Demonstration Thermography Report




Company    Testo Ltd                        Tester:

           Newman Lane                      Andy McGrath - Testo
           Alton, Hampshire, GU34 2QJ       Phone:      01420 544433
                                            E-Mail:     info @testo.co.uk


Device     Testo 882                        Serial No.: 01790945
                                            Lens:       Std 32 degree Wide Angle
                                                        Lens


Customer   Demonstration Thermography       Measuring Site:
           Report
                                            Demonstration Thermography Report
           Detached Property
                                            Thermal Survey of Detached Property
           UK

                                            Measuring Date: 4th October 2010


Task       Demonstration Thermography Report to highlight the capabilities of the
           Testo 882 series Thermal Imaging cameras and IR software .




                                Page 1/20
Demonstration Thermography Report

File:                                                  Date:                                 Measuring Time:
IV_00039.BMT                                         20/10/2010                                     07:48:01




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
These images provide an overall exterior view of the property.
These images are for the purpose of identification of the property for the first page of the Thermography
Report.
Thermal image displayed in " Iron " Palette.




                                                  Page 2/20
Demonstration Thermography Report

File:                                                  Date:                                Measuring Time:
IV_00001.BMT                                         20/10/2010                                    07:20:38




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects           Temp. [°C]     Emiss.      Refl. temp. [°C]   Remarks
Measure point 1                 20.1          0.95              20.0        -
Measure point 2                 17.8          0.95              20.0        -
Measure point 3                 20.3          0.95              20.0        -
Cold spot 1                      7.5          0.95              20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
Images of the interior of the Front Door, which is a Double Glazed PVC Door.
The thermal image highlights the ingress of cold air through the seals of the door, where the door should be
sealed to the frame.
It highlights that cold air is passing through both the left hand and right hand lower sections of the door.
A Temperature Profile Line Graph has been added to the image to highlight the temperature variation beteen
the walls, door and the area where the seals are leaking. Cold air ingress can also be seen tthrough the letter
box.
Spot temperature markers have been added to show the temperature variation.
The Auto Cold Spot Indicator has been applied and is indicating (CS1), that at the coldest point, the Apparent
Temperature is approx 7 degrees C colder in comparison to the wall temperatures of approx 19/20 degrees
C.
Thermal image displayed in " Iron " Palette


                                                 Page 3/20
Demonstration Thermography Report

File:                                                  Date:                                Measuring Time:
IV_00002.BMT                                         20/10/2010                                    07:21:09




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects           Temp. [°C]     Emiss.      Refl. temp. [°C]   Remarks
Measure point 1                 19.7          0.95              20.0        -
Measure point 2                 17.5          0.95              20.0        -
Measure point 3                 14.6          0.95              20.0        -
Measure point 4                 19.6          0.95              20.0        -
Cold spot 1                      7.2          0.95              20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
Images of the interior of the Front Door, which is a Double Glazed PVC Door. The thermal image highlights
the ingress of cold air through the seals of the door, where the door should be sealed to the frame. It
highlights that cold air is passing through both the left hand and right hand lower sections of the door.
A Temperature Profile Line Graph has been added to the image to highlight the temperature variation beteen
the walls, door and the area where the seals are leaking. Cold air ingress can also be seen tthrough the letter
box.
Spot temperature markers have been added to show the temperature variation.
The Auto Cold Spot Indicator has been applied and is indicating (CS1), that at the coldest point, the Apparent
Temperature is approx 7 degrees C colder in comparison to the wall temperatures of approx 19/20 degrees
C.
Thermal image displayed in " Iron " Palette


                                                 Page 4/20
Demonstration Thermography Report

File:                                                  Date:                                 Measuring Time:
IV_00004.BMT                                         20/10/2010                                     07:23:41




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects           Temp. [°C]     Emiss.      Refl. temp. [°C]    Remarks
Measure point 1                 20.0          0.95              20.0         -
Measure point 2                 19.0          0.95              20.0         -
Measure point 3                 19.1          0.95              20.0         -
Measure point 4                 20.2          0.95              20.0         -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
The images are of the Fireplace / Chimney Breast in the Lounge and the adjacent wall which is an exterior
wall.
The house has cavity wall insulation but this is not applied in the chimney breast area and therefore Cold air
ingress can be seen in the area around the fireplace in comparison to the areas of the wall where there are
cavity walls and insulation has been applied.
A Temperature Profile Line Graph has been added to the image to highlight the temperature variation
between the walls and the area around the fireplace.
Spot temperature markers have been added to show the temperature variation.
Thermal image displayed in " Iron " Palette




                                                  Page 5/20
Demonstration Thermography Report

File:                                                Date:                               Measuring Time:
IV_00007.BMT                                       20/10/2010                                   07:25:06




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Picture markings:
Measurement Objects          Temp. [°C]     Emiss.     Refl. temp. [°C]   Remarks
Measure point 1                16.6          0.95             20.0        -
Measure point 2                20.3          0.95             20.0        -
Measure point 3                21.1          0.95             20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
Thermal image displayed in " Iron " Palette
Images of Lounge Window and external wall showing temperature variation between Double Glazed window,
Cavity Insulated external wall and internal wall.
Thermal image displayed in " Iron " Palette.




                                                Page 6/20
Demonstration Thermography Report

File:                                                  Date:                                 Measuring Time:
IV_00012.BMT                                         20/10/2010                                     07:28:40




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
Images show Cold Air ingress around the base of a kitchen cupboard.
It was found that the Soil Stack/Down Pipe from the upstairs bathroom ran behind this cupboard into the
ground and cold air was entering the property in this area and escaping out under the cupboards plinth.
Thermal image displayed in " Iron " Palette.




                                                  Page 7/20
Demonstration Thermography Report

File:                                                  Date:                                 Measuring Time:
IV_00014.BMT                                         20/10/2010                                     07:30:20




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects           Temp. [°C]     Emiss.      Refl. temp. [°C]   Remarks
Measure point 1                 19.9          0.95              20.0        -
Measure point 2                 17.1          0.95              20.0        -
Measure point 3                 19.3          0.95              20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
Thermal image displayed in " Iron " Palette.




                                                  Page 8/20
Demonstration Thermography Report

File:                                                 Date:                                Measuring Time:
IV_00019.BMT                                        20/10/2010                                    07:32:29




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Picture markings:
Measurement Objects          Temp. [°C]     Emiss.      Refl. temp. [°C]   Remarks
Measure point 1                21.3          0.95              20.0        -
Measure point 2                17.1          0.95              20.0        -
Measure point 3                20.7          0.95              20.0        -
Cold spot 1                    16.5          0.95              20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
The images are of the En-suite bathroom ceiling and highlight cold patches in the ceiling, around the
Downlight and Extractor Fan Vent.
Further investigation (refer to images 83, 85, 86 & 87), showed that the loft insulation had been removed
from these ceiling areas when the bathroom was altered and the downlights and extract fan vent were fitted.
This highlights the difference in areas where the loft insulation is fitted and where it is now missing, thus
allowing cold ingress into the bathroom.
With the Spot temperature markers and the Auto Cold Spot Indicator, a temperature differential of approx 4/5
degrees can be seen across the ceiling.
Thermal image displayed in " Iron " Palette.




                                                 Page 9/20
Demonstration Thermography Report

File:                                                 Date:                                 Measuring Time:
IV_00023.BMT                                        20/10/2010                                     07:34:36




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Picture markings:
Measurement Objects          Temp. [°C]      Emiss.      Refl. temp. [°C]   Remarks
Measure point 1                20.3           0.95              20.0        -
Measure point 2                20.4           0.95              20.0        -
Measure point 3                15.5           0.95              20.0        -
Cold spot 1                    14.7           0.95              20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
The images are of the bedroom ceiling and highlight a large cold patch in the corner of the ceiling.
Further investigation showed that loft insulation had not been fitted in this area of the loft as it was under
some boarding, refer to images 83, 85, 86 & 87.This highlights the difference in areas where the loft
insulation is fitted and where it is missing, thus allowing cold ingress into the bedroom.
With the Spot temperature markers and the Auto Cold Spot Indicator, a temperature differential of approx 4/5
degrees can be seen across this section of the ceiling.
Thermal image displayed in " Iron " Palette




                                                 Page 10/20
Demonstration Thermography Report

File:                                                 Date:                                 Measuring Time:
IV_00028.BMT                                        20/10/2010                                     07:37:55




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Picture markings:
Measurement Objects          Temp. [°C]      Emiss.      Refl. temp. [°C]   Remarks
Measure point 1                21.0           0.95              20.0        -
Measure point 2                21.1           0.95              20.0        -
Measure point 3                18.2           0.95              20.0        -
Measure point 4                17.2           0.95              20.0        -
Cold spot 1                    16.5           0.95              20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
The images are of the landing ceiling area and highlight a number of large cold patches across the ceiling.
Further investigation showed that loft insulation had not been fitted in this area of the loft as it was under
some boarding.This highlights the difference in areas where the loft insulation is fitted and where it is
missing, thus allowing cold ingress into the bedroom.
With the Spot temperature markers and the Auto Cold Spot Indicator, a temperature differential of approx 4/5
degrees can be seen across this section of the ceiling.
Thermal image displayed in " Iron " Palette.




                                                 Page 11/20
Demonstration Thermography Report

File:                                                 Date:                                 Measuring Time:
IV_00083.BMT                                        20/10/2010                                     19:26:46




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Picture markings:
Measurement Objects              Temp. [°C]     Emiss.       Refl. temp. [°C] Remarks
Measure point 1                      12.7        0.95               20.0        -
Measure point 2                       9.7        0.95               20.0        -
Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and En-suite Bathroom
ceilings, this image is of the loft area and shows/verifies the missing loft insulation which was the cause of
the cold areas and was highlighted in the previous images.
This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring
from those rooms can be seen in the areas where there is no loft insulation.
These images confirm the thermal benefit of loft insulation.
Thermal image displayed in " Iron " Palette




                                                 Page 12/20
Demonstration Thermography Report

File:                                                 Date:                                Measuring Time:
IV_00085.BMT                                        20/10/2010                                    19:27:32




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and bathroom ceilings,
this image is of the loft area and shows/verifies the missing loft insulation which was the cause of the cold
areas and was highlighted in the previous images.
This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring
from those rooms can be seen in the areas where there is no loft insulation.
These images confirm the thermal benefit of loft insulation.
Thermal image displayed in "Blue / Red " Palette




                                                 Page 13/20
Demonstration Thermography Report

File:                                                 Date:                                Measuring Time:
IV_00086.BMT                                        20/10/2010                                    19:28:09




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and bathroom ceilings,
this image is of the loft area and shows/verifies the missing loft insulation which was the cause of the cold
areas and was highlighted in the previous images.
This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring
from those rooms can be seen in the areas where there is no loft insulation.
These images confirm the thermal benefit of loft insulation.
Thermal image displayed in " Iron " Palette




                                                 Page 14/20
Demonstration Thermography Report

File:                                                 Date:                                Measuring Time:
IV_00087.BMT                                        20/10/2010                                    19:28:20




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and bathroom ceilings,
this image is of the loft area and shows/verifies the missing loft insulation which was the cause of the cold
areas and was highlighted in the previous images.
This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring
from those rooms can be seen in the areas where there is no loft insulation.
These images confirm the thermal benefit of loft insulation.
Thermal image displayed in "Blue / Red " Palette




                                                 Page 15/20
Demonstration Thermography Report

File:                                                Date:                               Measuring Time:
IV_00025.BMT                                       20/10/2010                                   07:36:22




Picture parameters:
Emissivity:                     0.95
Refl. temp. [°C]:               20.0


Picture markings:
Measurement Objects          Temp. [°C]     Emiss.     Refl. temp. [°C]   Remarks
Measure point 1                21.2          0.95             20.0        -
Measure point 2                17.9          0.95             20.0        -
Measure point 3                20.9          0.95             20.0        -
Cold spot 1                    12.9          0.95             20.0        -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
The images are of the loft hatch which has a sealing arrangement but the Thermal image shows how there is
still some cold air ingress past the seals.
With the Spot temperature markers and the Auto Cold Spot Indicator, a significant temperature differential
can be seen across the loft hatch seals.
Thermal image displayed in " Iron " Palette




                                                Page 16/20
Demonstration Thermography Report

File:                                                  Date:                                  Measuring Time:
IV_00030.BMT                                         20/10/2010                                      07:38:37




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects           Temp. [°C]      Emiss.      Refl. temp. [°C]    Remarks
Measure point 1                 18.9           0.95              20.0         -
Measure point 2                 20.8           0.95              20.0         -
Measure point 3                 21.8           0.95              20.0         -



Profile line:




Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
The images are of the bathroom exterior and internal walls. The thermal image highlights the temperature
variation between the walls. The external wall has cavity wall insulation installed although there is a large
cold area (M1) where there is more cold air ingress compared to the majority of the wall.
Further investigation would be required to verify the existance of cavity wall insulation in this area.
Thermal image displayed in " Iron " Palette.




                                                  Page 17/20
Demonstration Thermography Report

File:                                                  Date:                                  Measuring Time:
IV_00040.BMT                                         20/10/2010                                      07:48:15




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects             Temp. [°C]    Emiss.       Refl. temp. [°C] Remarks
Measure point 1                     2.3         0.95              20.0         -
Measure point 2                     -1.5        0.95              20.0         -
Measure point 3                     2.7         0.95              20.0         -
Measure point 4                     -1.8        0.95              20.0         -
Measure point 5                     -4.4        0.95              20.0         -
Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
Thermal image displayed in " Iron " Palette.
The images are of the front of the house.
The images shows that there is a bedroom window open allowing heat out.
There are also two vent arrangements on the roof, the main vent at the top of the roof is the exhaust vent
from the Boiler and the second vent part way down the roof is from the soil stack.
There is a good uniform temperature profile across the exterior walls of the house and the spot temperature
markers highlight the difference in the thermal insulation properties of the various materials such as the brick
walls with cavity wall insulation, PVC Double glazed windows, PVC Double Glazed Door and the roof.




                                                  Page 18/20
Demonstration Thermography Report

File:                                                  Date:                                  Measuring Time:
IV_00053.BMT                                         20/10/2010                                      07:57:25




Picture parameters:
Emissivity:                      0.95
Refl. temp. [°C]:                20.0


Picture markings:
Measurement Objects             Temp. [°C]    Emiss.       Refl. temp. [°C] Remarks
Measure point 1                     1.5         0.95              20.0         -
Measure point 2                     -1.8        0.95              20.0         -
Measure point 3                     3.2         0.95              20.0         -
Remarks:
Demonstration Thermal Survey conducted at Detached Property.
The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera.
Images were taken of the exterior and the interior of the property to highlight any anomalies that could be
affecting the Thermal performance of the property.
The images are of the rear of the house.
The images shows the heat loss through the soffits just under the eaves/roof.
There is a good uniform temperature profile across the exterior walls of the house and the spot temperature
markers highlight the difference in the thermal insulation properties of the various materials such as the brick
walls with cavity wall insulation, PVC Double glazed windows and the roof.
Thermal image displayed in " Iron " Palette.

 Review:
Demonstration Thermography Report to highlight the capabilities of the Testo 882 series Thermal Imaging
camera and the Testo IR software.
This is an example report for Demonstration purposes only. The Report format is the "standard" template from
the selection of Report Templates available in the software.The images used in this report were taken with a
Testo 882 Thermal Imaging camera.
The Thermal images and this report are compiled to indicate the capability of the camera and the software and
its suitability for Thermally Surveying a wide range of applications, Industrial, Electrical, Building and many
more. The images are of a Detached property in the UK.
It should be noted that the Emissivity of individual materials / components were not taken into consideration for
the purpose of the Demonstration and therefore the indicated (Apparent),temperatures may not be truely
representative in this instance.

The purpose of the visit was to Demonstrate the Thermal Imaging camera, to show its capabilities and show
how it can be utilised for conducting Thermal Surveys of Buildings.The survey was not conducted in detail it
was for the purpose of the Demonstration of the equipment. The images taken are examples of some typical
anomalies that may be found when conducting a Thermal survey of a Domestic Dwelling.

The images taken were not of any specific areas or conditions/anomalies, the images taken/used were purely
                                                Page 19/20
Demonstration Thermography Report

The images taken were not of any specific areas or conditions/anomalies, the images taken/used were purely
for the Demonstration of the camera and the software.
The images taken were solely for the purpose of Demonstrating the Equipment and the software, not for
specific fault finding in this instance.
Testo do not provide Consultancy /Conclusions for any of the images taken during the course of the
Demonstration.
It is not the purpose of this report to specifically identify any faults found or comment on the images, it is to
highlight the capabilities of the camera / software and its use for various applications.

Some of the features of the camera and software have been applied to the images, such as:
Spot Temperature Markers have been added to the Thermal images to indicate temperatures.

Auto Hot / Cold Spot Indicator has been applied, which automatically highlights the Hottest or Coldest
temperature point in a defined area.

Temperature Profile Line Graph shows the temperature variation in graph form across the subject.

The images are automatically Time and Date stamped to verify the time and date when the image was taken.
The report also details the Emissivity Value relating to the image taken.




                                                            05/11/2010 ,

                                                                           Andy McGrath - Testo




                                                   Page 20/20

More Related Content

Viewers also liked

Thermography image comparison - testo 875 vs. competitors
Thermography image comparison - testo 875 vs. competitorsThermography image comparison - testo 875 vs. competitors
Thermography image comparison - testo 875 vs. competitorsTesto Limited
 
Testo - Refridgeration Engineering
Testo - Refridgeration EngineeringTesto - Refridgeration Engineering
Testo - Refridgeration EngineeringTesto Limited
 
Tg measurement solutions_energy_emission
Tg measurement solutions_energy_emissionTg measurement solutions_energy_emission
Tg measurement solutions_energy_emissionTesto Limited
 
Testo measurement solutions - Pharma
Testo measurement solutions - PharmaTesto measurement solutions - Pharma
Testo measurement solutions - PharmaTesto Limited
 
Testo 175 t3 datasheet
Testo 175 t3 datasheetTesto 175 t3 datasheet
Testo 175 t3 datasheetTesto Limited
 
Testo 176 t3-t4 datasheet
Testo 176 t3-t4 datasheetTesto 176 t3-t4 datasheet
Testo 176 t3-t4 datasheetTesto Limited
 
Testo - Food Safety in Restaurants
Testo - Food Safety in RestaurantsTesto - Food Safety in Restaurants
Testo - Food Safety in RestaurantsTesto Limited
 
How to setup your flue gas sensors
How to setup your flue gas sensorsHow to setup your flue gas sensors
How to setup your flue gas sensorsTesto Limited
 
Testo 176 p1 datasheet
Testo 176 p1 datasheetTesto 176 p1 datasheet
Testo 176 p1 datasheetTesto Limited
 
Testo - Measuring Instruments for Humidity
Testo - Measuring Instruments for HumidityTesto - Measuring Instruments for Humidity
Testo - Measuring Instruments for HumidityTesto Limited
 
Thermography image comparison - testo 875i vs. competitors
Thermography image comparison - testo 875i vs. competitorsThermography image comparison - testo 875i vs. competitors
Thermography image comparison - testo 875i vs. competitorsTesto Limited
 
Thermography image comparison - testo 885 vs. competitors
Thermography image comparison - testo 885 vs. competitorsThermography image comparison - testo 885 vs. competitors
Thermography image comparison - testo 885 vs. competitorsTesto Limited
 
Testo - Data loggers
Testo - Data loggersTesto - Data loggers
Testo - Data loggersTesto Limited
 
Testo - Measuring Instruments for RPM, Analysis, Current/Voltage
Testo - Measuring Instruments for RPM, Analysis, Current/VoltageTesto - Measuring Instruments for RPM, Analysis, Current/Voltage
Testo - Measuring Instruments for RPM, Analysis, Current/VoltageTesto Limited
 

Viewers also liked (16)

Thermography image comparison - testo 875 vs. competitors
Thermography image comparison - testo 875 vs. competitorsThermography image comparison - testo 875 vs. competitors
Thermography image comparison - testo 875 vs. competitors
 
Testo - Refridgeration Engineering
Testo - Refridgeration EngineeringTesto - Refridgeration Engineering
Testo - Refridgeration Engineering
 
Tg measurement solutions_energy_emission
Tg measurement solutions_energy_emissionTg measurement solutions_energy_emission
Tg measurement solutions_energy_emission
 
Testo measurement solutions - Pharma
Testo measurement solutions - PharmaTesto measurement solutions - Pharma
Testo measurement solutions - Pharma
 
Testo 175 t3 datasheet
Testo 175 t3 datasheetTesto 175 t3 datasheet
Testo 175 t3 datasheet
 
Testo - Thermator
Testo - ThermatorTesto - Thermator
Testo - Thermator
 
Testo 176 t3-t4 datasheet
Testo 176 t3-t4 datasheetTesto 176 t3-t4 datasheet
Testo 176 t3-t4 datasheet
 
Testo - Food Safety in Restaurants
Testo - Food Safety in RestaurantsTesto - Food Safety in Restaurants
Testo - Food Safety in Restaurants
 
Testo 720 datasheet
Testo 720 datasheetTesto 720 datasheet
Testo 720 datasheet
 
How to setup your flue gas sensors
How to setup your flue gas sensorsHow to setup your flue gas sensors
How to setup your flue gas sensors
 
Testo 176 p1 datasheet
Testo 176 p1 datasheetTesto 176 p1 datasheet
Testo 176 p1 datasheet
 
Testo - Measuring Instruments for Humidity
Testo - Measuring Instruments for HumidityTesto - Measuring Instruments for Humidity
Testo - Measuring Instruments for Humidity
 
Thermography image comparison - testo 875i vs. competitors
Thermography image comparison - testo 875i vs. competitorsThermography image comparison - testo 875i vs. competitors
Thermography image comparison - testo 875i vs. competitors
 
Thermography image comparison - testo 885 vs. competitors
Thermography image comparison - testo 885 vs. competitorsThermography image comparison - testo 885 vs. competitors
Thermography image comparison - testo 885 vs. competitors
 
Testo - Data loggers
Testo - Data loggersTesto - Data loggers
Testo - Data loggers
 
Testo - Measuring Instruments for RPM, Analysis, Current/Voltage
Testo - Measuring Instruments for RPM, Analysis, Current/VoltageTesto - Measuring Instruments for RPM, Analysis, Current/Voltage
Testo - Measuring Instruments for RPM, Analysis, Current/Voltage
 

Similar to Demonstration thermography report domestic dwelling general

Demo report 20 2 aa electrical
Demo report 20 2 aa  electricalDemo report 20 2 aa  electrical
Demo report 20 2 aa electricalTesto Limited
 
Demonstration thermography report photovoltaic panels
Demonstration thermography report photovoltaic panels Demonstration thermography report photovoltaic panels
Demonstration thermography report photovoltaic panels Testo Limited
 
Underfloor heating demo report
Underfloor heating demo reportUnderfloor heating demo report
Underfloor heating demo reportTesto Limited
 
Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1 Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1 Testo Limited
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Testo Limited
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Testo Limited
 
Testo thermal imaging power flushing application story
Testo thermal imaging power flushing application storyTesto thermal imaging power flushing application story
Testo thermal imaging power flushing application storyTesto Limited
 
With display and pushbuttons: compact infrared temperature sensors from ifm. ...
With display and pushbuttons: compact infrared temperature sensors from ifm. ...With display and pushbuttons: compact infrared temperature sensors from ifm. ...
With display and pushbuttons: compact infrared temperature sensors from ifm. ...ifm electronic gmbh
 
Heat simulator design Problem 1
Heat simulator design Problem 1Heat simulator design Problem 1
Heat simulator design Problem 1James Li
 
Testo 176 t1-t2 datasheet
Testo 176 t1-t2 datasheetTesto 176 t1-t2 datasheet
Testo 176 t1-t2 datasheetTesto Limited
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controllererdinc klima
 
Cyclic Heating Effect on Hardness of Aluminum
Cyclic Heating Effect on Hardness of AluminumCyclic Heating Effect on Hardness of Aluminum
Cyclic Heating Effect on Hardness of AluminumIJERA Editor
 
Testo 810 datasheet 2012
Testo 810 datasheet 2012Testo 810 datasheet 2012
Testo 810 datasheet 2012Testo Limited
 
Testo - Thermal Imaging - Industry
Testo - Thermal Imaging - IndustryTesto - Thermal Imaging - Industry
Testo - Thermal Imaging - IndustryTesto Limited
 
Testo 922 datasheet 2012
Testo 922 datasheet 2012Testo 922 datasheet 2012
Testo 922 datasheet 2012Testo Limited
 

Similar to Demonstration thermography report domestic dwelling general (15)

Demo report 20 2 aa electrical
Demo report 20 2 aa  electricalDemo report 20 2 aa  electrical
Demo report 20 2 aa electrical
 
Demonstration thermography report photovoltaic panels
Demonstration thermography report photovoltaic panels Demonstration thermography report photovoltaic panels
Demonstration thermography report photovoltaic panels
 
Underfloor heating demo report
Underfloor heating demo reportUnderfloor heating demo report
Underfloor heating demo report
 
Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1 Demonstration thermography report for super resolution 1
Demonstration thermography report for super resolution 1
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
 
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
Demonstration thermography report comparison between 320 x 240 versus 160 x 1...
 
Testo thermal imaging power flushing application story
Testo thermal imaging power flushing application storyTesto thermal imaging power flushing application story
Testo thermal imaging power flushing application story
 
With display and pushbuttons: compact infrared temperature sensors from ifm. ...
With display and pushbuttons: compact infrared temperature sensors from ifm. ...With display and pushbuttons: compact infrared temperature sensors from ifm. ...
With display and pushbuttons: compact infrared temperature sensors from ifm. ...
 
Heat simulator design Problem 1
Heat simulator design Problem 1Heat simulator design Problem 1
Heat simulator design Problem 1
 
Testo 176 t1-t2 datasheet
Testo 176 t1-t2 datasheetTesto 176 t1-t2 datasheet
Testo 176 t1-t2 datasheet
 
Fcc 01 free-coolin-controller
Fcc 01 free-coolin-controllerFcc 01 free-coolin-controller
Fcc 01 free-coolin-controller
 
Cyclic Heating Effect on Hardness of Aluminum
Cyclic Heating Effect on Hardness of AluminumCyclic Heating Effect on Hardness of Aluminum
Cyclic Heating Effect on Hardness of Aluminum
 
Testo 810 datasheet 2012
Testo 810 datasheet 2012Testo 810 datasheet 2012
Testo 810 datasheet 2012
 
Testo - Thermal Imaging - Industry
Testo - Thermal Imaging - IndustryTesto - Thermal Imaging - Industry
Testo - Thermal Imaging - Industry
 
Testo 922 datasheet 2012
Testo 922 datasheet 2012Testo 922 datasheet 2012
Testo 922 datasheet 2012
 

More from Testo Limited

Cloud based monitoring
Cloud based monitoringCloud based monitoring
Cloud based monitoringTesto Limited
 
Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014Testo Limited
 
Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014Testo Limited
 
Testo - PHPI - Feb 2014
Testo - PHPI - Feb 2014Testo - PHPI - Feb 2014
Testo - PHPI - Feb 2014Testo Limited
 
Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014Testo Limited
 
Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014Testo Limited
 
Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014Testo Limited
 
Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014Testo Limited
 
Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014Testo Limited
 
Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014Testo Limited
 
Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014Testo Limited
 
Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014Testo Limited
 
Testo (PWE) Jan 2014
Testo (PWE) Jan 2014Testo (PWE) Jan 2014
Testo (PWE) Jan 2014Testo Limited
 
Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014Testo Limited
 
Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014Testo Limited
 
Testo (mepca) Jan 2014
Testo (mepca) Jan 2014Testo (mepca) Jan 2014
Testo (mepca) Jan 2014Testo Limited
 
Testo (meat management) Jan 2014
Testo (meat management) Jan 2014Testo (meat management) Jan 2014
Testo (meat management) Jan 2014Testo Limited
 
Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014Testo Limited
 
Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014Testo Limited
 
Testo (installer) Jan 2014
Testo (installer) Jan 2014Testo (installer) Jan 2014
Testo (installer) Jan 2014Testo Limited
 

More from Testo Limited (20)

Cloud based monitoring
Cloud based monitoringCloud based monitoring
Cloud based monitoring
 
Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014Testo - STA guide - Feb 2014
Testo - STA guide - Feb 2014
 
Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014Testo - Plant and Works Engineering - Feb 2014
Testo - Plant and Works Engineering - Feb 2014
 
Testo - PHPI - Feb 2014
Testo - PHPI - Feb 2014Testo - PHPI - Feb 2014
Testo - PHPI - Feb 2014
 
Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014Testo - PHAM News - Feb 2014
Testo - PHAM News - Feb 2014
 
Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014Testo - Industrial Plant and Equipment - Feb 2014
Testo - Industrial Plant and Equipment - Feb 2014
 
Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014Testo - Heating Ventillation and Plumbing - Feb 2014
Testo - Heating Ventillation and Plumbing - Feb 2014
 
Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014Testo - Heating and Ventillation Review - Feb 2014
Testo - Heating and Ventillation Review - Feb 2014
 
Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014Testo - Food and Drink Network UK - Feb 2014
Testo - Food and Drink Network UK - Feb 2014
 
Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014Testo - Food and Drink International - Feb 2014
Testo - Food and Drink International - Feb 2014
 
Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014Testo - Environment and Energy Management - Feb 2014
Testo - Environment and Energy Management - Feb 2014
 
Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014Testo - Registered Gas Engineer - Feb 2014
Testo - Registered Gas Engineer - Feb 2014
 
Testo (PWE) Jan 2014
Testo (PWE) Jan 2014Testo (PWE) Jan 2014
Testo (PWE) Jan 2014
 
Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014Testo (plumbing and heating NI) Jan 2014
Testo (plumbing and heating NI) Jan 2014
 
Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014Testo (PHAM news) Jan 2014
Testo (PHAM news) Jan 2014
 
Testo (mepca) Jan 2014
Testo (mepca) Jan 2014Testo (mepca) Jan 2014
Testo (mepca) Jan 2014
 
Testo (meat management) Jan 2014
Testo (meat management) Jan 2014Testo (meat management) Jan 2014
Testo (meat management) Jan 2014
 
Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014Testo (laboratory news) Jan 2014
Testo (laboratory news) Jan 2014
 
Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014Testo (Connecting Industry instrumentation) Jan 2014
Testo (Connecting Industry instrumentation) Jan 2014
 
Testo (installer) Jan 2014
Testo (installer) Jan 2014Testo (installer) Jan 2014
Testo (installer) Jan 2014
 

Recently uploaded

Vip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts ServiceVip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts Serviceankitnayak356677
 
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | DelhiFULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | DelhiMalviyaNagarCallGirl
 
Marketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet CreationsMarketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet Creationsnakalysalcedo61
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation SlidesKeppelCorporation
 
rishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfrishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfmuskan1121w
 
Pitch Deck Teardown: NOQX's $200k Pre-seed deck
Pitch Deck Teardown: NOQX's $200k Pre-seed deckPitch Deck Teardown: NOQX's $200k Pre-seed deck
Pitch Deck Teardown: NOQX's $200k Pre-seed deckHajeJanKamps
 
Islamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in IslamabadIslamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in IslamabadAyesha Khan
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewasmakika9823
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessAggregage
 
Call Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any TimeCall Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any Timedelhimodelshub1
 
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfCatalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfOrient Homes
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...lizamodels9
 
Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...
Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...
Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...lizamodels9
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.Aaiza Hassan
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...lizamodels9
 
A.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry BelcherA.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry BelcherPerry Belcher
 
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCRsoniya singh
 
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… AbridgedLean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… AbridgedKaiNexus
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Roomdivyansh0kumar0
 

Recently uploaded (20)

Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCREnjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
Enjoy ➥8448380779▻ Call Girls In Sector 18 Noida Escorts Delhi NCR
 
Vip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts ServiceVip Female Escorts Noida 9711199171 Greater Noida Escorts Service
Vip Female Escorts Noida 9711199171 Greater Noida Escorts Service
 
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | DelhiFULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
FULL ENJOY - 9953040155 Call Girls in Chhatarpur | Delhi
 
Marketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet CreationsMarketing Management Business Plan_My Sweet Creations
Marketing Management Business Plan_My Sweet Creations
 
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
Keppel Ltd. 1Q 2024 Business Update  Presentation SlidesKeppel Ltd. 1Q 2024 Business Update  Presentation Slides
Keppel Ltd. 1Q 2024 Business Update Presentation Slides
 
rishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdfrishikeshgirls.in- Rishikesh call girl.pdf
rishikeshgirls.in- Rishikesh call girl.pdf
 
Pitch Deck Teardown: NOQX's $200k Pre-seed deck
Pitch Deck Teardown: NOQX's $200k Pre-seed deckPitch Deck Teardown: NOQX's $200k Pre-seed deck
Pitch Deck Teardown: NOQX's $200k Pre-seed deck
 
Islamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in IslamabadIslamabad Escorts | Call 03274100048 | Escort Service in Islamabad
Islamabad Escorts | Call 03274100048 | Escort Service in Islamabad
 
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service DewasVip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
Vip Dewas Call Girls #9907093804 Contact Number Escorts Service Dewas
 
Sales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for SuccessSales & Marketing Alignment: How to Synergize for Success
Sales & Marketing Alignment: How to Synergize for Success
 
Call Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any TimeCall Girls Miyapur 7001305949 all area service COD available Any Time
Call Girls Miyapur 7001305949 all area service COD available Any Time
 
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdfCatalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
Catalogue ONG NƯỚC uPVC - HDPE DE NHAT.pdf
 
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
Call Girls In Sikandarpur Gurgaon ❤️8860477959_Russian 100% Genuine Escorts I...
 
Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...
Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...
Call Girls In Kishangarh Delhi ❤️8860477959 Good Looking Escorts In 24/7 Delh...
 
M.C Lodges -- Guest House in Jhang.
M.C Lodges --  Guest House in Jhang.M.C Lodges --  Guest House in Jhang.
M.C Lodges -- Guest House in Jhang.
 
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
Call Girls In Radisson Blu Hotel New Delhi Paschim Vihar ❤️8860477959 Escorts...
 
A.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry BelcherA.I. Bot Summit 3 Opening Keynote - Perry Belcher
A.I. Bot Summit 3 Opening Keynote - Perry Belcher
 
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
(8264348440) 🔝 Call Girls In Keshav Puram 🔝 Delhi NCR
 
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… AbridgedLean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
Lean: From Theory to Practice — One City’s (and Library’s) Lean Story… Abridged
 
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130  Available With RoomVIP Kolkata Call Girl Howrah 👉 8250192130  Available With Room
VIP Kolkata Call Girl Howrah 👉 8250192130 Available With Room
 

Demonstration thermography report domestic dwelling general

  • 1. Demonstration Thermography Report Company Testo Ltd Tester: Newman Lane Andy McGrath - Testo Alton, Hampshire, GU34 2QJ Phone: 01420 544433 E-Mail: info @testo.co.uk Device Testo 882 Serial No.: 01790945 Lens: Std 32 degree Wide Angle Lens Customer Demonstration Thermography Measuring Site: Report Demonstration Thermography Report Detached Property Thermal Survey of Detached Property UK Measuring Date: 4th October 2010 Task Demonstration Thermography Report to highlight the capabilities of the Testo 882 series Thermal Imaging cameras and IR software . Page 1/20
  • 2. Demonstration Thermography Report File: Date: Measuring Time: IV_00039.BMT 20/10/2010 07:48:01 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. These images provide an overall exterior view of the property. These images are for the purpose of identification of the property for the first page of the Thermography Report. Thermal image displayed in " Iron " Palette. Page 2/20
  • 3. Demonstration Thermography Report File: Date: Measuring Time: IV_00001.BMT 20/10/2010 07:20:38 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 20.1 0.95 20.0 - Measure point 2 17.8 0.95 20.0 - Measure point 3 20.3 0.95 20.0 - Cold spot 1 7.5 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. Images of the interior of the Front Door, which is a Double Glazed PVC Door. The thermal image highlights the ingress of cold air through the seals of the door, where the door should be sealed to the frame. It highlights that cold air is passing through both the left hand and right hand lower sections of the door. A Temperature Profile Line Graph has been added to the image to highlight the temperature variation beteen the walls, door and the area where the seals are leaking. Cold air ingress can also be seen tthrough the letter box. Spot temperature markers have been added to show the temperature variation. The Auto Cold Spot Indicator has been applied and is indicating (CS1), that at the coldest point, the Apparent Temperature is approx 7 degrees C colder in comparison to the wall temperatures of approx 19/20 degrees C. Thermal image displayed in " Iron " Palette Page 3/20
  • 4. Demonstration Thermography Report File: Date: Measuring Time: IV_00002.BMT 20/10/2010 07:21:09 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 19.7 0.95 20.0 - Measure point 2 17.5 0.95 20.0 - Measure point 3 14.6 0.95 20.0 - Measure point 4 19.6 0.95 20.0 - Cold spot 1 7.2 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. Images of the interior of the Front Door, which is a Double Glazed PVC Door. The thermal image highlights the ingress of cold air through the seals of the door, where the door should be sealed to the frame. It highlights that cold air is passing through both the left hand and right hand lower sections of the door. A Temperature Profile Line Graph has been added to the image to highlight the temperature variation beteen the walls, door and the area where the seals are leaking. Cold air ingress can also be seen tthrough the letter box. Spot temperature markers have been added to show the temperature variation. The Auto Cold Spot Indicator has been applied and is indicating (CS1), that at the coldest point, the Apparent Temperature is approx 7 degrees C colder in comparison to the wall temperatures of approx 19/20 degrees C. Thermal image displayed in " Iron " Palette Page 4/20
  • 5. Demonstration Thermography Report File: Date: Measuring Time: IV_00004.BMT 20/10/2010 07:23:41 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 20.0 0.95 20.0 - Measure point 2 19.0 0.95 20.0 - Measure point 3 19.1 0.95 20.0 - Measure point 4 20.2 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. The images are of the Fireplace / Chimney Breast in the Lounge and the adjacent wall which is an exterior wall. The house has cavity wall insulation but this is not applied in the chimney breast area and therefore Cold air ingress can be seen in the area around the fireplace in comparison to the areas of the wall where there are cavity walls and insulation has been applied. A Temperature Profile Line Graph has been added to the image to highlight the temperature variation between the walls and the area around the fireplace. Spot temperature markers have been added to show the temperature variation. Thermal image displayed in " Iron " Palette Page 5/20
  • 6. Demonstration Thermography Report File: Date: Measuring Time: IV_00007.BMT 20/10/2010 07:25:06 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 16.6 0.95 20.0 - Measure point 2 20.3 0.95 20.0 - Measure point 3 21.1 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. Thermal image displayed in " Iron " Palette Images of Lounge Window and external wall showing temperature variation between Double Glazed window, Cavity Insulated external wall and internal wall. Thermal image displayed in " Iron " Palette. Page 6/20
  • 7. Demonstration Thermography Report File: Date: Measuring Time: IV_00012.BMT 20/10/2010 07:28:40 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. Images show Cold Air ingress around the base of a kitchen cupboard. It was found that the Soil Stack/Down Pipe from the upstairs bathroom ran behind this cupboard into the ground and cold air was entering the property in this area and escaping out under the cupboards plinth. Thermal image displayed in " Iron " Palette. Page 7/20
  • 8. Demonstration Thermography Report File: Date: Measuring Time: IV_00014.BMT 20/10/2010 07:30:20 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 19.9 0.95 20.0 - Measure point 2 17.1 0.95 20.0 - Measure point 3 19.3 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. Thermal image displayed in " Iron " Palette. Page 8/20
  • 9. Demonstration Thermography Report File: Date: Measuring Time: IV_00019.BMT 20/10/2010 07:32:29 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 21.3 0.95 20.0 - Measure point 2 17.1 0.95 20.0 - Measure point 3 20.7 0.95 20.0 - Cold spot 1 16.5 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. The images are of the En-suite bathroom ceiling and highlight cold patches in the ceiling, around the Downlight and Extractor Fan Vent. Further investigation (refer to images 83, 85, 86 & 87), showed that the loft insulation had been removed from these ceiling areas when the bathroom was altered and the downlights and extract fan vent were fitted. This highlights the difference in areas where the loft insulation is fitted and where it is now missing, thus allowing cold ingress into the bathroom. With the Spot temperature markers and the Auto Cold Spot Indicator, a temperature differential of approx 4/5 degrees can be seen across the ceiling. Thermal image displayed in " Iron " Palette. Page 9/20
  • 10. Demonstration Thermography Report File: Date: Measuring Time: IV_00023.BMT 20/10/2010 07:34:36 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 20.3 0.95 20.0 - Measure point 2 20.4 0.95 20.0 - Measure point 3 15.5 0.95 20.0 - Cold spot 1 14.7 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. The images are of the bedroom ceiling and highlight a large cold patch in the corner of the ceiling. Further investigation showed that loft insulation had not been fitted in this area of the loft as it was under some boarding, refer to images 83, 85, 86 & 87.This highlights the difference in areas where the loft insulation is fitted and where it is missing, thus allowing cold ingress into the bedroom. With the Spot temperature markers and the Auto Cold Spot Indicator, a temperature differential of approx 4/5 degrees can be seen across this section of the ceiling. Thermal image displayed in " Iron " Palette Page 10/20
  • 11. Demonstration Thermography Report File: Date: Measuring Time: IV_00028.BMT 20/10/2010 07:37:55 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 21.0 0.95 20.0 - Measure point 2 21.1 0.95 20.0 - Measure point 3 18.2 0.95 20.0 - Measure point 4 17.2 0.95 20.0 - Cold spot 1 16.5 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. The images are of the landing ceiling area and highlight a number of large cold patches across the ceiling. Further investigation showed that loft insulation had not been fitted in this area of the loft as it was under some boarding.This highlights the difference in areas where the loft insulation is fitted and where it is missing, thus allowing cold ingress into the bedroom. With the Spot temperature markers and the Auto Cold Spot Indicator, a temperature differential of approx 4/5 degrees can be seen across this section of the ceiling. Thermal image displayed in " Iron " Palette. Page 11/20
  • 12. Demonstration Thermography Report File: Date: Measuring Time: IV_00083.BMT 20/10/2010 19:26:46 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 12.7 0.95 20.0 - Measure point 2 9.7 0.95 20.0 - Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and En-suite Bathroom ceilings, this image is of the loft area and shows/verifies the missing loft insulation which was the cause of the cold areas and was highlighted in the previous images. This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring from those rooms can be seen in the areas where there is no loft insulation. These images confirm the thermal benefit of loft insulation. Thermal image displayed in " Iron " Palette Page 12/20
  • 13. Demonstration Thermography Report File: Date: Measuring Time: IV_00085.BMT 20/10/2010 19:27:32 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and bathroom ceilings, this image is of the loft area and shows/verifies the missing loft insulation which was the cause of the cold areas and was highlighted in the previous images. This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring from those rooms can be seen in the areas where there is no loft insulation. These images confirm the thermal benefit of loft insulation. Thermal image displayed in "Blue / Red " Palette Page 13/20
  • 14. Demonstration Thermography Report File: Date: Measuring Time: IV_00086.BMT 20/10/2010 19:28:09 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and bathroom ceilings, this image is of the loft area and shows/verifies the missing loft insulation which was the cause of the cold areas and was highlighted in the previous images. This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring from those rooms can be seen in the areas where there is no loft insulation. These images confirm the thermal benefit of loft insulation. Thermal image displayed in " Iron " Palette Page 14/20
  • 15. Demonstration Thermography Report File: Date: Measuring Time: IV_00087.BMT 20/10/2010 19:28:20 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. With reference to the images 19 and 23 which highlighted cold areas on the Bedroom and bathroom ceilings, this image is of the loft area and shows/verifies the missing loft insulation which was the cause of the cold areas and was highlighted in the previous images. This image is the reverse of the images taken in the bedroom and bathroom and here the heat transferring from those rooms can be seen in the areas where there is no loft insulation. These images confirm the thermal benefit of loft insulation. Thermal image displayed in "Blue / Red " Palette Page 15/20
  • 16. Demonstration Thermography Report File: Date: Measuring Time: IV_00025.BMT 20/10/2010 07:36:22 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 21.2 0.95 20.0 - Measure point 2 17.9 0.95 20.0 - Measure point 3 20.9 0.95 20.0 - Cold spot 1 12.9 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. The images are of the loft hatch which has a sealing arrangement but the Thermal image shows how there is still some cold air ingress past the seals. With the Spot temperature markers and the Auto Cold Spot Indicator, a significant temperature differential can be seen across the loft hatch seals. Thermal image displayed in " Iron " Palette Page 16/20
  • 17. Demonstration Thermography Report File: Date: Measuring Time: IV_00030.BMT 20/10/2010 07:38:37 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 18.9 0.95 20.0 - Measure point 2 20.8 0.95 20.0 - Measure point 3 21.8 0.95 20.0 - Profile line: Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. The images are of the bathroom exterior and internal walls. The thermal image highlights the temperature variation between the walls. The external wall has cavity wall insulation installed although there is a large cold area (M1) where there is more cold air ingress compared to the majority of the wall. Further investigation would be required to verify the existance of cavity wall insulation in this area. Thermal image displayed in " Iron " Palette. Page 17/20
  • 18. Demonstration Thermography Report File: Date: Measuring Time: IV_00040.BMT 20/10/2010 07:48:15 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 2.3 0.95 20.0 - Measure point 2 -1.5 0.95 20.0 - Measure point 3 2.7 0.95 20.0 - Measure point 4 -1.8 0.95 20.0 - Measure point 5 -4.4 0.95 20.0 - Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. Thermal image displayed in " Iron " Palette. The images are of the front of the house. The images shows that there is a bedroom window open allowing heat out. There are also two vent arrangements on the roof, the main vent at the top of the roof is the exhaust vent from the Boiler and the second vent part way down the roof is from the soil stack. There is a good uniform temperature profile across the exterior walls of the house and the spot temperature markers highlight the difference in the thermal insulation properties of the various materials such as the brick walls with cavity wall insulation, PVC Double glazed windows, PVC Double Glazed Door and the roof. Page 18/20
  • 19. Demonstration Thermography Report File: Date: Measuring Time: IV_00053.BMT 20/10/2010 07:57:25 Picture parameters: Emissivity: 0.95 Refl. temp. [°C]: 20.0 Picture markings: Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks Measure point 1 1.5 0.95 20.0 - Measure point 2 -1.8 0.95 20.0 - Measure point 3 3.2 0.95 20.0 - Remarks: Demonstration Thermal Survey conducted at Detached Property. The survey was conducted as part of a Demonstration of the Testo 882 series Thermal Imaging camera. Images were taken of the exterior and the interior of the property to highlight any anomalies that could be affecting the Thermal performance of the property. The images are of the rear of the house. The images shows the heat loss through the soffits just under the eaves/roof. There is a good uniform temperature profile across the exterior walls of the house and the spot temperature markers highlight the difference in the thermal insulation properties of the various materials such as the brick walls with cavity wall insulation, PVC Double glazed windows and the roof. Thermal image displayed in " Iron " Palette. Review: Demonstration Thermography Report to highlight the capabilities of the Testo 882 series Thermal Imaging camera and the Testo IR software. This is an example report for Demonstration purposes only. The Report format is the "standard" template from the selection of Report Templates available in the software.The images used in this report were taken with a Testo 882 Thermal Imaging camera. The Thermal images and this report are compiled to indicate the capability of the camera and the software and its suitability for Thermally Surveying a wide range of applications, Industrial, Electrical, Building and many more. The images are of a Detached property in the UK. It should be noted that the Emissivity of individual materials / components were not taken into consideration for the purpose of the Demonstration and therefore the indicated (Apparent),temperatures may not be truely representative in this instance. The purpose of the visit was to Demonstrate the Thermal Imaging camera, to show its capabilities and show how it can be utilised for conducting Thermal Surveys of Buildings.The survey was not conducted in detail it was for the purpose of the Demonstration of the equipment. The images taken are examples of some typical anomalies that may be found when conducting a Thermal survey of a Domestic Dwelling. The images taken were not of any specific areas or conditions/anomalies, the images taken/used were purely Page 19/20
  • 20. Demonstration Thermography Report The images taken were not of any specific areas or conditions/anomalies, the images taken/used were purely for the Demonstration of the camera and the software. The images taken were solely for the purpose of Demonstrating the Equipment and the software, not for specific fault finding in this instance. Testo do not provide Consultancy /Conclusions for any of the images taken during the course of the Demonstration. It is not the purpose of this report to specifically identify any faults found or comment on the images, it is to highlight the capabilities of the camera / software and its use for various applications. Some of the features of the camera and software have been applied to the images, such as: Spot Temperature Markers have been added to the Thermal images to indicate temperatures. Auto Hot / Cold Spot Indicator has been applied, which automatically highlights the Hottest or Coldest temperature point in a defined area. Temperature Profile Line Graph shows the temperature variation in graph form across the subject. The images are automatically Time and Date stamped to verify the time and date when the image was taken. The report also details the Emissivity Value relating to the image taken. 05/11/2010 , Andy McGrath - Testo Page 20/20