance Costs Traditional multi-module installations involve 3 times the connections for inter-unit power and communications cabling SBM 225 kVA + 225 kVA + or Tie The 9395 is a completely integrated large system. Everything is pre-wired and fully front-accessible with top or bottom cable entry standard. SIGNIFICANT SAVINGS IN CABLING AND INSTALLATION TIME 19 19
  • 20. Low TCO – Scalability “Inside the Box” – Single Module Upgradeability “Outside the Box” – Multi-Module Systems » Parallel for redundancy or capacity » Individual battery support removes a single-point-of-failure possibility Powerware® Hot Sync Paralleling Technology » Eliminates a single point of failure opportunity » Peer-to-peer paralleling without wires » Eliminates BUNDLES of inter-cabling » Easy to parallel units » Firmware setting changes » Hot Sync CAN bridge Card 20 20
  • 21. Superior Performance Superior performance is crucial to your business Eaton uses advanced systems and redundancy to ensure maximum uptime even when parts fail and systems malfunction » Redundancy » Superior battery management » Hot Sync paralleling 21 21
  • 22. Consistent Reliability – Redundancy Data center efficiency ISBM UPM 1 UPM 2 REDUNDANT UPMs surveys reveal that UPSs are often under loaded at 50% or lower. End users purchasing a 9395 with more than INTEGRATED one UPM can choose SBM (ISBM) the inherent redundancy option. Anytime the load is below 50% capacity, it is automatically redundant. » No other UPS manufacturer can offer this additional value to customers without adding a costly second UPS system. » It may be the single most important feature that saves the customer from dropping their load. 22 22
  • 23. Consistent Reliability – Superior Battery Management Conventional knowledge says that batteries must be subjected to continual float charging to maintain backup time and health of the batteries. Eaton engineers questioned this concept because: » Data shows that most VRLA batteries designed with a 10-year useful life are replaced every 4-5 years. » Float charging a battery accelerates positive grid corrosion of the lead plates reducing service life. » Float charging causes extra heat within the battery system, as compared to a cyclical charging system. And everyone knows that heat is a major factor in battery life. 23 23
  • 24. Consistent Reliability – Superior Battery Management ABM consists of three operating modes: » Charge Mode » Rest Mode » Test Mode The UPS enters Charge mode under any What if the battery is called upon to of the following conditions: support a load when the UPS is near the end of its rest mode? » Whenever the UPS is commanded to turn on Using a 15 minute battery as an example, the » After any Utility power outage lasting battery would provide all but 30 seconds of its longer than 15 seconds 15 minute backup time. This is proportionally » Whenever the battery is replaced (or the true for other battery sizes. battery breaker is opened and re-closed) 24 24
  • 25. Consistent Reliability – Superior Battery Management 25 25
  • 26. Consistent Reliability – Hot Sync No “single-point” failure » Units synchronize to Utility or load bus independently » Units load share within 5% independently » Units “selective trip” instantaneously » All without depending on inter module wiring! Accomplished without “Master/Slave” configuration » No Master “sync” or “load control signal” needed » Enhanced Reliability and Simpler installation » Easier and Quicker to troubleshoot » Tie cabinet (ISBM) is simple/reliable in concept and in implementation 26 26
  • 27. Real-time Information and Control Real-time Information and Control Keeping data centers and facilities online requires real-time information and control capabilities. Eaton UPSs offer flexible options to interface with multiple systems and give customers the best control. 27 27
  • 28. Real-time Information and Control Eaton Three-phase UPSs offer a variety of connectivity cards to provide custom information and control options to end-users » Web/SNMP » Modbus » AS400 relays » Serial port » Industrial Relay Card » Environmental monitoring probe » Hot Sync CAN Bridge Card 28 28
  • 29. Real-time Information and Control – PowerXpert 29 29
  • 30. Real-time Information and Control – ConnectUPS ConnectUPS Web Interface 30 30
  • 31. Real-time Information and Control – IPM/IPP Intelligent Power Manager software for monitoring » Monitor and manage multiple power devices across the network from any PC with an Internet browser » Compatible with VMware’s vCenter™ Server • View your power and network devices from the same vCenter dashboard • During a power event, the software triggers vMotion™ to transparently move virtual machines to an available server on the network for zero downtime Intelligent Power Protector software for shutdown » Gracefully shuts down computers and virtual machines/servers (powered by an Eaton UPS) during a power outage that lasts longer than the available battery runtime Download from the Power Quality website: www.eaton.com/intelligentpower 31 31
  • 32. Real-time Information and Control – eNotify MONITORED UPS CUSTOMER CONNECTIVITY MONITORING SERVICE DELIVERY AND BATTERY CENTER Equipment Connectivity Back Office (CMC) Service Delivery • Eaton 3-phase UPS • Web/SNMP card via • Monitors more than 1,500 • National coverage — (9395, 9390, 9315, 9315 customer-supplied UPS systems 240 field technicians in SBM, 9355, 9330, e-mail server connection • Collects, stores & trends US and Canada BladeUPS) • Daily outbound-only data • 24x7 coverage with • Eaton 1-phase UPS heartbeat e-mail from • Uses anomaly detection 4-hour response in top (9140, 9155, 9120, 9125, UPS to CRC for secure system to proactively 50 markets 9130, 9135, 9170+) connectivity identify & act on potential • Remote repair/ • 48 alarm events, • No remote control load-loss events diagnostics expedites 11 critical alarms capability • Customers can receive delivery monthly reports, real-time notification, & call CMC 7x24 with questions 32 32
  • 33. Support and Service Support and Service Eaton UPSs are a long-term investment, with the ability to have a service life of 20 years or more! That’s why we have a dedicated support and service team to assist customers with routine maintenance and questions to keep your investment running smoothly. 33 33
  • 34. Why Customers Buy Eaton Service » Service technician’s expert knowledge of Eaton products » Deal direct with the factory » Quick response by having 240+ field technicians » 24x7x365 emergency access for service contract customers to technical support and on-site technician » Safety – our technicians are trained and equipped to work within the latest OSHA and NFPA safety guidelines » Access to field parts inventory maintained by technician » Increased reliability – experienced technician with factory training, technical support resources, focused on a specific manufacturer’s product Source: Hahn Consulting UPS VOC Needs Assessments, 2002-2006, based on Eaton UPS 3P customer phone and personal interviews 34 34
  • 35. Eaton Service Numbers » Average number of emergencies successfully responded to annually >5,000 » Average speed of answering phone calls = 16 seconds » FirstTime Fix = 75% (2010) » Average tenure of Eaton field technician employees = 10.2 years » Number of Preventive Maintenance visits completed annually = >30,000 » Number of factory training hours in 2009 for Eaton field technicians = 12,480 hours » Training time for a new Eaton field technician = minimum of 16 weeks classroom/lab training, and up to one year of mentoring in the field » Overall Customer Satisfaction = 99% (2009) Source: Hahn Consulting UPS VOC Needs Assessments, 2002-2006, based on Eaton UPS 3P customer phone and personal interviews 35 35
  • 36. Field Technician Coverage – US & Canada 36 36
  • 37. Field Technician Coverage – Global Reach 37 37
  • 38. Sections 9x55 9390 9395 Success Stories 38 38
  • 39. 9X55 – Overview Product Snapshot Power Rating: 8-30 kVA Topology: Double-Conversion On-line Input Power Factor: >0.99 at full load Output Power Factor: 0.9 pf Input/Output Voltage: 208/208 or 220/220 input 120/208/240 Split Phase (9155) 480/208 or 600/208 w/ xfmr Frequency: 50/60 Hz selectable, auto-configuring Configuration: Tower 39 39
  • 40. 9X55 – Low Total Cost of Ownership 15 kVa Comparison 20 kVa Comparison Battery Runtime = 5 Minutes Battery Runtime = 18 Minutes Footprint = 408 Square Inches Footprint = 680 Square Inches Competitor C 15 kVA Competitor C 20 kVA Battery Runtime = 5 Minutes Battery Runtime = 5 Minutes Footprint = 1320 Square Inches Footprint = 1320 Square Inches At 15 kVA, the 9355 occupies At 20 kVA, the 9355 occupies 70 percent less footprint 48 percent less footprint and delivers over three times the battery runtime 40 40
  • 41. 9X55 – Low Total Cost of Ownership 10 & 15 kVA Dimensions Runtime (min) Footprint Configurations (inches) (square 10 kVA 15 kVA Product W D H inches) 75% 9355 12 34 32 408 9 5 smaller footprint! Competitor A 21 33 59 693 9 5 Competitor B 24 36 82 864 9 5 Competitor C 33 40 63 1320 9 5 Competitor D 36 20 35 720 9 5 13% Competitor E 24 33 64 792 9 5 more capacity! 20 & 30 kVA Dimensions Dimensions Footprint Configurations (inches) (inches) (square Product W D H inches) 20 kVA 30 kVA Up to 350% 9355 20 34 66 680 18 11 more Competitor A 21 33 59 693 5 5 runtime! Competitor B 24 36 82 864 5 5 Competitor C 33 40 63 1320 5 5 Competitor D 36 20 35 720 5 5 Competitor E 24 33 64 792 5 5 41 41
  • 42. 9X55 – Unique Product Features Integrated Power Distribution Modules provide customized distribution and connectivity 42 42
  • 43. 9X55 – Power Distribution » Factory Installed on-board Power Distribution Modules » PDM is equipped with circuit breakers, terminal block, and configurable output plugs » Maximum of 4 panels per PDM » The combined quantities of single locking receptacle panels (shown with an *) must not exceed 4 per PDM » PDM is ordered using 4 dedicated digits in the UPS CTO number. » PDM ships attached to the UPS PDM Panels: (2) 5-15R (2) 5-20R UL (2) 5-20R CSA (2) 6-15R (2) 6-20R (2) L5-15R (1) L5-20R* (1) L5-30R* (2) L6-15R (1) L6-20R* (1) L6-30R* (1) L14-20R* (1) L14-30R* (1) L21-20R (1) L21-30R IEC 320 C13 and C19 panels available (120V) 43 43
  • 44. 9X55 – Power Distribution The 9355’s on-board power distribution module is compatible with Eaton’s optional rack power modules (RPM) and enclosure power distribution units (ePDU™), providing maximum flexibility in distributing power throughout the facility or data center. Easier, Less Complex, and More Cost-Effective End-of-Row Solution for Price Sensitive Customer! Enabling Plug-and-Play Power Distribution Eaton RPMs and ePDUs simplify power distribution by reducing the number of cables to manage and distribution points to monitor Back To Main 44 44
  • 45. 9390 – Overview Product Snapshot Power Rating: 20-160 kVA Topology: Double-Conversion On-line Input Power Factor: >0.99 at full load Output Power Factor: 0.9 pf Input/Output Voltage: 208/208, 400/400, 480/480, 480/208, 600/600, 600/208 Frequency: 50/60 Hz selectable, auto-configuring Battery Types: VRLA, AGM, Gel, Wet Configuration: Tower 40 kVA 9390IT 20-80 kVA 100-160 kVA 45 45
  • 46. 9390 – Low Total Cost of Ownership Energy Saver System 46 46
  • 47. 9390IT – Low Total Cost of Ownership Dimensions Footprint (inches) (square inches) Product W D H 61% 9390IT 28 31 74 865 smaller Competitor A 59 38 79 2238 footprint! Competitor B 60 36 72 2136 13% more capacity! 47 47
  • 48. 9390 – Unique Product Features » Optional Integrated Batteries (9390IT) » Full compliment of Line & Match distribution cabinets (Pisano’s Grand Statement Here) » Serviceable design 48 48
  • 49. 9390 – Unique Product Features Line and Match system accessory cabinets » Use the most economical option (space and cost) to meet your site requirements. No other manufacturer offers the flexiblity of the Eaton 9390 line of accessory cabinets. IBC IAC IDC 49 49
  • 50. IAC 9390 IAC cabinet is available in three configurations » Maintenance Bypass » Parallel Tie » 42 Pole Distribution Maintenance Bypass Tie Distribution 50 50
  • 51. IDC Integrated Distribution Cabinet Incorporates any or all of three functionalities within a single cabinet » Maintenance Bypass » Step Down Transformer » Power Distribution • With (2) 42 pole load centers • With (1 to 6) distribution breakers • With (1) 42 pole panel and • (1-3) 225A SFBs 51 51
  • 52. 9390 IBC Variable battery bus configurations » 384VDC – 480VDC » (192 – 240 cells) » Virtually limitless runtime possibilities » Size batteries based on runtime, or » Size batteries based on lowest cost 0.8 and 0.9pf runtime Charts for sizing kVA upgrade support IBC-S » Up to 16 minutes @ 40kVA » Up to 7 minutes @ 80kVA IBC-L » 10 minutes to several hours… IBC-S IBC-L 570mm/22.5” WIDE 1085mm/42.7” WIDE 52 52
  • 53. Serviceability 100% Front Access » Fast, easy access » Unit can be backed up against wall or into a corner » No clearance needed at rear or sides Fast repair and return to service Mean time to repair (MTTR) less than 30 minutes » Power modules are field-replaceable units » Fan tray is a field-replaceable unit » Slide in/out design 9390 provides the best serviceability 53 53
  • 54. Serviceable Design (40/80kVA) Top cable entry area X-Slot communication bays Replaceable converter/inverter System Control modules and interface boards Redundant power supplies Slide out fan tray Input/Output connections DC connections Modular static switch assembly Bottom Back To cable entry area Main 54 54
  • 55. 9395 – Overview Product Snapshot Power Rating: 225-1100 kVA Topology: Double-Conversion On-line Input Power Factor: >0.99 at full load Output Power Factor: 0.9 pf Input/Output Voltage: 400/400, 480/480, 480/208 Frequency: 50/60 Hz selectable, auto-configuring Battery Types: VRLA, AGM, Gel, Wet Configuration: Tower 55 55
  • 56. 9395 – Low Total Cost of Ownership Energy Saver System 56 56
  • 57. 9395 – Footprint CROSS DENSITY FOOTPRINT DIMENSIONS COUNTRY MANUFACTURER kVA (kW per ft ) 2 WEIGHT (ft ) 2 (W x D x H, in.) FREIGHT COST Eaton 9395 550 29.6 2977 16.7 73.6 x 32.7 x 73.7 $893 COMPETITOR A 500 24.1 6900 18.7 69.0 x 39.0 x 82.0 $2,070 COMPETITOR B 500 24.0 5226 18.8 80.7 x 33.5 x 76.7 $1,568 COMPETITOR C 500 23.9 5512 20.9 94.0 x 32.0 x 71.0 $1,654 COMPETITOR D 500 23.1 5795 19.5 72.0 x 39.0 x 78.0 $1,739 COMPETITOR E 600 20.6 6373 29.1 99.8 x 42.0 x 80.0 $1,912 COMPETITOR F 500 15.1 6930 29.9 114.2 x 37.7 x 79.7 $2,079 57 57
  • 58. 9395 – Unique Product Features » VMMS » SMaRT Certification » Inherent Redundancy » Easy Capacity Test » Concurrent Maintenance » Flexible/Scalable/Upgradeable 58 58
  • 59. VMMS Principle Example With Same Load Applied To Different Multi-UPS Configurations 59 59
  • 60. VMMS Applications VMMS can be used in all multi-module (multiple-UPM) 9395 systems » Single 9395 units from 550kVA to 1100kVA » Distributed parallel systems SBM Systems Typical Applications Where VMMS Particularly Efficient » Redundant N+1 and 2N systems UPS’s • Lightly loaded: typically operate at loads < 45% load level where efficiency is not optimal » Data Centers, especially when UPS system feeds dual corded servers » Any applications when load is not constant 60 60
  • 61. SMaRT Certification The SMaRT Gold certified 9395 can contribute to points in two LEED Credit Categories for buildings and projects seeking certification. 61 61
  • 62. Inherent Redundancy Option Next Generation Reliability Data center efficiency surveys reveal that UPSs are often under loaded at 50% or lower. End users purchasing a Eaton 9395 with more than one UPM can use the inherent redundancy capability. Anytime the load is below 50% capacity, it is automatically redundant. » No other UPS manufacturer can offer this additional value to customers without adding a costly second UPS system » It may be the single most important feature that saves the customer from dropping their load 62 62
  • 63. Easy Capacity Load Testing The Eaton 9395 leverages an enhanced startup and commissioning offering exclusive to Eaton field technicians. It can take the place of some traditional load bank tests to save customers time and money during startup and commissioning. This load test ensures validation of performance of an installed UPS and can simulate various operations and power transfers. » No load banks to rent » No load connections needed » No wasted energy LOAD TEST CAPABILITY SAVES CUSTOMERS TIME AND MONEY 63 63
  • 64. Easy Capacity Load Testing An Eaton field technician applies full load, tests & calibrates: Rectifier RIB Inverter Static bypass switch Battery – with option to perform Fuses No Output full battery discharge test Contactors Connection & BIB Conductors Load Bank Needed ADDITIONAL THERMAL IMAGING TESTS ARE POSSIBLE ON UPS, INPUT CABLES AND SWITCHGEAR 64 64
  • 65. Easy Capacity Load Testing Easy Redundancy Test: » Eaton field technician can disable one UPM to demonstrate redundancy » Alternately loads each UPM to capacity in redundant systems X EASY SERVICE DISCONNECT FEATURE MAKES IT SIMPLE TO ISOLATE UPMS 65 65
  • 66. Flexible, Scalable, Upgradeable On-site On-site upgrade 275 kVA Redundant! upgrade 550 kVA Redundant! Add another 275 kVA in the field for redundancy, or for capacity » Simply choose an ISBM sized for future growth » Leave space on the left side Enables flexibility for future changes in load demands, and new requirements for higher reliability 66 66
  • 67. Concurrent Maintenance With the N+1 redundant designs of Powerware Hot Sync Technology (including units with the inherent redundancy option), you can completely isolate and service a redundant module, while the other module carries the load…no need to go to bypass for service “…high-availability cannot be achieved without considering the concurrent maintainability and the fault-tolerance of the underlying infrastructure” The Uptime Institute Back To CONCURRENT MAINTENANCE = HIGHER AVAILABILITY Main 67 67
  • 68. Success Stories Success Stories our strongest advocates…customers 68 68
  • 69. Our Customers: Collier County Eaton 9355 and 9390 UPS, eNotify and Service “They’re on the spot 24x7 if I need them. Whether I need to change a phone number in their system or have a question on a unit, they are very responsive.” David Holmes, Senior Facilities Management Department 69 69
  • 70. Our Customers: Miami Dolphins Eaton 9390 UPS “Just last week we lost power for about 20 seconds at the training facility. If you were standing inside the data center, you'd never have known.” Joe Curbelo, Director of Infrastructure Services 70 70
  • 71. Our Customers: Indianapolis Motor Speedway Productions Eaton 9355 UPS “We have the peace of mind that we won't lose data and that our data won't get corrupted... It allows all of our servers to keep on humming without interruption.” Scott Burgett, Maintenance Engineer 71 71
  • 72. Our Customers: CoSentry 9395 UPS with Energy Saver System “Competitive offerings with a track record didn’t exist—at least not for a modular UPS of this size. This application afforded the purchase of one UPS, so we were obviously delighted to find that we could purchase redundancy—effectively two for the price of one!” Kevin Dorhmann, Chief Technology Officer 72 72
  • 73. Our Customers: BMW Sauber Eaton 9395 UPS Hinwil, Switzerland With the 9395, BMW Sauber saves roughly one-fourth of the energy used by comparable systems. 73 73
  • 74. Our Customers: Southwest Airlines Eaton 9355, 9315 and Powerware Plus 750 UPS; PowerTrust Service Plans “Gary Rose and Jason Renshaw know me and I know them. I don’t have to worry when they come on-site. They know my building. They know my loads. And they know how critical it is.” Steve Hurst, Project Leader 74 74
  • 75. Our Customers: NetRiver Eaton 9395 UPS with Energy Saver System “That’s huge, because traditional UPSs are terrible in terms of efficiency. It’s like going to those places in the mall where you put your change in and get only part of it back. With this Eaton UPS, it’s like putting 100 pennies in and you get 99 cents back. Because we use billions of pennies, so to speak, it really adds up.” Adam Vierra, Sales and Marketing Manager 75 75
  • 76. Our Customers: American Kennel Club Eaton 9390 UPS “We wanted to know that we could buy something appropriate for our current needs but not have to throw it out and replace it if our power needs changed in the future.” Charles Kneifel, Chief Information Officer 76 76
  • 77. Our Customers: NextEnergy 9395 UPS “The nice thing about the 9395 is that a lot of the features that we needed developed were already there in some format.” Max Dorflinger, Director of Program Delivery 77 77
  • 78. Our Customers: U.S. Navy Tactical Training Group Pacific 9395 UPS “The Navy doesn’t want to put in something that’s not energy efficient. Everyone is trying to save money these days, and energy efficiency is an important part of that. Without a reliable UPS, if we had a power outage, training would go down for the entire west coast— or beyond.” Tom Hurst, Facilities Manager 78 78
  • 79. Our Customers: Washington Department of Ecology 9395 UPS “We are fully confident that the unit will handle everything we’re asking of it. The technician put it through extensive testing at the startup,” noting that assessments ranged from automatic transfer scenarios to load bank tests. “We know it’s going to hold the load.” Steve Strope, Facility Manager 79 79
  • 80. Our Customers: UNC Pembroke PowerTrust Service Plan with 9355 UPS Field Tech: David Horrell “In David, we have a technician who is as reliable as our Eaton UPS,” Barry Graves says. “The performance of our systems is critical, so we can’t settle for anything less.” 80 80
  • 81. Our Customers: Royal Caribbean Oasis of the Seas 20 UPS from 1 to 350 kVA 9395, 9390, 9355 and 9155 Marine UPS “We have worked with Eaton for over 10 years in all of our most demanding cruise ship construction projects,” says System Coordinator Ville Talsi of shipbuilding group STX Europe, Turku, Finland. “Their high quality products and field services around the world have guaranteed an enjoyable cruise experience for passengers and uninterrupted working for the sophisticated technology on board our ships.” Back To Main 81 81
  • 82. 82 82

Editor's Notes

  1. Okay – so what does all this mean for you? Cash to your bottom line! Dave mentioned earlier that deploying ESS is like getting Notes: Payback is for the UPS alone. It does not include batteries or accessories. $0.11 is a combined energy and kW demand number for simplification. It’s equivalent to $.10 per kW-hr and $7.20 of kW demand with even loading throughout the month. Usually, kW demand is calculated based on a peak window (such as highest 15 minutes during the month), resulting in charges that are higher. As Feb 2009 (latest month from which the data is available) Industrial ¢ 10.15 per kW-hr Commercial ¢6.98 per kW-hr Source: Energy Information Administration (http://www.eia.doe.gov/cneaf/electricity/epm/flash/flash.html) Other things to be aware of: @ 250kW the savings can also be expressed as a little over $4k per year per percentage point gain in efficiency. $74k per year divided by 3 is $24k per year. $24k per year divided by 6 points of efficiency gain is $4k per point @ 120kW the savings can also be expressed as a little over $2k per year per percentage point gain in efficiency. Assumptions not shown: Cooling load factor 0.7 of critical load Environmental data comes from the EPA’s Greenhouse Gas Equivalencies Calculator: http://www.epa.gov/solar/energy-resources/calculator.htm