1. Demonstration Thermography report
Company Testo Ltd Tester:
Newman Lane Andy McGrath
Alton, Hampshire, GU34 2QJ Phone: 01420 544433
E-Mail: amcgrath@testo.co.uk
Device Testo 875 series Serial No.: 1434423
Lens: 32 degree wide angle lens
Customer Demonstration Thermography Measuring Site:
Report
Thermal Surveys
Various Sites
Various Electrical Installations
UK /Applications for Demonstration
Purposes
Thermal Images with Testo 875 series
Thermal Imaging Cameras
Measuring Date: Various Measuring
Dates
Task Demonstration Thermography Report, to demonstrate the Capabilities of
the Testo Thermal Imaging cameras and the Testo IR software.
Demonstration Thermography Report of various Electrical Installations /
Applications.
Page 1/18
2. Demonstration Thermography report
File: Date: Measuring Time:
IV_00041.BMT 17/06/2008 15:23:23
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 96.8 0.95 20.0 -
Measure point 2 110.0 0.95 20.0 -
Measure point 3 109.3 0.95 20.0 -
Measure point 4 112.0 0.95 20.0 -
Measure point 5 112.2 0.95 20.0 -
Measure point 6 91.7 0.95 20.0 -
Measure point 7 95.7 0.95 20.0 -
Measure point 8 97.6 0.95 20.0 -
Remarks:
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera. Images of Electrical
equipment for Demonstration purposes to show the capabilities of the Testo 875 and the Testo IR software.
Image of Electrical connections. As can be seen from the spot temperature markers on the thermal image,
these connections are showing High temperatures and require further investigation.
Page 2/18
3. Demonstration Thermography report
File: Date: Measuring Time:
IV_00393.BMT 12/08/2010 13:45:48
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 38.3 0.95 20.0 -
Hot spot 1 49.5 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Blue / Red " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 3/18
4. Demonstration Thermography report
File: Date: Measuring Time:
IV_00218.BMT 28/10/2009 14:38:29
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 45.7 0.95 20.0 -
Hot spot 1 142.7 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Iron " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 4/18
5. Demonstration Thermography report
File: Date: Measuring Time:
IV_00223.BMT 28/10/2009 14:44:52
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 33.0 0.95 20.0 -
Measure point 2 45.2 0.95 20.0 -
Measure point 3 52.3 0.95 20.0 -
Hot spot 1 51.6 0.95 20.0 -
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Blue / Red " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 5/18
6. Demonstration Thermography report
File: Date: Measuring Time:
IV_00275.BMT 14/05/2010 11:16:42
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 33.4 0.95 20.0 -
Measure point 2 33.6 0.95 20.0 -
Hot spot 1 53.5 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Iron " Palette.
The Auto Hot Spot Indicator HS1, indicates the Apparent temperature of one of the supply cables.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 6/18
7. Demonstration Thermography report
File: Date: Measuring Time:
IV_00267.BMT 14/05/2010 11:09:59
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Hot spot 1 50.0 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Iron " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 7/18
8. Demonstration Thermography report
File: Date: Measuring Time:
IV_00268.BMT 14/05/2010 11:10:16
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 50.1 0.95 20.0 -
Hot spot 1 60.3 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Blue / Red " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 8/18
9. Demonstration Thermography report
File: Date: Measuring Time:
IV_00271.BMT 14/05/2010 11:11:37
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 68.9 0.95 20.0 -
Measure point 2 71.1 0.95 20.0 -
Hot spot 1 71.9 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Hot / Cold " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 9/18
10. Demonstration Thermography report
File: Date: Measuring Time:
IV_00272.BMT 14/05/2010 11:12:06
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 44.2 0.95 20.0 -
Measure point 2 44.0 0.95 20.0 -
Hot spot 1 44.8 0.95 20.0 -
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Iron " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 10/18
11. Demonstration Thermography report
File: Date: Measuring Time:
IV_00355.BMT 03/12/2008 10:12:57
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 46.8 0.95 20.0 Spot Temp 1 on Grey Phase of
Isolator
Measure point 2 42.0 0.95 20.0 Spot Temp 2 on Black Phase
cable
Measure point 3 39.3 0.95 20.0 Spot Temp 3 on Red Phase
cable
Measure point 4 28.8 0.95 20.0 Spot Temp 4 on Blue Phase
cable
Profile line:
Remarks:
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera. Images of Electrical
equipment for Demonstration purposes to show the capabilities of the Testo 875 and the Testo IR software.
Isolator Switch
Thermal image indicates the spot temperatures of the Phase connections.
A temperature profile line graph has been applied horizontally across the cables to highlight the temperature
variation.
As can be seen, the Grey phase is considerably hotter in comparison to the other phases.
It is therefore recommended that an inspection of these connections is conducted.
Page 11/18
12. Demonstration Thermography report
File: Date: Measuring Time:
IV_00273.BMT 14/05/2010 11:14:58
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 35.1 0.95 20.0 -
Hot spot 1 62.6 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.The thermal image
highlights the apparent temperature of a cable enclosed in the conduit.
The Thermal image is displayed in " Iron " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. Temperature profiles graphs applied to show temperature variation across components.
Page 12/18
13. Demonstration Thermography report
File: Date: Measuring Time:
IV_00423.BMT 11/12/2008 15:36:20
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 83.3 0.95 20.0 Spot Temp 1 Red Phase
Measure point 2 65.4 0.95 20.0 -
Measure point 3 70.5 0.95 20.0 -
Hot spot 1 90.7 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermography Survey.
Thermal Survey of Main Electrical Supply Cabinet, using the Testo 875 series Thermal Imaging camera.
Thermal and Digital image of all the Supply Panel. This is achieved in the confined space due to the Testo
875 camera being equipped as standard with a 32 degree, Wide Angle Lens.
3 Spot Temp markers have been added along with the Auto Hot Spot Indicator HS1, to indicate temperatures
along with a Temperature Profile Line Graph.
Page 13/18
14. Demonstration Thermography report
File: Date: Measuring Time:
IV_00356.BMT 03/12/2008 10:13:47
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 37.5 0.95 20.0 Red Phase cable
Measure point 2 41.1 0.95 20.0 Black Phase cable
Measure point 3 41.0 0.95 20.0 Grey Phase cable
Measure point 4 28.5 0.95 20.0 Blue Phase cable
Hot spot 1 42.3 0.95 20.0 -
Profile line:
Remarks:
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera. Images of Electrical
equipment for Demonstration purposes to show the capabilities of the Testo 875 and the Testo IR software.
Isolator Switch
Thermal image indicates the spot temperatures of the Phase connection cables higher up in the control panel
above the Isolator switch.
A temperature profile line graph has been applied horizontally across the cables to highlight the temperature
variation.
Page 14/18
15. Demonstration Thermography report
File: Date: Measuring Time:
IV_00040.BMT 16/02/2010 11:31:05
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Hot spot 1 91.1 0.95 20.0 -
Profile line:
Remarks:
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera during a Demonstration of
the camera.
The images taken have been used to compile an example report to demonstrate the capabilities of the Testo
Thermal Imaging camera and the Testo IR software.
The image is of a Conveyor Motor which is part of the Sheeting Production Line.
The Auto Hot Spot indicator (HS1) has been applied to the thermal image to automatically indicate the
hottest point in the defined area.
As can be seen, the Hottest point on the motor is approx 93 deg C.
This should be compared to the Manufacturers Operating Temperature range and monitored in the future. In
comparison to other Motors on this Conveyor system, this motor is running at a considerably hotter
temperature. Additional Spot temperature markers have been added to other sections of the motor for
comparison purposes. A Temperature Profile Line graph has been applied to give further visual
representation of the temperature profile across the motor.
The thermal image is displayed in " Iron " Palette.
Page 15/18
16. Demonstration Thermography report
File: Date: Measuring Time:
IV_00204.BMT 13/10/2008 16:14:05
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 71.6 0.95 20.0 SpotTemp 1 on Pump Body 1
Measure point 2 53.3 0.95 20.0 Spot Temp 2 on Flange
connector
Measure point 3 53.9 0.95 20.0 Spot Temp 3 on Flange
connector
Measure point 4 60.1 0.95 20.0 Spot Temp 4 on Pump Body 2
Hot spot 1 72.7 0.95 20.0 -
Profile line:
Remarks:
Demonstration Thermal Images of Electrical Installations.
Thermal and Digital images taken with Testo 875 series Thermal Imaging camera.
The Thermal image is displayed in " Iron " Palette.
Some features of the Testo IR software have been applied to the image to highlight / indicate comparative
Temperatures. The Auto Hot Spot Indicator HS1 is applied to automatically indicate the hottest point in the
defined area. A Temperature profile graph applied, to show temperature variation across components.An
Isotherm has been applied to highlight by colour, the area of the component that is within a defined
temperature range.
Page 16/18
17. Demonstration Thermography report
File: Date: Measuring Time:
IV_00702.BMT 14/04/2009 11:44:38
Picture parameters:
Emissivity: 0.95
Refl. temp. [°C]: 20.0
Picture markings:
Measurement Objects Temp. [°C] Emiss. Refl. temp. [°C] Remarks
Measure point 1 39.9 0.95 20.0 Spot Temp 1 for comparison
purposes.
Measure point 2 38.4 0.95 20.0 Spot Temp 2 for comparison
purposes.
Measure point 3 46.4 0.95 20.0 Spot Temp 3 for comparison
purposes.
Measure point 4 40.9 0.95 20.0 Spot Temp 4 for comparison
purposes.
Hot spot 1 49.1 0.95 20.0 Auto Hot Spot Indicates Hottest
point in defined area
Profile line:
Remarks:
Thermal and Digital Images taken with Testo 875 series Thermal Imaging camera as part of Demonstration
of camera.
Images taken to demonstrate the capabilities of the Testo 875 and the Testo IR software.
Images are of a Control Motor in a Production Line.
The Auto Hot spot indicator has been applied to the thermal image to indicate the Hottest point in the defined
area.
Additional Spot Temperature markers have been added to provide temperature comparisons on other parts
of the component.
A Temperature profile line graph has been applied to show the temperature profile across the component.
Page 17/18
18. Demonstration Thermography report
Review:
Demonstration Report utilising the Testo range of Thermal Imaging cameras and Testo IR software.
The objective of this Demonstration Thermography report is to demonstrate the report producing capabilities of
the software and the Quality of the Thermal images captured with Testo Thermal Imaging cameras.
The report is for demonstration purposes only.
The images are not to highlight any specific anomalies in Electrical Installations. The images were taken
during Demonstration visits and reproduced to demonstrate the capabilities of the cameras and software.
This is an example of the "Standard" report template from the software, using images from Testo Thermal
Imaging cameras, compiled into a Report using the Testo IR software.
The Thermal and Digital images are of various Electrical Installations / Applications.
The Thermal images indicate the "Apparent" temperatures on the equipment.
As the images are for Demonstration purposes, no account has been made in respect of Emissivity values for
Materials or Reflected Temperature, therefore the indicated temperatures are "Apparent" Temperatures.
Some of the features of the camera and the software have been applied to the thermal images.
Spot Temperature Markers have been added to the thermal image to indicate temperatures and to highlight
the temperature variation.
Auto Hot Spot Indicator has been applied which automatically highlights the hottest point in the defined area.
Temperature Profile Line Graph, shows the temperature variation in graph form across the electrical
components.
The thermal images can been presented in various palettes such as " Iron " and " Blue / Red", from the
selection of palettes available in the camera and the software.
The Thermal/Digital images are time and date stamped to verify the time and date when the images were
taken.
The report also stipulates the emissivity value relating to the thermal image.
27/07/2010 ,
Andy McGrath